Common air cleaners for particulate removal are broadly grouped as described below. These types of
air cleaner exist in both HVAC and in-room styles. Most of the discussion below is aimed at
HVAC-type devices, but the technology details are applicable to both. Users of in-room air cleaners
(IRAC) should refer to Chapter 66 in the 2023
ASHRAE Handbook—HVAC
Applications for more details specific to in-room applications.
Media filters are typically made from filter media in the form of paper or batting consisting of
fibers in various types, sizes, and configurations. The units collect dust directly in and on
the fibers at various efficiencies and with varying dust-holding capabilities. They can be
static or renewable media devices and do not need separate power sources other than that needed
for the HVAC or IRAC fan. The filters are discussed in more detail below, in approximate order
of increasing particle removal efficiency.
Panel Filters. Also known as impingement filters, these are flat pads. Thus, the
media velocity is always equal to the duct velocity. These filters can be constructed from a
variety of media, including spun glass, synthetic fibers such as polyester, polyurethane foam,
natural fibers, dry plastics, and various metals that may be fibrous or expanded sheets. Using
these coarse fiber media, these filters are typically characterized by a low initial pressure
drop and efficiencies not above MERV 6.
As filter efficiency increases, resistance to airflow often increases for the same airflow rate.
Therefore, to achieve greater filtration efficiencies while maintaining a pressure drop within
the design limits of HVAC systems, the media area exposed to the airstream may be increased.
These extended-surface filters include pleated
panels, mini-pleats, bag (or pocket) filters, and compact filters. The products most commonly
use nonwoven fiber mats or blankets of varying thicknesses, fiber sizes, and densities.
The most commonly used media for the construction of pleated
panels include carded and spunbond synthetics such as polyester and
polypropylene as well as natural fibers such as cotton. Pleat separation may be maintained
through the use of a variety of tech-niques, including the pleating of an expanded metal mesh
layer along with the media, the use of paperboard or polymer combs, hot-melt glue strips,
adhesive-coated string, or corrugated metal. New technologies that are becoming more popular
include materials such as cellulose and polylactic acid (PLA) fibers, which can be used to meet
certified biobased requirements. These filters typically fall into the MERV 7 to MERV 13
efficiency range.
Before 2000, bag or pocket
filters used air-laid micro-fiberglass almost exclusively; however,
since then a number of nonwoven synthetic media have been developed that use materials such as
polypropylene and polyester. The media are most often constructed of meltblown and spunbond
combinations and are almost always charged to achieve a given efficiency at a lower resistance
to airflow than uncharged types. The use of nanofibers has recently seen more widespread use for
enhancing the efficiency of these products.
The individual pockets may be stitched or heat-sealed around the perimeter. The desired spacing
between the media layers forming the pocket is controlled either by a span stitch or media web.
This prevents the pocket from “ballooning” and restricting the airflow. The
completed pockets are then assembled into a frame parallel to each other in the direction of the
airflow. These products are normally offered in the MERV 10 to MERV 16 range.
Compact filters include both box filters and mini-pleat products. The products cover the same
efficiency range as pocket filters; however, as the name implies, they can be used in
installations where there is insufficient depth to accommodate a bag filter. Box filters, also
referred to as rigid boxes or cells, use the same media as bag filters.
Because of the tight spacing requirements between pleats, special media were developed for
mini-pleat products. These include both wet-laid nonwovens as well as synthetics. Spacing
between the pleats is physically maintained by use of corrugated aluminum, hot-melt beads, or
string spacers. Some hybrid versions use a media that can be embossed for maintaining spacing.
These media may be supported by wire mesh or may be laminated to a stiffer nonwoven material
(e.g., a spunbond material) to achieve the rigidity requirements and to protect the more fragile
efficiency layer from abrasion. In still other designs, the media may be self supporting or, in
the case of bag filters, the design uses the airstream to inflate the pockets and maintain
spacing.
Extended-surface filters may also be constructed using
expanded polytetrafluoroethylene (ePTFE) membranes. These products typically fall into HEPA
classifications but can also be found at the very high end of the MERV range. Applications may
include semiconductor, microelectronics, pharmaceutical, and gas turbine inlet filtration.
Efficiencies for extended-surface filters are usually higher than those for panel filters. The
dust-holding capacities are also generally higher than for impingement filters simply due to the
increased media area. As an example, a 24 × 24 × 12 in. deep V-cell
product may use up to 200 ft2 of media area and have a typical media
velocity of 10 fpm at 2000 cfm system flow. A flat panel filter in the
same installation would have a media velocity of 500 fpm. Hence a higher efficiency
media may exhibit more resistance to airflow, but with significantly more media area the media
velocity may be lowered.
Initial resistance on an extended-surface filter varies with the choice of media and filter
geometry. Depth in direction of airflow varies from ~1 to 36 in.
Electret filters require no power in HVAC
installations and are composed of electrostatically charged media fibers. Various manufacturing
processes are used, many of them producing mats that contain both positively and negatively
charged fibers. Charged-fiber filter efficiency is determined by both the normal collection
mechanisms of a media filter and the strong local electrostatic effects (related to the amount
of electrostatic charge). The effects improve clean filter efficiency over similar uncharged
media without increasing resistance to airflow. However, ultrafine-particle dust collected on
the fibers usually reduces the efficiency as electrets age. Electret filters are also discussed
in ASHRAE Standard 52.2, Appendix J.
HEPA (high-efficiency particulate air) and ULPA (ultra-low-penetration air) are filters designed
to target the MPPS for a given flow rate. The original U.S. MIL standard for efficiency of a
HEPA filter specified that it must be a minimum of 99.97% efficient for 0.3 μm particles.
There are now a number of differing HEPA filter standards on the market that are described in
more detail in section 8 of this chapter. HEPA and ULPA filters are made in extended-surface
configurations of deep folds or a mini-pleat style of sub-micrometer glass fiber paper.
Synthetic materials, such as ePTFE and nanofibers, are also common materials for HEPA/ULPA.
These are usually combined with a spunbond scrim layer to protect the membrane.
These filters are the standard for cleanroom, nuclear, and toxic particulate applications and are
increasingly used in medical and pharmaceutical applications. Traditional HEPA filters for HVAC
use are often 12 in. deep and the initial pressure drop can be between 0.5
and 1.0 in. of water. As such, they are typically not used in residential HVAC
systems, where system blowers cannot handle the extra resistance to airflow. Note that there are
so-called “bypass HEPA” filter systems on the market that contain a fan and small
HEPA filter connected to an HVAC duct so that a portion of the air is drawn through the HEPA
filter, with the remainder passing unfiltered down the duct. The overall single-pass efficiency
of such a system will necessarily be far less than a HEPA filter. Standards that follow the
original HEPA definition of 99.97% efficiency for 0.3 µm diameter particles include
-
United States Military Standard MIL-STD-282
-
United States Department of Energy DOE-STD-3020-2015
-
American Society of Mechanical Engineers ASME AG-1
-
Institute of Environmental Sciences and Technology IEST-RP-CC001
Alternative HEPA definitions include those found in ISO
29463-1 (ISO 35H ≥ 99.95% efficient at MPPS, and ISO 40H ≥ 99.99%
efficient at MPPS), and the one from EN-1822-1 (HEPA
H13 ≥ 99.75% efficient at MPPS).
Prefiltering. Using less efficient prefilters upstream
of extended-surface filters is common and is sometimes justified economically by the potentially
longer life of the main filters. Economic considerations include prefilter material cost,
changeout labor, and increased fan power. Generally, prefilters should be considered only if
they can substantially reduce the part of the dust that may plug the protected filter and extend
the final filter’s lifetime. A prefilter usually is at least a MERV 8, with 6 as an
occasional lower end. They are commonly rated up to MERV 15. They are usually not more than 3
MERVs lower than the final filter. There can be either a two- or three-stage system set up for a
HEPA/ULPA filter. A two-stage would have a prefilter in the MERV 11 to 15 range before the
HEPA/ULPA. A three-stage would have a MERV 1 to 10 as an initial, a MERV 8 to 15 as a middle,
and a HEPA/ULPA as a final.
A single filter gage may be installed when a panel prefilter is placed adjacent to a final
filter. Because the prefilter is frequently changed on a schedule, the final filter pressure
drop can be read without the prefilter in place every time the prefilter is changed. For maximum
accuracy and economy of prefilter use, two gages can be used. Some air filter housings are
available with pressure taps between the pre- and final filter tracks to accommodate this
arrangement.
Temporary prefilters protecting higher-efficiency filters are worthwhile during construction to
capture heavy loads of coarse dust.
HEPA and ULPA filters should always be protected by prefilters.
Removal efficiencies and typical operating conditions for different types of media filters are
listed in Table
2.
Electronic Air Cleaners. In the past, the term electronic air cleaner (EAC) was somewhat synonymous with the term
electrostatic precipitator (ESP). More recently, EAC has been used to describe a wide variety of
powered air cleaners, including those that use electrostatic effects to reduce or remove air
particulate pollutants and those powered devices aimed at gas-phase pollutants such as
ultraviolet photocatalytic oxidation (UVPCO) devices. Electronic air cleaners that use
electrostatic effects to remove particles are available in many designs but fall into two major
categories: (1) electrostatic, plate-type precipitators and (2) electrically enhanced air
filtration. Various types of ionizers also fall into this category.
Corona discharge is used in most electronic air
cleaners designed to remove particulates from the air. Corona discharge is a form of electrical
discharge in which a small region of plasma is formed at an electrode with a relatively small
radius of curvature as compared to the geometry in the rest of the system. A wire and plate are
classic examples of such disparate electrodes, although metal points or carbon brushes are also
often used as corona electrodes. In such a system, as the electric potential between the
electrodes is increased, an electron avalanche will be initiated at or near the sharp electrode,
and a small region of plasma (glow corona) will be formed. When properly designed, the voltage
is held at that potential and not permitted to increase to the point at which an arc would occur
between the electrodes. At the edge of the corona region, ions are formed, which flow along
electric field lines to the ground electrode. The space charge created by the ions is typically
used to charge particles in electronic air cleaners designed for the removal of particles. A
complex series of reactions occurs within the corona plasma and reactive species are formed,
most notably ozone. The amount of ozone generated is typically roughly proportional to the
amount of current flowing through the discharge electrode, but other factors can influence the
amount of ozone produced, including electrode polarity, electrode tip size, and electrode
material.
Electrostatic precipitators (ESPs), which require a
power source during operation, are electronic air cleaners that create an electric field
transverse to the airflow to move charged particles along field lines to grounded plates. Very
large single-stage ESPs, in which high-voltage corona wires are suspended between a series of
parallel grounded plates, are often used in coal-fired power plants and cement factories. Such
ESPs may be 40 ft tall and have plate spacings on the order of 12 in.
ESPs designed for HVAC systems, on the other hand, are typically two-stage devices, consisting
of a first section containing corona wires and plates, and a second section consisting of
alternating high voltage and grounded plates. The second section is more effective at removing
smaller particulates due to reduced electrohydrodynamic turbulence in that section.
The first stage of a two-stage ESP is the ionization and particle charging section, in which the
small-diameter corona wires, typically at a positive DC voltage between 5 and 25 kV, are
suspended equidistant between grounded plates. Ions created by the corona discharge at the wire
flow toward the ground plates along electric field lines and charge particles in the airstream.
As particles accumulate charge, they are also influenced by the electric field and migrate
toward the grounded plates. The largest particles will acquire the most charge and they, along
with smaller particles that are already near the plates, will strike the plate and have a high
probability of being collected there. The remainder of the charged particles then pass into the
second stage, the collection section.
The collection section consists of a series of alternating high voltage and grounded parallel
plates. The parallel plates set up a uniform electric field transverse to the air flow and the
charged particles migrate towards the grounded plate as they move through the section. Voltage
differential can be the same as the differential between the sires and plates in the charging
section or could be a smaller potential of the plates are spaced more closely together. Once the
particles reach the grounded plate, they are removed from the airstream and collected by the
plates. Particle retention is a combination of electrical and intermolecular adhesion forces and
may be augmented by special oils or adhesives on the plates. Figure
3 shows a typical electrostatic plate-type precipitator cell.
In lieu of positive direct current, a negative potential also functions on generally the same
principle, but typically generates more ozone. With voltages of 5 to 25 kV (dc), safety measures
are required. A typical arrangement makes the air cleaner inoperative when the doors are removed
for cleaning the cells or servicing the power pack. Electronic air cleaners typically operate
from a 120 or 240 V (ac) single-phase electrical service. The high voltage supplied to the air
cleaner cells is normally created with solid-state power supplies. The electric power
consumption ranges from 20 to 40 W per 1000 cfm of air cleaner capacity.
Electrically Enhanced Air Filtration. Electrically
enhanced air cleaners use high voltage to enhance the collection capability of fibrous air
filters by polarizing and/or charging the filter fibers. They typically fall into two
categories: (1) those that use the polarization effect alone, and 2) those that use ionization
charging and polarization. In a polarizing system, the fibrous filter is placed in an electric
field strong enough to induce dipoles in/on the fibers. The localized region of charge on the
fibers serves to attract particles of the opposite charge and neutral particles with induced
dipoles. Although filter enhancement due to polarization alone is typically not as significant
as that due to particle or fiber charging, it is a measurable effect (Bergman et al, 1983). In
an ionizing electrically enhanced filtration system, the fibers and/or particles are charged via
a corona electrode system and the fibers are also typically polarized. Advantages to doing so
include increased efficiency without an increase in resistance to airflow. Figure 4
shows that the air cleaners consist of an ionizing section and a filtration section. The
ionizing section has a prefilter to prevent large debris from entering the air filter and to
focus the electrostatic field. The air is charged in a high-voltage ionizing section. In the
ionization section, the ionizer is connected to a high-voltage power supply and the particulate
is charged. The charged particles are collected in the media filter at earth ground potential.
Optional features are often available for electronic air cleaners. Downstream filters collect
particulates that agglomerate and blow off the cell plates. These are used mainly where heavy
contaminant loading occurs and extension of the cleaning cycle is desired. Cell collector plates
may be coated with special oils, adhesives, or detergents to improve both particle retention and
particle removal during cleaning. High-efficiency dry extended-media area filters are also used
as downstream filters in special designs. The electronic air cleaner used in such a system
improves the service life of the dry filter and collects small particles such as smoke.
Ionizers employed independently of an ESP or
electrically enhanced filtration system use ions produced by high voltages to charge particles
to cause agglomeration resulting in better capture by a filter downstream, or to lead particles
to plate out on oppositely charged surfaces such as walls, floors, and people.
A negative ionizer uses the principle of particle
charging but does not use a collecting section. Particles enter the ionizer of the unit, receive
an electrical charge, and then migrate to a grounded surface closest to the travel path.
Space Charge. Particulates that pass through an
ionizer and are charged, but not removed, carry the electrical charge into the space. If
continued on a large scale, a space charge builds up, which tends to drive these charged
particles to walls and interior surfaces. Thus, a low-efficiency electronic air cleaner used in
areas of high ambient dirt concentrations (or a malfunctioning unit), can blacken walls faster
than if no cleaning device were used (SMACNA, 2010).
Other types of EAC include needlepoint ionization (NPBI), dry hydrogen peroxide (DHP), and
photocatalytic oxidation (PCO), which may reduce certain types of particles using chemical
reactions with them. Although these EAC lack substantial verification data for efficacy or
safety at this point, the COVID-19 crisis has dramatically increased use of EACs. Some EAC
technologies with more limited applications before the pandemic have been used in wider
applications with exposure to an increased number of occupants. The safety concerns outlined in
this chapter apply to both new installations as well as the many devices that were expedited
into service for the alleviation of pandemic concerns.
Combining air cleaners involves installing air
cleaners in sequence in an HVAC system. For example, as mentioned above, an ESP may be used as a
particle coagulator (agglomerator) with a fibrous media filter downstream to catch the
agglomerated particles blown off the plates. The benefits of combining different air cleaning
processes vary. In addition to combining different particle removal technologies, an air
cleaning system may combine particle removal with gas-phase or bioaerosol removal technologies
(e.g., a particle filter followed by a carbon bed then a UV lamp system). Care should be taken
to be sure that the devices work well together. For example, a filter immediately downstream of
an ionizer may lead to better filtration or may limit the ability of the ionizer to charge
particles in the rooms.
Combination air cleaners include more than one
technology within the unit. These may include, for example, a HEPA and a UV lamp or a MERV 13
filter with a carbon bed. Combination units are most commonly found in IRAC. In some cases,
multiple technologies can allow the device to treat more than one type of pollutant, as in the
case of a media filter and a carbon bed addressing particles and gases. In others, one or more
technologies are used in combination to remove the same pollutant (e.g., filter and ionizer).
For combination units, consider the benefits of each technology and the possible interactions
between them. The difference between combining air cleaners and combination air cleaners is
simply that combination air cleaners are sold as a single unit,
whereas the combining ones are sold separately.