2. SYSTEM
CLASSIFICATIONS
Room air distribution systems can be classified according to their primary objective and the method used
to accomplish that objective. The objective of any air distribution system is to condition and/or
ventilate the space for its occupants, to support
processes within the space, or both.
Methods used to condition spaces can be classified as
-
Fully mixed systems intend to produce uniform
temperature and pollutant concentration with little or no stratification within the occupied
and/or process space. Overhead air distribution, with both supply and return/exhaust above
occupants or processes, is an example of this type of system.
-
Fully stratified systems intend little mixing of
air within the occupied and/or process space. Displacement ventilation, where the room air
moves in a plug- or piston-type motion, is an example of this type of system.
-
Partially mixed systems provide some mixing of air
in the occupied and/or process space while creating stratified conditions in the volume
above. Most underfloor air distribution designs (UFAD) are examples of this type of system.
-
Task/ambient air distribution focuses on
conditioning only a portion of the space for thermal comfort and/or process control.
Examples of task/ambient systems are personally controlled desk outlets and
spot-conditioning systems. Because task/ambient distribution requires a high level of
individual control, it is not covered in this chapter, but is discussed in Chapter 20 of the
2021 ASHRAE Handbook—Fundamentals. Additional
design
guidance is also provided in Bauman (2003).
Figure 2 illustrates
the spectrum between the two extremes (fully mixed and fully stratified) of room air distribution
strategies.
Review the following publications when selecting systems and equipment for room air distribution:
-
ANSI/ASHRAE Standard 55 establishes indoor thermal environmental
and personal factors for the occupied space.
-
ANSI/ASHRAE Standards 62.1 and 62.2 specify ventilation
requirements for acceptable indoor air quality. These standards are adopted as part of many
building codes.
-
ANSI/ASHRAE/IES Standards 90.1 and 90.2 provide minimum energy
efficiency requirements that affect supply air characteristics in various types of buildings
in low-rise and non-low-rise buildings.
Local codes should also be checked for applicability to each of these subjects.
Other useful references on selecting air distribution equipment include AMCA Standard 222, Chapter 20
of the 2021 ASHRAE
Handbook—Fundamentals, Chapter 58 of the 2023 ASHRAE
Handbook—HVAC Applications, ASHRAE’s (2013) UFAD
Guide:
Design, Construction and Operation of Underfloor Air Distribution Systems, Chen and Glicksman
(2003), Rock and Zhu (2002), Skistad (2002), and ASHRAE/REHVA’s Active and
Passive Beam Application Design Guide (Woollett and Rimmer 2014).
In fully mixed systems, supply air outlets, properly sized and located, establish then
control the air pattern in a room to obtain proper air mixing and temperature equalization.
Supply airflow from an outlet (primary air) entrains room
air into the outlet’s jet or jets. This entrained air (secondary
air) increases the combined air (total
air) in the jet as it proceeds farther from the outlet. The momentum of the
primary jet remains constant, so the jet’s velocity decreases as the mass increases. As the
two air masses mix, the temperature of the jet from a properly selected, installed, and operated
outlet approaches the room air temperature (Rock and Zhu 2002). Outlets should be sized to project
air so that its velocity and temperature reach acceptable levels before entering the occupied zone
of a space, often defined as the lowest 1.8 m of a room. Throw is the distance from the origin of the jet to the
point where the velocity of the total air is reduced to a desired value.
Outlet locations and patterns also affect a jet’s throw, entrainment, and temperature
equalization capabilities. Some general characteristics include the following:
-
When outlets are located close to a surface such as a ceiling, entrainment may be
restricted, which can result in a longer throw.
-
When the air pattern is spread horizontally in multiple directions, throw is reduced.
-
Outlets with horizontally radial airflow patterns (e.g., from a round diffuser) typically
have shorter throws than outlets with directional patterns.
-
An outlet cannot discharge air properly and uniformly unless the air enters it in a
straight and uniform manner.
Ceiling or sidewall outlets in cooling applications are often selected with supply air temperatures
at or above 11°C. Special high-induction outlets are available for use with
low-temperature air distribution systems (i.e., those with supply air temperature below
11°C). These outlets include special features and rapidly mix cold supply air with
room air at the outlet and effectively reduce the temperature differential between the supply and
room air. For further information, designers can consult ASHRAE’s (1996) Cold Air Distribution System Design Guide.
Accessories used with an outlet can regulate the volumetric flowrate of supply air and control its
flow pattern. Accessories may also be necessary for proper air distribution in a space, so they must
be selected and used according to the manufacturers’ recommendations.
Factors That Influence Selection
Coanda (Surface or
Ceiling) Effect. Via
restricting secondary air entrainment, a jet moving adjacent to or in contact with an
impermeable wall or ceiling creates a low-pressure area immediately adjacent to that surface,
causing the air to remain in contact with the surface substantially throughout the length of
throw. This Coanda effect, also referred to as the
surface or ceiling
effect, counteracts, to varying extents, the negative-buoyancy-driven
the drop of a horizontally projected cool airstream.
Round and four-way horizontal-throw ceiling outlets exhibit a high Coanda effect because the
discharge air pattern blankets the ceiling area surrounding each outlet. This effect diminishes
with a directional discharge that does not blanket the full ceiling surface surrounding the
outlet due to entrainment into the exposed sides of the jet. Sidewall outlets exhibit varying
degrees of Coanda effect, depending on the spread of the particular air pattern, the angle of
the jet, and the distance from the outlet’s discharge to the surface.
When outlets are mounted such that they discharge into a free space not near an adjacent surface
(e.g., exposed duct-mounted supply air grille applications), the airstream entrains air around
the entire perimeter of the jet. As a result, the rate of entrainment is higher and the throw is
shortened. More information on jet behavior can be found in Chapter 20 of the 2021 ASHRAE Handbook—Fundamentals.
Temperature Differential. The greater
the temperature differential between the supply air projected into a space and the air in the
space, the greater the buoyancy effect on the path of the supply airstream. Heated, horizontally
projected air rises and cooled air falls, so this effect should be considered during outlet
selection. Chapter 20 of the 2021 ASHRAE Handbook—Fundamentals
has further discussion of the buoyancy effect.
Low-temperature supply air or cold building start-up in a humid environment may cause
condensation. Consider the effect of condensation on outlet and space surfaces during outlet
selection.
Sound Level. The sound level
from an outlet is largely a function of its discharge velocity and transmission of HVAC system
noise, such as from fans and air turbulence, and may be desirable for masking other sounds, or,
if too high, may be considered noise by occupants. For a given air capacity, a larger outlet
face area has a lower discharge velocity and correspondingly lower generated sound. However, a
larger outlet also allows more system-generated sound to pass through the outlet, which may
appear as outlet-generated noise to occupants. High-frequency noise can result from excessive
outlet velocity but may also be generated in the duct by the moving airstream. Low-frequency
noise is usually generated by mechanical equipment and transmitted through the duct and outlet
to the room.
The cause of a noise complaint can usually be pinpointed as outlet or system sounds by removing
the outlet’s core during operation. If the noise remains essentially unchanged, the system
is the source. If the noise is significantly reduced, the outlet is likely the source. The noise
may be caused by a highly irregular velocity profile at the entrance to the outlet. ASHRAE
research project RP-1335 (Landsberger 2011) and Chapter 58 of the 2023 ASHRAE Handbook—HVAC Applications have more details on
the
effects of inlet conditions on air outlets.
Variable-Air-Volume (VAV) Outlet. A VAV outlet is an air outlet that
self-modulates its primary air flow rate with an integral air damper. Select outlets based on
the total range of airflow needed for the space served. Outlet performance characteristics
should be evaluated at both minimum and maximum flow. More information regarding selection of
outlets can be found in Chapter 58 of the
2023 ASHRAE Handbook—HVAC
Applications.
Outlet Selection Procedure
The following procedure is generally used in selecting and locating an outlet in a fully mixed
system. More details and examples are available in Rock and Zhu (2002) and Chapter 58 of the
2019 ASHRAE Handbook—HVAC Applications.
-
Determine the design flow rates of air to be supplied to each room. (See Chapters 17
and 18 of the 2021 ASHRAE Handbook—Fundamentals to
determine air quantities for heating and cooling modes.)
-
Select the type and quantity of outlets for each room, considering factors such as
air quantity required, distance available for throw or radius of diffusion,
structural characteristics, and architectural concepts.
-
Outlets may be sized and located to distribute air in the space to achieve acceptable
temperature and velocity in the occupied zone. Select and locate outlets such that
the air supplied reaches the breathing zone, as defined by ASHRAE Standard 62.1 for heating and cooling in many buildings.
-
Select the proper size outlet from the manufacturers’ performance data
according to air quantity, neck and discharge velocity, throw, distribution pattern,
and sound level. Note manufacturers’ recommendations regarding use. Also,
obstructions to the primary air distribution pattern require special study. In an
open space, the interaction of airstreams from multiple air outlets may alter a
single outlet’s throw, air temperature, or air velocity. As a result,
manufacturers’ data may be insufficient to predict air motion in a particular
space. The air diffusion performance index
(ADPI) is a useful tool in predicting outlet performance for
fully mixed systems; see Chapter
58 of the 2023 ASHRAE
Handbook—HVAC Applications for more information.
2.2 FULLY STRATIFIED SYSTEMS
Stratified room air distribution systems, typically called thermal
displacement ventilation, generally rely on supply outlets with very low
discharge velocities (e.g., 0.2 to 0.36 m/s based on total face area) to produce
minimal room air entrainment so that much of the temperature difference between supply and the
occupied zone’s air is preserved. With outlets placed low, and when in cooling mode, cool
supply air accumulates near the floor. Heat sources in the occupied zone create convection plumes
that originate around the boundaries of the heat source and rise naturally because of their
buoyancy. If these sources are near the supply airstream, supply air is entrained to fill the void
of the rising convection plume.
The cooling-mode temperature differential between supply and room air is generally less than that
commonly used for fully mixed systems. Exhaust air is generally higher temperature compared to fully
mixed systems, especially with high ceilings. Stratified systems used in transient spaces where
thermal comfort is less critical may, however, use air temperature differentials like those in fully
mixed systems.
Factors that Influence Selection
Space Considerations. To maximize system efficiency,
supply outlets are typically located below the occupant breathing level, so installed low in the
sidewall or in-floor. These supply outlets often take up considerably more surface area than
outlets used in fully mixed systems. Wall recessed outlets are common but can be configured as
quarter-round, semicircular, rectangular, or cylindrical to increase face area. Cylindrical air
outlets are generally mounted in a room’s open space, whereas the other configurations are
mounted in corners, adjacent to the side wall, or flush with the wall.
Space Heating Considerations. Skistad (2002) reported
that displacement ventilation can be combined successfully with radiators and convectors at
exterior walls to offset space heat losses. Radiant heating panels and heated floors also can be
used with displacement ventilation. When a secondary heating system is used, displacement
outlets should supply air at least 1 K cooler than room temperature to maintain
displacement airflow to the space.
System and Terminal Considerations. Low-velocity
supply air outlets used in fully stratified systems can function properly with either constant-
or variable-air-volume (CAV or VAV) supply air systems. For VAV applications, the supply air
flow rate should be varied via a thermostat located in the space at a height of 1.2 to 1.5
m.
For fully stratified systems in humid climates, using series fan-powered terminal units or other
mixing zone devices may allow supply air to be delivered from the central HVAC system at
conventional temperatures and then blended with return/plenum air in the terminal unit to bring
the air to an appropriate discharge temperature. However, this may compromise the space
contaminant removal benefits of the displacement system.
Outlet Selection Procedure
Supply outlets used in stratified air systems tend to be mounted low in the sidewall or in-floor.
They may also be mounted in the floor or risers beneath seats in public assembly facilities.
Both mounting locations can produce adequately low discharge velocities; however, the outlets
needed tend to be quite large. Because discharge velocities are very low, the supply airstream
produces little momentum, and small obstacles, other than heat sources, in the flow path have
little effect on its travel. Selection and application of air outlets for these systems is based
primarily on the following considerations:
-
Maintaining vertical temperature gradients
within the occupied zone that conform to ASHRAE Standard
55. Further guidance on designing for conformance to this standard is presented in
Chapter 58 of the 2023 ASHRAE Handbook—HVAC
Applications.
-
Maintaining a clear zone (also called
adjacent zone) to the outlets that is
acceptable to the function and occupancy of the space.
-
Providing acoustical performance that
conforms to the requirements of the space.
Supply outlets used in fully stratified systems are typically selected for a maximum face
velocity of 0.2 to 0.36 m/s. Limitation of the face velocity is determined by noise
requirements and proximity of occupants to the outlet. Where space noise requirements are not so
stringent and stationary occupants are far away from diffusers, higher face velocities can be
used. It is also important that the supply air outlet and its ductwork be designed to distribute
airflow evenly across the outlet’s entire discharge area to avoid excessive velocity
deviations.
The area adjacent to the supply outlet where local velocities may exceed 0.25 m/s is
defined as the adjacent zone, where local velocity/temperatures may combine to create drafty
conditions. Manufacturers of outlets specifically intended for fully stratified systems publish
predicted adjacent-zone values that depend on the outlet supply airflow rate and the initial
temperature difference between the supply and room air. Stationary occupants should not be
present routinely in the adjacent zone.
For applications requiring very low noise criteria, such as broadcast or recording studios or
performing arts venues, acoustical performance is an important consideration. Because of their
low-velocity discharge, these supply outlets can generally be selected to meet acoustical
criteria for these applications.
2.3 PARTIALLY MIXED SYSTEMS
Partially mixed room air distribution systems are those whose design intent is to create mixed
conditions in a portion of the room while maintaining thermal stratification in the remainder of the
space. Supply outlets for these systems are usually designed and selected to discharge supply air
from low sidewall or floor locations. These outlets produce high room air entrainment such that
velocity and temperature differentials between supply and room air can be quickly dissipated. This
results in relatively well-mixed room air conditions in some or all the occupied space, while
stratified conditions are maintained throughout the remainder. Although most underfloor air
distribution systems should be classified as partially mixed systems, underfloor air delivery can
also produce fully mixed or fully stratified room air distribution.
Because supply air is introduced in the occupied zone, the supply air temperature is generally set
above 16.7°C for cooling mode.
Factors That Influence Selection
Space Considerations. Partially mixed air distribution
systems often rely on a pressurized plenum to deliver conditioned air to the supply air outlets;
therefore, most of these outlets are not individually ducted. For example, underfloor air
distribution systems commonly use the cavity beneath a raised access floor as a pressurized
plenum. The supply outlets are mounted in the access floor tiles and can easily be relocated in
response to space changes and workstation relocation.
Most supply outlets used in pressurized floor plenum applications can be easily adjusted for
airflow by the space occupant. In such applications, it is usually effective to provide an
adjustable outlet in every office or workstation to afford occupants control of their own
environment. Many of these outlets can also be fitted with a thermostatically controlled damper
that provides variable air flow rates to the space.
System and Terminal Considerations. Supply air outlets
designed specifically for partially mixed room air distribution systems can use either CAV or
VAV systems. For VAV applications, the supply air flow rates should be determined via a
thermostat located in the space at a height of 1.2 to 1.5 m.
Outlet Selection Procedures
Supply outlets used in stratified air systems tend to be mounted low in the sidewall or in-floor.
Because of their high degree of mixing supply and room air together, these outlets can be
selected for much higher discharge velocities than those used in fully stratified systems,
resulting in significantly smaller outlet discharge areas. Selection and application of air
outlets for partially mixed systems is based primarily on the following considerations:
-
Maintaining vertical temperature gradients
in the occupied zone that conform to ASHRAE Standard 55.
Further guidance on designing for conformance to this standard is presented in
Chapter 58 of the 2023 ASHRAE Handbook—HVAC
Applications.
-
Maintaining an adjacent zone adjoining the
outlets that is acceptable to the function and occupancy of the space.
-
Providing acoustical performance that
conforms to the requirements of the space.
Supply outlets should be selected such that their vertical projection achieves comfort and
ventilation objectives. Limiting the vertical projection to a terminal velocity of 0.25
m/s of the supply air to below the respiration level, typically 1.4 m
per ASHRAE Standard 62.1, allows convective heat plume formation
around occupants to convey respiratory contaminants up and out of the occupied zone. This
creates breathing-level CO2 concentrations like those associated with fully
stratified room air distribution systems. Projections that exceed this level discourage
formation of such plumes and result in space ventilation like that of fully mixed systems.
The area adjacent to the supply outlet where local velocities may exceed 0.25 m/s is
defined as the adjacent zone, where local
velocity/temperatures may combine to create drafty conditions. Manufacturers of outlets
specifically intended for fully stratified systems publish predicted adjacent-zone values that
depend on the outlet supply airflow rate and the initial temperature difference between the
supply and room air. Stationary occupants should not be present routinely in the clear zone.
For applications requiring very low noise criteria, such as broadcast or recording studios or
performing arts venues, acoustical performance is an important consideration. These supply
outlets may be suitable to meet acoustical criteria for these applications.
Typically, supply air grilles are used in high sidewall, sill, or floor applications, where supply
air diffusers are most commonly used in ceilings or are mounted on exposed overhead ducts. Nozzles
are typically installed on high-sidewall locations in large spaces.
High Sidewall. An adjustable double-deflection grille
usually provides the most satisfactory solution. The vertical blades of the grille can be set for
approximately 50° maximum deflection to either side, which can usually cover the conditioned
space. Horizontal blades, if any, can be set to control the elevation of the discharge pattern.
Upward deflection minimizes thermal drop in cooling applications, especially when the air jet can
then attach to the ceiling.
Ceiling. Such installation is generally limited to ceiling
diffusers or grilles with curved vanes that discharge parallel to the mounting surface. For high
mounting locations (greater than 3 m above the occupied zone), vertically down
discharge outlets may be preferred for these high bay applications. Supply outlets installed in
2.4 to 3 m high ceilings can achieve satisfactory performance if appropriate
consideration is made for terminal velocities and temperature differentials in the occupied space.
Discharging the airstream directly into occupied zone may result in unacceptable comfort conditions.
Supply outlets needed for both heating and cooling from the same device should be carefully examined
for use in both modes.
Sill. Linear bar grilles are commonly used in sill
applications. The grille should be installed with the supply air jet directed vertically and away
from the occupied space. When the device is mounted 300 mm or less from the wall, a
device with 0° deflection is suitable. If the device is installed more than 300 mm
from the vertical surface, a linear bar grille with a fixed 15 to 30° deflection is recommended.
This device should be installed with the jet directed toward the wall. These grilles can be
available with doors, removable cores, or other means of access to mechanical equipment that may be
installed in the sill enclosure. The presence of window draperies or blinds and the effect of an
impinging airstream must be considered in the selection. In high-humidity applications in cold
locations, such as a natatorium in winter, special care is needed to prevent condensation on the
glazing and other cold exterior surfaces.
Floor. Linear bar grilles are often used for floor
applications. The designer should determine the traffic and floor loading on the grille; consult
local building code for minimum rating requirements and determine the manufacturer’s load
limit for the grille. The grille should be placed in low-traffic areas. A floor-mounted grille is
usually selected to discharge supply air along a wall or exterior surface. Install with the supply
air jet directed vertically and away from the occupied space. When the device is mounted 300
mm or less from the wall, a device with 0° deflection is suitable. If the device is
installed more than 300 mm from the vertical surface, a linear bar grille with a fixed
15 to 30° deflection is recommended. This device should be installed with the jet directed
toward the wall. The presence of window draperies or blinds and the effect of an impinging airstream
must be considered in the selection.
Underfloor air distribution (UFAD) typically employs swirl
or linear bar grille type supply outlets recessed into the floor that discharge directly into the
occupied zone. Displacement ventilation typically employs supply outlets fixed to the wall,
sometimes mounted in the ceiling or floor, that discharge directly into the occupied zone. When
sizing and locating the outlets, care should be taken to ensure occupant thermal comfort with either
type.
Table 1 shows the
types of supply air outlets and provides guidance for best use practices. This table is for guidance
only; designers should consult manufacturers’ literature for additional application
information.
3.2 RETURN AND EXHAUST AIR INLETS
Return air inlets may either be connected to a return duct or simply cover openings that transfer air
from one area to another; the latter are commonly called transfer
grilles. Exhaust air inlets remove air from a building and, therefore, are
almost always connected to an exhaust duct and usually a dedicated fan. Velocity, sound, and
pressure requirements for return and exhaust inlets are determined by size and configuration. In
general, the same type of equipment, such as grilles, slot diffusers, and ceiling diffusers used for
supplying air, may also be used for air return and exhaust. However, return/exhaust inlets do not
require the flow deflection, equalizing, and turning devices necessary for supply outlets; their
blades may be deflected for blocking lines of sight into ducts, if desired. Return and exhaust
inlets may be mounted in practically any location (e.g., ceilings, high or low sidewalls, floors,
and doors, the latter if fire code allows). Dampers such as the one shown in Figure 3A are sometimes used
in conjunction with return and exhaust grilles to aid system balancing. When used in a partially
mixed or fully stratified system, the returns and exhaust outlets should be located above the
occupied zone, either ceiling or high sidewall mounted unless superseded by other codes or
standards.
A supply air grille usually consists of a frame enclosing a set of either fixed or adjustable
vertical or horizontal vanes for a single-deflection grille, or both for a double-deflection grille.
These are typically used in sidewall, ceiling, sill, and floor applications. Return and exhaust
grilles usually have fixed vanes. Pressure drop and acoustic performance are optimized when blades
are not angled, though blades may often be adjusted to achieve a desired throw pattern from supply
grilles.
Adjustable-Blade Grilles. This is the most common type
used as a supply outlet. A single-deflection grille includes a set of either vertical or
horizontal vanes or blades. Vertical vanes deflect the airstream in the horizontal plane;
horizontal vanes deflect the airstream in the vertical plane. A double-deflection grille has a
second set of vanes, typically installed behind and at right angles to the face vanes and
controls the airstream in both horizontal and vertical planes.
Fixed-Blade Grilles. These are like the
adjustable-blade grille except that the vanes or blades are not adjustable and may be straight
or angled. For supply grilles, the angle(s) at which air is discharged depends on the deflection
of the vanes. Fixed-blade grilles are more commonly used as return or exhaust air inlets. Angled
blades reduce visibility into the ductwork.
Linear Bar Grilles. When used for supply, these
outlets typically have fixed bars at the face. The bars normally run parallel to the length of
the outlet and may be straight or angled. These devices supply air in a constant direction and
are usually attached to a separate supply air plenum that has its own inlet. Linear bar grilles
can be installed in multiple sections to achieve long, continuous lengths or installed as a
discrete length. Also commonly used in underfloor air distribution systems, some linear bar
grilles allow the discharge pattern to be changed using removable or adjustable cores. Many also
incorporate a damper and actuator for automatic control of the supply air flow rate via a space
thermostat. Linear bar grilles are sometimes manufactured with curved shapes for architectural
purposes. When linear bar grilles are used for supply, similar grilles are also commonly used as
return or exhaust inlets to provide a consistent architectural appearance.
Eggcrate Grilles. These fixed-blade grilles are only
recommended for return or exhaust applications and typically have large free areas exceeding 90%
of the face.
Transfer Grilles. These fixed-blade grilles are
installed in an interior wall or door allowing air transfer from an enclosed room to an adjacent
room or plenum to allow normalization of pressure between them.
Application-Specific Grilles
Security Grilles. Various fixed-blade grille types are
available for high-security applications. Security grilles are available with additional
features like heavy-duty construction, suicide deterrents, lattice faces, and tamperproof,
nonremovable blade designs. Institutional guidelines exist for proper selection and placement of
security grilles.
Heavy-Duty Grilles. Robust, heavy-duty designs are
available for applications that require greater durability (e.g., industrial, gymnasium,
institutional).
Spiral Duct Grilles. Grilles manufactured with a frame
designed to be mounted directly onto the surface of a round duct without requiring an additional
duct boot.
3.4 NOZZLES AND DRUM LOUVERS
Ball, jet, and adjustable nozzles and drum louvers direct high velocity air jets into the space.
These devices typically have long throws and no or few vanes in their airflow paths. They are often
installed in buildings as horizontally discharging high-sidewall outlets, in duct soffits (fur-downs) or in ductwork. Nozzles and drum louvers are
typically used in large spaces. Aircraft and automobile ventilation systems also use smaller
versions of these types of outlets (Rock and Zhu 2002).
The equations in Chapter 20 of the 2021 ASHRAE
Handbook—Fundamentals can be used to estimate throw from many such simple
duct
terminations or orifices. For complex situations, physical experiments, or computational fluid
dynamics (CFD) modeling, may be helpful in selection and design.
Diffusers usually generate a radial or directional discharge pattern. For ceiling applications, this
pattern is typically parallel to the mounting surface, thus creating a horizontal pattern. Diffusers
may also include adjustable deflectors that allow discharge to be directed perpendicular to the
mounting surface, creating a vertical pattern. A diffuser typically consists of an outer shell,
which contains a duct collar, and internal deflector(s), which define the diffuser’s
performance, including discharge pattern and direction. Refer to the ASHRAE Handbook Online version
of this chapter for illustrations of each diffuser.
Round Diffuser. This diffuser is a series of
concentric conical rings flush with the ceiling plane or with dropped inner cones, typically
installed either in gypsum-board ceilings or on exposed ducts. Round ceiling diffusers are
available in a broad range of sizes and capacities, and with or without adjustable inner cones
that allow the diffuser to discharge air either horizontally or vertically.
Square Diffuser. This diffuser consists of concentric
square, drawn louvers that radiate from the center of the diffuser. They are commonly mounted in
suspended or gypsum-board ceilings or are attached to exposed ducts. Their necks can be round or
rectangular, and the necks’ sizes should be matched to the ducts’. Available with
faces that are flush with the ceiling plane or with dropped inner cones, these diffusers have a
fixed horizontal radial discharge pattern or an adjustable discharge pattern that allows the
direction to be either horizontal or vertical. Special borders can be selected to accommodate
various mounting applications; for example, pans are available so that a desired face size can
be smaller than a suspended ceiling’s grid size.
Perforated Diffuser. This diffuser consists of a duct
collar and a single perforated plate that forms the diffuser’s face, with typical free
area of about 50%. The perforated face tends to create a slightly higher pressure drop and sound
than similarly sized square ceiling diffusers. They are available with deflection devices
mounted at the neck or on the face plate. The deflectors may be adjustable, to provide
horizontal air discharge in one, two, three, or four directions. Special borders can be selected
to accommodate various mounting applications.
Louvered-Face Diffuser. This diffuser consists of an
outer border, which includes an integral duct collar, and a series of louvers or curved blades.
Louvered-face diffusers typically provide a horizontal discharge perpendicular to the louver
length. The louvers may be arranged to provide four-way, three-way, two-way opposite, two-way
corner, or one-way discharge. Some louvered-face diffusers are available with adjustable louvers
that can change the discharge pattern. Special borders are available to accommodate various
mounting applications.
Plaque-Face Diffuser. This diffuser is constructed
with a duct collar and a single plaque that forms the diffuser’s face. This air outlet
typically has a horizontal, radial discharge pattern. Special borders can be selected to
accommodate various mounting applications.
Hemispherical Flow Diffuser. This diffuser provides a
vertically radial air discharge pattern. The discharge penetrates the conditioned space
perpendicular to the mounting surface. These diffusers are typically used for applications
needing high air change rates, and/or low local velocities. Some outlet models are flush to the
mounting surface; others protrude into the space below the ceiling. Most function similarly with
or without an adjacent ceiling surface.
Laminar Diffuser. Sometimes called nonaspirating, this diffuser provides a unidirectional
discharge perpendicular to the mounting surface. The free area of the perforated face is
typically less than 35%. Most outlets are designed to develop a uniform velocity profile over
the full face of the diffuser. This minimizes mixing with surrounding ambient air and reduces
entrainment of any surrounding contaminants. These diffusers are typically used in hospital
operating rooms, cleanrooms, or laboratories.
Linear Slot Diffuser. Linear slot diffusers may be
installed in multiple sections to achieve long, continuous lengths, or installed as a discrete
length. They can consist of a single slot or multiple slots and are available in configurations
that provide vertical to horizontal airflow. Typically, a supply air plenum is provided
separately and attached between the diffuser and the duct during installation. Other
applications include field mounting the linear slot diffuser directly into a supply duct.
T-Bar Slot Diffuser. This diffuser is manufactured
with an integral plenum and normally is installed in modular suspended (T-bar) ceilings.
Available with fixed-deflection or adjustable-pattern controllers, these devices can discharge
air from vertical to horizontal.
Light Troffer Diffuser. A light troffer diffuser
serves as the combined plenum, inlet, and attachment device to an air-handling light fixture,
which has a slot to receive the diffuser at or near the face of the lighting device, to
discharge supply air into the space. Only the air-handling slot is visible from the occupied
space.
Swirl Diffuser. This diffuser features a series of
openings arranged in a radial pattern around the center of the diffuser face. This promotes a
high degree of entrainment of room air, resulting in very high induction ratios, which maximize
mixing in the area adjacent to the diffuser face. Swirl diffusers may be mounted in ceiling,
sidewall, or floor locations. They are commonly used for UFAD applications where it is necessary
to locate the supply outlets close to the space occupants. When mounted in floor locations, care
should be taken to ensure that the diffuser can meet the floor loading requirements.
Displacement Diffuser. Typically located in floor or
low-sidewall locations, this diffuser is designed to limit discharge velocities to 0.2 to
0.36 m/s to minimize mixing between supply and room air. These outlets tend be large
to generate the low velocities required for thermal displacement ventilation: low-velocity
discharge allows the cooler supply air to fall to the floor and remain there because its
buoyancy is lower than that of the ambient room air above it. These outlets are available in
various shapes and configurations that facilitate flush or adjacent mounting to the sidewalls or
floor of the space.
Textile Air Dispersion System. This outlet system is
designed to both convey and disperse air within the space being conditioned. Diffusion options
include outlets selected for a full range of entrainment. The supply air is delivered through
(1) the weave of the fabric, (2) microperforations, (3) a long and narrow pattern of small jets,
(4) orifices, and/or (5) nozzles. Typically, these systems are made of fabric, sheet metal, or
plastic film.
Variable-Air-Volume (VAV) Diffuser. A VAV diffuser is
an air outlet that self-modulates its primary air flow rate with an integral air damper. Select
outlets based on the total range of airflow for the space served. Outlet performance
characteristics should be evaluated at both minimum and maximum flow. More information regarding
selection of outlets can be found in Chapter
58 of the 2023 ASHRAE
Handbook—HVAC Applications.
Variable Geometry Diffuser. One type of VAV outlet is
a variable geometry diffuser. These diffuser assemblies vary their discharge area or air pattern
in response to changes in space or supply air temperature.
Supply Air Diffuser Accessories
Dampers
can be attached to grilles (the combination of a grille and a damper is called a register), diffusers, or installed as separate units in
the duct, to regulate the device’s airflow rate:
-
Opposed-blade damper vanes rotate in
opposite directions (Figure 3A and
4A) and
are available for round, square, or rectangular necks.
-
Parallel-blade dampers rotate in the same
direction (Figure 3B).
-
Adjustable-vane dampers have individually
adjustable vanes.
-
Butterfly dampers are constructed with
opposing damper plates that move in opposite directions and are adjusted from a
center point (Figure
4B).
-
A splitter damper is a single-blade
device, hinged at one edge and usually located at the branch connection of a duct or
outlet (Figure
4C). The device is designed to allow adjustment at the branch connection of
a duct or outlet to adjust flow.
-
Radial sliding dampers consist of multiple
overlapping flat blades that rotate in the horizontal plane to restrict the
airstream (Figure
4D).
-
Radial opposed blade dampers consist of a
series of radial blades that pivot to restrict the airstream (Figure
4E).
Other miscellaneous accessories, such as remote control
devices to operate the dampers, and travel
limit stops, are also available.
When these dampers are located on or near the air outlet, they may cause nonuniform airflow
discharge and increased pressure drop and sound. In the 2023 ASHRAE
Handbook—HVAC Applications, Chapter
49 describes the effects
of damper location
on sound level and Chapter 58 addresses
the effects of damper location on sound, throw
performance, and pressure drop.
Extractors are installed in duct-collar connections to
the outlet and are used to improve the flow distribution into a supply outlet. The device shown
in Figure 3C has vanes that
pivot such that the supply airflow to the grille or register remains perpendicular to the face
of the outlet. The device shown in Figure 3D has fixed
vanes. Both devices restrict the area of the duct in which they are installed and should be used
only when the duct is large enough to allow the device to open to its maximum position without
unduly restricting airflow to the downstream duct. These devices may increase the system
pressure requirement, thereby limiting downstream airflow and increasing the sound level. An
extractor mounted directly to the grille, as shown in Figure 3F, is sometimes
called a scoop.
Adjustable vanes, as shown in Figure 3E, are
individually adjustable. Typically, two sets of vanes are used. One set equalizes flow across
the collar, and the other set turns the air. The vanes should not be adjusted to act as a damper
because balancing requires removing the grille to gain access and then reinstalling it to
measure airflow.
Equalizing or flow-straightening devices or grids allow adjustment of the airstream to obtain more
uniform flow to the diffuser.
Quadrant blank-off flat plates restrict airflow in one
or more quadrant(s) of the diffuser inlet.
Other balancing devices are available. Consult manufacturers’ literature as a source of
information for other air-balancing devices.
In air distribution systems, special control and acoustical equipment is frequently required to
introduce conditioned air into a space properly. Airflow controls for these systems consist
principally of terminal units, the most common of which historically were called VAV boxes, with which the airflow can be varied by
modulating valves, fan controls, or both. Terminal units such as those listed here are supplied with
or without cooling coils, fans, heat or reheat coils, and having either constant or variable primary
airflow rate. Terminal units typically control the flow of conditioned air supplied through a duct
from an air handler and deliver it to the occupied space, but sometimes, such as in the case of
underfloor units located in a cooled supply air plenum, may take the air directly from the plenum
with no primary duct. They may use a ducted or nonducted return plenum or room air induction to
affect space temperature control while maintaining a constant or variable discharge airflow rate
and/or temperature. Terminal units may also include, usually as accessories, sound reduction
devices, diffusers, filters, or other air treatment devices.
This section discusses control equipment for forced air-conditioning systems. Chapter 49 of the 2023
ASHRAE Handbook—HVAC Applications includes information on
sound
control in air-conditioning systems and sound ratings for air outlets.
Terminal units are factory-made assemblies for affecting air distribution. A terminal unit manually
or automatically performs one or more of the following functions: (1) controls air velocity, airflow
rate, pressure, or temperature; (2) mixes primary air from the duct system with air from the treated
space or from a secondary duct system; and (3) heats or cools the air. To achieve these functions,
terminal unit assemblies are made from an appropriate selection of the following components: casing,
mixing section, manual or automatic air control device, heat exchanger, induction section (with or
without fan), sound reduction devices, and flow controller.
Terminal units are typically classified as constant or variable air flow rate devices. They are
further categorized as either pressure-dependent, where airflow through the assembly varies in
response to changes in system pressure, or pressure-independent or -compensating, where airflow
through the device does not vary in response to changes in air pressure.
Variable-air-volume (VAV) reset controllers regulate airflow to a constant, fixed amount or to a
variable, modulating amount calculated by room demand. These controllers can be electric (typically
yielding pressure-dependent performance), analog, or digital electronic (giving pressure
independence), or pneumatic with pressure-dependent or -independent flow. Pressure-independent
controllers require an indication of actual airflow to reset the VAV airflow control device.
Temperature inputs are also required for calculating room demand for comfort conditioning.
Terminal unit controls are categorized as (1) system-powered, in which the airflow control device
derives the energy necessary for operation from supply air within the distribution system; or (2)
externally powered, in which the airflow control device derives its energy from a pneumatic or
electric outside source. Terminal units may be furnished with all necessary controls for their
operation, including actuators, regulators, motors, and thermostats or space temperature sensors, or
the controls may be furnished by someone other than the terminal unit manufacturer.
The unit’s flow control device can be adjusted manually or automatically. If the unit is
adjusted automatically, it is actuated by a control signal from a controller, thermostat, flow
regulator, or building management system (BMS), depending on the desired function of the terminal
unit.
Single-Duct Terminal Units
Single-duct terminal units can be cooling only, heating only, or cooling and heating. Terminal units for cooling modes often have
reheat coils that add sensible heat to the supply air as part of the overall humidity control.
Hot-water or steam coils, or electric resistance heaters, are placed in or attached directly to
the air discharge of the terminal unit. This type of equipment can provide varying reheat,
customized to the thermal zone being served.
The basic single-duct unit consists of an insulated casing, airflow regulator, and possibly also
an actuator, airflow-measuring device, and selected controls. Accessory discharge attenuators,
silencers, and multiple outlet attenuators are also common. In the lower and middle latitudes,
typical applications include those with
-
The supply air system is not tasked with the space heating requirements
-
Variable airflow rate and temperature (VVT) or other auto-changeover controls
-
Constant air volume
-
Constant pressure control
A single-duct unit with a reheat can also be used in
zones where heating-mode needs are low so that the reheat coil can serve dual purposes. The
terminal unit usually reheats at the minimum airflow setting. An auxiliary higher heating
setting may be available as an option with additional controls.
Interior zones, where ventilation requirements may be larger than the desired heating airflow,
may require additional reheat capacity.
A single-duct exhaust valve is a type of single-duct
ATU (air terminal unit) designed for exhaust air and consists of an insulated casing, airflow
regulator, and possibly also an actuator, airflow-measuring device, and selected controls.
Accessory inlet attenuators or silencers are sometimes used. Specialty materials may be needed
for corrosion resistance. The designer should consider pressure drop and system effects.
A venturi valve is a type of single-duct ATU and can
be used for either supply or exhaust. Traditionally, the device consisted of a round venturi
valve body and an internal shaft that supports a cone assembly. Newer technologies remove the
internal cone assembly and use damper blade assemblies to control airflow.
Cone Assembly Type. The cone assembly is spring-loaded on the shaft.
As pressure in the primary duct increases, the cone compresses the internal spring and moves
closer to the venturi throat, increasing resistance to the airstream. As pressure in the primary
duct decreases, the spring retracts and the cone assembly moves farther from the venturi throat,
decreasing resistance to the airstream. This is called mechanical
pressure independence. If the venturi valve is provided with an actuator
to allow for variable airflow, the actuator and positioning arm reposition the shaft, which in
turn moves the cone assembly relative to the throat, changing the airflow.
Damper Assembly Type. The damper assembly is controlled by an
actuator that responds to differential pressure between two different points along the venturi
valve body or by other means. The damper modulates to control airflow as pressure fluctuates,
yielding a pressure-independent system that directly
measures airflow through the valve body. A controller is used to modulate the valve damper
actuator and control the overall system sequence of operation, whether constant volume or
variable volume.
Dual-duct terminal units are typically controlled by a room thermostat or sensor. They are each
connected to two supply air ducts that deliver two of warm, cold, recirculated, mixed, or
outside air to provide desired room control. Volume-regulated units have individual airflow
control devices to regulate the amount of air from the two supply ducts. Dual-duct units can
have reheat coils too if mixing of the hot and cold ducts’ air is insufficient for
humidity control or space heating. When a single temperature control device regulates the
relative amounts of both warm and cold air to control temperature, a separate airflow control
device may function to control and limit total airflow from the unit. Specially designed baffles
may be required inside the unit or at its discharge to mix varying amounts of warm and cold air
and/or to provide uniform temperature distribution downstream. Dual-duct units can be equipped
with constant- or variable-flow control. These are typically pressure independent, to provide
consistent flow rate and temperature control. Dual-duct terminals may also be used with outdoor
air conditioned and supplied by a primary air-handling unit and ducted to the terminal units;
such systems’ AHUs maintain the required volumetric flow of ventilation air into the
spaces served. Dual-duct units with cooling and outdoor air may need a local heating device;
these primary-secondary air distribution systems thus
need careful analysis and design.
A nonmixing dual-duct unit is effectively two
single-duct terminal units side by side. The basic unit incorporates separate cold and hot air
inlets that are to be attached to the two primary-air ducts, with sometimes neutral-temperature
air in one of the ducts (e.g., during mild weather). The units are usually applied in exterior
zones in buildings where overhead heating and cooling are desired but not auxiliary heating, and
when zero minimum airflow is acceptable during changeover between heating and cooling. Proper
discharge configurations are required to reduce the likelihood of improper mixing.
A mixing dual-duct unit is the same, with an integral
mixing/attenuator section on the downstream end of the terminal unit to minimize temperature
stratification in the discharge airstream. They are often used in interior and exterior
zones in buildings (e.g., hospitals) where overhead heating and cooling are desired, but an
auxiliary heating coil is not, and zero minimum airflow is unacceptable during changeover
between heating and cooling. Evaluate mixing performance to fit the application, and consider
the additional pressure drop of mixing/attenuators sections.
Air-to-Air Induction Terminal
Units
Induction terminals supply primary air or a mixture of primary and recirculated air to the
conditioned space. They achieve this function with a primary air jet that induces recirculated
air, known as secondary air in this application, via grilles to the ceiling plenum or from
individual rooms via a return duct. Typically, the primary air is of higher design velocity than
that delivered to other types of terminal units, and the extra momentum is used as the inducing
energy source. The induction unit contains devices that are actuated in response to a thermostat
to modulate the mixture of primary air and induced secondary air. Reheat coils may be required
to meet interior load requirements. Historically, induction units were used with high-velocity
ducts, and often produced much noise. Modern versions often work well with much lower-velocity
air but require careful selection. Generally, induction units are considered where there is a
desire for zone-level air distribution equipment, installed in or over occupied spaces, that
have no fans or other components that may require frequent access for maintenance. Any terminal
unit that uses recirculated air must have an air filter, and that filter should be readily
accessible for inspection and periodic replacement.
Fan-Powered Terminal Units
Fan-powered terminal units are used as secondary-level air handlers in primary-secondary air
distribution systems and are typically installed in return air plenums. They can be specified
with either heating, reheating, or cooling coils, or a combination. They differ from air-to-air
induction units in that they each include a blower, driven by a small motor, which moves air
from the conditioned space, ceiling plenum, or floor plenum, that may be mixed with the primary
air from the main air handler. The characteristics of fan-powered units are
-
In heating mode, the primary air is mixed with usually warmer or cooler secondary air
that then passes through the unit’s heating coil.
-
The unit’s fan increases supply air pressure to deliver air to areas that
otherwise would be short of airflow.
-
With heating or cooling coils in the units, perimeter zones can be heated or cooled
without operating the main air handler when ventilation with outdoor air is not
required.
-
In-room air velocities can be kept consistently high to improve mixing.
-
Air velocities may be reduced in low-load conditions to decrease noise levels.
-
The main air handler operating pressure can be reduced with series fan-powered units
compared to other terminal units because the secondary-level fans provide some of
the total needed supply air pressure differential and may yield some fan-energy
savings.
-
In thermal storage and other systems with relatively low supply air temperatures,
series fan-powered terminal units may be used to mix the cold supply air with much
warmer induced return or plenum air, to moderate the discharge air temperature.
Some units are equipped with special insulation and a vapor retarder to reduce condensation with
below-dewpoint supply temperatures.
Fan-powered terminal units can be divided into two categories: (1) series, with all primary and
induced air passing through a blower in the unit that operates continuously during the occupied
mode; and (2) parallel, in which the blower operates only on demand when induced air or heat is
required.
Fan-powered terminal units typically use fractional horsepower alternating current (ac) electric
motors for their included blowers. Increasingly, high-efficiency electrically commutated motors
(ECMs) are used instead of older, less efficient motor designs. The efficiency of the motor
becomes more important as the units operate for more hours of each year.
A series unit typically has two inlets, one for
primary air from the central air handler and one for secondary air recirculated from the spaces
served, often via a ceiling or floor plenum. All air delivered to the zone passes through the
blower. The blower operates continuously whenever the primary air fan is on and can be cycled as
required when the primary fan is off. As the zone’s load decreases, an airflow control
device throttles the amount of primary air delivered to the blower. The blower makes up for this
reduced amount of primary air by acquiring more air from the conditioned space or ceiling plenum
through its secondary air inlet. Sometimes a series unit has two ducted inlets, like a dual-duct
terminal unit, in addition to the induction air inlet, which may or may not have ducting to it.
The second primary air duct is typically used for dedicated outdoor air systems. Fan airflow and
primary air can be varied when the units are in part-load condition, but fan airflow should
never be less than the total amount of air supplied to the unit by the ducted inlets.
Fan-Powered Series Flow. The basic unit consists of a
single-duct unit, blower/motor, and selected controls where the motor and primary damper are
arranged such that mixing occurs upstream of the blower; this unit is depicted in Figure 5. They also have
been called constant-volume or constant-fan units. Supplemental heating coils, such as
steam, hot water, or electric, are generally required. Electric-resistance heating coils are
typically located on the discharge of the unit; water coils may be on the discharge or the
induction port. Heating coils on the induction port, and thus upstream of the unit’s
blower, increase ambient temperature at its motor and decrease motor life. Supplemental cooling
coils are sometimes located on the induction port for some applications like when utilized in
conjunction with dedicated outdoor air systems. A low-profile version of the fan-powered series flow unit
is typically less than 300 mm tall and is commonly used where zoning requirements
limit building height and the architect wishes to maximize the number of floors, because these
units fit in a shallow ceiling plenum. Unlike standard fan-powered terminals, the fan/motor
assembly is installed flat on its side with the wheel rotating in a horizontal plane.
Fan-powered series-flow units are generally used for
-
Exterior zones where heating and cooling loads may vary considerably
-
Buildings where heating is desired when the central system is shut down during
unoccupied hours
-
Allowing lower central system supply duct static pressure
-
Where occupant comfort can be optimized, because the high-, sometimes constant-,
volume variable-temperature air delivery produces consistent air distribution,
acoustics, and ventilation air delivery
Dual Air Inlet Fan-Powered Series Flow. These units
are similar in construction to the standard series-flow terminals but have an additional air
inlet that provides a direct connection to the terminal unit for ventilation air. They are
commonly used in buildings where ventilation air is supplied via a dedicated ventilation duct
system to each terminal unit; this is generally done where it is desirable to monitor
ventilation air quantities to each zone.
Low-Temperature Fan-Powered Series Flow. These units
are the same as fan-powered series flow but have special construction to minimize the potential
for condensation. They can be used with cold-water/ice storage systems that provide
below-dewpoint temperature primary air to the zone terminals, or where standard terminals may be
exposed to high humidity.
Underfloor Fan-Powered Series Flow. This type is a
fan-powered series flow terminal unit designed to fit between the pedestal supports of raised-
or access-floor systems. They are available in several unit sizes, but with limited height and
width.
Primary and induction ports, if any, to such units may or may not be ducted. Typically, in
cooling mode, cool primary air is supplied to the well-sealed floor plenum, and heated air may
be ducted to the terminal unit that is then mixed with the cool air in varying amounts. In these
cases, the control system must perform the proper damper sequence to control room air
conditions.
Parallel fan-powered terminal units, in cooling mode,
supply the primary air directly to the space, bypassing its fan. In heating mode, the blower
section induces plenum air and is mounted in parallel with the primary airflow control device,
this unit is depicted in Figure 6. A backdraft
damper is included to limit the amount of primary air flowing through the blower section when
the blower is not energized. The blower in these units is generally energized after the primary
airflow has reached the minimum flow rate. Typically, the parallel unit provides constant-air
flow rate heating and variable air flow rate cooling. Although it is not recommended due to
control instability, these units are sometimes applied in CAV mode with electronically
commutated motors programmed to maintain constant airflow rate discharge. The motor control
algorithm gradually increases the unit’s fan speed as the primary airflow is reduced.
Parallel units are typically limited to one ducted supply inlet.
One weakness in parallel fan-powered terminals is leakage of primary air through the fan’s
backdraft damper and the mixing chamber housing. ASHRAE research project (RP-1292 (David 2007)
demonstrated that much of the energy saving associated with intermittent fan cycling is offset,
and in fact may be significantly less than the energy loss caused by this leakage.
Fan-Powered Chilled Water Series Flow. This unit type
takes all the features of a basic fan-powered series flow unit and incorporates a supplemental
cooling coil on the induction port. Typically, this cooling coil is designed for sensible
cooling only, to avoid condensation issues and in many cases, is used in conjunction with
dedicated outdoor air systems.
Fan-Powered Parallel Flow. Sometimes called variable-volume or intermittent-fan units, these consist of a single-duct
unit, blower/motor, backdraft damper, and selected controls; the motor and primary damper are
arranged such that mixing occurs downstream of the blower. Supplemental heating coils, either
steam, hot water, or electric, are generally required. Electric-resistance heating coils are
typically located on the discharge of the unit. Water coils may be on the discharge or the
induction port, although the discharge location adds to the supply air system’s static
pressure requirements and increases leakage through the backdraft damper, as shown in ASHRAE
RP-1292 (Davis 2007). Heating coils on the induction port increase the air temperature at the
unit’s fan motor and decrease its life.
Fan-powered parallel-flow units are used in exterior zones where heating and cooling loads may
vary considerably, and in buildings where heating is needed when the central air handler is shut
down during unoccupied hours.
Bypass Terminal Units. A bypass terminal unit handles
primary air through its inlet. The unit bypasses primary air to the ceiling plenum or to ducts
leading to the air handler’s return to meet the needs of the conditioned space. Primary
air, diverted into the ceiling plenum, returns to the central air handler as return air or
building exhaust. This method provides a low first cost with minimum controls, but it is energy
inefficient compared to other systems.
The basic bypass terminal consists of a diverter-type damper, actuator, bypass port, and selected
pressure-dependent controls. A balancing damper is recommended ahead of the inlet.
Bypass terminals are used primarily with packaged rooftop air conditioning equipment with a
direct-expansion (DX) coil where zoning is desired, but relatively constant airflows across the
system components (e.g., coils, fans) are required to minimize the potential for freeze-up. The
system offers a lower initial cost design. It does not provide the energy-saving advantages of a
VAV system with fan-speed control; almost all the energy savings are from the reduced motor
speeds that occur except at full design-load conditions.
This section discusses the use of hydronic and direct-expansion (DX) fan-coil units to control the
flow rate and temperature of air delivered to the space as required to maintain occupant thermal
comfort and/or ventilation rate. Chapter 5 discusses how fan-coil units
are integrated into the design of the building. Fan-coils operate independently of any central air
distribution system or are used similarly to some fan-powered terminal units.
There are various fan-coil systems to choose from when designing a building. Choosing
which one to use depends on the building owner’s considering installation, application,
operational cost, sustainability, thermal and acoustic performance, capacity, reliability, spatial
requirements, code restrictions, water or refrigerant piping distribution, maintenance, and unit
accessibility.
Fan-coil units are factory-made assemblies, and are typically much smaller than traditional,
centrally installed air-handling units. The fan-coil performs some combination of the following
functions: (1) temperature and humidity control, (2) ventilation of the conditioned space, (3)
filtration, and (4) room air distribution, including providing air motion for comfort. Their
blowers, when in operation, may provide beneficial acoustical masking in the spaces served. Fan-coil
units are available in various configurations, including vertical or horizontal airflow paths and
mounts for exposed or concealed locations in spaces. A zone temperature control device regulates the
fan-coil airflow rate or discharge air temperature, or possibly both.
As shown in Figure 7, the basic components of fan-coil
units are an integral or external filter frame, a heating or cooling coil, and fan. Both heating and
cooling coils may be included, depending on the needs of the thermal zone. The zone temperature
control device may be part of the fan-coil unit or supplied separately. Air entering the unit may be
100% recirculated air or a mixture of recirculated and outside air. The fan moves air from the
conditioned space through the coil or coils, which then transfers heat to or from the air. Fans are
usually placed after the coils (draw-through arrangements), but some fans are installed before the
coils (blow-through). The coils use steam, chilled or hot water, or refrigerant (DX), or are
electric resistance-heating elements. A filter is required at or upstream of the unit’s inlet
to minimize airborne particulates to keep downstream components cleaner. The fan and motor assembly
are generally arranged for quick removal for servicing. The fan may be directly or indirectly driven
by its electric motor. If the unit includes a dehumidifying cooling coil, it must be equipped with a
drain pan and drain for the condensate; an insulated pan may be desirable. Fan-coil casings are
typically galvanized or painted steel and may be prepped and painted after installation, but care is
needed not to cover permanent informational labels. The casing may be internally insulated for both
thermal and acoustic considerations.
Additional components are offered for many fan-coil units for specific applications, including fan
controls (e.g., modulating fan controls), thyristor control, or electronically commutated motors
(ECMs). A hydronic coil’s water valve piping package can include such components as manual or
automatic flow controls, pressure-independent water control valves, strainers, unions,
pressure-temperature ports, air vents, hose connections, drains, and balancing valves. The coil in a
DX system includes a fixed refrigerant expansion orifice device such as a capillary tube or a
thermal expansion valve. Electric heating controls include magnetic contact closure or solid-state
relays.
Fan-coil units are generally available in nominal sizes from95 to 1135 L/s or 2 to
21 kW, with direct drive permanent split capacitor (PSC) fan motors or ECMs for a wide
range of applications. These units can be used in ducted or nonducted single or multiroom
applications. They typically have multiple-row cooling coils and may have single- or multiple-row
heating coils. If a two-pipe hydronic system for seasonal heating or cooling is used, only one coil
may be included; however, four-pipe systems with separate heating and cooling coils are generally
recommended for improved comfort and overall efficiency. If steam is used instead of hot water, it
requires a separate coil. In a DX system, its coil is most often cooling-only, but heat pump
applications are increasingly of interest. For heat pump applications, specifying an electric
resistance heating coil is often also recommended. Fan-coil unit systems can
-
Require less building interstitial space, because the water/refrigerant piping system has
a higher energy density per unit fluid flow than an all-air system
-
Provide individual-zone temperature and humidity control
-
Enable retrofits to expand capacity beyond that of the existing air system.
-
Allow individual dwellings in multifamily buildings to have individual electrical meters
and separate air flows versus a central AHU
-
Provide occupants with independent temperature controls
DX fan-coil systems also eliminate the need for a central chiller plant. However, for DX fan-coil
units in high-rise buildings, the space required for mounting condensing units and the lift required
for oil in refrigerant lines must be considered. Minisplit and VRF systems that use a ducted indoor
fan-coil unit are available for high-rise and other applications, too.
Two- and Four-Pipe Hydronic Distribution Systems. When the
heating and cooling heat transfer fluids, typically treated water, are supplied to a common coil in
each terminal unit, it is called a two-pipe system, with one pipe for supply and one for return.
These are also called a heating/cooling changeover system. A four-pipe distribution system has
dedicated supply and return piping for the separate heating and cooling coils, or each circuit
within a common coil. The four-pipe system generally has a higher initial cost; however, it provides
(1) all-season availability of heating and cooling at each unit, (2) no summer/winter changeover
requirement at the terminal units, (3) controllability to maintain an energy-saving dead band
between heating and cooling, and (4) heating coil arrangements for either preheat or reheat.
A two-pipe system can only heat or cool, depending on the supply water temperature. During
intermediate seasons or when the building requires simultaneous heating and cooling, supplemental
electric heat is usually provided. The coil is typically sized larger for cooling, so careful
consideration of the heating water temperature is required; often it is lower than for a dedicated
hydronic heating coil.
Motors and Controls. When selecting a motor type, consider
features such as control type, control scheme, and sequence of operation. The differences between a
permanent split capacitor (PSC) versus an electronically commutated motor (ECM) affect the sequence
of operation, which in turn dictates type of room thermostats, controls, and water valves. When an
ECM is used in a fan-coil, both the fan motor and water control valve are typically modulated by a
controller based on room demand.
The most common control for fan-coils is a room thermostat. These thermostats come in both line
voltage (i.e., same voltage as motor) and 24 VAC; generally, a lower control loop voltage is
preferred due to safety expectations. Both thermostats offer simple on/off or multispeed control of
fan motors and open/close control of water control valves, although programmable versions are
readily available that adjust the temperature set point for expected occupancy variations (i.e.,
setback thermostats).
Analog controllers can provide high level of control for modulating components such as ECMs, water
valves, and silicon-controlled rectifiers (SCRs). The most advanced level of building control is
provided by direct digital control (DDC), which adds communication ability through a building
automation system (BAS).
Additional information on fan-coil unit motors and controls can be found in Chapter 58 of the 2023
ASHRAE Handbook—HVAC Applications.
Unit Types and Configurations. Fan-coil units are
available in many different configurations; however, not all configurations discussed here are
available for all types of units. Orientation of airflow from return to supply, unit features, and
dimensional characteristics constitute the major differences between configurations. Outdoor air can
be mixed with recirculated air in the plenum or at the fan-coil unit or be delivered directly to the
space separately from the fan-coil’s supply air. Changes in industry standards have increased
the use of coupling ventilation air to fan-coil units. The outdoor air can be pretreated or
unconditioned and ducted or nonducted. Fan-coil units are available with a variety of options to
handle outdoor air, such as mixing boxes, outdoor air duct collars, air measuring devices, or air
control devices.
Vertical Units. Low-profile vertical fan-coil units (called sill units or
cabinet heaters) are typically used beneath or adjacent to windows or exterior walls in concealed or
exposed cabinets. The low silhouette sometimes limits filter area, serviceability, capacity, and
cabinet geometry. Air is discharged vertically through grilles mounted on the top face of the
enclosure. Controls and water valves are typically located in the enclosure, with access from the
room for maintenance.
Vertical, high-output fan-coil units are designed for larger spaces or multiple rooms. The units are
typically located in a closet, where a door allows easy access. Ducted discharge air supplies
multiple outlets located throughout the space. The return is typically located near the floor of the
closet and may or may not be ducted. Typically, one thermostat controls the air temperature supplied
to all the spaces served.
Vertical stack fan-coil units, as depicted in Figure 8, are typically mounted
in walls of or vertical chases in the conditioned space, such as near the window of a hotel or dorm
room. Air is discharged into the space from high sidewall grilles or ducted to outlets throughout
the zone. Multiple stack units may be connected to a common set of risers to serve adjacent spaces.
The pipes can be in a cavity protected by fire-rated partitions separating multiple adjacent zones.
Floor-to-floor, vertical stack fan-coil units are typically supplied with chilled- and/or hot-water
risers and return downcomers, and a condensate downcomer. VRF versions are available too, as are
water-cooled heat pumps units. Vertical stack fan-coils with integral prefabricated risers located
directly above one another can reduce installation labor and time. Evaluation of floor-to-floor
centerlines is critical for riser and unit heights.
Horizontal Units. Horizontal overhead units may be concealed or exposed,
and some have discharge or return ducts. Discharge ducts may supply several outlets in one or more
rooms. Ducted units must be designed to handle higher external static pressure. Horizontal models
conserve floor space, but when located in furred ceilings, consideration should be given to access
and condensate removal. This type of fan-coil is oft-used, for example, in plenums over hallways in
hotels, apartments, and condominiums. The cooling is most often a DX split-system, and heating is
heat pump or electric resistance. Minisplit and VRF versions are available too.
Figure 9 shows a typical
low-profile horizontal fur-down fan-coil unit. Horizontal fur-down units are generally less than
280 mm in height and mounted in a fur-down below the ceiling level or in a soffit area.
The return is nonducted, typically through filter-return grilles; the interstitial area of the
soffit is the return plenum, which otherwise must be very well sealed. Supply air is typically
ducted to one or more two-way high-sidewall supply grilles. Horizontal fan-coil types are generally
used in space-constrained applications. A variation of the horizontal furdown unit includes a larger
return plenum, which has filter-frame accommodations and may be ducted to a return grille. The
addition of a return plenum with an externally finished cabinet allows the fan-coil unit to be
installed below the ceiling.
High-capacity, horizontal fan-coil units are generally up to 460 mm in height and
mounted above the ceiling in a return air plenum. These models have a higher capacity than fur-down
low-profile units, and generally serve multiple rooms with a ducted supply. The unit may have
multiple plenum arrangements, like fur-down models do, but the interstitial area is typically the
return plenum.
Underfloor Fan Coils. This fan-coil is like an underfloor
fan-powered terminal, but it includes a cooling coil to boost the cooling load at the perimeter of
zones or, for example, in conference rooms with raised floors. Another use may be in staircases or
podiums. If the cooling coil is designed to condense water vapor when operating, care must be taken
to provide for adequate drainage. Condensate pumps may be required. These fan-coils are available in
several unit sizes, but with limited height and width to fit under the raised floor.
For fan-coil applications in raised floors, typically either the supply or return air is ducted, and
thus the plenum is used for unducted flow of the other. The plenum must, therefore, be very well
sealed so that air does not leak in or out of unintended places; alternatively, both the supply and
return can be ducted and well sealed. In all cases, the control system must have the proper damper
sequence to control room air distribution to maintain the proper conditions in the occupied space.
Maintenance. Fan-coil systems require maintenance, which
is generally done via the occupied areas. Unit accessibility is important for inspections and when
performing routine maintenance such as filter replacement, coil and drain cleaning, and motor
servicing. Large fire-rated hatches may be required when units are placed in small plenums, for
example. When above suspended ceilings, the movable ceiling tiles may provide adequate access and
fire rating.
Chilled-beam systems are designed to address most or all the zone’s sensible heat gains or
losses locally using water, allowing the flow rate of preconditioned air from the air-handling unit
to be reduced to maintain only the required latent cooling and ventilation of the space. This often
results in ducted design airflow rate reductions of 60 to 80%, and thus similar reductions in air
distribution equipment capacity requirements. Chilled-water supply temperatures are maintained at or
above the room air dew point to prevent condensation on the beam heat transfer coil(s). The zone
must be very well sealed and air pressure differential optimized continuously to effectively
eliminate infiltration of uncontrolled humid air. Chilled-beam systems perform the following
functions:
-
Temperature control (sensible cooling and heating)
-
Latent cooling (when using drain pans or inductions units)
-
Room air distribution
-
Ventilation (active chilled beams)
-
Humidity control (active chilled beams)
Beam Types and Configurations
Active beams, as shown in Figure 10A are induction
terminals that consist of a primary air duct connection, a series of induction nozzles, hydronic
heat transfer coil(s), supply outlet(s), and induced air inlet section(s). Primary air,
discharged through the induction nozzles, creates a lower-pressure region that induces room air
through the chilled- and/or hot-water coil(s). The room air is conditioned before being mixed
with primary air, and then the mixture of primary and conditioned induced air is then discharged
to the space. This mixture’s temperature and/or flow rate is modulated in accordance with
the space demand and control strategy. Active chilled beams are available in the following
configurations:
-
Linear (one-way or two-way discharge)
-
Modular (four-way discharge)
-
Recessed
-
Floor mounted or cabinet style
-
Induction units (with integral drain pans)
Active beams, when properly applied, generally produce fully mixed room air distribution,
although displacement ventilation versions (cabinet style) are available as well. Their air
distribution characteristics depend on the beam’s supply outlet configuration, like those
described in Table 1. Most
active beams use linear slots on their discharge, and room air distribution is therefore
characteristic of that outlet type because the induced air produces significant supply air
velocity. The following piping configurations are generally used:
Cooling-only active beams use two pipes (supply and return) to their coils. Active beams can also
be used for overhead heating; when applied as such, the beams are typically provided with
four-pipe combined coils. These beams’ coils have a common fin stack, but the tubing that
passes through the stack is dedicated to either cooling or heating. In most cases, 75% of the
tube passes are dedicated to cooling, and 25% are supplied hot water. The water flow rate
through either circuit is varied by zone chilled- and/or hot-water control valves that are
modulated the zone temperature sensor.
Where both heating and cooling are needed but two-pipe beams are used, six-port control valves
can be effective. These valves incorporate four supply and return ports for both chilled and hot
water. They then determine the water source that is required and modulate the flow to and from
one or more two-pipe beams through a shared local two-pipe system. This can considerably reduce
zone piping costs and allow the use of more efficient two-pipe circuitry in the beam heat
transfer coils; however, it loses the ability to heat or cool each beam individually, if jointly
connected on a local two-pipe system.
Overhead beams, if so designed, may be used in suspended or finished ceilings, or independently
mounted below. Although active beams are usually installed in the upper part of the space, they
can also be located in sidewalls or at floor level, with their supply air delivered at high or
low velocity, depending on the air distribution strategy (mixing or displacement) that is
desired. Both active and passive chilled beams can be integrated with additional services (e.g.,
lighting or fire protection) as required.
Passive beams, as shown in Figure 10B, consist of a
sensible cooling coil and a casing, and can be fitted into an architectural enclosure when
exposed. They provide space sensible cooling mainly by negative-buoyancy-driven natural
convection: the coil provides heat exchange between the chilled water and the induced room air.
When cool water is circulated through the coil, room air between the fins is cooled and falls
naturally into the room. Displaced room air then pushes air through the beam’s coil.
There are two basic types of passive beams: exposed and recessed. Exposed passive beams are
commonly used in spaces without suspended ceilings (i.e., in rooms with either finished or no
ceilings).
Recessed passive beams are generally integrated into a suspended ceiling. When passive beams are
installed in such a ceiling, a minimum clearance between the top of the beam and any surface
above it should be provided to ensure a sufficient return air path. Generous shadow gaps, dummy
beam sections, and/or return or transfer grilles are recommended for creating the near-zero
pressure loss return air path from the room to the plenum.
Passive beams cannot be used effectively for heating spaces below them due to positive air
buoyancy. Instead, a decoupled heating system (e.g., low-level finned tube or radiant panels or
floors) is commonly used. However, the passive beams may be used at times to intentionally warm
the plenum or floor above them somewhat, for comfort or freeze protection.
Space ventilation and dehumidification must be provided by a complementary air delivery system.
Air delivery systems that promote fully stratified or partially mixed air distribution when in
cooling mode are often preferred, because passive beams mounted high operate more efficiently in
thermally stratified environments.
Additional information on active and passive beams can be found in Woollett and Rimmer (2014) and
Chapter 58 of the 2023 ASHRAE Handbook—HVAC Applications.
Air curtain units (ACUs) are local devices that supply high-velocity planar airstreams that act as
controlled barriers for environmental and thermal separation, as well as for resisting wind when a
building’s doors or windows are open.
When used as an environmental separation barrier, an ACU minimizes migration of gaseous or
particulate contaminants, deters flying insects, and may convey contaminants toward local exhaust.
As a thermal barrier, the ACU reduces cross migration of warm, lighter air flowing through the upper
part of the opening and cold, heavier air flowing through the lower part of the opening. As a wind
resistance barrier, it minimizes the effect of outdoor air blowing into a building’s openings.
An ACU can reduce the energy consumption of HVAC systems when areas of different temperatures need
separating, but physical barriers such as walls or doors cannot be used at certain or all times. ACU
energy effectiveness is defined by the amount of energy saved (i.e., the energy loss through an
opening prevented with an ACU) divided by the amount of energy that would have been lost without,
represented as a percentage. The cost effectiveness can be calculated similarly. Research has
demonstrated that air curtains can range in energy effectiveness from 60 to 90%, depending on the
type of unit and application (Costa et al. 2006; Giráldez et al. 2013). See Chapter 58 of the
2023 ASHRAE Handbook—HVAC Applications for more
information.
ACUs are constructed of a motor and fan, or a system of motors and fans, mounted inside a cabinet,
and a specialized plenum for discharge. Air is drawn in through either a ducted or nonducted intake,
specified with or without a filter, and discharged at a high velocity as an air curtain; this air
curtain is sometimes referred to as the ACU airstream.
The unit is normally mounted above or beside a door or window opening. Discharge across the opening
is either vertical, when the unit is mounted above the opening, or horizontal, when the unit is
mounted beside the opening. Due to fluid mechanics, air is entrained and mixed, from both sides,
into the curtain. Thus, the direction of the jet produced is important, and is often adjustable or
even actively controlled.
Unit Types and Configurations. ACUs are classified by two
different types of construction: non-recirculating and recirculating. The major differences between
the two systems are the airflow path, cabinet construction, range of effectiveness, and purchase and
installation costs.
A non-recirculating system draws air into the unit
directly from typically one indoor environment and is available in both horizontal and vertical
applications; horizontal-mount, vertical-down discharge is depicted in Figure
11. An air curtain equipped with inlet ductwork that draws air from outdoors only is also
considered to be nonrecirculating. This configuration is recommended for doorways that open
frequently (e.g., 10 times or more per hour). Flying insect control applications use this type of
unit exclusively because of its ability to generate a high-velocity airstream. It is the most common
system for environmental separation because of its low initial purchase and installation costs.
Nonrecirculating systems are typically used for special applications, due to their flexibility in
construction and installation.
A recirculating system draws air from ductwork, which
collects and returns much of the discharge air as well as entrained air to the ACU’s inlet as
shown in Figure
12. Applications often use a plenum with a floor return grille that is connected to the
ACU’s inlet with ductwork. An alternative construction includes horizontal flow, which
discharges and returns from side to side. These systems are recommended for doorways that are opened
for extended periods of time, with a high rate of traffic. Although its effectiveness rating is
higher, this system is only suitable for thermal separation applications. Recirculating systems use
lower velocities and are perceived as less obtrusive than non-recirculating systems.
Non-recirculating systems are normally self-contained systems that can be easily installed or
retrofitted to existing openings with minimal planning and changes to the opening and its sequence
of operation. Recirculating systems require preplanning and comprise a combination of components,
including discharge and return plenums, which require integration into the construction of the
opening and its sequence of operation.
The typical range of energy effectiveness for non-recirculating systems is 60 to 80%, whereas
recirculating systems range between 80 to 90% (Costa et al. 2006; Giráldez et al. 2013).
Non-recirculating systems also have a relatively low purchase and installation cost; recirculating
systems can have significantly higher installed cost.
Optional features available for both ACU types include heating, cooling, filters, and special
controls. Special casing materials and/or coatings may be required for outdoor mounting or harsh
environmental applications.
The availability of integrated heating and/or cooling options depends on the intended application and
cabinet construction requirements. Note that a heating or cooling option will not improve the air
curtain’s effectiveness; this serves as an enhancement to the application, independent of the
protection provided by the airstream. A heat source may be added for local supplemental heat to
reduce the windchill effect of the air curtain.
The most common heating types are
-
Electric heating coils: open (helical) or fin-tube element
-
Hydronic coil: hot water or steam
-
Indirect gas-fired: furnace uses heat exchanger to separate combustion air from heated
air curtain
-
Direct gas-fired: burner fires directly into airstream being heated, so may not be
acceptable for certain occupancies
-
DX evaporator coil: direct-expansion vapor compression refrigeration cycle system
Cooling options are used for the same general reasons as the heating options: occupant comfort,
supplemental cooling, or dehumidifying. Special care is needed in cooling applications to remove the
condensate generated in the cooling apparatus, also accounting for the higher face velocities across
the coil so as not to blow water droplets off the coil. The most common types are
Factors That Influence Selection. ACUs are typically
considered for four different applications:
-
Energy savings: indoor applications where doors or windows are used for pedestrian
traffic or the transporting of goods where they would be open long enough to impact the
designed load of the HVAC system. Examples include front or customer entry doors,
loading docks, service windows, ovens, and coolers or freezers.
-
Insect control (sanitation): indoor applications where doors or unscreened open windows
could allow entrance of flying insects that would create an unsanitary environment.
-
Code requirements: buildings that are being constructed to meet a jurisdictional code
requirement.
-
Process/special application: applications where the separation of two distinct
environments is required to prevent cross contamination, fume/odor control, or a process
that requires a direct stream of air to accomplish a specified task. Examples include
cleanrooms, car washes, and assembly line drying or cooling by convection.
Chapter 58 of the 2023 ASHRAE Handbook—HVAC Applications provides
details on these categories.
Product Selection. ACU selection depends on the width of
the opening and installation height. To maximize effectiveness, the ACU must cover at a minimum the
entire opening, and if possible should slightly overlap the opening’s frame. On wide openings,
two vertically mounted, low-air-velocity units can be used as an alternate solution to a single
horizontally mounted, high-air-velocity unit. The ACU discharge must have a free and clear path to
the entire opening for optimal performance.
Recent studies suggest that the minimum air velocity required at the floor to create an effective
barrier is 2 m/s (Yang et al. 2019). When selecting air curtains, commercially
available products are offered and designed specifically based on the opening size and application.
Manufacturers’ performance data should be consulted to determine the suitability of the ACUs
used. Data to determine ACU performance should be obtained from recognized test standards such as
ANSI/AMCA Standard 220.
Controls. ACU controls are essential to provide the
correct air curtain velocity, temperature, and depth. They are also used to prevent unnecessary
energy usage and overconditioning or overpressurizing the building entrance. Although supplemental
heating and/or cooling can be provided by a so-equipped air curtain unit, it should not be seen as
the primary source for conditioning internal areas. If an ACU is used for supplemental heating or
cooling, the energy consumed during these control sequences should not be considered in the
effectiveness rating of the unit. For convenience, user-operated controls are typically unit-mounted
and configured to satisfy the building occupants’ needs. To meet design, access, or security
requirements, optional remote-mounted controls may be available. At the simplest level of control,
only manual operation of the fan speed and heat output may be required. However, additional control
options include
The control unit may also have outputs for signaling failures or provide communication between the
ACUs and the central control system (e.g., BMS, BAS, emergency management system [EMS]). ACUs can be
equipped with controls as simple as a mechanical multispeed switch, or as sophisticated as an
integrated interface with a touchpad or LCD panel. The LCD panel can control values such as
discharge speed, heating/cooling status, indoor/outdoor set-point temperatures, failure reporting,
and filter contamination level.
Maintenance. ACUs typically require biannual maintenance,
depending on the application. Some designs may have motors and bearings that require periodic
lubrication. Many designs use permanently sealed bearings instead. ACUs require only occasional
cleaning of the blower impeller(s), cabinet interior, and heating apparatus, as well as filter
cleaning or replacement if so equipped.
ASHRAE members can access ASHRAE Journal articles and ASHRAE research project
final reports at technologyportal.ashrae.org. Articles and reports are also available for purchase
by nonmembers in the online ASHRAE Bookstore at www.ashrae.org/bookstore.
Asker, G.S.F. 1970. What, where and how of air curtain
systems. Heating, Piping and Air Conditioning (June).
AMCA. 2021. Laboratory methods of testing air curtains
for aerodynamic performance ratings. ANSI/AMCA Standard
220-21.
AMCA. 2017. Application manual for air curtain units.
AMCA Standard 222-16.
ASHRAE. 1996. Cold air distribution
system design guide.
ASHRAE. 2013. UFAD guide: Design,
construction and operation of underfloor air distribution.
ASHRAE. 2023. Thermal environmental conditions for human
occupancy. ANSI/ASHRAE Standard 55-2023.
ASHRAE. 2022. Ventilation for acceptable indoor air
quality. ANSI/ASHRAE Standard 62.1-2022.
ASHRAE. 2022. Energy standard for buildings except
low-rise residential buildings. ANSI/ASHRAE/IES Standard
90.1-2022.
Bauman, F. 2003. Underfloor air
distribution design guide. ASHRAE.
Bintzer, W., and F.A. Malehom. 1976. Air curtains on
electric arc furnaces at Lukens Steel Co. Iron and Steel Engineer
(July):53-55.
Chen, Q.Y., and L. Glicksman. 2003. System performance evaluation and design guidelines for displacement
ventilation. ASHRAE.
Costa, J.J., L.A. Oliviera, and M.C.G. Silva. 2006.
Energy savings by aerodynamic sealing with a downward-blowing plane air curtain: A numerical
approach. Energy and Buildings 38(10):1182-1193.
Davis, M., J.A. Bryant, D.L. O’Neal, A. Hervey,
and A. Cramlet. 2007. Comparison of the total energy consumption of series versus parallel fan
powered VAV terminal units, phases I and II. ASHRAE Research Project
RP-1292.
Giráldez H., C.D. Pérez Segarra, I.
Rodriguez, and A. Olivia. 2013. Improved semi-analytical method for air curtains prediction.
Energy and Buildings 66:258-266.
Goodfellow, H.D. 1985. Advanced
design of ventilation systems for contaminant control. Elsevier Science, B.V.,
Amsterdam.
Ivanitskaya, M.Y., A.S. Strongin, and E.A. Visotskaya.
1986. Studies of the air curtain application for the channel of the localizing ventilations.
Proceedings of Heating and Ventilation, TsNIIpromzdanii
(Moscow).
Landsberger, B., Z. Poots, and D. Reynolds. 2011.
Effects of typical inlet conditions on air outlet performance. ASHRAE Research Project RP-1335,
Final Report.
Posokhin, V.N. 1985. Design of
local ventilation systems for the process equipment with heat and gas release.
Mashinostroyeniye, Moscow (in Russian).
Posokhin, V.N., and V.A. Broida. 1980. Local exhausts incorporated with air curtain: Hydromechanics and heat
transfer in sanitary technique equipment. KNTI, Kazan (in Russian).
Powlesland, J.W. 1971. Air curtains. Canadian Mining Journal (October): 84-93.
Powlesland, J.W. 1973. Air curtains in controlled energy
flows. American Conference of Industrial Hygienists.
Rock, B.A., and D. Zhu. 2002. Designer’s guide to ceiling-based air diffusion. ASHRAE.
Skistad, H., E. Mundt, P. Nielsen, K. Hagström, and
J. Railio. 2002. Displacement ventilation in non-industrial premises. REHVA Guidebook 1. Federation of European Heating and Air-Conditioning
Associations, Brussels.
Stoler, V.D., and Y.L. Savelyev. 1977. Push-pull systems
design for the etching tanks. Heating, Ventilation, Water Supply, and
Sewage Systems Design 8(124). TsINIS, Moscow (in Russian).
Stroiizdat. 1992. Design manual:
Ventilation and air conditioning, 4th ed. Part 3(1). Stroiizdat, Moscow (in
Russian).
Strongin, A.S. 1993. Aerodynamic protection of hangars
against cold ingress through apertures. Building Services Engineering
Research and Technology 14(1).
Strongin, A.S., and M.V. Nikulin. 1991. A new approach
to the air curtain design. Construction and Architecture—Izvestiya
VUZOV (January):84-87 (in Russian).
UL. 2015. Heating and cooling equipment. ANSI/UL Standard 1995-2015. Underwriters Laboratory, Northbrook, IL.
Wang, L., and Z. Zhong. 2014. An approach to determine
infiltration characteristics of building entrance equipped with air curtains. Energy and Buildings 75:312-320.
Woollett, J., and J. Rimmer. 2014. Active and passive beam application design guide. ASHRAE and
Federation of European Heating, Ventilation and Air Conditioning Associations (REHVA),
Brussels.
Yang, S., H. Alrawashdeh, C. Zhang, D. Qi, and T.
Stathopoulos. 2019. Wind effects on air curtain performance at building entrances. Building and Environment 151(15):75-87.