Centrifugal pumps provide the primary force to distribute and recirculate
hot and chilled water in a variety of space-conditioning and plumbing systems. The pump provides a
predetermined flow of water to the space load terminal units or to a thermal storage chamber for release
at peak loads. The effect of centrifugal pump performance on the application, control, and operation of
various terminal units is discussed in Chapter 13. Other hydronic systems
that use pumps include (1) condensing water circuits to cooling towers (Chapters
14 and 40), (2) water-source heat pumps (Chapter 9), (3) boiler
feeds, and (4) condensate returns (Chapter 11). Boiler feed and condensate return pumps
for steam boilers should be selected based on boiler manufacturer’s requirements. Centrifugal
pumps can also be found in water treatment and service water-heating systems.
In a centrifugal pump, an electric motor or other power source rotates the impeller at the
motor’s rated speed. Impeller rotation adds energy to the fluid after it is directed into the
center or eye of the rotating impeller. The fluid is then acted on by centrifugal force and
rotational or tip-speed force, as shown in the vector diagram in Figure 1.
These two forces result in increased fluid velocity. The pump casing is designed for maximum
conversion of velocity energy of the fluid into pressure energy, either by the uniformly increasing
area of the volute or by diffuser guide vanes (when provided).
The construction features of a typical centrifugal pump are shown in Figure
2. These features vary according to manufacturer and type of pump.
Materials. Centrifugal pumps are generally available in
stainless steel-fitted, bronze-fitted, or iron-fitted construction. The choice of material depends
on those parts in contact with the liquid being pumped. The term “fitted” refers to the
materials of impeller and wear rings (if used) and the shaft sleeve. The casing is typically cast
iron. Stainless steel-fitted, bronze-fitted, and iron-fitted constructions are all appropriate for
general water applications. All-bronze construction is often used in potable water applications.
Mechanical seals are devices that prevent fluid leakage
along rotating shafts. They are used predominantly in clean hydronic applications, either as
unbalanced or balanced (for higher pressures) seals. Balanced seals are used for high-pressure
applications, particulate-laden liquids, or for extended seal life at lower pressures. Inside seals
operate inside the mechanical seal chamber, whereas outside seals have the rotating element outside
the box. Pressure and temperature limitations vary with the liquid pumped and the style of seal.
Shaft sleeves protect the motor or pump shaft.
Wear rings (if present) prevent wear to the impeller
and/or casing and are easily replaced when worn. Using wear rings is optional, because improved
casting abilities and part tolerances have reduced the need for them. Wear rings are intended for
applications with abrasive solutions, which are not typical in HVAC systems.
Ball bearings are most frequently used, except in
low-pressure circulators, where motor and pump bearings are the sleeve type.
A balance ring placed on the back of a single-inlet
enclosed impeller reduces the axial load, thereby decreasing the size of the thrust bearing and
shaft.
Normal operating speeds of motors are 600 to 3600 rpm. The pump manufacturer can help determine the
optimum pump speed for a specific application by considering pump efficiency, the available pressure
at the inlet to prevent cavitation, maintenance requirements, and operating cost.
Centrifugal pumps used in hydronic systems are single stage or multistage. (These terms refer to the
number of impellers in the pump housing.)
A centrifugal pump has either a volute or diffuser casing. Pumps with volute casings collect water from the impeller and discharge it
perpendicular to the pump shaft. Casings with diffusers discharge water parallel to the pump shaft.
All pumps described in this chapter have volute casings except the vertical turbine pump, which has
a diffuser casing.
Pumps may be classified as close-coupled or flexible-coupled to the electric motor. The close-coupled
pump has the impeller mounted on a motor shaft extension, and the flexible-coupled pump has an
impeller shaft supported by a frame or bracket that is connected to the electric motor through a
flexible coupling.
Pumps may also be classified by their mechanical features and installation arrangement. Close-coupled
pumps have an end-suction inlet for horizontal mounting or a vertical in-line inlet for direct
installation in the piping. Base-mounted pumps are (1) end-suction, frame-mounted or (2)
double-suction, horizontal or vertical split-case units. Double-suction pumps can also be arranged
vertically on a support frame with the motor vertically mounted on a bracket above the pump. Pumps
are usually labeled by their mounting position as either horizontal or vertical.
A circulator pump is a low-pressure, low-capacity, in-line centrifugal pump, with or without an
electric motor, consisting of an in-line casing that houses one impeller, which is intended for
pipe-mounted installation in heating systems or cooling distribution systems. This pump may have
a wet rotor (Figure 3) or may be driven by a
close-coupled (Figure 4) or
flexible-coupled motor (Figure 5).
Circulator pumps are commonly used in residential and commercial buildings to circulate source
water and to recirculate the flow of terminal coils to enhance heat transfer and improve the
control of large systems.
Close-Coupled, Single-Stage,
End-Suction Pump
The close-coupled pump is mounted on a horizontal motor supported by the motor or pump foot
mountings (Figure 5).
Mounting usually requires a solid concrete pad. The impeller is directly mounted on the motor
shaft, eliminating the need for flexible couplings. This compact pump has a single horizontal
inlet and vertical discharge. It may have one or two impellers.
Frame-Mounted, End-Suction Pump on
Base Plate
Typically, the motor and pump are mounted on a common, rigid base plate for horizontal mounting
(Figure 6).
Mounting requires a solid concrete pad. The motor is flexible-coupled to the pump shaft and
should have an Occupational Safety and Health Administration (OSHA)-approved guard. For
horizontal mounting, the piping is horizontal on the suction side and vertical on the discharge
side. This pump has a single suction.
Base-Mounted, Horizontal (Axial) or
Vertical, Split-Case, Single-Stage, Double-Suction Pump
The motor and pump are mounted on a common, rigid base plate for horizontal mounting (Figures
7 and 8).
Axial pumps can be vertically mounted with a vertical pump casing and motor mounting bracket
with open seal chamber design (see Figure
9). Mounting requires a solid concrete pad and rigid steel base plate, which may or may
not require grouting. The motor is flexible-coupled to the pump shaft, and the coupling should
have an OSHA-approved guard; a spacer coupling allows for removal of the pump’s rotating
element without disturbing the pump volute or movement of the pump’s motor and electrical
connections. A split case allows complete access to the impeller for maintenance. This pump may
have one or two double-suction impellers.
Base-Mounted, Horizontal,
Split-Case, Multistage Pump
The motor and pump are mounted on a common, rigid base plate for horizontal mounting (Figure
9). Mounting requires a solid concrete pad. The motor is flexible-coupled to the pump
shaft, and the coupling should have an OSHA-approved guard. Piping is horizontal on both the
suction and discharge sides. The split case allows complete access to the impellers for
maintenance. This pump has a single suction and may have one or more impellers for multistage
operation.
This close-coupled pump and motor are mounted on the pump casing. The unit is compact and depends
on the connected piping for support. Mounting requires adequately spaced pipe hangers and,
sometimes, a vertical casing support. The suction and discharge piping is horizontal. The pump
has a single or double suction impeller.
Vertical In-Line Split-Coupled
Pump
The suction and discharge flanges of this pump are oriented in the horizontal plane, on a common
centerline. The motor is installed vertically. The pump has an overhung impeller and a rigid
coupler. This design uses bushings but no bearing frame. The impeller is held in alignment by
the motor bearings, rigid coupling, and bushing. The coupler is a spacer design with a gap
between the motor shaft and pump shaft that is wider than the mechanical seal height. Removing
the coupler allows access to replace the mechanical seal between the motor shaft and pump shaft
without moving the motor. This pump can be either single or double suction (see Figures
10 and 11). Large
double-suction pumps may have a bushing in the bottom of the volute to keep the pump shaft
centered.
Vertical Turbine, Single- or
Multistage, Sump-Mounted Pump
Vertical turbine pumps have a motor mounted vertically on the pump discharge head for either
wet-sump or can-type mounting (Figure 12). This single-suction pump
may have one or multiple impellers for multistage operation. Mounting requires a solid concrete
pad or steel sole plate above the wet pit with accessibility to the screens or trash rack on the
suction side for maintenance. Can-type mounting requires a suction strainer. Piping is
horizontal on the discharge side and on the suction side. The sump should be designed according
to Hydraulic Institute (HI) recommendations.
4. PUMP PERFORMANCE CURVES
Performance of a centrifugal pump is commonly shown by a manufacturer’s performance curve (Figure 13). The figure displays
the pump power required for a liquid (water) with a specific gravity of 1.0 over a
particular range of impeller diameters and flows. The curves are based on standard test procedures
developed by the Hydraulic Institute (2008-2010) and the International Organization for
Standardization (ISO). The tests are performed by the manufacturer for a given pump volute or casing
and several impeller diameters, normally from the maximum to the minimum allowable in that volute.
The tests are conducted at a constant impeller speed for various flows.
Pump curves represent the average results from testing several pumps of identical design under
the same conditions. The curve is sometimes called the head-capacity curve (HQ) for the pump.
Typically, the discharge head of the centrifugal pump, sometimes called the total dynamic head
(TDH), is measured in feet of water flowing at a standard temperature and pressure. TDH
represents the difference in total head between the suction side and the discharge side of the
pump. This discharge head decreases as the flow increases (Figure 14). Motors are often selected to
be non-overloading at a specified impeller size and maximum flow to ensure safe motor operation
at all flow requirements.
The pump characteristic curve may be further described as flat or steep (Figure 15). Sometimes
these curves are described as a normal rising curve (flat), a drooping curve (steep), or a steeply
rising curve. The pump curve is considered flat if the pressure at shutoff is about 1.10 to 1.20
times the pressure at the best efficiency point. Flat characteristic pumps are usually installed in
closed systems with modulating two-way control valves. Steep characteristic pumps are usually
installed in open systems, such as cooling towers (see Chapter 14), where higher
head and constant flow are usually desired.
Pump manufacturers may compile performance curves for a particular set of pump volutes in a series
(Figure
16). The individual curves are shown in the form of an envelope consisting of the maximum
and minimum impeller diameters and the ends of their curves. This set of curves is known as a family
of curves. A family of curves is useful in determining the approximate size and model required, but
the particular pump curve (Figure 13) must then be used to
confirm an accurate selection.
Many pump manufacturers and HVAC software suppliers offer electronic versions for pump selection.
Pump selection software typically allows the investigation of different types of pumps and operating
parameters. Corrections for fluid specific gravity, temperature, and motor speeds are
easily performed.
5. HYDRONIC SYSTEM CURVES
Pressure drop caused by the friction of a fluid flowing in a pipe may be described by the Darcy-Weisbach equation:
Equation (1) shows that
pressure drop in a hydronic system (pipe, fittings, and equipment) is proportional to the square of
the flow (V2 or Q2
where Q is the flow). Experiments show that pressure drop is more nearly
proportional to between V1.85 and V1.9, or a nearly parabolic curve as shown in Figures
17 and 20. The design of the
system (including the number of terminals and flows, the fittings and valves, and the length of pipe
mains and branches) affects the shape of this curve.
Equation (1) may also
be expressed in head or specific energy form:
where
| Δh = head loss through friction,
ft (of fluid flowing)
|
| Δp = pressure drop, lb/ft2 |
| ρ = fluid density, lb/ft3 |
| f = friction factor, dimensionless |
| L = pipe length, ft |
| D = inside diameter of pipe, ft |
| V = fluid average velocity, ft/s |
| g = gravitational acceleration, 32.2
ft/s2 |
The system curve (Figure 17) defines the system
head required to produce a given flow rate for a liquid and its characteristics in a
piping system design. To produce a given flow, the system head must overcome pipe
friction, inside pipe surface roughness, actual fitting losses, actual valve losses, resistance to
flow due to fluid viscosity, and possible system effect losses. The general shape of this curve is
parabolic because, according to the Darcy-Weisbach equation (Equation [2]), the
head loss is proportional to the square of the flow.
If static pressure is present because of the height of the liquid in the system or the pressure in a
compression tank, this static is added to the system curve (Figure 18).
6. PUMP AND HYDRONIC SYSTEM CURVES
The pump curve and the system curve can be plotted on the same graph. The intersection of the two
curves (Figure 19) is the system operating point, where the pump’s developed
head matches the system’s head loss.
In a typical hydronic system, a thermostat or controller varies the flow in a load terminal by
positioning a two-way control valve to match the load. At full load the two-way valves are wide
open, and the system follows curve A in Figure 20. As the
load drops, the terminal valves begin closing to match the load (part load). This increases the
friction and reduces the flow in the terminals. The system curve gradually changes to curve B.
The operating point of a pump should be considered when the system includes two-way control valves.
Point 1 in Figure 21 shows the pump operating at the
design flow at the calculated design head loss of the system. But typically, the actual
system curve is slightly different from the design curve. As a result, the pump operates at point 2
and produces a flow rate higher than design.
To reduce the actual flow to the design flow at point 1, a balancing valve downstream from the pump
can be adjusted while all the terminal valves are in a wide-open position. This pump discharge
balancing valve imposes a pressure drop equal to the pressure difference between point 1 and point
3. The manufacturer’s pump curve shows that the capacity may be reduced by substituting a new
impeller with a smaller diameter or by trimming the
existing pump impeller. After trimming, reopening the balancing valve in the pump discharge then
eliminates the artificial drop and the pump operates at point 3. Points 3 and 4A demonstrate the
effect a trimmed impeller has on reducing flow.
Figure 22 is an
example of a system curve with both static head loss and variable head
loss. Such a system might be an open piping circuit between a refrigerating plant condenser and its
cooling tower. The elevation difference between the water level in the tower pan and the spray
distribution pipe creates the static head loss. The static loss occurs at all flow
rates.
Most variable-flow hydronic systems have individual two-way control valves on each terminal unit to
allow full diversity (random loading from zero to full load). Regardless of the load required in
most variable-flow systems, the designer establishes a minimum pressure difference to ensure that
any terminal and its control valve receive the design flow at full demand.
The low slope and steep slope curves in Figure 22
represent the boundaries for operation of the system. The net vertical difference between the curves
is the difference in friction loss developed by the distribution mains for the two extremes of
possible loads. The area in which the system operates depends on the diverse loading or unloading
imposed by the terminal units. This area represents the pumping energy that can be conserved with
one-speed, two-speed, or variable-speed pumps after a review of the pump power, efficiency, and
affinity relationships.
The theoretical power to circulate water in a hydronic system is the water horsepower (whp) and is calculated as follows:
where
= mass flow of
fluid, lb/min |
| Δh = total head, ft of fluid |
| 33,000 = units conversion, ft · lb/min per hp |
At 68°F, water has a density of 62.3 lb/ft3, and Equation (3) becomes
where
| Q = fluid flow rate, gpm |
| 3960 = units conversion, ft · gpm per hp |
Figure 23 shows how
water power increases with flow. At other water temperatures or for other fluids, Equation (4) is
corrected by multiplying by the specific gravity of the fluid.
The brake horsepower (bhp) required to
operate the pump is determined by the manufacturer’s test of an actual pump running under
standard conditions to produce the required flow and head as shown in Figure 13.
Pump efficiency is determined by comparing the output power to the input power:
Figure 24 shows a typical
efficiency versus flow curve.
The pump manufacturer usually plots the efficiencies for a given volute and impeller size on the pump
curve to help the designer select the proper pump (Figure 25). The best efficiency point (BEP) is the optimum efficiency for this pump;
operation above and below this point is less efficient. The locus of all the BEPs for each impeller size lies on a system curve
that passes through the origin (Figure 26).
For hydronic systems, basing centrifugal pump selection on the highest efficiency at the highest
possible application flow and head point may not result in the most efficient overall
pump selection, because this is often a rare operating point. To obtain the lowest life-cycle pump
power, consider the power required at various expected operating conditions and how much time is
spent at those conditions (duty cycle). This results in selecting pumps with the highest
efficiencies at the most common operating points, and favors pumps with wide regions of best
efficiency, as defined in Figure 26. In addition, centrifugal
pumps selected at a motor synchronous speed and then fitted with a reduced-diameter impeller to meet
the highest flow and head point may not be optimal. Centrifugal pumps have the highest efficiency at
the maximum impeller diameter, and new hydronic system pumps serving variable-flow systems exceeding
5 hp are required by ASHRAE Standard 90.1 to be variable
speed so they can operate at or below the motor synchronous speed. Therefore, selecting pumps at the
maximum impeller diameter and using reduced speed to reach the highest flow and head
operating point, and all other operating points, often results in the highest overall pump
efficiency and lowest power requirement. With variable-speed operation, ensure the speed at the
minimum flow and head operating point exceeds the motor minimum speed. Motor
suitability for operation below 30 to 50% of the motor synchronous speed should be verified with the
motor manufacturer.
The centrifugal pump, which imparts a velocity to a fluid and converts the velocity energy to
pressure energy, can be categorized by a set of relationships called affinity laws (Table 1).
The laws can be described as similarity processes that follow these rules:
-
Flow (capacity) varies with rotating speed N (i.e., the
peripheral velocity of the impeller).
-
Head varies as the square of the rotating speed.
-
Brake horsepower varies as
the cube of the rotating speed.
The affinity laws are useful for estimating pump performance at different rotating speeds or impeller
diameters D based on a pump with known characteristics. The following
two variations can be analyzed by these relationships:
-
By changing speed and maintaining constant impeller diameter, pump efficiency remains the
same, but head, capacity, and brake horsepower vary according
to the affinity laws.
-
By changing impeller diameter and maintaining constant speed, the pump efficiency for a
diffuser pump is not affected if the impeller diameter is changed by less than 5%.
However, efficiency changes if the impeller size is reduced enough to affect the
clearance between the casing and the periphery of the impeller.
The affinity laws assume that the system curve is known and that head varies as the
square of flow. The operating point is the intersection of the total system curve and the pump curve
(see Figure 19). Because the affinity law is
used to calculate a new condition caused by a flow or head change (e.g., reduced pump
speed or impeller diameter), this new condition also follows the same system curve. Figure 27 shows
the relationship of flow, head, and power as expressed by the affinity laws.
The affinity laws can also be used to predict the BEP at other pump speeds. As discussed in the
section on Pump Efficiency, the BEP follows a parabolic curve to zero as the pump speed is reduced
(Figure 26).
Multiple-speed motors can be used to reduce system overpressure at reduced flow. Standard two-speed motors are available with speeds of
1750/1150 rpm, 1750/850 rpm, 1150/850 rpm, and 3500/1750 rpm. Figure 28 shows the
performance of a system with a 1750/1150 multiple-speed pump. In the figure, curve A shows a
system’s response when the pump runs at 1750 rpm. When the pump runs at 1150 rpm, operation is
at point 1 and not at point 2 as the affinity laws predict. If the system were designed to operate
as shown in curve B, the pump would operate at shutoff and be damaged if run at 1150 rpm. This
example demonstrates that the designer must analyze the system carefully to determine the pump
limitation and the effect of lower speed on performance.
Variable-speed drives have a similar effect on pump curves. These drives normally have an infinitely
variable speed range, so that the pump, with proper controls, follows the system curve without any
overpressure. Figure 29 shows operation
of the pump in Figure 21 at 100%, 80%, 64%, 48%, and 32%
of the speed.
Although the variable-speed motor in this example can correct overpressure conditions, about 20% of
the operating range of the variable-speed motor is not used. The maximum speed required to provide
design flow and pressure is 80% of full speed (1400 rpm) and the practical lower limit is 30% (525
rpm) because of the characteristics of the system curve as well as pump and motor limitations. The
variable-speed drive and motor should be sized for actual balanced hydronic conditions.
The affinity laws can also be used to predict the effect of trimming the impeller to reduce
overpressure. If, for example, the system shown in Figure 29 were allowed to
operate at point 2, an excess flow of 15 to 25% would occur, depending on the shapes of the system
and pump curves. The pump affinity laws (Table 1) show that pump capacity varies
directly with impeller diameter. In Figure 29, the correct
size impeller operates at point 3. A diameter ratio of 0.8 would reduce the overcapacity from 125%
to 100%.
The second affinity law shows that head varies as the square of the impeller diameter.
For the pump in Figure 29 and an impeller
diameter ratio of 0.8, the delivered head of the pump is (0.8)2 = 0.64 or
64% of the design pump head.
The third affinity law states that pump power varies as the cube of the impeller diameter. For the
pump in Figure 29 and an impeller
diameter ratio of 0.8, the power necessary to provide the design flow is (0.8)3 = 0.512
or 51.2% of the original pump’s power.
In a single-volute centrifugal pump, uniform or near-uniform pressures act on the impeller at design
capacity, which coincides with the BEP. However, at other capacities, the pressures around the
impeller are not uniform and there is a resultant radial reaction (Figure
30).
Figure 31 shows the typical
change in radial thrust with changes in the pumping rate. Specifically, radial thrust decreases from
shutoff to the design capacity (if chosen at the BEP) and then increases as flow increases. The
reaction at overcapacity is roughly opposite that at partial capacity and is greatest at shutoff.
The radial forces at extremely low flow can cause severe impeller shaft deflection and, ultimately,
shaft breakage. This danger is even greater with high-pressure pumps.
11. NET POSITIVE SUCTION
CHARACTERISTICS
Particular attention must be given to the pressure and temperature of the water as it enters the
pump, especially in condenser towers, steam condensate returns, and steam boiler feeds. If the
absolute pressure at the suction nozzle approaches the vapor pressure of the liquid, vapor pockets
form in the impeller passages. The collapse of the vapor pockets (cavitation) is noisy and can be destructive to the pump impeller
(Figure 32).
The amount of pressure in excess of the vapor pressure required to prevent vapor pockets from forming
is known as the net positive suction
head required (NPSHR). NPSHR is a characteristic of a given
pump and varies with pump speed and flow. It is determined by the manufacturer and is included on
the pump performance curve.
NPSHR is particularly important when a pump is operating with hot liquids or is applied
to a circuit having a suction lift. The vapor pressure increases with water temperature and reduces
the net positive suction head available (NPSHA). Each pump has its
NPSHR, and the installation has its NPSHA, which is the total useful
energy above the vapor pressure at the pump inlet.
The following equation may be used to determine the NPSHA in a proposed design (Figure 33):
where
| hp = absolute pressure on
surface of liquid that enters pump, ft of head |
| hz = static
elevation of liquid above center line of pump (hz is negative if liquid
level is below pump center line), ft
|
| hvpa = absolute vapor pressure at
pumping temperature, ft |
| h and head losses in suction piping,
ft
|
To determine the NPSHA in an existing installation, the following equation may be used
(see Figure 34):
where
| ha = atmospheric head for
elevation of installation, ft |
| hs = head at inlet flange
corrected to center line of pump (hs is
negative if below atmospheric pressure), ft |
| V2/2g
head at point of measurement of hs,
ft
|
If the NPSHA is less than the pump’s NPSHR, cavitation, noise,
inadequate pumping, and mechanical problems will result. For trouble-free
design, the NPSHA must always be greater than the pump’s
NPSHR. In closed hot and chilled water systems where sufficient
system fill pressure is exerted on the pump suction, NPSHR is normally not a factor. Figure 34 shows pump curves
and NPSHR curves. Cooling towers and other open systems require calculations of
NPSHA.
A substantial amount of data is required to ensure that an adequate, efficient, and reliable pump is
selected for a particular system. The designer should review the following criteria:
-
Design flow
-
Pressure drop required for the most resistant loop
-
Minimum system flow
-
System pressure at maximum and minimum flows
-
Type of control valve: two-way or three-way
-
Continuous or variable flow
-
Pump environment
-
Number of pumps and standby
-
Electric voltage and current
-
Electric service and starting limitations
-
Motor quality versus service life
-
Water treatment, water conditions, and material selection
When a centrifugal pump is applied to a piping system, the operating point satisfies both the pump
and system curves (Figure 19). As the load changes, control
valves change the system curve and the operating point moves to a new point on the pump curve. Figure 35 shows the optimum regions to
use when selecting a centrifugal pump. The areas bounded by lines AB and AC represent operating
points that lie in the preferred pump selection range. However, because pumps are only manufactured
in certain sizes, selection limits of 66% to 115% of flow at the BEP are suggested. The satisfactory
range is that portion of a pump’s performance curve where the combined effect of circulatory
flow, turbulence, and friction losses are minimized. Where possible, pumps should be chosen to
operate to the left of the BEP because the pressure in the actual system may be less than design due
to overstated data for pipe friction and for other equipment. Otherwise, the pump operates at a
higher flow and possibly in the turbulent region (Stethem 1988).
However, if the designer is confident in the calculated design friction head loss for the system, the
pump should be selected as near the BEP as possible. If the pump is installed with a
variable-frequency drive (VFD), selecting the duty point slightly to the right of the BEP is even
better. As control valves modulate closed and the motor speed slows, the head and flow
of the pump drop, which moves the operating point down and to the left into a higher operating
efficiency region. Thus, by selecting the pump to the right of BEP, the pump’s efficiency
actually increases at part-load conditions, which is where systems typically operate.
In a large system, a single pump may not be able to satisfy the full design flow and yet provide both
economical operation at partial loads and a system backup. The designer may need to consider the
following alternative pumping arrangements and control scenarios:
-
Multiple pumps in parallel or series
-
Standby pump
-
Pumps with two-speed motors
-
Primary-secondary pumping
-
Variable-speed pumping
-
Distributed pumping
HVAC pumping systems are often designed for duty-standby operation wherein pumps (typically two
or more) are installed, with only one pump operating at a time. The other pump is on standby,
available to provide 100% flow redundancy in case the duty pump experiences failure or is shut
off for maintenance.
If the building does not require critical HVAC pumping service, then a duty-standby arrangement
may not be required and designing for multiple pumps in parallel may be more cost effective. The
appropriate level of redundancy should be discussed with the owner. For example, a flow capacity
split of 50:50 results in each pump being sized for 50% of the peak design flow; if one of the
pumps were unavailable, the remaining pump could provide approximately 70% of the peak design
flow rate (depending on the pump and system curves):
where
| n =number of pumps |
| Qn – 1 =flow rate at n – 1 |
| Qdesign =peak design flow rate |
This approach can reduce costs for equipment, pump installation, and electrical infrastructure. A
control strategy should also be considered for any parallel pumping application to optimize
operation and sequencing of the multiple pumps and further minimize operational cost.
An example of possible flow redundancy by application is shown in Table 2.
When pumps are applied in parallel, each pump
operates at the same head and provides its share of the system flow at that
head (Figure 36).
Generally, pumps of equal size are recommended, and the parallel pump curve is established by
doubling the flow of the single pump curve.
Plotting a system curve across the parallel pump curve shows the operating points for both single
and parallel pump operation (Figure 37).
Note that single-pump operation does not yield 50% flow. The system curve crosses the single
pump curve considerably to the right of its operating point when both pumps are running. This
leads to two important concerns: (1) the motor must be selected to prevent overloading during
operation of a single pump and (2) a single pump can provide standby service for up to 80% of
the design flow, the actual amount depending on the specific pump curve and system curve.
Construction of the composite curve for two dissimilar parallel pumps requires special care; for
example, note the shoulder in the composite pump curve in Figure
38.
Operation. The piping of parallel pumps (Figure 39) should permit
running either pump. A check valve is required in each pump’s discharge to prevent
backflow when one pump is shut down. Hand valves and a strainer allow one pump to be serviced
while the other is operating. A strainer protects a pump by preventing foreign material from
entering the pump. Using gages or a common gage with a trumpet valve, which includes several
valves as one unit, or pressure taps allows checking pump operation.
Flow can be determined (1) by measuring the pressure increase across the pump and using a factory
pump curve to convert the pressure to flow, or (2) by use of a flow-measuring station or
multipurpose valve. Parallel pumps are often used for hydronic heating and cooling. In this
application, both pumps operate during the cooling season to provide maximum flow and pressure,
but only one pump operates during the heating season.
When pumps are applied in series, each pump operates at the same flow rate and provides its share
of the total pressure at that flow (Figure 40). A
system curve plot shows the operating points for both single and series pump operation (Figure 41). Note
that the single pump can provide up to 80% flow for standby and at a lower power requirement.
As with parallel pumps, piping for series pumps should allow running either pump (Figure 42). A bypass with a
hand valve allows servicing one pump while the other is in operation. Operation and flow can be
checked the same way as for parallel pumps. A strainer prevents foreign material from entering
the pumps.
Note that both parallel and series pump applications require that the pump operating points be
used to accurately determine the actual pumping points. The manufacturer’s pump test curve
should be consulted. Adding too great a safety factor for pressure, using improper pressure drop
charts, or incorrectly calculating pressure drops may lead to a poor selection. In designing
systems with multiple pumps, operation in either parallel or series must be fully understood and
considered by both designer and operator.
A backup or standby pump of equal capacity and
pressure installed in parallel to the main pump is recommended to operate during an emergency or
to ensure continuous operation when a pump is taken out of operation for routine service. A
standby pump installed in parallel with the main pump is shown in Figure 37.
Primary-Secondary Pumping
In a primary-secondary or compound pumping arrangement, a secondary pump is selected to provide
the design flow in the load coil from the common pipe between the supply and return distribution
mains (Figure 43) (Coad 1985). The
pressure drop in the common pipe should not exceed 1.5 ft (Carlson 1972).
In circuit A of the figure, a two-way valve permits a variable flow in the supply mains by
reducing the source flow; a secondary pump provides a constant flow in the load coil. The source
pump at the chiller or boiler is selected to circulate the source and mains, and the secondary
pump is sized for the load coil. Three-way valves in circuits B and C provide a constant source
flow regardless of the load.
Variable-Speed Central Pumping
In a variable-speed pumping arrangement, constant flow pump(s) recirculate the chiller or boiler
source in a primary source loop, and a variable-speed distribution pump located at the source
plant draws flow from the source loop and distributes to the load terminals as shown in Figure 44. The speed of the
distribution pump is determined by a controller measuring differential pressure across the
supply-return mains or across selected critical zones. Two-way control valves are installed in
the load terminal return branch to vary the flow required in the load.
Variable-Speed Distributed Pumping
In a variable-speed distributed pumping arrangement, constant flow pump(s) recirculate the
chiller or boiler source in a primary source loop, and a variable-speed zone or building pump
draws flow from the source loop and distributes to the zone load terminals as shown in Figure 45. The speed of
the zone or building distribution pump is determined by a controller measuring zone differential
pressure across supply-return mains or across selected critical zones. Two-way control valves in
the load terminal return branch vary the flow required in the load.
Differential Pressure Control with
Predefined Control Curves
Intelligent variable-frequency-drive (VFD) products control differential pressure according to
predefined control curves. Typical control curves are either constant or variable (proportional)
pressure across the pump (Europump and Hydraulic Institute 2004). These predefined control
curves are programmed into the integrated pump controller (Bidstrup 2002). Control can be
achieved by using sensors (e.g., flow or pressure sensors), or by sensorless control.
Constant-pressure control is recommended if pressure losses in the distribution and supply
systems (pipe, boiler, heat exchanger, etc.) are low. Figure 46 shows differential
pressure across the pump with constant-pressure control. A1 to A3 are different operating
points. The differential pressure across the pump is constant and independent of flow. Because
of the low pressure losses in the distribution and supply systems, differential pressure across
the control valves is nearly constant, and optimal control performance is obtained at both full-
and part-load operation.
If pressure losses in the distribution and/or supply system are significant, variable-
(proportional-) pressure control is recommended. Figure 47 shows
the differential pressure across the pump when this method is selected. A1 to A3 are different
operating points. Differential pressure across the pump increases when flow increases.
Proportional pressure control compensates for pressure loss in the distribution and supply
systems with a linear approximation, with the result that differential pressure across the
control valves is nearly constant, and good control performance is obtained at both full- and
part-load operation.
Variable- (quadratic-) pressure control is also recommended if pressure losses in the
distribution and/or supply system are well known and it is ensured that the system is correctly
balanced. Figure 48 shows the
differential pressure across the pump when quadratic control is selected. A1 to A3 are different
operating points. Differential pressure across the pump increases exponentially as flow
increases. Quadratic-pressure control compensates for pressure loss with a quadratic
approximation to the system curve, enabling increased energy savings over proportional- pressure
control at part-loads.
Different settings of constant- and variable-pressure control can be selected to fit the pump to
the actual system resistance. Control curves are selected manually or by an external signal
(e.g., bus or infrared communication). Variable differential pressure control can also be
achieved by remote feedback from critical locations; if the critical locations can be identified
and remote control is an option, this can offer the best potential pump energy savings.
Figure 49
demonstrates the improvement in efficiency of
four-pole (1800 rpm) 25 to 125 hp motors from old, standard-efficiency models to
current standards and available premium efficiency models.
Electric motors drive most centrifugal pumps for hydronic systems. Internal combustion engines or
steam turbines power some pumps, especially in central power plants for large installations.
Electric motors for centrifugal pumps can be any of the horizontal or vertical electric motors
described in Chapter
45. The sizing of electric motors is critical because of the cost of electric power and the
desire for improved efficiency. Non-overloading motors should be used; that is, the motor nameplate
rating must exceed the pump brake horsepower (kW) at any point on the pump curve.
In addition to typical induction electrical motors, there is also a class of high-efficiency motors
known as electronically commutated motor (ECMs). The key
differences from standard induction motors are that ECMs (1) will not operate on main power, (2)
require a variable-speed controller to operate, and (3) are inherently higher in efficiency than
induction motors because of permanent magnet rotor construction. ECM motors are commonly available
up to 3.35 hp, although larger sizes are available.
Many pumps for hydronic systems are close coupled, with the pump impeller mounted on the motor shaft
extension. Other pumps are flexible coupled to the electric motor through a pump mounting bracket or
frame. A pump on a hydronic system with variable flow has a broad range of power requirements, which
results in reduced motor loading at low flow.
Many variable-speed drives (VSDs) are available for operating centrifugal pumps. Primarily, these
include variable-frequency drives, and, occasionally, direct-current, wound rotor, and eddy current
drives. Each drive has specific design features that should be evaluated for use with hydronic
pumping systems. The efficiency range from minimum to maximum speed (as shown in Figure 50)
should be investigated.
15. ENERGY CONSERVATION IN PUMPING
Pumps for heating and air conditioning consume appreciable amounts of energy. Economical use of
energy depends on the efficiency of pumping equipment and drivers, as well as the use of the pumping
energy required. Equipment efficiency (sometimes called the wire to water efficiency) shows how much
energy applied to the pumping system results in useful energy distributing the water. For an
electric-driven, constant speed pump, the equipment efficiency is
where
| ηe = equipment efficiency, 0 to 1 |
| ηp = pump efficiency, 0 to 1 |
| ηm = motor efficiency, 0 to 1 |
For a variable-speed pump, the variable-speed drive efficiency ηv (0 to 1) must be included in the equipment efficiency
equation:
16. INSTALLATION, OPERATION, ANDCOMMISSIONING
-
Pumps may be base-plate-mounted (Figure
51), either singly or in packaged sets, or installed in-line directly in the
piping system (Figure 52). Packaged sets
include multiple pumps, accessories, and electrical controls shipped to the job site on
one frame. Packaged pump sets may reduce the requirements for multiple piping and field
electrical connections and can be factory tested to ensure specified performance.
Pumping equipment, accessories, electrical controls, and/or packaged systems, must
comply with applicable seismic requirements for anchorage and equipment seismic
certifications, as described in local building codes.
-
A concrete pad provides a secure mounting surface for anchoring the pump base plate and
raises the pump off the floor to permit housekeeping. The minimum weight of
concrete that should be used is 2.5 times the weight of the pump assembly.
The pad should be at least 4 in. thick and 6 in. wider than the pump base
plate on each side.
-
In applications where the pump bolts rigidly to the pad base, level the pad base, anchor
it, and fill the space between pump base and the concrete with a non-shrink grout. Grout
prevents the base from shifting and fills in irregularities. Pumps mounted on vibration
isolation bases require special installation (see the section on Vibration Isolation and
Control in Chapter 49 of the 2023 ASHRAE Handbook—HVAC
Applications).
-
Support in-line pumps independently from the piping so that pump flanges are not
overstressed.
-
Once the pump has been mounted to the base, check the alignment of the motor to the pump.
Align the pump shaft couplings properly and shim the motor base as required. Incorrect
alignment may cause rapid coupling and bearing failure.
-
Pump suction piping should be direct and as smooth as possible. Install a strainer
(coarse mesh) in the suction to remove foreign particles that can damage the pump. Use a
straight section of piping at least 5 to 10 diameters long at the pump inlet and long
radius elbows to ensure uniform flow distribution. Suction diffusers may be installed in
lieu of the straight pipe requirement where spacing is a constraint. Eccentric reducers
at the pump flange reduce the potential of air pockets forming in the suction line.
-
If a flow-measuring station (venturi, orifice plate, or balancing valve) is located in
the pump discharge, allow 10 diameters of straight pipe between the pump discharge and
the flow station for measurement accuracy.
-
Pipe flanges should match the size of pump flanges. Mate flat-face pump flanges with
flat-face piping flanges and full-face gaskets. Install tapered reducers and increasers
on suction and discharge lines to match the pipe size and pump flanges.
-
If fine mesh screen is used in the strainer at initial start-up to remove residual
debris, replace it with normal-sized screen after commissioning to protect the pump and
minimize the suction pressure drop.
-
Install shutoff valves in the suction and discharge piping near the pump to permit
removing and servicing the pump and strainer without draining the system. Install a
check valve in the pump discharge to prevent reverse flow in a nonrunning pump when
multiple pumps are installed.
-
Where seismic considerations allow, install vibration isolators in the pump suction and
discharge lines to reduce transmission of vibration noise to building spaces (Figure 52). Properly
located pipe hangers and supports can reduce transmission of piping strains to the pump.
-
Investigate alternatives to conventional fittings. A suction diffuser in the pump inlet
is an alternative to an eccentric reducer and contains a strainer. Separate strainers
can be specified with screen size. A multipurpose valve in the pump discharge is an
alternative way to combine the functions of shutoff, check, and balancing valves.
-
Each pump installation should include pressure gages and a gage cock to verify system
pressures and pressure drop. As a minimum, pressure taps with an isolation valve and
common gage should be available at the suction and discharge of the pump. An additional
pressure tap upstream of the strainer allows checking for pressure drop.
Commissioning Base-Mounted
Centrifugal Pumps
-
Turn off power and tag disconnect off.
-
Remove coupling guard.
-
Check alignment. See instruction manual for alignment guidelines.
-
Rotate shaft several revolutions to ensure there is no binding.
-
Replace coupling guard.
-
Pressurize pump by opening suction and discharge valves.
-
Loosen vent plug on top of casing to release air. When all air is released, tighten
vent plug.
-
Close discharge valve.
-
Bump motor and check rotation. Rotation arrow is located on pump casing.
-
Turn on power to pump. Slowly open discharge valve until specified total
head is achieved.
-
If baseplate is not grouted, there might be some vibration. Loosen baseplate mounting
bolts one at a time. When vibration stops or is reduced, shim and retighten bolt.
Table 3 lists possible causes
and recommended solutions for pump or system noise. Table 4 lists
possible causes and recommended solutions for inadequate circulation.
ASHRAE. 1985. Hydronic systems: Variable-speed pumping
and chiller optimization. ASHRAE Technical Data Bulletin
1(7).
ASHRAE. 1991. Variable-flow pumping systems. ASHRAE Technical Data Bulletin 7(2).
ASHRAE. 1998. Fundamentals of water
system design. Self-Directed Learning Course.
Beaty, F.E., Jr. 1987. Sourcebook
of HVAC details. McGraw-Hill, New York.
Carrier. 1965. Carrier handbook of
air conditioning system design. McGraw-Hill, New York.
Clifford, G. 1990. Modern heating,
ventilating and air conditioning. Prentice Hall, New York.
Crane Co. 1988. Flow of fluids through valves, fittings,
and pipe. Technical Paper 410 (410M). Joliet, IL.
Dufour, J.W. and W.E. Nelson. 1993. Centrifugal pump sourcebook. McGraw-Hill, New York.
Garay, P.N. 1990. Pump application
desk book. Fairmont Press, Lilburn, GA.
Haines, R.W. and C.L. Wilson. 1994. HVAC systems design handbook, 2nd ed. McGraw-Hill, New York.
Hegberg, R.A. 1991. Converting constant-speed hydronic
pumping systems to variable-speed pumping. ASHRAE Transactions
97(1):739-745. Paper NY-91-11-1.
Karassik, I.J. 1989. Centrifugal
pump clinic. Marcel Dekker Inc., New York.
Karassik, I.J., W.C. Krutzsch, W.H. Fraser, and J.P.
Messina, eds. 1986. Pump handbook. McGraw-Hill, New York.
Levenhagen, J. and D. Spethmann. 1993. HVAC controls and systems. McGraw-Hill, New York.
Lobanoff, V.S. and R.R. Ross. 1986. Centrifugal pumps design and application. Gulf Publishing,
Houston.
Matley, J., ed. 1989. Progress in
pumps. Chemical Engineering, McGraw-Hill, New York.
McQuiston, F.C. and J.D. Parker. 1988. Heating, ventilating and air conditioning. John Wiley & Sons, New
York.
Monger, S. 1990. Testing and
balancing HVAC air and water systems. Fairmont Press, Lilburn, GA.
Rishel, J.B. 1994. Distributed pumping for pumping for
chilled- and hot-water systems. ASHRAE Transactions
100(1):1521-1527. Paper No-94-24-3.
Trane Co. 1965. Trane manual of air
conditioning. La Crosse, WI.