VRF systems are highly engineered, with single or multiple compressors, multiple indoor units (ducted and nonducted types), and oil and refrigerant management and control components. VRF provides flexibility by allowing for many different indoor units (with different capacities and configurations), individual zone control, and the unique ability to offer simultaneous heating and cooling in separate zones on a common refrigerant circuit, and heat recovery from one zone to another. Typical capacities range from 18,000 to 760,000 Btu/h for outdoor units and from 5000 to 120,000 Btu/h for indoor units.
VRF systems are equipped with at least one variable-speed and/or variable-capacity compressor. Figure 1 illustrates capacity control of a single variable-speed compressor; the compressor varies its speed to operate only at the levels necessary to maintain indoor environments to the specified requirements.
There are three basic types of VRF systems: cooling only (Figure 2), heat pump (Figure 2), and heat recovery (Figures 3 and 4). Heat pumps are air-conditioning systems capable of reversing the direction of the refrigerant flow to provide heating or cooling to the indoor space. All indoor units connected to a heat pump system can use individual control and set points, but they operate in the same mode of either heating or cooling at any given time.
Heat recovery units are heat pump systems that can provide simultaneous heating and cooling. All indoor units connected to a heat recovery system not only can use individual control and set points, but they can also individually operate in heating or cooling mode at any given time. To match the building’s load profiles, energy is transferred from one indoor space to another through the refrigerant line, and only one energy source is necessary to provide both heating and cooling. VRF systems also operate efficiently at part load because of the compressor’s variable capacity control.
Note: Figures 2 to 4 represent various methods of VRF system piping configurations. Please refer to each manufacturer’s data for specifics.
The following definitions are based on AHRI Standard 1230.
A heat pump multisplit system is an encased, factory-made, permanently installed assembly that takes heat from a heat source and delivers it to the conditioned space when heating is desired. It may remove heat from the conditioned space and discharge it to a heat sink if cooling and dehumidification are desired from the same equipment. Normal components include multiple indoor conditioning coils, compressor(s), and outdoor coil(s). Equipment may be provided in multiple assemblies, intended for use together. Other functions may include cleaning, circulating, and humidifying the air.
A VRF multisplit system is a split-system air conditioner or heat pump with a single refrigerant circuit, one or more outdoor units, at least one variable-speed compressor or other compressor combination that can vary system capacity by three or more steps, and multiple indoor fan-coil units that are individually metered and individually controlled by an integrated control device and common communications network. A VRF heat recovery multisplit system operates as an air conditioner or heat pump, and also can provide simultaneous heating and cooling operation by transferring recovered energy from the indoor units operating in one mode to other indoor units operating in the other mode. Variable refrigerant flow implies three or more steps of control on common, interconnecting piping.
AHRI has a certification program specifically for VRF multisplit air-conditioning and heat pump equipment. AHRI Standard 1230 applies to all VRF multisplit air-conditioning and heat pump/heat recovery equipment with capacities up to 760,000 Btu/h. It follows AHRI standard rating conditions, and covers all VRF multisplit, matched system air conditioners and heat pumps, regardless of electric power source, refrigeration cycle, or secondary fluid (e.g., air-to-air or water-to-air). In conducting all VRF testing, the following definition is used to configure the systems to be tested. This definition of “tested combination” from AHRI Standard 1230 has been a key factor in establishing equivalency of testing with VRF systems and other unitary systems:
3.26 Tested Combination. A sample basic model comprised of units that are production units, or are representative of production units, of the basic model being tested. The tested combination shall have the following features:
a. The basic model of a variable refrigerant flow system (“VRF system”) used as a Tested Combination shall consist of an outdoor unit (an outdoor unit can include multiple outdoor units that have been manifolded into a single refrigeration system, with a specific model number) that is matched with between 2 and 12 indoor units.
b. The indoor units shall:
b.1 Represent the highest sales model family as determined by type of indoor unit e.g. ceiling cassette, wall-mounted, ceiling concealed, etc.
b.2 Together, have a nominal cooling capacity between 95% and 105% of the nominal cooling capacity of the outdoor unit.
b.3 Not, individually, have a nominal cooling capacity greater than 50% of the nominal cooling capacity of the outdoor unit, unless the nominal cooling capacity of the outdoor unit is 24,000 Btu/h or less.
b.4 Have a fan speed that is consistent with the manufacturer’s specifications.
b.5 All be subject to the same minimum external static pressure requirement while being configurable to produce the same static pressure at the exit of each outlet plenum when manifolded as per section 2.4.1 of 10 CFR Part 430, Subpart B, Appendix M.
Table 1 lists VRF multisplit system classifications.
The following certification program ratings (from AHRI Standard 1230-2010) are verified by test:
VRF Multisplit Air Conditioners < 65,000 Btu/h
Standard rating cooling capacity, Btu/h
Energy efficiency ratio (EER; ratio of cooling capacity to power input values at any given set of rating conditions), Btu/W · h
Seasonal energy efficiency ratio (SEER); total cooling of a system with a capacity < 65,000 Btu/h during its normal use for cooling, divided by total electric energy input during the same period), Btu/W · h
VRF Multisplit Air Conditioners ≥ 65,000 Btu/h
Standard rating cooling capacity, Btu/W · h
Energy efficiency ratio (EER), Btu/W · h
Integrated energy efficiency ratio (IEER; a cooling part-load efficiency rating), Btu/W · h
VRF Multisplit Heat Pumps < 65,000 Btu/h
Standard rating cooling capacity, Btu/h
Seasonal energy efficiency ratio (SEER), Btu/W · h
Energy efficiency ratio (EER), Btu/W · h
High-temperature heating standard rating capacity, Btu/h
Region IV heating seasonal performance factor (HSPF; total heating output of a heat pump, including supplementary electric heat necessary to achieve building heating requirements during normal annual use for heating, divided by total electric power during the same period), minimum design heating requirement, Btu/W · h
VRF Multisplit Heat Pumps ≥ 65,000 Btu/h
Standard rating cooling capacity, Btu/h
Energy efficiency ratio (EER), Btu/W · h
Integrated energy efficiency ratio (IEER), Btu/W · h
High-temperature heating standard rating capacity, Btu/h
High-temperature coefficient of performance (COP); ratio of heating capacity to power input values at any given set of rating conditions; for heating COP, exclude supplementary resistance heat), W/W
Low-temperature heating standard rating capacity, Btu/h
Low-temperature coefficient of performance (COP), W/W
VRF Multisplit Heat Recovery Heat Pumps
Ratings as for VRF multisplit heat pumps
Simultaneous cooling and heating efficiency (SCHE; ratio of total system capacity for heating and cooling to effective power when operating in heat recovery mode) (50% heating/50% cooling); Btu/W · h
VRF Multisplit Heat Pumps Systems with Heat Rejection to Water
Standard rating cooling capacity, Btu/h
Energy efficiency ratio (EER), Btu/W · h
Integrated energy efficiency ratio (IEER), Btu/W · h
Heating standard rating capacity, Btu/h
Heating coefficient of performance (COP), W/W
Simultaneous cooling and heating efficiency (SCHE) (50% heating/50% cooling; heat recovery models only)
Other testing includes maximum operating conditions, voltage tolerance, low-temperature operation (cooling), insulation effectiveness (cooling), and condensate disposal (cooling), as outlined in Section 8 of AHRI Standard 1230.
Air-Source Outdoor and Water-Source Units
Air-source outdoor units and water-source units (sometimes called condensing units, air-to-air units, or air-to-water units) contain circuit boards, heat exchanger(s), and a choice of compressor(s). The compressor, the most important component in the VRF system, can be combined with several different types of heat exchange sources.
Most VRF systems use variable-speed scroll or rotary compressors. These compressors are reliable, have very few moving parts, provide continuous compression with little pulsation or vibration, and, through the variable-speed drive, provide modulating linear capacity control. Variable-speed scroll and rotary compressors offer quiet operation and excellent individual full- and part-load efficiencies, and because of precise machining, the vane flanks are sealed with only a thin film of oil. If a single compressor fails in a multiple-outdoor-unit system, peak capacity is lost, but the overall system can still provide partial cooling or heating.
Indoor units (also called fan-coil units, evaporator units, or air-handling units) are available in many different configurations (Figure 5), including
Multiple indoor unit types can be used within a single VRF system.
VRF systems have integrated controls in each component to ensure that all system components operate collectively. Depending on the application and design, a VRF system may be able to operate with many levels of controls (Figure 6). Each indoor unit may be managed by a local controller, or multiple indoor units serving the same zone can be operated by the same controller. Each manufacturer offers centralized controllers, which allow the user to monitor and control VRF systems and ancillary equipment from a single location or through the Internet. Manufacturers also offer open protocol communication gateways for higher-level monitoring.
System Expansion or Reconfiguration
The modular nature of VRF systems lends itself to easy system expansion or reconfiguration as building needs change. During design, the designer and client can discuss any possible future or changing needs in the building envelope.
VRF air-source outdoor units and water-source units can be sized based on future building requirements according to manufacturers’ recommendations to anticipate supplementary indoor units without affecting the performance of currently installed indoor units or overall system performance. This allows for VRF systems to accommodate the heating and cooling needs of the building as each section of the building is commissioned.
When a building or zone is repurposed, indoor units may be added, relocated, or exchanged with minimal disruption. Indoor units may be relocated or changed out for different types or capacities in a given space as occupancy needs change, as long as the overall system capacity capabilities are maintained. This can be accomplished by simply reconfiguring indoor unit refrigerant piping, electrical wiring, control wiring, and drain piping. Note, however, that in some applications, piping sizes may change as capacity sizes change. Obtain manufacturer recommendations on piping design and diversity parameters before performing any type of indoor unit installation or relocation.
A thorough understanding of how VRF heat pump units operate and how the different components function individually (and as part of the system) is important for successfully designing and applying VRF systems. Designers should consider many operation factors before proposing VRF heat pump systems for a building project:
At the zone level, a VRF heat pump system’s indoor units perform load management (sometimes called capacity control) through an EEV or LEV. At the system level, the outdoor unit conducts load management through the inverter-driven variable-speed compressor(s), or an alternative combination for varying capacity and variable-speed air-source outdoor unit fans.
For cooling operation, the compressor is controlled through monitoring the target evaporating temperature or target superheat. For heating operation, the compressor is controlled through monitoring the target condensing temperature or target subcooling (Figure 7).
These values are then used to control the VRF system’s compressor, fan motor, and EEV/LEV to ensure stable target temperature control, regardless of varying loads and environmental conditions (Table 2).
The indoor units of a VRF system are designed to operate at variable cooling capacities to match the load in the given zone. In cooling mode, the indoor unit’s EEVs or LEVs are controlled to maintain a target superheat value or evaporator temperature. Superheat is determined by calculating the temperature difference between the indoor unit vapor pipe thermistor and liquid refrigerant pipe thermistor. When the difference between set point and zone temperature decreases, the expansion valve throttles (and vice versa), maintaining the target superheat. The total system capacity is influenced by the number of indoor units operating in cooling mode, airflow rates, zone load, and indoor and outdoor ambient conditions.
The air-source outdoor units and water-source units operate as a variable condenser controlled to maintain a preset differential between the sink (ambient air or water) temperature and condensing temperature. Expansion takes place independently at each indoor unit. As the load for each individual indoor unit changes, the EEV/LEV modulates to control the target superheat and/or evaporator temperature. The compressor(s) adjust to match the total system load by varying the refrigerant flow as demanded by the indoor units.
Indoor unit sizing should be guided by calculated load, but the units’ variable capacity allows for design flexibility, and capacity-to-load matching is less critical than for single capacity systems.
In heating mode, the EEV or LEV of the indoor unit is controlled to maintain target subcooling or coil temperature. Subcooling is determined by calculating the temperature difference between the system condensing temperature and the indoor unit’s liquid pipe thermistor. When the difference between the set point and zone temperature decreases, the expansion valve throttles (and vice versa), maintaining the target subcooling. As with cooling mode, the total system capacity is influenced by the number of indoor units operating in cooling mode, airflow rates, zone load, and indoor and outdoor ambient conditions
The coil in the air-source outdoor unit or water-source unit is now acting as the evaporator, and the EEV or LEV opens and closes according to the superheat value detected in the suction pipe, operating as necessary to maintain the target superheat value. As the load at each individual indoor unit changes, the compressor(s) adjust to vary refrigerant flow to match the total system load.
Saturation Temperature Reset
Standard operation of the VRF system’s compressor(s) consists of maintaining either a target evaporating saturation temperature or a target condensing temperature; the target temperatures are typically fixed, as shown in Table 2. Under this control, maintaining system capacity is the priority.
Some VRF systems incorporate configurable control logic to allow the target saturation temperatures to float based on operating conditions (e.g., ambient temperature and indoor unit load) to balance between operating efficiency and capacity. During cooling, as load on the system drops, the target evaporating temperature is reset upward to reduce lift on the compressor and improve energy efficiency. As system load increases, the target evaporating temperature is reset downward to increase system capacity and maintain indoor comfort levels.
When heating, the target condensing temperature can be reset lower through the control logic during low-load conditions to reduce compressor lift and improve efficiency. As system load increases, the target condensing temperature is reset upward to increase system capacity and maintain indoor comfort levels.
Because response time and operation are affected, consult the manufacturer for specific operation parameters to determine which control strategy is best for design condition and application.
Heat recovery systems can transfer energy from one zone to another. The amount of energy transferred depends on the operation mode of the individual indoor units. The outdoor unit operates in cooling or heating as determined by the greater demand of the indoor units. Heat recovery operation can be common in shoulder seasons, and is applicable in all seasons if a building has different zone load profiles such as interior room loads versus exterior room loads. Heat recovery operation can also be applied to buildings with an east/west or north/south orientation, and when occupancy profiles are based on time of day.
Manufacturers offer two design approaches to VRF heat recovery operation: two-pipe and three-pipe systems.
Two-Pipe Systems.
Two-pipe VRF heat recovery systems include a heat recovery control unit (sometimes called a branch controller, branch box, or heat recovery unit) that acts as an intermediate heat exchanger between the indoor units and the outdoor unit(s). This unit houses a series of diverting valves and gas/liquid separators to move high- or low-pressure refrigerant between the indoor units, minimizing the load transferred directly to the outdoor unit (Figure 8).
Two-pipe VRF heat recovery systems are in total or balanced heat recovery mode when the peak zone heating and cooling loads are equal. During balanced heat recovery mode, hot refrigerant gas is delivered from the outdoor unit compressor to the heat recovery control unit, where it is then distributed to the indoor units in the zones that require heating.
Any subcooled refrigerant from the indoor units in heating mode is delivered back to the heat recovery control unit, where it is redistributed to the indoor units in cooling mode. Refrigerant leaving the indoor units in cooling mode is in a low-pressure vapor state, completing the state of equilibrium in the refrigeration cycle. This low-pressure vapor is delivered to the heat recovery control unit before returning to the outdoor unit compressor, where it is compressed to high-pressure gas by adding the heat of compression to the process. The cycle repeats itself in the preceding manner. If the system is not completely balanced between heating and cooling loads, the heat exchanger in the outdoor unit is not bypassed. Heat energy is partially absorbed or rejected, depending on the balance between heating and cooling loads.
Three-Pipe Systems.
Three-pipe VRF systems include one high-pressure vapor pipe, one low-pressure vapor pipe, and one liquid pipe between the outdoor unit and the heat recovery control unit(s). The heat recovery control unit controls the direction of refrigerant flow through the indoor units. In heating mode, the high-pressure vapor pipe opens and the low-pressure vapor pipe closes, allowing refrigerant to flow through the high-pressure vapor pipe and into the indoor unit, where it condenses, turning the indoor unit into a zoned condenser. In cooling mode, the high-pressure vapor pipe closes and the low-pressure vapor pipe opens, allowing refrigerant to flow through the liquid pipe into the indoor unit, where it evaporates, turning the indoor unit into an evaporator.
A three-pipe VRF system’s heat recovery units can have either single or multiple ports, and each port can provide heating or cooling independently of other ports (Figure 9). One or more indoor units can connect to each port on the heat recovery unit, but if multiple indoor units are connected to a single port, they will operate in the same mode. Numbers and capacity of indoor units connected must follow manufacturer’s recommendation.
Multilayer Heat Recovery in Water-Source VRF Systems.
Water-source VRF systems offer an opportunity for two levels of heat recovery, because heat energy can be exchanged between zones at the refrigerant level as well as between systems through the water loop (Figure 10).
As with all air-source heat pump systems, VRF outdoor unit heat exchanger coils can accumulate frost during heating operation under some temperature and humidity conditions. Defrost-cycle operation is included to melt accumulating frost, but it differs with each manufacturer.
Sometimes defrost initiates after a fixed time or variable minimum time, based on a temperature difference sensed between ambient and refrigerant. Some systems sense frost build-up through a temperature reduction in the low-pressure vapor refrigerant line, and/or a low temperature at the outdoor unit’s heat exchanger coils. Heating operation stops, and the system reverses refrigerant flow, making the outdoor unit coil a condenser to melt accumulating frost. Indoor units switch off for the duration of defrost operation to avoid unwanted cooling of the conditioned space. Alternatively, an indoor unit can maintain space temperature through an output signal to a supplemental heater (duct or perimeter), as controlled from a room-based thermistor.
Manufacturers may use a partial defrost approach, which uses a split-coil configuration in the outdoor unit(s), and defrost only half the coil at a time while still providing approximately 30 to 40% of its heating capacity. If a system has multiple outdoor units piped together to make a single system, manufacturers may choose to defrost each outdoor unit separately, or defrost all the outdoor units on a single system together to decrease overall system defrost time or ensure clearing the coil of ice most effectively. A manufacturer may also use logic that allows equipment to run either a partial defrost in conditions where it is easier to defrost the coil or when it does not adversely affect efficiency, or full defrost to ensure the coil is completely free of ice when it is more difficult to defrost the coil to maintain capacity.
Air-source outdoor units may be installed indoors, but each manufacturer has specific installation requirements for both ambient operating temperatures and potential ducting configurations for this application. Wherever the designer chooses to install the outdoor unit (indoors or out), it is important to consider that the unit will generate condensation and, therefore, may require a drain.
During normal operation, oil may migrate out of the compressor, so manufacturers may include an oil separator for each compressor in the outdoor unit(s). The oil separator uses compressor discharge velocity to spin refrigerant out to the separator’s shell, where oil collects on the walls, then drains by gravity to the bottom and back to the compressor’s oil sump.
Oil separators collect most of the oil; however, a small amount of oil remains entrained in the refrigerant leaving the separator, and often collects in the piping system and indoor units. To reclaim oil that settles in the system and away from the sump, the controls open the EEV or LEV in all indoor units (even if they are not in operation) after a set period of compressor operation. The compressor switches to a predetermined speed or setting to ensure oil in the system flushes back to the compressor sump. The oil recovery cycle generally engages after the compressor has been operating for a predetermined number of hours, and may factor in operational capacity to adjust the frequency of the cycle, or use an oil level sensor. Oil recovery typically lasts from 3 to 6 min and may affect operational mode, as defined by the manufacturer.
Zone comfort and associated indoor unit output are controlled based on a dry-bulb temperature set point in the space or at a central location. The sensible-to-total-cooling ratio is typically in the 70 to 80% range, depending on airflow across the unit and ambient air or condenser water temperatures. The rated capacities of the installed indoor units typically match the peak total heating or cooling load for the specific zone’s total, sensible, and latent elements. Indoor unit output follows the load profile curve for that specific zone. The sensible-to-latent-load ratio changes with indoor and outdoor ambient conditions in most cooling applications.
Some indoor units include a dry mode that could provide dehumidification once zone temperatures rise above a dew-point temperature threshold. In dry mode, the indoor unit operates at a low fan speed to keep the coil cold, and at sufficient capacity to remove moisture from the air without significantly lowering room temperature. If the zone temperature drops below a designated set point (depending on individual manufacturer’s specifications), the indoor unit may shut off.
If a dedicated outdoor air system (DOAS) is applied to a VRF system, the lower off-coil temperatures at the DOAS allow the DOAS to manage a significant proportion of the outdoor air’s latent cooling load. This lets the indoor units of the VRF system manage the majority of sensible and latent cooling loads of the indoor air.
In winter heating cycles where humidification is required to maintain zone comfort, a supplemental humidification unit can be used through the ventilation air system. An energy recovery ventilator (ERV), as opposed to a heat recovery wheel or core ventilator, as part of the ventilation air system can help reduce latent loads during cooling mode. In winter heating mode, cool, dry outdoor supply air is partially humidified by moist exhaust air. In summer cooling mode, moisture from outdoor supply air is transferred to the dry exhaust air, thus reducing the latent load on the VRF indoor units.
High-Heating-Performance Air-Source VRF Units
To improve the heating performance of air-source VRF systems in low-ambient-temperature conditions, manufacturers have developed refrigeration cycles so that 100% nominal heating performance can be maintained as low as 5°F ambient, and with approximately 80% heating output at –13°F. Strategies to achieve these heating performance levels include flash injection and a staged compression cycle.
Flash Injection.
Some air-source VRF systems include flash injection technology on a single-compressor refrigeration circuit to offer increased heating output at lower ambient temperatures. Such systems offer nominal heating output at ambient temperatures as low as 0°F. The flash gas flow is modulated to an intermediate point in the compression process based on the difference between the required heating output and external ambient conditions. Compressor speed is optimized based on the circuit load (Figure 11).
The flash injection cycle only operates in heating mode, and activates based on specific predetermined ambient conditions.
Staged Compression Cycle.
An alternative approach to achieving higher-temperature outputs at lower ambient conditions is to use compound compression with intermediate economizers (Figure 12).
In some climates, supplemental heating may still be required to meet peak heating loads for the zone.
When designing a project, many factors should be considered for VRF systems, including
New construction or retrofit applications
Construction schedule
Building orientation and layout
Building occupancy characteristics (including future zoning)
Peak heating and cooling load profiles (including occurrence)
Integration of renewable energy sources
Zone-specific design considerations, such as acoustic performance levels
Building space allocation for mechanical equipment
Opportunities for capturing waste heat in the mechanical system
Application-specific ventilation air requirements
Life-cycle performance and green-building certification expectations
Local design weather conditions
Local/remote control/monitoring requirements
Opportunities for simultaneous heating and cooling for comfort conditioning
After all factors are analyzed, the engineer may choose from a range of VRF system types.
Water-source VRF systems can be applied in the same design scenarios as air-source systems. They can also be used in a range of building application types, but must be integrated with geothermal heat sinks or boiler/cooling tower systems. If applied to year-round cooling applications, water-source VRF systems allow optimizing water-loop temperatures, along with compressor power input in correspondence with ambient wet bulb. The need for supplemental boiler/heating systems depends on the design.
Depending on the application design parameters, water-loop systems offer performance advantages over air-source systems, such as
High annual system COP levels (depending on system)
Consistent performance because of smaller fluctuations in loop temperature
Low- or high-ambient heating or cooling
No defrost cycles
Multilayer heat recovery
Nominal capacities for water-source systems are typically based on an entering water temperature of 70°F for heating, and 85°F for cooling. For appropriate system operation during standard heating and cooling modes, the entering water temperature can range from 50 to 113°F, but can operate with loop fluid temperatures as low as 14°F (e.g., in geothermal applications). Each manufacturer has its own specific performance characteristics.
The rated heated capacity of a water-source VRF system is not directly affected by the external ambient temperature. The condenser water-loop heat source, which can be a boiler or ground/well, can be sized to minimize or eliminate a reduction in heating capacity due to low ambient temperatures. The condenser water loop must be maintained at a predetermined temperature set point to ensure nominal heating output.
Air-source VRF systems have been applied in many design conditions, including
External ambient cooling design applications between 115 and –20°F
High-sensible-heat-ratio cooling applications
External ambient heating-dominant applications lower than –13°F
Low External Ambient Heating-Dominant Applications
Heating capacities of air-source VRF outdoor units are derated as ambient temperature decreases, down to approximately 60% heating capacity at –4°F. There are three strategies for decreasing the effect of lower ambient temperatures on VRF systems during the heating operation:
Sizing air-source VRF units to meet the design heating load
Integration with supplemental heating sources
Locating the air-source unit in a temperate or controlled ambient environment (e.g., equipment room, parking garage)
Integration with Supplemental Heating Sources
In some climates, supplemental heating may still be required to meet peak heating loads for the zone. VRF systems can be integrated with supplemental perimeter or duct-mounted electric, gas-fired, or hot-water-based heating systems. Supplemental heating components can be enabled based on a preset ambient temperature measured at the outdoor unit, and/or on a zone-by-zone basis using the indoor unit and a preset dead band between design space temperature and actual space temperature. If the application calls only for zone-by-zone activation, size the supplemental heating component based on the difference between the rated mechanical heating capacity at design conditions and peak design zone heat load. In some instances, full supplemental heating may need to be factored into the design.
The model building energy codes [ASHRAE/IES Standard 90.1 and the International Energy Conservation Code® (IECC®) (ICC 2015)] each have a prescriptive requirement for the use of air-side economizers, which use outdoor air instead of mechanical cooling to cool the indoor space. Air-side economizers are not required by the codes in every application. Climate zones 1a and 1b are exempt from this requirement, and in ASHRAE/IES Standard 90.1, for the remaining climate zones, indoor units (sometimes called fan-coil units, evaporator units, or air-handling units) with a cooling capacity under 54,000 Btu/h are exempt. Both model codes also provide exceptions related to increased energy efficiency for equipment in certain climate zones, and some state energy codes provide an exemption to the economizer requirement for VRF systems with heat recovery (simultaneous cooling and heating).
Generating Radiant Heating/Cooling and Domestic Hot Water
VRF systems can generate chilled or hot water for space cooling or heating purposes, or domestic hot water for other applications. In such applications, a refrigerant/water indoor heat exchange module with integrated controls is included in the system format. VRF manufacturers use different strategies to achieve each capability.
In some zones, indoor units could be replaced by a radiant floor or cooling/heating panel that receives water from a refrigerant-to-water heat exchanger. Adopting a similar strategy, the VRF system can generate domestic hot water with leaving water temperatures up to 160°F by using a heat exchanger with a booster refrigeration cycle. The refrigerant-to-water heat exchanger could also be used for preheating purposes in some applications. The refrigerant-to-water heat exchanger is selected based on design peak cooling/heating capacity, cooling/heating leaving water temperature, water-side design temperature difference, and water flow rates.
6. VRF SYSTEM DESIGN EXAMPLE
Performing a Load-Profile Analysis
The complete specification of a VRF system requires careful planning at the design stage, and a detailed analysis of project needs and the building’s annual cooling and heating load profiles are required before equipment is selected and sized.
For example, an engineer is designing an HVAC system for a 5000 ft2, single-story office commercial building in Nashville, Tennessee, with an east/west layout orientation. Nashville has a local design ambient condition of 94°F db for summer and 16°F db for winter. For the building’s cooling and heating load profile, see Table 4.
System Type Selection, Zoning, and Potential for Heat Recovery
VRF system selection, whether heat pump versus heat recovery or air-source versus water-source, is driven by many factors, most notably the best balance between operating costs and capital costs per unit area. A complete energy analysis of the building is necessary to evaluate which system type is most appropriate for the application.
After studying the peak load profile, the designer could divide the building into three main zones with similar occupancy profiles, with each zone served by a dedicated heat pump system. For the electrical room, the dedicated system (either water-source or low-ambient air-source) would operate in cooling mode all year.
There is potential, however, for heat recovery operation in this building. Waste heat from the cooling-only electrical room zone can be recovered and redistributed to other zones when those zones are in heating mode. The building’s east/west orientation indicates that, during the April/May and September/October shoulder seasons, some zones may need heating while others may need cooling. Changing peak occupancy levels may also offer opportunities for heat recovery. Waste energy from the reception area can be applied to other areas of the building if those areas require heat during shoulder seasons (Figure 13). If necessary, waste heat from the cooling-only electrical room zone could also be used to generate or preheat domestic hot water for the building. These factors offer a short payback period on any capital premium that the air-source heat recovery system has over the air-source heat pump system. Building analysis reveals that a VRF heat recovery system would be appropriate for this application.
Accurately Sizing Air-Source Outdoor and Indoor Units
Many factors must be considered before sizing the outdoor and indoor units. Outdoor unit size is based on the actual peak cooling or heating load, whichever is higher. Most VRF manufacturers have selection software that provides detailed information, taking into account correction factors for each specific operation to ensure proper design and sizing of system components. The following examples are provided to show how the software addresses adjustments to system capacity based on factors such as line lengths, ambient temperatures, and connected capacities of indoor units.
In the example, the peak cooling load is approximately 93,797 Btu/h, occurring at 3 pm in August; the peak heating load is 73,995 Btu/h, occurring at 8 am in January. The outdoor unit should be sized based on the peak cooling load of 93,797 Btu/h; thus, one 8 ton outdoor unit with 96,000 Btu/h for cooling and 108,000 Btu/h for heating should be chosen.
The effect of local ambient conditions on system performance also should be considered. The system may have reduced heating output at lower ambient conditions, or may operate in defrost more often than is desired. Designers should include the derating factor to verify that the chosen system will provide the required capacity at the necessary design temperatures. For the example, at the winter ambient design temperature of 16°F, an 8 ton air-cooled outdoor unit’s heating output is derated by a factor of 0.74 (Figure 14).
Thus, 0.74 × 108,000 = 79,920 Btu/h, which fulfills the peak heating load of the building. Additionally, the VRF system’s heating output can be derated based on the maximum refrigerant piping length from the outdoor unit to the farthest indoor unit. This capacity correction factor reflects the compressor energy expended when moving refrigerant through the VRF system. In the example, the maximum refrigerant piping length is 120 ft, so the heating capacity correction factor is 0.98 (Figure 15).
| Design winter ambient = 16°F, Derate factor = 0.74 |
| Refrigerant piping length correction factor at 120 ft = 0.98 |
| Corrected heating capacity = 108,000 × 0.74 × 0.98 = 78,322 Btu/h |
A similar process should be used when confirming the proposed system’s cooling performance. The rated condition temperature for outdoor unit cooling capacity is 95°F. In this example, the summer ambient design temperature is 94°F; therefore, derating is not required (Figure 16).
The system must be derated for refrigerant piping length. In the example, the maximum refrigerant piping length is 120 ft, and, as in the heating calculations, the cooling capacity correction factor is 0.98 (see Figure 15).
| Design summer ambient = 94°F db, Derate factor = 1.00 |
| Refrigerant piping length correction factor at 120 ft = 0.98 |
| Corrected cooling capacity = 96,000 × 0.98 = 94,080 Btu/h |
Designers also must verify that the connected nominal capacity of the indoor units is within the operating parameters of the selected system. VRF heat pump systems can operate with a connected nominal capacity of up to 130% of the outdoor unit nominal capacity. VRF heat recovery systems can operate with a connected nominal capacity of up to 150%, or, for some special applications, up to 200% of the outdoor unit nominal capacity. Connected capacity ratios depend on the system’s ability to meet peak cooling and heating loads; connected capacity ratio is calculated by indoor unit connected nominal capacity divided by outdoor unit nominal capacity.
For the example, the total indoor unit connected capacity is 122,000 Btu/h; the nominal outdoor unit capacity is 96,000 Btu/h: 122,000 Btu/h/96,000 Btu/h = 127%.
The 127% is within the connected capacity allowed for VRF heat recovery systems.
Indoor units are selected for each zone based on style and additional design considerations, such as the following:
Peak cooling and heating capacities
Ratio of sensible to latent cooling load
Air change rate (following ASHRAE Standard 62.1 criteria)
Sound performance criteria
Terminal unit air-side distribution and location restrictions
Ventilation air strategy
Integration with supplemental heating components, if any
For the example, the designer may include different indoor unit styles to satisfy project requirements (Figure 17). In the cooling-only zone (the electrical room), the sensible-to-latent cooling ratio is high; the indoor unit rating must be selected to match the requirements for the space.
Office 1 requires other design considerations:
| Peak cooling load | = | 14.580 Btu/h |
| Peak heating load | = | 15,240 Btu/h |
| Air change rate | = | 4 ach |
| Sound performance criteria | = | NC 35 |
| Ventilation supply | = | 85 cfm (see the Ventilation Air Strategy section) |
The designer could choose a ducted indoor unit with
| Nominal cooling output of 15,000 Btu/h |
| Nominal heating output of 17,000 Btu/h |
| Sound performance rating of NC 30 |
| Nominal airflow rate of 477 to 671 cfm |
Designers can select many different types of ventilation equipment to complement a VRF system. There are three main strategies: direct, integrated, and decoupled. Selection depends on climate, application, and equipment type.
Direct Method
Outdoor air is mixed with return air and conditioned by the VRF indoor unit. The minimum supply air temperature from the ventilation system should be 59 to 63°F, and sufficient mixing should be factored in to enable effective coil performance.
Used for applications in mild to moderate climates, and/or situations requiring small amounts of outdoor air.
Reduces system complexity and initial equipment costs.
Climate or ventilation volume requirements must be treated with caution where outdoor air could increase humidity levels to an unacceptable level in the space. For example, a high volume of outdoor air could result in high humidity levels in a conference room during unoccupied periods when the cooling load is reduced. Note that, to ensure minimum ventilation requirements, the VRF indoor unit fan must run at design fan speed at all times.
Integrated Method
Outdoor air is pretreated by mechanical means such as a 100% outdoor air unit, a DOAS, a heat recovery ventilator (HRV), or an energy recovery ventilator (ERV) before being supplied to the VRF indoor unit through the return air or supply ductwork.
Allows the dedicated ventilation system to handle all or part of the outdoor air load. The VRF indoor unit is sized for the internal space load, and possibly part of the outdoor air load.
Used for applications in moderate to extreme climates.
VRF indoor unit provides final tempering of the mixed airstream, and should be sized accordingly.
Allows reduced overall VRF equipment capacity and increased application flexibility.
Maintains ventilation air quantity by indoor unit fan operation.
Decoupled Method
Ventilation air is supplied directly to the conditioned space. Both a decoupled dedicated ventilation system, such as a DOAS, and a VRF system can be installed. The function of the VRF system is to maintain comfort in the conditioned space.
Allows the dedicated ventilation system to handle the entire outdoor air load. The VRF system is sized only for the internal space load.
Used for applications in any type of climate, and situations requiring any amount of outdoor air.
Can introduce large amounts of outdoor air as needed. The VRF indoor unit fan can be programmed to cycle on/off based on heating and cooling requirements, regardless of ventilation demands, thus increasing system efficiency.
Allows reduced VRF equipment capacity, and increases application flexibility.
DOAS system must be designed properly so that incoming outdoor air does not cause short-circuiting issues with return air of the VRF indoor units, or influence any temperature sensors. The supply temperature of the ventilation system should be carefully controlled to limit cold and hot drafts.
Other Considerations
Verify that the selected indoor unit type can handle the required amount of outdoor air, taking into account latent and sensible loads, and mixed-air wet-bulb temperatures.
Location of the space temperature sensors must be considered. Most VRF indoor units can be factory configured to measure space temperature from their respective return air sensors. Integrating outdoor air with the indoor unit can affect this temperature measurement and influence operation, possibly by overcooling or overheating the space. In this situation, a temperature sensor, such as a remote temperature sensor or a sensor located in the VRF system local controller, could be used to establish the actual space temperature.
Each VRF manufacturer recommends different refrigerant piping sizes and maximum to minimum vertical and horizontal lengths, based on refrigerant volumes and velocities required for efficient and stable system operation. Refer to manufacturer guidelines for specific details and industry and local codes for compliance. System refrigerant charge is a calculated value, whereas additional charge is determined by liquid-line volume.
Manufacturer-specific design software provides detailed refrigerant piping specifications and parameters for each project and application, such as
Refrigerant liquid and gas piping sizes
System design verification based on maximum height and length differences
System design verification based on the ratio of indoor unit to outdoor unit nominal capacity
Equipment bill of materials/quantities, including system refrigerant piping and charge
Project numbering and product specifications
Control and power schematics
Refrigerant Piping Guidelines
Refrigerant piping should be carefully considered, taking into account applicable codes and using risk management strategies. Many national, state, and local building codes require compliance with ASHRAE Standard 15 and/or ISO Standard 5149 in the design, construction, and installation o f refrigerant piping. It is necessary to follow national, state, and local building codes and work with the local authority having jurisdiction (AHJ) to ensure best practice. Considerations include the following:
Inspection: keep site-installed pipe joints exposed to view until all pressure and vacuum tests are completed and passed.
Ventilated spaces
Know the refrigerant concentration limit (RCL) and how it applies to each occupied space.
Know how much refrigerant is in the system in case a leak were to occur.
Evaluate connected spaces beyond the zone and connected ductwork:
Plenums: determine whether the space above the ceiling is part of the supply or return system.
Closures: if an indoor unit supplies multiple spaces and uses dampers, confirm the minimum open position.
Transfer openings: determine whether there is a transfer duct, transfer grill, undercut door, or other permanent opening to an adjoining space.
Location of piping and refrigerant bearing components: know where refrigerant may come from if a leak were to occur.
Determine whether the VRF indoor unit coil is in the space.
Determine whether refrigerant piping is exposed or in a connected space.
Determine whether refrigerant piping is enclosed with gastight and fire-resistive material.
Protect refrigerant piping
Exposed piping
Ensure exposed piping is at least 7.25 ft above the floor or is against the ceiling.
Ensure exposed piping is not installed in an enclosed public stairway, stair landing, or means of egress; consider enclosing piping with gastight and fire-resistive material to isolate from such areas.
Shafts and penetrations
Ensure piping is not located inside any elevator, dumbwaiter, or other shaft containing moving objects.
Ensure piping shaft is not open to living quarters or means of egress.
Use riser shafts with proper support between floors.
Use protective sleeves to protect piping from abrasions where it passes through walls, obstructions, or other materials.
VRF manufacturers offer factory-packaged controls that communicate through their system-specific protocol; most use two low-voltage control wires, which must comply with applicable local and national electrical codes. Various individual unit and/or system controllers are available, with the application dictating which controllers need to be installed. Simple controllers include the most basic functions such as operation mode, temperature control, and fan speed. More sophisticated controllers have scheduling, diagnostic functions, and more. Each manufacturer offers centralized controllers, which allow the user to monitor and control VRF systems and ancillary equipment from a single location or through the Internet. Manufacturers also offer open protocol communication gateways for higher-level monitoring using BACnet® or LonWorks®, but special programming may be required.
VRF system controls can be subdivided into
Integral Equipment Controls.
VRF air-source outdoor units, water-source units, heat recovery control units, and indoor units include refrigerant and air-side sensing and control devices, which allow the system to optimize its output (e.g., compressor speed, discharge temperatures, fan speed) based on inputs from a remote device. VRF equipment can function as a stand-alone system based only on local inputs.
Local System Controls.
VRF indoor units can be controlled individually by their own local controllers, with temperature sensing at the return air or local controller, or several indoor units can be grouped together under one local controller (see Figure 6). Each of the grouped indoor units may operate on or off according to the sensed return air temperature, independent of the other indoor units in the group, but all grouped indoor units will be in the same mode (heating or cooling) to provide air conditioning. Local system controls can include functions such as local set-point control, scheduling and setback capability, cooling/heating/auto modes, and indoor unit fan speed control. Depending on the maximum number of zones served by the local controller and on other factors, additional operation features may be included.
Central System Control.
Central control interfaces for VRF systems allow users to monitor and optimize the operation of multiple zones, including any decentralized compatible energy recovery ventilators (see Figure 6). This level of control offers added functionality over local controllers such as seasonal scheduling, remote monitoring and diagnostics, ability to integrate building plans and schematics, and system energy management such as sliding temperature control, optimized start-up control, and setback capabilities. See manufacturer guidelines for specific details. Many of these controls can allow users remote access to operate, monitor, and optimize the VRF system as well as ancillary devices or equipment (e.g., lighting, ventilation, third-party HVAC equipment) without requiring a building-based automation or management network. Access can typically be secured through web-based access licenses or other manufacturer-specific software tools (see Figure 6).
Gateway Control to Integrate with Open Protocol Systems.
Open protocol communication gateways allow higher-level monitoring and basic control of set points, fan speeds, mode, etc., via LonWorks or BACnet. Information may be used by the building management system to control other ancillaries such as lighting.
Safety Considerations for Refrigerants
As with any HVAC equipment, VRF systems must include design and application safeguards that protect occupants. Two standards provide the appropriate information for the design, construction, testing, installation, operation, and inspection of mechanical refrigeration systems: ASHRAE Standard 15 and ISO Standard 5149 (which takes a dynamic approach to design of refrigerant systems). It is necessary to follow national, state, and local building codes and work with the local AHJ to ensure best practice.
Designers also need to refer to ASHRAE Standard 34, which lists the most current information related to refrigerant designations, safety classifications, and refrigerant concentration limits (RCLs). ASHRAE Standard 34 refers to common names of refrigerants used in HVAC systems, instead of using the chemical name, formula, or trade name. The standard establishes a uniform system for assigning reference numbers and safety classifications to refrigerants (including blends).
To successfully apply refrigerant safety requirements to a project, the designer must know the following:
Classification and RCL of refrigerant used
Classification of occupancy type in which indoor unit and/or piping will be located
Total amount of refrigerant used in the system
Individual occupied zone(s) geometry and connected zones, if applicable
Methodology to calculate the maximum amount of refrigerant that can be safely dispersed into a specific zone
The smallest space in which any of the indoor units or piping could be located must be capable of safely dispersing the refrigerant charge of the entire VRF system in the unlikely event of a catastrophic leak or failure. Examples of spaces that may require additional consideration include; bathrooms, small offices or means of egress. It is recommended that the designer use a “fault tree analysis” similar to the following to evaluate the HVAC systems.
A fault tree analysis of the installed HVAC systems should be completed to evaluate the placement of system components to minimize the potential for refrigerant leaks into the conditioned space. When requested, copies of the fault tree analysis should be provided to the AHJ.
The following items serve as a starting point for the fault tree analysis to ensure that all factors are considered to minimize the potential for a refrigerant leak into the conditioned space (Note: ASHRAE Standard 15 does not define a leak rate, but ISO Standard 5149 defines a leak rate of 22 lb/h in Note 1 of Appendix A under paragraph A.5, “Alternative for risk management of refrigerating systems in occupied spaces.”):
Identify system components that are in the conditioned space.
Identify refrigerant piping that is in the conditioned space.
Identify the smallest occupied space in each HVAC system area and show compliance with the RCL of the refrigerant in use.
Identify connecting spaces and list the dimensions of the opening between the spaces and the air movement that achieves compliance with the RCL.
Identify the worst-case refrigerant leak scenario for each system.
Several options are available to manage smaller spaces; however, care is needed not to violate other local or national codes such as NFPA Standard 70. Options available to manage smaller spaces where the RCL would otherwise be exceeded include the following:
If cooling is required in the occupied space, one option is to increase the actual space volume by providing a permanent opening or connecting to an adjacent room, as described in ASHRAE Standard 15. A permanent opening can be included along the common wall between an electrical room and janitor closet to increase the size of the space; alternatively, install the ceiling high enough to provide the necessary volume, or omit the ceiling entirely.
A ducted indoor unit could serve several smaller offices, thus increasing the overall occupied space served by the system.
Central VRF systems can be subdivided into a series of smaller systems so that the total charge in a given system does not exceed the RCL limitations for a given space.
A dedicated system could serve the smaller space(s) so the total charge does not exceed the RCL limitations for a given space.
Do not install an indoor unit, but allow the code-required ventilation to maintain conditions in the space.
In summary, complying with ASHRAE Standard 15 and/or ISO Standard 5149 may only require simple adjustments to the project’s design: carefully considering the building’s zones, determining connected spaces, and optimally placing the piping and indoor units. With sound engineering practices, a VRF system can be designed to comply with all refrigerant safety requirements and other applicable code requirements.
Optimizing VRF Systems to Minimize Environmental Impact
VRF systems include features that make them highly efficient, and that should be applied effectively to optimize system performance and support sustainability. The part-load capabilities of VRF systems, along with their modular design, zoned approach, heat recovery operation (on some systems), and use of variable-frequency-drive (VFD) compressors, provide comfort conditioning while being optimized to use less energy. VRF systems use industry-accepted refrigerants chosen for their performance and adherence to global protocols. Depending on design outdoor air conditions, building heating loads, and capabilities of the VRF system, the heat pump cycle alone may provide enough heating without adding electric resistance heat.
There has been an increased desire for buildings to be sustainable and energy efficient, and several rating systems and documentation requirements are available that can lead to a “green” building certification. Examples include the Leadership in Energy and Environmental Design (LEED®) certification program developed by the U.S. Green Building Council (USGBC), and the National Green Building Certification developed by National Association of Home Builders (NAHB) in partnership with the International Code Council. These rating systems focus on efficient use of several resources (e.g., water, energy, materials) and promote certain criteria such as an appropriately ventilated indoor environment.
VRF system design has the largest effect on energy use for LEED certification, and may help earn points in the following categories:
Correct sizing.
System control: VRF system operations can be controlled centrally through a web-based portal.
Proper maintenance.
Correct installation.
Maximizing heat recovery potential.
Zone control and energy performance optimization: VRF system operations such as airflow direction control, fan speed, and temperature set points can be controlled through a wall-mounted local remote controller, or centrally through web-based control. Many VRF systems use an inverter-driven compressor, feature simultaneous heating and cooling operation, and include an integrated control system that allows scheduling of equipment in each room. An energy recovery ventilator (ERV) can be installed to further reduce energy usage.
Commissioning: a VRF controls network assists building commissioning by allowing easy testing, setting, and adjusting of the HVAC system.
Measurement and verification: energy savings can be estimated using building energy modeling software, and comparing the building design with a baseline as defined by ASHRAE Standard 90.1. Some VRF system manufacturers offer software or integration to building management systems for ongoing accountability and optimization of building energy consumption, and for monitoring and logging energy consumption, heat recovery cycles, static pressure, and ventilation air volumes. Actual energy usage data can be compared to the model.
VRF systems can also help obtain points for indoor air quality (IAQ):
Some VRF systems can meet minimum outdoor air requirements through ventilation connections of the indoor units.
In applications where more outdoor air is required, an ERV can be installed; when used with adequate air distribution from ducted units, this can increase ventilation rates above ASHRAE Standard 62.1 requirements.
In a construction IAQ management plan, the ERV can be used to flush the building before occupancy.
For indoor chemical and pollutant source control, many VRF system indoor evaporator units can be installed with a filter (consult a designer to ensure adequate static pressure is available to provide desired airflow performance). An ERV can also be integrated with a sensor to monitor CO2 levels, and then operate accordingly.
Effective commissioning of a VRF system is fundamental to future system performance (e.g., space comfort, operating efficiency, expected life cycle). The installed VRF system should be thoroughly pressure and vacuum tested before joints are insulated or closed in the wall, to identify leaks or other system related issues. Should system defects be identified, they must be resolved before the commissioning process can be completed. This resolution may involve repurging the lines with nitrogen, rebrazing piping connections, and/or reassembling flared joints, etc.
The VRF system should then be thoroughly evacuated to remove all air and moisture. Evacuation can also identify leaks that do not show up during pressure testing. Evacuation can take several days to effectively implement, especially if the system is large or contains a significant amount of moisture.
Accurately establishing and verifying the design system refrigerant charge is critical. Manufacturers piping design software typically provides the contractor with an additional system charge calculation based on liquid pipe length and diameter. Verification of total charge requirements based on the installed system parameters and via manual calculations as directed in equipment installation and operating documentation is recommended. Under- or overcharging can result in performance issues.
Because standard VRF systems are equipped with comprehensive diagnostic tools, the manufacturer’s full commissioning procedure must be carried out to obtain full benefit and verify that the complete system is operating correctly in all modes. Detailed commissioning checklists should be completed to demonstrate that the procedure has been followed, and to record the data for future reference.