CHAPTER 28 UNIT VENTILATORS, UNIT HEATERS, AND MAKEUP AIR UNITS VENTILATORS

 

A heating unit ventilator is an assembly whose principal functions are to heat, ventilate, and cool a space by introducing outdoor air in quantities up to 100% of its rated capacity. The heating medium may be steam, hot water, gas, or electricity. The essential components of a heating unit ventilator are the fan, motor, heating element, damper, filter, automatic controls, and outlet grille, all of which are encased in a housing.

An air-conditioning unit ventilator is similar to a heating unit ventilator; however, in addition to the normal winter function of heating, ventilating, and cooling with outdoor air, it is also equipped to cool and dehumidify during the summer. It is usually arranged and controlled to introduce a fixed quantity of outdoor air for ventilation during cooling in mild weather. The air-conditioning unit ventilator may be provided with a various of combinations of heating and air-conditioning elements. Some of the more common arrangements include

  • Combination hot- and chilled-water coil (two-pipe)

  • Separate hot- and chilled-water coils (four-pipe)

  • Hot-water or steam coil and direct-expansion coil

  • Electric heating coil and chilled-water or direct-expansion coil

  • Gas-fired furnace with direct-expansion coil

The typical unit ventilator has controls that allow heating, ventilating, and cooling to be varied while the fans operate continuously. In normal operation, the discharge air temperature from a unit is varied in accordance with the room requirements. The heating unit ventilator can provide ventilation cooling by bringing in outdoor air whenever the room temperature is above the room set point. Air-conditioning unit ventilators can provide refrigerated cooling when the outdoor air temperature is too high to be used effectively for ventilation cooling.

Unit ventilators are available for floor mounting, ceiling mounting, and recessed applications. They are available with various airflow and capacity ratings, and the fan can be arranged so that air is either blown through or drawn through the unit. With direct-expansion refrigerant cooling, the condensing unit can either be furnished as an integral part of the unit ventilator assembly or be remotely located.

Figure 1A shows a typical heating unit ventilator. The heating coil can be hot water, steam, or electric. Hot-water coils can be provided with face-and-bypass dampers for capacity control, if desired. Valve control of capacity is also available.

Figure 1B shows a typical air-conditioning unit ventilator with a combination hot- and chilled-water coil for use in a two-pipe system. This type of unit is usually provided with face-and-bypass dampers for capacity control.

Figure 1C illustrates a typical air-conditioning unit ventilator with two separate coils, one for heating and the other for cooling with a four-pipe system. The heating coil may be hot water, steam, or electric. The cooling coil can be either a chilled-water coil or a direct-expansion refrigerant coil. Heating and cooling coils are sometimes combined in a single coil by providing separate tube circuits for each function. In such cases, the effect is the same as having two separate coils.

Figure 1D illustrates a typical air-conditioning unit ventilator with a fan section, a gas-fired heating furnace section, and a direct- expansion refrigerant coil section.

 Application

Unit ventilators are used primarily in schools, meeting rooms, offices, and other areas where the density of occupancy requires controlled ventilation to meet local codes.

Typical Unit Ventilators

Figure 1. Typical Unit Ventilators


Floor-model unit ventilators are normally installed on an outer wall near the centerline of the room. Ceiling models are mounted against either the outer wall or one of the inside walls. Ceiling models discharge air horizontally. Best results are obtained if the unit can be placed so that the airflow is not interrupted by ceiling beams or surface-mounted lighting fixtures.

Downdraft can be a problem in classrooms with large window areas in cold climates. Air in contact with the cold glass is cooled and flows down into the occupied space. Floor-standing units often include one of the following provisions to prevent downdraft along the windows (Figure 2):

Methods of Preventing Downdraft along Windows

Figure 2. Methods of Preventing Downdraft along Windows


  • Window sill heating uses finned radiators of moderate capacity installed along the wall under the window area. Heated air rises upward by convection and counteracts the downdraft by tempering it and diverting it upward.

  • Window sill recirculation is achieved by installing the return air intake along the window sill. Room or return air to the unit includes the window’s cold downdrafts, thereby removing them from the occupied area.

  • Window sill discharge directs a portion of the unit ventilator discharge air into a delivery duct along the sill of the window. The discharge air, delivered vertically at the window sill, is distributed throughout the room, and the upwardly directed air combats downdraft.

 Selection

Items to be considered in the application of unit ventilators are

  • Unit air capacity

  • Percent minimum outdoor air

  • Heating and cooling capacity

  • Cycle of control

  • Location of unit

Mild-weather cooling capacity and number of occupants in the space are the primary considerations in selecting the unit’s air capacity. Other factors include state and local requirements, volume of the room, density of occupancy, and use of the room. The number of air changes required for a specific application also depends on window area, orientation, and maximum outdoor temperature at which the unit is expected to prevent overheating.

Rooms oriented to the north (in the northern hemisphere) with small window areas require about 6 air changes per hour (ach). About 9 ach are required in rooms oriented to the south that have large window areas. As many as 12 ach may be required for very large window areas and southern exposures. These airflows are based on preventing overheating at outdoor temperatures up to about 55°F. For satisfactory cooling at outdoor air temperatures up to 60°F, airflow should be increased accordingly.

These airflows apply principally to classrooms. Factories and kitchens may require 30 to 60 ach (or more). Office areas may need 10 to 15 ach.

The minimum amount of outdoor air for ventilation is determined after the total air capacity has been established. It may be governed by local building codes, or it may be calculated to meet the ventilating needs of the particular application. For example, ASHRAE Standard 62.1 requires 7.5 to 10 cfm of outdoor air per occupant (0.06 to 0.18 cfm/ft2) in lecture halls or classrooms, laboratories, and cafeterias, and 5 cfm per occupant in conference rooms.

The heating and cooling capacity of a unit to meet the heating requirement can be determined from the manufacturer’s data. Heating capacity should always be determined after selecting the unit air capacity for mild-weather cooling.

Capacity. Manufacturers publish the heating and cooling capacities of unit ventilators. Table 1 lists typical nominal capacities.

Table 1 Typical Unit Ventilator Capacities

Airflow, cfm

Heating Unit Ventilator Total Heating Capacity, Btu/h

A/C Unit Ventilator Total Cooling Capacity, Btu/h

500

38,000

19,000

750

50,000

28,000

1000

72,000

38,000

1250

85,000

47,000

1500

100,000

56,000


Heating Capacity Requirements. Because a unit ventilator has a dual function of introducing outdoor air for ventilation and maintaining a specified room condition, the required heating capacity is the sum of the heat required to bring outdoor ventilation air to room temperature and the heat required to offset room losses. The ventilation cooling capacity of a unit ventilator is determined by the air volume delivered by the unit and the temperature difference between the unit discharge and the room temperature.

Example.

A room has a heat loss of 24,000 Btu/h at a winter outdoor design condition of 0°F and an indoor design of 70°F, with 20% outdoor air. Minimum air discharge temperature from the unit is 60°F. To obtain the specified number of air changes, a 1250 cfm unit ventilator is required. Determine the ventilation heat requirement, the total heating requirement, and the ventilation cooling capacity of this unit with outdoor air temperature below 60°F.

Solution:

Ventilation heat requirement:

where


qv = heat required to heat ventilating air, Btu/h
ρ =density of air at standard conditions = 0.075 lb/ft3
cp = air specific heat = 0.24 Btu/lb·°F
Q = ventilating airflow, cfm
ti = required room air temperature, °F
to = outdoor air temperature, °F

Total heating requirement:

where

qt = total heat requirement, Btu/h
qs = heat required to make up heat losses, Btu/h

Ventilation cooling capacity:

where

qc = ventilation cooling capacity of unit, Btu/h
tf = unit discharge air temperature, °F

 Control

Many cycles of control are available. The main difference in the various cycles is the amount of outdoor air delivered to the room. Usually, a room thermostat simultaneously controls both a valve and either damper or step controller, to regulate the heat supply, and an outdoor and return air damper. A thermostat in the airstream prevents discharge of air below the desired minimum temperature. Unit ventilator controls provide the proper sequence for the following stages:

  • Warm-up. All control cycles allow rapid warm-up by having the units generate full heat with the outdoor damper closed. Thus 100% of the room air is recirculated and heated until the room temperature approaches the desired level.

  • Heating and ventilating. As the room temperature rises into the thermostat’s operating range, the outdoor air damper partially or completely opens to provide ventilation, depending on the cycle used. Auxiliary heating equipment is shut off. As the room temperature continues to rise, the unit ventilator heat supply is throttled.

  • Cooling and ventilating. When the room temperature rises above the desired level, the room thermostat throttles the heat supply so that cool air flows into the room. The thermostat gradually shuts off the heat and then opens the outdoor air damper. The airstream thermostat frequently takes control during this stage to keep the discharge temperature from falling below a set level.

There are three cycles of control commonly used for unit ventilators:

  • Cycle I. 100% outdoor air is admitted at all times, except during warm-up.

  • Cycle II. A minimum amount of outdoor air (normally 20 to 50%) is admitted during the heating and ventilating stage. This percentage is gradually increased to 100%, if needed, during the ventilation cooling stage.

  • Cycle III. Except during warm-up, a variable amount of outdoor air is admitted, as needed, to maintain a fixed temperature of air entering the heating element. The amount of air admitted is controlled by the airstream thermostat set low enough (often at 55°F) to provide cooling when needed.

Air-conditioning unit ventilators can include any of the three cycles in addition to the mechanical cooling stage, where a fixed amount of outdoor air is introduced. The cooling capacity is controlled by the room thermostat.

For maximum heating economy, the building temperature is reduced at night and during weekends and vacations. Several arrangements are used to accomplish this. One arrangement takes advantage of the natural convective capacity of the unit when the fans are off. This capacity is supplemented by cycling the fan with the outdoor damper closed as required to maintain the desired room temperature.

2. UNIT HEATERS

A unit heater is an assembly of elements with the main function of heating a space. The essential elements are a fan and motor, a heating element, and an enclosure. Filters, dampers, directional outlets, duct collars, combustion chambers, and flues may also be included. Some types of unit heaters are shown in Figure 3.

Typical Unit Heaters

Figure 3. Typical Unit Heaters


Unit heaters can usually be classified in one or more of the following categories:

  • Heating medium. Media include (1) steam, (2) hot water, (3) gas indirect-fired, (4) oil indirect-fired, and (5) electric heating.

  • Type of fan. Three types of fans can be considered: (1) propeller, (2) centrifugal, and (3) remote air mover. Propeller fan units may be arranged to blow air horizontally (horizontal blow) or vertically (downblow). Units with centrifugal fans may be small cabinet units or large industrial units. Units with remote air movers are known as duct unit heaters.

  • Arrangement of elements. Two types of units can be considered: (1) draw-through, in which the fan draws air through the unit; and (2) blow-through, in which the fan blows air through the heating element. Indirect-fired unit heaters are always blow-through units.

 Application

Unit heaters have the following principal characteristics:

  • Relatively large heating capacities in compact casings

  • Ability to project heated air in a controlled manner over a considerable distance

  • Relatively low installed cost per unit of heat output

  • Application where an elevated sound level is permissible

They are, therefore, usually placed in applications where the heating capacity requirements, physical volume of the heated space, or both, are too large to be handled adequately or economically by other means. By eliminating extensive duct installations, the space is freed for other use.

Unit heaters are mostly used for heating commercial and industrial structures such as garages, factories, warehouses, showrooms, stores, and laboratories, as well as corridors, lobbies, vestibules, and similar auxiliary spaces in all types of buildings. Unit heaters may often be used to advantage in specialized applications requiring spot or intermittent heating, such as at outer doors in industrial plants or in corridors and vestibules. Cabinet unit heaters may be used where heated air must be filtered.

Unit heaters may be applied to a number of industrial processes (e.g., drying and curing) that use heated air in rapid circulation with uniform distribution. They may be used for moisture absorption applications, such as removing fog in dye houses, or to prevent condensation on ceilings or other cold surfaces of buildings where process moisture is released. When such conditions are severe, unit ventilators or makeup air units may be required.

 Selection

The following factors should be considered when selecting a unit heater:

  • Heating medium to be used

  • Type of unit

  • Location of unit for proper heat distribution

  • Permissible sound level

  • Rating of the unit

  • Need for filtration

Heating Medium. The proper heating medium is usually determined by economics and requires examining initial cost, operating cost, and conditions of use.

Steam or hot-water unit heaters are relatively inexpensive but require a boiler and piping system. The unit cost of such a system generally decreases as the number of units increases. Therefore, steam or hot-water heating is most frequently used (1) in new installations involving a relatively large number of units, and (2) in existing systems that have sufficient capacity to handle the additional load. High-pressure steam or high-temperature hot-water units are normally used only in very large installations or when a high-temperature medium is required for process work. Low-pressure steam and conventional hot-water units are usually selected for smaller installations and for those concerned primarily with comfort heating.

Gas and oil indirect-fired unit heaters are frequently preferred in small installations where the number of units does not justify the expense and space requirements of a new boiler system or where individual metering of the fuel supply is required, as in a shopping center. Gas indirect-fired units usually have either horizontal propeller fans or industrial centrifugal fans. Oil indirect-fired units largely have industrial centrifugal fans. Some codes limit the use of indirect-fired unit heaters in some applications. Indirect-fired oil and gas units are of blow-through design to mitigate the possibility of combustion products entering the occupied space.

Electric unit heaters are used when the cost of available electric power is lower than that of alternative fuel sources and for isolated locations, intermittent use, supplementary heating, or temporary service. Typical applications are ticket booths, security offices, factory offices, locker rooms, and other isolated rooms scattered over large areas. Electric units are particularly useful in isolated and untended pumping stations or pits, where they may be thermostatically controlled to prevent freezing.

Type of Unit. Propeller fan units are generally used in non-ducted applications where the heating capacity and distribution requirements can best be met by units of moderate output and where heated air does not need to be filtered. Horizontal-blow units are usually installed in buildings with low to moderate ceiling heights. Downblow units are used in spaces with high ceilings and where floor and wall space limitations dictate that heating equipment be kept out of the way. Downblow units may have an adjustable diffuser to vary the discharge pattern from a high-velocity vertical jet (to achieve the maximum distance of downward throw) to a horizontal discharge of lower velocity (to prevent excessive air motion in the zone of occupancy). Revolving diffusers are also available.

Cabinet unit heaters are used when a more attractive appearance is desired. They are suitable for free-air delivery or low static pressure duct applications. They may be equipped with filters, and they can be arranged to discharge either horizontally or vertically up or down.

Industrial centrifugal fan units are applied where heating capacities and space volumes are large or where filtration of the heated air or operation against static resistance is required. Downblow or horizontal-blow units may be used, depending on the requirements.

Duct unit heaters are used where the air handler is remote from the heater. These heaters sometimes provide an economical means of adding heating to existing cooling or ventilating systems with ductwork. They require flow and temperature limit controls.

Location for Proper Heat Distribution. Units must be selected, located, and arranged to provide complete heat coverage while maintaining acceptable air motion and temperature at an acceptable sound level in the working or occupied zone. Proper application depends on size, number, and type of units; direction of airflow and type of directional outlet used; mounting height; outlet velocity and temperature; and air volumetric flow. Many of these factors are interrelated.

The mounting height may be governed by space limitations or by the presence of equipment such as display cases or machinery. The higher a downblow heater is mounted, the lower the temperature of air leaving the heater must be to force the heated air into the occupied zone. Also, the distance that air leaving the heater travels depends largely on the air temperature and initial velocity. A high discharge temperature reduces the area of effective heat coverage because of its buoyancy. High-temperature air is less dense than the cooler air of the space being heated.

Unit heaters for high-pressure steam or high-temperature hot water should be designed to produce approximately the same leaving air temperature as would be obtained from a lower temperature heating medium.

To obtain the desired air distribution and heat diffusion, unit heaters are commonly equipped with directional outlets, adjustable louvers, or fixed or revolving diffusers. For a given unit with a given discharge temperature and outlet velocity, the mounting height and heat coverage can vary widely with the type of directional outlet, adjustable louver, or diffuser. High-volume, low-speed fans in high-ceilinged areas are often used to augment air distribution and reduce temperature stratification.

Other factors that may substantially reduce heat coverage include obstructions (such as columns, beams, or partitions) or machinery in either the discharge airstream or approach area to the unit. Strong drafts or other air currents also reduce coverage. Exposures such as large glass areas or outer doors, especially on the windward side of the building, require special attention; arrange units so that they blanket the exposures with a curtain of heated air and intercept the cold drafts.

For area heating, place horizontal-blow unit heaters in exterior zones such that they blow either along the exposure or toward it at a slight angle. When possible, arrange multiple units so that the discharge airstreams support each other and create a general circulatory motion in the space. Interior zones under exposed roofs or skylights should be completely blanketed. Arrange downblow units so that the heated areas from adjacent units overlap slightly to provide complete coverage.

For spot heating of individual spaces in larger unheated areas, single unit heaters may be used, but allowance must be made for the inflow of unheated air from adjacent spaces and the consequent reduction in heat coverage. Such spaces should be isolated by partitions or enclosures, if possible.

Horizontal unit heaters should have discharge outlets located well above head level. Both horizontal and vertical units should be placed so that the heated airstream is delivered to the occupied zone at acceptable temperature and velocity. Outlet air temperature of free-air delivery unit heaters used for comfort heating should be 50 to 60°F higher than the design room temperature. When possible, locate units so that they discharge into open spaces, such as aisles, and not directly on the occupants. For further information on air distribution, see Chapter 20 of the 2017 ASHRAE Handbook—Fundamentals.

Manufacturers’ catalogs usually include suggestions for the best arrangements of various unit heaters, recommended mounting heights, heat coverage for various outlet velocities, final temperatures, directional outlets, and sound level ratings.

Sound Level in Occupied Spaces. Sound pressure levels in workplaces should be limited to values listed in Table 1 in Chapter 49 of the 2019 ASHRAE Handbook—HVAC Applications. Although the noise level is generated by all equipment within hearing distance, unit heaters may contribute a significant portion of noise level. Both noise and air velocity in the occupied zone generally increase with increased outlet velocities. An analysis of both the diverse sound sources and the locations of personnel stations establishes the limit to which the unit heaters must be held.

 Ratings of Unit Heaters.

Steam or Hot Water. Heating capacity must be determined at a standard condition. Variations in entering steam or water temperature, entering air temperature, and steam or water flow affect capacity. Typical standard conditions for rating steam unit heaters are dry saturated steam at 2 psig pressure at the heater coil, air at 60°F (29.92 in. Hg barometric pressure) entering the heater, and the heater operating free of external resistance to airflow. Standard conditions for rating hot-water unit heaters are entering water at 200°F, water temperature drop of 20°F, entering air at 60°F and 29.92 in. Hg barometric pressure, and the heater operating free of external resistance to airflow.

Gas-Fired. Gas-fired unit heaters are rated in terms of both input and output, in accordance with the approval requirements of the American Gas Association.

Oil-Fired. Ratings of oil-fired unit heaters are based on heat delivered at the heater outlet.

Electric. Electric unit heaters are rated based on the energy input to the heating element.

Effect of Airflow Resistance on Capacity. Unit heaters are customarily rated at free-air delivery. Airflow and heating capacity decrease if outdoor air intakes, air filters, or ducts on the inlet or discharge are used. The capacity reduction caused by this added resistance depends on the characteristics of the heater and on the type, design, and speed of the fans. As a result, no specific capacity reduction can be assigned for all heaters at a given added resistance. The manufacturer should have information on the heat output to be expected at other than free-air delivery.

Effect of Inlet Temperature. Changes in entering air temperature influence the total heating capacity in most unit heaters and the final temperature in all units. Because many unit heaters are located some distance from the occupied zone, possible differences between the temperature of the air actually entering the unit and that of air being maintained in the heated area should be considered, particularly with downblow unit heaters.

Higher-velocity units and units with lower vertical discharge air temperature maintain lower temperature gradients than units with higher discharge temperatures. Valve- or bypass-controlled units with continuous fan operation maintain lower temperature gradients than units with intermittent fan operation. Directional control of the discharged air from a unit heater can also be important in distributing heat satisfactorily and in reducing floor-to-ceiling temperature gradients.

Filters. Air from propeller unit heaters cannot be filtered because the heaters are designed to operate with heater friction loss only. If dust in the building must be filtered, centrifugal fan units or cabinet units should be used. Chapter 29 has further information on air cleaners for particulate contaminants.

 Control

The controls for a steam or hot water unit heater can provide either (1) on/off operation of the unit fan, or (2) continuous fan operation with modulation of heat output. For on/off operation, a room thermostat is used to start and stop the fan motor or group of fan motors. A limit thermostat, often strapped to the supply or return pipe, prevents fan operation in the event that heat is not being supplied to the unit. An auxiliary switch that energizes the fan only when power is applied to open the motorized supply valve may also be used to prevent undesirable cool air from being discharged by the unit.

Continuous fan operation eliminates both the intermittent blasts of hot air resulting from on/off operation and the stratification of temperature from floor to ceiling that often occurs during off periods. In this arrangement, a proportional room thermostat controls a valve modulating the heat supply to the coil or a bypass around the heating element. A limit thermostat or auxiliary switch stops the fan when heat is no longer available.

One type of control used with downblow unit heaters is designed to automatically return the warm air, which would normally stratify at the higher level, down to the zone of occupancy. Two thermostats and an auxiliary switch are required. The lower thermostat is placed in the zone of occupancy and is used to control a two-position supply valve to the heater. An auxiliary switch is used to stop the fan when the supply valve is closed. The higher thermostat is placed near the unit heater at the ceiling or roof level where the warm air tends to stratify. The lower thermostat automatically closes the steam valve when its setting is satisfied, but the higher thermostat overrides the auxiliary switch so that the fan continues to run until the temperature at the higher level falls below a point sufficiently high to produce a heating effect.

Indirect-fired and electric units are usually controlled by intermittent operation of the heat source under control of the room thermostat, with a separate fan switch to run the fan when heat is being supplied. For more information on automatic control, refer to Chapter 48 of the 2019 ASHRAE Handbook—HVAC Applications.

Unit heaters can be used to circulate air in summer. In such cases, the heat is shut off and the thermostat has a bypass switch, which allows the fan to run independently of the controls.

 Piping Connections

Piping connections for steam unit heaters are similar to those for other types of fan blast heaters. Unit heater piping must conform strictly to the system requirements, while allowing the heaters to function as intended. Basic piping principles for steam systems are discussed in Chapter 11.

Steam unit heaters condense steam rapidly, especially during warm-up periods. The return piping must be planned to keep the heating coil free of condensate during periods of maximum heat output, and the steam piping must be able to carry a full supply of steam to the unit to take the place of condensed steam. Adequate pipe size is especially important when a unit heater fan is operated under on/off control because the condensate rate fluctuates rapidly.

Recommended piping connections for unit heaters are shown in Figure 4. In steam systems, the branch from the supply main to the heater must pitch toward the main and be connected to its top to prevent condensate in the main from draining through the heater, where it might reduce capacity and cause noise.

Hot Water and Steam Connections for Unit Heaters

Figure 4. Hot Water and Steam Connections for Unit Heaters


The return piping from steam unit heaters should provide a minimum drop of 10 in. below the heater, so that the water pressure required to overcome resistances of check valves, traps, and strainers does not cause condensate to remain in the heater.

Dirt pockets at the outlet of unit heaters and strainers with 0.063 in. perforations to prevent rapid plugging are essential to trap dirt and scale that might affect the operation of check valves and traps. Always install strainers in the steam supply line if the heater has steam-distributing coils or is valve controlled.

An adequate air vent is required for low-pressure closed gravity systems. The vertical pipe connection to the air vent should be at least 3/4 in. NPT to allow water to separate from the air passing to the vent. If thermostatic instead of float-and-thermostatic traps are used in vacuum systems, a cooling leg must be installed ahead of the trap.

In high-pressure systems, it is customary to continuously vent the air through a petcock (as shown in Figure 4C), unless the steam trap has a provision for venting air. Most high-pressure return mains terminate in flash tanks that are vented to the atmosphere. When possible, use pressure-reducing valves to allow heater operation at low pressure. Traps must be suitable for the operating pressure encountered.

When piping is connected to hot-water unit heaters, it must be pitched to allow air to vent to the atmosphere at the high point in the piping. An air vent at the heater is used to facilitate air removal or to vent the top of the heater. The system must be designed for complete drainage, including placing nipple and cap drains on drain cocks when units are located below mains.

 Maintenance

Regular inspection, based on a schedule determined by the amount of dirt in the atmosphere, assures maximum operating economy and heating capacity. During design, ensure sufficient space for maintenance access to each component. Clean heating elements when necessary by brushing or blowing with high-pressure air or by using a steam spray. A portable sheet metal enclosure may be used to partially enclose smaller heaters for cleaning in place with air or steam jets. In some installations, however, it may be necessary to remove the heating element and wash it with a mild alkaline solution, followed by a thorough rinsing with water. Propeller units do not have filters and are, therefore, more susceptible to dust build-up on the coils.

Dirt on fan blades reduces capacity and may unbalance the blades, which causes noise and bearing damage. Fan blades should be inspected and cleaned when necessary. Vibration and noise may also be caused by improper fan position or loose set screws. Place a fan guard on downblow unit heaters that have no diffuser or other device to catch the fan blade if it comes loose and falls from the unit.

The amount of attention required by the various motors used with unit heaters varies greatly. Instructions for lubrication, in particular, must be followed carefully for trouble-free operation: excess lubrication, for example, may damage the motor, and an improper lubricant may cause the bearings to fail. Get instructions for care of the motor on any unit heater from the manufacturer and keep them at the unit.

Fan bearings and drives must be lubricated and maintained according to the instructions specified by the manufacturer. If the unit is direct connected, inspect the couplings periodically for wear and alignment. V-belt drives should have all belts replaced with a matched set if one belt shows wear.

Periodic inspections of traps, inspections of check and air valves, and the replacement of worn fans are other important maintenance functions. Strainers should be cleaned regularly. Filters, if included, must be cleaned or replaced when dirty.

3. MAKEUP AIR UNITS

 Description and Applications

Makeup air units are designed to condition ventilation air introduced into a space or to replace air exhausted from a building, in compliance with ASHRAE Standard 62.1 as applicable. The air exhausted may be from a process or general area exhaust, through either powered exhaust fans or gravity ventilators. The units may be used to prevent negative pressure within buildings or to reduce airborne contaminants in a space.

If temperature and/or humidity in the structure are controlled, the makeup air system must have the capacity to condition the replacement air. In most cases, makeup air units must be used to supply this conditioned makeup air. The units may heat, cool, humidify, dehumidify, and/or filter incoming air. They may be used to replace air in the conditioned space or to supplement or accomplish all or part of the airflow needed to satisfy the heating, ventilating, or cooling airflow requirements.

Makeup air can enter at a fixed flow rate or as a variable volume of outdoor air. It can be used to accomplish building pressurization or contamination reduction, and may be controlled in a manner that responds directly to exhaust flow. When compatible with the characteristics and class of the air being exhausted, makeup air units should also be connected to process exhaust with air-to-air heat recovery units, thermal wheels, heat pipes, or runaround coils (recovery loop exchangers) tested (when applicable) under ANSI/ASHRAE Standard 84.

Buildings under negative pressure because of inadequate makeup air may have the following symptoms:

  • Gravity stacks from unit heaters and processes back-vent.

  • Exhaust systems do not perform at rated volume.

  • The perimeter of the building is cold in winter because of high infiltration.

  • Severe drafts occur at exterior doors.

  • Exterior doors are hard to open or close completely.

  • Heating systems cannot maintain comfortable conditions throughout the building because the central core area becomes overheated.

  • Excessive condensation occurs.

Other Applications.

Spot Cooling. High-velocity air jets in the unit may be directed to working positions. During cold weather, supply air must be tempered or reduced in velocity to avoid overcooling workers.

Door Heating. Localized air supply at swinging doors or overhead doors, such as for loading docks, can be provided by makeup air units. Heaters may blanket door openings with tempered air. The temperature may be reset from the outdoor temperature or with dual-temperature air (low when the door is closed and high when the door is open during cold weather). Heating may be arranged to serve a single door or multiple doors by an air distribution system. Door heating systems may also be arranged to minimize entry of insects during warm weather. Air curtain units for door openings should be tested and comply with ANSI/AMCA Standard 220-05, section C408.2.3.

 Selection

Makeup air systems used for ventilation may be (1) sized to balance air exhaust volumes or (2) sized in excess of the exhaust volume to dilute contaminants. In applications where contaminant levels vary, variable-flow units should be considered so that the supply air varies for contaminant control and the exhaust volume varies to track supply volume. In critical spaces, the exhaust volume may be based on requirements to control pressure in the space.

Location. Makeup air units are defined by their location or the use of a key component. Examples are rooftop makeup air units, truss- or floor-mounted units, and sidewall units. Some manufacturers differentiate their units by heating mode, such as steam or direct gas-fired makeup air units.

Rooftop units are commonly used for large single-story industrial buildings to simplify air distribution. Access (via roof walks) is more convenient than access to equipment mounted in the truss; truss units are only accessible by installing a catwalk adjacent to the air units. Disadvantages of rooftop units are (1) they increase foot traffic on the roof, thus reducing its life and increasing the likelihood of leaks; (2) inclement weather reduces equipment accessibility; and (3) units are exposed to weather.

Makeup air units can also be placed around the perimeter of a building with air ducted through the sidewall. This approach limits future building expansion, and the effectiveness of ventilating internal spaces decreases as the building gets larger. However, access to the units is good, and minimum support is required because the units are mounted on the ground.

Use caution in selecting the location of the makeup air unit and/or its associated combustion air source, to avoid introducing combustible vapors into the unit. Consult state and local fire codes for specific guidance.

 Heating and Cooling Media.

Heating. Makeup air units are often identified by the heating or cooling medium they use. Heaters in makeup air systems may be direct gas-fired burners, electric resistance heating coils, indirect gas-fired heaters, steam coils, or hot-water heating coils. (Chapter 27 covers the design and application of heating coils.) Air distribution systems are often required to direct heat to spaces requiring it.

Natural gas can be used to supply an indirect-fired burner, as for a large furnace. (Chapter 33 has more information, including detailed heater descriptions.) In a non-recirculating direct-fired heater, levels of combustion products generated by the heater are very low (CO < 5.0 ppm, NO2 < 0.5 ppm, and CO2 < 4000 ppm) and are released directly into the airstream being heated. All air to a non-recirculating makeup air heater must be ducted directly from outdoor source. Non-recirculating direct gas-fired industrial air heaters are typically certified to comply with ANSI Standard Z83.4b/CSA3.7b-2006. In a recirculating makeup air heater, ventilation air to the heater must be ducted directly from an outdoor source to limit the concentration of combustion products in the conditioned space to a level below 25 ppm for CO, 3 ppm for NO2, and 5000 ppm for CO2. Recirculating direct gas-fired industrial air heaters are typically certified to comply with ANSI Standard Z83.18-2000. Installing carbon monoxide detectors to protect building occupants in the event of a heater malfunction is good engineering practice, and may be required by local codes.

Hydronic heating sections in spaces requiring a fully isolated source (100%) of outdoor air must be protected from freezing in cold climates. Low-temperature protection includes two-position control of steam coils; careful selection of the water coil heating surface and control valves; careful control of water supply temperature; and use of an antifreeze additive.

Cooling. Mechanical refrigeration with direct-expansion or chilled-water cooling coils, direct or indirect evaporative cooling sections, or well water coils may be used. Air distribution systems are often required to direct cooling to specific spaces that experience or create heat gain.

Because industrial facilities often have high sensible heat loads, evaporative cooling can be particularly effective. An evaporative cooler helps clean the air, as well. A portion of the spray water must be bled off to keep the water acceptably clean and to maintain a low solids concentration. Chapter 41 of this volume and Chapter 53 of the 2019 ASHRAE Handbook—HVAC Applications cover evaporative cooling in more detail.

Chapter 23 provides information on air-cooling coils. If direct-expansion coils are used in conjunction with direct-fired gas coils, the cooling coils’ headers must be isolated from the airstream and directly vented outdoors.

Filters. High-efficiency filters (approximately MERV 16 for near-HEPA performance) are not normally used in a makeup air unit because of their relatively high cost. HVAC prefilters are generally in the MERV 6 to 13 range, depending on particulate removal needs. Designers should ensure that all filters are easy to change or clean. Appropriate washing equipment should be located near all washable filters. Throwaway filters should be sized for easy removal and disposal. Chapters 29 and 30 have more information on air filters and cleaners.

Fans. Follow AMCA Standard 205-12 for fan selection. This standard addresses fans with a minimum impeller diameter of 5 in., operating with a shaft power of at least 1 hp, and with a total efficiency calculated according to one of the following fan test standards:

  • ANSI/AMCA Standard 210 (ANSI/ASHRAE Standard 51)

  • ANSI/AMCA Standard 230

  • AMCA Standard 260

  • ISO Standard 5801

ASHRAE Standard 90.1-2013 requires a fan efficiency grade (FEG) 67, and that the fan should be sized and selected within 15% of its peak total efficiency (FEG 71 under AMCA Standard 205 and ICC [2015]).

Fans should have variable-speed drives for possible energy savings or for use in variable-airflow systems.

 Control

Controls for a makeup air unit fall into the following categories: (1) local temperature controls, (2) airflow controls, (3) plant-wide controls for proper equipment operation and efficient performance, (4) safety controls for burner gas, and (5) building smoke control systems. For control system information, refer to Chapters 42, 42, and 48 of the 2019 ASHRAE Handbook—HVAC Applications.

Safety controls for gas-fired units include components to properly light the burner and to provide a safeguard against flame failure. The heater and all attached inlet ducting must be purged with at least four air changes before initiating an ignition sequence and before reignition after a malfunction. A flame monitor and control system must be used to automatically shut off gas to the burner upon burner ignition or flame failure. Critical malfunctions include flame failure, supply fan failure, combustion air depletion, power failure, control signal failure, excessive or inadequate inlet gas supply pressure, excess air temperature, and gas leaks in motorized valves or inlet gas supply piping.

Makeup air units should be interlocked with exhaust units to avoid overpressurization, and should include shutoff dampers with limit switches for when not in use. Damper leakage rates should be within limits set in ASHRAE Standard 90.1. These units should also be interlocked to the building’s fire alarm system to shut down in the case of a fire, where required by applicable codes.

Consider using automatic safety shutoff valves on interconnecting piping systems where there are risks of overtemperature, overpressure, or gas leaks.

 Applicable Codes and Standards

A gas-fired makeup air unit must be designed and built in accordance with NFPA Standard 54 and the requirements of the owner’s insurance underwriter. Local codes must also be observed when using direct-fired gas makeup air units because some jurisdictions prohibit or restrict their use and may also require exhaust fans to be used while the unit is in operation.

The following standard and codes and the sources in the References may also apply, depending on the application.

AHRI. 2014. Performance rating of air-to-air exchangers for energy recovery ventilation equipment. ANSI/AHRI Standard 1060. Air-Conditioning, Heating, and Refrigeration Institute, Arlington, VA.

ICC. 2015. International mechanical code® (IMC®). International Code Council, Falls Church, VA.

ICC. 2015. International fuel gas code® (IFGC®). International Code Council, Falls Church, VA.

 Commissioning

Commissioning of makeup air systems is similar to that of other air-handling systems, requiring attention to

  • Equipment identification

  • Piping system identification

  • Belt drive adjustment

  • Control system checkout in accordance with ASHRAE Guideline 11-2009

  • Documentation of system installation

  • Lubrication

  • Electrical system checkout for overload heater size and function

  • Cleaning and degreasing of hydronic piping systems

  • Pretreatment of hydronic fluids

  • Setup of chemical treatment program for hydronic systems and evaporative apparatus

  • Start-up of major equipment items by factory-trained technician

  • Testing and balancing

  • Planning of preventive maintenance program

  • Instruction of owner’s operating and maintenance personnel in accordance with proposed ASHRAE Guideline GPC 1.3P, Building Operation and Maintenance Training for the HVAC&R Commissioning Process

 Maintenance

Basic operating and maintenance data required for makeup air systems may be obtained from the ASHRAE Handbook chapters covering the components. Specific operating instructions are required for makeup air heaters that require changeover from winter to summer conditions, including manual fan speed changes, air distribution pattern adjustment, or heating cycle lockout. Operating and maintenance documentation should comply with ASHRAE Guideline 4-2008 (RA13).

Operations handling 100% outdoor air may require more frequent maintenance, such as changing filters, lubricating bearings, and checking the water supply to evaporative coolers/humidifiers. Filters on systems in locations with dirty air require more frequent changing, so a review may determine whether upgrading filter media would be cost-effective. More frequent cleaning of fans’ blades and heat transfer surfaces may be required in such locations to maintain airflow and heat transfer performance.

REFERENCES

ASHRAE members can access ASHRAE Journal articles and ASHRAE research project final reports at technologyportal.ashrae.org. Articles and reports are also available for purchase by nonmembers in the online ASHRAE Bookstore at www.ashrae.org/bookstore.

ACCA. 2005. Direct-fired MUA equipment. Technical Bulletin 109 (four parts). Air-Conditioning Contractors of America, Washington, D.C.

ACGIH. 2013. Industrial ventilation: A manual of recommended practice for design, 28th ed. American Conference of Governmental Industrial Hygienists, Cincinnati, OH.

AHRI. 2009. Central-station air-handling units. ANSI/AHRI Standard 430-2009. Air-Conditioning, Heating, and Refrigeration Institute, Arlington, VA.

AMCA. 2012. Energy efficiency classification for fans. ANSI/AMCA Standard 205-12. Air Movement and Control Association, Arlington Heights, IL.

AMCA. 2012. Laboratory methods of testing air circulating fans for rating and certification. ANSI/AMCA Standard 230-12. Air Movement and Control Association, Arlington Heights, IL.

AMCA. 2013. Laboratory methods of testing induced flow fans for rating. Standard 260-13. Air Movement and Control Association, Arlington Heights, IL.

ANSI. 2012. Laboratory methods of testing air curtains for aerodynamic performance ratings. Standard 220-05, Section C408.2.3. American National Standards Institute, New York.

ANSI. 2012. Recirculating direct gas-fired industrial heaters. Standard Z83.18-2012. American National Standards Institute, New York.

ANSI/CSA. 2013. Non-recirculating direct gas-fired industrial air heaters. ANSI Standard Z83.4/CSA3.7-2013. American National Standards Institute, New York.

ASHRAE. 2013. Ventilation for acceptable indoor air quality. ANSI/ASHRAE Standard 62.1-2013.

ASHRAE. 2013. Method of testing air-to-air heat/energy exchangers. ANSI/ASHRAE Standard 84-2013.

ASHRAE. 2013. Energy standard for buildings except low-rise residential buildings. ANSI/ASHRAE/IESNA Standard 90.1-2013.

ASHRAE. 2006. Energy conservation in existing buildings. ASHRAE/IESNA Standard 100-2006.

ASHRAE. 2009. Field testing of HVAC controls components. Guideline 11-2009.

ICC. 2015. International green construction code® (IgCC®). International Code Council, Washington, D.C.

ISO. 2007. Industrial fans—Performance testing using standardized airways. Standard 5801:2007. International Organization for Standardization, Geneva.

BIBLIOGRAPHY

Brown, W.K. 1990. Makeup air systems—Energy saving opportunities. ASHRAE Transactions 96(2):609-615. Paper SL-90-05-1.

Bridgers, F.H. 1980. Efficiency study—Preheating outdoor air for industrial and institutional applications. ASHRAE Journal 22(2):29-31.

Burroughs, H.E. 2005. Filtration and building security. ASHRAE Journal April 2005:24-29.

Gadsby, K.J., and T.T. Harrje. 1985. Fan pressurization of buildings—Standards, calibration and field experience. ASHRAE Transactions 91(2B): 95-104. Paper HI-85-03-1.

Holness, G.V.R. 1989. Building pressurization control: Facts and fallacies. Heating/Piping/Air Conditioning (February).

NFPA. 2018. National fuel gas code. Standard 54-2018. National Fire Protection Association, Quincy, MA.

Persily, A. 1982. Repeatability and accuracy of pressurization testing. In Thermal Performance of the Exterior Envelopes of Buildings II, Proceedings of ASHRAE/DOE Conference. ASHRAE SP 38:380-390.

PG&E. 2002. Improving commercial kitchen ventilation system performance: Optimizing makeup air. Design Guide 2.



The preparation of the sections on Unit Ventilators and Unit Heaters is assigned to TC 6.1, Hydronic and Steam Equipment and Systems. The preparation of the section on Makeup Air Units is assigned to TC 5.8, Industrial Ventilation.