In addition, an air-to-air heat exchanger (e.g., heat pipe, coil runaround loop, fixed-plate heat
exchanger, rotary heat exchanger) may be used to enhance moisture removal by a mechanical dehumidifier
or air conditioner. The section on wraparound heat exchangers discusses how dehumidification processes
can be improved by using such a device. Other uses of air-to-air heat exchangers are covered in Chapter 26.
1. MECHANICAL DEHUMIDIFIERS
Mechanical dehumidifiers remove moisture by passing air over a surface that has been cooled below the
air’s dew point. This cold surface may be the exterior of a chilled-water coil or a
direct-expansion refrigerant coil. To prevent overcooling the space (and avoid the need to add heat
energy from another source), a mechanical dehumidifier also usually has means to reheat the air,
normally using recovered and recycled energy (e.g., recovering heat from hot refrigerant vapor in
the refrigeration circuit) or, in the case of a chilled-water dehumidifying system, using wrap
around heat exchangers to absorb heat energy from incoming air then passively transferring it around
the cooling coil into the leaving air). Using external energy input for reheat is wasteful and is
prohibited or limited in many countries (see ASHRAE Standard 90.1).
A mechanical dehumidifier differs from a typical off-the-shelf air conditioner in that the
dehumidifier usually has a much lower sensible heat ratio (SHR). The dehumidifier starts the
compressor on a call for dehumidification, whereas an air conditioner starts the compressor on a
call for sensible cooling. Typically, a room dehumidifier has an SHR of 0.6 or less, compared to a
standard air-conditioning system of 0.8 SHR. Dehumidifiers must also allow condensation from the
cooling coil to drain easily from the coils. They may need air velocities over the cooling coil
lower than those for a typical air conditioner, to improve moisture runoff and minimize carryover of
condensed moisture.
In addition, the need to introduce code-mandated ventilation air may require that outdoor air be
treated to avoid introducing excessive moisture. Basic strategies include precooling outdoor air
entering the air-conditioning evaporator coil, or providing a separate system to provide properly
conditioned outdoor air. For some low-dew-point (below 7°C) applications,
mechanical dehumidification may be used as the first stage, with desiccant dehumidification for the
final stage to maximize efficiency and minimize installed cost.
Although the main purpose of a mechanical dehumidifier is to remove moisture from the air, many
features can be incorporated for various applications, such as
-
Dehumidifying and cooling (no reheat)
-
Dehumidifying with partial reheat (leaving dry-bulb temperature is cooler than with a
dehumidifier with full reheat)
-
Dehumidifying with full reheat
-
Dehumidifying with heat recovery to various heat sinks
-
Dehumidification capacity modulation
-
Reheat capacity modulation
-
Ventilation air introduction
-
Auxiliary space or water heating
Often, mechanical dehumidifiers can be incorporated in a system to use waste heat from mechanical
cooling (e.g., heat rejection to a swimming pool, whirlpool, domestic hot water, heat pump loop,
chilled-water loop, or remote air-cooled condenser).
Outdoor dehumidifiers should be protected against internal moisture condensation when winter
conditions are severe, because of the higher dew-point temperature of air circulating in the unit.
Psychrometrics of Dehumidification
Figures 1 and 2
show the process of air moving over the dehumidifying coil and being reheated. Many
manufacturers size the dehumidifying coil for only part of the unit total airflow. This allows
them to introduce outdoor air after the dehumidifying coil and allows more unit airflow for the
condenser reheat coil to maintain proper system refrigeration pressures when rejecting
refrigerant heat to the airstream. Figures
3 and 4 show a
bypass air process.
In Figures 1 and 2,
air enters the dehumidifying coil at point A. The dehumidifying coil removes sensible heat (SH)
and latent heat (LH) from the airstream. The dehumidified, cooled air leaves the coil at its
saturation temperature at point B. The total heat removed (TH) is the net cooling capacity of
the system.
In reheating, the refrigerant (hot gas) rejects heat it has obtained from multiple sources.
Sensible heat absorbed in the air-cooling process is rejected to air leaving the cooling coil.
This air is at point C, which is the same dry-bulb temperature as the entering air minus the
moisture content. This heat is also rejected into the airstream, raising the air temperature to
point D. Also, nearly all electric power required to drive the refrigeration cycle is converted
to heat. This portion of heat rejection raises the air leaving temperature to point E.
This process assumes that all heat is rejected by the refrigerant reheat coil. Depending on
refrigerant system complexity, any part of the total heat rejection can be diverted to other
heat exchangers (condensers/desuperheaters).
Dehumidifier supply air temperatures can be controlled between 10 and 35°C.
However, system design should not rely on a mechanical dehumidifier as a dependable heat source
for space heating, because heat is only available when the unit is operating.
In Figures
3 and 4, air
enters the dehumidifying coil at point A. The dehumidifying coil removes sensible heat (SH) and
latent heat (LH) from the airstream. The dehumidified, cooled air leaves the coil at its
saturation temperature at point B. The total heat removed (TH) is the net cooling capacity of
the system.
In Figure
3, the air at B mixes with the bypass air to get to point C. In reheating, the
refrigerant (hot gas) rejects heat it has obtained from three sources. First, sensible heat
absorbed in the air-cooling process is rejected to air leaving the cooling coil. This air is at
point D, which is the same dry-bulb temperature as the entering air minus the moisture content.
Next, the latent heat removal that causes the moisture to condense also adds heat to the hot
refrigerant gas. This heat is also rejected into the airstream, raising the air temperature to
point E. Finally, nearly all electric power required to drive the refrigeration cycle is
converted to heat. This portion of heat rejection raises the air’s leaving temperature to
point F.
This process assumes that all heat is rejected by the refrigerant reheat coil. Depending on
refrigerant system complexity, any part of the total heat rejection can be diverted to other
heat exchangers (condensers/desuperheaters).
Dehumidifier supply air temperatures can be controlled between 18 and 40°C.
However, system design should not rely on a mechanical dehumidifier as a dependable heat source
for space heating, because heat is only available when the unit is operating.
Residential Dehumidifiers
Portable Dehumidifiers. These are smaller (usually
less than 3.5 kW), simpler versions of commercial dehumidifiers. They are
self-contained and easily movable. They are designed to be used in localized areas, such as
basements or other high-moisture areas.
As shown in Figure 5, a single fan draws
humid room air through the cold coil, removing moisture that either drains into the water
receptacle or passes through the cabinet into some other means of disposal. The cooled air
passes through the condenser, reheating the air.
Portable dehumidifiers ordinarily maintain satisfactory humidity levels in an enclosed space when
the airflow rate and unit placement move the entire air volume of the space through the
dehumidifier once an hour.
Design and Construction. Portable dehumidifiers use hermetic
motor-compressors; the refrigerant condenser is usually conventional finned tube. Refrigerant
flow is usually controlled by a capillary tube, although some high-capacity dehumidifiers use an
expansion valve. A propeller fan moves air through the unit at typical airflows of 70 to
120 L/s.
The refrigerated surface (evaporator) is usually a bare-tube coil, although finned-tube coils can
be used if they are spaced to allow rapid runoff of water droplets. Vertically disposed
bare-tube coils tend to collect smaller drops of water, promote quicker runoff, and result in
less condensate reevaporation compared to finned-tube or horizontally arranged bare-tube coils.
Continuous bare-tube coils, wound in a flat circular spiral (sometimes with two coil layers) and
mounted with the flat dimension of the coil in the vertical plane, are a good design compromise
because they have most of the advantages of the vertical bare-tube coil.
Evaporators are protected against corrosion by finishes such as waxing, painting, or anodizing
(on aluminum). Waxing reduces the wetting effect that promotes condensate formation; however,
tests on waxed versus nonwaxed evaporator surfaces show negligible loss of capacity. Thin paint
films do not have an appreciable effect on capacity.
Removable water receptacles, provided with most dehumidifiers, hold 7.5 to 11 L and
are usually made of plastic to withstand corrosion. Easy removal and handling without spillage
are important. Most dehumidifiers also provide either a means of attaching a flexible hose to
the water receptacle or a fitting provided specially for that purpose, allowing direct gravity
drainage to another means of disposal external to the cabinet.
An adjustable humidistat (30 to 80%) automatically cycles the unit to maintain a preselected
relative humidity. The humidistat may also provide a detent setting for continuous operation.
Some models also include a sensing and switching device that automatically turns the unit off
when the water receptacle is full.
Dehumidifiers are designed to provide optimum performance at standard rating conditions of
27°C db room temperature and 60% rh. When the room is less than
18°C db and 60% rh, the evaporator may freeze. This effect is especially
noticeable on units with a capillary tube.
Some dehumidifiers are equipped with defrost controls that cycle the compressor off under
frosting conditions. This control is generally a bimetal thermostat attached to the evaporator
tubing, allowing dehumidification to continue at a reduced rate when frosting conditions exist.
The humidistat can sometimes be adjusted to a higher relative humidity setting, which reduces
the number and duration of running cycles and allows satisfactory operation at low-load
conditions. Often, especially in the late fall and early spring, supplemental heat must be
provided from other sources to maintain above-frosting temperatures in the space.
Capacity and Performance Rating. Portable dehumidifiers are available
with moisture removal capacities of 5 to 30 L per 24 h, and are operable from
ordinary household electrical outlets (115 or 230 V, single-phase, 60 Hz). Input varies from 200
to 800 W, depending on the output capacity rating.
AHAM Standard DH-1 establishes a uniform procedure for determining
the rated capacity of dehumidifiers under specified test conditions and establishes other
recommended performance characteristics. An industry certification program sponsored by AHAM
covers the great majority of portable dehumidifiers and certifies dehumidification capacity.
The U.S. Environmental Protection Agency (EPA) qualifies dehumidifiers to carry its ENERGY
STAR® label if they remove the same amount of moisture as similarly sized
standard units, but use at least 10% less energy. The EPA’s ENERGY STAR website provides
additional information on qualifying products (EPA 2020).
Whole-House Dehumidifiers. Whole-house dehumidifiers
have higher moisture removal capacity than portable dehumidifiers. Blowers in whole-house
dehumidifiers are typically more powerful because they draw air through the unit at higher
external static pressures as compared to portable dehumidifiers. The design allows for
connection of ductwork to the unit’s inlet and outlet. Moist air is typically drawn from
either the return plenum of the HVAC system ductwork (Figure 6) or
from a centrally located register. The air is dehumidified and then discharged into the supply
ductwork of the HVAC system for distribution. To prevent reevaporation of moisture from the HVAC
system evaporator coil, the dry air enters the system downstream of the coil.
Whole-house dehumidifiers typically integrate controls to allow operation of the HVAC system
blower while dehumidifying the air; this allows the dry air to be distributed throughout the
home. Some dehumidifiers are equipped with controls to bring in outdoor air, which can then be
run through the dehumidifier before being distributed to the rest of the home. Sensors are
typically located inside the dehumidifier to measure the temperature and relative humidity of
air passing through the unit as opposed to the surrounding air. Controls on some models may
provide for installation of a remote humidistat or humidity sensor. Drain tubing must typically
be installed on the dehumidifier and routed to the nearest floor drain. Most models include an
internal condensate overflow switch or provide for the installation of a field-installed
overflow switch that will turn the unit off if it overflows.
Units are typically sheltered from the elements and should not be installed in locations that can
experience freezing temperatures. Whole-house dehumidifiers are typically located near the HVAC
system for convenient access to the supply and return plenums and to drains. Systems may be
installed in basements, closets, crawlspaces, or attics, so dehumidifier cabinets are typically
insulated. When units are installed over a finished area, drain pans are commonly installed
under the unit.
Codes. Domestic dehumidifiers
are designed to meet the safety requirements of UL Standard 474, Canadian Electrical Code,
and ASHRAE Standard 15. UL-listed and CSA-approved equipment have a
label or data plate indicating approval. UL also publishes the Electrical
Appliance and Utilization Equipment Directory, which covers this type of appliance.
General-Purpose Dehumidifiers
Basic components of general-purpose dehumidifiers are shown in Figure 7. An air filter
is required to protect the evaporator. Dehumidifying coils, because of their depth and
thoroughly wetted surfaces, are excellent dust collectors and not as easily cleanable as much
thinner air-conditioning evaporator coils. However, the large amount of condensate has a
self-cleaning effect. A bypass damper at the evaporator coil allows airflow adjustments for the
evaporator without decreasing airflow for the reheat coil. Dehumidifying and reheat coils may
operate at different airflows.
The compressor may be isolated from the airstream or located in it. Locating the compressor in
the airstream may make service more difficult, but this arrangement allows heat lost through the
compressor casing to be provided to the conditioned space while reducing the size of the
enclosure. During the cooling season, this compressor location reduces the unit’s sensible
cooling capacity.
Code-required outdoor air may be introduced between the evaporator and reheat coil. The amount of
outdoor air should be controlled to not adversely affect the refrigeration system’s
operation. Preheating outdoor air may be required in colder climates. Use caution when
introducing outdoor air before the evaporator coil. Some applications (e.g., indoor swimming
pools) have a constant moisture load year round. The dehumidifier’s performance is based
on the conditions of the air moving across the evaporator coil. Mixing outdoor air with space
return air before the evaporator coil changes the dehumidifier’s performance to latent
removal, which may be less than the space load and result in the inability to maintain the
original design conditions. The unit’s latent capacity can be significantly reduced when
outdoor air is introduced before the evaporator coil.
Computerized controls can sense return air temperature and relative humidity. Remote wall-mounted
sensors are also available. More sophisticated controls are desirable to regulate dew-point
temperature and maintain the desired relative humidity in the space.
General Considerations. Before considering
installation of any type of dehumidification equipment, all latent loads should be identified
and quantified. In many cases, this might lead to decisions that reduce the latent load. For
example, a storage facility that does not have an adequate vapor retarder in the building
envelope should be retrofitted before attempting to calculate the amount of moisture migration
through the structure. The same approach should be taken to reduce the amount of uncontrolled
air infiltration.
Consider covering large water surfaces, such as vats, and/or providing a local exhaust hood to
evacuate concentrated water vapor from where it is generated. Although these corrections seem to
add cost to a project, the resulting reduced size of the dehumidifier and its lower operating
cost often result in an attractive financial payback.
Other special considerations include the following:
-
High volumes of outdoor air. A project may
start out as suitable for a general-purpose dehumidifier. However, once outdoor air
requirements are quantified to compensate for exhaust and to pressurize the
facility, a general-purpose dehumidifier may no longer be applicable. The maximum
acceptable portion of outdoor air for general-purpose dehumidifiers is limited, and
depends on climatic conditions and the desired indoor conditions to be maintained.
As a general rule, when outdoor air requirements exceed 20% of the
dehumidifier’s total airflow, the manufacturer should be consulted to
determine whether the equipment is suitable for the application. In many cases, a
direct-exchange (DX) dedicated outdoor air system unit should be considered instead.
-
Low-return-air-temperature applications.
When the return air temperature is below 18°C, consult the
dehumidifier manufacturer to determine whether the equipment is suitable for the
application. Recognize that defrost control might be required.
DX Dedicated Outdoor Air System (DOAS) Units
A DX dedicated outdoor air system (DX-DOAS) unit is
used to separately condition outdoor air brought into the building for ventilation or to replace
air that is being exhausted. (As such, select a DX-DOAS unit based on its latent
dehumidification capacity, not necessarily on its total air-conditioning capacity.) This
conditioned outdoor air is then delivered either directly to each occupied space, to small HVAC
units located in or near the space, or to a central air handler serving the spaces. Meanwhile,
the local or central HVAC equipment is used to maintain space temperature. Treating outdoor air
separately from recirculated return air makes it more straightforward to verify sufficient
ventilation airflow and enables humidity control in the occupied spaces. Decoupling the latent
load from the sensible using a DX-DOAS can make both the dehumidifier and sensible cooling
equipment more efficient.
DX-DOAS units use a vapor compression refrigeration cycle as part of the system to cool the air
below its dew point and condense the moisture on a dehumidifying coil.
AHRI Standard 921 establishes requirements for the
testing and rating of moisture removal capacity and moisture removal efficiency of DX-DOAS
units. ASHRAE Standard 198 prescribes test methods for rating
DX-DOAS units.
DX-DOAS units may require simultaneous heat rejection to the reheat coil and/or another condenser
(air- or water-cooled), because it may not always be possible or warranted in the application to
reject the total heat of rejection from the dehumidifying coil to the conditioned airstream. A
rainproof air intake and cooling capacity modulation (or staging) are important. With constantly
changing weather conditions, even throughout the day, compressor capacity must be adjusted to
prevent coil freeze-ups. Basic components are shown in Figure 8.
Auxiliary heating may be required for year-round operation in some climates. Water- and
steam-heating coils should have freeze protection features. When using indirect-fired gas
heaters, the combustion chamber should be resistant to condensation.
DX-DOAS units may be interfaced with a building automation system (BAS) to control the
unit’s on/off status and operating mode, because most spaces do not require continuous
ventilation or replacement air. Air exhaust systems must also be synchronized with the DX-DOAS
unit to maintain proper building pressurization.
The inclusion of exhaust air energy recovery within DX-DOAS units provides the opportunity to
transfer energy between the two airstreams. A typical arrangement is shown in Figure 9.
For more information on DOAS, see Chapter 51.
Indoor Swimming
Pool Dehumidifiers
Indoor pools (natatoriums) are an efficient application for mechanical
dehumidifiers. Humidity control is required 24 h a day, year-round. Dehumidifiers are available
as single- and double-blower units (see Figures 10 to 13).
AHRI Standard 911 establishes requirements for testing
and rating moisture removal capacity and moisture removal efficiency of indoor pool
dehumidifiers. ASHRAE Standard 190 prescribes test methods for
rating these units.
The latent heat (LH) from dehumidification (see Figure
2) comes nearly exclusively from pool water (excluding humidity from makeup air and
latent heat from large spectator areas). Loss of evaporation heat cools the pool water. By
returning evaporation heat losses to the pool water, the sensible heat between points C and D of
Figure
2 is not rejected into the supply air, which can reduce supply air temperature by
approximately 8 K. ASHRAE Standard 90.1 requires that
heated pools be provided with a vapor-retardant pool cover unless 60% of their energy for
heating is site recovered. Use of compressor waste heat for pool water heating may satisfy this
requirement.
Energy Considerations. The pool water temperature,
space temperature, and relative humidity conditions maintained at a facility directly affect
occupant comfort, dehumidifier size, and operating costs. It is important that the design
engineer understand the effects of changes to these conditions to properly establish realistic
operating conditions for a given project. Operating temperatures can change dramatically,
depending on the type of pool being designed. See Table 2 in Chapter 6 of the 2023 ASHRAE Handbook—HVAC Applications for additional
information.
The peak dehumidification load and peak energy conditions may not be concurrent in a natatorium.
The peak dehumidification load generally occurs on a summer design day where the latent load
from ventilation air is at its peak. The peak energy condition often is in the winter, when
cold, dry ventilation air is a significant heating load and dehumidification credit to the
space. In addition to extra heating costs, introducing more outdoor air than required by code in
winter increases operating costs by driving space relative humidity levels down. This increases
pool water evaporation and, consequently, pool water heating, makeup water, and pool chemical
costs. Low humidity levels also increase bather discomfort through the evaporation effect across
the surface of bathers’ skin, causing a chilling effect on leaving the pool.
Fan energy can be a significant portion of the total energy consumed by a natatorium dehumidifier
because the supply air fan operates constantly and delivers relatively high amounts of air.
Many dehumidifiers have exhaust fans to maintain the natatorium at a negative pressure. This
exhaust air is energy rich, and heat recovery should be considered. Dehumidifiers are available
with heat recovery such as heat pipes, glycol-runaround loops, compressorized heat pumps, and
plate heat exchangers that transfer heat from the energy-rich exhaust air to cold incoming
ventilation air (see Chapter 26).
Condensation. Note that the space dew point in most
pools is above 17°C. Even when space conditions are properly maintained, there
is still a significantly higher chance, compared to traditional conditioned spaces, that
condensation might occur in the space or within the HVAC system. Condensation is possible in
winter or summer.
Most codes have adopted ASHRAE Standard 62.1 to determine the amount
of outdoor air required for acceptable indoor air quality. Introducing outdoor air that is
cooler than the room dew-point temperature could lead to condensation. This is especially
important in areas that experience cold winters. If condensation might occur, preheating the
outdoor air is required.
Most dehumidifiers have a cooling mode. The units are generally designed to ensure supply air to
the space is warmer than the space dew point. When adding additional cooling capacity to a
dehumidifier, summer condensation is a concern if supply air could be cooled below the dew point
of either the outdoor air or the space.
Designers are encouraged to verify that all necessary measures to avoid condensation have been
taken, especially when modifying or customizing standard products from manufacturers. Discharge air must always be supplied at a temperature higher than the
room dew-point temperature. Similarly, blended airstreams must not be allowed to result
in temperatures cooler than the space dew point.
Single-blower pool dehumidifiers (Figure 10) are
similar to general-purpose dehumidifiers (see Figure 4),
with the following exceptions:
-
Recovered heat from the refrigeration circuit can be used to provide heating to one
or more pools or for domestic water preheat.
-
All components in the airstream must be corrosion-resistant to chloramine-laden air.
Electrical panels must be fully isolated from the chloramine-laden airstream.
-
The pool water heater must be resistant to chlorinated water.
-
Cross-contamination prevention features in the pool water heater are not required,
but should be considered to prevent introducing refrigerant oil to the pool water if
a breach occurred.
-
Polyol ester (POE) refrigerant oil will damage polyvinyl chloride (PVC) piping.
Figure
11 shows a double-blower pool dehumidifier with economizer dampers and a full-sized
return fan located upstream of the evaporator coil. This configuration can provide up to 100%
makeup air to maintain humidity levels, which can be attractive when the outdoor dew point is
below the required indoor dew point during mild weather, or in climates when enough hours of
dry- and wet-bulb conditions are below the level to be maintained. Preheating outdoor air may be
required to prevent condensation inside the mixing box. Also, this configuration does not
recover energy from the warm, moist exhaust air. During dehumidifying coil operation, the amount
of makeup and exhaust air is limited by outdoor conditions, especially during the heating
season. Cold makeup air may lower the mixed-air temperature to the point where the dehumidifying
coil cannot extract any moisture. Be careful during economizer operation to not introduce more
outdoor air than required by code, so as not to lower the space humidity below design levels, as
discussed in the section on Energy Considerations.
In some regions, it is economically attractive to remove moisture from the exhaust air to recover
its latent heat. In this case, the dehumidifying coil is installed in the return air section. Figure
12 shows a double-blower pool dehumidifier with economizer dampers and return fan
located downstream of the evaporator coil. A damper system can also be incorporated to exhaust
before the evaporator coil during colder conditions and after the evaporator during warmer
conditions. This configuration recovers energy from the warm, moist exhaust air; however,
exhausting air from downstream of the evaporator coil also reduces the unit’s sensible
capacity by the amount of the exhaust air. The ratio of return air to exhaust air must be
considered to determine the unit’s capacity to remove moisture from the conditioned space.
Figure
13 shows a different unit configuration that addresses concerns related to blower energy
use during the various operating modes. This unit can operate with the supply blower only, or
with the addition of one or two exhaust blowers.
Most manufacturers also offer some means of air-to-air heat recovery between the exhaust and
makeup airstreams (see Chapter 26). During
cold weather, this arrangement preheats entering makeup air with heat recovered from the exhaust
airstream. Latent heat recovery may not be practical, however, because it transfers moisture to
the entering air, thus possibly increasing dehumidification requirements.
Control systems should be compatible with building automation systems; however, the BAS must not
disable dehumidifier operation because indoor pools always need some dehumidification,
regardless of occupancy, and require specialized control sequences.
General Considerations. The primary function of an
indoor swimming pool dehumidifier is to maintain the space dew-point temperature at the design
level year round and to provide adequate air circulation to comply with minimum air change
rates.
For more information on indoor swimming pool (natatorium) applications, see Chapter 6 of the 2023
ASHRAE Handbook—HVAC Applications.
Types of Equipment. Indoor swimming pool dehumidifiers
are available in single- and double-blower configurations (see Figures 10 to 13).
Heat from the refrigeration circuit can be (1) used to reheat supply air, (2) used to heat pool
water, or (3) rejected to the outdoors by an optional air- or water-cooled condenser. Equipment
configurations are available to use the heat for any combination of these three purposes.
The equipment can be located indoors or outdoors, and may be manufactured as a single package or
as a split system with a remote condenser. Avoiding remote condensers with long refrigerant
lines reduces refrigerant charge. Indoor, air-cooled condensers are typically equipped with a
blower-type fan suitable for duct connections. An optional economizer allows for introduction of
up to 100% of outdoor air (turning off the compressors) when conditions are appropriate.
When selecting a dehumidifier for an indoor swimming pool application, several questions need to
be addressed to ensure that the dehumidifier can maintain the space conditions:
-
In what mode of operation is the dehumidifier rated?
-
Does the rating include ventilation air, and what effect, if any, does it have on
dehumidifier performance?
-
Does the unit include exhaust air, and what effect, if any, does it have on
dehumidifier performance?
-
Does the cost of running a second fan offset the energy saved by the economizer?
-
Will the dehumidifier maintain the desired space conditions during all modes of
operation?
Design for ice rink dehumidifiers is similar to that of general-purpose dehumidifiers (see Figure 4).
However, because of the lower temperatures, airflow and dehumidifying and reheat coils are
selected in accordance with the following conditions:
-
The dehumidifying coil may or may not have an air bypass, depending on the location
of makeup air intake and/or coil selection.
-
The dehumidifying coil may have means to defrost or to prevent frost formation.
-
Makeup air treatment is limited.
For large spectator areas, special makeup air dehumidifiers may be required.
General Considerations. For community ice rinks with
small spectator areas (or none), it is customary to install two small dehumidifiers over the
dasher boards in a diagonal arrangement, 3.7 to 4.6 m above the ice surface (Figure 14).
Take care that discharge air from dehumidifiers is not directed toward the ice surface. Forced
airflow at any temperature may damage the ice surface. Ice rinks with large spectator areas have
different requirements.
The spectator area is typically maintained at 21°C. To limit moisture migration
to the ice sheet, space conditions must be maintained at 50% rh or less. The resulting dew-point
temperature is then 10°C or less. The air temperature over the ice sheet in the
dasher boards, however, is approximately 3 K lower than the air in the
spectator area. With an air temperature of 18°C and a dew-point temperature of
10°C or less, fog over the ice sheet cannot develop. As a general rule,
mechanical ice rink dehumidifiers are most effective for condensation and fog control when
dry-bulb space temperature is at least 8 K above the dew point. For additional fog
and condensation prevention methods, see Chapter 44 of the 2022 ASHRAE
Handbook—Refrigeration.
Industrial products and surfaces can sweat, causing corrosion, dimensional distortions, and other
deterioration from excess humidity in the air. In some cases, this humidity is caused by leakage
or infiltration; in other cases, it may be from indoor storage or processes. Normal air
conditioning is not always adequate to control excess humidity, leading to material or
structural damages and cool but damp working conditions. Industrial dehumidifiers use
direct-expansion refrigeration coils to remove moisture and thus lower the supply air dew point
to
-
Prevent undesirable condensing or sweating on products and surfaces
-
Improve product/process quality
-
Help reduce building repair and maintenance costs
-
Provide a comfortably dry working environment (max. 60% rh)
-
Minimize biological pollutants such as mold spores
Some mechanical dehumidifiers may also contribute to space heating and/or cooling, recover heat
energy for processes, and/or recover water for allowable purposes.
Sources of Humidity. Indoor air
quality is affected by several key factors, which vary in importance depending on the location
of the building and on the activity for which a building is designed. Relative humidity is
usually a critical air quality factor, with high indoor relative humidity resulting from the
following sources of moisture:
-
Increased quantities of humid outdoor air brought in to improve air quality
-
Openings, infiltration and permeation
-
Moisture produced by occupants
-
Moisture released by products or processes
Moisture migrates from areas of high vapor pressure to areas of low vapor pressure. In the
summer, when the outdoor air is warm and humid, moisture can find a path to the interior of a
cooler or drier structure. This could be from openings in the building such as doors,
infiltration through cracks and poorly sealed joints, or permeation in the case of low-quality
or nonexistent vapor retarders. In many instances, the primary source of humidity is from
outdoor air purposely brought into the structure to meet air quality standards, or to replace
air being exhausted because of contamination.
Occupants contribute to the moisture load through respiration and perspiration; amounts depend on
the number of people and their activities. A worker involved in heavy lifting can generate seven
times the moisture of a co-worker seated at rest. In agricultural or laboratory structures,
animals also produce a moisture load.
Indoor materials or processes may give off moisture. Storing or cooking fruits, vegetables, or
other foodstuffs may release moisture indoors. The presence of open tanks of water or the
storing or handling of wet materials, such as wood, may also release moisture indoors.
Moisture dissolved in indoor air will condense onto any surface that is at a temperature lower
than the room air’s dew-point temperature. This can lead to quality and productivity
problems or even to damage to the building and plant equipment. Rust and corrosion can affect
metal surfaces, electrical controls and contacts, etc., which can lead to increased costs and
even to potentially hazardous conditions.
For typical conditions (temperatures and relative humidities) of industrial applications, see
Table 1 of
Chapter 15 of the 2023 ASHRAE Handbook—HVAC
Applications.
Dehumidifiers for Controlled Environment Agriculture
(CEA)
If the main conditioning system is not selected to handle the high dehumidification load of a
grow or drying space, the engineer may use a combination of a primary cooling air-handling
system combined with in-room or ducted dehumidifiers to support the main cooling system for the
water load in these rooms. Dehumidifiers for controlled environment agriculture share many of
the characteristics of general-purpose dehumidifiers (see Figures 4
and 7), but may have a few
additional design considerations because of the specialized nature of their application:
-
Dehumidifiers can be the primary total environmental control or used in conjunction
with a primary cooling system.
-
Care must be taken in the engineering calculations of load to ensure that
the combined systems can address the loads for the entire duration of
the plant’s life cycle, day and night, and all associated
transition periods.
-
The watering rate can vary widely between growing recipes; a thorough
discussion with the grower must be had to understand the water and
lighting loads for each stage of life of the plant when that plant
enters and leaves that room.
-
The capacity of dehumidifiers is typically reported on a
litres-per-day rate. Careful consideration of the
calculations should be undertaken for the hourly water removal rate,
calculated at the actual room conditions at the time and additional
sensible heat component added by the dehumidification units.
-
Air distribution is of critical importance in grow rooms, especially when using
unitary dehumidification units with ducted primary conditioning systems.
Dehumidification outlets provide warm or hot very dry air, and if that air is
directed at the plants in either grow rooms or drying rooms, the plants will realize
localized microclimates.
-
In a grow room, this causes these plants to dry out more quickly. In some
cases this will cause these plants to grow faster than the rest of the
room, eventually running short of water, exposing them to risk of
failure. Should the grower increase the amount of watering, then the
balance of plants will be exposed to over-watering, and cause failure as
well.
-
In drying rooms, product can be damaged from drying too quickly or by
over-drying causing damage to the plant material and decreasing product
quality.
-
Dehumidifiers for growing rooms in CEA are typically much larger than general-purpose
or portable dehumidifiers, with 240 to 2300 L/day (10 to 90 kg/h)
capacities
-
Great care must be taken with respect to placement with the maintenance
of these units in mind. The larger dehumidification systems can weigh
hundreds of kilograms and require gantries or trolleys to
move when they require replacement.
-
Dehumidifiers of this type are still under severe duty loading and will
have abbreviated service lives when compared to dehumidifiers in more
conventional applications. As such, maintenance access and ease of unit
“swapping” is crucial to the successful future operation of
these systems.
-
Keep in mind that replacement of units is preferable upon component
failure to reduce the downtime impact on the rooms and keep the rooms
clear of debris associated with maintenance activities.
-
Use an evaporator bypass damper, variable airflow rate, and/or defrost cycle to
ensure operation during cooler lights-off or end-of-grow-cycle conditions, which can
be as low as 18°C at 40% rh (4°C dp).
-
Careful consideration must be made with regard to the derating of the
capacity of the dehumidifiers in reduced temperature environments, such
as nighttime use and more prevalently drying room use.
-
Dry rooms may have significant initial water vapor loading for the first
two days of the dry period to reach 50% weight goals to reduce the
potential propagation of molds within the harvested materials.
-
The transition from day to night in a grow room is the largest water
removal rate ratio, effectively a negative sensible heat ratio where the
combined HVAC system should only be dehumidifying and warming the room
with basically neutral air. This period is generally more than 30 min
and less than an hour, depending upon the size of plants. This period,
if not properly addressed, exposes the plants to very high relative
humidity, both choking the plants ability to transpire, causing
condensation, and propagation of fungus and bacteria.
-
Use minimum efficiency reporting value (MERV) 13 filters or better to provide
adequate mold spore reducing filtration (see ASHRAE Standard 52.2 for details on MERV filters)
-
Controls integration between the dehumidification units and the primary
cooling/conditioning system is required to eliminate hunting of the room. Typical
on-board controls for unitary dehumidifiers reference local relative humidity, and
that sensor will be affected by changes in the room temperature.
-
For instance, cycling DX type systems can cause run away hunting between
the primary cooling and the dehumidification systems, causing over
drying of the room, or over heating of the room.
-
Most dehumidification units are fitted with remote relays to trigger
their stages, and those should be tied into an electronic controls
system so that the dehumidification units may be staged appropriately
along with the cooling and reheat provided by the main conditioning
system.
-
Many rooms require multiple dehumidifiers to address the water load. By
not interconnecting them, large swings in humidity will be experienced,
even if using staggered set points between the units.
General Considerations. Because most grow rooms are
sensible cooling primary load facilities, care is needed to ensure that heat gain from the
dehumidification process can be managed by the existing or designed sensible cooling devices. A
CEA dehumidifier can be selected with remote heat rejection to provide some or all of the
sensible cooling required. This approach may achieve better energy management by ensuring that
the facility is not forced to oversize or overuse sensible cooling devices to counter heat gain
from dehumidification equipment in the space.
Grow rooms can require washdown cycles. Ensure that selected equipment has washdown capabilities
to reduce pathogen and mold growth, and that filters are easily accessible for regular
replacement.
CEA rooms should be considered process air and handled appropriately as such. The typical
relative humidity excursions from set point that are typically acceptable in a comfort cooling
environment are not acceptable for grow rooms.
Dehumidification of grow rooms is a wildly variable application of HVAC equipment. The room
calculations should be made for selections of the equipment in an all-sensible environment:
lights and fans on, but no plants. They should also be made for the heaviest day condition:
lights on and loaded with plants transpiring at the maximum expected amount. What is commonly
missed is calculating the day-night transition and the steady-state night conditions. All four
of these major load cases must be satisfied successfully by the combination of central cooling
and unitary dehumidification units. Further, these load cases should be calculated for young
plants entering rooms that can be over-dried with systems that cannot be turned down or bypassed
to reduce the water removal rate.
When looking at the calculations for the sensible and latent heat loads within the room, the
engineer should be mindful that the plants themselves do not constitute a latent load as they
are not a heat source. The plants will take the energy from the lights, and as long as the vapor
pressure deficit is correct for them to transpire, the transpiration will convert the sensible
load from the room into a latent load through the latent heat of evaporation. With this in mind,
the calculations can be made for the maximum sensible load (lights on, no plants) and the
maximum water removal rate, which can actually require more energy than the sensible case,
making the SHR of the total system effectively 0 or negative.
The calculations should not add the calculated sensible and latent loads. The calculation should
start with the total sensible energy gain into the room as case 1. This is very easily addressed
by the main cooling system. Then, the watering recipes should be examined to find the steady
state transpiration load into the room. This transpiration converts sensible heat into latent
heat through adiabatic cooling. When looking at case 2 (lights on/heavy plants), the engineer
may find that the water load going into the room creates a latent load that exceeds the lighting
power. This is often the case in nurseries where there can be heavy young, non-flowering plants,
within a space with nursery-level lighting. The engineer should then select dehumidification
equipment to address the water load, taking into consideration the contribution from the main
cooling equipment, and then recalculating the main cooling equipment with the dehumidification
heat rejection taken into consideration. In many cases, the reheat provided by the
dehumidification equipment can make up for the sensible shortfall, allowing the main cooling
equipment to be roughly equivalent size as the sensible case. In many existing installations,
Engineers have made the mistake of adding the sensible and latent loads together.
Then, the selected equipment should be calculated against the two final operating conditions:
case 3 (lights off/plants transpiring) and case 4 (lights off/plants asleep). Case 3 represents
a pure dehumidification operation case. The sensible heating elements are all shut down, while
the plants continue to transpire at the same rate they had during the day for a period of about
40 minutes (±15 min). However, the systems should not immediately decrease the
temperature set point at the same time, or there will be an over-cooling (further pressure on
relative humidity) followed by an over-drying condition when the plants go to sleep. Case 4
represents the lights off hours where the plants have gone to sleep. The transpiration load
typically decreases to about 5 to 10% of the daytime rate and there is no real sensible loads
aside from circulation fans and the building envelope.
The issue here is that the equipment will not be sized appropriately (oversized) and cause short
cycling. This short cycling not only leads to shorter equipment life, but it causes severe
control excursions with respect to room humidity. The classic example is a dry room served by a
two stage direct-expansion packaged HVAC unit when the DX coils both cycle off. The wet coil
allows the discharge air humidity to spike and it takes some time for the system to cycle back
on. This can cause excessive condensation within the supply ducts, water intrusion into the
rooms, etc.
Dehumidification for CEA rooms is crucial to maintaining the water vapor levels, and what growers
call vapor pressure deficit (VPD). This is simply the
concept of relative humidity (rh) with a specific bent towards the vapor pressure of water
rather than just a percent of total carrying capacity. The plants are able to transpire when the
vapor pressure deficit is ideal across the stomata. Growers target different VPDs for different
parts of the plant’s life, the type or strain of plant, and what they are trying to
achieve with that plant.
Maintenance of VPD is more important than maintaining temperature. If the plant can continue to
transpire, even in over- or under-temperature excursions, there will not likely be damage to the
plants. In this way, dehumidification equipment becomes the driving factor in the system design.
Over-temperature conditions of a space is OK, as long as it is not too dry. However, allowing a
space to get overly wet in order to maintain the space temperature is a recipe for fungus and
poor plant health, even for short periods of time. Very great care should be taken when
considering equipment to eliminate short cycling, maintenance of off-cycle conditions, etc.
VPD, like relative humidity, is based on temperature. So, it is possible to achieve the proper
VPD at any given operating temperature. Because of this, it should be assumed that the plant can
and will transpire water into the space at the given watering rates, no matter the temperature
within the room. It also means, that great care should be taken when transitioning set points
and operating conditions.
The largest example of this is the change from day mode to night mode. Day mode set points can
generally be in the Fsupper 20s or over 30°C with relative humidity in the 55
to 65% range. By the end of the day, the plants are transpiring at their steady day awake
levels, and then the lights are either dimmed and turned off or just shut off quickly. In this
event, it is critical to keep the night set point from being a double-step-change on the control
systems because the lights have gone out, the sensible load in the room has all but been
eliminated and the plants continue to transpire. It is very typical to see relative humidity
spike out after the lights shut off in conventionally constructed grow rooms. When this happens,
damage can occur to the plants as they suffocate in this condition. The propagation of fungus is
also typically associated with this transition period.
In addition to the above conditions, it should be noted that grow rooms are to be considered
harsh environments. There is dust and intense UV light, and the space is typically cleaned with
strong chemicals between harvests to eliminate pests, fungus, bacteria, etc. Ensure that the
equipment, ductwork, filters, etc., have been selected to give long service life even if treated
with chemicals such as chlorine dioxide, hydrogen peroxide, etc. Further, the operators may use
a wash-down approach to these spaces. Investigate the intended cleaning standard operating
procedures or consider signage on the equipment if it might be susceptible to certain chemicals
or conditions.
Tunnel Dryer Dehumidifier
A general-purpose dehumidifier system removes moisture from a product inside the drying tunnel.
Air at the desired temperature and humidity constantly recirculates around the product,
continuously removing moisture. Tunnel dryer dehumidifier design is similar to that of a
general-purpose dehumidifier (see Figure 4).
Because of the closely controlled space humidity, temperature, and airflow, select the
dehumidifying and reheat coils in accordance with the following conditions:
-
The dehumidifying coil must have variable apparatus dew-point control; it might also
have an air bypass, depending on coil selection.
-
The reheat coil needs variable reheat control.
-
A means of external heat rejection is required (e.g., heat rejection to a heat pump
loop, chilled-water loop, fluid cooler, or remote air-cooled condenser).
Process Considerations. A precision control system is
required to prevent overdrying by automatically shutting off or by reducing capacity when the
moisture content in the product has reached the desired level. Continuous control of temperature
and relative humidity improves the drying process and maintains product quality, and potentially
can reduce operating cost compared to ventilation only. Users should be able to specify drying
temperature to best preserve initial product quality.
Design Considerations. The usual operating range for
tunnel dryer dehumidifiers is 15 to 38°C db and 10 to 38°C dew
point. An average air velocity of 2.54 m/s across the tunnel net free area is
recommended for effective drying.
Tunnels should be no longer than 9 m, to prevent saturated air at the tunnel’s
end. Construction must be air- and vaportight to prevent moisture infiltration from surrounding
spaces.
Some products may produce corrosive contaminants, so tunnel dryer dehumidifier components should
be corrosion resistant.
For a typical installation of a tunnel dryer dehumidifier, see Figure 15.