CHAPTER 14 CONDENSER WATER SYSTEMS

 

AS part of the vapor-compression cycle for mechanical refrigera- tion, the heat of compression produced must be rejected to complete the refrigeration cycle. Refrigerant systems may be cooled by air or water. In water-cooled systems, water flows through the condenser and is called condenser water. Condenser water systems are classified as (1) once-through systems (e.g., city water, well-water, or lake/groundwater systems), or (2) recirculating or cooling tower systems. This chapter focuses on open condenser water systems and evaporative coolers; for information on closed-loop systems used in ground-source heat pump loops, see Chapter 49 of this volume and Chapter 35 of the 2019 ASHRAE Handbook—HVAC Applications

1. ONCE-THROUGH CITY WATER SYSTEMS

Once-through city water systems use water from the city’s potable water supply and circulate through the refrigeration equipment condenser (e.g., walk-in cooler, computer room unit) to reject heat and discharge water directly to the sewer. Many municipalities prohibit this type of direct water cooling because of water conservation restrictions, although some localities allow its use as a standby or emergency condenser water system for critical refrigeration needs such as for computer rooms, research laboratories, or critical operating room or life support machinery. In addition, standards such as ASHRAE Standard 189.1 do not allow once-through city water for heat rejection. If city water is allowed for condenser water purposes, then allowed flow may be limited to less than 0.2 gpm per ton. The designer should contact the local water department to determine the viability of this system.

Figure 1 shows a water-cooled condenser using city water. The return (leaving water) piping is routed at a higher elevation than the condenser so that the condenser is always full of water. Water flow through the condenser is regulated by a control valve in the supply or discharge line, usually actuated from condenser head pressure to (1) maintain a constant condensing temperature with load variations and (2) close when the refrigeration compressor turns off. City water systems should always include approved backflow prevention devices and open (air gap) drains. When more than one condenser is used on the same circuit, use individual control valves.

Condenser Connections for Once-Through City Water System

Figure 1. Condenser Connections for Once-Through City Water System


Piping materials for these systems are generally nonferrous, usually copper but sometimes high-pressure plastic, because corrosion-protective chemicals cannot be used. Scaling can be a problem with higher-temperature condensing surfaces when the water has a relatively high calcium content. In these applications, use mechanically cleanable straight tubes in the condenser.

Piping should be sized according to the principles outlined in Chapter 22 of the 2017 ASHRAE Handbook—Fundamentals with velocities of 5 to 10 fps for design flow rates. A pump is usually not required where city water is used. Well water can be used in lieu of city water, connected on the service side of the pumping/pressure control system. Because most well water has high calcium content, scaling on the condenser surfaces can be a problem.

Another once-through system uses lake or river water. Although these systems eliminate the need for a cooling tower, they require particular attention to filtering out sediment, particulates, and other materials that could foul the system. In the United States, special permitting is required from the local Department of Natural Resources (DNR) and the Environmental Protection Agency (EPA). Particular attention must be paid to the design of intake structures and keeping the velocity below 0.5 fps so as not to intake aquatic wildlife. Local disturbances or seasonal weather conditions can cause lake or river water elevations to fluctuate, so ensure that the system uses proper safeguards or vacuum priming systems as required.

2. OPEN COOLING TOWER SYSTEMS

Open systems have at least two points of interface between the system water and the atmosphere; they require a different approach to hydraulic design, pump selection, and sizing than do closed hot-and chilled-water systems. Some heat conservation systems rely on a split condenser heating system that includes a two-section condenser. One section of the condenser supplies heat for closed-circuit heating or reheat systems; the other section serves as a heat rejection circuit, which is an open system connected to a cooling tower (see Chapter 40).

In selecting a pump for a cooling tower/condenser water system, consider the static head and the system friction loss. The pump inlet must have an adequate net positive suction head (see Chapter 40). In addition, continuous contact with air introduces oxygen into the water and concentrates minerals that can cause scale and corrosion on a continuing basis. Fouling factors and an increased pressure drop caused by aging of the piping must be taken into account in the condenser piping system design (see Chapter 22 of the 2017 ASHRAE Handbook—Fundamentals). Corrosion and erosion are not just limited to condenser water piping: the chiller condenser water bundle sees the same water. It is not uncommon to coat the condenser water box with epoxy paint or other material to prolong its life. Similarly, adding nylon tube inserts extends the life of the tube ends at the tube sheet walls.

The required water flow rate depends on the refrigeration unit used and on the temperature of the available condenser water. Cooling tower water is available for return to the condenser at a temperature several degrees above the design wet-bulb temperature, depending on tower performance. An approach of 7°F to the design wet-bulb temperature is frequently considered an economically sound design. In city, lake, river, or well water systems, the maximum water temperature that occurs during the operating season must be used for equipment selection and design flow rates and temperature ranges.

The required flow rate through a condenser may be determined with manufacturers’ performance data for various condensing temperatures and capacities. With air-conditioning refrigeration applications, a return or leaving condenser water temperature of 95°F has been standard practice. If economic feasibility analyses can justify it, higher leaving-water temperatures (and lower condenser flow rates) may be beneficial to the chilled-water system.

Figure 2 shows a typical cooling tower system for a refrigerant condenser. Water flows to the pump from the tower basin or sump and is discharged under pressure to the condenser and then back to the tower. When it is desirable to control condenser water temperature or maintain it above a predetermined minimum, water is diverted through a control valve directly back to the tower basin. (preferred method). The alternative bypass option shown in Figure 2 is not recommended because it does not keep the basin water circulating and warm, and thus allows possible freezing of water in the basin and exposed piping, even if the piping is insulated and the basin heated. Full flow is desired in the bypass piping, because reduced flow may increase the risk of freezing.

Cooling Tower Piping System

Figure 2. Cooling Tower Piping System


Piping from the tower sump to the pump requires some precautions because, at this point, the water is basically flowing due to gravity. The sump level should be above the top of the pump casing for positive prime, and piping pressure drop should be minimized such that there is always adequate net positive suction head (NPSH) on the pump. Not having adequate NPSH leads to pump cavitation and potential damage to the pump impeller, thereby requiring close attention, accurate head calculation, and appropriate pump selections, as discussed in the following sections. All piping must pitch up to the tower basin, if possible, to eliminate air pockets. It is not unusual to have this piping a diameter or two larger than the pump discharge or pressurized piping.

If used, suction strainers should be equipped with inlet and outlet gages to indicate through excessive pressure drop when cleaning is required. In-line pipe strainers are not recommended for cooling tower systems because they tend to become blocked and turn into a reliability problem in themselves. Many designers depend on large mesh screens in the tower sump and condenser heads designed with settling basins to remove particulate matter. If a strainer is deemed necessary, two-large capacity basket strainers, installed in parallel such that they can be alternately put into service and valved out for cleaning, are recommended.

 Air and Vapor Precautions

Both vapor and air can create serious problems in open cooling tower systems. Water vaporizes in the pump impeller if adequate net positive suction head is not available. When this occurs, the pump loses capacity, and serious damage to the impeller can result. Equally damaging vaporization can occur in other portions of the system where pressure in the pipe can drop below the vapor pressure at the operating water temperature. On shutdown, these very low pressures can result from a combination of static pressure and momentum. Vaporization is often followed by an implosion, which causes destructive water hammer. To avoid this problem, keep all sections of the piping system except the return line to the upper tower basin below the basin level. When this cannot be achieved, perform a thorough dynamic analysis of the piping system for all operating conditions; a soft start and stop control such as a variable-frequency drive on the pump motor is recommended as an additional precaution, and all actuated control valves should be slow closing.

Air release is another characteristic of open condenser water systems that must be addressed. Because the water/air solution in the tower basin is saturated at atmospheric pressure and cold-water basin temperature, the system should be designed to maintain the pressure at all points in the system sufficiently above atmospheric that no air will be released in the condenser or in the piping system (see Figures 2 and 3 in Chapter 13).

Another cause of air in the piping system is vortexing at the tower basin outlet. This can be avoided by ensuring that the maximum flow does not exceed that recommended by the tower manufacturer. Release of air in condenser water systems is the major cause of corrosion, and it causes decreased pump flow (similar to cavitation), water flow restrictions in some piping sections, and possible water hammer. Antivortexing devices can be added to the piping to mitigate this occurrence. These features often are available on strainers and suction diffusers.

 Pump Selection and Pressure Calculations

The elements of required pump head are illustrated in Figure 3. Because there is an equal head of water between the level in the tower sump or interior reservoir and the pump on both the suction and discharge sides, these static heads cancel each other and can be disregarded.

Schematic Piping Layout Showing Static and Suction Head

Figure 3. Schematic Piping Layout Showing Static and Suction Head


The elements of pump head are (1) static head from tower sump or interior reservoir level to the tower header, (2) friction loss in suction and discharge piping, (3) pressure loss in the condenser, (4) pressure loss in the control valves, (5) pressure loss in the strainer, and (6) pressure loss in the tower nozzles, if used. Added together, these elements determine the required pump total dynamic head.

Normally, piping is sized for water velocities between 5 and 12 fps. As stated previously, piping on the discharge of the pump may see the higher velocities, and piping on the suction side should see the lower velocities. Refer to Chapter 22 of the 2017 ASHRAE Handbook—Fundamentals for piping system pressure losses. Friction factors for 15-year-old pipe are commonly used. Manufacturers’ data contain pressure drops for the condenser, cooling tower, control valves, and strainers.

If multiple cooling towers are to be connected, the piping should be designed so that the pressure loss from the tower to the pump suction is exactly equal for each tower. The basin water operating level should physically be at the same elevation, or the lower basin could overflow. Additionally, large equalizing lines or a common reservoir can be used to ensure this. However, for reliability, redundancy, and ease of maintenance, multiple basins are often preferred.

Evaporation in a cooling tower concentrates the dissolved solids in the circulating water. This concentration can be limited by discharging a portion of the water as overflow or blowdown, either by discharging or bleeding a continuous stream of water, or by using a conductivity sensor to activate blowdown valves in the system. An estimate of the bleed rate should equal the amount of evaporation occurring in the tower.

Makeup water is required to replace water lost by evaporation, blowdown, and drift. Automatic float valves or level controllers are usually installed to maintain a constant water level. If float valves are used, the control system should be tuned to desensitize the readings from turbulent, foaming water in the cooling tower basin. If a reservoir is used, the level devices may be installed in a “stilling” tube to read less-turbulent water levels.

 Water Treatment

Water treatment is necessary to prevent scaling, corrosion, and biological fouling of the condenser and circulating system. The extent and nature of the treatment depends on the chemistry of the available water and on the system design characteristics. On large systems, fixed continuous-feeding chemical treatment systems are frequently installed in which chemicals, including acids for pH control, must be diluted and blended and then pumped into the condenser water system. Corrosion-resistant materials may be required for surfaces that come in contact with these chemicals. In piping system design, provisions for feeding the chemicals, blowdowns, drains, and testing must be included. Because cooling towers move great quantities of air and the water flow acts as an air washer, towers can introduce a great deal of airborne particulate into the basin and condenser water system. Therefore, side-stream filtration with separate pumping systems is recommended. For further information on water treatment, refer to Chapter 40 of this volume and Chapter 50 of the 2019 ASHRAE Handbook—HVAC Applications

 Freeze Protection and Winter Operation

Outdoor piping must be protected (insulated and heat traced) or drained when a tower operates intermittently during cold weather. The most satisfactory arrangement is to provide an indoor reservoir tank into which the cold-water basin drains by gravity, as shown in Figure 4A. The makeup, overflow, and pump suction lines are then connected to the indoor reservoir tank rather than to the tower basin. This arrangement may also use vertical turbine pumps that save floor space compared to a base-mounted centrifugal pump. The indoor basin also serves as a settling basin for any waterborne particulate; thus, the basin should be drained or cleaned annually to avoid biological growth and potential fouling of the chiller’s condenser surfaces. If the system is small, many cooling tower manufacturers have remote sump tanks as an option.

Cooling Tower Piping to Avoid Freeze-Up

Figure 4. Cooling Tower Piping to Avoid Freeze-Up


Size the reservoir or sump for the entire system water volume that drains back into the sump when the pumps deenergize. A common rule of thumb is to add the volume of water required if the condenser water pumps were to run for 3 min as a minimum level to have enough water to prime the piping system. The reservoirs should have high- and low-water alarms and makeup water level controls. Also consider the pump suction requirements to prevent vortexing to determine the depth. Because the pipe entering the sump also may contain great quantities of air, the sump should have a vent or open grate of adequate size.

For winter operation, consider using a condenser water bypass directly to the reservoir to prevent water that is too cold entering the condenser. Never operate a cooling tower in the winter without a heat load. If the tower has variable-frequency drives (VFDs), they should be modulated to keep the water temperature above freezing. Fan reversal for several minutes can be used for deicing, but must be discussed with the tower manufacturer to determine any limitations.

A control sequence for the piping arrangement of Figure 4A with rising water temperature would be as follows:

  • A temperature sensor measures the temperature of water leaving the indoor sump.

  • As the temperature starts to rise, the diverting valve begins directing some of the water over the tower.

  • After the water is in full flow over the tower and the temperature continues to rise above set point, the fan is started on low speed, with the speed increasing until the water temperature reaches set point.

  • With falling water temperature, the opposite sequence occurs.

Tower basin heaters or heat exchangers connected across the supply and return line to the tower can also be selected. Steam or electric basin heaters are most commonly used. An arrangement incorporating an indoor heater is shown in Figure 4B.

3. LOW-TEMPERATURE (WATER ECONOMIZER) SYSTEMS

When open cooling tower systems are used for generating chilled water directly, through an indirect heat exchanger such as a plate frame heat exchanger, or with a chiller thermocycle circuit, the bulk water temperature is such that icing can occur on or within the cooling tower, with destructive effects. The piping circuit precautions are similar to those described in the section on Open Cooling Tower Systems, but they are much more critical. For precautions in protecting cooling towers from icing damage, see Chapter 40.

Water from open cooling tower systems should not be piped directly through cooling coils, unitary heat pump condensers, or plate-frame heat exchangers unless the water is first filtered through a high-efficiency filtering system and the water treatment system is managed carefully to minimize the dissolved solids. Even with these precautions, cooling coils should have straight tubes arranged for visual inspection and mechanical cleaning, unitary heat pumps should be installed for easy removal and replacement, and plate frame heat exchangers should be installed for ready accessibility for disassembly and cleaning.

ASHRAE Standard 90.1-2016 recommends an integrated or series configuration for water-side (fluid) economizers in chilled-water systems. Taylor (2014) is a good resource for fluid economizer designs.

4. CLOSED-CIRCUIT EVAPORATIVE COOLERS

Because of the potential for damaging freezing of cooling towers, some designers prefer to use closed-circuit evaporative/dry coolers for water economizer chilled-water systems. One of the many different configurations of these systems is shown in Figure 5. The open water is simply recirculated from the basin to the sprays of the evaporative cooler, and the cooling water system is a closed hydronic system usually using a glycol/water mixture for freeze protection (see Chapter 39). The open water system is then drained in freezing weather and the cooling heat exchanger unit is operated as a dry heat exchanger. This type of system in some configurations can be used to generate chilled water through the plate-frame heat exchanger shown or to remove heat from a closed heat pump circuit. The glycol circuit is generally not used directly either for building cooling or for the heat pump circuit because of the economic penalty of the glycol system. The closed circuit is designed in accordance with the principles and procedures described in Chapter 13.

Closed-Circuit Evaporative Cooler System

Figure 5. Closed-Circuit Evaporative Cooler System


5. OTHER SOURCES OF WATER

Often, potable water for cooling tower makeup is unavailable or too expensive to use, such as in the arid areas of the Middle East. Other fluids available for use in cooling towers include treated sewage effluent (TSE) and sea water. Both fluids require additional investigation of their effects on chiller condenser and cooling tower surfaces, because of increased fouling and corrosivity. When using either TSE or sea water, chiller condenser tubes are typically titanium or stainless steel and cooling tower fill is generally modified to a thicker material with stainless steel fasteners and noncorrosive materials such as pultruded glass fiber. Consult the cooling tower and chiller vendors early in design for design direction, efficiency, and cost implications.

6. OVERPRESSURE CAUSED BY THERMAL FLUID EXPANSION

When open condenser water systems are used at low temperatures for winter cooling, special precautions should be taken to prevent damaging overpressurization caused by thermal expansion. This phenomenon has been known to cause severe damage when a section of piping containing water at a lower temperature than the surrounding space is isolated while cold. This isolation could be intentional, such as isolation by two service valves, or it could be as subtle as a section of piping isolated between a check valve and a control valve. If such an isolation occurs when water at 45°F is in a 1 in. pipe passing through a 75°F space, Figure 41 in Chapter 13 reveals that the pressure would increase by 815 psi, which would be destructive to many components of most condenser water systems. Refer to the section on Other Design Considerations in Chapter 13 for a discussion of this phenomenon.

BIBLIOGRAPHY

ASHRAE members can access ASHRAE Journal articles and ASHRAE research project final reports at technologyportal.ashrae.org. Articles and reports are also available for purchase by nonmembers in the online ASHRAE Bookstore at www.ashrae.org/bookstore.

ASHRAE. 2016. Energy standard for buildings except low-rise residential buildings. ANSI/ASHRAE/IES Standard 90.1-2016.

Baltimore Aircoil Company. 2005. Product & application handbook, vol. 1. Baltimore Aircoil Company, Baltimore.

ASHRAE. 2013. District cooling guide.

Hensley, J.C., ed. 1998. Cooling tower fundamentals. Marley Cooling Tower, Overland Park, KS.

Lindahl, P. 2014. Cold weather operation of cooling towers. ASHRAE Journal 56(3).

Schwedler, M. 1998. Take it to the limit... or just halfway? ASHRAE Journal 40(7).

Schwedler, M., and B. Bakkum. 2009. Upgrading chilled water systems. ASHRAE Journal 51(11).

Taylor, S. 2011. Optimizing design and control of chilled water plants, part 1: Chilled water distribution system selection. ASHRAE Journal 53(7).

Taylor, S. 2014. Engineer’s notebook: How to design and control waterside economizers. ASHRAE Journal 56(5).



The preparation of this chapter is assigned to TC 6.1, Hydronic and Steam Equipment and Systems.