Active panel surface coverings like carpets and pads on the floor can have a pronounced effect on a panel system’s performance. The added thermal resistance rc reduces the panel surface heat flux. To reestablish the required performance, the water temperature must be increased (decreased in cooling). Thermal resistance of a panel covering is
If there are covered and bare floor panels in the same hydronic system, it may be possible to maintain a sufficiently high water temperature to satisfy the covered panels and balance the system by throttling the flow to the bare slabs. In some instances, however, the increased water temperature required when carpeting is applied over floor panels makes it impossible to balance floor panel systems in which only some rooms have carpeting unless the piping is arranged to permit zoning using more than one water temperature.
Either hydronic or electric circuits control the active panel surface temperature. The required effective surface temperature tp necessary to maintain a combined heat flux q (where q = qr + qc) at steady-state design conditions can be calculated by using applicable heat flux equations for qr and qc, depending on the position of the panel. At a given ta, AUST must be predicted first. Figures 9 and 10 can also be used to find tp when q and AUST are known. The next step is to determine the required average water (brine) temperature tw in a hydronic system. It depends primarily on tp, tube spacing M, and the characteristic panel thermal resistance ru. Figure 9 provides design information for heating and cooling panels, positioned either at the ceiling or on the floor.
The combined heat flux for ceiling and floor panels can be read directly from Figure 9. Here qu is the combined heat flux on the floor panel and qd is the combined heat flux on the ceiling panel. For an electric heating system, tw scales correspond to the skin temperature of the cable. The following algorithm (TSI 1994) may also be used to design and analyze panels under steady-state conditions:
where
|
td
|
=
|
average skin temperature of tubing (electric cable), °C
|
|
q
|
=
|
combined heat flux on panel surface, W/m2
|
|
ta
|
=
|
dry-bulb indoor air design temperature, °C. In floor-heated or ceiling-cooled indoor spaces that have large fenestration, ta may be replaced with AUST.
|
|
Do
|
=
|
outside diameter of embedded tube or characteristic contact width of attached heating or cooling element with panel (see Table 1), m
|
|
M
|
=
|
on-center spacing of adjacent tubes (electric cables), m
|
|
2W
|
=
|
net spacing between tubing (electric cables), M – Do, m
|
|
η
|
=
|
fin efficiency, dimensionless
|
The first two terms in Equation (23) give the maximum (minimum in cooling) value of the panel surface temperature profile; consequently, if tube spacing M is too large, hot strips along the panel surface may occur in heating, or local condensation occur on these cold strips in sensible cooling mode.
The following equation, which includes transverse heat diffusion in the panel and surface covers, may be used to calculate the fin coefficient f:
where
|
f
|
=
|
fin coefficient
|
|
m
|
=
|
2 + rc/2rp
|
|
n
|
=
|
total number of different material layers, including panel and surface covers
|
|
xi
|
=
|
characteristic thickness of each material layer i, m
|
|
ki
|
=
|
thermal conductivity of each layer i, W/(m · K)
|
For a hydronic system, the required average water (brine) temperature is
where qb is the flux of back and perimeter heat losses (positive) in a heated panel or gains (negative) in a cooling panel.
This algorithm may be applied to outdoor slab heating systems, provided that the combined heat flux q is calculated according to Chapter 51 in the 2015 ASHRAE Handbook—HVAC Applications, with the following conditions: no snow, no evaporation, q (in panel heating) = qh (radiation and convection heat flux in snow-melting calculations). With a careful approach, outdoor slab cooling systems may be analyzed by incorporating the solar radiation gain, thermal radiation, and forced convection from the sky and ambient air.
ISO Standard 18566-2014 provides an in-depth description of the design, installation, and control of radiant panels.
Figure 9 may also be used for panels with tubing not embedded in the panel:
-
xp = 0 if tubes are externally attached.
-
In spring-clipped external tubing, Di = 0 and Do is the clip thickness.
Warm air and electric heating elements are two design concepts influenced by local factors. The warm-air system has a special cavity construction where air is supplied to a cavity behind or under the panel surface. The air leaves the cavity through a normal diffuser arrangement and is supplied to the indoor space. Generally, these systems are used as floor panels in schools and in floors subject to extreme cold, such as in an overhang. Cold outdoor temperatures and heating medium temperatures must be analyzed with regard to potential damage to the building construction. Electric heating elements embedded in the floor or ceiling construction and unitized electric ceiling panels are used in various applications to provide both full heating and spot heating of the space.
Residential heating applications usually consist of tubes or electric elements embedded in masonry floors or plaster ceilings. This construction is suitable where loads are stable and building design minimizes solar effects. However, in buildings where fenestration is large and thermal loads change abruptly, the slow response, thermal lag, and override effect of masonry panels are unsatisfactory. Metal ceiling panels with low thermal mass respond quickly to load changes (Berglund et al. 1982).
Panels are preferably located in the ceiling because it is exposed to all other indoor surfaces, occupants, and objects in the conditioned indoor space. It is not likely to be covered, as floors are, and higher surface temperatures can be maintained. Figure 10 gives design data for ceiling and wall panels with effective surface temperatures up to 140°C.
Example 1.
An in-slab, on-grade panel (see Figure 20) will be used for both heating and cooling. M = 300 mm, ru = 0.09 (m2 · K)/W, and rc/rp is less than 4. ta is 20°C in winter and 4.5°C in summer.
AUST is expected to be 1 K less than ta in winter heating and 0.5 K higher than ta in summer cooling.
What is the average water temperature and effective floor temperature (1) for winter heating when qu = 130 W/m2, and (2) for summer cooling when –qu = 50 W/m2?
Solution:
Winter heating
To obtain the average water temperature using Figure 9, start on the left axis where qu = 130 W/m2. Proceed right to the intersect ru = 0.09 and then down to the M = 300 mm line. The reading is AUST + 31, which is the solid line value because rc/rp < 4. As stated in the initial problem, AUST = ta − 1 or AUST = 20 – 1 = 19°C. Therefore, the average water temperature would be tw = 31 + 19 = 50°C.
To find the effective floor temperature, start at qu = 130 W/m2 in Figure 9 and proceed right to AUST = ta – 1 K. The solid line establishes 12 K as the temperature difference between the panel and the indoor air. Therefore, the effective floor temperature tp = ta + 12 or tp = 20 + 12 = 32°C.
Summer cooling
Using Figure 9, start at the left axis at –qu = 50 W/m2. Proceed to ru = 0.09, and then up (for cooling) to M = 300 mm, which reads ta – 11 or 24.5 – 11 = 13.5°C average water temperature for cooling.
To obtain the effective floor temperature at –qu = 50 W/m2, proceed to AUST – ta = +0.5 K, which reads –5°C. Therefore, the effective floor temperature is 24.5 – 5 = 19.5°C.
Example 2.
An aluminum extrusion panel, which is 0.127 mm thick with heat element spacing of M = 150 mm, is used in the ceiling for heating. If a ceiling heat flux qd of 1260 W/m2 is required to maintain room temperature ta at 20°C, what is the required heating element skin temperature td and effective panel surface temperature tp?
Solution:
Using Figure 10 enter the left axis heat flux qd at 1260 W/m2. Proceed to the line corresponding to ta = 20°C and then move up to the M = 150 mm line. The ceiling heating element temperature td at the intersection point is 160°C. From the bottom axis of Figure 10, the effective panel surface temperature tp is 129°C.
3. RADIANT HEATING AND COOLING SYSTEMS
The following are the most common forms of panels applied in radiant heating and cooling systems:
-
Hydronic ceiling panels
-
Embedded tubing in ceilings, walls, or floors
-
Electric ceiling panels for heating only
-
Electrically heated ceilings or floors
3.1 HYDRONIC CEILING PANELS
Metal ceiling panels can be integrated into a system that heats and cools. In such a system, a source of dehumidified ventilation air is required in summer, so the system is classed as an air-and-water system. Also, various amounts of forced air are supplied year-round. When metal panels are applied for heating only, a ventilation system may be required, depending on local codes.
Ceiling panel systems are an outgrowth of perforated metal, suspended acoustical ceilings. These ceiling panel systems are usually designed into buildings where the suspended acoustical ceiling can be combined with panel heating and cooling. The panels can be designed as small units to fit the building module, which provides extensive flexibility for zoning and control, or the panels can be arranged as large continuous areas for maximum economy. Some ceiling installations require active panels to cover only part of the indoor space and compatible matching acoustical panels for the remaining ceiling area.
Three types of metal ceiling systems are available. The first consists of light aluminum panels, usually 300 by 600 mm, attached in the field to 15 mm galvanized pipe coils. Figure 12 shows a metal ceiling panel system that uses 15 mm pipe laterals on 150, 300, or 600 mm centers, hydraulically connected in a sinuous or parallel-flow welded system. Aluminum ceiling panels are clipped to these pipe laterals and act as a heating panel when warm water is flowing or as a cooling panel when chilled water is flowing.
The second type of panel consists of a copper coil secured to the aluminum face sheet to form a modular panel. Modular panels are available in sizes up to about 910 by 1520 mm and are held in position by various types of ceiling suspension systems, most typically a standard suspended T-bar 600 by 1200 mm exposed grid system. Figure 13 shows metal panels using a copper tube pressed into an aluminum extrusion, although other methods of securing the copper tube have proven equally effective.
Metal ceiling panels can be perforated so that the ceiling becomes sound absorbent when acoustical material is installed on the back of the panels. The acoustical blanket is also required for thermal reasons, so that reverse loss or upward flow of heat from the metal ceiling panels is minimized.
The third type of panel is an aluminum extrusion face sheet with a copper tube mechanically fastened into a channel housing on the back. Extruded panels can be manufactured in almost any shape and size. Extruded aluminum panels are often used as long, narrow panels at the outside wall and are independent of the ceiling system. Panels 380 or 510 mm wide usually satisfy a typical office building’s heating requirements. Lengths up to 6 m are available. Figure 14 shows metal panels using a copper tube pressed into an aluminum extrusion. Some manufacturers also use graphite as a panel material.
Performance data for extruded aluminum panels vary with the copper tube/aluminum contact and test procedures used. Hydronic ceiling panels have a low thermal resistance and respond quickly to changes in space conditions. Table 1 gives thermal resistance values for various ceiling constructions.
Metal ceiling panels can be used with any of the all-air cooling systems described in Chapter 2. Chapters 17 and 18 of the 2017 ASHRAE Handbook—Fundamentals describe how to calculate heating loads. Double-glazing and heavy insulation in outside walls reduce transmission heat losses. As a result, infiltration and reheat have become of greater concern. Additional design considerations include the following:
-
Perimeter radiant heating panels extending not more than 1 m into the indoor space may operate at higher temperatures, as described in the section on Hydronic Panel Systems.
-
Hydronic panels operate efficiently at low temperature and are suitable for condenser water heat reclaim systems.
-
Locate ceiling panels adjacent to the outside wall and as close as possible to the areas of maximum load. The panel area within 1 m of the outside wall should have a heating capacity equal to or greater than 50% of the wall transmission load.
-
Ceiling system designs based on passing return air through perforated modular panels into the plenum space above the ceiling are not recommended because much of this heat is lost to the return air system in heating mode.
-
When selecting heating design temperatures for a ceiling panel surface or average water temperature, the design parameters are as follows:
-
Excessively high temperatures over the occupied zone will cause the occupant to experience a “hot head effect.”
-
Temperatures that are too low can result in an oversized, uneconomical panel and a feeling of coolness at the outside wall.
-
Give ceiling panel location priority.
-
With normal ceiling heights of 2.4 to 2.8 m, panels less than 1 m wide at the outside wall can be designed for 113°C surface temperature. If panels extend beyond 1 m into the indoor space, the panel surface temperature should be limited to the values as given in Figure 15.
-
Allow sufficient space above the ceiling for installation and connection of the piping that forms the panel ceiling.
-
Hydronic ceiling panels provide a fast-response system (Watson et al. 1998).
Metal acoustic panels provide heating, cooling, sound absorption, insulation, and unrestricted access to the plenum space. They are easily maintained, can be repainted to look new, and have a life expectancy in excess of 30 years. The system is quiet, comfortable, draft-free, easy to control, and responsive. The system is a basic air-and-water system.
Metal heating panels, hydronic and electric, are applied to building perimeter spaces for heating in much the same way as finned-tube convectors. They can also be integrated into the ceiling design to provide a narrow band of panel heating around the perimeter of the building. The panel system offers advantages over baseboard or overhead air in appearance, comfort, operating efficiency and cost, maintenance, and product life.
ASHRAE Standard 138 discusses testing and rating of ceiling panels.
3.2 EMBEDDED SYSTEMS WITH TUBING IN CEILINGS, WALLS, OR FLOORS
Layout and design of embedded systems for heating and cooling begin early in the job. The type and location chosen influences the design and, conversely, thermal considerations may dictate which system type to use. ISO Standard 11855-2012 provides an in-depth description of the design, installation, and control of embedded radiant systems. One of the following types of construction is generally used:
-
Pipe or tube is embedded in the lower portion of a concrete slab, generally within 25 mm of its lower surface (Figure 16). If plaster is to be applied to the concrete, the piping may be placed directly on the wood forms. If the slab is to be used without plaster finish, the piping should be installed not less than 20 mm above the undersurface of the slab. The minimum coverage must comply with local building code requirements.
-
Pipe or tube is embedded in a metal lath and plaster ceiling. If the lath is suspended to form a hung ceiling, the lath and heating coils are securely wired to the supporting members so that the lath is below, but in good contact with, the coils. Plaster is then applied to the metal lath, carefully embedding the coil as shown in Figure 17.
-
Smaller-diameter copper or thermoplastic tube is attached to the underside of wire or gypsum lath. Plaster is then applied to the lath to embed the tube, as shown in Figure 18.
-
Other forms of ceiling construction are composition board, wood paneling, etc., with warm-water piping, tube, or channels built into the panel sections.
Coils are usually laid in a sinusoidal pattern, although some header or grid-type coils have been used in ceilings. Coils are typically thermoplastic tube, spaced from 100 to 300 mm on centers, depending on the required heat flux, pipe or tube size, and other factors.
Where plastering is applied to pipe coils, a standard three-coat gypsum plastering specification is followed, with a minimum of 10 mm of cover below the tubes when they are installed below the lath. Generally, the surface temperature of plaster panels should not exceed 50°C, which may be satisfied by limiting the average water temperature to a maximum temperature of 60°C.
Insulation should be placed above the coils to reduce back loss, which is the difference between heat supplied to the coil and net useful heat output to the heated indoor space.
To protect the plaster installation and to ensure proper air drying, heat must not be applied to the panels for two weeks after all plastering work has been completed. When the system is started for the first time, water supplied to the panels should not be more than 10 K above the prevailing indoor air temperature and not in excess of 32°C.
Water should be circulated at this temperature for about two days, and then increased at a rate of about 3 K per day to 60°C.
During the air-drying and preliminary warm-up periods, there should be adequate ventilation to carry moisture from the panels. No paint or paper should be applied to the panels before these periods have been completed or while the panels are being operated. After paint and paper have been applied, an additional shorter warm-up period, similar to first-time starting, is also recommended.
Although piping embedded in walls is not as widely used as floor and ceiling panels, it can be constructed by any of the methods outlined for ceilings or floors. Its design is similar to other hydronic panels [see Equations (22) to (26)]. Equations (5) and (12) give the heat flux at the surface of wall panels.
Interest has increased in floor heating with the introduction of nonmetallic tubing and new design, application, and control techniques. Whichever method is used for optimum floor output and comfort, it is important that heat be evenly distributed over the floor. Spacing is generally 100 to 300 mm on centers for the coils. Wide spacing under tile or bare floors can cause uneven surface temperatures.
Embedded Tubes or Pipes in Concrete Slab.
Thermoplastic, rubber, ferrous, and nonferrous pipes, or composite tubes (e.g., thermoplastic tubes with aluminum sleeves) are used in floor slabs that rest on grade. Hydronic coils are constructed as sinusoidal-continuous coils or arranged as header coils with a spacing of
150 to 450 mm on centers. The coils are generally installed with
40 to 100 mm of cover above them. Insulation is recommended to reduce perimeter and back losses where the outer surface is exposed to the exterior.
Figure 19 shows application of hydronic coils in slabs resting on grade. Coils should be embedded completely and should not rest on an interface. Any supports used for positioning heating coils should be nonabsorbent and inorganic. Reinforcing steel, angle iron, pieces of pipe or stone, or concrete mounds can be used. No wood, brick, concrete block, or similar materials should support coils. A waterproofing layer is desirable to protect insulation and piping.
Where coils are embedded in structural load-supporting slabs above grade, construction codes may affect their position. Otherwise, the coil piping is installed as described for slabs resting on grade.
Embedded systems may fail sometime during their life. Adequate valves and properly labeled drawings help isolate the point of failure.
Suspended Floor Tubing or Piping.
Piping may be applied on or under suspended wood floors using several construction methods. Piping may be attached to the surface of the floor and embedded in a layer of concrete or gypsum, mounted in or below the subfloor, or attached directly to the underside of the subfloor using metal panels to improve heat transfer from the piping. An alternative method is to install insulation with a reflective surface and leave an air gap of
50 to 100 mm to the subfloor. Whichever method is used for optimum floor output and comfort, it is important that heat be evenly distributed throughout the floor. Tubing generally has a spacing of
100 to 300 mm on centers. Wide spacing under tile or bare floors can cause uneven surface temperatures.
Figure 20 depicts construction with piping embedded in concrete or gypsum. The embedding material is generally 25 to 50 mm thick when applied to a wood subfloor. Gypsum products specifically designed for floor heating can generally be installed 25 to 40 mm thick because they are more flexible and crack-resistant than concrete. When concrete is used, it should be of structural quality to reduce cracking caused by movement of the wood frame or shrinkage. The embedding material must provide a hard, flat, smooth surface that can accommodate a variety of floor covers.
As shown in Figure 21, tubing may also be installed in the subfloor. The tubing is installed on top of the rafters between the subflooring members. Heat diffusion and surface temperature can be improved uniformly by adding metal heat transfer plates, which spread heat beneath the finished flooring.
A third construction option is to attach the tube to the underside of the subfloor with or without metal heat transfer plates. The construction is depicted in Figure 22.
Transfer from the hot-water tube to the surface of the floor is the important consideration in all cases. The floor surface temperature affects the actual heat transfer to the space. Any hindrance between the heated water tube and the floor surface reduces system effectiveness. The method that transfers and spreads heat evenly through the subfloor with the least resistance produces the best results.
3.3 ELECTRICALLY HEATED RADIANT SYSTEMS
Several panel systems convert electrical energy to heat, raising the temperature of conditioned indoor surfaces and the indoor air. These systems are classified by the temperature of the heated system. Higher-temperature surfaces require less area to maintain occupant comfort. Surface temperatures are limited by the ability of the materials to maintain their integrity at elevated temperatures. The maximum effective surface temperature of floor panels is limited to what is comfortable to occupants’ feet.
Prefabricated Electric Ceiling Panels.
These panels are available in sizes
300 to 1800 mm wide by 600 to 3600 mm long by 13 to 50 mm thick. They are constructed with metal, glass, or semirigid fiberglass board or vinyl. Heated surface temperatures range from
40 to 150°C, with corresponding heat fluxes ranging from
270 to 1100 W/m2 for 120 to 480 V services.
A panel of gypsum board embedded with insulated resistance wire is also available. It is installed as part of the ceiling or between joists in contact with a ceiling. Heat flux is limited to 240 W/m to maintain the board’s integrity by keeping the heated surface temperature below 40°C. Nonheating leads are furnished as part of the panel.
Some panels can be cut to fit; others must be installed as received. Panels may be either flush or surface-mounted, and in some cases, they are finished as part of the ceiling. Rigid 600 by 1200 mm panels for lay-in ceilings (Figure 23) are about 25 mm thick and have a mass of 2.6 to 11 kg. Typical characteristics of an electric panel are listed in Table 4. Panels may also be (1) surface-mounted on gypsum board and wood ceilings or (2) recessed between ceiling joists. Panels range in size from 1200 mm wide to 2400 mm long. Their maximum power output is 1000 W/m2.
Electric Ceiling Panel Systems.
These systems are laminated conductive coatings, printed circuits, or etched elements nailed to the bottom of ceiling joists and covered by
13 mm gypsum board. Heat flux is limited to
190 W/m2. In some cases, the heating element can be cut to fit available space. Manufacturers’ instructions specify how to connect the system to the electric supply. Appropriate codes should be followed when placing partitions, lights, and air grilles adjacent to or near electric panels.
Electric Cables Embedded in Ceilings.
Electric heating cables for embedded or laminated ceiling panels are factory-assembled units furnished in standard lengths of
25 to 550 m. These cable lengths cannot be altered in the field. The cable assemblies are normally rated at
9 W/m and are supplied in capacities from 200 to 5000 W in roughly 200 W increments. Standard cable assemblies are available for 120, 208, and 240 V. Each cable unit is supplied with
2 m nonheating leads for connection at the thermostat or junction box.
Electric cables for panel heating have electrically insulated sleeves resistant to medium temperature, water absorption, aging effects, and chemical action with plaster, cement, or ceiling lath material. This insulation is normally made of polyvinyl chloride (PVC), which may have a nylon jacket. The thickness of the insulation layer is usually about 3 mm.
For plastered ceiling panels, the heating cable may be stapled to gypsum board, plaster lath, or similar fire-resistant materials with rust-resistant staples (Figure 24). With metal lath or other conducting surfaces, a coat of plaster (brown or scratch coat) is applied to completely cover the metal lath or conducting surface before the cable is attached. After the lath is fastened on and the first plaster coat is applied, each cable is tested for continuity of circuit and for insulation resistance of at least 100 kΩ measured to ground.
The entire ceiling surface is finished with a cover layer of thermally noninsulating sand plaster about 13 to 19 mm thick, or other approved noninsulating material applied according to manufacturer’s specifications. The plaster is applied parallel to the heating cable rather than across the runs. While new plaster is drying, the system should not be energized, and the range and rate of temperature change should be kept low by other heat sources or by ventilation until the plaster is thoroughly cured. Vermiculite or other insulating plaster causes cables to overheat and is contrary to code provisions.
For laminated drywall ceiling panels, the heating cable is placed between two layers of gypsum board, plasterboard, or other thermally noninsulating fire-resistant ceiling lath. The cable is stapled directly to the first (or upper) lath, and the two layers are held apart by the thickness of the heating cable. It is essential that the space between the two layers of lath be completely filled with a noninsulating plaster or similar material. This fill holds the cable firmly in place and improves heat transfer between the cable and the finished ceiling. Failure to fill the space between the two layers of plasterboard completely may allow the cable to overheat in the resulting voids and may cause cable failure. The plaster fill should be applied according to manufacturer’s specifications.
Electric heating cables are ordinarily installed with a 150 mm nonheating border around the periphery of the ceiling. A 200 mm clearance must be provided between heating cables and the edges of the outlet or junction boxes used for surface-mounted lighting fixtures. A 50 mm clearance must be provided from recessed lighting fixtures, trim, and ventilating or other openings in the ceiling.
Heating cables or panels must be installed only in ceiling areas that are not covered by partitions, cabinets, or other obstructions. However, it is permissible for a single run of isolated embedded cable to pass over a partition.
The National Electrical Code® (NFPA Standard 70) requires that all general electrical power and lighting wiring be run above the thermal insulation or at least 50 mm above the heated ceiling surface, or that the wiring be derated.
In drywall ceilings, the heating cable is always installed with the cable runs parallel to the joist. A 65 mm clearance between adjacent cable runs must be left centered under each joist for nailing. Cable runs that cross over the joist must be kept to a minimum. Where possible, these crossings should be in a straight line at one end of the indoor space
For cable having a heat flux of 9 W/m, the minimum permissible spacing is 40 mm between adjacent runs. Some manufacturers recommend a minimum spacing of 50 mm for drywall construction.
The spacing between adjacent runs of heating cable can be determined using the following equation:
where
|
M
|
=
|
cable spacing, mm
|
|
An
|
=
|
net panel heated area, m2
|
|
C
|
=
|
length of cable, m
|
Net panel area An in Equation (28) is the net ceiling area available after deducting the area covered by the nonheating border, lighting fixtures, cabinets, and other ceiling obstructions. For simplicity, Equation (28) contains a slight safety factor, and small lighting fixtures are usually ignored in determining net ceiling area.
Electrical resistance of the electric cable must be adjusted according to its temperature at design conditions (Ritter and Kilkis 1998):
where
|
R
|
=
|
electrical resistance of electric cable at standard temperature (20°C), Ω/m
|
|
αe
|
=
|
thermal coefficient for material resistivity, °C−1
|
|
αo
|
=
|
thermal expansion coefficient, °C−1
|
|
td
|
=
|
surface temperature of electric cable at operating conditions [see Equation (23)], °C
|
The 65 mm clearance required under each joist for nailing in drywall applications occupies one-fourth of the ceiling area if the joists are 400 mm on centers. Therefore, for drywall construction, the net area An must be multiplied by 0.75. Many installations have a spacing of 40 mm for the first 600 mm from the cold wall. Remaining cable is then spread over the balance of the ceiling.
Cable embedded in walls similar to ceiling construction is used in Europe. Because of possible damage from nails driven for hanging pictures or from building alterations, most U.S. codes prohibit such panels. Some of the prefabricated panels described in the preceding section are also used for wall panel heating.
Electric heating cable assemblies such as those used for ceiling panels are sometimes used for concrete floor heating systems. Because the possibility of cable damage during installation is greater for concrete floor slabs than for ceiling panels, these assemblies must be carefully installed. After the cable has been placed, all unnecessary traffic should be eliminated until the concrete layer has been placed and hardened.
Preformed mats are sometimes used for electric floor slab heating systems. These mats usually consist of PVC-insulated heating cable woven into or attached to metallic or glass fiber mesh. Such mats are available as prefabricated assemblies in many sizes from 0.2 to 9 m2 and with heat fluxes from 160 to 270 W/m2. When mats are used with a thermally treated cavity beneath the floor, a heat storage system is provided, which may be controlled for off-peak heating.
Mineral-insulated (MI) heating cable is another effective method of slab heating. MI cable is a small-diameter, highly durable, flexible heating cable composed of solid electric-resistance heating wire or wires surrounded by tightly compressed magnesium oxide electrical insulation and enclosed by a metal sheath. MI cable is available in stock assemblies in a variety of standard voltages, heat fluxes (power densities), and lengths. A cable assembly consists of the specified length of heating cable, waterproof hot-cold junctions, 2 m cold sections, UL-approved end fittings, and connection leads. Several standard MI cable constructions are available, such as single conductor, twin conductor, and double cable. Custom-designed MI heating cable assemblies can be ordered for specific installations.
Other outer-sleeve materials that are sometimes specified for electric floor heating cable include (1) silicone rubber, (2) lead, and (3) tetrafluoroethylene (Teflon®).
For a given floor heating cable assembly, the required cable spacing is determined from Equation (24). In general, cable heat flux and spacing should be such that floor panel heat flux is not greater than 160 W/m. Check the latest edition of the National Electrical Code® (NFPA Standard 70) and other applicable codes to obtain information on maximum panel heat flux and other required criteria and parameters.
Floor Heating Cable Installation.
When PVC-jacketed electric heating cable is used for floor heating, the concrete slab is laid in two pours. The first pour should be at least
75 mm thick and, where practical, should be insulating concrete to reduce downward heat loss. For a proper bond between the layers, the finish slab should be placed within 24 h of the first pour, with a bonding grout applied. The finish layer should be between
40 and 50 mm thick. This top layer must not be insulating concrete. At least
25 mm of perimeter insulation should be installed as shown in
Figure 25.
The cable is installed on top of the first pour of concrete no closer than 50 mm from adjoining walls and partitions. Methods of fastening the cable to the concrete include the following:
-
Staple the cable to wood nailing strips fixed in the surface of the rough slab. Daubs of cement, plaster of paris, or tape maintain the predetermined cable spacing.
-
In light or uncured concrete, staple the cable directly to the slab using hand-operated or powered stapling machines.
-
Nail special anchor devices to the first slab to hold the cable in position while the top layer is being poured.
Preformed mats can be embedded in the concrete in a continuous pour. The mats are positioned in the area between expansion and/or construction joints and electrically connected to a junction box. The slab is poured to within 40 to 50 mm of the finished level. The surface is rough-screeded and the mats placed in position. The final cap is applied immediately. Because the first pour has not set, there is no adhesion problem between the first and second pours, and a monolithic slab results. A variety of contours can be developed by using heater wire attached to glass fiber mats. Allow for circumvention of obstructions in the slab.
MI electric heating cable can be installed in concrete slab using either one or two pours. For single-pour applications, the cable is fastened to the top of the reinforcing steel before the pour is started. For two-layer applications, the cable is laid on top of the bottom structural slab and embedded in the finish layer. Proper spacing between adjacent cable runs is maintained by using prepunched copper spacer strips nailed to the lower slab.
Panel design requires determining panel area, type, and arrangement as well as the supply water temperature and flow rate. Panel performance is directly related to indoor space conditions. Air-side design also must be established. Heating and cooling loads may be calculated by procedures covered in Chapters 17 and 18 of the 2017 ASHRAE Handbook—Fundamentals. For cooling load calculations, the procedure based on the heat balance (HB) method is recommended, because other simplified methods developed for all-air systems [such as the radiant time series (RTS) method] are not as appropriate for radiant-system applications (Feng et al. 2013b, 2014). The procedure is as follows:
-
Determine indoor design dry-bulb temperature, relative humidity, and dew point.
-
Calculate sensible and latent heat gains.
-
Establish minimum supply air quantity for ventilation.
-
Calculate latent cooling available from supply air.
-
Calculate sensible cooling available from supply air.
-
Determine remaining sensible cooling load to be satisfied by panel system.
-
Determine minimum permissible effective cooling panel surface temperature that will not lead to surface condensation at design conditions.
-
Determine AUST.
-
Determine necessary panel area for remaining sensible cooling.
-
Determine average panel cooling water (brine) temperature for given tube spacing, or determine necessary tube spacing if average panel cooling water (brine) temperature is known.
-
Designate indoor design dry-bulb temperature for panel heating.
-
Calculate room heat loss.
-
Determine AUST. Use Equation (14) to find surface temperatures of exterior walls and exposed floors and ceilings. Interior walls are assumed to have surface temperatures equal to indoor air temperature.
-
Calculate required effective surface temperature of panel. Refer to Figures 9 and 10 if AUST does not greatly differ from indoor air temperature. Otherwise, use Equations (5), (9), (10), (11), and (12) or refer to Figures 1 and 3.
-
Determine panel area. Refer to Figures 9 and 10 if AUST does not vary greatly from indoor air temperature.
-
Refer to manufacturers’ data for panel surface temperatures higher than those given in Figures 9 and 10. For panels with several covers, average temperature of each cover and effective panel surface temperature must be calculated and compared to temperature-withstanding capacity for continuous operation of every cover material. For this purpose, Equation (23) may be used: add thermal resistances of all cover layers between panel surface and cover layer in question, then multiply by q and add to first two terms in Equation (23). This is tha, approximated temperature of the particular layer at design.
-
Determine tube spacing for a given average water temperature or select electric cable properties or electric mat size.
-
In a hydronic panel system, if tube spacing is known, determine required average water temperature.
-
Design panel arrangement.
Other Steps Common for Sensible Heating and Cooling
-
Check thermal comfort requirements in the following steps [see Chapter 9 of the 2017 ASHRAE Handbook—Fundamentals and NRB (1981)].
-
Determine occupant’s clothing insulation value and metabolic rate (see Tables 4, 7, and 8 in Chapter 9 of the 2017 ASHRAE Handbook—Fundamentals).
-
Determine optimum operative temperature at coldest point in conditioned space (see the Comfort Equations for Radiant Heating section in Chapter 9 of the 2017 ASHRAE Handbook—Fundamentals. Note that the same equations may be adopted for panel cooling).
-
Determine MRT at the coldest point in the conditioned space [see Chapter 16 and Fanger (1972)]. Note: If indoor air velocity is less than 0.4 m/s and MRT is less than 50°C, operative temperature may be approximated as the average of MRT and ta.
-
From the definition of operative temperature, establish optimum indoor design air temperature at coldest point in the room. If optimum indoor design air temperature varies greatly from designated design temperature, designate a new temperature.
-
Determine MRT at hottest point in conditioned space.
-
Calculate operative temperature at hottest point in conditioned space.
-
Compare operative temperatures at hottest and coldest points. For light activity and normal clothing, the acceptable operative temperature range is 20 to 24°C [see NRB (1981) and ANSI/ASHRAE Standard 55-2013]. If the range is not acceptable, the panel system must be modified.
-
Calculate radiant temperature asymmetry (NRB 1981). Acceptable ranges are less than 5 K for warm ceilings, 15 K for cool ceilings, 10 K for cool walls, and 27 K for warm walls at 10% local discomfort dissatisfaction (ANSI/ASHRAE Standard 55-2013).
-
Determine water flow rate and pressure drop. Refer to manufacturers’ guides for specific products, or use the guidelines in Chapter 22 of the 2017 ASHRAE Handbook—Fundamentals. Chapter 13 of this volume also has information on hydronic heating and cooling systems.
-
The supply and return manifolds must be carefully designed. If there are circuits of unequal coil lengths, the following equation may be used (Hansen 1985; Kilkis 1998) for a circuit i connected to a manifold with n circuits:
where
|
|

|
|
Qi
|
=
|
flow rate in circuit i, L/s
|
|
Qtot
|
=
|
total flow rate in supply manifold, L/s
|
|
Li
|
=
|
coil length of hydronic circuit i, m
|
|
r
|
=
|
1.75 for hydronic panels (Siegenthaler 1995)
|
Application, design, and installation of panel systems have certain requirements and techniques:
-
As with any hydronic system, look closely at the piping system design. Piping should be designed to ensure that water of the proper temperature and in sufficient quantity is available to every grid or coil at all times. Proper piping and system design should minimize the detrimental effects of oxygen on the system. Reverse-return systems should be considered to minimize balancing problems.
-
Hydronic panels can be used with two- and four-pipe distribution systems. Figure 26 shows a typical system arrangement. It is common to design for a 10 K temperature drop for heating across a given grid and a 3 K rise for cooling, but larger temperature differentials may be used, if applicable.
-
Individual panels can be connected for parallel flow using headers, or for sinuous or serpentine flow. To avoid flow irregularities in a header-type grid, the water channel or lateral length should be greater than the header length. If the laterals in a header grid are forced to run in a short direction, using a combination series-parallel arrangement can solve this problem. Serpentine flow ensures a more even panel surface temperature throughout the heating or cooling zone.
-
Noise from entrained air, high-velocity or high-pressure-drop devices, or pump and pipe vibrations must be avoided. Water velocities should be high enough to prevent separated air from accumulating and causing air binding. Where possible, avoid automatic air venting devices over ceilings of occupied spaces.
-
Design piping systems to accept thermal expansion adequately. Do not allow forces from piping expansion to be transmitted to panels. Thermal expansion of ceiling panels must be considered.
-
In hydronic systems, thermoplastic, rubber tubes, steel, or copper pipes are used widely in ceiling, wall, or floor panel construction. Where coils are embedded in concrete or plaster, no threaded joints should be used for either pipe coils or mains. Steel pipe should be the all-welded type. Copper tubing should be a soft-drawn coil. Fittings and connections should be minimized. Bending should be used to change direction. Solder-joint fittings for copper tube should be used with a medium-temperature solder of 95% tin, 5% antimony, or capillary brazing alloys. All piping should be subjected to a hydrostatic test of at least three times the working pressure. Maintain adequate pressure in embedded piping while pouring concrete.
-
Placing the thermostat on a wall where it can observe both the outdoor exposed wall and the warm panel should be considered. The normal thermostat cover reacts to the warm panel, and thermal radiation from the panel to the cover tends to alter the control point so that the thermostat controls 1 to 2 K lower when the outdoor temperature is a minimum and the panel temperature is a maximum. Experience indicates that panel-heated spaces are more comfortable under these conditions than when the thermostat is located on a back wall.
-
If throttling valve control is used, either the end of the main should have a fixed bypass, or the last one or two rooms on the mains should have a bypass valve to maintain water flow in the main. Thus, when a throttling valve modulates, there will be a rapid response.
-
When selecting heating design temperatures for a ceiling panel surface, the design parameters are as follows:
-
Excessively high temperatures over the occupied zone cause the occupant to experience a “hot head effect.”
-
Temperatures that are too low can result in an oversized, uneconomical panel and a feeling of coolness at the outside wall.
-
Locate ceiling panels adjacent to perimeter walls and/or areas of maximum load.
-
With normal ceiling heights of 2.4 to 2.8 m, panels less than 1 m wide at the outside wall can be designed for 113°C surface temperature. If panels extend beyond 1 m into the indoor space, the panel surface temperature should be limited to the values given in Figure 15. The surface temperature of concrete or plaster panels is limited by construction.
-
Floor panels are limited to surface temperatures of less than 29°C in occupied spaces for comfort reasons. Subfloor temperature may be limited to the maximum exposure temperature specified by the floor cover manufacturer.
-
When the panel chilled-water system is started, the circulating water temperature should be maintained at indoor air temperature until the air system is completely balanced, the dehumidification equipment is operating properly, and building relative humidity is at design value.
When the panel area for cooling is greater than the area required for heating, a two-panel arrangement (Figure 27) can be used. Panel HC (heating and cooling) is supplied with hot or chilled water year-round. When chilled water is used, the controls activate panel CO (cooling only) mode, and both panels are used for cooling.
-
To prevent condensation on the cooling panels, the panel water supply temperature should be maintained at least 0.5 K above the indoor design dew-point temperature. This minimum difference is recommended to allow for the normal drift of temperature controls for water and air systems, and also to provide a factor of safety for temporary increase in indoor relative humidity.
-
Selection of summer design indoor dew point below 10°C generally is not economical.
-
The most frequently applied method of dehumidification uses cooling coils. If the main cooling coil is six rows or more, the dew point of leaving air will approach the leaving water temperature. The cooling water leaving the dehumidifier can then be used for the panel water circuit.
-
Several chemical dehumidification methods are available to control latent and sensible loads separately. In one application, cooling tower water is used to remove heat from the chemical drying process, and additional sensible cooling is necessary to cool the dehumidified air to the required system supply air temperature.
-
When chemical dehumidification is used, hygroscopic chemical dew-point controllers are required at the central apparatus and at various zones to monitor dehumidification.
-
When cooled ceiling panels are used with a variable-air-volume (VAV) system, the air supply rate should be near maximum volume to ensure adequate dehumidification before the cooling ceiling panels are activated.
Other factors to consider when using panel systems are
-
Evaluate the panel system to take full advantage in optimizing the physical building design.
-
Select recessed lighting fixtures, air diffusers, hung ceilings, and other ceiling devices to provide the maximum ceiling area possible for use as panels.
-
The air-side design must be able to maintain relative humidity at or below design conditions at all times to eliminate any possibility of condensation on the panels. This becomes more critical if indoor space dry- and wet-bulb temperatures are allowed to drift for energy conservation, or if duty cycling of the fans is used.
-
Do not place cooling panels in or adjacent to high-humidity areas, such as near a lobby entrance, or a kitchen.
-
Anticipate thermal expansion of the ceiling and other devices in or adjacent to the ceiling.
-
The design of operable windows should discourage unauthorized opening.
Automatic controls for panel heating may differ from those for convective heating because of the thermal inertial characteristics of the panel and the increase in mean radiant temperature in the space under increasing loads. However, low-mass systems using thin metal panels or thin underlay with low thermal heat capacity may be successfully controlled with conventional control technology using indoor sensors. Many of the control principles for hot-water heating systems described in Chapters 13 and 15 also apply to panel heating. Because panels do not depend on air-side equipment to distribute energy, many control methods have been used successfully; however, a control interface between heating and cooling should be installed to prevent simultaneous heating and cooling.
High-thermal-mass panels such as concrete slabs require a control approach different from that for low-mass panels. Because of thermal inertia, significant time is required to bring such massive panels from one operating point to another, say from vacation setback to standard operating conditions. This will result in long periods of discomfort during the delay, then possibly periods of uncomfortable and wasteful overshoot. Careful economic analysis may reveal that nighttime setback is not warranted.
Once a slab is at operating conditions, the control strategy should be to supply the slab with heat at the rate that heat is being lost from the space (MacCluer et al. 1989). For hydronic slabs with constant circulator flow rates, this means modulating the temperature difference between the outgoing and returning water; this is accomplished with mixing valves, fuel modulation, or, for constant thermal power sources, pulse-width modulation (on/off control). For some applications, more advanced control techniques, such as model predictive control, may be used to optimize the balance of thermal comfort and energy consumption (Feng et al. 2015; Olde-wurtel et al. 2012). Slabs with embedded electric cables can be controlled by pulse-width modulators such as the common round thermostat with anticipator or its solid-state equivalent.
Outdoor reset control, another widely accepted approach, measures the outdoor air temperature, calculates the supply water temperature required for steady operation, and operates a mixing valve or boiler to achieve that supply water temperature. If the heating load of the controlled space is primarily a function of outdoor air temperature, or indoor temperature measurement of the controlled space is impractical, then outdoor reset control alone is an acceptable control strategy. When other factors such as solar or internal gains are also significant, indoor temperature feedback should be added to the outdoor reset.
In all panel applications, precautions must be taken to prevent excessive temperatures. A manual boiler bypass or other means of reducing the water temperature may be necessary to prevent new panels from drying out too rapidly.
Sensible Cooling Controls
The average water temperature in the hydronic circuit of radiant systems can be controlled either by mixing, by heat exchange, or by using the water leaving the dehumidifier. Other considerations are listed in the section on General Design Considerations. It is imperative to dry out the building space before starting the panel water system, particularly after extended down periods such as weekends. Such delayed starting action should be automated.
Radiant cooling systems require the following basic areas of temperature control: (1) exterior zones; (2) areas under exposed roofs, to compensate for transmission and solar loads; and (3) each typical interior zone, to compensate for internal loads. For optimum results, each area of the building with significantly different heating or cooling loads should be independently controlled.
Temperature control of the indoor air and panel water supply should not be a function of the outdoor weather. Normal thermostat drift is usually adequate compensation for the slightly lower temperatures desirable during winter weather. This drift should result in an indoor air temperature change of no more than 0.8 K. Control of interior zones is best accomplished by devices that reflect the actual presence of the internal load elements. Frequently, time clocks and current-sensing devices are used on lighting feeders.
In comfort heating, the effective surface temperature of a heated floor slab is held to a maximum of 27 to 29°C. As a result, when the heated slab is the primary heating system, thermostatic controls sensing air temperature should not be used to control the heated slab temperature; instead, the heating system should be wired in series with a slab-sensing thermostat. The remote sensing thermostat in the slab acts as a limit switch to control maximum surface temperatures allowed on the slab. The ambient sensing thermostat controls the comfort level. For supplementary slab heating, as in kindergarten floors, a remote sensing thermostat in the slab is commonly used to tune in the desired comfort level. Indoor-outdoor thermostats are used to vary the floor temperature inversely with the outdoor temperature. If the building heat loss is calculated for an outdoor temperature between 21 to –19°C, and the effective floor temperature range is maintained between 21 to 29°C with a remote sensing thermostat, the ratio of change in outdoor temperature to change in the heated slab temperature is 40:8, or 5:1. This means that a 5 K drop in outdoor temperature requires a 1 K increase in the slab temperature. An ambient sensing thermostat is used to vary the ratio between outdoor and slab temperatures. A time clock is used to control each heating zone if off-peak slab heating is desirable.
In heating systems, lowering nighttime air and surface temperatures can produce less satisfactory results in thermally massive radiant systems such as embedded tubing in concrete floors. These systems cannot respond to a quick increase or decrease in heating demand within the relatively short time required, resulting in a very slow reduction of the space temperature at night and a correspondingly slow pickup in the morning. Light panels, such as plaster or metal ceilings and walls, may respond to changes in demand quickly enough for satisfactory results from lowered nighttime air and panel temperatures. Berglund et al. (1982) demonstrated the speed of response on a metal ceiling panel to be comparable to that of convection systems. However, in cooling operation, thermally massive embedded systems can offer cost- and energy-saving opportunities through nighttime precooling when electricity costs are typically lower, as are outdoor dry- and wet-bulb temperatures.
ASHAE. 1956. Thermal design of warm water ceiling panels. ASHAE Transactions 62:71.
ASHAE. 1957. Thermal design of warm water concrete floor panels. ASHAE Transactions 63:239.
ASHRAE. 1976. Energy calculations I—Procedures for determining heating and cooling loads for computerizing energy calculations.
ASHRAE. 2013. Thermal environmental conditions for human occupancy. ANSI/ASHRAE Standard 55-2013.
ASHRAE. 2013. Method of testing for rating ceiling panels for sensible heating and cooling. ANSI/ASHRAE Standard 138-2013.
Berglund, L., R. Rascati, and M.L. Markel. 1982. Radiant heating and control for comfort during transient conditions. ASHRAE Transactions (88): 765-775.
Buckley, N.A. 1989. Application of radiant heating saves energy. ASHRAE Journal 31(9):17-26.
CEN. 2011. Water based surface embedded heating and cooling systems—Part 4: Installation. Standard EN 1264-4:2011. European Committee for Standardization, Brussels.
CEN. 2004. Ventilation for buildings—Chilled ceilings—Testing and rating. Standard EN 14240:2004. European Committee for Standardization, Brussels.
CEN. 2013. Free hanging heating and cooling surfaces for water with a temperature below 120°C. Standard EN 14037:2013. European Committee for Standardization, Brussels.
DOE. 2002. Energy consumption characteristics of commercial building HVAC systems, vol. III: Energy savings potential. TIAX ref. no. 68370-00, for Building Technologies Program, U.S. Department of Energy. Contract no. DE-AC01-96CE23798. Washington, D.C.
Fanger, P.O. 1972. Thermal comfort analysis and application in environmental engineering. McGraw-Hill, New York.
Feng, J., S. Schiavon, and F. Bauman. 2013a. Impact of solar heat gain on radiant floor cooling system design. Proceedings of the 11th REHVA World Congress-CLIMA 2013, Prague, Czech Republic.
Feng, J., S. Schiavon, and F. Bauman. 2013b. Cooling load differences between radiant and air systems. Energy and Buildings 65:310-321.
Feng, J., F. Chuang, F. Borrelli, and F. Bauman. 2015. Model predictive control of radiant slab systems with evaporative cooling sources. Energy and Buildings 87:199-210.
Hansen, E.G. 1985. Hydronic system design and operation. McGraw-Hill, New York.
ISO. 2012. Building environment design—Design, dimensioning, installation and control of embedded radiant heating and cooling systems. Standard 11855-2012. International Organization for Standardization, Geneva.
ISO. 2014. Building environment design—Design, test methods and control of hydronic radiant heating and cooling panel systems. Standard 18566-2014. International Organization for Standardization, Geneva.
Kalisperis, L.N. 1985. Design patterns for mean radiant temperature prediction. Department of Architectural Engineers, Pennsylvania State University, University Park.
Kalisperis, L.N., and L.H. Summers. 1985. MRT33GRAPH—A CAD program for the design evaluation of thermal comfort conditions. Tenth National Passive Solar Conference, Raleigh, NC.
Kilkis, B.I. 1998. Equipment oversizing issues with hydronic heating systems. ASHRAE Journal 40(1):25-31.
Kollmar, A., and W. Liese. 1957. Die Strahlungsheizung, 4th ed. R. Oldenburg, Munich.
Lindstrom, P.C., D. Fisher, and C. Pedersen. 1998. Impact of surface characteristics on radiant panel output. ASHRAE Research Project RP-876, Final Report.
Liu, X., X. Xiang, K. Zhao, and Y. Jiang. 2015. Cooling performance comparison of radiant floor system and all-air system with solar radiation. 6th International Building Physics Conference, IBPC 2015. Energy Procedia 78:2322-2327.
MacCluer, C.R., M. Miklavcic, and Y. Chait. 1989. The temperature stability of a radiant slab-on-grade. ASHRAE Transactions 95(1):1001-1009.
Meierhans R., and B.W. Olesen. 2002. Art museum in Bregenz—Soft HVAC for a strong architecture. ASHRAE Transactions 108(2).
Min, T.C., L.F. Schutrum, G.V. Parmelee, and J.D. Vouris. 1956. Natural convection and radiation in a panel heated room. ASHAE Transactions 62: 337.
NFPA. 2016. Installation of sprinkler systems. Standard 13-2016. National Fire Protection Association, Quincy, MA.
NFPA. 2014. National electrical code®. Standard 70-2014. National Fire Protection Association, Quincy, MA.
NRB. 1981. Indoor climate. Technical Report 41. The Nordic Committee on Building Regulations, Stockholm.
Oldewurtel, F., A. Parisio, C. N. Jones, D. Gyalistras, M. Gwerder, V. Stauch, B. Lehmann, and M. Morari. 2012. Use of model predictive control and weather forecasts for energy efficient building climate control. Energy and Buildings 45:15-27
Parmelee, G.V., and R.G. Huebscher. 1947. Forced convection, heat transfer from flat surfaces. ASHVE Transactions 53:245.
Ritter, T.L., and B.I. Kilkis. 1998. An analytical model for the design of in-slab electric heating panels. ASHRAE Transactions 104(1B):1112-1115.
Sartain, E.L., and W.S. Harris. 1956. Performance of covered hot water floor panels, part I—Thermal characteristics. ASHAE Transactions 62:55.
Scheatzle, D.G. 2003. Establishing a baseline data set for the evaluation of hybrid (radiant/convective) HVAC systems. ASHRAE Research Project RP-1140, Final Report.
Schutrum, L.F., and C.M. Humphreys. 1954. Effects of non-uniformity and furnishings on panel heating performance. ASHVE Transactions 60:121.
Schutrum, L.F., and J.D. Vouris. 1954. Effects of room size and non-uniformity of panel temperature on panel performance. ASHVE Transactions 60:455.
Schutrum, L.F., G.V. Parmelee, and C.M. Humphreys. 1953a. Heat exchangers in a ceiling panel heated room. ASHVE Transactions 59:197.
Schutrum, L.F., G.V. Parmelee, and C.M. Humphreys. 1953b. Heat exchangers in a floor panel heated room. ASHVE Transactions 59:495.
Siegenthaler, J. 1995. Modern hydronic heating. Delmar Publishers, Boston.
Simmonds, P. 2006. Radiant cooled floors—Operation and control dependent upon solar radiation. ASHRAE Transactions 112(1):358-367.
Steinman, M., L.N. Kalisperis, and L.H. Summers. 1989. The MRT-correction method—An improved method for radiant heat exchange. ASHRAE Transactions 95(1):1015-1027.
Sugawara, F., M. Nobushisa, and H. Miyazawa. 1996. Comparison of mite-allergen and fungal colonies in floor dust in Seoul (Korea) and Koriyama (Japan) dwellings. Journal of Architecture, Planning and Environmental Engineering, Architectural Institute of Japan 48:35-42.
TSI. 1994. Fundamentals of design for floor heating systems (in Turkish). Turkish Standard 11261. Turkish Standards Institute, Ankara.
Walton, G.N. 1980. A new algorithm for radiant interchange in room loads calculations. ASHRAE Transactions 86(2):190-208.
Watson, R.D., K.S. Chapman, and J. DeGreef. 1998. Case study: Seven-system analysis of thermal comfort and energy use for a fast-acting radiant heating system. ASHRAE Transactions 104(1B):1106-1111.
Wilkes, G.B., and C.M.F. Peterson. 1938. Radiation and convection from surfaces in various positions. ASHVE Transactions 44:513.
ALI. 2003. Fundamentals of panel heating and cooling, short course. ASHRAE Learning Institute.
Babiak, J., B. Olesen, and D. Petras. 2007. REHVA guidebook no. 7: Low temperature heating and high temperature cooling. Federation of European Heating, Ventilation and Air Conditioning Associations, Brussels.
BSR/ASHRAE. 2003. Method of test for determining the design and seasonal efficiencies of residential thermal distribution systems. Draft Standard 152P, 2nd Public Review.
Buckley, N.A., and T.P. Seel. 1987. Engineering principles support an adjustment factor when sizing gas-fired low-intensity infrared equipment. ASHRAE Transactions 93(1):1179-1191.
Chapman, K.S., and P. Zhang. 1995. Radiant heat exchange calculations in radiantly heated and cooled enclosures. ASHRAE Transactions 101(2): 1236-1247.
Chapman, K.S., J. Ruler, and R.D. Watson. 2000. Impact of heating systems and wall surface temperatures on room operative temperature fields. ASHRAE Transactions 106(1).
Hanibuchi, H., and S. Hokoi. 2000. Simplified method of estimating efficiency of radiant and convective heating systems. ASHRAE Transactions 106(1).
Hogan, R.E., Jr., and B. Blackwell. 1986. Comparison of numerical model with ASHRAE designed procedure for warm-water concrete floor-heating panels. ASHRAE Transactions 92(1B):589-601.
Jones, B.W., and K.S. Chapman. 1994. Simplified method to factor mean radiant temperature (MRT) into building and HVAC system design. ASHRAE Research Project RP-657, Final Report.
Kilkis, B.I. 1993. Computer-aided design and analysis of radiant floor heating systems. Paper no. 80. Proceedings of Clima 2000, London (Nov. 1-3).
Kilkis, B.I. 1993. Radiant ceiling cooling with solar energy: Fundamentals, modeling, and a case design. ASHRAE Transactions 99(2):521-533.
Kilkis, B.I., S.S. Sager, and M. Uludag. 1994. A simplified model for radiant heating and cooling panels. Simulation Practice and Theory Journal 2:61-76.
Kilkis, B.I., A.S.R. Suntur, and M. Sapci. 1995. Hybrid HVAC systems. ASHRAE Journal 37(12):23-28.
Nall, D. 2013. Thermally active floors. ASHRAE Journal 36(1-3).
Ramadan, H.B. 1994. Analysis of an underground electric heating system with short-term energy storage. ASHRAE Transactions 100(2):3-13.
Sprecher, P., B. Gasser, O. Böck, and P. Kofoed. 1995. Control strategy for cooled ceiling panels. ASHRAE Transactions 101(2).
Watson, R.D., and K.S. Chapman. 2002. Radiant heating and cooling handbook. McGraw-Hill, New York.
For additional literature on high-temperature radiant heating, see the Bibliography in Chapter 16.