Liquid-chilling systems cool water, brine, or other secondary coolant for
air conditioning or refrigeration. The chiller may be either factory-assembled and wired or shipped in
sections for erection in the field. The most frequent application is water chilling for building air
conditioning, although brine cooling for low-temperature refrigeration and chilling fluids in industrial
processes are also common. The heat that is removed from the chilled liquid along with the heat from the
compressor work input is typically rejected by the condenser into an air or water heat sink.
Alternatively, that heat can be used for beneficial building or process heating, in which case the
chiller is referred to as a heat pump or simply a heater.
The basic components of a vapor-compression chiller include one or more compressor(s), liquid cooler
(evaporator), condenser, compressor drive(s), liquid-refrigerant expansion or flow-control device, and
control center. It may also include a receiver, economizer, expansion turbine, and/or subcooler. In
addition, auxiliary components may be used, such as a lubricant cooler, lubricant separator,
lubricant-return device, purge unit, lubricant pump, refrigerant transfer unit, refrigerant vents,
and/or additional control valves.
For information on absorption equipment, see Chapter 18 of the 2022 ASHRAE
Handbook—Refrigeration.
1. GENERAL
CHARACTERISTICS
1.1 PRINCIPLES OF OPERATION
Liquid (usually water or water/glycol mixture) enters the cooler, where it is chilled by liquid
refrigerant evaporating at a lower temperature. The refrigerant evaporates as it absorbs heat from
the liquid and is drawn into the compressor. The compressor performs work on the refrigerant gas,
which increases the pressure and temperature so that it may reject the evaporator heat and heat of
compression to the cooling medium in the condenser. The condenser cooling medium, typically water,
is heated in the process. The condensed liquid refrigerant then flows back to the evaporator through
an expansion device, where some of the liquid refrigerant changes to vapor (flashes) as pressure
drops. Flashing cools the liquid to the saturated temperature at evaporator pressure. The following
modifications (sometimes combined for maximum effect) reduce flash gas and increase the net
refrigeration per unit of power consumption.
Subcooling.
Condensed refrigerant may be subcooled below its saturated condensing temperature in either the
subcooler section of a water-cooled condenser or a separate heat exchanger. Subcooling reduces
flashing and increases the refrigeration effect in the chiller.
Economizing.
This process can occur either in a direct-expansion (DX), an expansion turbine, or a flash system.
In a DX
system, the main liquid refrigerant is usually cooled in the shell of a
shell-and-tube heat exchanger, at condensing pressure, from the saturated condensing temperature to
within several degrees of the intermediate saturated temperature. Before cooling, a small portion of
the liquid flashes and evaporates in the tube side of the heat exchanger to cool the main liquid
flow. Although subcooled, the liquid is still at the condensing pressure.
An expansion turbine extracts rotating
energy as a portion of the refrigerant vaporizes. As in the DX system, the remaining liquid is
supplied to the cooler at intermediate pressure.
In a flash
system, the entire liquid flow is expanded to intermediate pressure in a
vessel that supplies liquid to the cooler at saturated intermediate pressure; however, the liquid is
at intermediate pressure.
Flash gas enters the compressor either at an intermediate stage of a multistage centrifugal
compressor, at the intermediate stage of an integral two-stage reciprocating compressor, at an
intermediate pressure port of a screw compressor, or at the inlet of a high-pressure stage on a
multistage reciprocating or screw compressor.
Liquid Injection. Condensed liquid is throttled to the
intermediate pressure and injected into the second-stage suction of the compressor to prevent
excessively high discharge temperatures and, in the case of centrifugal machines, to reduce noise.
For screw compressors, condensed liquid is injected into a port fixed at slightly below discharge
pressure to provide lubricant cooling.
1.2 COMMON LIQUID-CHILLING SYSTEMS
The refrigeration components of a basic water-cooled chiller are shown in Figure 1. Chilled
water enters the cooler at 14°C, for example, and leaves at
6°C. Condenser water leaves a cooling tower at 30°C, enters
the condenser, and returns to the cooling tower near 38°C. Condensers may also
be cooled by air or evaporation of water. This system, with a single compressor and one
refrigerant circuit with a water-cooled condenser, is used extensively to chill water for air
conditioning because it is relatively simple and compact.
A multiple-chiller system has two or more chillers connected by parallel or series piping to a
common chilled-liquid distribution system. Multiple chillers offer operational flexibility,
standby capacity, and less disruptive maintenance. The chillers can be sized to handle a base
load and increments of a variable load to allow each chiller to operate at its most efficient
point.
Multiple-chiller systems offer some standby capacity if repair work must be done on one chiller.
Using multiple smaller chillers rather than one larger chiller may reduce starting in-rush
current as well as power costs at partial-load conditions. Maintenance can be scheduled for one
chiller during part-load times, and sufficient cooling can still be provided by the remaining
unit(s). These advantages require an increase in installed cost and space, however.
Traditionally, flow was held constant through the chillers for stable control. Today, variable-flow chilled-water systems are
preferred in many applications to achieve plant energy and first-cost savings. Chillers selected
for these applications should be capable of turning the chilled-liquid flow down to at least 60%
of the design flow to ensure intended pumping energy savings can be achieved. Both variable-flow
and primary/secondary hydronic systems are discussed in further detail in Chapter 13.
In the parallel arrangement, when design chilled-water temperature is above about
7°C, all units should be controlled by the combined exit liquid temperature or
by the return water temperature (RWT), because overchilling will not cause dangerously low water
temperature in the operating machine(s). Chilled-water temperature can be used to cycle one unit
off when it drops below a capacity that can be matched by the remaining units.
When the design chilled-water temperature is below about 7°C, each machine
should be controlled by its own chilled-water temperature, both to prevent dangerously low
evaporator temperatures and to avoid frequent shutdowns by low-temperature cutout. The
temperature differential setting of the RWT must be adjusted carefully to prevent short-cycling
caused by the step increase in chilled-water temperature when one chiller is cycled off. These
control arrangements are shown in Figures
2 and 3.
In the series arrangement, the evaporator vessel must
handle the entire system flow in both chillers, so they should be selected with the combined
pressure drop in mind. No overchilling by either unit is required, and compressor power
consumption is lower than for the parallel arrangement at partial loads. Each chiller provides
part of the overall system temperature differential. Because the first chiller operates at a
higher evaporator temperature (meaning lower lift), it operates more efficiently than the second
chiller, thereby improving overall system efficiency. In addition, because evaporator
temperature never drops below the design value (because no overchilling is necessary), the
chances of evaporator freeze-up are minimized. However, the chiller should still be protected by
a low-temperature safety control. If operating flexibility, standby capacity, or ability to
operate on one chiller during maintenance of the other are desired, the piping must be arranged
such that all flow can bypass either chiller and the system can operate on the non-bypassed
chiller. This means that each chiller should be specified to be able to provide the overall
system temperature differential.
If the condenser water side of the chillers is to be designed in series, the condensers are best
piped in a counterflow arrangement so that the first machine is provided with warmer condenser
and chilled water and the second machine is provided with colder entering condenser and chilled
water. Refrigerant compression for each unit is nearly the same. If about 55% of design cooling
capacity is assigned to the first machine and about 45% to the second machine, identical units
can be used. In this way, either machine can provide the same standby capacity if the other is
down, and the machines may be interchanged to equalize the number of operating hours on each.
A control system for two machines in series is shown in Figure
4. Both units are modulated to a certain capacity; then, one unit shuts down, leaving
less than 100% load on the operating machine.
One machine should be shut down as soon as possible, with the remaining unit carrying the full
load. This not only reduces the number of operating hours on a unit, but also leads to less
total power consumption because the coefficient of performance (COP) tends to decrease below
full-load value when unit load drops much below 50%.
The largest factor that determines total liquid chiller owning cost is the cooling load size;
therefore, the total required chiller capacity should be calculated accurately. The practice of
adding 10 to 20% to load estimates is unnecessary because of the availability of accurate load
estimating methods, and it proportionately increases costs of equipment purchase, installation, and
the poor efficiency resulting from wasted power. Oversized equipment can also cause operational
difficulties such as frequent on/off cycling or surging of centrifugal machines at low loads. The
penalty for a small underestimation of cooling load, however, is not serious. On the few design-load
days of the year, increased chilled-liquid temperature is often acceptable. However, for some
industrial or commercial loads, a safety factor can be added to the load estimate.
Use the life-cycle cost (discussed in Chapter 38 of
the 2023 ASHRAE Handbook—HVAC Applications) to minimize overall
purchase and operating costs. Total owning cost is comprised of the following:
-
Equipment price. Each machine type and/or
manufacturer’s model should include all necessary auxiliaries such as starters and
vibration mounts. If these are not included, their price should be added to the base
price. Include associated equipment, such as condenser water pump, tower, and piping.
-
Installation cost. Factory-packaged machines
are both less expensive to install and usually considerably more compact, thus saving
space. The cost of field assembly must also be evaluated.
-
Energy cost. Using an estimated load schedule
and part-load power consumption curves furnished by the manufacturer, a year’s
energy cost should be calculated.
-
Water cost. With water-cooled towers, the cost
of acquisition, water treatment, tower blowdown, and overflow water should be included.
-
Maintenance cost. Each bidder may be asked to
quote on a maintenance contract on a competitive basis.
-
Insurance and taxes.
-
Regulatory/codes. Changes in regulations could
require replacement of chiller fluids, upgrades of electronics, or improvements in
efficiencies.
For packaged chillers that include heat recovery, system cost and performance should be compared in
addition to equipment costs. For example, the heat recovery chiller installed cost should be
compared with the installed cost of a chiller plus a separate heating system. Also consider the
following factors: (1) energy costs, (2) maintenance requirements, (3) life expectancy of equipment,
(4) standby arrangement, (5) relationship of heating to cooling loads in terms of size and
concurrence, (6) effect of package selection on sizing, and (7) type of peripheral equipment.
Condensers and coolers are often available with either liquid
heads, which require water
pipes to be disconnected for tube access and maintenance, or marine-type water
boxes, which allow tube access with water piping intact. The liquid head is
less expensive. The cost of disconnecting piping must be greater than the additional cost of
marine-type water boxes to justify using the latter. Typically, an elbow and union or flange
connection can be installed immediately next to liquid heads to facilitate removing heads. By making
sure that all specialty piping components (valves, controls, strainers, etc.) fall outside the tube
bundle boundary, the liquid heads can be removed with minimal pipe disassembly.
Figure
5 shows types of liquid chillers and their ranges of capacities.
For air-cooled condenser duty, brine chilling, or other high-pressure applications from 280 to
about 700 kW, scroll and screw liquid chillers are more frequently installed than
centrifugals. Centrifugal liquid chillers (particularly multistage machines), however, may be
applied quite satisfactorily at high pressures.
Advancements in technology, refrigerants, and manufacturer offerings all affect which compression
technology is best suited for a given liquid chiller application. Centrifugal packages are typically
available to about 12 MW, and field-assembled machines to about 35 MW.
The chilled-liquid temperature sensor sends an air
pressure (pneumatic control) or electrical signal (electronic control) to the control circuit,
which then modulates compressor capacity in response to leaving or return chilled-liquid
temperature change from its set point. This control also applies to chillers used for heat
recovery. Chillers used exclusively for heating use the leaving or return condenser cooling
medium temperature to modulate the compressor capacity. The method of compressor capacity
modulation varies depending on the type of liquid chillers:
Scroll and reciprocating chillers use combinations of
involute/cylinder unloading and on/off compressor cycling of single or multiple compressors.
Centrifugal liquid chillers, driven by electric
motors, commonly use adjustable prerotation
vanes, which are sometimes combined with movable diffuser walls. Turbine and engine drives and
inverter-driven, variable-speed electric motors
allow use of speed control in addition to prerotation vane modulation, reducing power
consumption at partial loads.
Screw compressor liquid chillers include a slide valve
that adjusts the length of the compression path. Inverter-driven, variable-speed electric
motors, turbines, and engine drives can also modulate screw compressor speed to control
capacity.
In air-conditioning applications, most centrifugal and screw compressor chillers modulate from
100% to approximately 10% load. Although relatively inefficient, hot-gas bypass can be used to
reduce capacity to nearly 0% with the unit in operation.
Reciprocating chillers are available with simple
on/off cycling control in small capacities and with multiple steps of unloading down to 12.5% in
the largest multiple-compressor units. Most intermediate sizes provide unloading to 50, 33, or
25% capacity. Hot-gas bypass can reduce capacity to nearly 0%.
The water temperature controller is a thermostatic
device that unloads or cycles the compressor(s) when the cooling load drops below minimum unit
capacity. An anti-recycle timer is sometimes used to
limit starting frequency.
On centrifugal or screw compressor chillers, a current
limiter or demand limiter
limits compressor capacity during periods of possible high power consumption (such as pulldown)
to prevent current draw from exceeding the design value; such a limiter can be set to limit
demand, as described in the section on Centrifugal Liquid Chillers.
Controls That Influence the Liquid Chiller
Condenser cooling water may need to be controlled to avoid falling below the manufacturer’s
recommended minimum limit, to regulate condenser pressure. Normally, the temperature of water
leaving a cooling tower can be controlled by fans, dampers, or a water bypass around the tower.
Tower bypass allows water velocity through the condenser tubes to be maintained, which prevents
low-velocity fouling.
A flow-regulating valve is another common means of control. The orifice of this valve modulates
in response to condenser pressure. For example, reducing pressure decreases water flow, which,
in turn, raises condenser pressure to the desired minimum level.
For air-cooled or evaporative condensers, compressor discharge pressure can be controlled by
cycling fans, shutting off circuits, or flooding coils with liquid refrigerant to reduce heat
transfer.
A reciprocating chiller usually has a thermal expansion valve, which requires a restricted range
of pressure to avoid starving the evaporator (at low pressure).
An expansion valve(s) usually controls a screw compressor chiller. Cooling tower water
temperature can be allowed to fall with decreasing load from the design condition to the chiller
manufacturer’s recommended minimum limit.
Screw compressor chillers above 525 kW may use flooded evaporators and evaporator
liquid refrigerant controls similar to those used on centrifugal chillers.
A thermal expansion valve may control a centrifugal chiller at low capacities. Higher-capacity
machines may use a pilot-operated thermal control valve, an electronically controlled valve,
fixed orifice(s), a high-pressure float, or even a low-side float valve to control refrigerant
liquid flow to the cooler. These latter types of controls allow relatively low condenser
pressures, particularly at partial loads. Also, a centrifugal machine may surge if pressure is
not reduced when cooling load decreases. In addition, low pressure reduces compressor power
consumption and operating noise. For these reasons, in a centrifugal installation, cooling tower
water temperature should be allowed to fall naturally with decreasing load and wet-bulb
temperature, except that the liquid chiller manufacturer’s recommended minimum limit must
be observed.
Older systems often used dedicated control devices for each function of the chiller. Modern
chiller systems typically use a microprocessor control center that can handle many control
functions at once and can combine several control points into a single sensor. Some or all of
the following safety algorithms or cutouts may be provided in a liquid-chilling package to stop
compressor(s) automatically. Cutouts may be manual or automatic reset.
-
High condenser pressure. This pressure
switch opens if the compressor discharge pressure exceeds the allowable limit. It is
usually a dedicated pressure switch that interrupts the chiller main run circuit to
ensure a positive shutdown in an overpressure situation.
-
Low refrigerant pressure (or temperature).
This device opens when evaporator pressure (or temperature) reaches a minimum safe
limit.
-
High lubricant temperature. This device
protects the compressor if loss of lubricant cooling occurs or if a bearing failure
causes excessive heat generation.
-
High motor temperature. If loss of motor
cooling or overloading because of a failure of a control occurs, this device shuts
down the machine. It may consist of direct-operating bimetallic thermostats,
thermistors, or other sensors embedded in the stator windings; it may be located in
the discharge gas stream of the compressor.
-
Motor overload. Some small,
reciprocating-compressor hermetic motors may use a directly operated overload in the
power wiring to the motor. Some larger motors use pilot-operated overloads.
Centrifugal and screw-compressor motors generally use starter overloads or
current-limiting devices to protect against overcurrent.
-
Magnetic bearing overload. Magnetic
bearings are designed to sustain mechanical loads up to an electromagnetic
threshold. Thermal, current, or proximity sensing devices are typically used along
with associated controls to limit operation and protect the bearings. Sleeve or
rolling element bearings are also typically provided in the bearing package to
sustain dynamic forces during shutdown sequences.
-
Low lubricant sump temperature. This
switch is used either to protect against lubricant heater failure or to prevent
starting after prolonged shutdown before lubricant heaters have had time to drive
off refrigerant dissolved in the lubricant.
-
Low lubricant pressure. To protect against
clogged lubricant filters, blocked lubricant passageways, loss of lubricant, or a
lubricant pump failure, a switch shuts down the compressor when lubricant pressure
drops below a minimum safe value or if sufficient lubricant pressure is not
developed shortly after the compressor starts.
-
Chilled-liquid flow interlock. This device
may not be furnished with the liquid-chilling package, but it is needed in external
piping to protect against cooler freeze-up in case the liquid stops flowing. An
electrical interlock is typically installed either in the factory or in the field.
Most chiller control panels include a terminal for field-connecting a flow switch.
-
Condenser water flow interlock. This
device, similar to the chilled-liquid flow interlock, is sometimes used in external
piping.
-
Low chilled-liquid temperature. Sometimes
called freeze protection, this cutout
operates at a minimum safe value of leaving chilled-liquid temperature to prevent
cooler freeze-up in the case of an operating control malfunction.
-
Relief valves. In accordance with ASHRAE
Standard 15, relief valves, rupture disks, or both, set
to relieve at shell design working pressure, must be provided on most pressure
vessels or on piping connected to the vessels. Fusible plugs may also be used in
some locations. Pressure relief devices should be vented outdoors or to the
low-pressure side, in accordance with regulations or the standard.
1.5 STANDARDS AND TESTING
AHRI Standard 550/590 provides requirements for rating and testing
liquid-chilling machines. ASHRAE Standard 90.1 sets requirements for
minimum efficiencies. Design and construction of refrigerant pressure vessels are governed by ASME
Boiler and Pressure Vessel Code, Section VIII, except when design
working pressure is 103 kPa (gage) or less (as is usually the case for R-514A
liquid-chilling machines). Water-side design and construction of a condenser or evaporator are not
within the scope of the ASME code unless design pressure is greater than 2070 kPa or
design temperature is greater than 99°C.
ASHRAE Standard 15 applies to all liquid chillers and new refrigerants on
the market. Requirements for equipment rooms are included. Methods for measuring unit sound levels
are described in AHRI Standard 575.
The following maintenance specifications apply to reciprocating, centrifugal, and screw chillers.
Equipment should be neither overmaintained nor neglected. Establish a preventive maintenance
schedule; items covered can vary with the nature of the application. The list is intended as a
guide; in all cases, the manufacturer’s specific recommendation should be followed.
-
Condenser water treatment: treatment is determined specifically for the condenser
water used.
-
Operating conditions: daily log sheets should be kept (either manually or
automatically) to indicate trends and provide advance notice of deteriorating
chillers.
-
Brine quality for concentration and corrosion inhibitor levels.
-
Leak check
-
Purge operation
-
System dryness
-
Lubricant level
-
Lubricant filter pressure drop
-
Refrigerant quantity or level
-
System pressures and temperatures
-
Water flows
-
Expansion valves operation
Regularly Scheduled Maintenance
-
Condenser and lubricant cooler cleaning
-
Evaporator cleaning on open systems
-
Calibrating pressure, temperature, and flow controls
-
Tightening wires and power connections
-
Inspection of starter contacts and action
-
Safety interlocks
-
Dielectric checking of hermetic and open motors
-
Tightness of hot gas valve
-
Lubricant filter and drier change
-
Analysis of lubricant and refrigerant
-
Seal inspection
-
Partial or complete valve or bearing inspection, as per manufacturer’s
recommendations
-
Vibration levels
Extended Maintenance Checks
-
Compressor guide vanes and linkage operation and wear
-
Eddy current inspection of heat exchanger tubes
-
Compressor teardown and inspection of rotating components
-
Other components as recommended by manufacturer
2. SCROLL AND
RECIPROCATING LIQUID CHILLERS
Components and Their Functions
Scroll and reciprocating compressors described in Chapter 38
are positive-displacement machines that maintain fairly constant-volume flow rate over a wide
range of pressure ratios. The following types of compressors are commonly used in
liquid-chilling machines:
-
Welded hermetic, to about 1055kW chiller capacity
-
Semihermetic, to about 700 kW chiller capacity
-
Direct-drive open, to about 1600 kW chiller capacity
Open motor-driven reciprocating liquid chillers are
usually more expensive than hermetically sealed units, but have an efficiency benefit of not
rejecting motor heat into the refrigeration cycle. Hermetic motors are generally
suction-gas-cooled; the rotor is mounted on the compressor crankshaft.
Condensers may be evaporative, air, or water cooled. Water-cooled versions may
be tube-in-tube, shell-and-coil, shell-and-tube, or plate heat exchangers. Most shell-and-tube
condensers can be repaired; others must be replaced if a refrigerant-side leak occurs.
Air-cooled condensers are much more common than evaporative condensers. Less maintenance is
needed for air-cooled heat exchangers than for the evaporative type. Remote condensers can be
applied with condenserless packages. (Information on condensers can be found in Chapter
39.)
Coolers
are usually direct expansion, in which
refrigerant evaporates while flowing inside tubes or plate channels and liquid is cooled as it
is guided in multiple passes over the outside of the tubes by shell-side baffles for shell and
tube heat exchangers, or as liquid flows in counterflow for plate heat exchangers. Flooded
coolers are sometimes used on industrial chillers. Flooded coolers maintain a level of
refrigerant liquid on the shell side of the cooler, while liquid to be cooled flows through
tubes inside the cooler. Tube-in-tube coolers are sometimes used with small machines; they offer
low cost when repairability and installation space are not important criteria. Chapter
42 describes coolers in more detail.
The thermal expansion valve, capillary, or other
device modulates refrigerant flow from the condenser to the cooler to maintain enough suction
superheat to prevent any unevaporated refrigerant liquid from reaching the compressor.
Excessively high values of superheat are avoided so that unit capacity is not reduced. (For
additional information, see Chapter 11 in the 2022 ASHRAE
Handbook—Refrigeration.)
Lubricant cooling is not usually required for air
conditioning. However, if it is necessary, a refrigerant-cooled coil in the crankcase or a
water-cooled cooler may be used. Lubricant coolers are often used in applications that have a
low suction temperature or high pressure ratio when extra lubricant cooling is needed.
Capacities and Types Available
Available capacities range from about 7 to 1600 kW. Multiple scroll and
reciprocating compressor units are popular for the following reasons:
-
The number of capacity increments is greater, resulting in closer liquid temperature
control, lower power consumption, less current in-rush during starting, and extra
standby capacity.
-
Multiple refrigerant circuits are used, resulting in the potential for limited
servicing or maintenance of some components while maintaining cooling.
R-410A has been the primary refrigerant used in scroll chiller applications. R-134a or R-407C is
frequently used in reciprocating chiller applications. R-134a or R-407C are suitable for both
open and hermetic compressors. Lower global-warming-potential (GWP) refrigerants R-454B and R-32
are increasingly being used in scroll chiller applications. R-513A is a lower-GWP alternative to
R134a for reciprocating chillers.
R-410A provides greater capacity than R-134a for a given compressor displacement, resulting in
physically smaller compressors required. R-717 (ammonia) has similar capacity characteristics to
R-407C, but, because of odor and toxicity, R-717 use in public or populated areas is restricted.
However, R-717 chillers are becoming more popular because of the pull for lower-global-warming
refrigerants and natural refrigerants. R-717 units are typically open-drive compressors and are
piped with steel because copper cannot be used in ammonia systems.
2.2 PERFORMANCE CHARACTERISTICS AND OPERATING PROBLEMS
A distinguishing characteristic of scroll and reciprocating compressors is pressure rise impact on
capacity. Pressure rise has only a slight influence on the volume flow rate of the compressor, and,
therefore, scroll and reciprocating liquid chillers retain nearly full cooling capacity, even on
above-design-wet-bulb days. It is well suited for air-cooled condenser operation and low-temperature
refrigeration. Typical performance is shown in Figure
6 and compared with centrifugal and screw compressors. Capacity control methods include the
following:
-
Unloading reciprocating compressor cylinders (one at a time or in pairs)
-
On/off cycling of compressors
-
Pulse width modulation unloading of scroll compressors
-
Hot-gas bypass
-
Compressor variable-speed control
-
Combination of the previous methods
Figure
7 shows the relationship between system demand and performance of a compressor with three
steps of unloading. As cooling load drops to the left of fully loaded compressor line A, compressor
capacity is reduced to that shown by line B, which produces the required refrigerant flow. Because
cooling load varies continuously whereas machine capacity is available in fixed increments, some
compressor on/off cycling or successive loading and unloading is required to maintain fairly
constant liquid temperature. In practice, a good control system minimizes load/unload or on/off
cycling frequency while maintaining satisfactory temperature control.
Two types of ratings are published. The first, for a packaged liquid chiller, lists values of
capacity and power consumption for many combinations of leaving condenser water and
chilled-water temperatures (ambient dry-bulb temperatures for air-cooled models). The second
type of rating shows capacity and power consumption for different condensing and chilled-water
temperatures. This type of rating allows selection with a remote condenser that can be
evaporative, water, or air cooled. Sometimes the required rate of heat rejection is also listed
to aid in selecting a separate condenser.
With all liquid-chilling systems, power consumption increases as condensing temperature rises.
Therefore, the smallest package, with the lowest ratio of input to cooling capacity, can be used
when condenser water temperature is low, the remote air-cooled condenser is relatively large, or
when leaving chilled-water temperature is high. The cost of the total system, however, may not
be low when liquid chiller cost is minimized. Increases in cooling tower or fan-coil cost will
reduce or offset the benefits of reduced compression ratio. Life-cycle costs (initial cost plus
operating expenses) should be evaluated.
A fouling allowance of 0.044 (m2 · K)/kW is included
in manufacturers’ ratings in accordance with AHRI Standard
550/590. However, fouling factors greater than 0.044 should be considered if water
conditions are not ideal.
2.4 CONTROL CONSIDERATIONS
Scroll and reciprocating chillers are most commonly distinguished from centrifugal and screw
compressor-operated chillers by their use of increments of capacity reduction rather than continuous
modulation. Therefore, special arrangements must be used to establish precise chilled-liquid
temperature control while maintaining stable operation free from excessive on/off cycling of
compressors or unnecessary loading and unloading of cylinders or scroll modulation.
To help provide good temperature control, return chilled-liquid temperature sensing is normally used
by units with steps of capacity control. The resulting flywheel effect in the chilled-liquid circuit
damps out excessive cycling. Leaving chilled-liquid temperature sensing prevents excessively low
leaving chilled-liquid temperatures if chilled-liquid flow falls significantly below the design
value. It may not provide stable operation, however, if rapid load changes are encountered.
An example of a basic control circuit for a packaged scroll/reciprocating chiller with three steps of
unloading is shown in Figure 8. The
on/off switch controls start-up and starts the programmed timer. Assuming that the flow switch,
field interlocks, and chiller safety devices are closed, pressing the momentarily closed reset
button energizes control relay C1, locking in the safety circuit and the motor-starting circuit.
When the timer completes its program, timer switch 1 closes and timer switch 2 opens. Timer relay TR
energizes, stopping the timer motor. When timer switch 1 closes, the motor-starting circuit is
completed and the motor contactor holding coil is energized, starting the compressor.
The four-stage thermostat controls the compressor capacity in response to demand. Cylinders are
loaded and unloaded, or scroll pulse width modulation is controlled, by deenergizing and energizing
the unloader solenoids. If load is reduced so that return water temperature drops to a predetermined
setting, the unit shuts down until demand for cooling increases.
Opening a device in the safety circuit deenergizes control relay C1 and shuts down the compressor.
The liquid line solenoid is also deenergized. Manual reset is required to restart. The crankcase
heater is often energized whenever the compressor is shut down to prevent liquid refrigerant
migration to the compressor oil sump, which can impact reliability from oil dilution and flooding at
startup.
If the automatic reset, low-pressure cutout opens, the compressor shuts down, but the liquid line
solenoid remains energized. The timer relay TR is deenergized, causing the timer to start and
complete its program before the compressor can be restarted. This prevents rapid cycling of the
compressor under low-pressure conditions. A time delay low-pressure switch can also be used for this
purpose with the proper circuitry.
For multiple-chiller applications and a 6 K chilled-liquid temperature range, a parallel
chilled-liquid arrangement is common because of the high cooler pressure drop resulting from the
series arrangement. For a large (10 K) range, however, the series arrangement
eliminates the need for overcooling when only one unit is operating. Special coolers with low
water-pressure drop may also be used to reduce total chilled-water pressure drop in the series
arrangement.
Air-cooled scroll and reciprocating liquid chillers are often configured with a reversing valve in
the refrigerant circuit and applied as heat pump chillers. Such chillers have the ability to
seasonally be configured for either heating or cooling duty. Glycol is required in the water loop to
prevent freezing in cold climates. In addition, air-cooled scroll and reciprocating chillers can be
applied with a fluid to refrigerant heat exchanger in the compressor discharge line that
desuperheats the discharge gas and reclaims that heat for other building heating needs.
3. CENTRIFUGAL LIQUID
CHILLERS
Components and Their Function
Chapter 38 describes centrifugal compressors.
Because they are not positive displacement, they offer a wide range of capacities continuously
modulated over a limited range of pressure ratios. By altering built-in design items (e.g.,
number of stages, compressor speed, impeller diameters, choice of refrigerant), they can be used
in liquid chillers having a wide range of design chilled-liquid temperatures and design
condensing fluid temperatures. The ability to vary capacity continuously to match a wide range
of load conditions with nearly proportional changes in power consumption makes a centrifugal
compressor desirable for both close temperature control and energy conservation. Its ability to
operate at greatly reduced capacity allows it to run most of the time with infrequent starting.
The centrifugal compressor has a minimum of bearing and other contacting surfaces that can wear;
wear is also minimized by providing forced lubrication to those surfaces before start-up and
during shutdown. Bearing wear usually depends more on the number of start-ups than the actual
hours of operation. Thus, reducing the number of start-ups extends system life and reduces
maintenance costs.
Compressors may be open or hermetic. Open compressors may be driven by steam or gas turbines or
engines, or electric motors, with or without speed-increasing gears. (Engine and turbine drives
are covered in Chapter 7, and electric
motor drives in Chapter
45.)
Packaged electric-drive chillers may be open or hermetic and use two-pole, 50 or 60 Hz polyphase
electric motors, with or without speed-increasing gears, which may be installed in a separate
gearbox from the compressor. Several types of starters are commonly used with water-cooled
chillers; starter selection depends on many variables, including cost, electrical system
characteristics, voltage, and power company regulations at the installation. The electric drive
motor can also be started with a variable-frequency drive (VFD), which provides a reduced-power
start and can provide significant efficiency improvement at less than full load.
For larger chillers, starters or VFDs may be unit-mounted or remote-mounted from the chiller. The
vast majority of units have unit mounting, which saves space, reduces installation costs, and
increases the reliability of the chiller system. Unit-mounted starters or VFDs are predominant
on centrifugal chillers because the entire chiller’s electrical requirement is supplied
with power through a single-point connection. Several electrical connections are required for
remote-mounted starters or VFDs, and separate electrical feeds are required for the compressor,
oil pump, and unit controls. These separate wiring connections must be field installed between
the remote starter and the chiller.
Flooded coolers are commonly used, although direct-expansion coolers can also be used. The
typical flooded cooler uses copper or copper alloy tubes that are mechanically expanded into the
tube sheets, and, in some cases, into intermediate tube supports.
Because liquid refrigerant that flows into the compressor increases power consumption and may
cause internal damage, mist eliminators or baffles are often used in flooded coolers to minimize
refrigerant liquid entrainment in the suction gas. (Additional information on coolers for liquid
chillers is found in Chapter 41.)
The condenser is generally water cooled, with refrigerant condensing on the outside of copper
tubes. Large condensers may have refrigerant drain baffles, which direct refrigerant condensate
from within the tube bundle directly to liquid drains, reducing the liquid film thickness on the
lower tubes.
Air-cooled condensers can be used with units that use higher-pressure refrigerants, but with
considerable increase in unit energy consumption at design conditions. Compare operating costs
(including costs for cooling towers and condenser water pumps) for air-cooled and water-cooled
condensing.
System modifications, including subcooling and economizing (described under Principles of
Operation), are often used to conserve energy by enhancing the refrigeration cycle efficiency.
Some units combine the condenser, cooler, and refrigerant flow control in one vessel; a
subcooler may also be incorporated. (Additional information about thermodynamic cycles is in
Chapter 2 of the 2021 ASHRAE Handbook—Fundamentals. Chapter 39 in this volume has information on
condensers and subcoolers.)
Capacities and Types Available
Centrifugal packages are available from about 280 kW to over 14 MW at nominal
conditions of 7°C leaving chilled-water temperature and 35°C
leaving condenser water temperature, but these limits are continually changing. Field-assembled
machines extend to about 35 MW. Single- and two-stage internally geared machines
and two- and three-stage direct-drive machines are commonly used in packaged units. Electric
motor-driven machines constitute the majority of units sold.
All refrigerants have advantages and disadvantages that must be carefully considered when
choosing a refrigerant and chiller. Legislative phaseout requirements also differ, based on
environmental properties [e.g., ozone depletion potential (ODP)] and direct and indirect
contributions to global warming as quantified by various metrics [e.g., global warming potential
(GWP), total equivalent warming impact (TEWI), life-cycle climate performance (LCCP)]. Table 1 gives some
properties of example refrigerants; for details, see Chapters 29 and 30 of the 2021 ASHRAE Handbook—Fundamentals.
Table 1 summarizes these
values for various refrigerants.
Global warming is a major global environmental
concern. Refrigerants contribute to the greenhouse effect both directly (e.g., from leakage into
the atmosphere during operation, maintenance, or at end of life) and indirectly (from energy
used to operate air-conditioning equipment). The total warming effect of a chiller should take
into account both these effects.
Direct contribution to global warming is evaluated by the refrigerant’s GWP and the amount
of refrigerant released in the atmosphere during the life of the equipment. Indirect
contribution to global warming is related to chiller efficiency: a less efficient chiller
requires more power to be generated at the local power plant, and thus has a greater indirect
contribution to global warming. TEWI and LCCP are two metrics used to evaluate the combined
effect of direct and indirect global warming contributions.
Whereas ozone-depleting substances are addressed by the Montreal Protocol, there are no
global-warming-based phaseouts currently in effect for air-conditioning refrigerants in
stationary applications. However, with the increasing attention on greenhouse gases, the
industry is likely moving toward refrigerants with reduced GWP values.
Safety is also an important consideration. Regardless
of the refrigerant selected, refrigerant leak detectors, alarms, and emergency ventilation are
now required by code in many applications. Safety classifications of refrigerants are
categorized by a code, with a letter designating toxicity levels [A = occupational exposure
limit (OEL) of ≥400 ppm; B = OEL of <400 ppm] and a numeral indicating flammability
ranking (1 to 3, with lower numbers indicating lower flammability). For example, R-123 has a B1
classification, and R-22 and R-134a have A1 classifications, as described in ASHRAE Standard 34. With proper safety procedures, R-123, R-22, and R-134a
are all allowed under most North American codes.
Chiller operating pressure also affects pressure
vessel requirements, emissive potential, and ancillary equipment:
-
Any chiller with components operating below atmospheric pressure [e.g., R-514A,
R-1233zd(E)] must have a purge device to remove noncondensable gases, which may leak
into the machine.
-
Chillers with all components operating above atmospheric pressure (e.g., R-134a,
R-513A) do not require a purge device.
-
A pressure vessel code may be required, depending on design working pressure.
-
A chiller’s refrigerant leak potential is related to the selected
refrigerant’s molecular weight and saturation pressure range, coupled with the
machine’s hermetic integrity and installation, maintenance, and service
practices. In general, all chillers have the potential for extremely low emissions.
ASHRAE Standard 147 provides methods for design,
manufacturing and operational practices to achieve low leakage rates. Typical
refrigerant leakage rates vary between 0.5 to 2.0% per year.
Refrigerant stability and material compatibility are also important
considerations in chiller design; ways to control typical contaminants must be considered, as
well. Various contaminants and their control are discussed in Chapter 7 of the 2022 ASHRAE Handbook—Refrigeration. Selecting elastomers and
electrical insulating materials requires special attention because many of these materials are
affected by refrigerants. Additional information on material selection can be found in Chapter 6
of the 2022 ASHRAE Handbook—Refrigeration, and information on
testing methods can be found in ASHRAE Standard 97.
Energy efficiency is a factor when selecting a
refrigerant and chiller system. Each refrigerant discussed in this section has a different
theoretical or baseline energy performance, according to its thermodynamic and thermophysical
properties. Table 1 lists the
theoretical COP at temperatures and pressures commonly applied in commercial comfort
air-conditioning applications. From that baseline, chiller manufacturers enhance their designs
to optimize refrigerant properties for the selected refrigerant. Also, some chillers are more
efficient at peak load, whereas others perform better at off-peak conditions, so an accurate
load model is necessary to make a fully informed choice. Chiller performances at peak and
off-peak operating conditions are a function of specific chiller and compressor design, not
refrigerant type. More thorough data on refrigerant properties are available in Chapters 29 and
30 of the 2021 ASHRAE Handbook—Fundamentals.
For additional information on properties of refrigerants and their applications, see ASHRAE Standards 15 and 34.
3.2 PERFORMANCE AND OPERATING
CHARACTERISTICS
Figure
9 shows a compressor’s performance at constant speed with various inlet guide vane
settings. Figure
10 shows a compressor’s performance at various speeds in combination with inlet guide
vanes. Capacity is modulated at constant speed by automatic adjustment of prerotation vanes that
swirl the refrigerant gas at the impeller eye. This effect matches demand by shifting the compressor
performance curve downward and to the left (as shown in Figure
9). Compressor efficiency, when unloaded in this manner, is superior to suction throttling.
Some manufacturers automatically reduce diffuser width or throttle the impeller outlet with
decreasing load.
Speed control for a centrifugal compressor offers even
lower power consumption. Variable-frequency drive (VFD) control continuously reduces the
compressor’s capacity, keeping operation in the maximum efficiency region over a much broader
range of operation. Essentially, the VFD adjusts the compressor’s speed to keep the inlet
guide vanes (IGVs) as open as possible to meet the system lift requirements, with the lowest power
consumption. Combined with the drop in condenser water temperature that occurs naturally in an
air-conditioning system, the variable-speed centrifugal compressor more efficiently meets the flow
and lift condition or state point required by the system.
Although capacity is directly related to a change in speed, the lift produced is proportional to the
square of the change in speed.
Hot-gas bypass allows the compressor to operate down to zero
load. This feature is a particular advantage for intermittent industrial applications such as
cooling quenching tanks. Bypass vapor maintains power consumption at the same level attained just
before starting bypass, regardless of load reductions.
Figure
11 shows an application where condenser water decreases with load, and the resulting temperature lift. A typical reduction in entering condenser water
temperature of 6 K helps to reduce temperature lift at low load. Other factors
producing lower lift at reduced loads include the following:
-
Reduced condenser cooling water range (difference between entering and leaving
temperatures, resulting from decreasing heat rejection)
-
Decreased temperature difference between condensing refrigerant and leaving condenser
water
-
Similar decrease between evaporating refrigerant and leaving chilled-liquid temperature
-
Multiple chillers configured in series or series-counterflow
In applications where the wet-bulb temperature drops with cooling load, even greater decreases in
entering condenser water temperature may be achieved depending on the system design.
In cooling tower applications, minimum water temperatures can be controlled by a cooling tower
bypass, or for better system efficiency by cooling tower fan control as required by ASHRAE Standard 90.1. When optimizing the heat rejection system efficiency, the
chiller, cooling tower, and pump energy should all be considered to determine the design condenser
flow rate.
Surging occurs when the system-specific work becomes greater than the compressor-developed specific
work or above the surge line indicated in Figures
9 and 10.
Excessively high temperature lift and corresponding specific work commonly originate from
-
Excessive condenser or evaporator water-side fouling beyond the specified allowance
-
Inadequate cooling tower performance and higher-than-design condenser water temperature
-
Noncondensable gases in the condenser, which increase condenser pressure
-
Condenser flow less than design
A centrifugal chiller with specified details is typically selected using a manufacturer’s
computer-generated selection program, many of which are AHRI certified. Capacity, unloading stability requirements, efficiency requirements,
liquid flow turndown requirements, number of passes, water-side pressure drop in each of the
heat exchangers, and desired electrical characteristics are input to select the chiller.
Unloading stability is important in evaluating the
part-load operating condition for a centrifugal chiller. If head pressure during part-load
operation is higher than the chiller was selected for, the impeller may not be able to overcome
the lift, and the chiller may begin unstable operation, causing the compressor to surge. For
humid regions, typical stability is chosen at approximately 50% of full load at design entering
condenser water, to guard against surge conditions.
Centrifugal chillers are typically selected for full- and/or part-load coefficient of performance
(COP) targets. Then they are checked for part-load stability using software provided by the
chiller manufacturer. A typical part-load stability check may involve running the chiller at
part-load points at entering condenser water temperatures that follow a relief profile
representative of the project climate zone, building load profile, and system heat rejection
design (e.g., cooling tower, dry cooler).
Most manufacturers offer variations of evaporators, condensers, tube counts, tube types,
compressor gears, impellers, etc. All of these permutations create an enormous product offering
that is much too difficult to fit into a tabular format. For this reason, computer programs are
the norm for chiller selections and ratings because they can analyze hundreds of combinations in
a very short time.
In accordance with AHRI Standard 550/590, manufacturers’
ratings include a condenser fouling allowance of
0.044 (m2 · K)/kW. (Chapter 39
has further information about fouling factors.) To reduce fouling, a minimum water velocity of
about 1 m/s is recommended in condensers. Maximum water velocities exceeding
3.3 m/s are not recommended because of potential erosion problems with copper
tubes.
Proper water treatment and regular tube cleaning are recommended for all liquid chillers to
reduce power consumption and operating problems. Chapter 50 of the 2023 ASHRAE Handbook—HVAC Applications has water treatment
information.
Continuous or daily monitoring of the quality of the condenser water is desirable. Checking the
quality of the chilled liquid is also desirable. Intervals between checks become greater as the
possibilities for fouling contamination become less (e.g., an annual check should be sufficient
for closed-loop water-circulating systems for air conditioning). Corrective treatment is
required, and periodic, usually annual, cleaning of the condenser tubes usually keeps fouling
within the specified allowance. In applications where more frequent cleaning is desirable, an
online cleaning system may be economical.
Follow the chiller manufacturer’s mounting recommendations to prevent transmission or
amplification of vibration to adjacent equipment or structures. Auxiliary pumps, if not
connected with flexible fittings, can induce vibration of the centrifugal unit, especially if
the rotational speed of the pump is nearly the same as either the compressor prime mover or the
compressor. Flexible tubing becomes less flexible when it is filled with liquid under pressure
and some vibration can still be transmitted. General information on noise measurement and
control may be found in Chapter 8 of the 2021 ASHRAE
Handbook—Fundamentals, Chapter 49 of the 2023 ASHRAE
Handbook—HVAC Applications, and AHRI Standard 575.
3.4 CONTROL CONSIDERATIONS
In centrifugal systems, the chilled-liquid temperature sensor is usually placed in
thermal contact with the leaving chilled water (leaving condenser water for heating). In electrical
control systems, the electrical signal is transmitted to an electronic control module, which
controls the operation of an electric motor(s) positioning the capacity-controlling inlet guide
vanes. For variable-speed chillers, the electronic control module’s objective is to meet the
temperature set point at the lowest speed possible, with inlet guide vanes as wide open as possible
without surging. A current limiter is usually included on machines with electric motors. An
electrical signal from a current transformer in the compressor motor controller is sent to the
electronic control module. The module receives indications of both leaving chilled-water temperature
and compressor motor current. The part of the electronic control module responsive to motor current
is called the current limiter. It overrides the demands of the temperature sensor.
Inlet guide vanes, independent of demands for cooling, do
not open more than the position that results in the present setting of the current limiter. The
chilled-liquid temperature sensor provides a signal. The controlling module receives both that
signal and the motor current electrical signal and controls the positioning of the inlet guide
vanes.
The current limiter on most machines can limit current
draw during periods of high electrical demand charges. This control can be set from about 40 to 100%
of full-load current. When power consumption is limited, cooling capacity is correspondingly
reduced. If cooling load only requires 50% of the rated load, the current (or demand) limiter can be
set at 50% without loss of cooling. By setting the limiter at 50% of full current draw, any
subsequent high demand charges are prevented during pulldown after start-up. Even during periods of
high cooling load, it may be desirable to limit electrical demand if a small increase in chiller
liquid temperature is acceptable. If temperature continues to decrease after capacity control
reaches its minimum position, a low-temperature control stops the compressor and restarts it when a
rise in temperature indicates the need for cooling. Manual controls may also be provided to bypass
temperature control. Capacity control is at its minimum position when the compressor starts, to
provide an unloaded starting condition.
Additional operating controls are needed for appropriate operation of lubricant pumps, lubricant
heaters, purge units, and refrigerant transfer units. An anti-recycle
timer should also be included to prevent frequent motor starts.
Multiple-unit applications require additional controls for capacity modulation and proper unit
sequencing. (See the section on Multiple-Chiller Systems.)
Safety controls protect the unit under abnormal
conditions. Safety cutouts may be required for high condenser pressure, low evaporator refrigerant
temperature or pressure, low lubricant pressure, high lubricant temperature, high motor temperature,
magnetic bearing overload, and high discharge temperature. Auxiliary safety circuits are usually
provided on packaged chillers. At installation, the circuits are field-wired to field-installed
safety devices, including auxiliary contacts on the pump motor controllers and flow switches in the
chilled-water and condenser water circuits. Safety controls are usually provided in a lockout
circuit, which trips out the compressor motor controller and prevents automatic restart. The
controls reset automatically, but the circuit cannot be completed until a manual reset switch is
operated and the safety controls return to their safe positions.
Purge units
may be required for centrifugal liquid-chilling machines to maintain system hermetic chemistry
integrity and efficiency. ASHRAE Standard 147 requires purge units for
liquid-chilling machines using refrigerants with working pressures below atmospheric pressure. If a
purge unit were not used, air and moisture would accumulate in the refrigerant side. Noncondensable
gases collect in the condenser during operation, reducing the heat-transfer coefficient and
increasing condenser pressure as a result of both their insulating effect and their partial
pressure. Compressor power consumption increases, capacity decreases, and surging may occur.
Free moisture may build up once the refrigerant becomes saturated. Acids produced by a reaction
between free moisture and the refrigerant then cause internal corrosion. A purge unit prevents
accumulation of noncondensable gases and ensures internal cleanliness of the chiller. However, a
purge unit does not reduce the need to check for and repair leaks, which is required maintenance for
any liquid chiller. Purge units may be manual or automatic, compressor operated, or compressorless.
To reduce the potential for air leaks when chillers are off, chillers may be heated externally to
pressurize them to atmospheric pressure.
ASHRAE Standard 15 requires most purge units and rupture disks to be
vented outdoors. Because of environmental concerns and the increasing cost of refrigerants,
high-efficiency (air-to-refrigerant) purges are available that reduce refrigerant losses during
normal purging.
Lubricant coolers may be water cooled, using condenser
water when the quality is satisfactory, or chilled water when a small loss in net cooling capacity
is acceptable. These coolers may also be refrigerant or air cooled, eliminating the need for water
piping to the cooler.
A refrigerant transfer unit may be provided for
maintenance of centrifugal liquid chillers. The unit consists of a small reciprocating compressor
with electric motor drive, a condenser (air or water cooled), a lubricant reservoir and separator,
valves, and interconnecting piping. Refrigerant transfers in three steps:
-
Gravity drain. When the receiver is at the
same level as or below the cooler, some liquid refrigerant may be transferred to the
receiver by opening valves in the interconnecting piping.
-
Pressure transfer. By resetting valves and
operating the compressor, refrigerant gas is pulled from the receiver to pressurize the
cooler, forcing refrigerant liquid from the cooler to the storage receiver. If the
chilled-liquid and condenser water pumps can be operated to establish a temperature
difference, refrigerant migration from the warmer vessel to the colder vessel can also
be used to help transfer refrigerant.
-
Pump-out. After the liquid refrigerant has
been transferred, valve positions are changed and the compressor is operated to pump
refrigerant gas from the cooler to the transfer unit condenser, which sends condensed
liquid to the storage receiver. If any chilled liquid (water, brine, etc.) remains in
the cooler tubes, pump-out must be stopped before cooler pressure drops below the
saturation condition corresponding to the chilled liquid’s freezing point.
If the saturation temperature corresponding to cooler pressure is below the chilled-liquid freezing
point when recharging, refrigerant gas from the storage receiver must be introduced until cooler
pressure is above this condition. The compressor can then be operated to pressurize the receiver and
move refrigerant liquid into the cooler without danger of freezing.
Water-cooled transfer unit condensers provide fast refrigerant transfer. Air-cooled condensers
eliminate the need for water, but they are slower and more expensive.
Cooling without operating the compressor of a centrifugal liquid chiller is called free cooling.
When a supply of condenser water is available at a temperature below the needed chilled-water
temperature, some chillers can operate as a thermal siphon. Low-temperature condenser water
condenses refrigerant, which is either drained by gravity or pumped into the evaporator.
Higher-temperature chilled water causes the refrigerant to evaporate, and vapor flows back to
the condenser because of the pressure difference between the evaporator and the condenser. This
free-cooling accessory is limited to a fraction of the chiller design capacity, and this option
is not available from all manufacturers. Free-cooling capacity depends on chiller design and the
temperature difference between the desired chilled-water temperature and the condenser water
temperature. Free cooling is also available external to the chiller using either direct or
indirect methods, as described in Chapter 40.
Any building or plant with simultaneous heating and cooling loads has the potential for a heat
recovery installation.
Heat recovery systems extract heat from liquid being chilled and reject some of that heat, plus
the energy of compression, to a warm-water circuit for reheat or heating. Air-conditioned spaces
thus furnish heating for other spaces in the same building. During the full-cooling season, all
heat must be rejected outdoors, usually by a cooling tower. During spring or fall, some heat is
required indoors, while some heat extracted from air-conditioned spaces must be rejected
outdoors.
Heat recovery offers a low heating cost and reduces space requirements for equipment. The control
system must, however, be designed carefully to take the greatest advantage of recovered heat and
to maintain proper temperature and humidity in all parts of the building. Chapter 9
covers balanced heat recovery systems.
Because cooling tower water is not satisfactory for heating coils, a separate, closed warm-water
circuit with another condenser bundle or auxiliary condenser, in addition to the main water
chiller condenser, must be provided. In some cases, it is economically feasible to use a
standard condenser and a closed-circuit heat exchanger.
Instead of rejecting all heat extracted from the chilled liquid to a cooling tower, a separate,
closed condenser cooling water circuit is heated by the condensing refrigerant for comfort
heating, preheating, or reheating. Some factory packages include an extra condenser water
circuit, either a double-bundle condenser or an auxiliary condenser.
A centrifugal heat recovery package is controlled as follows:
Chilled-liquid temperature is controlled by a sensor
in the leaving chilled-water line signaling the capacity control device.
Hot-water temperature is controlled by a sensor in the
hot-water line that modulates a cooling tower bypass valve. As the heating requirement
increases, hot-water temperature drops, opening the tower bypass slightly. Less heat is rejected
to the tower, condensing temperature increases, and hot-water temperature is restored as more
heat is rejected to the hot-water circuit.
The hot-water temperature selected affects the installed cost of the heat recovery package, as
well as on the power consumption while heating. Lower hot-water temperatures of 35 to
41°C result in a less expensive machine that uses less power. Higher temperatures
require greater compressor motor output, perhaps higher-pressure condenser shells, sometimes
extra compression stages, or a cascade arrangement. Installed cost of the centrifugal heat
recovery machine increases as a result.
Another concern in design of a central chilled-water plant with heat recovery compressors is the
relative size of cooling and heating loads. These loads should be equalized on each machine so
that the compressor may operate at optimum efficiency during both full cooling and full heating
seasons. When the heating requirement is considerably smaller than the cooling requirement,
multiple chillers lower operating costs and allow less-expensive standard centrifugal packages
to be used for the rest of the cooling requirement. In multiple packages, only one unit is
designed for heat recovery and carries the full heating load.
Another consideration for heat recovery chiller systems is the potential for higher cooling
energy use. A standard commercial building water chiller operates with condenser water
temperatures at or below 38°C. For heat recovery to be of practical use, the
condenser water may need to operate at higher temperatures, thereby increasing the
chiller’s energy consumption. The design engineer must examine the trade-off between
higher cooling energy use versus lower heating energy use; the heat recovery chiller system may
not necessarily be advantageous.
Two types of air-cooled centrifugal systems are used. One consists of a water-cooled centrifugal
package with a closed-loop condenser water circuit. Condenser water is cooled in a water/air
heat exchanger. This arrangement results in higher condensing temperature and increased power
consumption. In addition, winter operation requires using glycol in the condenser water circuit,
which reduces the heat transfer coefficient of the unit.
The other type of unit is directly air-cooled, which eliminates the intermediate heat exchanger
and condenser water pumps, resulting in lower power requirements. However, condenser and
refrigerant piping must be leak free.
Because a centrifugal machine will surge if it is subjected to a pressure appreciably higher than
design, the air-cooled condenser must be designed to reject the required heat. In common
practice, selection of a reciprocating air-cooled machine is based on an outdoor dry-bulb
temperature that will be exceeded 5% of the time. A centrifugal chiller may be unable to operate
during such times because of surging, unless the chilled-water temperature is raised
proportionately. Thus, the compressor impeller(s) and/or speed should be selected for the
maximum dry-bulb temperature to ensure that the desired chilled-water temperature is maintained
at all times. In addition, the condenser coil must be kept clean.
An air-cooled centrifugal chiller should allow the condensing temperature to fall naturally to
about 21°C during colder weather. The resulting decrease in compressor power
consumption is greater than that for reciprocating systems controlled by thermal expansion
valves.
During winter shutdown, precautions must be taken to prevent cooler liquid freezing caused by a
free cooling effect from the air-cooled condenser. A thermostatically controlled heater in the
cooler, in conjunction with a low-refrigerant-pressure switch to start the chilled-liquid pumps,
will protect the system.
Centrifugal liquid-chilling units are most frequently used for water-chilling applications, but
they are also used with secondary coolants such as calcium chloride, methylene chloride,
ethylene glycol, and propylene glycol. (Chapter 31 of the 2021 ASHRAE
Handbook—Fundamentals describes properties of secondary coolants.) Coolant
properties must be considered in calculating heat transfer performance and pressure drop.
Because of the greater temperature rise, higher compressor speeds and possibly more stages may
be required for cooling these coolants. Compound and/or cascade systems are required for
low-temperature applications.
Many process applications condense vapors such as ammonia, chlorine, or hydrogen fluoride.
Centrifugal liquid-chilling units are used for these applications.
3.7 OPERATION AND MAINTENANCE
Proper operation and maintenance are essential for reliability, longevity, and safety. Chapter 40 of
the 2023 ASHRAE Handbook—HVAC Applications includes general
information on principles, procedures, and programs for effective maintenance. The
manufacturer’s operation and maintenance instructions should also be consulted for specific
procedures. In the United States, Environmental Protection Agency (EPA) regulations require (1)
certification of service technicians, (2) a statement of minimum pressures necessary during system
evacuation, and (3) definition of when a refrigerant charge must be removed before opening a system
for service. All service technicians or operators maintaining systems must be familiar with these
regulations.
Normal operation conditions should be established and recorded at initial start-up. Changes from
these conditions can be used to signal the need for maintenance. One of the most important items is
to maintain a leak-free unit.
Leaks on units operating at subatmospheric pressures allow air and moisture to enter the unit, which
increases condenser pressure. Although the purge unit can remove noncondensable gases sufficiently
to prevent an increase in condenser pressure, continuous entry of air and attendant moisture into
the system promotes refrigerant and lubricant breakdown and corrosion. Leaks from units that operate
above atmospheric pressure may release environmentally harmful refrigerants. Regulations require
that annual leakage not exceed a percentage of the refrigerant charge. It is good practice, however,
to find and repair all leaks.
Periodic analysis of the lubricant and refrigerant charge can also identify system contamination
problems. High condenser pressure or frequent purge unit operation indicate leaks that should be
corrected as soon as possible. With positive operating pressures, leaks result in loss of
refrigerant and operating problems such as low evaporator pressure. A leak check should also be
included in preparation for a long-term shutdown. (Chapter 7 in the 2022 ASHRAE
Handbook—Refrigeration discusses the harmful effects of air and moisture.)
Normal maintenance should include periodic lubricant and refrigerant filter changes as recommended by
the manufacturer. All safety controls should be checked periodically to ensure that the unit is
protected properly.
Cleaning inside tube surfaces may be required at various intervals, depending on water condition.
Condenser tubes may only need annual cleaning if proper water treatment is maintained. Cooler tubes
need less frequent cleaning if the chilled-water circuit is a closed loop.
If the refrigerant charge must be removed and the unit opened for service, the unit should be
leak-checked, dehydrated, and evacuated properly before recharging. Chapter 8 of the 2022 ASHRAE Handbook—Refrigeration has information on dehydrating,
charging, and testing.
Components and Their Function
Single-, twin-, and tri-screw compressors are positive-displacement machines with nearly constant
flow performance. Compressors for liquid chillers can be both lubricant-injected and
lubricant-injection-free. (Chapter 38 describes screw compressors in
detail.)
The cooler may be flooded or direct expansion. The flooded cooler is more sensitive to freezing
inside the tubes, requires more refrigerant, and the lack of suction superheat requires an
alternative expansion device control, such as high-side or low-side refrigerant level control.
Flooded coolers generally have better performance and the heat exchanger tubes can be cleaned.
The DX cooler’s suction superheat enables superheat control of the expansion device, is
less likely to freeze, and higher refrigerant velocity inside the tubes returns lubricant to the
lubricant system rapidly. The decision to use one or the other is based on the relative
importance of these factors on a given application.
Screw coolers have the following characteristics: (1) high maximum working pressure, (2)
continuous lubricant scavenging, (3) no mist eliminators (flooded coolers), and (4) distributors
designed for high turndown ratios (direct-expansion coolers). A suction-gas to high-pressure
liquid-refrigerant heat exchanger is sometimes incorporated into the system to provide
subcooling for increased capacity, reduced likelihood of vapor generation in the liquid line
upstream of the expansion device, increased suction superheat for more stable expansion device
control, and potential for reduced power consumption. (For further information on coolers, see
Chapter 42.)
The condenser is typically included as part of the liquid-chilling package when water cooled;
however, it may be remote. Air-cooled screw liquid chilling packages are also common. When
remote air-cooled or evaporative condensers are applied to liquid-chilling packages, a liquid
receiver generally replaces the water-cooled condenser on the package structure. Water-cooled
condensers are the cleanable shell-and-tube type (see Chapter
39).
Efficient lubricant separators are required. The types and efficiencies of these separators vary
according to refrigerant and application. Field-built systems require better separation than
complete factory-built systems. Ammonia applications are most stringent because no appreciable
lubricant returns with suction gas from the flooded coolers normally used in ammonia
applications. However, separators are available for ammonia packages, which do not require the
periodic addition of lubricant customary on other ammonia systems. The types of separators used
are centrifugal, demister, gravity, coalescer, and combinations of these.
Semihermetic compressor units may use a centrifugal separator as an integral part of the hermetic
motor while cooling the motor with discharge gas and lubricant simultaneously. A schematic of a
typical refrigeration system is shown in Figure 12.
High-lift systems, such as those with a remote air-cooled condenser, or chillers used for heating
duty, along with ammonia systems with a lubricant separator on the high side may have lubricant
temperatures that require a lubricant cooler. Lubricant cooler loads vary widely, depending on
the refrigerant and application, but they can be substantial because lubricant injected into the
compressor absorbs part of the heat of compression. Lubricant is cooled by one of the following
methods:
-
Water-cooled using condenser water, evaporative condenser sump water, chilled water,
or a separate water- or glycol-to-air cooling loop
-
Air-cooled using a lubricant-to-air heat exchanger
-
Refrigerant-cooled (where lubricant cooling load is low)
-
Refrigerant liquid injection into the compressor
-
Condensed refrigerant liquid thermal recirculation (thermosiphon), where appropriate
compressor head pressure is available
The latter two methods are the most economical both in first cost and overall operating cost
because cooler maintenance and special water treatment are eliminated.
Capacities and Types Available
Screw compressor liquid chillers are most commonly available as factory-packaged units from about
100 to 2100 kW. Both open and semihermetic styles are manufactured. Packages
without water-cooled condensers, with receivers, are made for use with air-cooled or evaporative
condensers. Most factory-assembled liquid chilling packages use R-134a.
Additionally, compressor units, comprised of a compressor, hermetic or open motor, and lubricant
separator and system, are available from 70 to 7000 kW. These are used with remote
evaporators and condensers for low-, medium-, and high-evaporating-temperature applications.
Condensing units, similar to compressor units in range and capacity but with water-cooled
condensers, are also built. Similar open motor-drive units are available for ammonia, as are
booster units.
The refrigerants most commonly used with screw compressors on liquid chiller applications are
R-134a and R-717. R-513A and R-515B are increasing in use as lower-GWP refrigerant replacements
for R-134a.
4.2 PERFORMANCE AND OPERATING CHARACTERISTICS
Figure
6 compares screw compressor operating characteristics with those for scroll/reciprocating
and centrifugal compressors. Because the screw compressor is a positive-displacement compressor, it
does not surge. Additionally, because it has no clearance volume in the compression chamber, it
pumps high-volumetric flows at high pressure lift. Consequently, screw compressor chillers suffer
the least capacity reduction at high condensing temperatures.
The screw compressor provides stable operation across its operating envelope because it is a
positive-displacement machine. The operating range is wide because discharge temperature is kept low
and thus is not a limiting factor due to the lubricant injection into the compression chamber.
Consequently, the compressor is able to operate single-stage at high pressure ratios.
An economizer heat exchanger can be installed to improve capacity and lower power consumption at
full- and part-load operation. An example is shown in Figure 12, where the main
refrigerant liquid flow leaving the condenser is split, with flow to the main expansion device being
subcooled in a heat exchanger via evaporation of refrigerant at mid-stage pressure that is connected
to the intermediate-pressure port in the compressor. The evaporating pressure in this heat exchanger
is higher than the suction pressure of the compressor.
Lubricant separators must be sized for the compressor size, type of system (factory assembled or
field connected), refrigerant, and type of cooler. Direct-expansion coolers have less stringent
separation requirements than do flooded coolers. In a direct-expansion system, refrigerant
evaporates in the tubes, which means that velocity is kept sufficiently high that lubricant rapidly
returns to the compressor. In a flooded evaporator, the refrigerant is outside the tubes, and an
external lubricant-return device must be used to minimize the concentration of lubricant in the
cooler, or a lubricant separator must be included with very low oil circulation. Discharge check
valves are used to minimize backflow and lubricant loss during shutdown, and prevent screw reverse
rotation, which can impact reliability in some applications.
Because the lubricant in systems with a high-side lubricant sump is exposed to the high-pressure side
of the unit, precautions must be taken to prevent lubricant dilution. Dilution can also be caused by
excessive floodback through the suction or intermediate ports, which decreases discharge superheat
and results in high refrigerant concentration in the lubricant. Unless properly monitored, it may go
unnoticed until serious operating or mechanical problems are experienced.
Screw liquid chiller ratings are generally presented similarly to those for centrifugal chiller
ratings. Tabular values include capacity and power consumption at various chilled-water and
condenser water temperatures. In addition, ratings are given for packages without the condenser
that list capacity and power versus chilled-water temperature and condensing temperature.
Ratings for compressors alone are also common, showing capacity and power consumption versus
suction saturation temperature and condensing saturation temperature for a given refrigerant.
Typical part-load power consumption is shown in Figure
13. Power consumption of screw chillers benefits from reducing condensing water
temperature as the load decreases, as well as operating at the lowest practical pressure at full
load. However, because direct-expansion systems require a pressure differential, the power
consumption saving is not as great at part load, as shown.
A fouling allowance of 0.044 (m2 · K)/kW is
incorporated in screw compressor chiller ratings. Excessive fouling (above design value)
increases power consumption and reduces capacity. Fouling water-cooled lubricant coolers results
in higher than desirable lubricant temperatures.
4.4 CONTROL CONSIDERATIONS
Screw chillers with slide valve and/or variable-speed unloading provide continuous capacity
modulation, from 100% capacity down to 10% or less. The leaving chilled-liquid temperature is sensed
for capacity control. Safety controls commonly required are (1) lubricant failure switch, (2)
high-discharge-pressure cutout, (3) low-suction-pressure switch, (4) cooler flow switch, (5)
high-lubricant- and discharge-temperature cutout, (6) hermetic motor inherent protection, (7)
lubricant pump and compressor motor overloads, and (8) low-lubricant-temperature
(floodback/dilution) protection. The compressor is unloaded automatically (slide valve driven to
minimum position) before starting. Once it starts operating, the slide valve is controlled
hydraulically by a temperature-load controller that energizes the load and unloads solenoid valves.
The current limit relay protects against motor overload from higher than normal condensing
temperatures or low voltage, and also allows a demand limit to be set. An antirecycle timer is used
to prevent overly frequent recycling. Lubricant sump heaters are energized during the off cycle. A
hot-gas-capacity control is optionally available and prevents automatic recycling at no-load
conditions such as is often required in process liquid chilling. A suction-to-discharge starting
bypass sometimes aids starting and allows use of standard starting torque motors.
Some units are equipped with electronic regulators specially developed for screw compressor
characteristics. These regulators include proportional-integrating (PI) control of leaving brine
temperature and functions such as automatic/manual control, capacity indication, time circuits to
prevent frequent recycling and to bypass the lubricant pressure cutout during start-up, switch for
unloaded starting, etc. (Typical external connections are shown in Figure
14.)
A refrigerant transfer unit is similar to the unit
described in the section on Auxiliaries under Centrifugal Liquid Chillers, and is designed for an
appropriate operating pressure. Its flexibility is increased by including a reversible liquid pump
on the unit. It is available as a portable unit or mounted on a storage receiver.
A lubricant-charging pump is useful for adding lubricant
to the pressurized lubricant sump. Two types are used: a manual pump and an electric motor-driven
positive-displacement pump.
Acoustical enclosures are available for installations that
require low noise levels.
Because of the screw compressor’s positive-displacement characteristic and lubricant-injected
cooling, its use for high-pressure-differential applications is limited only by power considerations
and maximum design working pressures. Therefore, it is used for many special applications because of
reasonable compressor cost and no surge characteristic. Some of the fastest-growing areas include
the following:
-
Heat recovery installations
-
Air-cooled split packages with field-installed interconnecting piping, and factory-built
rooftop packages
-
Low-temperature brine chillers for process cooling
-
Ice rink chillers
-
Power transmission line lubricant cooling
High-temperature compressor and condensing units are used increasingly for air conditioning because
of the higher efficiency of direct air-to-refrigerant heat exchange resulting in higher evaporating
temperatures. Many of these installations have air-cooled condensers.
Manufacturer’s maintenance instructions should
be followed, especially because some items differ substantially from reciprocating or centrifugal
units. Water-cooled condensers must be cleaned of scale periodically (see the section on General
Maintenance). If condenser water is also used for the lubricant cooler, this should be considered in
the treatment program. Lubricant coolers operate at higher temperatures and lower flows than
condensers, so it is possible that the lubricant cooler may have to be serviced more often than the
condenser.
Because large lubricant flows are a part of the screw compressor system, monitor the lubricant filter
pressure drop carefully and change the elements periodically. This is particularly important in the
first month or so after start-up of any factory-built package, and is essential on field-erected
systems. Because the lubricant and refrigeration systems merge at the compressor, loose dirt and
fine contaminants in the system eventually find their way to the lubricant sump, where they are
removed by the lubricant filter. Similarly, monitor the filter-drier cartridges for pressure drop
and moisture during initial start and regularly thereafter. Generally, if a system reaches
acceptable dryness, it stays that way unless it is opened.
It is good practice to check the lubricant for acidity periodically, using commercially available
acid test kits. Lubricant does not need to be changed unless it is contaminated by water, acid, or
metallic particles. Also, a refrigerant sample should be analyzed yearly to determine its condition.
Yearly or during a regularly scheduled shutdown, (1) check and calibrate all operation and safety
controls, (2) tighten all electrical connections, (3) inspect power contacts in starters, (4)
dielectrically check hermetic and open motors, and (5) check the alignment of open motors.
Regularly perform leak testing of the unit. A water-cooled package used for summer cooling should be
leak tested annually. A flooded unit with proportionately more refrigerant in it, used for
year-round cooling, should be tested every four to six months. A process air-cooled chiller designed
for year-round operation 24 h per day should be checked every one to three months.
Based on 6000 operating hours per year and depending on the preceding considerations, a typical
inspection or replacement timetable is as follows:
ASHRAE members can access ASHRAE Journal articles and ASHRAE research project
final reports at technologyportal.ashrae.org. Articles and reports are also available for purchase
by nonmembers in the online ASHRAE Bookstore at www.ashrae.org/bookstore.
AHRI. 2003. Performance rating of water chilling
packages using the vapor compression cycle. Standard 550/590.
Air-Conditioning, Heating, and Refrigeration Institute, Arlington, VA.
AHRI. 2008. Method of measuring machinery sound within
an equipment space. Standard 575. Air-Conditioning, Heating, and
Refrigeration Institute, Arlington, VA.
ASHRAE. 2022. Safety code for mechanical refrigeration.
ANSI/ASHRAE Standard 15-2022.
ASHRAE. 2022. Designation and safety classification of
refrigerants. ANSI/ASHRAE Standard 2022.
ASHRAE. 2017. Sealed glass tube method to test the
chemical stability of materials for use within refrigerant systems. ANSI/ASHRAE Standard 97-2007 (RA 2017).
ASHRAE. 2019. Reducing the release of halogenated
refrigerants from refrigerating and air-conditioning equipment and systems. ANSI/ASHRAE Standard 147-2019.
ASME. 2015. Boiler and pressure
vessel code, Section VIII. American Society of Mechanical Engineers, New York.
Carrier. 2004. Water-cooled
chillers. Technical Development Program TDP-623.
ASHRAE. 2019. Method of testing liquid-chilling
packages. ANSI/ASHRAE Standard 30-2019.
Calm, J.M. 2007. Resource, ozone, and global warming
implications of refrigerant selection for large chillers. Paper
ICR07-E1-535, Proceedings of the 22nd International Congress of
Refrigeration, Beijing. Chinese Association of Refrigeration, Beijing, and
International Institute of Refrigeration, Paris.
Calm, J.M., and G.C. Hourahan. 2007. Refrigerant data
update. HPAC Engineering 79(1):50-64.
IPCC. 2005. Safeguarding the ozone
layer and the global climate system: Issues related to hydrofluorocarbons and
perfluorocarbons. Intergovernmental Panel on Climate Change.
USGBC. 2009. Green building rating
system for new construction and major renovations. U.S. Green Building Council,
Leadership in Energy and Environmental Design, Washington, D.C.