CHAPTER 29. AIR CLEANERS FOR PARTICULATE CONTAMINANTS

 

This chapter discusses removal of contaminants from both ventilation and recirculated air used for conditioning building interiors. The filters mentioned in this chapter are primarily used for HVAC systems and for the protection of equipment. Complete air cleaning may require removing of airborne particles, microorganisms, and gaseous contaminants, but this chapter only covers removal of airborne particles and briefly discusses bioaerosols. Chapter 47 of the 2023 ASHRAE Handbook—HVAC Applications covers the removal of gaseous contaminants. Chapter 62 of the 2023 ASHRAE Handbook—HVAC Applications covers bioaerosols and UV air cleaners in more depth.

The total suspended particulate concentration in applications discussed in this chapter seldom exceeds 2 mg/m3 and is usually less than 0.2 mg/m3 of air (Chapter 11 of the 2022 ASHRAE Handbook—Fundamentals). This is in contrast to flue gas or exhaust gas from processes, where dust concentrations typically range from 200 to 40,000 mg/m3. Chapter 46 of the 2023 ASHRAE Handbook—HVAC Applications discusses exhaust gas control.

Most air cleaners discussed in this chapter are not used in exhaust gas streams because of the extreme dust concentration, large particle size, high temperature, high humidity, and high airflow rate requirements that may be encountered in process exhaust. However, the air cleaners discussed here are used extensively in supplying makeup air with low particulate concentration to industrial processes.

1. TERMINOLOGY

 Definitions

Aerodynamic diameter. The diameter of a spherical particle with a density of 1000 kg/m3 and the same settling velocity as the irregular particle of interest.

Aerosol. Solid and/or liquid particles suspended in air.

Air cleaner. Device or system for removing contaminants from air in a ventilation system, building or other enclosed space.

Air filter. A device containing filter media, typically mounted in a frame, that is designed to remove particles from an air stream onto the fibers in the air filter media.

Air filter media. Portion of a filtration system (such as close-woven textiles, metal screens, papers, nonwoven fabrics, granular beds, or porous media) that effects separation of particles from air.

Air purifier. See Air cleaner

Arrestance. Measure of the ability of a filter to remove a standard test from the air passing through it, under given operating conditions. Arrestance is expressed as a percentage by weight of the test dust (ISO 29464).

Bioaerosol. Particles of biological origin suspended in air (ISO 29464).

Dust-holding capacity. Total weight of synthetic loading dust captured by an air-cleaning device added up over all of the incremental dust loading steps.

Duct air cleaner. See In-duct air cleaner

Duct-mounted air cleaner. See In-duct air cleaner

Electret air filter. An air filter in which the fibers in the filter media contain a one-time initial electrical charge designed to boost particle capture efficiency, particularly early in the life of the filter.

Electrically enhanced air purifier. See Electrically enhanced air cleaner

Electrically enhanced air cleaner. A type of electronic air cleaner that includes filter media positioned within an electric field and/or actively ionically charged to increase the particle collection efficiency of the filter media. Additionally, particles may be ionically precharged prior to their arrival at the filter media.

Electronic air cleaner (EAC). An air cleaner that uses electrical power for at least part of the mechanism by which particles are removed from an airstream. Types include electrostatic precipitators (ESPs) and electrically enhanced air purifiers, among others.

Electrostatic precipitator (ESP). A type of electronic air cleaner that uses high-voltage wires or points to charge particles via corona discharge and then move the particles transverse to the airflow to grounded collection plates by the imposition of an electric field via the same or secondary plate high voltage electrodes.

Fibrous air filter. See Air filter

Fractional efficiency. See Particle size removal efficiency

In-duct air cleaner. An air cleaner designed to be installed in an HVAC duct.

In-room air cleaner. A stand-alone device that includes an air cleaner and a blower, or other means to move air through the air cleaner, in a housing. In-room air cleaners typically have an electrical cord and are plugged into an electrical outlet.

In-room air purifier. See In-Room Air Cleaner

Mechanical media air filter. An air filter in which particle removal is accomplished via mechanical filtration mechanisms only and not via electrostatic effects.

Media air filter. See Air Filter

Most penetrating particle size (MPPS). The size of particles that most easily pass through a filter, whether the filter is infiltration or air purifier system.

Particle size removal efficiency. The fraction or percentage of particles retained by an air cleaner for a given particle-size range.

Particulate air filter. Device for separating solid and/or liquid particles from an airstream passing through the device.

Particulate matter (PM). Solid and/or liquid particles of various sizes.

Penetration. The fraction or percentage of particles that pass through an air cleaner for a given particle-size range.

Portable air purifier. See In-room air cleaner

Pressure drop. See Resistance to airflow

Removal Efficiency by Particle Size. See Particle size removal efficiency

Resistance to airflow. Difference in absolute (static) pressure between two points in an airflow system. This parameter is often called pressure drop.

Resistance to airflow. Difference in absolute (static) pressure between two points in an airflow system. This parameter is often called pressure drop.

Respirable fraction. The subfraction of the inhaled particles that penetrates into the alveolar region of the lung (i.e., includes the respiratory bronchioles, the alveolar ducts and sacs)

Room air cleaner. See In-room air cleaner

Room air purifier. See In-room air cleaner

Stand-alone air cleaner. See In-room air cleaner

 Acronyms

AFI. Air Filter Institute.

AHRI. Air-Conditioning, Heating, and Refrigeration Institute.

AHU. Air-handling unit.

ASME. American Society of Mechanical Engineers.

BI/BO. Bag-in/bag-out.

CEN. Comité Européen de Normalisation.

DEHS. Di-ethyl-hexyl-sebacate.

DHC. Dust-holding capacity.

DOP. Dioctyl phthalate.

EN. European norm (European standard).

EPA. Environmental Protection Agency.

EB. Existing buildings.

ETS. Environmental tobacco smoke.

HEPA. High-efficiency particulate air.

IEST. Institute of Environmental Sciences and Technology.

IPA. Isopropyl alcohol.

ISO. International Organization for Standardization.

LCC. Life-cycle cost.

LEED. Leadership in Energy and Environmental Design.

MERV. Minimum efficiency reporting value.

MIL-STD. U.S. Military standard.

MPPS. Most penetrating particle size.

MSHA. Mine Safety and Health Administration.

NAFA. National Air Filtration Association.

NC. New construction.

NIOSH. National Institute for Occupational Safety and Health.

NIST. National Institute of Standards and Technology.

PAO. Polyalphaolefin.

PM. Particulate matter.

PSE. Particle size removal efficiency.

PSL. Polystyrene latex.

UL. Underwriters Laboratory.

ULPA. Ultra-low particulate air.

VAV. Variable air volume.

2. ATMOSPHERIC AEROSOLS

Atmospheric contaminants are a complex mixture of smokes, mists, fumes, dry granular particles, bioaerosols, and natural and synthetic fibers. When suspended in a gas such as air, this mixture is called an aerosol. A sample of atmospheric aerosol usually contains soot and smoke, silica, clay, decayed animal and vegetable matter, organic materials in the form of lint and plant fibers, and metallic fragments. It may also contain living organisms, such as mold spores, bacteria, and plant pollens, which may cause diseases or allergic responses. (Chapter 11 of the 2021 ASHRAE Handbook—Fundamentals contains further information on atmospheric contaminants.) A sample of atmospheric aerosol gathered at any point generally contains materials common to that locality, together with other components that originated at a distance but were transported by air currents or diffusion. These components and their concentrations vary with the geography of the locality (urban or rural), season of the year, weather, direction and strength of the wind, and proximity of dust sources.

Mobility Versus Particle Diameter Median number particle size distributions for each geographical region (CSSA = Central, South, and Southeast Asia; EA = East Asia; EU = Europe; NAAN = North America, Australia, & New Zealand; LA = Latin America) (Wu and Boor 2021)

Figure 1. Mobility Versus Particle Diameter Median number particle size distributions for each geographical region (CSSA = Central, South, and Southeast Asia; EA = East Asia; EU = Europe; NAAN = North America, Australia, & New Zealand; LA = Latin America) (Wu and Boor 2021)


Aerosol sizes range from 0.01 µm and smaller for freshly formed combustion particles and radon progeny; to 0.1 µm for aged cooking and cigarette smokes; from 0.1 to 10 µm for airborne dust, microorganisms, and allergens; and up to 100 µm and larger for airborne soil, pollens, and allergens.

Number concentrations of atmospheric aerosols generally peak at submicron sizes and decrease rapidly as the particulate size increases above 1 µm. In fact, number concentrations of particles in urban aerosols are predominantly below 0.5 µm, dependent upon geographic location.

For a given size, the concentration can vary by several orders of magnitude over time and by location, particularly near an aerosol source, such as human activities, equipment, furnishings, and pets (Block and Bokalders 2010). This wide range of particulate size and concentration makes it impossible to design one cleaner for all applications.

3. AEROSOL CHARACTERISTICS

The characteristics of aerosols that most affect air filter performance include particle size and shape, mass, concentration, and electrical properties. The most important of these is particle size. Figure 3 in Chapter 11 of the 2021 ASHRAE Handbook—Fundamentals gives data on the sizes and characteristics of a wide range of airborne particles that may be encountered.

Particle size in this discussion refers to aerodynamic particle size. Particles less than 0.1 µm in diameter are generally referred to as ultrafine-mode or nanoparticles, those between 0.1 and 2.5 µm are termed fine mode, and those larger than 2.5 µm as coarse mode. Whereas ultrafine- and fine-mode particles may be formed together, fine- and coarse-mode particles typically originate by separate mechanisms, are transformed separately, have different chemical compositions, and require different control strategies. Vehicle exhaust is a major source of ultrafine particles. Ultrafines are minimally affected by gravitational settling and can remain suspended for days at a time. Fine-mode particles generally originate from condensation or are directly emitted as combustion products. Many microorganisms (bacteria and fungi) either are in this size range or produce components this size. These particles are less likely to be removed by gravitational settling and are just as likely to deposit on vertical surfaces as on horizontal surfaces. Coarse-mode particles are typically produced by mechanical actions such as erosion and friction. Coarse particles are more easily removed by gravitational settling, and thus have a shorter airborne lifetime.

For industrial hygiene purposes, particles ≤ 5 µm in diameter are considered respirable particles (RSPs) because a large percentage of this size range has been shown to reach the alveolar region of the lungs. A cutoff of 5.0 µm includes 80 to 90% of the particles that can reach the functional pulmonary region of the lungs (James et al. 1991; Phalen et al. 1991). Willeke and Baron (1993) describe a detailed aerosol sampling technique for RSPs, including the use of impactors. See also the discussion in the section on Sizes of Airborne Particles in Chapter 11 of the 2021 ASHRAE Handbook—Fundamentals.

In the United States, particulate matter (PM) levels in outdoor air are regulated by the Environmental Protection Agency (EPA). Outdoor PM is a complex mixture of small particles and liquid droplets; their effects on health are related to size. Smaller particles have more impact because they penetrate deeper into the respiratory system. Currently, there are two regulated size ranges:

  • PM10. Inhalable particles with diameters that are generally 10 μm and smaller according to the EPA; typical sources include road dust and industrial emissions

  • PM2.5. Fine inhalable particles with diameters that are generally 2.5 μm and smaller; the main sources are industrial emissions and combustion exhaust from automobiles, power plants, and heating systems

PM1, which is not regulated, consists of fine and ultrafine particles of less than 1 μm aerodynamic diameter.

The U.S. Clean Air Act requires the EPA to impose both primary standards designed to protect public health, and secondary standards intended to protect against adverse environmental effects. The limits presently in place (Federal Register 2013) are shown in Table 1. There is no filtration requirement for areas of noncompliance.

Bioaerosols are a diverse class of particles of biological origin. They include bacteria, fungal spores, fungal fragments, pollen grains, subpollen particles, viruses, pet- and pest-associated allergens, and plant debris (Fröhlich-Nowoisky et al. 2016). They are of particular concern in indoor air because of their association with allergies and asthma and their ability to cause disease. Chapters 10 and 11 of the 2021 ASHRAE Handbook—Fundamentals contain more detailed descriptions of these contaminants.

Bioaerosols range in size from 0.01 to 100 µm. Single bacterial cells are approximately 1 µm or less in aerodynamic diameter; however, they are often transported as larger bacterial cell agglomerates (~2 to 5 µm) or attached to other biological and abiotic particles. Unicellular fungal spores are generally 2 to 5 µm in aerodynamic diameter and multicellular fungal spores are larger than 10 µm (Després et al. 2012; Qian et al. 2012). Fungal fragments are typically less than 1 µm in size (Mensah-Attipoe et al. 2016). Pollen grains range in size from 10 to 100 µm (Després et al. 2012), while subpollen particles span ~0.01 µm to several micrometers in size (Taylor et al. 2004). Individual viruses can be as small as 0.02 to 0.03 µm, but are typically carried on larger particles (Verreault et al. 2008). Pet- and pest-associated allergens are approximately 1 to ≥20 µm in size (O’Meara and Tovey 2000). Virus- or bacteria-containing particles (from human sneezing, coughing, singing, etc.) include saliva/sputum and other compounds from the human respiratory tract, such that these particles will be bigger (often much bigger) than the individual virus or bacterium.

Table 1 U.S. EPA Standards for Particulate Matter in Outdoor Air

Type of Standard

Time Period Applicable

PM10, μg/m3

PM2.5, μg/m3

Primary

24 h

150

35

 

1 yr

—

12

Secondary

24 h

150

35

 

1 yr

—

15

Source: EPA (2015).


Throughout the COVID-19 pandemic, the terms droplet, droplet nuclei, aerosol particle, etc., were used in different ways by different people, especially across the infectious disease to aerosol science areas. To clearly understand these discussions, determine which use of the words is important in context. However, generally speaking drop or droplet is used to mean larger pieces of wet saliva/sputum/biological content. Depending on the person and time, this may mean different sizes, including bigger than 5 μm, bigger than 10 μm, or even bigger than 100 μm. When used, droplet most often means bigger particles that will fall out of still air very quickly. Droplet nuclei is used to mean smaller particles, but the use seems to be less specific. Aerosols or aerosol particles are used to indicate particles that can stay in the air for many minutes, hours, or longer. In this context, it may mean particles emitted from a person at that size or that dried down from bigger particles.

4. AIR-CLEANING APPLICATIONS

Different air-cleaning applications require different degrees of air cleaning effectiveness. In some industrial environments, ventilation removing only the larger dust particles from the airstream may produce acceptable cleanliness of the structure, protection of mechanical equipment, and employee health.

Certain industrial processes may also generate finer particulate contaminants that can impact employee health and may require a higher level of filtration.

In other applications, surface discoloration must be prevented. Unfortunately, the smaller components of atmospheric aerosol are the worst offenders in smudging and discoloring building interiors. Air cleaners or medium- to high-efficiency filters are required to remove smaller particles, especially the respirable fraction, which often must be controlled for comfort and health reasons. In cleanrooms or when radioactive or other dangerous particles are present, high- or ultrahigh-efficiency filters should be selected. For more information on cleanrooms, see Chapter 19 of the 2023ASHRAE Handbook—HVAC Applications.

Major factors influencing filter design and selection include (1) degree of air cleanliness required, (2) specific particle size range or aerosols that require filtration, (3) aerosol concentration, (4) resistance to airflow through the filter, (5) design filter for sealing and face velocity to achieve published performance and to include the capability of HVAC system to push air through it, (6) change-out cycle requirements, (7) energy consumption requirements, (8) special disposal mandates, and (9) resistance to certain conditions (physical, chemical, or biological).

5. MECHANISMS OF PARTICLE COLLECTION

In particle collection, air cleaners made of fibrous media rely on the following five main principles or mechanisms (Figure 2):

Straining or Sieving. The coarsest kind of filtration strains particles through an opening smaller than the particle being removed. It is most often observed as the collection of large particles and lint on the filter surface. The mechanism is not adequate to achieve the filtration of submicrometre aerosols through fibrous matrices, which occurs through other physical mechanisms, as follows.

Inertial Impingement. When particles are large or dense enough that they cannot follow the airstream around a fiber, they cross over streamlines, hit the fiber, and remain there if the attraction is strong enough. With flat-panel and other minimal-media-area filters having high air velocities (where the effect of inertia is most pronounced), the particle may not adhere to the fiber because drag and bounce forces are so high. In this case, a viscous coating (preferably odorless and nonmigrating) is applied to the fiber to enhance retention of the particles. This adhesive coating is critical to metal mesh impingement filter performance. This is also called inertial impaction.

Interception. Particles that follow the airstream close enough to a fiber that the particle contacts the fiber and remains there mainly because of van der Waals forces (i.e., weak intermolecular attractions between temporary dipoles). The adhesion process depends on air velocity through the media being low enough not to dislodge the particles; particles may be dislodged by other particles, causing shedding through the filter with repeated bounces. Interception is the predominant capture mechanism in extended-media filters such as bag and deep-pleated rigid cartridge types.

Diffusion. The path of very small particles is not smooth but erratic and random within the airstream. This is caused by gas molecules in the air bombarding them (Brownian motion), producing an erratic path that brings the particles close enough to a media fiber to be captured by interception. As more particles are captured, a concentration gradient forms in the region of the fiber, further enhancing filtration by diffusion and interception. The effects of diffusion increase with decreasing particle size and media velocity.

Electrostatic Effects. Particle or media electrostatic charge can produce changes in dust collection affected by the electrical properties of the airstream. Some particles may carry a natural charge. Passive electrostatic (without a power source) filter fibers are often electrostatically charged during their manufacture or (in some materials) by blowing dry air through the media. Charges on the particle and media fibers can produce a strong attracting force if opposite. The influence of this mechanism is highest when the media is new and clean. As the filter captures dust on the fibers, the particles will mask the charge, leading to lower collection efficiency.

Electrostatic precipitators, which are a class of electronic air cleaners, capture particles by charging them with high-voltage wires and then capturing the particles on oppositely charged plates. The mechanism is similar to that used with charged media, except the charging of the particles is intentionally induced by the air cleaner and the devices require power to operate.

Collection Mechanisms for Filter Fiber

Figure 2. Collection Mechanisms for Filter Fiber


Ionizers may be used to enhance particle capture by producing charged particles that will stick to a following filter’s fibers. This mechanism is similar to that of the charged filters of electronic air cleaners in that oppositely charged particles and collection surfaces are fundamental to the collection of particles. Ionizers are also used to create ions that attach to particles in the air, which in turn leads to agglomeration (particles sticking together to form larger particles that are more easily removed by a filter than the original, smaller particles). Ionizers not immediately followed by a filter may cause charged or agglomerated particles to stick to other surfaces such as walls, floors, drapes, and lungs.

Chemical Effects. Chemical effects can also remove particles from air. Reactive air cleaners (RACs) include a variety of technologies that rely on some form of chemistry to work. They require power to operate. RACs may introduce reactive species into the air that may reduce particles of some chemical contents to CO2 and water or other intermediary species (e.g., organic particles will react with ozone, whereas aluminosilicates may not). Since the mechanisms vary across the types of devices and are not clearly understood, they are not elucidated here.

6. TYPES OF AIR CLEANERS AND PERFORMANCE

Common air cleaners for particulate removal are broadly grouped as described below. These types of air cleaner exist in both HVAC and in-room styles. Most of the discussion below is aimed at HVAC-type devices, but the technology details are applicable to both. Users of in-room air cleaners (IRAC) should refer to Chapter 66 in the 2023 ASHRAE Handbook—HVAC Applications for more details specific to in-room applications.

Common air cleaners can be grouped as follows:

  • Media filters constructed from fibers in various configurations

  • Electronic air cleaners, which rely on electrostatic effects for removal efficiency and require supplied power to operate

  • Air cleaners that rely on chemical effects to remove particles and usually require supplied power to operate

  • Combination air cleaners that use two or more technologies. In addition to those mentioned previously, they may include gas-phase removal or bioaerosol removal/inactivation technologies such as carbon filters or ultraviolet (UV) lamps

 Media Filters

Media filters are typically made from filter media in the form of paper or batting consisting of fibers in various types, sizes, and configurations. The units collect dust directly in and on the fibers at various efficiencies and with varying dust-holding capabilities. They can be static or renewable media devices and do not need separate power sources other than that needed for the HVAC or IRAC fan. The filters are discussed in more detail below, in approximate order of increasing particle removal efficiency.

Panel Filters. Also known as impingement filters, these are flat pads. Thus, the media velocity is always equal to the duct velocity. These filters can be constructed from a variety of media, including spun glass, synthetic fibers such as polyester, polyurethane foam, natural fibers, dry plastics, and various metals that may be fibrous or expanded sheets. Using these coarse fiber media, these filters are typically characterized by a low initial pressure drop and efficiencies not above MERV 6.

As filter efficiency increases, resistance to airflow often increases for the same airflow rate. Therefore, to achieve greater filtration efficiencies while maintaining a pressure drop within the design limits of HVAC systems, the media area exposed to the airstream may be increased. These extended-surface filters include pleated panels, mini-pleats, bag (or pocket) filters, and compact filters. The products most commonly use nonwoven fiber mats or blankets of varying thicknesses, fiber sizes, and densities.

The most commonly used media for the construction of pleated panels include carded and spunbond synthetics such as polyester and polypropylene as well as natural fibers such as cotton. Pleat separation may be maintained through the use of a variety of tech-niques, including the pleating of an expanded metal mesh layer along with the media, the use of paperboard or polymer combs, hot-melt glue strips, adhesive-coated string, or corrugated metal. New technologies that are becoming more popular include materials such as cellulose and polylactic acid (PLA) fibers, which can be used to meet certified biobased requirements. These filters typically fall into the MERV 7 to MERV 13 efficiency range.

Before 2000, bag or pocket filters used air-laid micro-fiberglass almost exclusively; however, since then a number of nonwoven synthetic media have been developed that use materials such as polypropylene and polyester. The media are most often constructed of meltblown and spunbond combinations and are almost always charged to achieve a given efficiency at a lower resistance to airflow than uncharged types. The use of nanofibers has recently seen more widespread use for enhancing the efficiency of these products.

The individual pockets may be stitched or heat-sealed around the perimeter. The desired spacing between the media layers forming the pocket is controlled either by a span stitch or media web. This prevents the pocket from “ballooning” and restricting the airflow. The completed pockets are then assembled into a frame parallel to each other in the direction of the airflow. These products are normally offered in the MERV 10 to MERV 16 range.

Compact filters include both box filters and mini-pleat products. The products cover the same efficiency range as pocket filters; however, as the name implies, they can be used in installations where there is insufficient depth to accommodate a bag filter. Box filters, also referred to as rigid boxes or cells, use the same media as bag filters.

Because of the tight spacing requirements between pleats, special media were developed for mini-pleat products. These include both wet-laid nonwovens as well as synthetics. Spacing between the pleats is physically maintained by use of corrugated aluminum, hot-melt beads, or string spacers. Some hybrid versions use a media that can be embossed for maintaining spacing. These media may be supported by wire mesh or may be laminated to a stiffer nonwoven material (e.g., a spunbond material) to achieve the rigidity requirements and to protect the more fragile efficiency layer from abrasion. In still other designs, the media may be self supporting or, in the case of bag filters, the design uses the airstream to inflate the pockets and maintain spacing.

Extended-surface filters may also be constructed using expanded polytetrafluoroethylene (ePTFE) membranes. These products typically fall into HEPA classifications but can also be found at the very high end of the MERV range. Applications may include semiconductor, microelectronics, pharmaceutical, and gas turbine inlet filtration.

Efficiencies for extended-surface filters are usually higher than those for panel filters. The dust-holding capacities are also generally higher than for impingement filters simply due to the increased media area. As an example, a 24 × 24 × 12 in. deep V-cell product may use up to 200 ft2 of media area and have a typical media velocity of 10 fpm at 2000 cfm system flow. A flat panel filter in the same installation would have a media velocity of 500 fpm. Hence a higher efficiency media may exhibit more resistance to airflow, but with significantly more media area the media velocity may be lowered.

Initial resistance on an extended-surface filter varies with the choice of media and filter geometry. Depth in direction of airflow varies from ~1 to 36 in.

Electret filters require no power in HVAC installations and are composed of electrostatically charged media fibers. Various manufacturing processes are used, many of them producing mats that contain both positively and negatively charged fibers. Charged-fiber filter efficiency is determined by both the normal collection mechanisms of a media filter and the strong local electrostatic effects (related to the amount of electrostatic charge). The effects improve clean filter efficiency over similar uncharged media without increasing resistance to airflow. However, ultrafine-particle dust collected on the fibers usually reduces the efficiency as electrets age. Electret filters are also discussed in ASHRAE Standard 52.2, Appendix J.

HEPA (high-efficiency particulate air) and ULPA (ultra-low-penetration air) are filters designed to target the MPPS for a given flow rate. The original U.S. MIL standard for efficiency of a HEPA filter specified that it must be a minimum of 99.97% efficient for 0.3 μm particles. There are now a number of differing HEPA filter standards on the market that are described in more detail in section 8 of this chapter. HEPA and ULPA filters are made in extended-surface configurations of deep folds or a mini-pleat style of sub-micrometer glass fiber paper. Synthetic materials, such as ePTFE and nanofibers, are also common materials for HEPA/ULPA. These are usually combined with a spunbond scrim layer to protect the membrane.

These filters are the standard for cleanroom, nuclear, and toxic particulate applications and are increasingly used in medical and pharmaceutical applications. Traditional HEPA filters for HVAC use are often 12 in. deep and the initial pressure drop can be between 0.5 and 1.0 in. of water. As such, they are typically not used in residential HVAC systems, where system blowers cannot handle the extra resistance to airflow. Note that there are so-called “bypass HEPA” filter systems on the market that contain a fan and small HEPA filter connected to an HVAC duct so that a portion of the air is drawn through the HEPA filter, with the remainder passing unfiltered down the duct. The overall single-pass efficiency of such a system will necessarily be far less than a HEPA filter. Standards that follow the original HEPA definition of 99.97% efficiency for 0.3 µm diameter particles include

  • United States Military Standard MIL-STD-282

  • United States Department of Energy DOE-STD-3020-2015

  • American Society of Mechanical Engineers ASME AG-1

  • Institute of Environmental Sciences and Technology IEST-RP-CC001

Alternative HEPA definitions include those found in ISO 29463-1 (ISO 35H ≥ 99.95% efficient at MPPS, and ISO 40H ≥ 99.99% efficient at MPPS), and the one from EN-1822-1 (HEPA H13 ≥ 99.75% efficient at MPPS).

Prefiltering. Using less efficient prefilters upstream of extended-surface filters is common and is sometimes justified economically by the potentially longer life of the main filters. Economic considerations include prefilter material cost, changeout labor, and increased fan power. Generally, prefilters should be considered only if they can substantially reduce the part of the dust that may plug the protected filter and extend the final filter’s lifetime. A prefilter usually is at least a MERV 8, with 6 as an occasional lower end. They are commonly rated up to MERV 15. They are usually not more than 3 MERVs lower than the final filter. There can be either a two- or three-stage system set up for a HEPA/ULPA filter. A two-stage would have a prefilter in the MERV 11 to 15 range before the HEPA/ULPA. A three-stage would have a MERV 1 to 10 as an initial, a MERV 8 to 15 as a middle, and a HEPA/ULPA as a final.

A single filter gage may be installed when a panel prefilter is placed adjacent to a final filter. Because the prefilter is frequently changed on a schedule, the final filter pressure drop can be read without the prefilter in place every time the prefilter is changed. For maximum accuracy and economy of prefilter use, two gages can be used. Some air filter housings are available with pressure taps between the pre- and final filter tracks to accommodate this arrangement.

Temporary prefilters protecting higher-efficiency filters are worthwhile during construction to capture heavy loads of coarse dust.

HEPA and ULPA filters should always be protected by prefilters.

Removal efficiencies and typical operating conditions for different types of media filters are listed in Table 2.

Table 2 Typical Properties and Operating Conditions for Media filters

Filter Type

Typical MERV

Typical Operating Conditions

Initial Resistance to Airflow, in. of water

Final Resistance to Airflow, in. of water

Duct Velocity, fpm

Media Velocity, fpm

Panel

1 to 6

0.05 to 0.25

0.50 to 1.0

295 to 500

Same as duct velocity

Low-efficiency renewable/cleanable

4 to 6

0.4 to 0.5

0.4 to 1.0

295 to 500

Same as duct velocity

Extended-surface

7 to 16

0.25 to 1.0

0.5 to 1.5

up to 600

6 to 90 for intermediate efficiency

Electret

5 to 16

0.2 to 1.0

0.5 to 1.5

300 to 500

10 to 200

HEPA/ULPA

More efficient than MERV 16

0.5

2.0

50 to 500

50 to 100


Electronic Air Cleaners. In the past, the term electronic air cleaner (EAC) was somewhat synonymous with the term electrostatic precipitator (ESP). More recently, EAC has been used to describe a wide variety of powered air cleaners, including those that use electrostatic effects to reduce or remove air particulate pollutants and those powered devices aimed at gas-phase pollutants such as ultraviolet photocatalytic oxidation (UVPCO) devices. Electronic air cleaners that use electrostatic effects to remove particles are available in many designs but fall into two major categories: (1) electrostatic, plate-type precipitators and (2) electrically enhanced air filtration. Various types of ionizers also fall into this category.

Corona discharge is used in most electronic air cleaners designed to remove particulates from the air. Corona discharge is a form of electrical discharge in which a small region of plasma is formed at an electrode with a relatively small radius of curvature as compared to the geometry in the rest of the system. A wire and plate are classic examples of such disparate electrodes, although metal points or carbon brushes are also often used as corona electrodes. In such a system, as the electric potential between the electrodes is increased, an electron avalanche will be initiated at or near the sharp electrode, and a small region of plasma (glow corona) will be formed. When properly designed, the voltage is held at that potential and not permitted to increase to the point at which an arc would occur between the electrodes. At the edge of the corona region, ions are formed, which flow along electric field lines to the ground electrode. The space charge created by the ions is typically used to charge particles in electronic air cleaners designed for the removal of particles. A complex series of reactions occurs within the corona plasma and reactive species are formed, most notably ozone. The amount of ozone generated is typically roughly proportional to the amount of current flowing through the discharge electrode, but other factors can influence the amount of ozone produced, including electrode polarity, electrode tip size, and electrode material.

Electrostatic precipitators (ESPs), which require a power source during operation, are electronic air cleaners that create an electric field transverse to the airflow to move charged particles along field lines to grounded plates. Very large single-stage ESPs, in which high-voltage corona wires are suspended between a series of parallel grounded plates, are often used in coal-fired power plants and cement factories. Such ESPs may be 40 ft tall and have plate spacings on the order of 12 in. ESPs designed for HVAC systems, on the other hand, are typically two-stage devices, consisting of a first section containing corona wires and plates, and a second section consisting of alternating high voltage and grounded plates. The second section is more effective at removing smaller particulates due to reduced electrohydrodynamic turbulence in that section.

The first stage of a two-stage ESP is the ionization and particle charging section, in which the small-diameter corona wires, typically at a positive DC voltage between 5 and 25 kV, are suspended equidistant between grounded plates. Ions created by the corona discharge at the wire flow toward the ground plates along electric field lines and charge particles in the airstream. As particles accumulate charge, they are also influenced by the electric field and migrate toward the grounded plates. The largest particles will acquire the most charge and they, along with smaller particles that are already near the plates, will strike the plate and have a high probability of being collected there. The remainder of the charged particles then pass into the second stage, the collection section.

The collection section consists of a series of alternating high voltage and grounded parallel plates. The parallel plates set up a uniform electric field transverse to the air flow and the charged particles migrate towards the grounded plate as they move through the section. Voltage differential can be the same as the differential between the sires and plates in the charging section or could be a smaller potential of the plates are spaced more closely together. Once the particles reach the grounded plate, they are removed from the airstream and collected by the plates. Particle retention is a combination of electrical and intermolecular adhesion forces and may be augmented by special oils or adhesives on the plates. Figure 3 shows a typical electrostatic plate-type precipitator cell.

In lieu of positive direct current, a negative potential also functions on generally the same principle, but typically generates more ozone. With voltages of 5 to 25 kV (dc), safety measures are required. A typical arrangement makes the air cleaner inoperative when the doors are removed for cleaning the cells or servicing the power pack. Electronic air cleaners typically operate from a 120 or 240 V (ac) single-phase electrical service. The high voltage supplied to the air cleaner cells is normally created with solid-state power supplies. The electric power consumption ranges from 20 to 40 W per 1000 cfm of air cleaner capacity.

Cross Section of Plate-Type Precipitator Air Cleaner

Figure 3. Cross Section of Plate-Type Precipitator Air Cleaner


Electrically Enhanced Air Filtration. Electrically enhanced air cleaners use high voltage to enhance the collection capability of fibrous air filters by polarizing and/or charging the filter fibers. They typically fall into two categories: (1) those that use the polarization effect alone, and 2) those that use ionization charging and polarization. In a polarizing system, the fibrous filter is placed in an electric field strong enough to induce dipoles in/on the fibers. The localized region of charge on the fibers serves to attract particles of the opposite charge and neutral particles with induced dipoles. Although filter enhancement due to polarization alone is typically not as significant as that due to particle or fiber charging, it is a measurable effect (Bergman et al, 1983). In an ionizing electrically enhanced filtration system, the fibers and/or particles are charged via a corona electrode system and the fibers are also typically polarized. Advantages to doing so include increased efficiency without an increase in resistance to airflow. Figure 4 shows that the air cleaners consist of an ionizing section and a filtration section. The ionizing section has a prefilter to prevent large debris from entering the air filter and to focus the electrostatic field. The air is charged in a high-voltage ionizing section. In the ionization section, the ionizer is connected to a high-voltage power supply and the particulate is charged. The charged particles are collected in the media filter at earth ground potential.

Optional features are often available for electronic air cleaners. Downstream filters collect particulates that agglomerate and blow off the cell plates. These are used mainly where heavy contaminant loading occurs and extension of the cleaning cycle is desired. Cell collector plates may be coated with special oils, adhesives, or detergents to improve both particle retention and particle removal during cleaning. High-efficiency dry extended-media area filters are also used as downstream filters in special designs. The electronic air cleaner used in such a system improves the service life of the dry filter and collects small particles such as smoke.

Electrically Enhanced Air Cleaner with Prefilter

Figure 4. Electrically Enhanced Air Cleaner with Prefilter


Ionizers employed independently of an ESP or electrically enhanced filtration system use ions produced by high voltages to charge particles to cause agglomeration resulting in better capture by a filter downstream, or to lead particles to plate out on oppositely charged surfaces such as walls, floors, and people.

A negative ionizer uses the principle of particle charging but does not use a collecting section. Particles enter the ionizer of the unit, receive an electrical charge, and then migrate to a grounded surface closest to the travel path.

Space Charge. Particulates that pass through an ionizer and are charged, but not removed, carry the electrical charge into the space. If continued on a large scale, a space charge builds up, which tends to drive these charged particles to walls and interior surfaces. Thus, a low-efficiency electronic air cleaner used in areas of high ambient dirt concentrations (or a malfunctioning unit), can blacken walls faster than if no cleaning device were used (SMACNA, 2010).

Other types of EAC include needlepoint ionization (NPBI), dry hydrogen peroxide (DHP), and photocatalytic oxidation (PCO), which may reduce certain types of particles using chemical reactions with them. Although these EAC lack substantial verification data for efficacy or safety at this point, the COVID-19 crisis has dramatically increased use of EACs. Some EAC technologies with more limited applications before the pandemic have been used in wider applications with exposure to an increased number of occupants. The safety concerns outlined in this chapter apply to both new installations as well as the many devices that were expedited into service for the alleviation of pandemic concerns.

Combining air cleaners involves installing air cleaners in sequence in an HVAC system. For example, as mentioned above, an ESP may be used as a particle coagulator (agglomerator) with a fibrous media filter downstream to catch the agglomerated particles blown off the plates. The benefits of combining different air cleaning processes vary. In addition to combining different particle removal technologies, an air cleaning system may combine particle removal with gas-phase or bioaerosol removal technologies (e.g., a particle filter followed by a carbon bed then a UV lamp system). Care should be taken to be sure that the devices work well together. For example, a filter immediately downstream of an ionizer may lead to better filtration or may limit the ability of the ionizer to charge particles in the rooms.

Combination air cleaners include more than one technology within the unit. These may include, for example, a HEPA and a UV lamp or a MERV 13 filter with a carbon bed. Combination units are most commonly found in IRAC. In some cases, multiple technologies can allow the device to treat more than one type of pollutant, as in the case of a media filter and a carbon bed addressing particles and gases. In others, one or more technologies are used in combination to remove the same pollutant (e.g., filter and ionizer). For combination units, consider the benefits of each technology and the possible interactions between them. The difference between combining air cleaners and combination air cleaners is simply that combination air cleaners are sold as a single unit, whereas the combining ones are sold separately.

7. AIR CLEANER TEST METHODS

The distinguishing operating characteristics of particle removal air cleaners are particle size removal efficiency, resistance to airflow, service life, and life-cycle cost. Quickly stated, efficiency measures the ability of the air cleaner to remove particles from an airstream. Minimum efficiency during the life of the filter is the most meaningful characteristic for most filters and applications. Resistance to airflow (or simply resistance) is the static pressure drop differential across the filter at a given face velocity. The term static pressure differential is interchangeable with pressure drop and resistance. Life-cycle cost is the evaluation of device performance in the application in terms of overall cost, along with filter service life, including element cost, energy consumption, maintenance, disposal, etc. The discussion below introduces relevant test methods from ASHRAE and other organizations. Refer to the actual methods for more details.

Air filter testing is complex, and no individual test adequately describes all filters or air cleaners. Ideally, performance testing of equipment should simulate operation under actual conditions and evaluate the characteristics important to the equipment user. Although the filters are available and tested at higher air velocity, most AHU manufacturers design filter banks to be operated at 500 fpm or below. Wide variations in the amount and type of particles in the air being cleaned make evaluation difficult. Another complication is the difficulty of closely relating measurable performance to the specific requirements of users. Recirculated air tends to have a larger proportion of lint than does outdoor air. However, performance tests should strive to simulate actual use as closely as possible.

Air cleaner test methods have been developed by the heating and air-conditioning industry, the automotive industry, the atomic energy industry, and government and military agencies. In 2005, the ISO reactivated technical committee TC 142, Cleaning Equipment for Air and Other Gases, whose scope includes test methods for particle filters of various types and efficiencies, particle filter media, and room air cleaners. ASHRAE has cooperated closely with TC 142, and several ASHRAE documents have been used in development of TC 142 standards.

 General Ventilation (HVAC) Testing

Several tests have become standard in general ventilation applications in the United States. In 1968, the test techniques developed by the U.S. National Bureau of Standards (now the National Institute of Standards and Technology [NIST]) and the Air Filter Institute (AFI) were unified (with minor changes) into a single test procedure, ASHRAE Standard 52-1968. Siegel (2002) and Whitby et al. (1956) give details of the original codes. ASHRAE Standard 52-1968 was discontinued in 2009 and replaced by ASHRAE Standard 52.2. Other important standards discussed below include ISO 16890, past European standard EN 779, and standards for testing HEPA and ULPA filters.

ASHRAE Standard 52.2. ASHRAE Standard 52.2-2017 contains minimum efficiency reporting values (MERVs) for air cleaner particle size efficiency. In 2008, the standard incorporated arrestance testing from the discontinued ASHRAE Standard 52.1. Table 3 provides an approximate cross-reference for air cleaners tested under discontinued ASHRAE Standards 52.1 and 52.2. Currently, there is no ASHRAE standard for testing electronic air cleaners; the current industry-accepted test method for electronic air cleaners is AHRI Standard 680. This test involves loading the filter with dust that does not contain a conductive component and allows comparison to media filtration.

ASHRAE Particle Size Removal Efficiency (PSE) Test. ASHRAE Standard 52.2 prescribes a way to test air-cleaning devices for removal efficiency by particle size while addressing two air cleaner performance characteristics important to users: the ability of the device to remove particles from the airstream and its resistance to airflow. In this method, air cleaner testing is conducted at a specific airflow based on the upper limit of the air cleaner’s application range. Airflows are based on specific face velocities between 118 and 748 fpm, which yields between 472 and 2990 cfm for a nominal 24 by 24 in. filter. The test aerosol consists of laboratory-generated potassium chloride particles dispersed in the airstream. Optical particle counters size and count the particles in 12 defined, geometric logarithmic-scale, equally distributed particle size ranges both upstream and downstream for efficiency determinations. The test encompasses 0.3 to 10 µm particles. The clean-filter efficiency test is followed by five dust loadings, using ASHRAE dust, to increase the pressure drop across the filter. Efficiency tests are performed after each dust loading.

A set of particle size removal efficiency performance curves is developed from the test. The minimum efficiency value in each size channel is used as a composite curve representing performance in the range of sizes. Efficiencies on the composite curve are averaged for small, medium, and large particles; these averages are used to determine the MERV of the air cleaner. Since 2020, the same values are also used to calculate PM efficiencies (PM52.210, PM52.22.5, and PM52.21) to meet the needs of those working with PM data. A complete test report includes (1) a summary of the test, (2) removal efficiency curves of the clean devices at each of the loading steps, (3) a composite minimum removal efficiency curve, (4) the MERV, (5) the PM efficiencies, and (6) resistance/pressure drop curves.

In 2008, Appendix J on conditioning was added as an optional part of Standard 52.2. If used, this conditioning step replaces the current first (small) dust loading. This step simulates the efficiency drop seen in many charged filters in actual use: the high concentration of 40 to 50 nm aerosol exposes the filter to many particles of a size common in ambient and indoor air. This step does not completely remove the charge on the fibers. When Appendix J is used in a full Standard 52.2 test, the nomenclature used to report results is MERV-A (ASHRAE 2008).

ASHRAE 52.2 only official covers media filters in the standard test, so it does not officially include electronic air cleaners. This is largely due to the carbon content of the loading dust that may short out electronic devices and the lack of a consensus non-pressure drop test dust loading endpoint for devices that do not increase noticeably in pressure drop. Still, the procedures for the clean filter and correlation tests may be used to determine the particle size dependent efficiency for these devices as long as the report is labeled a modified test or otherwise not a formal 52.2 test.

Bioaerosol testing was added to ASHRAE 52.2 as an optional appendix to allow standard testing for non-UV-only devices that are HVAC mounted. ASHRAE 185.1 covers bioaerosol removal/inactivation testing for UV devices. The new option within 52.2 uses the same basic techniques but allows them to be applied to devices, including filters, that are not covered by ASHRAE 185.1.

ASHRAE 52.2 Arrestance Test. ASHRAE Standard 52.2 defines synthetic test dust as a compounded test dust consisting of (by weight) 72% ISO Standard 12 103-A2 fine test dust, 23% powdered carbon, and 5% no. 7 cotton linters. A known amount of the prepared test dust is fed into the test unit at a known and controlled concentration. The amount of dust in the air leaving the test filter is determined by passing the entire airflow through a high-efficiency final filter (≥98%) downstream of the test filter and measuring the gain in filter weight. The synthetic weight arrestance is calculated using the weights of the dust captured on the final high-efficiency filter and the total dust fed.

Atmospheric aerosol particles range from a small fraction of a micrometre to tens of micrometres in diameter. The artificially generated dust cloud used in the ASHRAE arrestance method is considerably coarser than typical atmospheric dust. It tests the ability of a filter to remove the largest atmospheric aerosol particles and gives little indication of filter performance in removing the smallest particles. However, where the mass of dust in the air is the primary concern, this is a valid test because most of the mass is contained in the larger particles. Where extremely small particles (such as respirable sizes) are involved, arrestance rating does not differentiate between filters. Arrestance test results are nly used in MERV determination for MERV 1 to 4; for these filters, the arrestance is the only metric beyond the determination that an E3 based on the clean filter data is less than 20%.

ASHRAE 52.2 Dust-Holding Capacity (DHC) Test. Synthetic test dust (as described in the preceding section) is fed to the filter in accordance with ASHRAE Standard 52.2 procedures. The pressure drop across the filter (its resistance to airflow) rises as dust is fed. The test normally ends when resistance reaches the maximum operating resistance set by the manufacturer. However, not all filters of the same type retain collected dust equally well. The test, therefore, requires that arrestance be measured at least four times during dust loading and that the test be terminated when two consecutive arrestance values of less than 85%, or one value equal to or less than 75% of the maximum arrestance, have been measured. The ASHRAE dust-holding capacity is, then, the integrated amount of dust held by the filter up to the time the dust-loading test is terminated. (See ASHRAE Standard 52.2 for more detail.)

ISO Standard 16890. ISO 16890, Air Filters for General Ventilation, is a set of standards added to the general ventilation test method arsenal in 2016. It has replaced EN 779 wherever it was specified. This standard uses a similar test procedure to ASHRAE 52.2, but uses an isopropyl alcohol vapor discharge method and includes a unique rating system that relates the measured filter performance to typical urban and rural air pollution conditions. The result is a removal efficiency specified in terms of particulate matter (PM) and shown as ePM. As an example, a filter with rated performance of ISO ePM2.5 75% removes 75% of particles that are 2.5 microns in size or less, as measured by the standard.

This international filtration standard is split into four parts:

  • Part 1: Technical specifications, requirements and classification system based upon particulate matter efficiency (ePM)

  • Part 2: Measurement of fractional efficiency and air flow resistance

  • Part 3: Determination of the gravimetric efficiency and the air flow resistance versus the mass of test dust captured

  • Part 4: Conditioning method to determine the minimum fractional test efficiency

EN 779 (Now Replaced by ISO 16890 between 2016 and 2018). CEN developed EN Standard 779, Particulate Air Filters for General Ventilation—Requirements, Testing, Marking, in 1993. Its last revision, Particulate Air Filters for General Ventilation—Determination of the Filtration Performance, was approved and published in 2012. Efficiency is reported as an average efficiency after loading with ASHRAE dust. In this latest revision, minimum efficiency requirements for discharged filters are 35% for F7, 55% for F8, and 70% for F9. This is 0.4 mm efficiency, measured on media samples after discharge in liquid isopropyl alcohol (IPA). The test aerosol as specified in the standard is DEHS.

 HEPA and ULPA Testing

Penetration Tests. For high-efficiency filters of the type used in cleanrooms and nuclear applications (HEPA or ULPA filters), there are several tests that may be specified, depending on end use. These tests rely on the use of oil-based test aerosols or polystyrene latex spheres (PSL) to challenge the filter.

These tests measure penetration of the test aerosol through the filter under test. The aerosol cloud is fed to the filter, which is held in a special test fixture. Any aerosol that penetrates the body of the filter or leaks through gasket cracks passes into the region downstream from the filter, where it is thoroughly mixed. Air leaving the fixture thus contains the average concentration of penetrating smoke. This concentration, as well as the upstream concentration, is measured by a light-scattering photometer.

Filter penetration P (%) is given as

(1)

Penetration, not efficiency, is usually specified in the test procedure because HEPA filters have efficiencies so near 100% (e.g., 99.97% or 99.99% on 0.30 µm particles). Penetration and efficiency E are related by the equation E = 100 – P. For example, a filter penetration of 0.03% can be displayed as having a filter efficiency of 99.97%.

Penetration tests are highly dependent upon three factors:

  • Aerosol Types. DOP (dioctyl phthalate or bis-[2-ethylhexyl] phthalate) was the original test aerosol as specified by U.S. Military Standard MIL-STD-282, but this aerosol has been replaced by DEHS (di-ethyl-hexyl-sebacate) or PAO (polyalphaolefin, PAO Emery 3004) or equivalents. Polystyrene latex spheres (PSL) are solid aerosols that can be made to a specified size.

  • Particle Size. Every filter has a most penetrating particle size (MPPS) that is aerosol and velocity dependent, and dependent upon the filter design and filter media in use. Some tests will specify a certain particle size to test, such as 0.1 or 0.3 μm, or they will use MPPS as the particle size to calculate efficiency.

  • Test Velocity. In general, the lower the velocity that a filter is tested at will improve its filtration efficiency. It is easier for a filter to capture very small particles at slower speeds.

MIL-STD-282. Military Standard MIL-STD-282 (Revision B, December 22, 2015) and U.S. Army document 136-300-175A (1965) (replaced by Carlon and Guelta 1992) was first approved in 1956, specifying the use of DOP (dioctyl phthalate, also known as bis-[2-ethylhexyl] phthalate) as the test aerosol. DOP is an oily liquid with a high boiling point. In this method, a smoke cloud of DOP droplets condenses from DOP vapor.

The count median diameter for DOP aerosols is about 0.18 µm, and the mass median diameter is about 0.27 µm with a cloud concentration of approximately 20 to 80 mg/m3 under properly controlled conditions. The procedure is sensitive to the mass median diameter, and DOP test results are commonly referred to as efficiency at 0.30 µm particle size. This penetration diameter is, of course, velocity dependent.

The DOP smoke cloud is fed to the filter, which is held in a special test fixture. Any smoke that penetrates the body of the filter or leaks through gasket cracks passes into the region downstream from the filter, where it is thoroughly mixed. Air leaving the fixture thus contains the average concentration of penetrating smoke. This concentration, as well as the upstream concentration, is measured by a light-scattering photometer.

IEST Recommended Practices RP-CC 001.6 and RP-CC 007.3. The Institute of Environmental Sciences and Technology has published two recommended practices: IEST RP-CC 001.6, HEPA and ULPA Filters, and IEST RP-CC 007.3, Testing ULPA Filters.

ISO 29463. ISO 29463, parts 2 to 5, have replaced EN 1822, parts 2 to 5, for the method of test for very high efficiency filters. EN-1822 part 1 remains for the classification of filters. This standard uses DEHS, PAO, or PSLs to determine filter efficiency at MPPS.

European Standard EN 1822 (Now Replaced by ISO 29463). Introduced in 1998, the EN 1822 filter standard was the first European standard to translate filtration knowledge into a classification system for HEPA filters. This test used DEHS aerosol to determine filter efficiency at MPPS. This standard has been replaced by ISO 19463.

 Leakage (Scan) Tests

For HEPA filters, leakage tests are sometimes desirable to show that no small “pinhole” leaks exist or to locate any that may exist so they may be patched. Essentially, this is the same technique as used in the oil aerosol (DOP) penetration test, except that the downstream concentration is measured by scanning the face of the filter and its gasketed perimeter with a moving isokinetic sampling probe. The exact point of smoke penetration can then be located and repaired. This same test (described in IEST RP-CC 001.6) can be performed after the filter is installed. Smoke produced by a portable generator is not uniform in size, but its average diameter can be approximated as 0.6 µm. Particle diameter is less critical for leak location than for penetration measurement. The leak scan test is typically done for filters with 99.99% or higher efficiencies, in applications for which locating and repairing a discrete leak are more important.

 In-Situ Testing

ISO 29462. In 2008, ASHRAE published Guideline 26 to provide a test method for evaluating filters in place in building HVAC systems. This guideline was adopted without technical change by the ISO and published as ISO Standard 29462-2013. Subsequently, ASHRAE decided to withdraw Guideline 26.

ISO 29462 presents a method for determining the in-place efficiency of individual particle filters or filter systems installed in building HVAC systems, as long as the filter or system is amenable to testing (e.g., enough space in the HVAC system to install sensors, well-sealed doors, etc.; a checklist is provided). Using a particle counter, particles in several size ranges between 0.3 and 5 μm that are circulating in the HVAC system are measured several times upstream and downstream of the filter to provide statistically robust data. Then, the removal efficiency is calculated by particle size. Pressure drop across the filter, temperature, and relative humidity are recorded. The test method is theoretically applicable to all filters in HVAC systems. However, it is unlikely to yield statistically significant results for filters with efficiencies lower than MERV 11 because of the size distribution of particles typically found in building HVAC systems.

Note that field data generally show larger uncertainties than measurements made in a laboratory. For filter/filter system tests, this is because of the variety of different HVAC environments and particle types likely to be encountered, and the difficulties in controlling environmental variables during the test. ISO 29462 includes a procedure for reducing uncertainty by subjecting a reference filter to measurement both in the field and in a laboratory.

 Respirator Tests

Test standards have been developed in the United States for respirator air filters to receive NIOSH approvals, covered under 42 CFR Part 84. These standards rate respirators as oilproof (P), oil-resistant (R), or not oilproof (N), along with an efficiency rating such as N95.

 Environmental Tests

Air cleaners may be subjected to fire, high humidity, a wide range of temperatures, mechanical shock, vibration, and other environmental stress. Several standardized tests exist for evaluating these environmental effects on air cleaners. U.S. Military Standard MIL-STD-282 includes shock tests (shipment rough handling) and filter media water-resistance tests. Several U.S. Atomic Energy Commission agencies (now part of the U.S. Department of Energy) specify humidity and temperature-resistance tests (DOE 1997, 2003).

UL Standard 900. This destructive test procedure measures the amount of flame, smoke, or both generated by a filter when subjected to a burner in a test duct. Additionally, to pass, a filter must not generate sparks beyond the discharge length of the test duct.

This procedure does not consider filter performance regarding particle collection at any point of its test life, and pertains to a clean filter only. As filters accumulate particles, the burning, smoke, and spark characteristics change based on the contaminant in the media; thus, UL Standard 900 applies only to new filters. Once a filter has been put in service, the classification is no longer valid.

UL Standard 586. This test was specifically designed to evaluate the performance of a HEPA filter in extreme and rigorous conditions. While being particle challenged, the filter is subjected to extreme cold, heat, and humidity. In addition, there are shock tests simulating shipping and handling stresses to evaluate physical durability, and a flame test on the media. The standard also has some specific construction requirements for various portions of each element.

In 1991, UL Standard 586 was required by the Department of Defense for Nuclear material applications. It is an integral part of ASME Standard AG-1, Code on Nuclear Air and Gas Treatment.

The UL tests do not evaluate the effect of collected dust on filter flammability; depending on the dust, this effect may be severe. UL Standard 867 applies to electronic air cleaners. UL 2998 covers ozone emissions from air cleaners. The standard test is done in a chamber, but there is an option for a single-pass test.

 AHRI Standards

The Air-Conditioning, Heating, and Refrigeration Institute published AHRI Standards 680 (residential) and 850 (commercial/industrial) for air filter equipment. Standard 680 applies to both media and electronic air cleaners, and specifies rating conditions for performance, capacity, and restriction. These standards establish (1) definitions and classification; (2) requirements for testing and rating; (3) specification of standard equipment; (4) performance and safety requirements; (5) proper marking; (6) conformance conditions; and (7) literature and advertising requirements. However, certification of air cleaners is not a part of these standards.

 AHAM Standards

Particulate removal air cleaners may also be non-HVAC mounted. In-room air cleaners sometimes include filters that are tested per ASHRAE 52.2 or HEPA standards, but these air cleaners in their entirety are tested per the American Household Appliance Manufactures (AHAM) chamber test. In-room air cleaners and associated standards created by AHAM are discussed in more detail in Chapter 66 in the 2023 ASHRAE Handbook—HVAC Applications.

8. SELECTION AND MAINTENANCE

In addition to criteria affecting the degree of air cleanliness, factors such as cost (initial investment, maintenance, and energy effectiveness), space requirements, and airflow resistance have led to the development of a wide variety of air cleaners. Comparisons of different air cleaners can be made from data obtained by standardized test methods.

To evaluate filters and air cleaners properly for a particular application, consider the following factors:

  • Types of contaminants present indoors and outdoors

  • Sizes and concentrations of contaminants

  • Source type, including whether constant or intermittent

  • Air cleanliness levels required in the space

  • Air filter efficiency needed to achieve cleanliness

  • Space available to install and access equipment

  • Life-cycle costing, including

    • Operating resistance to airflow (static pressure differential) for HVAC; final resistance to airflow as well as clean-device resistance should be compatible with the fans and other resistance in an HVAC system

    • Power consumption for in-room air cleaners

    • Disposal or cleaning requirements of spent filters/parts

    • Initial cost of selected system

    • Cost of replacement filters or cleaning

    • Cost of warehousing filter stock and change-out labor

Savings (from reduced housekeeping expenses, protection of valuable property and equipment, dust-free environments for manufacturing processes, improved working conditions, and even health benefits) should be credited against the cost of installing and operating an adequate system. The capacity and physical size of the required unit may emphasize the need for low maintenance cost. Operating cost, predicted life, and efficiency are as important as initial cost because air cleaning is a continuing process.

Panel filters do not have efficiencies as high as can be expected from extended-surface filters, but their initial cost and upkeep are generally low. Compared to moving-curtain filters, panel filters of comparable efficiencies require more attention to maintain the resistance within reasonable limits. However, single-stage, face- or side-access, low- to medium-efficiency filters of MERV 6 to 10 from a 2 in. pleat to a 12 in. deep cube, bag, or deep pleated cartridge, require less space with lower initial cost, and have better efficiency. The bag and cartridges generally have a similar service life to that of a roll filter.

If efficiency of MERV 11 or higher is required, extended-surface filters or electronic air cleaners should be considered. The use of very fine glass fiber mats or other materials in extended-surface filters has made these available at the highest efficiency.

Typical Filter Locations for HVAC System

Figure 5. Typical Filter Locations for HVAC System


Initial cost of an extended-surface filter is lower than for an electronic unit, but higher than for a panel type. Operating and maintenance costs of some extended-surface filters may be higher than for panel types and electronic air cleaners, but efficiencies are always higher than for panel types; the cost/benefit ratio must be considered. Pressure drop of media-type filters is greater than that of electronic types, and slowly increases during their useful life. Advantages include the fact that no mechanical or electrical services are required. Choice should be based on both initial and operating costs (life-cycle costs), as well as on the degree of cleaning efficiency and maintenance requirements.

Although electronic air cleaners have higher initial and maintenance costs, they have high initial efficiencies in cleaning atmospheric air, largely because of their ability to remove fine particulate contaminants. System resistance remains unchanged as particles are collected, and efficiency is reduced until the resulting residue is removed from the collection plates to prepare the equipment for further duty. The manufacturer must supply information on maintenance or cleaning. Also, note that electronic air cleaners may not collect particles greater than 10 µm in diameter.

Figure 5 shows where filtration can be placed in an HVAC system. Each area indicates the point of potential need for particulate removal.

The typical contaminants listed in Table 3 appear in the general reporting group that removes the smallest known size of that specific contaminant. The order in which they are listed has no significance, and the list is not complete. The typical applications and typical air cleaners listed are intended to show where and what type of air cleaner could be and/or has been traditionally used. Traditional usage may not represent the optimum choice, so using the table as a selection guide is not appropriate when a specific performance requirement is needed. An air cleaner application specialist should then be consulted and manufacturers’ performance curves should be reviewed.

Note that MERV 17 to 20, which were shown in early versions of ASHRAE Standard 52.2 to give readers a feeling for where HEPAs could be considered to fit into the MERV scale, were removed because of the confusion when readers assumed these theoretical MERV values existed and tried to use ASHRAE testing procedures for them. ASHRAE 52.2 does not test to these filter levels. For HEPA filters, refer to the ISO or IEST classification system (IEST 2007, 2009; ISO 2012).

Table 3 Application Guidelines for MERV Filters

Std. 52.2 Minimum Efficiency Reporting Value (MERV)

Typical Controlled Contaminant

Typical Applications and Limitations

Typical Air Filter/Cleaner Type

16

15

14

13

0.30 to 1.0 µm Particle Size

All bacteria

Most tobacco smoke

Droplet nuclei (sneeze)

Cooking oil

Most smoke

Insecticide dust

Copier toner

Most face powder

Most paint pigments

Hospital inpatient care

General surgery

Smoking lounges

Superior commercial buildings

Bag Filters

Nonsupported (flexible) microfine fiberglass or synthetic media. 300 to 900 mm (12 to 36 in.) deep, 6 to 12 pockets.

Box Filters

Rigid style cartridge filters 150 to 300 mm (6 to 12 in.) deep may use lofted (air laid) or paper (wet laid) media.

12

11

10

9

1.0 to 3.0 µm Particle Size

Legionella

Humidifier dust

Lead dust

Milled flour

Coal dust

Auto emissions

Nebulizer drops

Welding fumes

Superior residential

Better commercial buildings

Hospital laboratories

Bag Filters

Nonsupported (flexible) microfine fiberglass or synthetic media. 300 to 900 mm (12 to 36 in.) deep, 6 to 12 pockets.

Box Filters

Rigid style cartridge filters 150 to 300 mm (6 to 12 in.) deep may use lofted (air laid) or paper (wet laid) media.

8

7

6

5

3.0 to 10.0 µm Particle Size

Mold

Spores

Hair spray

Fabric protector

Dusting aids

Cement dust

Pudding mix

Snuff

Powdered milk

Commercial buildings

Better residential

Industrial workplaces

Paint booth inlet air

Pleated Filters

Disposable, extended surface, 25 to 125 mm (1 to 5 in.) thick with cotton-polyester blend media, cardboard frame.

Cartridge Filters

Graded density viscous coated cube or pocket filters, synthetic media.

Throwaway

Disposable synthetic media panel filters.

4

3

2

1

>10.0 µm Particle Size

Pollen

Spanish moss

Dust mites

Sanding dust

Spray paint dust

Textile fibers

Carpet fibers

Minimum filtration

Residential

Window air conditioners

Throwaway

Disposable fiberglass or synthetic panel filters

Washable

Aluminum mesh, latex coated animal hair, or foam rubber panel filters

Electrostatic

Self charging (passive) woven polycarbonate panel filter

Note: A MERV for other than HEPA/ULPA filters also includes a test airflow rate, but it is not shown here because it has no significance for the purposes of this table.


Common sense and some knowledge of how air cleaners work help the user achieve satisfactory results. Air cleaner performance varies from the time it is first installed until the end of its service life. Generally, the longer a media-type filter is in service, the higher the efficiency. The accumulation of contaminants begins to close the porous openings, and, therefore, the filter is able to intercept smaller particles. However, there are exceptions that vary with different styles of media-type filters. Electronic air cleaners and charged-fiber media filters start at high efficiency when new (or after proper service, in the case of electronic air cleaners), but their efficiency decreases as contaminants accumulate. Charged media filters may drop as much as 50% of the initial efficiency, especially at lower particle sizes, unless the drop-off effect is countered by significant collection of larger particles and buildup of filter cake to add in collection. Some air cleaners, particularly low-efficiency devices, may begin to shed some collected contaminants after being in service. Testing with standardized synthetic loading dust attempts to predict this, but such testing rarely, if ever, duplicates the air cleaner’s performance on atmospheric dust.

The loading rate of all filters depends on the type and concentration of particles in the air being handled and the operating cycle of the system. Media filters may be monitored for resistance to airflow and changed when a predetermined level is reached to minimize filter costs, or they may be changed on a time-based schedule for ease of scheduling. Life-cycle cost (LCC), including energy necessary to overcome the filter resistance (which will vary by fan and other resistance in the HVAC system), should be calculated to evaluate the overall cost of the filtering system.

 Residential Air Cleaners

Panel air filters with a MERV 7 or lower, traditionally used for residential applications, may be of spun glass and only filter out the largest of particles. These filters may prevent damage to downstream equipment, but they do little to improve air quality in the residence. MERV 8 or better filters are now recommended. To use higher-MERV filters in residential applications, it is important to be sure the system can handle the pressure drop. If space exists, deeper filters may help reduce pressure drop while increasing the efficiency (and MERV) of filters. Residential architects and contractors should consider providing deeper filter banks (2 to 6 in. during new construction and renovations to allow homeowners greater flexibility in choosing higher-MERV filtration.

In addition to particle removal efficiency, system runtime has a large impact on the effectiveness of air cleaners used in central residential forced-air heating and cooling systems. These systems typically operate only in response to demands for heating or cooling. ASHRAE RP-1691 used building energy modeling combined with an indoor air mass balance model to predict the impacts of various MERV filters on reducing indoor concentrations of PM2.5 and UFPs of outdoor origin. Azimi et al. (2016) estimated that low system runtimes mean that even the highest levels of filtration efficiency cannot achieve more than ~50% particle removal in the space, and that effectiveness depends strongly on home vintage, climate zone, and ventilation strategy. Touchie and Siegel (2018) analyzed central residential system runtime data from over 7000 homes in North America and found that the median system runtime was only 18%, with considerable variation between homes. Moreover, at low to average runtimes, it was noted that effectiveness of the filter matters much less because the system does not run enough for a sufficient air volume to pass through the filter and have a substantial impact on particle concentrations. Increasing runtimes (e.g., by operating systems in fan-only mode continuously or for great cycle lengths) can improve filtration effectiveness but will come with an additional energy cost.

 VAV Systems

ASHRAE tests on numerous different media-type air cleaners under both constant and variable airflow showed no significant performance differences under different flow conditions, and the air cleaners were not damaged by VAV flow. Low-efficiency air cleaners did show substantial reentrainment for both constant and VAV flow (Rivers and Murphy 2000).

 Antimicrobial Treatment of Filter Media

Several varieties and all efficiencies of filters have been treated with antimicrobial additives. The key performance goal is to reduce the growth of microbial organisms in filter components (e.g., the media itself, separators in high-efficiency minipleats, framing components). The intent is not to make the air clean and free of viable microbes, but rather to prevent filter components from becoming the microbial reservoir.

An ASHRAE-funded research project tested low-efficiency filters for microbial reduction for both initial and loaded conditions (Foarde et al. 2000). Under normal use, fibrous air cleaners were found to be unlikely to become a source of microbial contamination to the space, and antimicrobial treatment usually did not increase the filtration efficiency for bioaerosols. The dust cake was found to mask the antimicrobial eliminating contact with the bioaerosols. In the United States, EPA guidelines must be met for the antimicrobial product to be used in air filters.

 Maintenance

Various cleaning methods have been recommended for permanent media filters; the most widely used involves washing the filter with steam or water (frequently with detergent).

If maintained properly by regular cleaning, including wiping the wires, ESPs have relatively constant pressure drop and efficiency. If they are not cleaned regularly, dendritic buildup on the wires can reduce the efficiency or the unit and may lead to sparking. Accumulated dust can build up to the point that arcing may occur in the collection section of the air cleaner. This may reduce the collection efficiency, as well as produce unwanted extraneous noise. Dust buildup in the ionizer section can also reduce efficiency.

Plate-type air cleaner cells must be cleaned periodically with detergent and hot water. Some designs incorporate automatic wash systems that clean the cells in place; in others, the cells are re-moved for cleaning. The frequency of cleaning (washing) the cell depends on the contaminant and the concentration. Industrial applications may require cleaning every 8 h, but a residential unit may only require cleaning every one to three months. The timing of the cleaning schedule is important to keep the unit performing at peak efficiency. For some contaminants, special attention must be given to cleaning the ionizing wires. The air cleaner must be maintained based on the recommendations of the manufacturer.

Electrically enhanced air cleaners have a longer service life between maintenance than plate-type precipitators. Maintenance consists of replacing the filter and cleaning the ionizing section and prefilter.

9. AIR CLEANER INSTALLATION

An air filter must fit into the duct or frame it is installed into, and it must be sealed in to achieve the expected performance. Thus, the size of the filter and method of installation are both critical for particle removal to be achieved. Many air cleaners are available in units of convenient size for manual installation, cleaning, and replacement. A typical unit filter may be a 16 to 25 in. square or rectangle, from 1 to 16 in. in depth, and of either the dry or viscous impingement type. In large systems, the frames in which these units are installed are bolted or riveted together to form a filter bank. Automatic filters are constructed in sections offering several choices of width up to 70 ft and generally range in height from 40 to 200 in., in 4 to 6 in. increments. Several sections may be bolted together to form a filter bank.

Several manufacturers provide side-loading access filter sections for various types of filters. Filters are changed from outside the duct, making service areas in the duct unnecessary, thus saving cost and space.

Of course, in-service efficiency of an air filter is sharply reduced if air leaks through the bypass dampers or poorly designed filter-holding frames. Filters must be sealed in so that all the air goes through the filter; bypass will result in lower removal efficiency due to the untreated air. The higher the filter efficiency, the more careful attention must be paid to the rigidity and sealing effectiveness of the frame. For example, a 10% bypass for a 40% efficient filter only results in a 4% loss in removal, whereas an 80% efficiency filter with the same 10% bypass results in 20% less removal. Sealing may be achieved by a simple clamp, pressing into a gasket, a tight fit in a holder, or use of a sealant. In addition, high-efficiency filters must be handled and installed with care. The National Air Filtration Association (NAFA 2006) suggests some precautions needed for HEPA filters.

Air cleaners may be installed in the outdoor-air intake ducts of buildings and residences and in the recirculation and bypass air ducts; however, the prefilters (in a two- or three-stage system) should be placed upstream of heating or cooling coils and other air-conditioning equipment in the system to protect that equipment from dust. Dust in commercial buildings where outdoor air is brought in is likely to be predominantly alumniosilicates, whereas dander is likely to predominate in solely recirculated air such as in residences (Owen et al. 2014). Where high-efficiency filters protect critical areas such as cleanrooms, it is important that filters be installed as close to the room as possible to prevent pickup of particles between the filters and the outlet. The ultimate installation is the unidirectional flow room, in which the entire ceiling or one entire wall becomes the final filter bank.

Although published performance data for all air filters are based on straight-through unrestricted airflow perpendicular to the frame, V-bank designs with 30 to 60° angles are common in commercial applications. Cooling coils are often designed with face velocities not to exceed 500 fpm, and filter banks are often specified at lower face velocities such as 350 fpm. The use of V-banks allows AHU manufacturers to accommodate such designs while maintaining consistent height and width of adjacent AHU sections. Care should be taken to ensure filters receive even air distribution. Uneven air distribution leads to uneven loading of filters. When filters become unevenly loaded, more air flows through the cleaner areas of the filter, and the higher velocities through the clean areas decrease filter performance.

Failure of air filter installations to give satisfactory results can, in most cases, be traced to faulty installation, improper maintenance, or both. The most important requirements of a satisfactory and efficiently operating air filter installation are as follows:

  • The filter must be of ample capacity for the amount of air and dust load it is expected to handle. An overload of 10 to 15% is regarded as the maximum allowable. When air volume is subject to future increase, a larger filter bank should be installed initially.

  • The filter must be suited to the operating conditions, such as degree of air cleanliness required, amount of dust in the entering air, type of duty, allowable pressure drop, operating temperature, and maintenance facilities. Where UV lamps are also used, filters of some materials should not be directly irradiated because it may degrade the filter; check with the filter and UV company to determine compatibility.

The following recommendations apply to filters installed with central fan systems:

  • Duct connections to and from the filter should change size or shape gradually to ensure even air distribution over the entire filter area. SMACNA standards should be followed for all elbows, junctions, and transitions upstream of the filter bank.

  • When installing electrostatic precipitators, duct approaches to and from the air cleaner housing should be arranged so that airflow is distributed uniformly over the face area. Panel prefilters should also be used to help distribute airflow and to trap large particles that might short out or cause excessive arcing in the high-voltage section of the air cleaner cell. Design parameters of air velocity, ionizer field strength, cell plate spacing, depth, and plate voltage must match the application requirements (e.g., contaminant type, particle size, volume of air, required efficiency). Many units are designed for installation into central heating and cooling systems for total air filtration. Other self-contained units are furnished complete with air movers for source control of contaminants in specific applications that need an independent air cleaner.

  • Locate the filter far enough from the fan to prevent or reduce reentrainment of particles, especially during start/stop cycles.

  • Provide sufficient space in front of (upstream) or behind (downstream of) the filter, or both, depending on its type, to make it accessible for inspection and service. A distance of 20 to 40 in. is required, depending on the filter chosen.

  • Provide conveniently sized access doors to the filter service areas.

  • All doors on the clean-air side should be gasketed to prevent infiltration of unclean air. All connections and seams of the sheet-metal ducts on the clean-air side should be airtight. The filter bank must be caulked to prevent bypass of unfiltered air, especially when high-efficiency filters are used.

  • Lights should be permanently installed in access sections where personnel are required to enter the AHU for filter replacements and inspections.

  • Filters installed close to an outdoor air inlet should be protected from the weather by suitable louvers or an inlet hood.

  • In areas with extreme rainfall or where water can drip over or bounce (travel) up in front of the inlet, use drainable track moisture separator sections upstream of the first filter bank. Place a large-mesh wire bird screen in front of the louvers or in the hood. In areas with snowfall potential, care should be taken to ensure that the maximum snow drift accumulation against the exterior wall does not exceed the height of the outdoor air inlet, because snow may melt and damage filter.

  • Filters, other than electronic air cleaners, should consider having permanent indicators (airflow resistance gage) to give notice when the filter reaches its final pressure drop or is exhausted, as with automatic roll media filters. Where pressure drop indicators are not feasible to determine replacement times for filters, a filter replacement schedule shall be established to ensure that filters do not remain in service beyond their loading capabilities.

  • Electronic air cleaners should have an indicator or alarm to indicate when high voltage is off or shorted out.

When filters are exposed to UV lighting, filtration media and housing shall be fabricated with UV resistant materials.

 Filter Sealing And Installation Techniques

Gasket Seal. The gasket is applied to either the upstream or downstream flange. The gasket is compressed between an opposing mating surface of housing or filter fixing grid.

Gel Seal. The filter frame is provided with an integral gel channel that is filled with a low-outgassing polyurethane-based gel (ISPE 2019). The gel interfaces with an opposing knife edge integral to the housing or filter fixing grid. The gel penetrating knife edge creates a positive seal between the housing and the filters. This technique is most often used in bottom-loading or room side replaceable applications.

Knife Edge Seal. In this case, the filter frame is produced with integral knife edge. The knife edge interfaces with a gel channel that is integral to the housing or filter fixing grid. This technique is preferred in common plenum applications where the weight of the filter and pressure from airflow create a positive seal. No mounting hardware should be required.

10. SAFETY CONSIDERATIONS

Safety ordinances should be investigated when the installation of an air cleaner is contemplated (UL, AFI, NIST). Combustible filtering media may not be allowed by some local regulations. Combustion of dust and lint on filtering media is possible, although the media itself may not burn. This may cause a substantial increase in filter combustibility. Smoke detectors and fire sprinkler systems should be considered for filter bank locations. In some cases, depending on the contaminant, hazardous material procedures must be followed during removal and disposal of the used filter. Bag-in/bag-out (BI/BO) filter housings should be seriously considered in those cases.

Many air filters are efficient collectors of bioaerosols. When provided with moisture and nutrients, the microorganisms can multiply and may become a health hazard for maintenance personnel and building occupants. Moisture in filters can be minimized by preventing (1) entrance of rain, snow, and fog; (2) carryover of water droplets from coils, drain pans, and humidifiers; and (3) prolonged exposure to elevated humidity. Changing or cleaning filters regularly is important for controlling microbial growth.

Good health-safety practices for personnel handling dirty filters include wearing personal protective equipment (PPE), which includes a face mask, nitrile gloves, shoe covers, and safety glasses; and thorough washing upon completion. Old filters should be placed in plastic bags or other containers for safe disposal. Be careful not to shake or drop it, as particles can be released into the air by any sudden movements. Tie and tape the bag shut.

All high-voltage devices (such as electrostatic precipitators) can produce ozone, which is toxic and damaging not only to human lungs, but to paper, rubber, and other materials. When properly designed and maintained, an electronic air cleaner produces an ozone concentration that only reaches a fraction of the limit acceptable for continuous human exposure and is less than that prevalent in many American cities (EPA 1996). Continuous arcing and brush discharge in an electrostatic precipitator may yield an ozone level that is annoying or mildly toxic; this is indicated by a strong ozone odor. Although the nose is sensitive to ozone, only actual measurement of the concentration can determine whether a hazardous condition exists.

It is recommended to use ozone-producing devices that have a certification such as UL 867 or UL 2998 to avoid developing concentrations in excess of the NIOSH Regular Exposure Limit of 100 ppb (or lower if required by a local authority having jurisdiction or other site specific requirements). Real-time ozone monitoring should be used for all equipment not meeting the requirements of UL 2998.

REFERENCES

ASHRAE members can access ASHRAE Journal articles and ASHRAE research project final reports at technologyportal.ashrae.org. Articles and reports are also available for purchase by nonmembers in the online ASHRAE Bookstore at www.ashrae.org/bookstore.

AHRI. 2009. Performance rating residential air filter equipment. Standard 680-2009. Air-Conditioning and Refrigeration Institute, Arlington, VA.

AHRI. 2004. Performance rating of commercial and industrial air filter equipment. Standard 850-2004. Air-Conditioning and Refrigeration Institute, Arlington, VA.

ASHRAE. 2008. Guideline for field testing of general ventilation devices and systems for removal efficiency in-situ by particle size and resistance to flow. Guideline 26-2008.

ASHRAE. 1992. Gravimetric and dust-spot procedures for testing air-cleaning devices used in general ventilation for removing particulate matter. ANSI/ASHRAE Standard 52.1-1992.

ASHRAE. 2017. Method of testing general ventilation air-cleaning devices for removal efficiency by particle size. ANSI/ASHRAE Standard 52.2-2017.

ASHRAE. 2015. Method of testing UV-C lights for use in air-handling units or air ducts to inactivate airborne microorganisms. ANSI/ASHRAE Standard 185.1-2015.

ASME. 2017. Code on nuclear air and gas treatment. Standard AG-1. American Society of Mechanical Engineers, New York.

Azimi, P.,D. Zhao, and B. Stephens. 2016. Modeling the impact of residential HVAC filtration on indoor particles of outdoor origin (RP-1691). Science and Technology for the Built Environment 22(4):431-462. dx.doi.org/10.1080/23744731.2016.1163239.

Bergman, W., A. Biermann, and W. Kuhl. 1983. Electric air filtration: Theory, laboratory studies, hardware development, and field evaluations (UCID--19952). Lawrence Livermore Laboratory. www.osti.gov/servlets/purl/5412011.

Block, M. and V. Bokalders. 2010. The whole building handbook: How to design healthy, efficient and sustainable buildings. Routledge, London.

Carlon, H., and M. Guelta. 1992. Implementation of DOP replacement with selected materials in mask and filter testing penetrometer machines. Report ADA254560. Chemical Research Development and Engineering Center, Aberdeen Proving Ground, MD.

CEN. 2012. Particulate air filters for general ventilation—Determination of the filtration performance. Standard EN 779. Comité Européen de Normalisation, Brussels.

CEN. 2009. High efficiency air filters (EPA, HEPA and ULPA)—Part 1: Classification, performance testing, marking; Part 2: Aerosol production, measuring equipment, particle counting statistics; Part 3: Testing flat sheet filter media; Part 4: Determining leakage of filter elements (Scan method); Part 5: Determining the efficiency of filter elements. Standard EN 1822. Comité Européen de Normalisation, Brussels.

Després, V.R., J.A. Huffman, S.M. Burrows, C. Hoose, A.S. Safatov, G. Buryak, J. Fröhlich-Nowoisky, W. Elbert, M.O. Andreae, U. Pöschl, and R. Jaenicke. 2012. Primary biological aerosol particles in the atmosphere: A review. Tellus B: Chemical and Physical Meteorology 64(1).

DOE. 1997. Specification for HEPA filters used by DOE contractors. DOE-STD-3020-97 (archived).

DOE. 2003. Nuclear air cleaning handbook. DOE-HDBK-1169-2003.

EPA. 1996. National air quality and emissions trends reports. EPA 454/R-96-005. U.S. Environmental Protection Agency, Office of Air Quality Planning and Standards, Research Triangle Park, NC.

EPA. 2015. National ambient air quality standards (NAAQS). Environmental Protection Agency, Washington, D.C. www.epa.gov/criteria-air-pollutants/naaqs-table.

Eurovent. 1996. Method of testing air filters used in general ventilation for determination of fractional efficiency. Document 4/9. Eurovent, Brussels.

Eurovent. 2005. In sit determination of fractional efficiency of general ventilation filters. Document 4/10. Eurovent, Brussels.

Federal Register. 2013. National Ambient Air Quality Standards for Particulate Matter; Final Rule. 40 CFR Parts 50, 51, 52, 53, and 58. Federal Register 78: 3086-3287.

Foarde, K.K., J.T. Hanley, and A.C. Veeck. 2000. Efficacy of antimicrobial filter treatments. ASHRAE Journal 42(12):52.

Fröhlich-Nowoisky, J., C.J. Kampf, B. Weber, J.A. Huffman, C. Pöhlker, M.O. Andreae, N. Lang-Yona, S.M. Burrows,S.S. Gunthe, W. Elbert, H. Su, P. Hoor, E. Thines, T. Hoffmann, V.R. Després, and U. Pöschl. 2016. Bioaerosols in the Earth system: Climate, health, and ecosystem interactions. Atmospheric Research 182:346-376.

IEST. 2007. Testing ULPA filters. IES RP-CC 007.2. Institute of Environmental Sciences and Technology, Mount Prospect, IL.

IEST. 2009. HEPA and ULPA filters. IES RP-CC 001.6. Institute of Environmental Sciences and Technology, Mount Prospect, IL.

ISPE. 2019. Good practice guide: HVAC & process equipment air filters. International Society for Pharmaceutical Engineering, North Bethesda, MD.

James, A.C., W. Stahlhofen, G. Rudolf, M.J. Egan, W. Nixon, P. Gehr, and J.K. Briant. 1991. The respirator tract deposition model proposed by the ICRP task group. Radiation Protection Dosimetry 38:159-165.

ISO. 1997. Road vehicles—Test dust for filter evaluation. Standard 12103: 1997. International Organization for Standardization, Geneva.

ISO. 2012. Field testing of general ventilation filtration devices and systems for in situ removal efficiency by particle size and resistance to airflow. Standard 29462. International Organization for Standardization, Geneva.

ISO. (In development.) Air filters for general ventilation. ISO/DIN Standard 16890. International Organization for Standardization, Geneva, and German Institute for Standardization, Berlin.

Mensah-Attipoe, J., S. Saari, A,-M. Veijalainen, P. Pasanen, J. Keskinen, J.T.T. Leskinen, and T. Reponen. 2016. Release and characteristics of fungal fragments in various conditions. Science of the Total Environment 547:234-243.

NAFA. 2006. Installation, operation and maintenance of air filtration systems, 2nd ed. National Air Filtration Association, Washington, D.C.

NIOSH. 1995. Federal regulation for certifying air-purifying particulate respirators. Code of Federal Regulations 42 CFR 84. National Institute for Occupational Safety and Health, Washington, D.C. www.ecfr.gov.

Nutting, A., and R.F. Logsdon. 1953. New air filter code. Heating, Piping and Air Conditioning (June):77.

Offermann, F.J., S.A. Loiselle, and R.G. Sextro. 1992. Performance of air cleaners in a residential forced air system. ASHRAE Journal 34(7):51-57.

O’Meara, T., and E. Tovey. 2000. Monitoring personal allergen exposure. Clinical Reviews in Allergy and Immunology 18:341-395.

Owen, K., R. Pope, and J. Hanley. 2014. How do pressure drop, efficiency, weight gain, and loaded dust composition change throughout filter lifetime? ASHRAE Transactions 120(1):366-381. Paper NY-14-032.

Phalen, R.F., R.G. Cuddihy, G.I. Fisher, O.R. Moss, R.B. Schlesinger, D.L. Swift, and H.-C. Yeh. 1991. Main features of the proposed NCRP respiratory tract model. Radiation Protection Dosimetry 38:179-184.

Qian, J., D.Hospodsky, N. Yamamoto, W.W. Nazaroff, and J. Peccia. 2012. Size-resolved emission rates of airborne bacteria and fungi in an occupied classroom. Indoor Air 22(4):339-351.

Rivers, R.D., and D.J. Murphy. 2000. Air filter performance under variable air volume conditions. ASHRAE Transactions 106(2).

Siegel, J. 2002. Standard 52: Filtering through the facts. ACHR News (December). www.achrnews.com/articles/89177-standard-52-filtering-through-the-facts.

SMACNA. 2010. HVAC systems applications, 2nd edition. Sheet Metal and Air Conditioning Contractors’ National Association, Inc. Chantilly, VA.

Taylor, P.E., R.C. Flagan, A.G. Miguel, R. Valenta, and M.M. Glovsky. 2004. Birch pollen rupture and the release of aerosols of respirable allergens. Clinical & Experimental Allergy 34:1591-1596.

Touchie, M.F., and J.A. Siegel. 2018. Residential HVAC runtime from smart thermostats: Characterization, comparison, and impacts. Indoor Air.

UL. 2009. High efficiency, particulate, air filter units. ANSI/UL Standard 586-2009. Underwriters Laboratories, Inc., Northbrook, IL.

UL. 2000. Electrostatic air cleaners. ANSI/UL Standard 867-2000. Underwriters Laboratories, Inc., Northbrook, IL.

UL. 2004. Air filter units. ANSI/UL Standard 900-2004. Underwriters Laboratories, Inc., Northbrook, IL.

U.S. Army. 1965. Instruction manual for the installation, operation, and maintenance of penetrometer, filter testing, DOP, Q107. Document 136-300-175A. Edgewood Arsenal, MD.

Verreault, D., S. Moineau, and C. Duchaine. 2008. Methods for sampling of airborne viruses. Microbiology and Molecular Biology Reviews 72(3):413-444.

Whitby, K.T., A.B. Algren, and R.C. Jordan. 1956. The dust spot method of evaluating air cleaners. Heating, Piping and Air Conditioning (December):151.

Willeke, K., and P.A. Baron, eds. 1993. Aerosol measurement: Principles, techniques and applications. Van Nostrand Reinhold, New York.

Wu, T. and B.E. Boor. Urban aerosol size distributions: a global perspective, Atmos. Chem. Phys. 21(11):8883-8914.

BIBLIOGRAPHY

AHAM. 2009. Method for measuring the performance of portable household electric room air cleaners following accelerated particulate loading. Standard AC-3-2009. Association of Home Appliance Manufacturers, Chicago, IL.

ASHRAE. 2010. Ventilation for acceptable indoor air quality. ANSI/ASHRAE Standard 62.1-2010.

ASHRAE. 2010. Ventilation and acceptable indoor air quality in low-rise residential buildings. ANSI/ASHRAE Standard 62.2-2010.

Brown, R.C. 1993. Air filtration. Pergamon Press, New York.

Dickenson, T.C. 1997. Filters and filtration handbook. Elsevier Science, New York.

Dill, R.S. 1938. A test method for air filters. ASHRAE Transactions 44:379..

DiNardi, S.R., ed. 2003. The occupational control environment: Its evaluation, control and management, 2nd ed. AIHA Press, Fairfax, VA.

Dorman, R.G. 1974. Dust control and air cleaning. Pergamon, New York.

EPA. 1997. An office building occupants’ guide to indoor air quality. U.S. Environmental Protection Agency, Indoor Environments Division, Washington, D.C.

EPA. 2006. Air quality criteria for ozone and related photochemical oxidants. EPA/600/R-05/004aF-cF. U.S. Environmental Protection Agency, Washington, D.C.

Foarde, K.K., and D.W. VanOsdell. 1994. Investigate and identify indoor allergens and toxins that can be removed by filtration. ASHRAE Research Project RP-760, Final Report.

Hamblin, C., P.J. Goodchild, and A. Hollinrake. 1994. The development of a HEPA filter with improved dust holding characteristics. United Kingdom Atomic Energy Authority, Separation Technology Department.

Hinds, W.C. 1999. Aerosol technology: Properties, behavior, and measurement of airborne particles, 2nd ed. John Wiley & Sons, New York.

Howden Buffalo. 1999. Fan engineering handbook, 9th ed. Howden Buffalo Company, Buffalo, NY.

Hutton, I.M. 2007. Handbook of nonwoven filter media. Elsevier, Oxford, UK.

ISO. 2013. Field testing of general ventilation filtration devices and systems for in situ removal efficiency by particle size and resistance to airflow. International Organization for Standardization, Geneva, Switzerland.

Kemp, S.J., T.H. Kuehn, D.Y.H. Pui, D. Vesley, and A.J. Streifel. 1995. Filter collection efficiency and growth of the microorganisms on filters loaded with outdoor air. ASHRAE Transactions 101(1):228-238.

Kemp, S.J., T.H. Kuehn, D.Y.H. Pui, D. Vesley, and A.J. Streifel. 1995. Growth of microorganisms on HVAC filters under controlled temperature and humidity conditions. ASHRAE Transactions 101(1):305-316.

Kerr, G., and L.C. Nguyen Thi. 2001. Identification of contaminants, exposure effects and control options for construction/renovation activities. Final Report, ASHRAE Research Project RP-961.

Kuehn, T.H., B. Gacek, C-H. Yang, D.T. Grimsrud, K.A. Janni, A.J. Streifel, and M. Pearce. 1996. Identification of contaminants, exposure effects and control options for construction/renovation activities. ASHRAE Transactions 102(2):89-101.

Kulkarni, P., P.A. Baron, and K. Willeke, eds. 2011. Aerosol measurement, principles, techniques and applications, 3rd ed. John Wiley & Sons, NY.

Landsberger, S., and M. Creatchman, eds. 1999. Elemental analysis of airborne particles. Gordon & Breach Science Publishers, Malaysia.

Lev, S., L.S. Ruzer, and N.H. Harley, eds. 2012. Handbook on aerosols: Measurement, dosimetry and health effects, 2nd ed. CRC Press, Boca Raton, FL.

Licht, W. 1980. Air pollution control engineering: Basic calculations for particulate collection. Marcel Dekker, New York.

Liu, B.Y., and K.L. Rubow. 1986. Air filtration by fibrous filter media. In Fluid-filtration: Gas. ASTM STF973. American Society for Testing and Materials, Philadelphia, PA.

Liu, B.Y.H. 1976. Fine particles. Academic Press, New York.

Maroni, M., B. Siefert, and T. Lindvall, eds. 1995. Indoor air quality: A comprehensive reference book. Elsevier, Oxford, UK.

Marshal, I.A. 1998. Aerosol particle size analysis. Royal Society of Chemistry, London.

McDonald, B. 2011. PM based air filter efficiency and rating. Proceedings of Annual Conference of American Filtration and Separations Society.

Morey, P.R. 1994. Suggested guidance on prevention of microbial contamination for the next revision of ASHRAE Standard 62. Indoor Air Quality’94. ASHRAE.

NAFA. 2007. NAFA guide to air filtration, 4th ed. National Air Filtration Association, Washington, D.C.

NRC. 1981. Indoor pollutants. National Research Council, National Academy Press, Washington, D.C.

Ogawa, A. 1984. Separation of particles from air and gases, vols. I and II. CRC Press, Boca Raton, FL.

Parker, K.R., ed. 1997. Applied electrostatic precipitation. Chapman & Hall, New York.

Rivers, R.D. 1988. Interpretation and use of air filter particle-size-efficiency data for general-ventilation applications. ASHRAE Transactions 88(1).

U.S. Government. 1988. Cleanroom and work station requirements, controlled environments. Federal Standard 209D, amended 1991. Available from GSA, Washington, D.C.

Walsh, P.J., C.S. Dudney, and E.D. Copenhaver, eds. 1984. Indoor air quality. CRC Press, Boca Raton, FL.



The preparation of this chapter is assigned to TC 2.4, Particulate Air Contaminants and Particulate Contaminant Removal Equipment.