Ultraviolet (uv) energy is a form of electromagnetic radiation with a
wavelength shorter than that of visible light, but longer than x-rays. UV radiation is present in
sunlight and constitutes about 10% of the total electromagnetic radiation output from the sun. The UV
wavelength spectrum can be subdivided into following ranges and bands within the range:
-
UV-A (long-wave; 400 to 315 nm)
-
UV-B (medium-wave; 315 to 280 nm)
-
UV-C (short-wave; 280 to 100 nm): the most effective wavelengths for germicidal control
Although the sun emits all UV wavelengths, UV-C and lower wavelengths are blocked by the ozone layer in
the earth’s atmosphere. Thus, UV-C wavelengths for practical use are produced by germicidal UV
sources such as lamps.
UV below 240 nm can lead to ozone formation in the air. Care must be taken, and caution is urged when
using UV products operating near this wavelength band.
Use of UV lamps and lamp systems to disinfect surfaces, room air, and airstreams dates to about 1900; see
Reed (2010), Riley (1988) and Schechmeister (1991) for extensive reviews of UV disinfection. Early work
established that the most effective UV wavelength range for inactivation of microorganisms was between
220 to 300 nm, with peak effectiveness near 265 nm. UV was used during the polio outbreak of the 1950s
and the Mycobacterium tuberculosis (TB) outbreak of the 1990s; the COVID-19
pandemic led to renewed interest in UV technology.
UV-C energy disrupts the DNA and RNA of a wide range of microorganisms, rendering them harmless (Brickner
et al. 2003; CIE 2003). Figure 1 shows the
relative effectiveness of UV-C energy at various wavelengths to cause DNA damage in a representative
common bacterium; effectiveness is not significantly different for other bacteria and viruses. Most
commercially available UV-C lamps are low-pressure mercury lamps that emit at least 90% of their UV
energy at 253.7 nm, close to the optimal wavelength.
Germicidal ultraviolet (GUV) in the UV-C band has been used in air ducts,
air-handling units, upper-room, and mobile UV-C applications for some time, and its use is becoming
increasingly frequent as concern about energy, maintenance, and indoor air quality increases. UV-C
energy is used as an engineering control to interrupt the transmission of pathogenic organisms, such as
Mycobacterium tuberculosis (TB), influenza viruses, fungi, and possible
bioterrorism agents (Brickner et al. 2003; CDC 2002, 2005; GSA 2003; IES 2022). In addition, it has been
used extensively to irradiate air-conditioning cooling coils to remove biofilms, maintain cleanliness,
and provide energy savings.
This chapter includes a review of the fundamentals of UV-C energy’s impact on microorganisms; how
UV-C lamps generate germicidal ultraviolet energy; the various components that comprise UV-C devices and
systems; and a review of human safety and maintenance issues.
ACGIH. The American Conference of Governmental Industrial
Hygienists; a professional association of industrial hygienists and practitioners of related
professions.
Burn-in time. Period of time that UV lamps are powered on
before they reach stable output, typically 100 h for mercury lamps.
CIE. Commission Internationale de l’Eclairage
(International Commission on Illumination); an independent, nonprofit organization dedicated to the
science and art of light and lighting, color and vision, photobiology, and image technology;
recognized by IS as an international standardization body.
Droplet nuclei. Airborne particles formed from evaporation
of fluids emitted from infected hosts when they cough, sneeze, or talk, containing bacteria or
viruses able to transmit disease from person to person. Droplet nuclei generally have an aerodynamic
diameter less than 5 μm, which allows them to remain suspended in air for long periods; thus,
they can be carried on normal air currents in a room and beyond to adjacent spaces. When inhaled,
droplet nuclei can penetrate into the alveolar region of the lung.
Erythema (actinic). Reddening of the skin, with or without
inflammation, caused by the actinic effect of solar radiation or artificial optical radiation. See
CIE (1987) for details. (Nonactinic erythema can be caused by various chemical or physical agents.)
Exposure. Being subjected to something (e.g., infectious
agents, irradiation, particulates, and/or chemicals) that could have harmful effects. For example, a
person exposed to M. tuberculosis does not necessarily become infected.
Exposure dose. Radiant exposure (J/m2,
unweighted) incident on biologically relevant surface.
Fluence. Radiant flux passing from all directions through
a unit area in J/m2 or J/cm2; includes backscatter (reflection).
Germicidal radiation. Optical radiation able to inactivate
microorganisms.
GUV (germicidal UV). Common term used to describe UVGI.
Irradiance. Power of electromagnetic radiation incident on
a surface per unit surface area, typically reported in microwatts per square centimeter
(μW/cm2). See CIE (1987) for details.
Mycobacterium tuberculosis. The namesake member of the M. tuberculosis complex of microorganisms, and the most common cause of
tuberculosis (TB) in humans. In some instances, the species name refers to the entire M. tuberculosis complex, which includes M.
bovis, M. africanum, M. microti,
M. canettii, M. caprae, and M. pinnipedii.
NIOSH. National Institute for Occupational Safety and
Health; the U.S. federal agency responsible for researching and making recommendations to prevent
work-related injury and illness.
Optical radiation. Electromagnetic radiation at
wavelengths between x-rays (λ ≈ 1 nm) and radio waves (λ ≈ 1 mm). See CIE
(1987) for details.
Peak/center wavelength. Wavelength at which a UV-C source
emits the most intense germicidal energy.
Permissible exposure time (PET). Calculated time period
that humans, with unprotected eyes and skin, can be exposed to a given level of UV irradiance
without exceeding the NIOSH recommended exposure limit (REL) or ACGIH Threshold Limit
Value® (TLV®) for UV radiation.
Personal protective equipment (PPE). Protective clothing,
helmets, goggles, respirators, or other gear designed to protect the wearer from injury from a given
hazard, typically used for occupational safety and health purposes.
Photokeratitis. Defined by CIE (1993) as corneal
inflammation after overexposure to ultraviolet radiation.
Photoconjunctivitis. Defined by CIE (1993) as a painful
conjunctival inflammation that may occur after exposure of the eye to ultraviolet radiation.
Photokeratoconjunctivitis. Inflammation of cornea and
conjunctiva after exposure to UV radiation. Wavelengths shorter than 320 nm are most effective in
causing this condition. The peak of the action spectrum is approximately at 270 nm. See CIE (1993)
for details. Note: Different action spectra have been published for
photokeratitis and photoconjuctivitis (CIE 1993); however, the latest studies support the use of a
single action spectrum for both ocular effects.
REL. Recommended exposure limit for occupational exposure
to UV radiation.
Spectral distribution. Distribution of radiant power
across a range of wavelengths.
Threshold Limit Value®
(TLV®). An exposure level under which most people can work
consistently for 8 h a day, day after day, without adverse effects. Used by the ACGIH to designate
degree of exposure to contaminants. TLVs are listed either for 8 h as a time-weighted average (TWA)
or for 15 min as a short-term exposure limit (STEL).
Ultraviolet radiation. Optical radiation with a wavelength
shorter than that of visible radiation. (See CIE [1987] for details.) The range between 100 and 400
nm is commonly subdivided into
-
UV-A 315 to 400 nm
-
UV-B 280 to 315 nm
-
UV-C 100 to 280 nm
Ultraviolet germicidal irradiation (UVGI). Use of
ultraviolet C-band energy to kill or inactivate microorganisms. UVGI is generated by UV-C lamps that
kill or inactivate microorganisms by emitting ultraviolet radiation, predominantly at a wavelength
of 253.7 nm.
UV-C LED. Light-emitting diode that emits ultraviolet-C
(UV-C) radiation.
UV dose. Product of UV irradiance and exposure time on a
given microorganism or surface, typically reported in millijoules per square centimetre
(mJ/cm2) or microwatt seconds per square centimetre
(μW · s/cm2).
Wall plug efficiency (WPE). Total optical output power
divided by the total injected electrical power.
Wavelength. Distance between repeating units of a wave
pattern, commonly designated by the Greek letter lambda (λ) and typically measured in
nanometres (nm).
GUV inactivates microorganisms by damaging the structure of nucleic acids and proteins at the
molecular level, making them incapable of reproducing. Absorbed UV photons can damage DNA in
various ways, but the most significant damage event is the creation of pyrimidine dimers, where
two adjacent thymine or cytosine bases bond with each other instead of across the double helix
as usual (Diffey 1991). In general, the DNA molecule with pyrimidine dimers is unable to
function properly, resulting in the organism’s inability to replicate or even its death
(Diffey 1991; Miller et al. 1999; Setlow 1997; Setlow and Setlow 1962). An organism that cannot
reproduce is no longer capable of causing disease (Martin et al. 2008).
The survival fraction of a microbial population exposed to UV-C energy is an exponential function
of dose:
where
| N0 =initial number of live microorganisms |
| Nt =number of live microorganisms after any time
Δt |
| Nt/N0
=fraction of microorganisms surviving |
| k =microorganism-dependent rate constant,
cm2/(μW · s) |
| Eeff =effective (germicidal) irradiance received
by microorganism, μW/cm2 |
| Dose= Eff × Δt, (μW · s)/cm2 |
The units shown are common, but others are used as well, including irradiance in W/m2
and dose in J/m2 (note: 1 J = 1
W · s).
Equation (1)
describes an exponential decay in the number of living microorganisms at a constant level of
UV-C exposure. For any application, the ability of UV-C to inactivate microogranisms is a
function of dose, which is the irradiance received at
the target area multiplied by the exposure or treatment time.
Use of Equation (1)
is complicated by the movement of the target microorganisms in the airstream and the fact that
the UV-C irradiance is not of constant intensity within the duct. In addition, the physical
parameters of the duct, duct airflow, duct reflectance, and UV installation have the potential
to affect both the irradiance and the microorganisms’ response to it. As is the case with
upper-room UV installation design, the design parameters for UV-C for in-duct applications are
not simple because of some uncertainty in the data available to analyze them, and because of
secondary effects.
A key difference between surface decontamination and airborne inactivation of organisms is
exposure time. Residence time for in-duct devices is on the order of seconds or fractions of
seconds. In a moving airstream, exposure time is limited by the effective distance in which the
average irradiance was calculated; for instance, at 2.54 m/s, 0.3 m of distance
takes 0.12 s. Conversely, when irradiating surfaces in an HVAC such as cooling coils, as well as
upper- or whole-room air treatment UV systems, exposure time is typically continuous, so much
lower levels of UV intensity are required.
Susceptibility of Microorganisms to
UV Energy
Organisms differ in their susceptibility to UV inactivation; Figure
2 shows the general ranking of susceptibility by organism groups. A few examples of
familiar pathogenic organisms are included in each group for information (see Table 1). Note that
it is impossible to list all of the organisms of possible interest in each group. Depending on
the application, consult a public health or medical professional, microbiologist, or other
individual with knowledge of the threat or organism(s) of concern.
As shown in Figure
2, viruses and vegetative bacteria are the most susceptible to UV-C, followed by the
Mycobacteria, bacterial spores, and, finally, fungal spores, which
are the most resistant. In each group, an individual species may be significantly more resistant
or susceptible than others, so this ranking should only be used as a rough guideline. Note that
spore-forming bacteria and fungi also have vegetative states, which are markedly more
susceptible to inactivation than the spores themselves. Using Equation (1), it is clear that
larger values of k represent more susceptible microorganisms and
smaller values represent less susceptible ones. Units of k
(m2/J) are the inverse of the units used for dose.
Using k values to design HVAC duct systems can be challenging. Values
of k vary over several orders of magnitude, depending on organism
susceptibility, wavelength, and values reported in the literature for the same microorganism
sometimes differ greatly. An updated list of published susceptibilities of a variety of species
can be found in Masjudi et al. (2021). Not that this publication uses D90 values instead of
k; to convert from D90,
The wide variation for a single-species results from several factors, the most important of which
is differences in the conditions under which measurements were conducted (in air, in water, on
plates). Especially for many of the vegetative organisms, the amount of protection offered by
layering, organic matter, humidity, and components of ambient air can significantly affect their
susceptibility to UVGI (VanOsdell and Foarde 2002). Take care when using published values, and
obtain the original papers to evaluate the relevance of the k value
of any particular organism to a specific application.
3. GERMICIDAL ULTRAVIOLET SOURCES AND
EQUIPMENT
Although other options exist, currently the most energy-efficient UV-C lamps and most widely used
sources are low-pressure mercury discharge lamps. These lamps contain mercury, which vaporizes
when the lamp is lit. The mercury atoms accelerate because of the electrical field in the
discharge colliding with the noble gas and reach an excited stage. The excited mercury atoms
emit almost 85% of their energy at 253.7 nm wavelength. Very little energy is emitted in the
visible spectrum, so the remaining energy results in various other wavelengths in the UV
spectrum (mainly 185 nm). However, most UV-C lamps used for most applications are made with a
special glass that prevents the 185 nm wavelength from being emitted from the lamp.
UV low-pressure mercury lamps exist in different shapes, which are mostly based on general
lighting fluorescent lamps:
-
Cylindrical or linear lamps may be any
length or diameter. Like fluorescent lamps, most UV lamps have electrical connectors
at both ends, but single-ended versions also exist. Typical diameters are 28
mm T8, 20 mm T6, and 16 mm T5.
-
U-tube lamps have the electrical connector
at one end. They have a continuously curved bend at the outer end.
UV low-pressure mercury lamps can be grouped into the following three output types:
-
Standard-output lamps operate typically at
425 mA.
-
High-output lamps have hot cathode
filaments sized to operate from 800 up to 1200 mA. Gas mixture and pressure are
optimized to deliver a much higher UV-C output while maintaining long lamp life, in
the same lamp dimensions as standard-output lamps.
-
Amalgam lamps have hot cathode filaments
sized to operate at 1200 mA or higher. The gas mixture, pressure, and sometimes lamp
diameter have been optimized for delivering even higher UV output without
deteriorating lamp life.
As shown in Figure 3, UV lamps use
electrodes between which the electrical discharge runs and are filled with a noble gas such as
argon, neon, or a mixture of the two. A small amount of mercury is present in the envelope.
Hot-cathode lamps emit electrons through thermo-ionic
emission. The electrodes consist of electrical filaments coated with a special material that
lowers the emission potential. The electrodes are heated by current before starting the
discharge and, once started, the discharge current itself can maintain the heat. Hot-cathode
lamps typically allow much higher power densities than cold-cathode lamps, and thus generate
much more UV-C intensity.Though more efficient, hot-cathode lamps are sensitive to on/off
cycles.
The outer envelope of UV-C lamps is made of special UV-transmitting glass or quartz. Special
wires are sealed into this envelope to allow transmission of electrical energy to the
electrodes, in a fashion similar to fluorescent lamps.
Two types of glass are used for UV-C lamps. Specialized soft glass is used to produce UV-C lamps
that emit 253.7 nm, but the ozone-producing wavelength of 185 nm is filtered out. Quartz glass
(hard) can be used to produce UV lamps either with the 253.7 nm output wavelength or with both
the 185 and 253.7 nm output wavelengths by changing transmission properties of the quartz.
To maintain UV output over time, the inside of the glass/quartz tube is typically coated with a
special protective layer to slow down the decrease of UV transmission over time.
Mercury can be present in UV lamps as a pure metal or as an amalgam. The amount of mercury is
always (slightly) overdosed because some mercury will be chemically bound during the life of the
lamp. The actual amount of mercury in the lamp varies, depending on the application, but it can
be very small (less than 5 mg). An amalgam is used in lamps having a higher wall temperature
because of their higher design working currents. The amalgam keeps the mercury pressure constant
over a certain temperature range, providing more stable UV output over that range.
UV-C Lamp Drivers or Ballasts
All mercury gas discharge lamps, including UV lamps, require an electronic power supply (i.e.,
driver) or ballast to operate. The power supply provides a high initial voltage to initiate the
discharge, and then rapidly limits the lamp current to safely sustain the discharge.
The ballast must match the lamp specification, especially lamp current and power. To maximize
lamp lifetime, keep electrode preheating and starting conditions in mind. Electronic ballasts
typically operate at high frequencies to 30 to 100 kHz. It is strongly advised to use the
recommended power supply for each lamp type because less than optimum conditions will affect the
lamp's starting characteristics, UV-C output, and operating life.
Circuit Type and Operating Mode. Ballasts and drivers
for low-pressure mercury lamps are designed according to the following primary lamp operation
modes:
-
In preheat, lamp electrodes are heated
before beginning discharge, and no auxiliary power is applied across the electrodes
during operation.
-
In rapid start, lamp electrodes are heated
before and during operation. The ballasts have special secondary windings to provide
the proper low voltage to the electrodes during operation. The advantages include
smooth starting, longer lamp life, and dimming capabilities.
-
Program start drivers incorporate starting
steps. The first step applies voltage to electrodes until they are heated to an
optimal temperature. The second step applies a lower voltage across the electrodes,
thus igniting them with a minimal loss of the filaments’ emissive material.
This minimal loss ideally equates to a longer lamp life.
-
Instant-start drivers do not heat the
electrodes before operation. Drivers for instant-start lamps are designed to provide
a relatively high starting voltage (compared to preheat and rapid-start lamps) to
initiate discharge across the unheated electrodes. They are not recommended for
cold-air applications or if frequent switching is needed.
Preheat mode is more efficient than rapid start, because separate power is not required to
continuously heat the electrodes. Electronic drivers with preheat or program start offer smooth
starting, long life, and good switching behavior.
Instant-start operation is more energy efficient than rapid or program start, but output is
generally lower and lamp life can be shorter when lamps are frequently switched on and off.
Energy Efficiency. UV lamps convert roughly 30 to 40%
of the input power to UV output. Additionally, some of the power supplied into a UV lamp system
produces waste heat energy. There are two primary ways to improve efficiency of a UV lamp
system:
Audible Noise. Because electronic high-frequency
drivers have smaller magnetic components, they typically have a lower sound rating and should
not emit perceptible hum. Most electronic drivers are A-rated for sound.
Electromagnetic Compatibility. Because they operate at
high frequency, electronic drivers may produce electromagnetic interference (EMI), which can
affect any operating frequency, or radiofrequency interference (RFI), which applies only to
radio and television frequencies. This interference could affect the operation of sensitive
electrical equipment, such as system controls, televisions, or medical equipment. Good-quality
electronic drivers should incorporate features necessary to maximize protection for the
operating environment and to operate well within regulatory limits.
Inrush Current. All electrical devices, including
power supplies, have an initial current surge that is greater than their steady-state operating
current. National Electrical Manufacturers Association (NEMA) Standard 410 covers worst-case power supply inrush currents. All
circuit breakers and light switches are designed for inrush currents. The electrical system
should be designed with this issue in mind.
Total Harmonic Distortion (THD). Harmonic distortion
occurs when the wave-shape of current or voltage varies from a pure sine wave. Except for a
simple resistor, all electronic devices, including electromagnetic and electronic power
supplies, contribute to power line distortion. THD is generally considered as the percent of
harmonic current the power supply adds to the power distribution system. ANSI Standard C82.11 for electronic drivers specifies a maximum THD of 32%.
However, most electric utilities now require that the THD of electronic drivers be 20% or less.
Dimming. Unlike other lamp designs, low-pressure
mercury UV lamps can only be dimmed when electrode temperature is maintained while lamp arc
current or voltage is reduced.
Electronic dimming drivers alter the output power to
the lamps in the driver itself, driven by a low-voltage signal into the driver circuit. This
allows control of one or more drivers independent of the electrical distribution system. With
dimming electronic systems, a low-voltage control network can be used to group drivers into
arbitrarily sized control zones. Dimming range differs greatly; most electronic dimming drivers
can vary output levels between 100% and about 10% of full output, but drivers are also available
that operate lamps down to 1% of full output.
Germicidal Lamp Cooling and Heating
Effects
Output of UV lamps is dependent on mercury vapor pressure within the lamp envelope. The mercury
vapor pressure is controlled by the temperature of the cold spot (the coldest portion of the UV
lamp during lamp operation), as shown in Figure
4. If the mercury vapor pressure is low, UV output will be low because there are not
enough mercury atoms to generate full UV radiation. Too high a mercury vapor pressure can also
decrease UV output, because the excess evaporated mercury absorbs ultraviolet rays generated in
the UV lamp.
In low-pressure mercury lamps, mercury vapor pressure reaches its optimal level in still air at
25°C. Depending on lamp type, the cold-spot temperature must be between
38 and 50°C to reach maximum UV output. In moving air, the cold-spot
temperature of standard lamps may be too low to reach the required UV output (Figure
5). Special windchill-corrected lamps can be designed to make the lamps function more
optimally in cold moving air.
By introducing mercury into the lamp in the form of amalgams, the cold-spot temperature can be
increased to between 70 and 120°C, making it possible to reach optimum UV
output at higher temperatures. Amalgams provide a broadened peak in UV output versus
temperature, so that near-optimum UV output is obtained over an extended range of ambient
temperatures.
Output of UV-C lamps decreases over time. UV-C lamps are rated in effective hours of UV-C
emission, and not in end of electrical life hours. Many UV-C lamps are designed to emit
intensity levels at the end of their useful life that are 50 to 85% or more of that measured at
initial operation (after 100 h burn-in time). Lamp manufacturers’ specification data
should provide information on useful life. UV-C systems should be designed for the expected
output at the end of effective life or the recommended lamp change.
UV-C lamps typically have a useful lifetime of more than one year of constant operation. The
useful lifetime can degrade rapidly if lamps are frequently turned on and off, however,
UV-C lamp intensity is measured in μW/cm2, and manufacturers typically obtain
their lamp intensity measurements by taking the UV-C intensity reading 1 m from the
center of a UV lamp, in an open-air ambient of approximately 24°C and with
approximately zero air movement. ASHRAE Standards 185.1-2015 and
185.2-2014 address test standard protocols for measuring UV-C lamp system outputs and their
ability to inactivate airborne and surface microorganisms inside air-handling units,
respectively.
The irradiance E on a small surface at point P on a distance a from a linear UV-C lamp length AB = L
can be calculated using Equation (2) if the UV output of the lamp is represented by ϕ
(Figure 6):
At shorter distances (a < 0.5L), the
irradiance is inversely proportional to the distance of the measurement point from the lamp, as
can be seen from the following simplified equation.
Induction lamps use an induced current from induction coils to maintain plasma discharge. The
plasma discharge characteristics are similar to standard linear tubes, except no filament is
required to produce electrons. Not having filament electrodes increases the operating lifetime
to around 50,000 h (compared to around 8000 h for a filament-type bulb). Ballasts are
approximately the same volume as those required for filament lamps. Lamps with electrical powers
of 300 W are common, producing about 100 W of UV-C at 254 nm. Induction lamps have been shown to
be very susceptible to cooling effects, as discussed previously.
Excimer lamps are relatively new types of discharge lamps that provide different UV-C wavelength
choices (Blatchley 2022). The most used lamps used for germicidal applications are krypton
chloride (KrCl) lamps, predominantly emitting at 222 nm; because of their popularity in
disinfecting surfaces and air in occupied spaces, this discussion applies mainly to KrCl lamps.
It has been found that a narrow wavelength range of about 200 to 230 nm is significantly safer
to human (and animal) skin and eyes as compared to other UV-C wavelengths. KrCl excimer lamps
have the potential to eliminate microorganisms and viruses safely while people are in occupied
spaces.
The emission of these excimer lamps is based on a molecular emission. The fill gas (krypton and a
small amount of chlorine) forms excimer molecules (KrCl) in an electric discharge; this
discharge excites these molecules, which emit UV at a molecule-specific wavelength of 222 nm.
Because the chlorine would destroy electrodes (usually made of tungsten) on the inside of the
discharge vessel, these lamps are electrodeless. The electrical energy is provided through the
glass wall by outer electrodes.
Various lamp designs are on the marketplace. The original design consists of two axial tubes
where the annular space is filled with the gas. One electrode (usually a highly reflective metal
tube) is mounted on the inside, and a mesh electrode on the outside (Figure 7A). Depending on lamp power,
tube diameters of 25 to 40 mm and lamp lengths of 100 to 300 mm are
typical.
Another type is provided as a whole module, including an optical filter, consisting of up to four
single-tube bulbs (Figure 7B). Two electrodes supply
energy along the axis of the bulbs, provide cooling, and reflect light to the front of the
module. These lamps have a (total) power of 12 W and a size of about 60 × 60
mm.
A third type is a flat micro plasma lamp, where discharge occurs between two flat plates
separated by a much smaller distance than in the other types (Figure 7C). The metal electrodes are
printed on the front and back sides of the lamp. The power range varies between 5 and 70 W, and
the size varies accordingly.
The spectrum of a KrCl lamps shows a (relatively) strong peak at 222 nm and lower continuum
emission up to 270 nm, with a peak at 258 nm. The ratio of the continuum to the 222 nm line
depends on lamp design and varies between manufacturers. Note that the visual appearance of the
operating lamps can vary as well, but typically they appear as pink or lightly blue.
Important: the continuum at wavelengths above 230 nm significantly
influences the photobiological safety rating of these lamps (see the section on Safety). For
highest safety, it is recommended that occupied applications use only filtered KrCl lamps that
block out wavelengths greater than 230 nm (Blatchley 2022), as in Figure
8.
Because the lamps are filled with gas, the UV-C output is instant after turning them on.
Depending on lamp design and driver, the output will only change by a relatively small amount
while the temperature stabilizes. There are no internal electrodes, so lamp lifetime is
typically not influenced by on/off cycling but varies between manufacturers. Note that visual
inspection will not reveal whether a lamp is still emitting far UV-C; measurements of the output
irradiance must be performed to verify proper operation.
Excimer lamps must be operated by lamp specific drivers, usually supplied by the lamp provider.
The driver creates a high-output AC voltage in the range of 3000 to 10 000 V,
depending on lamp type and power. Most modern drivers use pulsed output with pulse lengths of a
few microseconds. Driver input voltage the driver varies by manufacturer, but most lower-power
drivers operate at low-input voltage of 12 to 24 V DC. Wall-plug energy (WPE) efficiency of
excimer lamps is typically less than 5%.
Measuring lamp power of excimer lamps is challenging (high voltage, short pulses, and small
currents), so their power ratings typically refer to the combination of lamp and driver. In the
United States, ANSI Standard LM93 describes these measurement
methods. Additionally, since these lamps are always used in some kind of luminaire with
reflectors, the measurement is limited to irradiance measurements (typically at 1 m
distance). The optical power output of the lamp must be obtained by goniometer measurements.
Radiometers to measure irradiance of KrCl lamps are available. It is important that the detector
is calibrated to the light source that will be measured. For filtered KrCl lamps, calibration at
222 nm is usually sufficient; however, measurement error with unfiltered lamps can be
unpredictably high.
Wavelengths between 100 and 240 nm (including 222 nm) radiation have been shown to create
measurable amounts of ozone. The actual ozone concentration in an application depends on the
output power of the lamp(s) in a room and other parameters, including the design of the lamp
(see the section on Safety). It is recommended to operate KrCl lamps in well-ventilated rooms.
A pulsed xenon system uses a high-pressure arc chamber to ionize xenon gas through a high-voltage
discharge, resulting in emission of intense bursts of broad-spectrum light typically ranging
from 180 nm in the ultraviolet range to the visible and infrared range. Various xenon lamp
shapes, such as linear, spiral, and U-shaped (Rehmet 1980), can be manufactured with appropriate
triggering mechanisms, and the lamp envelope can be tailored to achieve different effective UV
spectral cutoffs (e.g., 370, 240, 190, and 160 nm) for specific applications ranging from
microbial inactivation to polymer curing. The pulsing system allows customization of pulse rates
(1.5 to 100 pulses per second) and lamp duty cycles to suit specific requirements.
Pulsed xenon lamps emit light across the germicidal spectrum from 200 to 315 nm, have similar
germicidal effects as mercury lamps (Linden et al. 2000), and operate with the same disinfection
processes. Theoretically, the broad spectrum may result in additional damage mechanisms like
photodimerization, photohydration, photo-crosslinking, and photo splitting (Harm 1980; Kowalski
2009). However, the other types of damage mechanisms do not significantly contribute to UV
disinfection because single- and double-strand breaks and DNA-DNA cross-links occur only at
doses that are several orders of magnitude higher than those typically used for UV disinfection
(Jagger 1967; Masschelein 2002; Setlow 1996).
Pulsing and broad-spectrum light generation have various desirable properties, including high
disinfection efficiency, low heat generation, lack of mercury, and rapid startup, but careful
design consideration is necessary for safe application. In rooms with glass windows and doors,
the bright visible light from pulsed xenon devices should be tuned to work outside the range of
pulse frequencies that can trigger photoepileptic seizures in photosensitive individuals. The
infrared light generated by the lamps can interfere with some devices that use non-encoded
infrared light for sensing and communication. Furthermore, depending on the specific
application, it is important to select pulsed xenon lamps with appropriate spectral cutoffs to
mitigate the risk of ozone generation (Claus 2021).
Commercial uses of UV-C LEDs have emerged into products and HVAC equipment for multiple germicidal
applications, as well as in many non-HVAC applications. Individual LEDs are solid-state optics and
optoelectrical components that, once incorporated into products, allow a wide range of capabilities
and customizable performances depending on the technology, number of LEDs, positions, manner of
operation, etc. UV-C LEDs can be designed for germicidal output around the peak efficiency of the
standard germicidal response function (~265 nm; see Figure 1).
LEDs are made up from semiconductor materials on substrates that generate directional UV-C radiation
through direct bandgap transitions. They do not require any burn-in time to stabilize output. The
U.S. Department of Energy (2021, 2022) Solid State Lighting program made in-depth review of
specifically AlGaN UV-C and UV-B LEDs on sapphire substrates and compared to LEDs with indium
gallium nitride (InGaN) alloys common for UV-A and illumination.
The nature of LEDs makes them minuscule point-source surface-mounted
device (SMD) components (a typical LED package size is 3.5 by 3.5 mm) to
design into modules and arrays of LEDs for various germicidal purposes. The circuit board components
can run both in series, in parallel, or mixed circuits. The instantaneous on/off power-switching
capability (i.e., with no warm-up time delay) of such LED circuit groupings allows toggling active
disinfection by duty cycling. This characteristic also simplifies exposure safety switches and can
extend LED lifetime. The electrical control and drive circuit for forward voltage and drive currents
can be made with simple low-voltage components, and device product designs are often engineered to
run on the common low-voltage drive lines in the equipment and system without needing any additional
ballasts.
UV-C LEDs allow highly customizable germicidal irradiation devices by sustainable non-hazardous
materials, but the specific spectral distribution, peak wavelength, and performance characteristics
differ widely across manufacturers and device design for equipment and systems.
It’s also possible to combine UV-C LEDs with other pathogen mitigation technologies (e.g.,
photocatalytic oxidation [PCO]) when driven by UV-A LEDs irradiating a titanium dioxide
(TiO2) catalyst surface in the same compact device and board.
UV-C LED Performance
Characteristics
Although UV-C LED technologies differ by their specific peak emission wavelength, spectral
distribution, optical, and electrical limitations, they typically have a peak wavelength
emission between 260 to 280 nm when used for germicidal applications. Both lower and higher
wavelengths are possible in other applications (e.g., curing and sensors). UV-C LED components
can be categorized based on their light extraction efficiency; their specified germicidal
efficacy also depends on the chosen and supported drive current they operate in. For example, a
UV-C LEDs on AlN substrate can be offered as part bins with either 60, 70, or 80 mW emission
when operated by a 500 mA drive current. Note that the efficacy and safety of an LED peak
wavelength differ from more monochromatic sources. Every LED has a spectral distribution and
bandwidth (Figure
9A), thus the germicidal radiation across the actual LED emission band may be either
more or less effective than their stated peak wavelength. As mentioned previously, LED outputs
are measured using different techniques and test methods compared to other UV sources because
LEDs are point sources, whereas lamps are line sources (see Table
4 for applicable test methods).
LED component performance can also change by integrated lenses or collar reflectors. As
directional point-sources, the native conical beam shape and viewing angle in AlN UV-C LEDs is
~130°, but there is also less intense wider-angled emission that can be collimated forward
with these types of optical components. Other types of LEDs can have more side emissions due to
their substrate and epitaxial structure. An LED component can also host multiple LED diodes
within the same SMD and optical package for added output. As with any electric circuit
component, humidity and condensate risk may need consideration during design (e.g., protective
enclosures or coatings), as well as circuitry self-heating and power consideration during
product development for any specific application requirement.
With board modules and multiple LEDs, it is important to consider manufacturing variability
between LEDs and to design for worst case to ensure intended germicidal efficacy throughout
specified product life. This is especially important for UV-C LEDs with their peak wavelength
situated on the slope of the standard germicidal response function curve rather than at the
vertex, because variations and wavelength shifts may have big impact on germicidal performance.
The width of the spectral distribution around the peak wavelength, typically noted by full width at half maximum (FWHM), is useful to
understand how much of the broadband emission output is germicidal for any target pathogen (Figure
9A).
The peak wavelength in output can also shift by ambient temperature and designed drive current.
As example, an AlN UV-C LED, can shift by 1 nm by an ambient temperature step from 20°C to
80°C (Figure
9B) and by 1 nm when lowering the drive current from 500mA to 100mA (Figure
9C).
Wall-plug efficiency (WPE) is the ratio between the
electrical power going into the LED and its usable light coming out. The losses and efficiencies
are shown in Figure
10 and differ between LED technologies. Wall-plug efficiencies are dependent on
wavelength and other factors and are currently typically below 10%.
The choice of drive current also impacts the LED’s WPE. For example, an AlN UV-C LED with
integrated focal lens can scale from typically 20 mW germicidal radiation with 7% WPE by 50 mA
drive current up to 160 mW germicidal radiation at 500 mA drive current, but the WPE is reduced
to 5% (Figure
11).
Drive currents and thermal management need design consideration because of the low WPE, meaning a
lot of self-heating is generated that needs to be mitigated from the electric circuit, and
especially because the lifetime and radiant power output of UV-C LEDs diminish in higher
temperature. As example, the germicidal radiation may drop ~20% with an ambient temperature
shift from 20°C to 80°C. Consequently, placing LEDs in cold ambient air
(e.g., downstream from cooling coils) or using controlled operation only during active airflow
benefits their germicidal output and simplifies thermal management and heatsink design (Figure
12).
Manufacturers should typically specify lifetime hours data with Life
remaining (L, % transmission) and Batch (B, %
of total LEDs) values. L value defines the target percentage of output
comparing with the initial output. B value means a target statistical confidence interval. Thus,
B50 indicates that no more than 50% of LEDs would be expected to have their light output drop
below the target L value maintenance level. B10 would give a duration where only 10% of the LEDs
are still expected to meet the L value within the given time. For example, a rating of L70B50 as
10, 000 hours would mean that, after operating for 10, 000 hours, 50% of LEDs have dropped to
70% of their original radiant power.
Thus, LB values indicate a targeted and application-specific lifetime for maintenance use (e.g.,
to ensure a duration where there is adequate germicidal efficacy for a given application) and
are not typically a time-to-failure after which the LED has stopped working completely.
LED lifetime is affected by the chosen drive current and how well the device’s thermal
management design handles the resulting junction temperatures (inner diode temperature in the
depletion region where the electrons and holes recombine to generate photons) and other
influences from the ambient environment. Another parameter is solder-point temperature, which is
the thermal path from the SMD LED package to the soldered circuit board surface and depends on
the LED package technology.
An AlN UV-C LED with L70 rated at 25, 000 hours when driven by 350 mA and a measured
35°C solder-point temperature could extend this lifetime in practice by
lowering the drive current or by a more beneficial ambient environment or heatsink design.
Correctly designed and integrated, UV-C LEDs generally do not suffer detrimental impact by pulsed
operation and frequent on/off power-switching. Hence, targeted L-value lifetime numbers can
convert into much longer calendar lifetimes, depending on the application and duty cycling.
Also, since the radiation output for germicidal dosing in equipment can be distributed across
multiple contributing LEDs, adding more LEDs in design (where possible) can lower the duty cycle
of each LED and yield much longer target lifetimes and replacement cycles. It is important to
clarify what designed performance is expected at the end of any stated lifetime, and to
understand that other components in the device (e.g., power supply, control circuits,
enclosures) can affect product lifetime.
Maintenance, Monitoring, and
Replacement
Despite the customization and flexibility on designing for long target lifetimes and maintenance
cycles, other maintenance tasks may still be needed, such as regular cleaning of quartz windows
on a UV-C LED enclosure to maintain optimal performance. Review with the manufacturer.
Engineered spectral distribution by UV-C LEDs for germicidal applications typically prevents
output below ~242 nm, where ozone can start to form, so germicidal UV-C LEDs are generally not
ozone generators.
Waste management or replacement of UV-C LED devices is straightforward because the LEDs
themselves are considered as electronic waste.
5. UV-C PHOTODEGRADATION OF MATERIALS
UV-C energy can be detrimental to organic materials and may result in material damage or
discoloration (ACGIH 2015; Bolton 2001; Kauffman 2011). Much of what is known about UV
photodegradation comes from studies of sunlight, which has UV components. Unlike UV-A and UV-B, UV-C
has very little penetrating power and will not penetrate through regular glass, plastic, or most
solid materials. The extent of material degradation damage is a function of the material type, UV
wavelength, and applied dose. Longer UV wavelengths are more penetrating, whereas shorter UV
wavelengths have higher energy. Shorter UV wavelengths may also generate ozone, which can oxidize
organic materials resulting in material degradation.
As such, if the UV is not applied properly and vulnerable materials are not shielded or substituted,
degradation can occur (NEHC 1992). Material degradation can result in a possible loss in system
performance and/or potential safety concerns. In an HVAC system, the extent of material degradation
caused by UV-C energy varies greatly with type of material, UV intensity, length of exposure, and
design of the component. UV-C intensity in a system can be as high as 10 000
µW/cm2 for airstream disinfection, or about 50 to 100 µW/cm2 for
cooling coil maintenance, although typical designs use much higher intensity. For many HVAC
components, such as certain filter media and insulation or gasket foams, degradation can be rapid
and severe, destroying the material (Kauffman 2011, 2012, 2017). Inorganic materials such as glass,
glass fibers, and metal are not affected by UV-C exposure. The detailed data in the Kauffman studies
are based on exposure to 254 nm UV wavelengths and can be used to estimate degradation of an item at
different UV intensity levels and exposure times; Table
2 gives an overview that can be used to determine what materials to avoid or shield in a
system.
As a general rule, solid materials performed better than porous/fibrous materials because of the
minimal surface penetration by UV-C radiation. Based on the relative degradation, the materials were
ranked with respect to the UV-C resistance as follows:
-
A: No effect (inorganic materials only; all organic materials exhibit some degradation)
-
B: Minor effect (mainly cosmetic changes, not likely to affect materials ability to
perform its duty)
-
C: Moderate effect (some cracking/pitting suggesting protection/shielding should be
considered)
-
D: Severe effect (structural damage, not recommended)
Although UV-C photodegradation is of concern, with the selection of the proper material or metallic
shielding of other components, the problem can be significantly reduced and components can be
expected to meet product design life. The useful life of organic materials may be extended by
protecting them with UV absorbers, stabilizers, or reflective pigments or coatings.
UV lamps should be replaced at the end of their useful life, based on recommendations of the
equipment manufacturer. It may be prudent to simply change lamps annually (8760 h when lamps are
run continuously) to ensure that adequate UV energy is supplied. Lamps can operate long after
their useful life, but with the potential of greatly reduced performance. The typical useful
life of low-pressure mercury UV-C lamps is 9000 h of continuous operation but the lifetime could
be impacted by power supply selection, system design, risk tolerance, or manufacturer
recommendations. Switching lamps on and off too often may lead to early lamp failure, depending
on the power supply type used. Consult the lamp manufacturer for specific information on
expected lamp life and effects of switching.
Lamp replacement should be done wearing nitrile or latex gloves to avoid depositing oils from
one’s hands on the bulb envelope. Before activation, lamps should be wiped down with
isopropanol after installation to remove any contaminants.
UV lamps should be treated the same as other mercury-containing devices, such as fluorescent
bulbs, according to local regulations. Most lamps must be treated as hazardous waste and cannot
be discarded with regular waste. Low-mercury bulbs often can be discarded as regular waste;
however, some state and local jurisdictions classify these lamps as hazardous waste. The U.S.
EPA’s universal waste regulations allow users to treat mercury lamps as regular waste for
the purpose of transporting to a recycling facility (EPA 2011). This simplified process was
developed to promote recycling. The National Electrical Manufacturers Association (NEMA)
maintains a list of companies claiming to recycle or handle used mercury lamps at www.lamprecycle.org.
Maintenance personnel should routinely perform periodic visual inspection of the UV lamp
assembly. Typically, a viewing port or an access door window is sufficient for in-duct
applications. Any burned-out or failing lamps should be replaced immediately.
Depending on the application and environment, a maintenance plan may need to include direct
physical inspection of the fixture. If the lamp has become dirty, it should be cleaned with a
lint-free cloth and commercial glass cleaner or isopropyl alcohol.
Future UV-C systems may include a feedback component to alert maintenance personnel to UV-C lamp
failure or UV-C output degradation.
Hazards of Ultraviolet Radiation to Humans
UV-C is a low-penetrating form of UV compared to UV-A or UV-B. Measurements of human tissue show
that 4 to 7% of UV-C (along with a wide range of wavelengths, 250 to 400 nm) is scattered
(Diffey 1983) and absorbed in the first 2 μm of the stratum corneum (outer dead layer of
human skin), thus minimizing the amount of UV-C transmitted through the epidermis (Bruls 1984).
Far more energy is absorbed into the stratum corneum and surface cells in the far UV-C at
wavelengths less than 235 nm (Finlayson 2022; Nishigori 2023).
Although UV photons are more energetic than the visible portion of the electromagnetic spectrum,
UV-C and UV-B are invisible to humans. Therefore, exposure to ultraviolet energy can result in
ocular damage, which may initially go unnoticed.
Ocular damage generally begins with photokeratitis
(inflammation of the cornea), but can also result in conjunctivitis (inflammation of the conjunctiva [ocular
lining]). Symptoms, which may not be evident until several hours after exposure, may include an
abrupt sensation of sand in the eyes, tearing, and eye pain, possibly severe. These symptoms
usually appear within 6 to 12 h after UV exposure, and resolve within 24 to 48 h.
Cutaneous damage consists of erythema, a reddening of
the skin. It is like a mild sunburn with no tanning. The maximum effect of erythema occurs at a
wavelength of 296.7 nm in the UV-B band. UV-C radiation at a wavelength of 253.7 nm is less
effective, but is still an acute skin hazard.
The International Commission on Illumination (CIE) provides a thorough review of UV-C photocarcinogenesis risks from germicidal lamps (CIE
2010).
Acute overexposure to UV-C band radiation is not
incapacitating unless greatly exceeding exposure guidelines, but generally regresses after
several days, leaving no permanent damage.
In recent years, there has been growing interest in far UV-C (200 to 235 nm). These wavelengths
show far less penetration into surface cells of the cornea and the skin.
UV-C energy does not normally penetrate through solid substances and is attenuated by most
materials. Quartz glass, soda barium glass, and PTFE plastic have high transmissions for UV-C
radiation.
UV-C energy can reflect from most polished metals and several types of painted and nonpainted
surfaces (Wengraitis and Reed 2012); however, a surface’s ability to reflect visible light
cannot be used to indicate its UV-C reflectance. The fact that a blue glow can be observed on
the metal surface from an operating low-pressure UV fixture lamp could indicate the presence of
UV, and a measurement should be performed to ensure there is no exposure risk. The lack of
reflected blue light does not necessarily indicate the absence of UV energy.
Well-designed and commissioned upper-room UV-C installations, education of maintenance personnel,
signage, and safety switches can avoid overexposure. During commissioning and before operation
of the UV-C installation, hand-held radiometers with sensors tuned to the read the specific 254
nm wavelength should be used to measure stray UV-C energy (primarily in upper-air systems).
In 1972, the Centers for Disease Control and Prevention (CDC) and National Institute for
Occupational Safety and Health (NIOSH) published a recommended
exposure limit (REL) for occupational exposure to UV radiation. REL is
intended to protect workers from the acute effects of UV exposure, although photosensitive
persons and those exposed concomitantly to photoactive chemicals might not be protected by the
recommended standard. The American Conference of Governmental Industrial Hygienists (ACGIH) also
issues similar Threshold Limit Values (TLVs®) for occupational exposure to
ultraviolet radiation in the spectral region between 180 and 400 nm, and represent conditions to
which nearly all workers may be repeatedly exposed without adverse health effects. The RELs and
TLVs for occupational exposure to UV incident on skin or eye are based on the irradiance and
time of exposure.
Table
3 lists some permissible exposure times for different levels of UV-C irradiance.
Exposures exceeding CDC/NIOSH REL levels require use of personal protective equipment (PPE),
which consists of eyewear and clothing known to be nontransparent to UV-C penetration and which
covers exposed eyes and skin. The basic REL limit is a cumulative daily exposure of 3 mJ/cm2
(effective), which is spectrally weighted to a hazard-weighting function S(λ). Thus, it is time-weighted and the values in Table
3 reflect a steady-state, continuous exposure for that duration. Obviously, during a day
most individuals do not remain in a fixed position, so it is possible to expect a total exposure
duration that is less than a full day.
Although the overall spectral ranges covered by NIOSH RELs and ACGIH TLVs differ slightly, for
most practical UV-C exposures the values were identical from 1972 until the end of 2021. The
updated TLVs for eye and skin safety for different wavelengths are shown in Table
4 and Figure
13 (ACGIH 2022).
UV inspection, maintenance, and repair workers typically do not remain in one location during the
course of their workday, and therefore are not exposed to UV irradiance levels for 8 h.
Threshold Limit Value® (TLV®) consideration should be based on
occupancy use of spaces treated by UV-C systems (ACGIH 2023).
Some indoor plants do not tolerate prolonged UV-C exposure and should not be hung in the upper
room if upper-air UV systems are used.
At 253.7 nm, the CDC/NIOSH REL is 6 mJ/cm2 (6000 μJ/cm2) for a daily 8
h work shift. ACGIH’s (2023) TLV for UV radiation is identical to the REL for this
wavelength. Permissible exposure times (PET) can be calculated for various irradiance levels
using the following equation:
Some UV lamps used in the industry have spectral outputs around 185 nm and are designed to
produce ozone for specific remediation applications. Adequate safety precautions are advised
when using these lamps.
Excimer (far UV-C) lamps with spectral outputs around 222 nm also have the potential to generate
ozone (Jiminez 2023; Link 2023). These lamps can generate ozone via photochemical reactions as
well as from their corona discharge. The amount of ozone depends on the type, number, and
configuration of lamps used in the application, as well as the level of ventilation, airflow,
air mixing, and air exchange rate for that application (Blatchely 2022).
UV performance and safety levels can be measured with a calibrated UV radiometer with a cosine
corrected detector. When measuring occupant safety, apply a field-of-view (FOV) hood to the
detector and take the measurement directly facing the device at 1.8 m at various
locations in a room or occupied space; measurements must be taken in the same location each
time. If the readings indicate a dosage in constantly occupied areas exceeding 6
mJ/cm2 in an 8 h period, the UV systems must be deactivated until adjustments can be
made or the manufacturer can be contacted. UV-C measurements should be taken
-
At initial installation
-
Whenever new lamps are installed (newer lamp designs may have increased irradiance)
-
Whenever modifications are made to the GUV system or room (e.g., adjusting fixture
height or location or position of louvers, adding UV-absorbing or -reflecting
materials, changing room dimensions or modular partition height)
Upper-air applications of GUV inevitably expose room components (walls, ceiling, louvers, lights,
etc.) to strong radiation. Monitor condition of these elements to ensure that degradation has no
negative effects on the facility’s safety. Further guidance on GUV, including the approach
to time-weighted averaging of human exposures is provided by ANSI/IES (2021).
Upper-air systems should have on/off switches and an electrical disconnect device on the louvers.
If UV radiation measurement taken at initial installation exceed the recommended exposure limit,
all highly UV-reflecting materials should be removed, replaced, or covered. UV-absorbing paints
containing titanium oxide can be used on ceilings and walls to minimize reflectance in the
occupied space. Most ceiling tiles are of relatively low reflectance (Wengraitis 2012).
Warning labels must be posted on all upper-air UV fixtures to alert personnel of potential eye
and skin hazards. Damaged or illegible labels must be replaced as a high priority. Warning
labels must contain the following information:
-
Wall sign for upper-air UV-C Caution:
Ultraviolet energy. Switch off lamps before entering upper room.
-
General warning posted near UV-C lamps Caution: Ultraviolet energy. Protect eyes
and skin.
-
Warning posted on the door of air handlers where UV-C lamps are present in ductwork
Warning: Ultraviolet energy in duct.
Disconnect power before servicing.
In-duct systems should be fully enclosed to prevent leakage of UV radiation to unprotected
persons or materials outside of the HVAC equipment.
All access panels or doors to the lamp chamber and panels or doors to adjacent chambers where UV
radiation may penetrate or be reflected should have warning labels in appropriate languages.
Labels should be on the outside of each panel or door, in a prominent location visible to people
accessing the system.
Lamp chambers should also have electrical disconnect devices. Positive disconnection devices are
preferred over switches. Disconnection devices must be able to be locked or tagged out, and
should be located outside the lamp chamber, next to the chamber’s primary access panel or
door. Devices should be wired in series so that opening any single access point deenergizes the
entire UV system. On/off devices for UV lamps must not be installed in the same location as
general room lighting; instead, they must be in a location that only authorized persons can
access, and should be locked to ensure that they are not accidentally turned on or off.
UL Standard 1995 requires that no opening permits leakage of UV-C
greater than 0.1 µW/cm2, and points of intentional access to UV sources must be
equipped with an interlocking mechanism that deenergizes the UV sources when opened.
The lamp chamber should have one or more viewports of UV-C-absorbing materials (ordinary glass).
Viewports should be sized and located to allow an operating UV system to be viewed from outside
of the HVAC equipment.
Personnel Safety Training
Workers should be provided with as much training as necessary, including health and safety
training, and some degree of training in handling lamps and materials. Workers should be made
aware of hazards in the work area and trained in precautions to protect themselves. Training
topics should include
Workers expected to clean up broken lamps should be trained in proper protection, cleanup, and
disposal.
No personnel should be subjected to direct UV exposure in excess of current exposure guidelines,
but if potentially hazardous exposure is unavoidable, personnel should wear protective clothing
(no exposed skin), protective eyewear, and gloves. Most eyewear, including prescription glasses,
may be sufficient to protect eyes from UV, but not all offer complete coverage (energy could
still reach the eyes from the sides or reflections from inside the glasses); standard-issue,
full wraparound protective goggles may be the best alternative.
If individual lamp operating condition must be observed, this should preferably be done using the
viewport window(s).
Access to lamps should only be allowed when lamps are deenergized. The lamps should be turned off
before air-handling unit (AHU) or fan shutdown to allow the lamps to cool. Workers should always
wear protective eyewear and puncture-resistant gloves for protection in case a lamp breaks.
Access to the lamp chamber should follow a site-specific lock-out/tag-out procedure. Do not rely
on panel and door safety switches as the sole method to ensure deenergized lamps. Doors may be
inadvertently closed or switches may be inadvertently contacted, resulting in unexpected lamp
activation.
If workers will enter the condensate area of equipment, the condensate pan should be drained and
any residual water removed.
In general, avoid performing readings with the fan running and workers inside an AHU (e.g., to
test for output reduction caused by air cooling). Tests of this nature should be instrumented
and monitored from outside the equipment.
During maintenance, renovation, or repair work in rooms where upper-air UV systems are present,
all UVGI systems must be deactivated before personnel enter the upper part of the room.
If a mercury lamp breaks, all workers must exit the HVAC equipment. Panels or doors should be
left open and any additional lamp chamber access points should also be opened. Do not turn
air-handling unit fans back on. After a period of 15 minutes, workers may reenter the HVAC
equipment to begin lamp clean-up.
If a lamp breaks in a worker’s hand, the worker should not exit the HVAC equipment with the
broken lamp. Carefully set the broken lamp down, then exit the equipment. When possible, try not
to set the broken lamp in any standing condensate water. Follow standard ventilation and reentry
procedures.
Cleanup requires special care because of mercury drop proliferation and should be performed by
trained workers. As a minimum, workers should wear cut-resistant gloves, as well as safety
glasses to protect eyes from glass fragments. Large lamp pieces should be carefully picked up
and placed in an impervious bag. HEPA-vacuum the remaining particles, or use other means to
avoid dust generation.
8. INSTALLATION AND COMMISSIONING
Ensuring the performance and safety of UVGI systems deployed at a facility is of paramount
importance. It is recommended that equipment manufacturers provide complete installation details and
drawings to ensure that the equipment is installed properly and operates as designed.
Currently there is no consensus guidance on the design, installation, commissioning, and
certification of UVGI systems. Those currently applying it rely on various sources, including
manufacturers’ literature, peer-reviewed publications, and handbooks. At present, the most
well-developed areas of standards related to UVGI applications are the rating of some lamps,
electrical safety standards, and safe human exposure limits. NALMCO had been developing a
certification for UV technicians (www.nalmco.org/guv-training). Facility managers and system installers should
require detailed documentation to ensure that installed equipment performs in accordance with the
specified design and meets all applicable performance and safety standards.
Note that most installed systems comprise multiple individual UV fixtures/devices; the performance
and safety of the integrated system depend on the number and configuration of these multiple
fixtures in the treatment space along with their interaction with other items in that treatment
space. Examples include a UV system comprising multiple fixtures used for coil cleaning or air
disinfection inside HVAC units, or a room application entailing multiple upper-room or
ceiling-mounted fixtures. This becomes increasingly important when considering occupied versus
unoccupied spaces. Although there are certain common issues in the application of such systems, such
as lamp performance and safety, the information and methods needed to validate the installed system
will be different. These systems would also need to comply with any relevant standards for field
installations, which are currently lacking in industry. System providers should be able to validate
the system performance and safety by in-situ field testing and measurements if possible, or by
providing validated mathematical modeling outputs for UV fluence, IES files (i.e., photometric data
files), etc., that are specific to that installation and/or independent field or case studies
validating their system. For in-duct, coil disinfection, and surface disinfection systems, a key
need is accurate calculation of UV dose, which depends mainly on the radiation field in the device.
For both standalone recirculating and upper-air systems, airflow patterns in the space served are
also critical because they determine how effectively contaminated air is brought into the
irradiation zone of the device.
The commissioning authority may require a performance and safety test on a sample installation to
determine whether the system meets specifications. Measurement and monitoring of irradiance using
calibrated radiometers or color change dosimeters can be used to verify installed lamp ratings or
performance, check for UV leakage at the time of manufacture and as installed, verify irradiance
levels on cooling coil surfaces, and verify the safety of installed UVGI systems. Broad-range UV
photosensors are needed instead of narrow-band UVC sensors to accommodate the different light
sources and spectral output available. Control measures such as PPE, safety interlock switches,
remote operation, viewports, etc., should be implemented to ensure protection against any UV
exposure above acceptable levels. The section on Safety in this chapter describes the various
aspects of safety (electrical, photobiological, ozone, photochemical, photodegradation) that need to
be validated and monitored for GUV systems. Control measures such as PPE, safety interlock switches,
remote operation, and viewports should be implemented to ensure protection against any UV exposure
above acceptable levels.
Table 5
lists performance and safety standards and guidelines that are applicable to GUV systems. In the
2023 ASHRAE Handbook—HVAC Applications, see Chapter 62 for
additional information on UV use, and Chapter
44 for information on building
commissioning and UV
systems.
Just as it is customary to express the size of aerosols in micrometres and electrical
equipment’s power consumption in watts, regardless of the prevailing unit system, it is also
customary to express total lamp UV output, UV fluence, and UV dose using SI units.
ASHRAE members can access ASHRAE Journal articles and ASHRAE research project
final reports at technologyportal.ashrae.org. Articles and reports are also available for purchase
by nonmembers in the online ASHRAE Bookstore at www.ashrae.org/bookstore.
Abshire, R.L., and H. Dunton. 1981. Resistance of
selected strains of Pseudomonas aeruginosa to low-intensity
ultraviolet radiation. Applied Environmental Microbiology
41(6):1419-1423.
ACGIH. 2022. TLVs®
and BEIs®. American Conference of Governmental Industrial Hygienists,
Cincinnati.
ANSI. 2011. High-frequency fluorescent lamp ballasts.
Standard C82.11-2011. American National Standards Institute,
Washington, D.C.
ANSI/IES. 2021. Recommended practice: Ultraviolet
germicidal irradiation (UVGI). Recommended Practice RP-44-21.
American National Standards Institute and Illuminating Engineering Society.
ASHRAE. 2015. Method of testing UV-C lights for use in
air-handling units or air ducts to inactivate airborne microorganisms. ANSI/ASHRAE Standard 185.1-2015.
ASHRAE. 2014. Method of testing ultraviolet lamps for
use in HVAC&R units or air ducts to inactivate microorganisms on irradiated surfaces.
ANSI/ASHRAE Standard 185.2-2014.
Bahnfleth, W.P., and W.J. Kowalski. 2004. Clearing the
air on UVGI systems. RSES Journal, pp. 22-24.
Blatchley, E.R., D.J. Brenner, H. Claus, T.E. Cowan,
K.G. Linden, Y. Liu, T. Mao, S.J. Park, P.J. Piper, R.M. Simmons, and D. Sliney. 2022. Far UV-C
radiation: An emerging tool for pandemic control. Critical Reviews in
Environmental Science and Technology (Jun):733-753.
doi.org/10.1080/10643389.2022.2084315.
Bolton, J.R. 2001. Ultraviolet
applications handbook. Photosciences, Ontario.
Brickner, P.W., R.L. Vincent, M. First, E. Nardell, M.
Murray, and W. Kaufman. 2003. The application of ultraviolet germicidal irradiation to control
transmission of airborne disease: Bioterrorism countermeasure. Public
Health Report 118(2):99-114.
Bruls, W. 1984. Transmission of human epidermis and
stratum corneum as a function of thickness in the ultraviolet and visible wavelengths. Journal of Photochemistry and Photobiology 40:485-494.
CDC. 2005. Guidelines for preventing the transmission of
Mycobacterium tuberculosis in health-care settings. Morbidity and Mortality Weekly Report (MMWR) 37-38, 70-75.
CIE. 1987. International lighting
vocabulary, 4th ed. Commission Internationale de L’Eclairage, Vienna.
CIE. 1993. CIE collection in photobiology and
photochemistry. Publications 106/1 (Determining ultraviolet action
spectra), 106/2 (Photokeratitis), and 106/3 (Photoconjunctivitis). Commission Internationale de
L’Eclairage, Vienna.
CIE. 2010. UV-C photocarcinogenesis risks from
germicidal lamps. Publication CIE 187:2010. Commission
Internationale de L’Eclairage, Vienna.
Claus, H. 2021. Ozone generation by ultraviolet lamps.
Photochemistry and Photobiology 97(Feb):471-476.
doi.org/10.1111/php.13391.
Diffey, B.L. 1983. A mathematical model for ultraviolet
optics in skin. Physics in Medicine and Biology 28:657-747.
Finlayson, L., I.R.M. Barnard, L. McMillan, S.H.
Ibbotson, C.T.A. Brown, E. Eadie, and K. Wood. 2022. Depth penetration of light into skin as a
function of wavelength from 200 to 1000 nm. Photochemistry and
Photobiology 98(4):974-981. doi.org/10.1111/php.13550.
GSA. 2003. The facilities standards
for the Public Buildings Service. Public Buildings Service of the General Services
Administration, Washington, D.C.
Harm, W. 1980. Biological effects
of ultraviolet radiation. Cambridge University Press.
Jagger, J. 1967. Introduction to
research in ultraviolet photobiology. Prentice-Hall, Englewood Cliffs, NJ.
Kauffman, R. 2011. Study the degradation of typical HVAC
materials, filters and components irradiated by UVC energy. ASHRAE Research Project RP-1509,
Final Report.
Kauffman, R. 2012. Study the degradation of typical HVAC
materials, filters and components irradiated by UVC energy: Part I—Literature search.
ASHRAE Transactions 118(2):638-647. Paper SA-12-026.
Kaufman, R.E. 2017. Study the HVAC system
photodegradation caused by the low level UVC light irradiance used for coil maintenance and air
stream disinfection (RP-1724). ASHRAE Research Project, Final Report.
Kauffman, R., and J. Wolf. 2012. Study the degradation
of typical HVAC materials, filters and components irradiated by UVC energy. Part II. Polymers.
ASHRAE Transactions 118(2):648-659. Paper SA-12-027.
Kauffman, R., and J. Wolf. 2013. Study the degradation
of typical HVAC materials, filters and components irradiated by UVC energy. Part III.
Manufactured products. ASHRAE Transactions 119(1):203-213. Paper DA-13-018.
Kowalski, W.J. 2002. Immune
building systems technology. McGraw-Hill, New York.
Kowalski, W.J. 2009. Ultraviolet
germicidal irradiation handbook: UVGI for air and surface disinfection. Springer,
Berlin.
Luckiesh, M. 1946. Applications of
germicidal, erythemal and infrared energy. D. Van Nostrand, New York.
Masschelein, W.J. 2002. Ultraviolet
light in water and wastewater sanitation. Lewis Publishers, Boca Raton, FL.
NEHC. 1992. Ultraviolet radiation
guide. Navy Environmental Health Center, Bureau of Medicine and Surgery, Norfolk,
VA.
NEMA. 2011. Performance testing for lighting controls
and switching devices with electronic drivers and discharge ballasts. Standard 410-2011. National Electrical Manufacturers Association,
Rosslyn, VA.
Nishigori, C., N. Yamano, M. Kunisada, A.
Nishiaki-Sawadam, H. Ohashi, and T. Igarashi. 2023. Biological impact of shorter wavelength
ultraviolet radiation-C. Photochemistry and Photobiology
99(2):335-343. doi.org/10.1111/php.13742.
NIOSH. 1972. Criteria for a recommended standard:
Occupational exposure to ultraviolet radiation. Publication
73-11009. National Institute for Occupational Safety and Health, Washington, D.C.
Philips Lighting. 1992. Disinfection by UV-radiation. Eindhoven, the Netherlands.
Reed, N.G. 2010. The history of ultraviolet germicidal
irradiation for air disinfection. Public Health Reports
125(1):15-27.
Rehmet, M. 1980. Xenon lamps. IEEE
Proceedings A (Physical Science, Measurement and Instrumentation, Management and Education,
Reviews) 127(3):190-195. doi.org/10.1049/ip-a-1.1980.0030.
Riley, R.L. 1988. Ultraviolet air disinfection for
control of respiratory contagion. In Architectural design and indoor
microbial pollution, pp. 179-197. Oxford University Press, New York.
Schechmeister, I.L. 1991. Sterilization by ultraviolet
radiation. In Disinfection, sterilization and preservation, pp.
535-565. Lea and Febiger, Philadelphia.
Scheir, R., and F.B. Fencl. 1996. Using UVGI technology
to enhance IAQ. Heating, Piping and Air Conditioning 68:109-14,
117-8, 123-4.
Setlow, J.K. 1966. Photoreactivation. In Radiation Research Supplement, vol. 6: Structural defects in DNA and
their repair in microorganisms, pp. 141-155.
Sylvania. 1982. Germicidal and short-wave ultraviolet
radiation. Sylvania Engineering Bulletin 0-342.
UL. 2011. Heating and cooling equipment. ANSI/UL Standard 1995-2011.
VanOsdell, D., and K. Foarde. 2002. Defining the
effectiveness of UV lamps installed in circulating air ductwork. Final
Report, Air-Conditioning and Refrigeration Technology Institute 21-CR Project
610-40030.
Wengraitis, S., and N.G. Reed. 2012. Ultraviolet
spectral reflectance of ceiling tiles, and implications for the safe use of upper-room
ultraviolet germicidal irradiation. Photochemistry and Photobiology
88(6):1480-1488. doi.org/10.1111/j.1751-1097.2012.01193.x.
Westinghouse. 1982. Westinghouse sterilamp germicidal
ultraviolet tubes. Westinghouse Engineering Notes A-8968.
ASHRAE. 2017. Thermal environmental conditions for human
occupancy. ANSI/ASHRAE Standard 55-2017.
Bernstein, J.A., R.C. Bobbitt, L. Levin, R. Floyd, M.S.
Crandall, R.A. Shalwitz, A. Seth, and M. Glazman. 2006. Health effects of ultraviolet
irradiation in asthmatic children’s homes. Journal of Asthma
43(4):255-262.
Blatt, M.S., T. Okura, and B. Meister. 2006. Ultraviolet
light for coil cleaning in schools. Engineered Systems
(March):50-61.
Boyce, P. 2003. Controlling
tuberculosis transmission with ultraviolet irradiation. Rensselaer Polytechnic
Institute, Troy, NY.
CIE. 2003. Ultraviolet air
disinfection. Commission Internationale de L’Eclairage, Vienna.
Coker, A., E. Nardell, P. Fourie, W. Brickner, S.
Parsons, N. Bhagwandin, and P. Onyebujoh. 2001. Guidelines for the
utilization of ultraviolet germicidal irradiation (UVGI) technology in controlling the
transmission of tuberculosis in health care facilities in South Africa. South African
Centre for Essential Community Services and National Tuberculosis Research Programme, Medical
Research Council, Pretoria.
Department of General Services. 2001. Working with ultraviolet germicidal irradiation (UVGI) lighting systems: Code
of safe practice. County of Sacramento, CA.
DIN. 2013. Optical radiation physics and illumination
engineering. Standard 5031-10:2013-12. German Institute for
Standardization, Berlin.
First, M.W., E.A. Nardell, W.T. Chaisson, and R.L.
Riley. 1999. Guidelines for the application of upper-room ultraviolet irradiation for preventing
transmission of airborne contagion—Part 1: Basic principles. ASHRAE
Transactions 105(1):869-876. Paper CH-99-12-1.
First, M.W, F.M. Rudnick, K. Banahan, R.L. Vincent, and
P.W. Brisker. 2007. Fundamental factors affecting upper-room ultraviolet germicidal
irradiation—Part 1: Experimental. Journal of Environmental
Health 4: 1-11.
First, M.W., K. Banahan, and T.S. Dumyahn. 2007.
Performance of ultraviolet light germicidal irradiation lamps and luminaires in long-term
service. Leukos 3:181-188.
IES. 2011. The lighting
handbook, 10th ed. D. DiLaura, K. Houser, R. Mistrick, and G. Steffy, eds.
Illuminating Engineering Society, New York.
Ka, M., H.A.B. Lai, and M.W. First. 2004. Size and UV
germicidal irradiation susceptibility of Serratia marcescens when
aerosolized from different suspending media. Applied and Environmental
Microbiology (Apr.): 2021-2027.
Kethley, T.W., and K. Branch. 1972. Ultraviolet lamps
for room air disinfection: Effect of sampling location and particle size of bacterial aerosol.
Archives of Environmental Health 25(3):205-214.
Ko, G., M.W. First, and H.A. Burge. 2000. Influence of
relative humidity on particle size and UV sensitivity of Serratia
marcescens and Mycobacterium bovis BCG aerosols. Tubercle and Lung Disease 80(4-5):217-228.
Kowalski, W.J. 2006. Aerobiological
engineering handbook. McGraw-Hill, New York.
Kowalski, W.J., and W.P. Bahnfleth. 2002. UVGI design
basics for air and surface disinfection. HPAC Engineering
72(1):100-110.
Kujundzic, E., M. Hernandez, and S.L. Miller. 2007.
Ultraviolet germicidal irradiation inactivation of airborne fungal spores and bacteria in
upper-room air and HVAC in-duct configurations. Journal of Environmental
Engineering Science 6:1-9.
Levetin, E., R. Shaughnessy, C. Rogers, and R. Scheir.
2001. Effectiveness of germicidal UV radiation for reducing fungal contamination within
air-handling units. Applied and Environmental Microbiology
67(8):3712-3715.
Masjoudi, M., M. Mohseni, and J.R. Bolton. 2021.
Sensitivity of bacteria, protozoa, viruses, and other microorganisms to ultraviolet radiation.
Journal of Research of the National Institute of Standards and
Technology 126. doi.org/10.6028/jres.126.021.
Menzies, D., J. Popa, J. Hanley, T. Rand, and D. Milton.
2003. Effect of ultraviolet germicidal lights installed in office ventilation systems on
workers’ health and well being: Double-blind multiple cross over trial. Lancet 363:1785-1792.
Miller, S.L., M. Fennelly, M. Kernandez, K. Fennelly, J.
Martyny, J. Mache, E. Kujundzic, P. Xu, P. Fabian, J. Peccia, and C. Howard. 2002. Efficacy of
ultraviolet irradiation in controlling the spread of tuberculosis. Final
Report, Centers for Disease Control, Atlanta, GA, and National Institute for
Occupational Safety and Health, Washington, D.C.
Montgomery, R., and R. Baker. 2006. Study verifies coil
cleaning saves energy. ASHRAE Journal 48(11):34-36.
Riley, R.L., and S. Permutt. 1971. Room air disinfection
by ultraviolet irradiation of upper air: Air mixing and germicidal effectiveness. Archives of Environmental Health 22(2):208-219.
Riley, R.L., M. Knight, and G. Middlebrook. 1976.
Ultraviolet susceptibility of BCG and virulent tubercle bacilli. American
Review of Respiratory Disease 113:413-418.
Riley, R.L., S. Permutt, and J.E. Kaufman. 1971.
Convection, air mixing, and ultraviolet air disinfection in rooms. Archives
of Environmental Health 22(2):200-207.
Rudnick, F. 2007. Fundamental factors affecting
upper-room germicidal irradiation—Part 2: Predicting effectiveness. Journal of Occupational and Environmental Hygiene 4(5):352-362.
RLW Analytics. 2006. Improving indoor environment
quality and energy performance of California K-12 schools, project 3: Effectiveness of UVC light
for improving school performance. Final Report, California Energy
Commission Contract 59903-300.
Siegel, J., I. Walker, and M. Sherman. 2002. Dirty air
conditioners: Energy implications of coil fouling. Proceedings of the ACEEE
Summer Study on Energy Efficiency in Buildings. pp. 287-299.
Witham, D. 2005. Ultraviolet—A superior tool for
HVAC maintenance. IUVA Congress, Tokyo.
Xu, P., J. Peccia, P. Fabian, J.W. Martyny, K.P.
Fennelly, M. Hernandez, and S.L. Miller. 2003. Efficacy of ultraviolet germicidal irradiation of
upper-room air in inactivating airborne bacterial spores and mycobacteria in full-scale studies.
Atmospheric Environment 37(3):405-419.