CHAPTER 26. AIR-TO-AIR ENERGY RECOVERY EQUIPMENT

Air-to-air energy recovery is the process of recovering heat or/and moisture between two airstreams at different temperatures and humidities. This process is important in maintaining acceptable indoor air quality (IAQ) while maintaining low energy costs and reducing overall energy consumption. This chapter describes various technologies for air-to-air energy recovery. Thermal and economic performance, maintenance, and related operational issues are presented, with emphasis on energy recovery for ventilation.

Energy can be recovered either in its sensible (temperature only) or latent (moisture) form, or combination of both from multiple sources. Sensible energy can be extracted, for example, from outgoing airstreams in dryers, ovens, furnaces, combustion chambers, and gas turbine exhaust gases to heat supply air. Units used for this purpose are called sensible heat exchange devices or heat recovery ventilators (HRVs). Devices that transfer both heat and moisture are known as energy or enthalpy devices or energy recovery ventilators (ERVs). HRVs and ERVs are available for commercial and industrial applications as well as for residential and small-scale commercial uses.

Air conditioners use much energy to dehumidify moist airstreams. Excessive moisture in the air of a building can result in mold, allergies, and bacterial growth. ERVs can enhance dehumidification with packaged unitary air conditioners. Introducing outdoor or ventilation air is the primary means of diluting air contaminants to achieve acceptable indoor air quality. ERVs can cost-effectively provide large amounts of outdoor air to meet a building’s minimum ventilation requirements as prescribed in ASHRAE Standards 62.1 and 62.2.

Types of ERVs include fixed-plate heat exchangers, rotary wheels, heat pipes, runaround loops, thermosiphons, and twin-tower enthalpy recovery loops. Performance is typically characterized by effectiveness; pressure drop, pumping, or fan power of fluids; cross flow (i.e., amount of air leakage from one stream to the other); and frost control (used to prevent frosting on the heat exchanger). Recovery efficiency, the ratio of output of a device to its input, is also often considered. In energy recovery ventilators, effectiveness refers to the ratio of actual energy or moisture recovered to the maximum possible amount of energy and/or moisture that can be recovered.

Fluid stream pressure drops because of the friction between the fluid and solid surface, and because of the geometrical complexity of the flow passages. Pumping or fan power is the product of the fluid volume flow rate and pressure drop. Economic factors such as cost of energy recovered and capital and maintenance cost (including pumping power cost) play a vital role in determining the economic feasibility of recovery ventilators for a given application.

1. APPLICATIONS

Air-to-air energy recovery systems may be categorized according to their application as (1) process-to-process, (2) process-to-comfort, or (3) comfort-to-comfort. Some typical air-to-air energy recovery applications are listed in Table 1.

Table 1. Typical Applications for Air-to-Air Energy Recovery

Method

Application

Process-to-process

and

Process-to-comfort

Dryers

Ovens

Flue stacks

Burners

Furnaces

Incinerators

Paint exhaust

Welding exhaust

Comfort-to-comfort

Swimming pools

Locker rooms

Residential

Operating rooms

Nursing homes

Animal ventilation

Plant ventilation

Smoking exhaust


In process-to-process applications, heat is captured from the process exhaust stream and transferred to the process supply airstream. Equipment is available to handle process exhaust temperatures as high as 1600°F.

Process-to-process recovery devices generally recover only sensible heat and do not transfer latent heat, because moisture transfer is usually detrimental to the process. In cases involving condensable gases, less recovery may be desired to prevent condensation and possible corrosion.

In process-to-comfort applications, waste heat captured from process exhaust heats building makeup air during winter. Typical applications include foundries, strip-coating plants, can plants, plating operations, pulp and paper plants, and other processing areas with heated process exhaust and large makeup air volume requirements.

Although full recovery is usually desired in process-to-process applications, recovery for process-to-comfort applications must be modulated during warm weather to prevent overheating the makeup air. During summer, no recovery is required. Because energy is saved only in the winter and recovery is modulated during moderate weather, process-to-comfort applications save less energy annually than do process-to-process applications.

Process-to-comfort recovery devices generally recover sensible heat only and do not transfer moisture between airstreams.

In comfort-to-comfort applications, the energy recovery device lowers the enthalpy of the building supply air during warm weather and raises it during cold weather by transferring energy between the ventilation air supply and exhaust airstreams.

Air-to-air energy recovery devices for comfort-to-comfort applications may be sensible heat exchange devices (i.e., transferring sensible energy only) or energy exchange devices (i.e., transferring both sensible energy and moisture). These devices are discussed further in the section on Additional Technical Considerations.

When outdoor air humidity is low and the building space has an appreciable latent load, an ERV can recover sensible energy while possibly slightly increasing the latent space load because of water vapor transfer within the ERV. It is therefore important to determine whether the given application calls for HRV or ERV.

HRVs are suitable when outdoor air humidity is low and latent space loads are high for most of the year, and also for use with swimming pools, chemical exhaust, paint booths, and indirect evaporative coolers.

ERVs are suitable for applications in schools, offices, residences and other applications that require year-round economical preheating or/and precooling of outdoor supply air.

2. BASIC THERMODYNAMICS

The second law of thermodynamics states that heat energy always transfers from a region of high temperature to one of low temperature. This law can be extended to say that mass transfer always occurs from a region of high vapor pressure to one of low vapor pressure. The ERV facilitates this transfer across a separating wall (shown by a thick horizontal line in Figure 1) made of a material that conducts heat and is permeable to water vapor. Moisture is transferred when there is a difference in vapor pressure between the two airstreams.

On a typical summer day, supply air at temperature, humidity, or enthalpy of x1 and mass flow rate ms enters the ERV, while exhaust air from the conditioned space enters at conditions x3 and m3. Because conditions at x3 are lower than conditions at x1, heat and mass transfer from the supply airstream to the exhaust airstream because of differences in temperature and vapor pressures across the separating wall. Consequently, the supply air exit properties decrease, while those of the exhaust air increase. Exit properties of these two streams can be estimated, knowing the flow rates and the effectiveness of the heat exchanger.

Airstream Numbering Convention

Figure 1. Airstream Numbering Convention


ASHRAE Standard 84 defines effectiveness as

(1)

 Thermodynamics of Heat Recovery Ventilators

From Figure 1, the sensible effectiveness εs of a heat recovery ventilator is given as

(2a)

where qs is the actual sensible heat transfer rate given by

(2b)

where qs,max is the maximum sensible heat transfer rate given by

(2c)

where

qs

=

sensible heat transfer rate, Btu/h

qs,max

=

maximum sensible heat transfer rate,Btu/h

εs

=

sensible effectiveness

t1

=

dry-bulb temperature at location 1 in Figure 1, °F

ms

=

supply dry air mass flow rate, lb/min

me

=

exhaust dry air mass flow rate, lb/min

Cmin

=

smaller of cpsms and cpeme

cps

=

supply moist air specific heat at constant pressure, Btu/lb · °F

cpe

=

exhaust moist air specific heat at constant pressure, Btu/lb · °F

Assuming no water vapor condensation in the HRV, the leaving supply air condition is

(3a)

and the leaving exhaust air condition is

(3b)

Equations (2), (3a), and (3b) assume steady-state operating conditions; no heat or moisture transfer between the heat exchanger and its surroundings; no cross-leakage, and no energy gains or losses from motors, fans, or frost control devices. Furthermore, condensation or frosting does not occur or is negligible. These assumptions are generally nearly true for larger commercial HRV applications. Note that the HRV only allows transfer of sensible heat energy associated with heat transfer because of temperature difference between the airstreams or between an airstream and a solid surface. These equations apply even in winter, if there is no condensation in the HRV.

The sensible heat energy transfer qs from the heat recovery ventilator can be estimated from

(3c)

(3d)

(3e)

where

Qs

=

volume flow rate of supply air, cfm

Qe

=

volume flow rate of exhaust air, cfm

ρs

=

density of dry supply air, lb/ft3

ρe

=

density of dry exhaust air, lb/ft3kg/m3

t1, t2, t3, t4

=

inlet and exit temperatures of supply and exhaust airstreams, respectively

mmin

=

smaller of ms and me

Because cp s and cp e are nearly equal, these terms may be omitted from Equations (1) to (4).

Sensible heat exchangers (HRVs) can be used in virtually all cases, especially for swimming pool, paint booth, and reheat applications. Equations (1) to (3e) apply for both HRVs and ERVs with appropriate selection of x1, x2, x3, and x4.

 Thermodynamics of Energy Recovery Ventilators

The ERV allows the transfer of both sensible and latent heat, the latter because of the difference in water vapor pressures between the airstreams or between an airstream and a solid surface. ERVs are available as desiccant rotary wheels and also as membrane plate exchangers; although other gases may also pass through the membrane (Sparrow et al. 2001a) of membrane plate energy exchangers, it is assumed in the following equations that only the water vapor is allowed to pass through the membrane.

From Figure 1, assuming no condensation in the ERV, the latent effectiveness εL of an energy recovery ventilator is given as

(4a)

where qL is the actual latent heat transfer rate given by

(4b)

where qL,max is the maximum heat transfer rate given by

(4c)

where

εL

=

latent effectiveness

hfg

=

enthalpy of vaporization, Btu/lb

w

=

humidity ratios at locations indicated in Figure 1

ms

=

supply dry air mass flow rate, lb/min

me

=

exhaust dry air mass flow rate, lb/min

mmin

=

smaller of ms and me

Because the enthalpy of vaporization from Equation (4a) can be dropped out from numerator and denominator, Equation (4a) can be rewritten as

(4d)

where εm is moisture effectiveness, numerically equal to latent effectiveness εL, and mw is actual moisture transfer rate given by

(4e)

where ms,max is the maximum moisture transfer rate given by

(4f)

Assuming no water vapor condensation in the ERV, the leaving humidity ratios can be given as follows. The supply air leaving humidity ratio is

(5a)

and the leaving exhaust air humidity ratio is

(5b)

The total effectiveness εt of an energy recovery ventilator is given as

(6a)

where qt is the actual total energy transfer rate given by

(6b)

where qt,max is the maximum total energy transfer rate given by

(6c)

where

εt

=

total effectiveness

h

=

enthalpy at locations indicated in Figure 1, Btu/lb

ms

=

supply dry air mass flow rate, lb/min

me

=

exhaust dry air mass flow rate, lb/min

mmin

=

smaller of ms and me

The leaving supply air condition is

(7a)

and the leaving exhaust air condition is

(7b)

Assuming the stream at state 1 is of higher humidity, the latent heat recovery qL from the ERV can be estimated from

(8a)

(8b)

(8c)

where

hfg

=

enthalpy of vaporization or heat of vaporization of water vapor, Btu/lb

w1, w2, w3, w4

=

inlet and exit humidity ratios of supply and exhaust airstreams, respectively

The total energy transfer qt between the streams is given by

(9)

(10a)

(10b)

where

h1s

=

enthalpy of supply air at inlet, Btu/lb

h3e

=

enthalpy of exhaust air at inlet, Btu/lb

h2s

=

enthalpy of supply air at outlet, Btu/lb

h4e

=

enthalpy of exhaust air at outlet, Btu/lb

ERVs can be used where there is an opportunity to transfer heat and mass (water vapor) (e.g., humid areas, schools, offices with large occupancies). Latent energy transfer can be positive or negative depending on the direction of decreasing vapor pressure. Depending on conditions, the supply airstream flowing through an ERV may gain heat energy (+qs) from the adjoining stream, but lose latent energy (−qL) if it transfers the water vapor to the adjoining stream. Heat and latent energy gain may be in the same or opposite direction. The total net energy gain is the difference between qs and qL, as shown in Example 1.

 

Example 1.

Inlet supply air enters an ERV with a flow rate of 9350 cfm at 95°F and 20% rh. Inlet exhaust air enters with a flow rate of 9050 cfm at 75°F and 50% rh. Assume that the energy exchanger was tested under ASHRAE Standard 84, which rated the sensible heat transfer effectiveness at 50% and the latent (water vapor) transfer effectiveness at 50%. Assuming the specific heat of air is 0.24 Btu/lb · °F and the latent heat of vaporization to be 1100 Btu/lb, determine the sensible, latent, and net energy gained by the exhaust air.

Solution:

From the psychrometric chart, the properties of air at 95°F and 20% rh are

and the properties of air at 75°F and 50% rh are

The mass flow rate at state 1 is obtained from

Similarly, the mass flow rate at state 3 is obtained from

These equal mass flow rates conform with ASHRAE Standard 84.

Exit temperatures of the airstreams can be obtained from the Equations (3a) and (3b) as follows:

The exit humidity of the airstreams is found from Equations (5a) and (5b) as follows:

The sensible heat gained by the exhaust stream is found from Equation (3c) as

The latent heat gained by the exhaust stream is found from Equation (8a) as

The net heat energy gained by the exhaust airstream is therefore

If the incoming outdoor air conditions had been at 95°F and 14% rh, then the net energy gained by the exhaust airstream would have been zero. The outlet exhaust airstream enthalpy at 85°F and 0.0082 lb/lb of dry air is given in the psychrometric chart as 29.4 Btu/lb. The net heat gained by the exhaust airstream [found from Equation (10)] is close to 945 Btu/min.


The fan power Ps required by the supply air is estimated from

(11)

The fan power Pe required by the exhaust air is estimated from

(12)

where

Ps

=

fan power for supply air, hp

Pe

=

fan power for exhaust air, hp

Δps

=

pressure drop of supply air caused by fluid friction, in. of water

Δpe

=

pressure drop of exhaust air caused by fluid friction, in. of water

ηf

=

overall efficiency of fan and motor or product of fan and motor efficiencies

However, the density and viscosity of air vary with the temperature. The variation of viscosity with temperature is given by the Sutherland law as

(13)

where

T

=

absolute temperature, °F

To

=

reference temperature, °F

S

=

constant = 198.7°F

Treating air as an ideal gas, the pressure drop Δp at any temperature T is related to the pressure drop Δpo at reference temperature To and is expressed as

(14)

Equation (14) is only accurate when the Reynolds number ReD for airflow through the exchanger is in the range

where

(15)

where

ρ

=

air density, lb/ft3

V

=

average velocity in flow channels, fpmm/s

Dh

=

hydraulic diameter of flow channels, ft

μ

=

dynamic viscosity at average temperature , lb/ft · min

For fully developed laminar flow through an energy exchanger (e.g., an energy wheel), the corresponding dimensionless pressure drop relation similar to Equation (14) is given as

(16)

where ReD < 2000.

Equations (14) and (16) cannot be used in the case of (1) flow channels that are not reasonably smooth; (2) flow Reynolds numbers that are out of range; (3) significant exchanger fouling caused by condensation, frost, or dust; (4) excessive nonuniform property distributions inside the exchanger; or (5) significant pressure deformation of the flow channels (e.g., some plate cross-flow exchangers).

The total pumping power P of the ERV can be given as

(17)

 Ideal Air-to-Air Energy Exchange

An ideal air-to-air energy exchanger

  • Allows temperature-driven heat transfer between participating airstreams

  • Allows partial-pressure-driven moisture transfer between the two streams

  • Minimizes cross-stream transfer of air, other gases (e.g., pollutants), biological contaminants, and particulates

  • Optimizes energy recovery performance to minimize pressure drop while providing reasonable cost, dimensions, and weight

Heat transfer is an important energy recovery vehicle from airstreams that carry waste heat. The role of moisture transfer as an energy recovery process is less well known and merits explanation.

Consider an air-to-air energy exchanger operating in a hot, humid climate in a comfort air-conditioning application. If the energy exchanger exchanges heat but not moisture, it cools outdoor ventilation air as it passes through the exchanger to the indoor space. Heat flows from the incoming outdoor air to the outgoing (and cooler) exhaust air drawn from the indoor conditioned space. This does very little to mitigate the high humidity carried into the indoor space by the outdoor ventilation air and may even increase the relative humidity in the conditioned space, resulting in increased refrigeration and/or reheat to dehumidify the air and achieve acceptable comfort conditions. On the other hand, if the energy exchanger transfers both heat and moisture, the humid outdoor supply air transfers moisture to the less-humid inside exhaust air as the streams pass through the energy exchanger. The lower humidity of the entering ventilation air requires less energy input for comfort conditioning.

3. AIRFLOW ARRANGEMENTS

Heat exchanger effectiveness depends heavily on the airflow direction and pattern of the supply and exhaust airstreams. Parallel-flow exchangers (Figure 2A), in which both airstreams move along heat exchange surfaces in the same direction, have a theoretical maximum effectiveness of 50%. Counterflow exchangers (Figure 2B), in which airstreams move in opposite directions, can have a theoretical effectiveness approaching 100%, but typical units have a lower effectiveness. Theoretical effectiveness for cross-flow heat exchangers is somewhat lower than for counterflow, and typical units have effectiveness of 50 to 70% (Figure 2C) and 60 to 85% for multiple-pass exchangers (Figure 2D).

In practice, construction limitations favor designs that use transverse flow (or cross-flow) over much of the heat exchange surface (Figures 2C and 2D).

 Effectiveness

Heat or energy exchange effectiveness as defined in Equation (1) is used to characterize each type of energy transfer in air-to-air exchangers. For a given set of inlet properties and flow rates, knowledge of each effectiveness allows the designer to calculate the sensible, latent, and total energy transfer rates using Equations (3c), (8c), and (10a), respectively. These effectiveness values can be determined either from measured test data or using correlations that have been verified in the peer-reviewed engineering literature. These correlations can also be used to predict energy transfer rates and outlet air properties for operating conditions different from those used for certification purposes. Predicting effectiveness for noncertified operating conditions using certified test data is the most common use of correlations for HVAC designs. Although correlations are not available for all types of air-to-air exchangers under all operating conditions, they are available for the most common types of air-to-air exchanger under operating conditions which have no condensation or frosting.

Heat Exchanger Airflow Configurations

Figure 2. Heat Exchanger Airflow Configurations


 Rate of Energy Transfer

The rate of energy transfer depends on the operating conditions and the intrinsic characteristics of the energy exchanger, such as the geometry of the exchanger (parallel flow/counterflow/cross-flow, number of passes, fins), thermal conductivity of walls separating the streams, and permeability of walls to various gases. As in a conventional heat exchanger, energy transfer between the airstreams is driven by cross-stream dry-bulb temperature differences. Energy is also transported piggyback-style between the streams by cross-stream mass transfer, which may include air, gases, and water vapor. In another mode of energy transfer, water vapor condenses into liquid in one of the two airstreams of the exchanger. The condensation process liberates the latent heat of condensation, which is transferred to the other stream as sensible heat; this two-step process is also called latent heat transfer.

Latent energy transfer between airstreams occurs only when moisture is transferred from one airstream to another without condensation, thereby maintaining the latent heat of condensation. Once moisture has crossed from one airstream to the other, it may either remain in the vapor state or condense in the second stream, depending on the temperature of that stream.

Rotating-wheel and permeable-walled flat-plate energy recovery units are used because of their moisture exchange function. Some cross-stream mass transfer may also occur through leakage even when such transfer is unintended. This may alter exchanger performance from its design value, but for most HVAC applications with exhaust air from occupied spaces, small transfers to the supply air are not important. However, these transfers can and should be evaluated during design, and in many cases can be controlled.

Heat transfer differs in principle from mass transfer. Heat transfer only occurs when there is a temperature difference. In the case of air-to-air exchange between the supply and exhaust airflow, heat transfer by conduction and convection only occurs when there is a temperature difference between these airstreams. Remember the following facts about heat/mass exchanger performance:

  • Effectiveness for moisture transfer may not equal the effectiveness for heat transfer.

  • Total energy effectiveness may not equal either the sensible or latent effectiveness.

Net total energy transfer and effectiveness need careful examination when the direction of sensible (temperature-driven) transfer is opposite to that of latent (moisture or water vapor) transfer.

ERV performance is expressed by the magnitudes of pumping power and sensible, latent, or total energy recovered. The energy recovered is estimated from the exit temperatures or humidity ratios, which are directly related to the effectiveness. Effectiveness is a function of two parameters: the number of transfer units (NTU) and thermal flow capacity ratio Cr.

(18)

(19)

where

U

=

overall heat transfer coefficient, related to flow rates and dimensions of fluid flow path in heat exchanger, Btu/h · ft2 · °F

A

=

area of heat exchanger, ft2

Cmax

=

maximum of mscps and mecpe

See Figure 9 for the variation of effectiveness with NTU for a rotary heat wheel. Variation of effectiveness is similar for plate exchangers.

4. ADDITIONAL TECHNICAL CONSIDERATIONS

The rated effectiveness of energy recovery units is obtained under balanced flow conditions (i.e., the flow rates of supply and exhaust airstreams are the same). However, these ideal conditions do not always exist, because of design for positive building pressure, air leakage, fouling, condensation, or frosting, and the following other factors.

 Air Leakage

Air leakage refers to any air that enters or leaves the supply or exhaust airstreams. Zero air leakage in either airstream would require m1 to equal m2 and m3 to equal m4. External air leakage occurs when the ambient air surrounding the energy recovery system leaks into (or exits) either or both airstreams. Internal air leakage occurs when holes or passages are open to the other airstream. Internal air leakage occurs when heat or energy exchanger design allows (1) tangential air movement in the wheel’s rotational direction and (2) air movement through holes in the barrier between airstreams. Under some pressure differentials, air leaks in and out of each airstream in nearly equal amounts, giving the illusion that there is no air leakage. Heat and water vapor transfer could appear to be greater than it actually is.

Leakage varies with heat exchanger type and design, airstream static pressure differences, and the physical condition of the heat exchanger (see Table 3). Air leakage is seldom zero because external and internal air pressures are usually different, causing air to leak from areas of higher pressure to those of lower pressure. Cross-leakage, cross-contamination, or mixing between supply and exhaust airstreams may occur in air-to-air heat exchangers and may be a significant problem if exhaust gases are toxic or odorous.

Air leakage between incoming fresh air and outgoing exhaust air can be classified into two mechanisms: cross-flow and carryover.

Cross-flow leakage is caused primarily by difference in static pressures between states 2 and 3 and/or between states 1 and 4, as shown in Figure 3. This is a major cause of cross-flow leakage, and underscores the importance of specifying precise locations for fans that circulate the airstreams. Cross-flow can also be caused by factors such as provisions for surging, geometrical irregularities, and local velocity distribution of the airstreams.

Carryover occurs in rotary recovery units because of wheel rotation out of one airstream into the other. Exhaust air trapped in cavities in the heat transfer medium is carried into the fresh airstream by the wheel’s rotation.

Air Leakage in Energy Recovery Units

Figure 3. Air Leakage in Energy Recovery Units


The test estimate of the air leakage is characterized by two dimensionless parameters: the exhaust air transfer ratio (EATR) and outdoor air correction factor (OACF). During these tests, m2 = m3, while an inert tracer gas is introduced at station 3 (Shang et al. 2001a):

(20)

where c1, c2, and c3 are the concentrations of inert gas at states 1, 2, and 3, respectively. EATR is the ratio of the concentration increase in supply air relative to the maximum concentration difference between stations 3 and 1. It is representative of the air mass leakage from exhaust air into supply air, when the air-to-air heat exchanger is operating at mass flow rates and static pressures equal to those at which the device was tested.

(21)

where m1 and m2 are the mass flow rates of the incoming fresh airstream at state 1 and 2, respectively. OACF gives the ratio of outdoor airflow required at the inlet (station 1) relative to the supply flow at 2 to compensate for air that leaks into or out of the exchanger, to meet the required net supply airflow to the building space, when the air-to-air heat exchanger is operating at mass flow rates and static pressures equal to those at which the device was tested.

Ideal operating conditions exist when there is no air leakage between the streams, EATR is close to zero, and OACF approaches 1. Deviations from ideal conditions indicate air leakage between the airstreams, which complicates the determination of accurate values for pressure drop and effectiveness. Methods to estimate actual flow rates at states 1, 2, 3, and 4 when air leakage exists and the values of the parameters EATR and OACF are known are discussed in Friedlander (2003) and Moffitt (2003). EATR and OACF must be determined when evaluating any HRV or ERV in which leakage between airstreams occurs, when evaluating the actual flow rate of outdoor air supplied for a given ventilation requirement, and when estimating the capacity of ventilator fans, as shown by the following.

 Air Capacity of Ventilator Fans

For a given ventilation requirement Qv, the density-corrected volume flow rate capacity Q1 of the supply fan is greater than Q2 if air leakage exists (see Figure 3).

In the following calculations, be sure to obtain the value for EATR that applies to the device when it operates at the airflow volumes and static pressure that will exist in the specific application. The leakage flow rate from the exhaust to the supply air can be estimated by the equation

If the ventilation requirement is Qv, then the actual volume flow rate of supply air to the space is calculated as

This may be simplified as

which gives the quantity of air entering the space. Assuming steady-state conditions, balanced flow through the energy recovery ventilator, the density corrected quantity of air leaving the building space (Q3) should be same as air supplied to the space Q2.

(22)

Combining Equation (22) and Equation (21) gives

(23)

Equation (23) gives the volume flow rate capacity of the intake, which equals the exhaust outlet for balanced airflow. [Fan capacity depends on location. This statement only applies to the supply fan at station 1 (blow-through); its capacity would change at station 2 (draw-through).]

 Pressure Drop

Pressure drop for each airstream through an energy recovery unit depends on many factors, including exchanger design, mass flow rate, temperature, moisture, and inlet and outlet air connections. The pressure drop must be overcome by fans or blowers. Because the power required for circulating airstreams through the recovery unit is directly proportional to the pressure drop, the pressure drop through the energy recovery unit should be known. The pressure drop may be used with the fan efficiency to characterize the energy used by the exchanger and in turn the efficiency (not effectiveness) of an application.

 Maintenance

The method used to clean a heat exchanger depends on the transfer medium or mechanism used in the energy recovery unit and on the nature of the material to be removed. Grease build-up from kitchen exhaust, for example, is often removed with an automatic water-wash system. Other kinds of dirt may be removed by vacuuming, blowing compressed air through the passages, steam cleaning, manual spray cleaning, soaking the units in soapy water or solvents, or using soot blowers. The cleaning method should be determined during design so that a compatible heat exchanger can be selected.

Cleaning frequency depends on the quality of the exhaust airstream. Residential and commercial HVAC systems generally require only infrequent cleaning; industrial systems, usually more. Consult equipment suppliers about the specific cleaning and maintenance requirements of systems being considered.

 Filtration

Filters are recommended and should be placed in both the supply and exhaust airstreams to reduce fouling and thus the frequency of cleaning. Exhaust filters are especially important if the contaminants are sticky or greasy or if particulates can plug airflow passages in the exchanger. Supply filters eliminate insects, leaves, and other foreign materials, thus protecting both the heat exchanger and air-conditioning equipment. Snow or frost can block the air supply filter and cause severe problems. Specify steps to ensure a continuous flow of supply air.

 Controls

Heat exchanger controls may control frost formation or regulate the amount of energy transferred between airstreams at specified operating conditions. For example, ventilation systems designed to maintain specific indoor conditions at extreme outdoor design conditions may require energy recovery modulation to provide an economizer function, to prevent overheating ventilation supply air during cool to moderate weather or to prevent overhumidification. Modulation methods include tilting heat pipes, changing rotational speeds of (or stopping) heat wheels, or bypassing part of one airstream around the heat exchanger using dampers (i.e., changing the supply-to-exhaust mass airflow ratio).

 Fouling

Fouling, an accumulation of dust or condensates on heat exchanger surfaces, reduces heat exchanger performance by increasing resistance to airflow, interfering with mass transfer, and generally decreasing heat transfer coefficients. Increased resistance to airflow increases fan power requirements and may reduce airflow.

Increased pressure drop across the heat exchanger core can indicate fouling and, with experience, may be used to establish cleaning schedules. Reduced mass transfer performance (latent effectiveness) indicates fouling of permeable membranes or desiccant sorption sites. Heat exchanger surfaces must be kept clean to maximize system performance.

 Corrosion

Process exhaust frequently contains corrosive substances. If it is not known which construction materials are most corrosion resistant for an application, the user and/or designer should examine on-site ductwork, review literature, and contact equipment suppliers before selecting materials. A corrosion study of heat exchanger construction materials in the proposed operating environment may be warranted if installation costs are high and the environment is corrosive. Experimental procedures for such studies are described in an ASHRAE symposium (ASHRAE 1982). Often contaminants not directly related to the process are present in the exhaust airstream (e.g., welding fumes or paint carryover from adjacent processes).

Moderate corrosion generally occurs over time, roughening metal surfaces and increasing their heat transfer coefficients. Severe corrosion reduces overall heat transfer and can cause cross-leakage between airstreams because of perforation or mechanical failure.

 Condensation and Freeze-Up

Condensation, ice formation, and/or frosting may occur on heat exchange surfaces. Ignoring entrance and exit effects, four distinct air/moisture regimes may occur as the warm airstream cools from its inlet condition to its outlet condition. First, there is a dry region with no condensate. Once the warm airstream cools below its dew point, there is a condensing region, which wets the heat exchange surfaces. If the heat exchange surfaces fall below freezing, the condensation freezes. Finally, if the warm airstream temperature falls below its dew point and is also below freezing temperature, sublimation causes frost to form. The locations of these regions and rates of condensation and frosting depend on the duration of frosting conditions; airflow rates; inlet air temperature and humidity; heat exchanger core temperature; heat exchanger effectiveness; geometry, configuration, and orientation; and heat transfer coefficients.

Sensible heat exchangers, which are ideally suited to applications in which heat transfer is desired but humidity transfer is not (e.g., swimming pools, kitchens, drying ovens), can benefit from the latent heat released by the exhaust gas when condensation occurs. One pound of moisture condensed transfers about 1050 Btu to the incoming air at room temperature. Equipment design should provide for continuous draining of the condensate from the unit. Transfer of latent heat occurs at the point of condensation, and little available energy remains in the condensate.

Condensation increases the heat transfer rate and thus the sensible effectiveness; it can also significantly increase pressure drops in heat exchangers with narrow airflow passage spacing. Frosting fouls the heat exchanger surfaces, which initially improves energy transfer but subsequently restricts the exhaust airflow, which in turn reduces the energy transfer rate. In extreme cases, the exhaust airflow (and supply, in the case of heat wheels) can become blocked. Defrosting a fully blocked heat exchanger requires that the unit be shut down for an extended period. As water cools and forms ice, it expands, which may seriously damage the heat exchanger core unless the water is entirely removed.

For frosting or icing to occur, an airstream must be cooled to a dew point below 32°F. Enthalpy exchangers transfer moisture from the airstream with higher moisture content (usually the warmer airstream) to the less humid one. As a result, frosting or icing occurs at lower supply air temperatures in enthalpy exchangers than in sensible heat exchangers. Cross-flow heat exchangers are more frost tolerant than other plate exchangers because frost blockage only occurs over a fraction of the exchanger exhaust airflow passages.

For these reasons, some form of freeze control must be incorporated into heat exchangers that are expected to operate under freezing conditions. Frosting and icing can be prevented by preheating supply air or reducing heat exchanger effectiveness (e.g., reducing heat wheel speed, tilting heat pipes, bypassing some supply air around the heat exchanger). Alternatively, the heat exchanger may be periodically defrosted. Manufacturers of commercially available packaged heat or energy ventilators routinely incorporate frosting control strategies or mechanisms appropriate to their equipment and its targeted application.

ASHRAE research project RP-543 discusses performance of several freeze control strategies (Phillips et al. 1989a, 1989b). ASHRAE research project RP-544 (Barringer and McGugan 1989a, 1989b) covers performance of enthalpy heat exchangers. Many effective defrost strategies have been developed for residential air-to-air heat exchangers, and may also be applied to commercial installations. Phillips et al. (1992) describe frost control strategies and their impact on energy performance in various climates.

If cyclic frost methods are used, the defrost period should be long enough to completely remove the frost, ice, and water during each defrost period.

Total heat exchangers transfer moisture from the more humid airstream to the less humid one. In winter, this results in an exhaust stream that is partially dehumidified as it is cooled. As a result, frosting or icing generally occurs at lower temperatures than in sensible-only heat exchangers. On the other hand, sensible heat exchangers can benefit from the latent heat released in a high-humid-exhaust airstream when condensation occurs.

See the Bibliography for sources of more information on frost growth and control.

5. PERFORMANCE RATINGS

Standard laboratory rating tests and predictive computer models give exchanger performance values for (1) heat transfer, (2) moisture transfer, (3) cross-stream air transfer, (4) average exhaust mass airflow, and (5) supply mass airflow leaving the exchanger. Effectiveness ratios for heat and mass water vapor transfer must be separately determined by rating tests in a laboratory that is staffed and instrumented to meet requirements of ASHRAE Standard 84 and AHRI Standard 1060. It may be very difficult to adhere to any standard when field tests are made.

ASHRAE Standard 84 (1) establishes a uniform method of testing for obtaining performance data; (2) specifies the data required, calculations to be used, and reporting procedures for testing each of seven independent performance factors and their uncertainty limits; and (3) specifies the types of test equipment. The independent performance factors are sensible (εs), latent (εl), and total (εt) effectivenesses; supply (ΔPs) and exhaust (ΔPe) air pressure drops; exhaust air transfer ratio (EATR), which characterizes the fraction of exhaust air transferred to the supply air; and outdoor air correction factor (OACF), which is the ratio of supply inlet to outlet airflow.

AHRI Standard 1060 is an industry-established standard for rating air-to-air heat/energy exchanger performance for use in energy recovery ventilation equipment. This standard, based on ASHRAE Standard 84, establishes definitions, requirements for marking and nameplate data, and conformance conditions intended for the industry, including manufacturers, engineers, installers, contractors, and users. Standard temperature and humidity conditions at which equipment tests are to be conducted are specified for summer and winter conditions. Published ratings must be reported for each of the seven performance factors specified in ASHRAE Standard 84. The ARI certification program using Standard 1060 is used to verify ratings published by manufacturers.

AHRI Standard 1060 requires balanced airflow rates (see Figure 3) and the following conditions:

Winter:

Outdoor air at t1 = 35°F and tw1 = 33°F

Indoor (room) air at t3 = 67°F

tw3 = 58°F and p2p3 = 0

Summer:

Outdoor air at t1 = 95°F and tw1 = 78°F

Indoor (room) air at t3 = 75°F

tw3 = 63°F and p2p3 = 0

Balanced mass airflows, as required for parts of the ASHRAE and AHRI standard test methods, are rarely achieved in field operation for air-handling systems. Fans are nearly constant-volume devices usually designed to run at a preset rpm. Significantly more mass airflow is transported in cold (winter) conditions than in hot (summer) conditions.

For estimating changes in exchanger performance factors at each operating condition, ASHRAE Standard 84 specifies knowledge of seven performance factors (i.e., ΔPs, ΔPe, εs, εL, εt, EATR, and OACF), but AHRI Standard 1060 certifies performance at only a few standard operating conditions. At other operating conditions, these performance factors must be extrapolated using accepted correlations.

Variables that can affect these performance factors for total energy transfer or sensible heat transfer devices include (1) water vapor partial-pressure differences; (2) heat transfer area; (3) air velocity or mass flow rates through the heat exchangers; (4) airflow arrangement or geometric configuration, or characteristic dimension of the flow passage through the recovery ventilator; and (5) method of frost control. The effect of frost control method on seasonal performance is discussed in Phillips et al. (1989a), and sensible versus latent heat recovery for residential comfort-to-comfort applications is addressed in Barringer and McGugan (1989b).

Current testing standards do not validate exchanger performance for testing conditions that require freezing or condensing temperatures, unbalanced airflow ratios, high pressure differentials, or air leakage rates based on varying the inputs. An alternative test setup using a multifunction wind tunnel facility is presented by Sparrow et al. (2001) to provide comprehensive performance data for conditions other than existing standards.

6. TYPES AND APPLICATIONS OF AIR-TO-AIR HEAT EXCHANGERS

 Fixed-Plate Heat Exchangers

Plate exchangers are available in many configurations, materials, sizes, and flow patterns. Many have modules that can be arranged to handle almost any airflow, effectiveness, and pressure drop requirement. Plates are formed with spacers or separators (e.g., ribs, dimples, ovals) constructed into the plates or with external separators (e.g., supports, braces, corrugations). Airstream separations are sealed by folding, multiple folding, gluing, cementing, welding, or any combination of these, depending on the application and manufacturer. Ease of access for examining and cleaning heat transfer surfaces depends on the configuration and installation.

Heat transfer resistance through the plates is small compared to the airstream boundary layer resistance on each side of the plates. Heat transfer efficiency is not substantially affected by the heat transfer coefficient of the plates. Aluminum is the most popular plate construction material because of its nonflammability and durability. Polymer plate exchangers may improve heat transfer by causing some turbulence in the channel flow, and are popular because of their corrosion resistance and cost-effectiveness. Steel alloys are used for temperatures over 400°F and for specialized applications where cost is not a key factor. Plate exchangers normally conduct sensible heat only; however, water-vapor-permeable materials, such as treated paper and microporous polymeric membranes, may be used to transfer moisture, thus providing total (enthalpy) energy exchange.

Most manufacturers offer modular plate exchangers. Modules range in capacity from 25 to 10,000 cfm and can be arranged into configurations exceeding 100,000 cfm. Multiple sizes and configurations allow selections to meet space and performance requirements.

Plate spacing ranges from 0.1 to 0.5 in., depending on the design and application. Heat is transferred directly from the warm airstreams through the separating plates into the cool airstreams. Usually design, construction, and cost restrictions result in the selection of cross-flow exchangers, but additional counterflow patterns can increase heat transfer effectiveness.

Normally, both latent heat of condensation (from moisture condensed as the temperature of the warm exhaust airstream drops below its dew point) and sensible heat are conducted through the separating plates into the cool supply airstream. Thus, energy is transferred but moisture is not. Recovering 80% or more of the available waste exhaust heat is possible.

Fixed-plate heat exchangers can achieve high sensible heat recovery and total energy effectiveness because they have only a primary heat transfer surface area separating the airstreams and are therefore not inhibited by the additional secondary resistance (e.g., pumping liquid, in runaround systems or transporting a heat transfer medium) inherent in some other exchanger types. In a cross-flow arrangement (Figure 4), they usually do not have sensible effectiveness greater than 75% unless two devices are used in series as shown in Figure 2D.

One advantage of the plate exchanger is that it is a static device with little or no leakage between airstreams. As velocity increases, the pressure difference between the two airstreams increases (Figure 5). High differential pressures may deform the separating plates and, if excessive, can permanently damage the exchanger, significantly reducing the airflow rate on the low-pressure side as well as the effectiveness and possibly causing excessive air leakage. This is not normally a problem because differential pressures in most applications are less than 4 in. of water. In applications requiring high air velocities, high static pressures, or both, plate exchangers built to withstand these conditions are available and should be specified.

Fixed-Plate Cross-Flow Heat Exchanger

Figure 4. Fixed-Plate Cross-Flow Heat Exchanger


Variation of Pressure Drop and Effectiveness with Airflow Rates for Membrane Plate Exchanger

Figure 5. Variation of Pressure Drop and Effectiveness with Airflow Rates for Membrane Plate Exchanger


Most sensible plate exchangers have condensate drains, which remove condensate and also wastewater in water-wash systems. Heat recovered from a high-humidity exhaust is better returned to a building or process by a sensible heat exchanger rather than an enthalpy exchanger if humidity transfer is not desired.

Frosting can be controlled by preheating incoming supply air, bypassing part of the incoming air, recirculating supply air through the exhaust side of the exchanger, or temporarily interrupting supply air while maintaining exhaust. However, frost on cross-flow heat exchangers is less likely to block the exhaust airflow completely than with other types of exchangers. Generally, frost should be avoided unless a defrost cycle is included.

Fixed-plate heat exchangers can be made from permeable microporous membranes designed to maximize moisture and energy transfer between airstreams while minimizing air transfer. Suitable permeable microporous membranes for this emerging technology include cellulose, polymers, and other synthetic materials such as hydrophilic electrolyte. Hydrophilic electrolytes are made from sulphonation chemistry techniques and contain charged ions that attract polar water molecules; adsorption and desorption of water occur in vapor state.

Airstreams exiting a cross-flow plate exchanger display temperature stratification when there is a temperature difference between the two airstreams (Figure 6) Enthalpy plate exchangers will also display humidity stratification. This should be considered if the temperature of one of these airstreams is to be measured (e.g., to control operation of downstream conditioning equipment or of a defrost mechanism).

Typical Temperature Stratification at Outlets of Cross-Flow Heat Exchanger

Figure 6. Typical Temperature Stratification at Outlets of Cross-Flow Heat Exchanger


 Rotary Air-to-Air Energy Exchangers

A rotary air-to-air energy exchanger, or rotary enthalpy wheel, has a revolving cylinder filled with an air-permeable medium having a large internal surface area. Adjacent supply and exhaust airstreams each flow through half the exchanger in a counterflow pattern (Figure 7). Heat transfer media may be selected to recover sensible heat only or total (sensible plus latent) heat.

Sensible heat is transferred as the medium picks up and stores heat from the hot airstream and releases it to the cold one. Latent heat is transferred as the medium adsorbs water vapor from the higher-humidity airstream and desorbs moisture into the lower-humidity airstream, driven in each case by the vapor pressure difference between the airstream and energy exchange medium. Thus, the moist air is dried while the drier air is humidified. In total heat transfer, both sensible and latent heat transfer occur simultaneously. Sensible-only wheels (not coated with desiccant) can also transfer water via a mechanism of condensation and reevaporation driven by dew point and vapor pressure; the effectiveness varies strongly with conditions. Because rotary exchangers have a counterflow configuration and normally use small-diameter flow passages, they are quite compact and can achieve high transfer effectiveness.

Air contaminants, dew point, exhaust air temperature, and supply air properties influence the choice of materials for the casing, rotor structure, and medium of a rotary energy exchanger. Aluminum, steel, and polymers are the usual structural, casing, and rotor materials for normal comfort ventilating systems. Exchanger media are fabricated from metal, mineral, or synthetic materials and provide either random or directionally oriented flow through their structures.

Rotary Air-to-Air Energy Exchanger

Figure 7. Rotary Air-to-Air Energy Exchanger


Random-flow media are made by knitting wire into an open woven cloth or corrugated mesh, which is layered to the desired configuration. Aluminum mesh is packed in pie-shaped wheel segments. Stainless steel and monel mesh are used for high-temperature and corrosive applications. These media should only be used with clean, filtered airstreams because they plug easily. Random-flow media also require a significantly larger face area than directionally oriented media for a given airflow and pressure drop.

Directionally oriented media are available in various geometric configurations. The most common consist of small (0.06 to 0.08 in.) air passages parallel to the direction of airflow. Air passages are very similar in performance regardless of their shape (triangular, hexagonal, parallel plate, or other). Aluminum foil, paper, plastic, and synthetic materials are used for low and medium temperatures. Stainless steel and ceramics are used for high temperatures and corrosive atmospheres.

Media surface areas exposed to airflow vary from 100 to 1000 ft2/ft3, depending on the type of medium and physical configuration. Media may also be classified by their ability to recover sensible heat only or total heat. Media for sensible heat recovery are made of aluminum, copper, stainless steel, and monel. Media for total heat recovery can be from any of a number of materials and treated with a desiccant (typically zeolites, molecular sieves, silica gels, activated alumina, titanium silicate, synthetic polymers, lithium chloride, or aluminum oxide) to have specific moisture recovery characteristics.

 Cross-Leakage.
 Cross-leakage (mixing between supply and exhaust airstreams) can occur in all rotary energy exchangers by two mechanisms: carryover and seal leakage. Cross leakage can be reduced by placing the blowers so that they promote leakage of outdoor air to the exhaust airstream. A purge section also can be installed on the heat exchanger to reduce cross leakage.

In many applications, recirculating some air is not a concern. However, critical applications such as hospital operating rooms, laboratories, and cleanrooms require stringent control of carryover. Carryover can be reduced to less than 0.1% of the exhaust airflow with a purge section but cannot be completely eliminated.

The theoretical carryover of a wheel without a purge section is directly proportional to the speed of the wheel and the void volume of the medium (75 to 95% void, depending on type and configuration). For example, a 10 ft diameter, 8 in. deep wheel with a 90% void volume operating at 14 rpm has a carryover volumetric flow of

If the wheel is handling a 20,000 cfm balanced flow, the percentage carryover is

The exhaust fan, which is usually located at the exit of the exchanger, should be sized to include leakage and purge airflows.

 Control.
 Two control methods are commonly used to regulate wheel energy recovery. In supply or exhaust air bypass control, the amount of supply air allowed to pass through the wheel establishes the supply air temperature. An air bypass damper, controlled by a wheel supply air discharge temperature sensor, regulates the proportion of supply air permitted to bypass the exchanger.

The second method regulates the energy recovery rate by varying wheel rotational speed. The most frequently used variable-speed drives are (1) a silicon controlled rectifier (SCR) with variable-speed dc motor, (2) a constant-speed ac motor with hysteresis coupling, and (3) an ac frequency inverter with an ac induction motor. The dehumidification capacity and reheating effectiveness of a energy wheel can be varied by changing the wheel speed (Figure 8A) or by bypassing air around the wheel (Figure 8B) (Moffitt 2010). Figure 8A is a typical capacity curve for varying the wheel’s rotation speed when the outdoor air is cooler and drier than the exhaust air; when outdoor air conditions are cooler and more humid, capacity may increase at low speeds (Simonson et al. 2000).

Figure 9 shows the effectiveness ε, sensible heat transfer only, with balanced airflow, convection-conduction ratio less than 4, and no leakage or cross-flow, of a regenerative counterflow heat wheel versus number of transfer units (NTU). This simple example of a regenerative wheel also shows that regenerative counterflow rotary effectiveness increases with wheel speed (Cr is proportional to wheel speed), but there is no advantage in going beyond Cr/Cmin = 5 because the carryover of contaminants increases with wheel speed. See Kays and Crawford (1993) or Shah (1981) for details.

Latent and Sensible Effectiveness Versus (A) Wheel Speed and (B) Bypassed Air (Moffitt 2010)

Figure 8. Latent and Sensible Effectiveness Versus (A) Wheel Speed and (B) Bypassed Air

(Moffitt 2010)


Rotary energy or enthalpy wheels are more complex than heat wheels, but recent research has characterized their behavior using laboratory and field data (Johnson et al. 1998).

A dead band control, which stops or limits the exchanger, may be necessary when no recovery is desired (e.g., when outdoor air temperature is higher than the required supply air temperature but below the exhaust air temperature). When outdoor air temperature is above the exhaust air temperature, the equipment operates at full capacity to cool incoming air. During very cold weather, it may be necessary to heat the supply air, stop the wheel, or, in small systems, use a defrost cycle for frost control.

Rotary enthalpy wheels require little maintenance and tend to be self-cleaning because the airflow direction is reversed for each rotation of the wheel. The following maintenance procedures ensure best performance:

  • Clean the medium when lint, dust, or other foreign materials build up, following the manufacturer’s instructions.

  • Maintain drive motor and train according to the manufacturer’s recommendations. Speed-control motors that have commutators and brushes require more frequent inspection and maintenance than induction motors. Brushes should be replaced, and the commutator should be periodically turned and undercut.

  • Inspect wheels regularly for proper belt or chain tension.

  • Refer to the manufacturer’s recommendations for spare and replacement parts.

 Systems with Multiple Energy Recovery Exchangers

Multiple exchangers are often used in air-handling systems that have a cooling coil, to enhance dehumidification capability. The first air-to-air exchanger in the outdoor airstream is used to recover exhaust energy and reduce the required coil capacity. The second exchanger’s purpose is to increase the coil’s latent removal. This second exchanger is either a sensible heat exchanger or a passive desiccant wheel. A sensible exchanger (e.g., coil loop, plate exchanger, heat pipe, wheel) reheats the air as it leaves the cooling coil. This simultaneously precools the return air. The cooled return air that is exhausted then precools the outdoor air by passing through the first exchanger. A passive dehumidification wheel works similarly: it re-moves water vapor from air leaving the coil and transfers the vapor, with some heat, to the return air. The second exchanger can be in parallel with the first exchanger, as shown in Figure 10 (Moffitt 2011). The corresponding processes are shown in Figure 11 (Moffitt 2011); use of a passive desiccant wheel is shown on the right side of the figure.

Effectiveness of Counterflow Regenerator (Shah 1981)

Figure 9. Effectiveness of Counterflow Regenerator
(Shah 1981)


The second exchanger can also be placed in series with the cooling coil as shown in Figure 12 (Moffitt 2011), where it has a similar effect. The first exchanger reduces the cooling capacity by recovery exhaust energy. The second exchanger improves latent cooling and reduces the sensible cooling delivered by the system. The corresponding processes are shown in Figure 13 (Moffitt 2011); use of a passive desiccant wheel is shown on the right side of the figure.

Multiple Energy Recovery Exchangers in Parallel Mode (Moffitt 2011)

Figure 10. Multiple Energy Recovery Exchangers in Parallel Mode
(Moffitt 2011)


 Coil Energy Recovery (Runaround) Loops

A typical coil energy recovery loop (Figure 14) places extended-surface, finned-tube water coils in the supply and exhaust airstreams of a building or process. The coils are connected in a closed loop by counterflow piping through which an intermediate heat transfer fluid (typically water or antifreeze solution) is pumped.

Psychrometric Processes of Exchangers in Parallel Mode (Moffitt 2011)

Figure 11. Psychrometric Processes of Exchangers in Parallel Mode
(Moffitt 2011)


Moisture must not freeze in the exhaust coil air passage. A dual-purpose, three-way temperature control valve prevents the exhaust coil from freezing. The valve is controlled to maintain the temperature of solution entering the exhaust coil at 40°F or above. This condition is maintained by bypassing some of the warmer solution around the supply air coil. The valve can also ensure that a prescribed air temperature from the supply air coil is not exceeded.

Multiple Energy Recovery Exchangers in Series Mode (Moffitt 2011)

Figure 12. Multiple Energy Recovery Exchangers in Series Mode
(Moffitt 2011)


Coil energy recovery loops are highly flexible and well suited to renovation and industrial applications. The loop accommodates remote supply and exhaust ducts and allows simultaneous transfer of energy between multiple sources and uses. An expansion tank must be included to allow fluid expansion and contraction. A closed expansion tank minimizes oxidation when ethylene glycol is used.

Standard finned-tube water coils may be used; however, these need to be selected using an accurate simulation model if high effectiveness and low costs are needed (Johnson et al. 1995). Integrating runaround loops in buildings with variable loads to achieve maximum benefits may require combining the runaround simulation with building energy simulation (Dhital et al. 1995). Manufacturers’ design curves and performance data should be used when selecting coils, face velocities, and pressure drops, but only when the design data are for the same temperature and operating conditions as in the runaround loop.

The coil energy recovery loop cannot transfer moisture between airstreams; however, indirect evaporative cooling can reduce the exhaust air temperature, which significantly reduces cooling loads. For the most cost-effective operation, with equal airflow rates and no condensation, typical effectiveness values range from 45 to 65%. The highest effectiveness does not necessarily give the greatest net life-cycle cost saving.

Typically, the sensible heat effectiveness of a coil energy recovery loop is independent of the outdoor air temperature. However, when the capacity is controlled, the sensible heat effectiveness decreases.

Coil energy recovery loops use coils constructed to suit their environment and operating conditions. For typical comfort-to-comfort applications, standard coil construction usually suffices. In process-to-process and process-to-comfort applications, the effect of high temperature, condensable gases, corrosives, and contaminants on the coil(s) must be considered. Above 400°F, special construction may be required to ensure a permanent fin-to-tube bond. The effects of condensable gases and other adverse factors may require special coil construction and/or coatings. Chapters 23 and 27 discuss the construction and selection of coils in more detail.

Complete separation of the airstreams eliminates cross-contamination between the supply and exhaust air.

Coil energy recovery loops require little maintenance. The only moving parts are the circulation pump and three-way control valve. However, to ensure optimum operation, the air should be filtered, the coil surface cleaned regularly, the pump and valve maintained, and the transfer fluid refilled or replaced periodically. Fluid manufacturers or their representatives should be contacted for specific recommendations.

The thermal transfer fluid selected for a closed-loop exchanger depends on the application and on the temperatures of the two airstreams. An inhibited ethylene glycol solution in water is common when freeze protection is required. These solutions break down to an acidic sludge at temperatures above 275°F. If freeze protection is needed and exhaust air temperatures exceed 275°F, a nonaqueous synthetic heat transfer fluid should be used. Heat transfer fluid manufacturers and chemical suppliers should recommend appropriate fluids.

 Desiccant and Heat Wheel Systems

The Center for Climate and Energy Solutions’ 2015 international conference on climate change emphasized reducing greenhouse gas emissions and requiring more efficient equipment, including HVAC systems (which consume significant electrical power) (C2ES 2015). Sensible and desiccant wheels can be used in combination with a heat pump direct evaporative cooler (DEC) to achieve this goal, as shown in the following cases.

Psychrometric Processes of Exchangers in Series Mode (Moffitt 2011)

Figure 13. Psychrometric Processes of Exchangers in Series Mode
(Moffitt 2011)


The heat dissipated in the condenser of a heat pump can be used to regenerate the desiccant wheel (Sheng et al. 2015) and has a potential of significant energy cost savings. At design conditions for Atlanta, Georgia, for a 100% replacement air system as shown in Figure 15, this approach can reduce cooling capacity requirements by 52% and net electrical shaft power requirements by more than 24% compared to the conventional vapor-compression system (Dhamshala 2016).

Coil Energy Recovery Loop

Figure 14. Coil Energy Recovery Loop


Heat Pump Augmented by Heat and Desiccant Wheels (Damshala 2016)

Figure 15. Heat Pump Augmented by Heat and Desiccant Wheels
(Damshala 2016)


Figure 16 shows an advanced desiccant system for 100% outdoor supply air (OSA) mode with heat and desiccant wheels and direct evaporative cooler (DEC) in combination with a heat pump. This system could reduce cooling capacity requirements by 59% and net electrical shaft power requirements by close to 30% at the same design conditions as for Figure 15 (Dhamshala 2016).

Heat Pump Augmented by Evaporative Cooler and Heat and Desiccant Wheels

Figure 16. Heat Pump Augmented by Evaporative Cooler and Heat and Desiccant Wheels


A simplified system suitable for surgery rooms (able to provide optimum temperature and humidity control) consists of a preheater, desiccant wheel with type 3 desiccant, and a cooling coil, as shown in Figure 17. The type 3 desiccant in the desiccant wheel has a large affinity to adsorb water vapor when the relative humidity of the air is high (as it is in states 6 and 7), whereas it gives off moisture at states 4 and 5 (which have lower humidity). The simplicity of this system not only reduces maintenance costs but can also save significant energy costs.

System for Surgery Room (based on concepts presented in Murphy 2006)

Figure 17. System for Surgery Room
(based on concepts presented in Murphy 2006)


A desiccant system consisting of two evaporative coolers and heat and desiccant wheels for a 100% replacement air application, as shown in Figure 18, could provide all the space summer cooling needs without the use of an air conditioner. This system can reduce net electrical power requirements by more than 90% at design conditions for the city of Phoenix, Arizona (Dhamshala 2016). The only electrical power required is for the fan power and rotation of the wheels. The magnitude of estimated electrical power savings should be of similar range for the entire dry (B) region of the ASHRAE climatic zones, with small differences.

Desiccant System of Evaporative Coolers and Heat and Desiccant Wheels

Figure 18. Desiccant System of Evaporative Coolers and Heat and Desiccant Wheels


Note that the minuscule heat energy required (6.15 kW) in the heater can easily be obtained from an air-to-air heat exchanger using outdoor air (which, at 103°F, exceeds the minimum temperature) before it enters the desiccant wheel. The cost of water supplied to the evaporative coolers is estimated to be negligible.

Accurate estimates of energy cost savings over a year can be obtained through detailed computer simulations of systems for a specific building with given building loads using the hourly weather data. Highly specialized desiccant systems using a DOAS can be designed to serve the buildings with specific loads or needs (Moffitt 2015). Sultan et al. 2015 provide an overview of various widely used solid-desiccant air systems.

Ge et al. (2015), Tu et al. (2015), and Zeng et al. (2014) found that two-stage desiccant systems can be designed to use low-grade heat energy resources, such as waste energy at the site or solar collectors, which can yield greater energy cost savings.

To best use existing energy resources available at a specific temperature or grade, perform a series of second-law analyses on a variety of desiccant systems (including a two-stage unit) to find the maximum energy cost savings and to identify the components of the system that have largest exergy destruction (Enteria et al. 2013; Liu et al. 2016; Tu et al. 2015a, 2015b).

An emerging technology combining liquid-desiccant solutions (e.g., lithium chloride) with an evaporative cooler has the potential to save significant energy costs (Gao et al. 2015). A simplified schematic suitable for use in various climates is shown in Figure 19.

The process air consisting of outdoor air mixed with return air enters the dehumidifier at state 2 and leaves the dehumidifier at state 3. Three additional fluid streams are also supplied to the dehumidifier: (1) the strong liquid desiccant solution entering at state 8 and leaving as a weak solution of desiccant at state 9 after absorbing moisture from the process air, (2) the water stream entering at state 11 through the nozzle and leaving at state 12 to cool the liquid desiccant and the process air, and (3) a stream of outdoor air entering at state 6 and leaving the dehumidifier at state 7. The evaporative cooler is supplied with water entering at state 10 that cools the process air. A fraction of process air leaving the cooler is rerouted through the cooler, which is sprayed with water entering the cooler.

Schematic of Liquid Desiccant System and Evaporative Cooler (NREL)

Figure 19. Schematic of Liquid Desiccant System and Evaporative Cooler
(NREL)


Heat energy is required to regenerate the liquid desiccant solution; it can use waste heat energy, if available at the site, or use solar collectors. A combination of heat and desiccant wheels with this liquid-desiccant system might provide an economical system that is environmentally friendly.

 Heat Pipe Heat Exchangers

Figure 20 shows a typical heat pipe assembly. Hot air flowing over the evaporator end of the heat pipe vaporizes the working fluid. A vapor pressure gradient drives the vapor to the condenser end of the heat pipe tube, where the vapor condenses, releasing the latent energy of vaporization (Figure 21). The condensed fluid is wicked or flows back to the evaporator, where it is revaporized, thus completing the cycle. Thus the heat pipe’s working fluid operates in a closed-loop evaporation/condensation cycle that continues as long as there is a temperature difference to drive the process. Using this mechanism, the heat transfer rate along a heat pipe is up to 1000 times greater than through copper (Ruch 1976).

Heat Pipe Assembly

Figure 20. Heat Pipe Assembly


Energy transfer in heat pipes is often considered isothermal. However, there is a small temperature drop through the tube wall, wick, and fluid medium. Heat pipes have a finite heat transfer capacity that is affected by factors such as wick design, tube diameter, working fluid, and tube (heat pipe) orientation relative to horizontal. In current designs, a wick is replaced by circumferential grooves that facilitate capillary-action flow of condensed refrigerant back to the evaporator section.

Heat Pipe Operation

Figure 21. Heat Pipe Operation


HVAC systems use copper or aluminum heat pipe tubes with aluminum or copper fins. Fin designs include continuous corrugated plate, continuous plain, and spiral. Modifying fin design and tube spacing changes pressure drop at a given face velocity.

For process-to-comfort applications with large temperature changes, tubes and fins are usually constructed of the same material to avoid problems with different thermal expansions of materials. Heat pipe heat exchangers for exhaust temperatures below 425°F are most often constructed with aluminum tubes and fins. Protective coatings allow inexpensive aluminum to replace exotic metals in corrosive atmospheres; these coatings have a minimal effect on thermal performance.

Heat pipe heat exchangers for use above 425°F are generally constructed with steel tubes and fins. The fins are often aluminized to prevent rusting. Composite systems for special applications may be created by assembling units with different materials and/or different working fluids.

Selecting the proper working fluid for a heat pipe is critical to long-term operation. The working fluid should have high latent heat of vaporization, a high surface tension, and a low liquid viscosity over the operating range; it must be thermally stable at operating temperatures. Decomposition of the thermal fluids can form noncondensable gases that deteriorate performance. For low-temperature applications, gases such as helium can be used as working fluid; for moderate temperatures, commercial refrigerants and liquids such as water can be used; and for high temperatures, liquid metals such as sodium or mercury can be used.

Heat pipe heat exchangers typically have no cross-contamination for pressure differentials between airstreams of up to 50 in. of water. A vented double-wall partition between the airstreams can provide additional protection against cross contamination. If an exhaust duct is attached to the partition space, any leakage is usually withdrawn and exhausted from the space between the two ducts.

Heat Pipe Exchanger Effectiveness

Figure 22. Heat Pipe Exchanger Effectiveness


Heat pipe heat transfer capacity depends on design and orientation. Figure 22 shows a typical effectiveness curves for various face velocities and rows of tubes. As the number of rows increases, effectiveness increases at a decreasing rate. For example, doubling the number of rows of tubes in a 60% effective heat exchanger increases the effectiveness to 75%. The effectiveness of a counterflow heat pipe heat exchanger depends on the total number of rows such that two units in series yield the same effectiveness as a single unit of the same total number of rows. Series units are often used to facilitate handling, cleaning, and maintenance. Effectiveness also depends on outdoor air temperature and the ratio of mass flow rates of the airstreams. Typically, heat capacity in the cooling season increases with a rise in outdoor air temperature. It has an opposite effect during the heating season. Effectiveness typically increases with the ratio of mass flow rates of the fluids (flow rate of the fluid with warmer entering temperature over that of cooler entering fluid temperature).

The heat transfer capacity of a heat pipe increases roughly with the square of the inside diameter of the pipe. For example, at a given tilt angle, a 1 in. inside diameter heat pipe will transfer roughly 2.5 times as much energy as a 5/8 in. inside diameter pipe. Consequently, heat pipes with large diameters are used for larger-airflow applications and where level installation is required to accommodate both summer and winter operation.

Heat transfer capacity is virtually independent of heat pipe length, except for very short heat pipes. For example, a 4 ft long heat pipe has approximately the same capacity as an 8 ft pipe. Because the 8 ft heat pipe has twice the external heat transfer surface area of the 4 ft pipe, it will reach its capacity limit sooner. Thus, in some applications, it is more difficult to meet capacity requirements as the heat pipes become longer. A system can be reconfigured to a taller face height and more numerous but shorter heat pipes to yield the same airflow face area while improving system performance. In typical HVAC comfort applications, if the heat pipe capacity is not reached, longer heat pipes can be used to recover more energy.

The selection of fin design and spacing should be based on the dirtiness of the two airstreams and the resulting cleaning and maintenance required. For HVAC applications, 11 to 14 fins per in. (fpi) is common. Wider spacing (8 to 10 fpi) is usually used for industrial applications. Plate-fin heat pipe heat exchangers can easily be constructed with different fin spacing for the exhaust and supply airstreams, allowing wider fin spacing on the dirty exhaust side. This increases design flexibility where pressure drop constraints exist and also prevents deterioration of performance caused by dirt build-up on the exhaust side surface.

Changing the tilt of a heat pipe controls the amount of heat it transfers. Operating the heat pipe on a slope with the hot end below (or above) the horizontal improves (or retards) condensate flow back to the evaporator end of the heat pipe. This feature can be used to regulate the effectiveness of the heat pipe heat exchanger (Guo et al. 1998). Introducing the action of gravity makes the device a hybrid heat pipe/thermosiphon.

Heat Pipe Heat Exchanger with Tilt Control

Figure 23. Heat Pipe Heat Exchanger with Tilt Control


Tilt control is achieved by pivoting the exchanger about the center of its base and attaching a temperature-controlled actuator to one end of the exchanger (Figure 23). Pleated flexible connectors attached to the ductwork allow freedom for the small tilting movement of only a few degrees.

Tilt control may be desired

  • To change from supply air heating to supply air cooling (i.e., to reverse the direction of heat flow) during seasonal changeover

  • To modulate effectiveness to maintain desired supply air temperature (often required for large buildings to avoid overheating air supplied to the interior zone)

  • To decrease effectiveness to prevent frost formation at low outdoor air temperatures (with reduced effectiveness, exhaust air leaves the unit at a warmer temperature and stays above frost-forming conditions)

Other devices, such as face-and-bypass dampers and preheaters, can also be used to control the rate of heat exchange.

Recent design improvements allow bidirectional heat transfer in heat pipes. Some heat pipe manufacturers have eliminated the need for tilting for capacity control or seasonal changeover. Once installed, the unit is removed only for routine maintenance. Capacity and frost control can also be achieved through bypassing airflow over the heat pipes, as for air coils. Bypassing airflow is the preferred method of control in applications where the average (annual) recovery efficiency ratio (RER) is important, because the reduced airflow through the heat pipe results in reduced air pressure losses during periods of modulation.

Heat pipe heat exchangers can be used to retrofit an existing air-conditioning system to improve energy recovery and dehumidification. By using a heat pipe heat exchanger, summer performance improves because the supply airstream is precooled before it enters the cooling coil. This allows more moisture removal along with cooling; the total energy consumption (kWh) and peak demand (kW) load are both reduced, yielding lower energy bills and healthier IAQ (Mathur 1997a, 1997b, 1997c, 1997d). Heat absorbed by the evaporator portion of the heat pipe heat exchanger can be used for reheating the cold saturated air after the cooling coil. Because both precooling and reheating are beneficial to the system, the RER in dehumidification applications is double that of an identical exchanger used in energy recovery. This can totally eliminate the electrical coil that is required for heating and its associated energy consumption (kW). For new installations, the air-conditioning systems can be downsized by using heat pipe heat exchangers (Mathur 1996, 1997a, 1997b, 1997c, 1997d, 2000). Similarly, for winter, the energy from the exhaust airstream is recovered and then transferred to the cold supply airstream via heat pipe heat exchanger. This preheats the air that enters the heating coil. Hence, a heat pipe heat exchanger can be used throughout the year to recover energy in both heating and cooling seasons (Mathur 1997a, 1997b, 1997c, 1997d; Yau 2008).

Heat pipe heat exchangers are used for energy recovery in building and hospitals (Mathur 1996, 1997a, 1997b, 1997c, 1997d; Mostafa et al. 2007; Yau 2007). Though these systems were initially designed for sensible energy recovery only, they are also used to control humidity of the conditioned space (Mathur 2000; Wu et al. 1997). Heat pipe heat exchangers can be used year round for heating, cooling, and dehumidification (Mathur 1997a, 1997b, 1997c, 1997d; Yao 2009).

Example 2. Sensible Heat Energy Recovery in a Heat Pipe

Outdoor air at 50°F enters a six-row heat pipe with a flow rate of 660 lb/min and a face velocity of 500 fpm. Exhaust air enters the heat pipe with the same velocity and flow rate but at 75°F. The pressure drop across the heat pipe is 0.6 in. of water. The supply air density is 0.08 lb/ft3. The efficiency of the electric motor and the connected fan are 90 and 75%, respectively. Assuming the performance characteristics of the heat pipe are as shown in Figure 18, determine the sensible effectiveness, exit temperature of supply air to the space, energy recovered, and power supplied to the fan motor.

Solution:

From Figure 18, at face velocity of 500 fpm and with six rows, the effectiveness is about 58%. Because the mass flow rate of the airstreams is the same and assuming their specific heat of 0.24 Btu/lb · °F is the same, then the exit temperature of the supply air to the space can be obtained from Equation (3a):

The sensible energy recovered can be obtained from Equation (3c) as

The supply air fan power can be obtained from Equation (11) as

Because there are two airstreams, neglecting the difference in the air densities of the airstreams, the total pumping power of the heat pipe is twice the above value (i.e., 2.3 hp).


 Thermosiphon Heat Exchangers

Two-phase thermosiphon heat exchangers are sealed systems that consist of an evaporator, a condenser, interconnecting piping, and an intermediate working fluid that is present in both liquid and vapor phases. Two types of thermosiphon are used: a sealed tube (Figure 24) and a coil type (Figure 25). In the sealed-tube thermosiphon, the evaporator and the condenser are usually at opposite ends of a bundle of straight, individual thermosiphon tubes, and the exhaust and supply ducts are adjacent to each other (this arrangement is similar to that in a heat pipe system). In coil-type thermosiphons, evaporator and condenser coils are installed independently in the ducts and are interconnected by the working fluid piping (this configuration is similar to that of a coil energy recovery loop).

Sealed-Tube Thermosiphons

Figure 24. Sealed-Tube Thermosiphons


A thermosiphon is a sealed system containing a two-phase working fluid. Because part of the system contains vapor and part contains liquid, the pressure in a thermosiphon is governed by the liquid temperature at the liquid/vapor interface. If the surroundings cause a temperature difference between the regions where liquid and vapor interfaces are present, the resulting vapor pressure difference causes vapor to flow from the warmer to the colder region. The flow is sustained by condensation in the cooler region and by evaporation in the warmer region. The condenser and evaporator must be oriented so that the condensate can return to the evaporator by gravity (Figures 20 and 25). For coil-type thermosiphon loops (Figure 25), static liquid level or refrigerant charge has a significant effect on system performance. The static charge should be optimized: a low static charge leads to dryout in the evaporator and reduced system performance, and a high charge suppresses boiling in the evaporator. Optimum charge levels have been found to be around 80% (Mathur 1990a, 1990b; Mathur and McDonald 1986).

Coil-Type Thermosiphon Loops

Figure 25. Coil-Type Thermosiphon Loops


In thermosiphon systems, a temperature difference and gravity force are required for the working fluid to circulate between the evaporator and condenser. As a result, thermosiphons may be designed to transfer heat equally in either direction (bidirectional), in one direction only (unidirectional), or in both directions unequally.

Although similar in form and operation to heat pipes, thermosiphon tubes are different in two ways: (1) they have no wicks and hence rely only on gravity to return condensate to the evaporator, whereas heat pipes use capillary forces; and (2) they depend, at least initially, on nucleate boiling, whereas heat pipes vaporize the fluid from a large, ever-present liquid/vapor interface. Thus, thermosiphon heat exchangers may require a significant temperature difference to initiate boiling (Mathur and McDonald 1987; McDonald and Shivprasad 1989). Thermosiphon tubes require no pump to circulate the working fluid. However, the geometric configuration must be such that liquid working fluid is always present in the evaporator section of the heat exchanger.

Thermosiphon loops differ from other coil energy recovery loop systems in that they require no pumps and hence no external power supply, and the coils must be appropriate for evaporation and condensation. Two-phase thermosiphon loops are used for solar water heating (Mathur 1990a) and for performance enhancement of existing (i.e., retrofit applications) air-conditioning systems (Mathur 1997a, 1997b, 1997c, 1997d). Two-phase thermosiphon loops can be used to downsize new air-conditioning systems and thus reduce the overall project costs. Figure 26 shows thermosiphon loop performance (Mathur and McDonald 1986) for an eight-row, 12 fpi system in unidirectional mode. Figure 27 shows the performance of the same system as a function of percent static charge for an overall temperature difference of 63°F.

Eight-Row, 12 fpi Unidirectional System; Static Charge of 80% (Mathur and McDonald 1986)

Figure 26. Eight-Row, 12 fpi Unidirectional System; Static Charge of 80%
(Mathur and McDonald 1986)


Typical Performance of Two-Phase Thermosiphon Loop as Function of Percent Static Charge: Eight Rows, 12 fpi Unidirectional System; Overall Temperature Difference of 63°F (Mathur and McDonald 1986)

Figure 27. Typical Performance of Two-Phase Thermosiphon Loop as Function of Percent Static Charge: Eight Rows, 12 fpi Unidirectional System; Overall Temperature Difference of 63°F
(Mathur and McDonald 1986)


These energy recovery systems are currently available to enhance the system performance (similar to heat pipe heat exchangers) of the current systems or to downsize the new equipment. Using two-phase thermosiphon loop systems or other energy recovery systems can improve the overall EERs of the systems and can earn significant Leadership in Energy and Environmental Design™ (LEED®) points.

Example 3. Sensible Heat Energy Recovery in a Two-Phase Thermosiphon Loop

Outdoor air at 10°F enters an eight-row. two-phase thermosiphon loop with a face area of 2 ft2 at a face velocity of 430 fpm. Exhaust air enters the two-phase thermosiphon loop with the same velocity with same face area at 75°F. Pressure drop across the heat pipe is 0.72 in. of water. The supply air density is 0.0843 lb/ft3. Efficiencies of the electric motor and connected fan are 90 and 75%, respectively. Assuming the performance characteristics of the two-phase thermosiphon as shown in Figure 26, determine the sensible effectiveness, exit temperature of supply air to the space, energy recovered, and power supplied to the fan motor.

Solution:

From the data given, the overall temperature difference between supply and exhaust airstreams is 65°F (i.e., 75 − 10 = 65). From Figure 26, at face velocity of 430 fpm and with eight rows, the effectiveness is about 52.5%. Because the mass flow rate of the airstreams is the same and assuming their specific heat of 0.24 Btu/lb · °F is the same, then the exit temperature of the supply air to the space can be obtained as follows:

The sensible energy recovered can be obtained from Equation (3c) as

The supply air fan power [Equation (11)] is

Because there are two airstreams, the total pumping power of the two-phase thermosiphon loop (neglecting the differences in air density between the airstreams) is approximately twice the value of Ps (i.e., 0.30 hp).


 Liquid-Desiccant Cooling Systems

Liquid-desiccant cooling systems (LDCSs) have great potential in reducing energy costs associated with meeting latent loads in high-occupancy commercial building applications. An LDCS can produce very dry air as long as the desiccant solution is supplied to its dehumidifier at low temperatures. However, an LDCS requires additional components: two or three plate-to-plate heat exchangers, a separate cooling tower, pump, fan, and a packed-bed humidifier and regenerator.

When exposed to moist air at the proper temperature and concentration, some chemical solutions (e.g., lithium chloride, lithium bromide, calcium chloride, triethylene glycol) can either absorb water vapor from, or release water vapor to, the airstream. These chemicals, known as liquid desiccants, are used to dehumidify air with significantly less energy consumption than by a mechanical refrigeration system. Liquid desiccants also have the advantage of removing bacteria and dust from the air compared to solid desiccant wheels or mechanical vapor compression systems. It requires a lower-temperature (less than 180°F) heat source for regeneration, which can be provided by solar energy or waste heat from local equipment. Moisture transfer between the desiccant solution and process air is caused by the difference in vapor pressures at the desiccant surface and that of the air passing over it. The desiccant collects moisture when its vapor pressure is lower than that of the water vapor in the air, and releases it when its vapor pressure is higher. Absorption of water vapor releases heat energy, including the heat of vaporization and, in some cases, additional heat. After absorbing water vapor from the processes air, the solution temperature increases slightly, and its concentration drops as absorbed water vapor becomes part of the solvent of the solution. For cyclic operation, the desiccant solution is regenerated to restore its original concentration; this involves heating the solution with a low-grade heat source and exposing the heated solution to an airstream, as shown in Figure 28 (Williams 2007). Often, outdoor air is used as a scavenging airstream in regeneration. Heat added to the desiccant solution for regeneration is of low grade and can be obtained from a source at no more than 160°F. Such low-temperature energy sources are often available as waste heat in many applications.

Typical Dehumidification of Outdoor Air by Liquid-Desiccant System (Williams 2007)

Figure 28. Typical Dehumidification of Outdoor Air by Liquid-Desiccant System
(Williams 2007)


As seen in Figure 28, the hot, humid process air to be dehumidified enters the packed-bed dehumidifier or absorber at state 1 and leaves at state 2. The concentrated desiccant solution enters the absorber at state 5 and leaves at state 6 as dilute solution after absorbing water vapor from the process airstream. The dilute solution now passes through a liquid-to-liquid plate heat exchanger to recover some of the heat energy from the concentrated solution exiting the regenerator. The dilute solution is heated further to the required temperature in the desiccant solution heating coil and is sprayed over the incoming outdoor scavenging air passing through the regenerator. For air-to-air energy recovery purposes, the exhaust air from the space can be used for greater effectiveness in place of outdoor scavenging air. Because of the high inlet temperature of the desiccant solution, its vapor pressure is relatively higher than that of the incoming air, causing moisture transfer from the solution to the air. The inlet temperature of the desiccant solution to the regenerator for the given state of the air at state 8 is such that the desiccant concentration is restored to its value at state 6 as it exits the regenerator. The concentrated desiccant solution leaving the regenerator transfers heat energy to the incoming dilute solution exiting the packed-bed dehumidifier, in the liquid-to-liquid plate heat exchanger. Further temperature reduction of the desiccant solution, if required before it enters the absorber, can be accomplished by using cooling water from a cooling tower in the desiccant cooling coil. During extreme high-latent-load conditions, chilled water, rather than water from a cooling tower, may be necessary to cool the desiccant solution before it enters the absorber. The temperature of the solution at the inlet of the absorber strongly influences the air-dehumidifying capacity. The higher the concentration and lower the temperature of the solution, the higher the moisture absorbed and lower the humidity of the exiting air from the absorber.

Table 2. Types of Liquid-Desiccant Solutions

Desiccant Type

No of Investigators

Typical Concentration Range, %

Operating Temperatures, °F

LiCl

7

34 to 43

77 to 81

TEG

5

92 to 98

68 to 114

LiBr

4

42.6 to 57

68 to 93

CaCl2

2

40 to 43

81

KCOOH

1

72.8 to 74

71 to 77

Source: Jain and Bansal (2007).


 Types of Desiccant Solutions.
 Desiccant solutions used by different investigators, as well as their key features, are shown in Table 2.

Lithium chloride (LiCl) is a good candidate material because it has good desiccant characteristics and does not vaporize in air at ambient temperature, but it is corrosive. Calcium chloride (CaCl2) is an equally good candidate for desiccant choice and is less expensive than LiCl. A 50%/50% combination of LiCl and CaCl2 is also being investigated. Triethylene glycol (TEG) has a low vapor pressure that enables effective dehumidification in the absorber, but it also makes it vulnerable to evaporation. Special coatings may be required to avoid corrosion, and efficient absorber design may be needed to prevent liquid or desiccant carryover.

 Fluid Flow Configuration.
 Four different types of fluid flow configurations are used by different investigators in the packed beds for absorbers and regenerators.
  • Counter flow

  • Parallel flow

  • Cross flow

  • Falling film

Most applications are counter flow, because it provides the maximum enthalpy and humidity effectiveness for the packed beds.

 Types of Packing.
 Packing arrangements are basically either structured or random types. In some cases, vertical surfaces or tubes are used, over which the desiccant solution falls as a thin film. The purpose of packing is to provide the maximum surface area for the desiccant solution to come in contact with the process air. The greater the area, the greater the dehumidification. The main parameters affecting bed arrangement are the enhancement of heat and mass transfer, air pressure drop, and pumping power to circulate the fluids through the bed. The main advantage of structured packing is the low pressure drop, whereas that of random packing is high heat and mass transfer but with high pressure drop. Packing compactness is typically expressed in terms of packing density at, in units of m2/m3. Typically, packing densities exceeding 200 m2/m3 have been achieved in the field. A higher packing density allows for more dehumidification but also produces greater pressure drop for the fluid streams. In random packing arrangements, packing is made up of Berl saddles, Raschig rings, and saddles of various trademarked designs, whereas in structured packing, the packing consists of cellulose rigid media pads, wood grids, expanded metal lash packing, or double spiral rings.

 Twin-Tower Enthalpy Recovery Loops

One method of ventilation air enthalpy recovery is liquid desiccant twin-tower systems. In this air-to-liquid, liquid-to-air enthalpy recovery system, sorbent liquid circulates continuously between supply and exhaust airstreams, alternately contacting both airstreams directly in contactor towers (Figure 29). This liquid transports water vapor and heat. The sorbent solution is usually a halogen salt solution such as lithium chloride, calcium chloride, and water. Pumps circulate the solution between supply and exhaust contactor towers.

Both vertical and horizontal airflow contactor towers are available, and both types can be combined in a common system. Contactor towers of both configurations are commonly available with airflow capacities of up to 84,000 scfm.

Twin-Tower System Performing Indirect Evaporative Air Cooling: (A) Schematic and (B) Installation in Building

Figure 29. Twin-Tower System Performing Indirect Evaporative Air Cooling: (A) Schematic and (B) Installation in Building


In the vertical configuration, the supply or exhaust air passes vertically through the contact surface counterflow to the sorbent liquid to achieve high contact efficiency. In the horizontal configuration, air passes horizontally through the contact surface cross flow to the sorbent liquid, yielding a slightly lower contact efficiency.

The contactor surface is usually made of nonmetallic materials. Air leaving the contactor tower passes through demister pads, which remove any entrained sorbent solution. The halogen salt solution does not offgas or vaporize.

 Design Considerations.
 Twin-tower enthalpy recovery systems operate primarily in the comfort conditioning range; they are not suitable for high-temperature applications. During summer, these systems operate efficiently with building supply outdoor air temperatures as high as 115°F. Winter supply air temperatures as low as −40°F can be tolerated without freezing or frosting problems because the sorbent solution is an effective antifreeze at all useful concentrations. During weather conditions that are not advantageous for energy recovery, the system automatically shuts down the pump(s), thereby saving operating power. When outdoor conditions warrant energy recovery, the system restarts automatically. Because contactor supply and exhaust air towers are independent units connected only by piping, supply and exhaust air fans can be located wherever desired. Contactor towers can operate with air inlet static pressure from −6 to 6 in. of water, but require less than 1.8 in. of water air-side pressure drop. The exhaust contactor tower may operate at a higher internal static pressure than the supply contactor tower without danger of exhaust-to-supply cross contamination.

Particulate cross contamination does not occur because wetted particulates remain in the sorbent solution until they are filtered. Limited gaseous cross contamination may occur, depending on the solubility of the gas in the sorbent solution. Sorbent solutions, especially halide brines, are bactericidal. Lithium or calcium chloride as used in twin-tower systems is viricidal against all viruses.

If the building or process exhaust contains large amounts of lint, animal hair, or other solids, filters should be placed upstream of the exhaust air contactor tower; if it contains large amounts of gaseous contaminants, such as chemical fumes and hydrocarbons, investigate the possibility of cross contamination as well as the possible effects of contaminants on the sorbent solution. When using twin-tower systems in controlled-humidity applications in colder climates, saturation effects (which can cause condensation, frosting, and icing in other types of equipment) may overdilute the twin towers’ sorbent solution. Heating the sorbent liquid supplied to the supply air contactor tower can prevent dilution, as shown in Figure 29A. Heating raises the discharge temperature and humidity of air leaving the supply contactor tower, thus balancing the humidity of the system and preventing overdilution.

A thermostat sensing the leaving air temperature from the supply air contactor tower is commonly used to control the solution heater to deliver constant-temperature air regardless of outdoor temperature. Automatic addition of makeup water to maintain a fixed concentration of the sorbent solution enables the twin-tower system to deliver supply air at fixed humidity during cold weather. Thus, the system provides a constant supply air temperature and humidity without preheat or reheat coils or humidifiers.

Any number of supply air towers can be combined with any number of exhaust air towers, as shown in Figure 29B. If a sufficient elevation difference exists between supply and exhaust towers, gravity may be used to return the sorbent solution from the upper tower(s) in lieu of pumped flow. Twin-tower energy recovery systems can be retrofitted to existing buildings. The towers are connected to each other with piping. The solution piping can be easily installed inside or outside the building. Twin-tower enthalpy recovery systems operate with only routine maintenance. Complete instructions on procedures as well as spare-parts lists are included in operating manuals relevant to each installation. Periodically, the circulation pumps, spray nozzles, liquid transfer controls, and mist eliminators need checking and adjusting or maintenance. Halide brine solutions are normally used as energy transfer media in twin-tower systems. Manufacturers provide technical support, including solution sampling services to monitor and report changes in concentration and pH, thus ensuring continued maximum performance.

 Indirect Evaporative Air Cooling

In indirect evaporative air cooling, exhaust air passing through a water spray absorbs water vapor until it becomes nearly saturated. As the water evaporates, it absorbs sensible energy from the air, lowering its temperature. The evaporatively cooled exhaust air can then be used to cool supply air through an air-to-air heat exchanger, which may be used either for year-round energy recovery or exclusively for its evaporative cooling benefits. This process follows a constant wet-bulb line on a psychrometric chart: the airstream enthalpy remains nearly constant, moisture content increases, and dry-bulb temperature decreases.

Indirect evaporative cooling has been used with heat pipe heat exchangers, runaround coil loop exchangers, and flat-plate heat exchangers for summer cooling (Dhital et al. 1995; Johnson et al. 1995; Mathur 1990a, 1990b, 1992, 1993; Scofield and Taylor 1986). Exhaust air or a scavenging airstream is cooled by passing it through a water spray, wet filter, or other wetted media, resulting in a greater overall temperature difference between the supply and exhaust or scavenging airstreams and thus more heat transfer. Energy recovery is further enhanced by improved heat transfer coefficients because of wetted exhaust-side heat transfer surfaces. No moisture is added to the supply airstream, and there are no auxiliary energy inputs other than fan and water pumping power. The coefficient of performance (COP) tends to be high, typically from 9 to 20, depending on available dry-bulb temperature depression. The dry-bulb temperature decrease in the exhaust airstream caused by evaporative cooling tends to be 85 to 95% of the maximum available difference between the exhaust air inlet dry-bulb and wet-bulb temperatures. Therefore, exhaust air evaporative cooling is usually most cost effective in hot, dry climates where the evaporator can be used frequently to obtain large exhaust air dry-bulb temperature depressions.

Without a bypass scheme for either the evaporator or air-to-air heat exchanger, the net annual energy costs include the extra annual fan power for these devices as well as the benefit of evaporative cooling.

Because less mechanical cooling is required with evaporative cooling, energy consumption and peak demand load are both reduced, yielding lower energy bills. Overall mechanical refrigeration system requirements are reduced, allowing use of smaller mechanical refrigeration systems. In some cases, the mechanical system may be eliminated. Chapter 41 of this volume and Chapter 52 of the 2019 ASHRAE Handbook—HVAC Applications have further information on evaporative cooling.

Example 4. Indirect Evaporative Cooling Recovery

Room air at 86°F and 63°F wb (ρ = 0.075 lb/ft3) with a flow rate of 32,000 cfm is used to precool 32,000 cfm of supply outdoor air at 102°F and 68°F wb (ρ = 0.071 lb/ft3) using an aluminum fixed-plate heat exchanger and indirect evaporative cooling. The evaporative cooler increases the exhaust air to 90% rh before it enters the heat exchanger. The sensible effectiveness is given by the manufacturer as 78%. Assuming EATR = 0 and OACF ≈ 1, determine the leaving supply air conditions and energy recovered, and check the energy exchange balance.

Solution:

First, determine the exhaust air condition entering the exchanger (i.e., after it is adiabatically cooled). Air at 86°F db, 63°F wb cools to 64°F db, 63°F wb as shown by the process line from point A to point 3 in Figure 30. In this problem the volumetric flows are equal, but the mass flows are not.

  1. Because data on pressure drop are missing, skip this step.

  2. Calculate the theoretical maximum heat transfer.

    Based on a preliminary assessment, the supply air is not expected to cool below its wet-bulb temperature of 68°F. Thus, use sensible heat Equation (3c).

  3. Establish the sensible effectiveness.

    From manufacturer’s exchanger selection data for indirect evaporative coolers, an effectiveness of 78% is found to be appropriate.

  4. Calculate actual energy transfer at the design conditions.

  5. Calculate leaving air conditions.

    1. Leaving supply air temperature is

    2. Leaving exhaust air temperature is

  6. Check performance.

  7. Plot conditions on psychrometric chart (Figure 30), and confirm that no latent exchange occurred.

    Because EATR = 0 and OACF ≈ 1, Steps 8 to 10 are not presented here.


Indirect Evaporative Cooling Recovery (Example 5)

Figure 30. Indirect Evaporative Cooling Recovery (Example 5)


 Precooling Air Reheaters (Series Application)

In some applications, such as ventilation in hot, humid climates, supply air is cooled below the desired delivery temperature to condense moisture and reduce humidity. Using this overcooled supply air to precool outdoor air reduces the air-conditioning load, which allows refrigeration equipment to be downsized and eliminates the need to reheat supply air with purchased energy.

In this three-step process, shown in Figure 31, outdoor air passes through an air-to-air heat exchanger, where it is precooled by supply air leaving the cooling coil. It is then further cooled and dehumidified in the cooling coil. After leaving the cooling coil, it passes through the other side of the air-to-air heat exchanger, where the incoming supply air reheats it.

Precooling Air Reheater

Figure 31. Precooling Air Reheater


Fixed-plate, heat pipe, and rotary heat wheel exchangers can be used to reheat precooled supply air. At part-load operation, the amount of heat transferred from precooling to reheating may require modulation. This can be done using the heat rate control schemes in Table 3.

Example 5. Precooling Air Reheater Dehumidifier

In this application, 3400 cfm of outdoor supply air at 95 and 81°F wb (ρ = 0.069 lb/ft3) is used to reheat 3400 cfm of the same air leaving a cooling coil (exhaust) at 52.1 and 51.8°F wb using a sensible heat exchanger as a precooling air reheater. The reheated air is to be between 75 and 79°F. In this application, the warm airstream is outdoor air and the cold airstream is the same air after it leaves the cooling coil. The unit’s manufacturer lists its effectiveness as 58.4%. For EATR = 0 and OACF ≈ 1, determine the leaving precooled and reheated air conditions and energy recovered, and check the energy exchange balance.

Solution:

  1. Because data on pressure drop are missing, skip this step.

  2. Calculate the theoretical maximum energy transfer.

    The air being reheated will have less mass than the outdoor air entering the precooler because moisture will condense from it as it passes through the precooler and cooling coil. Reheat is sensible heat only, so Equation (2c) is used to determine the theoretical maximum energy transfer.

  3. Establish the sensible effectiveness.

    The manufacturer give the effectiveness as 58.4% at the designated operating conditions.

  4. Calculate actual energy transfer at design conditions.

  5. Calculate leaving air conditions.

    Because condensation occurs as the outdoor airstream passes through the precooling side of the heat exchanger, use Equation (26) to determine its leaving enthalpy, which is the inlet condition for the cooling coil. Sensible heat transfer Equation (27) is used to determine the temperature of air leaving the preheat side of the heat exchanger.

    1. Precooler leaving air conditions

      Entering enthalpy, determined from the psychrometric chart for 95°F db and 81°F wb, is 44.6 Btu/lb.

      The wet-bulb temperature for saturated air with this enthalpy is 75°F. This is point 2 on the psychrometric chart (Figure 32), which is near saturation. Note that this precooled air is further dehumidified by a cooling coil from point 2 to point 3 in Figure 32.

    2. Reheater leaving air conditions

      Entering enthalpy, determined from the psychrometric chart for 52.1°F db and 51.8°F wb, is 21.3 Btu/lb.

      The wet-bulb temperature for air with this temperature and enthalpy is 61.3°F.

  6. Check performance.

  7. Plot conditions on psychrometric chart (Figure 32).

Because EATR = 0 and OACF ≈ 1, Steps 8 to 10 are not presented here.


Table 3. Comparison of Air-to-Air Energy Recovery Devices

Fixed Plate

Membrane Plate

Energy Wheel

Heat Wheel

Heat Pipe

Runaround Coil Loop

Thermosiphon

Liquid Desiccant

Airflow arrangements

Counterflow Cross flowa

Counterflow Cross flowa

Counterflow Parallel flow

Counterflow

Counterflow Parallel flow

Counterflow Parallel flow

Equipment size range, cfm

50 and up

50 and up

50 to 74,000 and up

50 to 74,000 and up

100 and up

100 and up

100 and up

Typical sensible effectiveness (ms = me), %c

50 to 75

55 to 75

65 to 80

65 to 80

40 to 60b

45 to 65b

40 to 60

40 to 60b

Typical latent effectiveness,* %c

0

25 to 60

50 to 80

0

0

0

0

50 to 75b,d

Total effectiveness,* %c

20 to 50

35 to 70

55 to 80

25 to 60

15 to 35

40 to 75d

Face velocity, fpm

200 to 1000

200 to 600

500 to 1000

400 to 1000

400 to 800

300 to 600

400 to 800

300 to 450

Pressure drop, in. of water

0.4 to 4

0.4 to 2

0.4 to 1.2

0.4 to 1.2

0.6 to 2

0.6 to 2

0.6 to 2

0.7 to 1.2

EATR, %

0 to 2

0 to 5

0.5 to 10

0.5 to 10

0 to 1

0

0

0

OACF

0.97 to 1.06

0.97 to 1.06

0.99 to 1.1

1 to 1.2

0.99 to 1.01

1.0

1.0

1.0

Temperature range, °F

−75 to 1470

−40 to 140

−65 to 1470

−65 to 1470

−40 to 200

−50 to 930

−40 to 104

−40 to 115

Typical mode of purchase

Exchanger only

Exchanger in case

Exchanger and blowers

Complete system

Exchanger only

Exchanger in case

Exchanger and blowers

Complete system

Exchanger only

Exchanger in case

Exchanger and blowers

Complete system

Exchanger only

Exchanger in case

Exchanger and blowers

Complete system

Exchanger only

Exchanger in case

Exchanger and blowers

Complete system

Coil only

Complete system

Exchanger only

Exchanger in case

Complete system

Advantages

No moving parts

Low pressure drop

Easily cleaned

No moving parts

Low pressure drop

Low air leakage

Moisture/mass transfer

Moisture/mass transfer

Compact large sizes

Low pressure drop

Available on all ventilation system platforms

Compact large sizes

Low pressure drop

Easily cleaned

No moving parts except tilt

Fan location not critical

Allowable pressure differential up to 2 psi

Exhaust airstream can be separated from supply air

Fan location not critical

No moving parts

Exhaust airstream can be separated from supply air

Fan location not critical

Latent transfer from remote airstreams

Efficient microbiological cleaning of both supply and exhaust airstreams

Limitations

Large size at higher flow rates

Few suppliers

Long-term maintenance and performance unknown

Supply air may require some further cooling or heating

Some EATR without purge

Some EATR with purge

Effectiveness limited by pressure drop and cost

Few suppliers

Predicting performance requires accurate simulation model

Effectiveness may be limited by pressure drop and cost

Few suppliers

Few suppliers

Maintenance and performance unknown

Heat rate control (HRC) methods

Bypass dampers and ducting

Bypass dampers and ducting

Bypass dampers and wheel speed control

Bypass dampers and wheel speed control

Tilt angle down to 10% of maximum heat rate

Bypass valve or pump speed control

Control valve over full range

Control valve or pump speed control over full range

EATR = exhaust air transfer ratio

OACF = outdoor air correction factor

a Rated effectiveness values are for balanced flow conditions for cross flow. Effectiveness values increase slightly if flow rates of either or both airstreams are higher than flow rates at which testing is done.

b Data not based on third-party certified data.

c Data based on typical range of third-party certified data.

d Face velocity of 250 to 500 fpm.


Precooling Air Reheater Dehumidifier (Example 5)

Figure 32. Precooling Air Reheater Dehumidifier (Example 5)


7. COMPARISON OF AIR-TO-AIR ENERGY RECOVERY SYSTEMS

It is difficult to compare different types of air-to-air energy recovery systems based on overall performance. They can be compared based on certified ratings such as sensible, latent, and total effectiveness or on air leakage parameters. Comparing them on payback period or maximum energy cost savings requires accurate values of their capital cost, life, and maintenance cost, which vary from product to product for the same type of recovery system. Without such data, and considering the data available in the open literature such as that presented by Besant and Simonson (2003), use Table 3’s comparative data for common types of air-to-air energy recovery devices.

 Characterizing System Efficiency of Heat or Energy Recovery Ventilators

A measure of energy recovery ventilator performance is the relative magnitude of actual energy recovered and power supplied to fans to circulate the airstreams. The cost of power supplied to the fans depends on the pressure drop of airstreams, volume flow rate, and combined efficiency of the fan motor systems. The quality of power supplied to the fans is high, and its cost per unit energy is much higher than the quality and cost of energy recovered in the ventilator. The magnitude and costs of these two forms of energy vary over the year. Besant and Simonson (2003) suggest that a parameter such as recovery efficiency ratio (RER) may be introduced to characterize the efficiency of the recovery ventilators:

(24)

RER is similar to the energy efficiency ratio (EER) for chillers or unitary air-conditioning equipment. Besant and Simonson (2003) also suggest that the entire system performance, including the recovery ventilator, can be represented by the ratio of COP and RER.

RER is typically expressed in units of Btu/Wh; energy recovered can be sensible, latent, or total, in Btu/h, and energy expended is that spent for circulating exhaust and supply air through the energy recovery unit, expressed in watts. In AHRI Guideline V, RERTotal, RERsensible, and RERlatent are defined as

(25a)

(25b)

(25c)

where

min

=

minimum mass flow rate of supply and exhaust airstreams

h1

=

enthalpy at state 1

t1

=

temperature at state 1

ω1

=

humidity ratio at state 1

Pcomp

=

direct power input of recovery component

Pblower

=

blower power required for energy recovery component

(25d)

where

C

=

unit conversion constant, 8.52 ft3·in. of water/min · W

ΔP

=

pressure loss of component for supply or exhaust airstreams, in. of water

Qblower supply

=

supply fan airflow, cfm

Qblower exhaust

=

exhaust fan airflow, cfm

ηfan/motor

=

combined fan and motor efficiency

Note that other alternatives (e.g., comparing operating points on a fan curve) that accurately characterize the additional fan power required by the component are acceptable means of obtaining blower power.

For a flow rate of 1000 cfm and typical values of airstream pressure drop and motor and fan efficiencies, RERsensible can range from 25 to 30 Btu/Wh. Considering the conversion factor of 1 W = 3.413 Btu/h, the calculated value of RER suggest that the energy recovered is about 7.3 to 8.8 times that used to operate the energy recovery unit. The quality of thermal energy is about one-third that of electric power, so the actual energy recovered is about three times the cost of energy spent for energy recovery.

The combined efficiency (CEF) is the ratio of the net heating/cooling delivered to the total electric power consumed. CEF can also be related to the sensible, latent, or total recovered energy and is related to the RER; energy efficiency ratio (EER), which is typically provided by manufacturers of unitary equipment; and load ratio Y. It represents the percentage of the system load (heating, cooling, humidification and/or dehumidification) met by the energy recovery component. The higher load ratio allows use of smaller equipment, thereby affecting capital costs. CEFcooling can be estimated as

(25e)

where

(25f)

(25g)

For a typical value of EER = 10 for an unitary system, and a load ratio of about 0.3, the CEFcooling can range from 14 to 18 Btu/Wh. Use of an energy recovery unit and its effects on system sizing and annual net savings for various climatic regions are discussed in AHRI Guideline V.

 Selection of Heat or Energy Recovery Ventilators

Heat and energy recovery ventilators are available as heat exchangers only or as a complete system, including the heat exchangers and fan/motor systems, as indicated in Table 3. Energy recovery is also available integrated into unitary air-conditioning equipment or in both standard and custom air-handling systems. Selection of such units is primarily dictated by the quantity of ventilation air. Several manufacturers have developed software or tables to help select these units. The user may have to determine the required fan size (see Example 9), if only the heat exchanger is to be purchased.

However, the true overall system performance is the life-cycle cost, which takes into account the capital and maintenance costs. Because of lack of sufficient data on these factors, they are not presented in Table 3.

8. ECONOMIC CONSIDERATIONS

Air-to-air energy recovery systems are used in both new and retrofit applications. These systems should be designed for the maximum cost benefit or least life-cycle cost (LCC) expressed either over the service life or annually and with an acceptable payback period.

The annualized system owning, operating, and maintenance costs are discussed in Chapter 37 of the 2019 ASHRAE Handbook—HVAC Applications. Although the capital cost and interest term in this method imply a simple value, it is in fact a complex function of the future value of money as well as all the design variables in the energy/heat exchanger. These variables include the mass of each material used, cost of forming these materials into a highly effective energy/heat exchanger, cost of auxiliary equipment and controls, and cost of installation.

The operating energy cost for energy recovery systems involves functions integrated over time, including variables such as flow rate, pressure drop, fan efficiency, energy cost, and energy recovery rate. The calculations are complex because air-heating and/or cooling loads are, for a range of supply temperatures, time dependent in most buildings. Time-of-use schedules for buildings can impose different ventilation rates for each hour of the day. Electrical utility charges often vary with time of day, amount of energy used, and peak power load. For building ventilation air-heating applications, the peak heat recovery rate usually occurs at the outdoor supply temperature at which frosting control throttling must be imposed. In addition to designing for the winter design temperature, heat recovery systems should be optimized for peak heat recovery rate, taking frost control into account.

Overall exchanger effectiveness ε should be high (see Table 3 for typical values); however, a high ε implies a high capital cost, even when the exchanger is designed to minimize the amount of materials used. Energy costs for fans and pumps are usually very important and accumulate operating cost even when the energy recovery system must be throttled back. For building ventilation, throttling may be required much of the time. Thus, the overall LCC minimization problem for optimal design may involve 10 or more independent design variables as well as several specified constraints and operating conditions [see, e.g., Besant and Johnson (1995)].

In addition, comfort-to-comfort energy recovery systems often operate with much smaller temperature differences than most auxiliary air-heating and cooling heat exchangers. These small temperature differences need more accurate energy transfer models to reach the maximum cost benefit or lowest LCC. Most importantly, recovered energy at design may be used to reduce the required capacity of heating and cooling equipment, which can be significant in both system performance/efficiency and economics.

The payback period (PP) is best computed after the annualized costs have been evaluated. It is usually defined as

(26)

where

Cs,init

=

initial system cost

ITC

=

investment tax credit for energy-efficient improvements

Ce

=

cost of energy to operate the system for one period

Tinc

=

net income tax rate where rates are based on last dollar earned (i.e., marginal rates) = (local + state + federal rate) – (federal rate) (local + state rate)

CRF

=

capital recovery factor

i

=

effective discount rate adjusted for energy inflation

n

=

total number of periods under analysis

The inverse of this term is usually called the return on investment (ROI). Well-designed energy recovery systems normally have a PP of less than 5 years, and often less than 3 years. Paybacks of less than 1 year are not uncommon in comfort-to-comfort applications in hot, humid climates, primarily because of the reduced size of cooling equipment required.

Other economic factors include the following.

System Installed Cost. Initial installed HVAC system cost is often lower for air-to-air energy recovery devices because mechanical refrigeration and fuel-fired heating equipment can be reduced in size. Thus, a more efficient HVAC system may also have a lower installed total HVAC cost. The installed cost of heat recovery systems becomes lower per unit of flow as the amount of outdoor air used for ventilation increases.

Life-Cycle Cost. Air-to-air energy recovery cost benefits are best evaluated considering all capital, installation, operating, and energy-saving costs over the equipment life under normal operating conditions in terms of the life-cycle cost. As a rule, neither the most efficient nor the least expensive energy recovery device will be most economical. Optimizing the life-cycle cost for maximum net savings may involve many design variables, requiring careful cost estimates and use of an accurate recovery system model with all its design variables [see, e.g., Besant and Simonson (2000)].

Energy Costs. The absolute cost of energy and relative costs of various energy forms are major economic factors. High energy costs favor high levels of energy recovery. In regions where electrical costs are high relative to fuel prices, heat recovery devices with low pressure drops are preferable.

Amount of Recoverable Energy. Economies of scale favor large installations. Equipment is commercially available for air-to-air energy recovery applications using 50 cfm and above.

Grade of Exhaust Energy. High-grade (i.e., high-temperature) exhaust energy is generally more economical to recover than low-grade energy. Energy recovery is most economical for large temperature differences between the waste energy source and destination.

Coincidence and Duration of Waste Heat Supply and Demand. Energy recovery is most economical when supply coincides with demand and both are relatively constant throughout the year. Thermal storage may be used to store energy if supply and demand are not coincident, but this adds cost and complexity to the system.

Proximity of Supply to Demand. Applications with a large central energy source and a nearby waste energy use are more favorable than applications with several scattered waste energy sources and uses.

Operating Environment. High operating temperatures or the presence of corrosives, condensable gases, and particulates in either airstream results in higher equipment and maintenance costs. Increased equipment costs result from the use of corrosion- or temperature-resistant materials, and maintenance costs are incurred by an increase in the frequency of equipment repair and wash down and additional air filtration requirements.

Effect on Pollution Control Systems. Removing process heat may reduce the cost of pollution control systems by (1) allowing less expensive filter bags to be used, (2) improving the efficiency of electronic precipitators, or (3) condensing out contaminant vapors, thus reducing the load on downstream pollution control systems. In some applications, recovered condensable gases may be returned to the process for reuse.

Effect on Heating and Cooling Equipment. Heat recovery equipment may reduce the size requirements for primary utility equipment such as boilers, chillers, and burners, as well as the size of piping and electrical services to them. Larger fans and fan motors (and hence fan energy) are generally required to overcome increased static pressure loss caused by the energy recovery devices. Auxiliary heaters may be required for frost control.

Effect on Humidifying or Dehumidifying Equipment. Selecting total energy recovery equipment results in the transfer of moisture from the airstream with the greater humidity ratio to the airstream with the lesser humidity ratio. This is desirable in many situations because humidification costs are reduced in cold weather and dehumidification loads are reduced in warm weather.

9. ENERGY AND/OR MASS RECOVERY CALCULATION PROCEDURE

The rate of energy transfer to or from an airstream depends on the rate and direction of heat transfer and water vapor (moisture) transfer. Under customary design conditions, heat and water vapor transfer will be in the same direction, but the rate of heat transfer will not be the same as the rate of energy transfer by the cross-stream flow of water vapor. This is because the driving potentials for heat and mass transfer are different, as are the respective wall resistances for the two types of transport. Both transfer rates depend on exchanger construction characteristics. Equation (26) is used to determine the rate of energy transfer when sensible (temperature) and latent (moisture) energy transfer occurs; Equation (27) is used for sensible-only energy transfer.

(27)

(28)

where

qt

=

qs + qL = total energy transfer, Btu/h

qs

=

sensible heat transfer, Btu/h

Q

=

airflow rate, cfm

ρ

=

air density, lb/ft3

cp

=

specific heat of air = 0.24 Btu/lb · °F

tin

=

dry-bulb temperature of air entering exchanger, °F

tout

=

dry-bulb temperature of air leaving exchanger, °F

hin

=

enthalpy of air entering heat exchanger, Btu/lb

hout

=

enthalpy of air leaving heat exchanger, Btu/lb

The following general procedure may be used to determine the performance and energy recovered in air-to-air energy recovery applications at each operating condition.

Step 1. Determine supply and exhaust air pressure drops Δps and Δpe across exchanger.

Request air pressure drops Δps and Δpe across the heat or energy exchanger from the manufacturer, who may have certified AHRI Standard 1060 test condition data obtained using ASHRAE Standard 84 as a test procedure and analysis guide. These data may be extrapolated to non-AHRI conditions by the manufacturer using correlations such as Equations (14) or (16), if their restrictions are satisfied. For other flow conditions, somewhat different correlations may be more accurate to determine the pressure drop.

Step 2. Calculate theoretical maximum moisture and energy transfer rates mmax and qmax.

The airstream with the lower mass flow mmin limits heat and moisture transfer. Some designers specify and prefer working with airflows stated at standard temperature and pressure conditions. To correctly calculate moisture or energy transfer rates, the designer must determine mass flow rates. For this reason, the designer must know whether airflow rates are quoted for the entry conditions specified or at standard temperature and pressure conditions. If necessary, convert flow rates to mass flow rates (e.g., scfm to lb/min) and then determine which airstream has the minimum mass.

The theoretical maximum moisture, sensible heat, latent heat and total energy rates are given by Equations (4f), (2c), (4c), and (6c), respectively.

The split between latent and sensible energy can be determined by plotting airstream conditions on a psychrometric chart as shown in Figure 33. Maximum sensible heat transfer is represented by a horizontal line drawn between the two dry-bulb temperatures, and maximum latent energy transfer is represented by the vertical line.

Step 3. Establish moisture, sensible, and total effectiveness εs, εL, and εt.

Maximum Sensible and Latent Heat from Process A-B

Figure 33. Maximum Sensible and Latent Heat from Process A-B


Each of these ratios is obtained from manufacturers’ product data using input conditions and airflows for both airstreams. The effectiveness for airflows depends on (1) exchanger construction, including configuration, heat transfer material, moisture transfer properties, transfer surface area, airflow path, distance between heat transfer surfaces, and overall size; and (2) inlet conditions for both airstreams, including pressures, velocities, temperatures, and humidities. In applications with unequal airflow rates, the enthalpy change will be higher for the airstream with the lesser mass flow.

Step 4. Calculate actual moisture (latent) and energy (sensible, latent or total) transfer rates.

The actual moisture, sensible heat, latent heat, and total energy rates are given by Equations (4e), (2b), (4b), and (6b), respectively. Note that εm (mass effectiveness) = εL (latent effectiveness), as shown by Equations (4a) and (4d).

Step 5. Calculate leaving air properties for each airstream using Equations (3), (5), and (7).

With an enthalpy or moisture-permeable heat exchanger, moisture (and its inherent latent energy) is transferred between airstreams. With a sensible-only heat exchanger, if the warmer airstream is cooled below its dew point, the resulting condensed moisture transfers additional energy. When condensation occurs, latent heat is released, maintaining that airstream at a higher temperature than if condensation had not occurred. This higher air temperature (potential flux) increases the heat transfer to the other airstream. The sensible and total effectiveness are widely used because the energy flow in the condensate is relatively small in most applications. (Freezing and frosting are unsteady conditions that should be avoided unless a defrost cycle is included.) Equations (5a) and (5b) must be used to calculate the leaving air humidity conditions, and Equations (7a) and (7b) to calculate the enthalpy values for airstreams in which inherent latent energy transfer occurs. Equations (3a) and (3b) may be used for airstreams if only sensible energy transfer is involved.

Step 6. Check energy transfer balance between airstreams.

Equations (3c) and (3d) can be used to estimate the sensible energy for the two airstreams, and Equations (8a) and (8b) can estimate the total energy for the two airstreams. Total energy transferred from one airstream should equal total heat transferred to the other. Calculate and compare the energy transferred to or from each airstream. Differences between these energy flows are usually because of measurement errors.

Step 7. Plot entering and leaving conditions on psychrometric chart.

Examine the plotted information for each airstream to verify that performance is reasonable and accurate.

(Steps 8 to 10 apply only when EATR0 and OACF1.)

Step 8. Obtain data on exhaust air transfer ratio (EATR > 0 and typically 0.05 > EATR > 0 for regenerative wheels).

Request the EATR data from the manufacturer, who may have certified AHRI Standard 1060 test condition data obtained using ASHRAE Standard 84 as a test procedure and analysis guide. These data may be extrapolated to non-AHRI test conditions using correlations relating EATR to air pressure differences between the supply and exhaust and, for rotary regenerative wheels, carryover caused by wheel rotation. Shang et al. (2001a) show that, for regenerative wheels, a correlation may be developed between EATR and carryover ratio, Rc, and OACF, but for other air-to-air exchangers EATR will be very small or negligible.

Step 9. Obtain data on outdoor air correction factor (OACF ≈ 1 and typically 0.9 < OACF < 1.1 for regenerative wheels).

Request the OACF data from the manufacturer, who may have certified AHRI Standard 1060 test condition data obtained using ASHRAE Standard 84 as a test procedure and analysis guide. These data may be extrapolated to non-AHRI test conditions using correlations relating OACF to pressure differences (Shang et al. 2001b), for regenerative wheels; for other exchangers, OACF will be very nearly 1.0.

Step 10. Correct the supply air ventilation rate, moisture transfer rate, and energy transfer rates for EATR ≠ 0 and OACF ≠ 1.0.

Values of EATR significantly larger than zero and OACF significantly different than 1.0 imply the air-to-air exchanger is transferring air between the exhaust and supply airstreams. This transfer may be important, especially for some devices such as regenerative wheels. Shang et al. (2001b) show a method to correct the energy rates when EATR ≠ 0 and OACF ≠ 1. The procedure to correct the supply air ventilation rate is shown in Example 9.

Example 6. Sensible Heat Recovery in Winter

Exhaust air at 75°F and 10% rh with a flow rate of 800 lb/min preheats an equal mass flow rate of outdoor air at 0°F and 60% rh (ρ = 0.087 lb/ft3) using an air-to-air heat exchanger with a measured effectiveness of 60%. Airflows are specified in scfm, so an air density of 0.075 lb/ft3 for both airstreams is appropriate. Assuming EATR = 0 and OACF ≈ 1, determine the leaving supply air temperatures and energy recovered, and check the heat exchange balance.

Solution:

Note: the numbers correspond to the steps in the calculation procedure.

  1. Because data on pressure drop are missing, skip this step.

  2. Calculate the theoretical maximum heat transfer.

    The two inlet conditions plotted on a psychrometric chart (Figure 34) indicate that, because the exhaust air has low relative humidity, latent energy transfer does not occur. Using Equation (2c), the theoretical maximum sensible heat transfer rate qs is

  3. Establish the sensible effectiveness.

    From manufacturer’s literature and certified performance test data, effectiveness is determined to be 60% at the design conditions.

  4. Calculate actual heat transfer at given conditions.

    Using Equation (2b),

  5. Calculate leaving air conditions.

    Because no moisture or latent energy transfer will occur,

    1. Leaving supply air temperature t2 is given as

    2. Leaving exhaust air temperature t4 is given as

  6. Using Equations (3c) and (3d), check performance.

  7. Plot conditions on psychrometric chart to confirm that no moisture exchange occurred (Figure 34).

    Because EATR = 0 and OACF ≈ 1, Steps 8 to 10 of the calculation procedure are not presented here.


Sensible Heat Recovery in Winter (Example 6)

Figure 34. Sensible Heat Recovery in Winter (Example 6)


Example 7. Sensible Heat Recovery in Winter with Water Vapor Condensation

Exhaust air at 75°F and 28% rh (ρ = 0.075 lb/ft3) and flow rate of 10,600 cfm is used to preheat 9500 cfm of outdoor air at 14°F and 50% rh (ρ = 0.084 lb/ft3) using a heat exchanger with a sensible effectiveness of 70%. Assuming EATR = 0 and OACF ≈ 1, determine the leaving supply air conditions and energy recovered, and check the energy exchange balance.

Solution:

The supply airstream has a lower airflow rate than the exhaust airstream, so it may appear that the supply airstream limits heat transfer. However, determination of mass flow rates for the given entry conditions shows that the mass flow rate of the supply airstream (47,900 lb/h) is slightly greater than that of the exhaust airstream (47,600 lb/h), so exhaust is the limiting airstream. Nevertheless, because the mass difference is negligible, it is convenient to use supply air volume as the limiting airstream.

  1. Because data on pressure drop are missing, skip this step.

  2. Calculate the theoretical maximum sensible heat transfer.

    The limiting airstream, the supply airstream, will be preheated in the heat exchanger, so it is not subject to condensation. Therefore, Equation (2c) is used:

  3. Select sensible effectiveness.

    From manufacturer’s literature and performance test data, the sensible effectiveness is determined to be 70% at the design conditions.

  4. Calculate actual heat transfer at design conditions using Equation (2b):

  5. Calculate leaving air conditions.

    1. Leaving supply air temperature is calculated by

    2. Because the dew point of exhaust air at inlet is 38.4°F, condensation occurs on the exhaust side, so the leaving exhaust air temperature cannot be determined using Equation (3b). The entering exhaust air enthalpy and humidity ratio are determined for the dry-bulb temperature of 75°F and 28% rh using a psychrometric chart and found to be h3 = 23.7 Btu/lb and w3 = 0.0052 lb/lb. However, the leaving exhaust air enthalpy can be determined by

      Because the air will be saturated at the outlet of exhaust air, the dry-bulb or wet-bulb temperature and humidity ratio corresponding to an enthalpy of 13.43 Btu/lb is found to be t4 = 35.7°F and w4 = 0.0044 lb/lb. The rate of moisture condensed mw is

  6. Check performance.

    Neglect the enthalpy of the condensed water by adding the energy lost through condensation of vapor to the sensible heat lost of the exhausting air.

  7. Plot conditions on psychrometric chart (Figure 35). Note that moisture condenses in the exhaust side of the heat exchanger.

    Because EATR = 0 and OACF ≈ 1, Steps 8 to 10 of the calculation procedure are not presented here.


Sensible Heat Recovery in Winter with Condensate (Example 7)

Figure 35. Sensible Heat Recovery in Winter with Condensate
(Example 7)


Example 8. Total Heat Recovery in Summer

Exhaust air at 75°F and 63°F wb (ρ = 0.073 lb/ft3) with a flow rate of 10,600 cfm is used to precool 8500 cfm of supply outdoor air at 95°F and 81°F wb (ρ = 0.069 lb/ft3) using a hygroscopic total energy exchanger. The sensible and total effectiveness for this heat exchanger are 70 and 56.7%, respectively. Assuming EATR = 0 and OACF ≈ 1, determine the leaving supply air conditions and energy recovered, and check the energy exchange balance.

Solution:

  1. Because data on pressure drop are missing, skip this step.

  2. Calculate the theoretical maximum heat transfer.

    The supply airstream is a lesser or limiting airstream for energy and moisture transfer. Determine entering airstream enthalpies and humidity ratio from psychrometric chart.

    The theoretical maximum sensible and total heat transfer rates can be obtained as follows:

  3. Determine supply sensible and total effectiveness.

    The manufacturer’s selection data for the design conditions provide the following effectiveness ratios:

  4. Calculate energy transfer at design conditions.

  5. Calculate leaving air conditions.

    1. Supply air conditions

      From the psychrometric chart, the supply air humidity ratio and wet-bulb temperature are found to be w2 = 0.0145 and tw2 = 71.6°F.

    2. Exhaust air conditions

      From the psychrometric chart, the exhaust humidity ratio and wet-bulb temperature are found to be w4 = 0.0134 and tw4 = 71.6°F.

  6. Check total performance (Equations 9 and 10).

  7. Plot conditions on psychrometric chart (Figure 36).

    Because EATR = 0 and OACF ≈ 1, Steps 8 to 10 are not presented here.


Total Heat Recovery in Summer (Example 8)

Figure 36. Total Heat Recovery in Summer (Example 8)


Example 9. Total Energy Recovery with EATR ≠ 0 and OACF ≠ 1.0.

An ERV manufacturer claims a product has performance characteristics as shown in Figure 37. A building has a ventilation requirement of 850 cfm and exhaust air at 75°F and 63°F wb (ρ = 0.075 lb/ft3) is used to precool supply outdoor air at 95°F and 81°F wb (ρ = 0.072 lb/ft3).

  1. Assuming EATR = 0 and OACF ≈ 1, determine the leaving supply air conditions and energy recovered, and check the energy exchange balance.

  2. If EATR = 5% and OACF = 1.05, determine the actual airflow rates.

Solution:

  1. From Figure 5, at a flow rate of 850 cfm, the pressure drop Δp = 0.9 in. of water. Assuming the effective efficiency of the fan motor combination is about 0.6, the power Ps required to circulate the supply air can be obtained from Equation (11) as

    Assuming the balanced flow the power required to circulate the exhaust air would be same, therefore the total power P required to circulate the airstreams would be twice this amount.

  2. Calculate the theoretical maximum heat transfer.

    Determine entering airstream enthalpies and humidity ratio from the psychrometric chart.

    The theoretical maximum heat transfer rates can be obtained as follows:

    Note that sum of sensible and latent energy should equal the total energy.

  3. Determine supply sensible and total effectiveness.

    From Figure 5 at a flow rate of 850 cfm, εs = 0.73, εL = 0.68, and εt = 0.715.

  4. Calculate energy transfer at design conditions.

  5. Calculate leaving air conditions.

    1. Supply air conditions

      From the psychrometric chart, the supply air humidity ratio and wet-bulb temperature are w2 = 0.0129 and tw2 = 69.2°F.

    2. Exhaust air conditions

      From the psychrometric chart, the exhaust humidity ratio and wet-bulb temperature are found to be w4 = 0.0164, tw4 = 76.1°F.

  6. Check total performance.

  7. Plot conditions on psychrometric chart (Figure 37).

  8. Obtain data on EATR. (Given: EATR = 5% or 0.05.)

  9. Obtain data on OACF. (Given: OACF = 1.05.)

  10. Correct the supply air ventilation rate, the moisture transfer rate, and energy transfer rates EATR ≠ 0 and OACF ≠ 1.0.

    The net ventilation rate is 850 cfm and the EATR = 0.05; therefore, the actual flow rate Q2 to the space can be obtained from Equation (22) as

    Because OACF = 1.05, the actual flow rate Q1 of fresh air from outdoor can be calculated from Equation (23) as

    To balance the flow rates into the ERV, the actual air flow rates at states 3 and 4 are as shown in Figure 38.


Total Energy Recovery with EATR ≠ 0 and OACF ≠ 1 (Example 9)

Figure 37. Total Energy Recovery with EATR ≠ 0 and
OACF ≠ 1 (Example 9)


Actual Airflow Rates at Various State Points (Example 9)

Figure 38. Actual Airflow Rates at Various State Points
(Example 9)


Supply and exhaust fan capacity should match the flows required at their locations. Example 9’s results are for balanced flow. Assuming flow rates in the ERV are same as the outdoor air ventilation requirements, then the effectiveness would be same as that for no air leakage. If air leaks at the inlet and outlet of the energy recovery ventilator, then the exit conditions of air temperature and humidity at states 3 and 4 can be calculated as those of the airstream mixture. For instance, the properties at state 2 would be those of an airstream mixture at state 2 for no air leakage and air quantity (Q32) at state 3. The error for these calculations should be less than 5%.

Shang et al. (2001a) show a method to accurately estimate the energy rates when EATR ≠ 0 and OACF ≠ 1.

10. SYMBOLS

A

=

area of recovery exchanger, ft2

cp

=

specific heat of moist air, Btu/lb ·°F

C

=

capital cost

Ce

=

cost of energy

Cr

=

ratio of Cmin/Cmax

Cs,int

=

initial system capital cost

CRF

=

capital recovery factor

h

=

enthalpy, Btu/lb

hfg

=

enthalpy of vaporization, Btu/lb

i

=

arbitrary state, or discount rate

ITC

=

income tax credit

ms

=

mass flow rate of supply moist air from outdoors, lb/min

me

=

mass flow rate of exhaust moist air, lb/min

min

=

minimum mass flow rate of supply and exhaust airstreams, lb/min

n

=

number of years in consideration, years

NTU

=

number of transfer units = UA/Cmin

p

=

pressure, in. of water

pp

=

payback period, years

P

=

pumping power, Btu/h

q

=

heat transfer rate, Btu/h

Q

=

volume flow rate, cfm

S

=

reference temperature, °F

t

=

moist air temperature at state i, °F

tw3

=

wet-bulb temperature of moist air at state 3, °F

T

=

absolute temperature, °F, or tax

U

=

overall heat transfer coefficient, Btu/h · ft2 · °F

V

=

mean velocity, fpm

w

=

humidity ratio

 Greek Letters

εs

=

sensible effectiveness of heat or energy wheel

εL

=

latent effectiveness of energy wheel

εt

=

total effectiveness of ERV

η

=

efficiency

ρ

=

density, lb/ft3

σ

=

volume fraction

ϕ

=

relative humidity

ω

=

rotational speed of the wheel, rpm

 Subscripts

a

=

air

e

=

exhaust side of heat/energy exchanger, exit or energy

f

=

fan or fan motor combination

if

=

threshold temperature of the outdoor air for freezing to occur

in

=

indoor conditions of building space

inc

=

increment

h

=

hydraulic

L

=

latent

max

=

maximum value

min

=

minimum value

o

=

reference state or outlet

p

=

constant pressure

s

=

supply side or suction side

t

=

total

REFERENCES

AHRI. 2014. Performance rating air-to-air heat exchangers for energy recovery ventilation heat equipment. ANSI/AHRI Standard 1060-2014. Air-Conditioning, Heating, and Refrigeration Institute, Arlington, VA

AHRI. 2011. Calculating the efficiency of energy recovery ventilation and its effect on efficiency and sizing of building HVAC systems. AHRI Guideline V-2011. Air-Conditioning, Heating, and Refrigeration Institute, Arlington, VA.

ASHRAE. 1982. Symposium on energy recovery from air pollution control. ASHRAE Transactions 88(1):1197-1225.

ASHRAE. 2013. Ventilation for acceptable indoor air quality. ANSI/ASHRAE Standard 62.1-2013.

ASHRAE. 2013. Ventilation and acceptable indoor air quality in low-rise residential buildings. ANSI/ASHRAE Standard 62.2-2013.

ASHRAE. 2013. Method of testing air-to-air heat/energy exchangers. ANSI/ASHRAE Standard 84-2013.

Barringer, C.G., and C.A. McGugan. 1989a. Development of a dynamic model for simulating indoor air temperature and humidity. ASHRAE Transactions 95(2):449-460.

Barringer, C.G., and C.A. McGugan. 1989b. Effect of residential air-to-air heat and moisture exchangers on indoor humidity. ASHRAE Transactions 95(2):461-474.

Besant, R.W., and A.B. Johnson. 1995. Reducing energy costs using run-around systems. ASHRAE Journal 37(2):41-47.

Besant, R.W., and C.J. Simonson. 2000. Air-to-air energy recovery. ASHRAE Journal 42(5):31-38.

Besant, R.W., and C. Simonson. 2003. Air-to-air exchangers. ASHRAE Journal 45(4):42-50.

C2ES. 2015. Center for Climate and Energy Solutions. www.c2es.org.

Dhamshala, P. 2016. Modern practices in design of air-conditioning and refrigerated systems. The University of Tennessee, Chattanooga, Graphic Services, Chattanooga.

Dhital, P., R. Besant, and G.J. Schoenau. 1995. Integrating run-around heat exchanger systems into the design of large office buildings. ASHRAE Transactions 101(2):979-999.

Enteria, N., H. Yoshino, R. Takaki, H. Yonekura, A. Satake, and A. Mochida. 2013. First and second law analysis of the developed solar-desiccant air-conditioning system (SDACS) operation during the summer day. Energy and Buildings 60:239-251.

Friedlander, M. 2003. How certified ratings can improve system design. Seminar at ASHRAE Winter Annual Meeting, Chicago.

Gao, W.Z., Y.P. Cheng, A.G. Jiang, T. Liu, and K. Anderson. 2015. Experimental investigation on integrated liquid desiccant—Indirect evaporative air cooling system utilizing the Maisotesenko cycle. Applied Thermal Engineering 88:288-296.

Ge, T.S., Y.J. Dai, R.Z. Wang, and Y. Li. 2015. Performance of two-stage rotary desiccant cooling system with different regeneration temperatures. Energy 81:556-566.

Guo, P., D.L. Ciepliski, and R.W. Besant. 1998. A testing and HVAC design methodology for air-to-air heat pipe heat exchangers. International Journal of HVAC&R Research (now Science and Technology for the Built Environment) 4(1):3-26.

Jain, S., and P.K. Bansal. 2007. Performance analysis of liquid desiccant dehumidification systems. International Journal of Refrigeration 30(5): 861-872.

Johnson, A.B., R.W. Besant, and G.J. Schoenau. 1995. Design of multi-coil run-around heat exchanger systems for ventilation air heating and cooling. ASHRAE Transactions 101(2):967-978.

Johnson, A.B., C.J. Simonson, and R.W. Besant. 1998. Uncertainty analysis in the testing of air-to-air heat/energy exchangers installed in buildings. ASHRAE Transactions 104(1B):1639-1650.

Kays, W.M., and M.E. Crawford, 1993. Convective heat and mass transfer, 3rd ed. McGraw-Hill, New York.

Liu, X., T. Zhang, Y. Zheng, and R. Tu. 2016. Performance investigation and exergy analysis of two-stage desiccant wheel systems. Renewable Energy 86:877-888.

Mathur, G.D. 1990a. Long-term performance prediction of refrigerant charged flat plate solar collector of a natural circulation closed loop. ASME HTD 157:19-27.

Mathur, G.D. 1990b. Indirect evaporative cooling using heat pipe heat exchangers. ASME Symposium, Thermal Hydraulics of Advanced Heat Exchangers, ASME Winter Annual Meeting, Dallas.

Mathur, G.D. 1992. Indirect evaporative cooling. Heating/Piping/Air Conditioning 64(4):60-67.

Mathur, G.D. 1993. Retrofitting heat recovery systems with evaporative coolers. Heating/Piping/Air Conditioning 65(9):47-51.

Mathur, G.D. 1997a. Performance enhancement of existing air conditioning systems. Proceedings of Intersociety Energy Conversion Engineering Conference, Honolulu, American Institute of Chemical Engineers, Paper #97367, pp. 1618-1623.

Mathur, G.D. 1997b. Using heat pipe heat exchangers for reducing high energy costs of treating ventilation air. Proceedings of Intersociety Energy Conversion Engineering Conference, American Institute of Chemical Engineers, vol. 2, pp. 1447-1452.

Mathur, G.D. 1997c. Predicting yearly energy savings using BIN weather data with heat pipe heat exchangers. Proceedings of Intersociety Energy Conversion Engineering Conference, American Institute of Chemical Engineers, vol. 2, pp. 1391-1396.

Mathur, G.D. 1997d. Performance enhancements of existing air conditioning systems. Proceedings of Intersociety Energy Conversion Engineering Conference, American Institute of Chemical Engineers, vol. 3, pp. 1618-1623.

Mathur, G.D. 2000. Controlling space humidity with heat pipe heat exchangers. Proceedings of Intersociety Energy Conversion Engineering Conference, American Institute of Chemical Engineers, vol. 2, pp. 835-842.

Mathur, G.D., and T.W. McDonald. 1986. Simulation program for a two-phase thermosiphon-loop heat exchanger. ASHRAE Transactions 92(2A): 473-485.

Mathur, G.D., and T.W. McDonald. 1987. Evaporator performance of finned air-to-air two-phase thermosiphon loop heat exchangers. ASHRAE Transactions 98(2):247-257.

McDonald, T.W., and D. Shivprasad. 1989. Incipient nucleate boiling and quench study. Proceedings of CLIMA 2000 1:347-352. Sarajevo, Yugoslavia.

Moffitt, R. 2003. Personal communication and reference, Trane Application Engineering Manual SYS-APM003-EN.

Moffitt, R. 2010. Using energy recovery to improve dehumidification performance and control. Seminar 34, ASHRAE Winter Meeting, Orlando.

Moffitt, R. 2011. Energy wheel capacity control. Trane.

Mostafa, A.A., and M.M. Mausa. 2007. Heat pipe heat exchanger for heat recovery in air conditioning. Applied Thermal Engineering 27(4):795-801.

Moffitt, R. 2015. Dedicated outside air system with dual energy recovery used with distributed sensible cooling equipment. ASHRAE Transactions, Paper AT-15-C047.

Murphy, J. 2006. Temperature and humidity control in surgery rooms. ASHRAE Journal, June.

Phillips, E.G., R.E. Chant, B.C. Bradley, and D.R. Fisher. 1989a. A model to compare freezing control strategies for residential air-to-air heat recovery ventilators. ASHRAE Transactions 95(2):475-483.

Phillips, E.G., R.E. Chant, D.R. Fisher, and B.C. Bradley. 1989b. Comparison of freezing control strategies for residential air-to-air heat recovery ventilators. ASHRAE Transactions 95(2):484-490.

Phillips, E.G., D.R. Fisher, R.E. Chant, and B.C. Bradley. 1992. Freeze-control strategy and air-to-air energy recovery performance. ASHRAE Journal 34(12):44-49.

Ruch, M.A. 1976. Heat pipe exchangers as energy recovery devices. ASHRAE Transactions 82(1):1008-1014.

Scofield, M., and J.R. Taylor. 1986. A heat pipe economy cycle. ASHRAE Journal 28(10):35-40.

Shah, R.K. 1981. Thermal design theory for regenerators. In Heat exchangers: Thermal-hydraulic fundamentals and design. S. Kakec, A.E. Bergles, and F. Maysinger, eds. Hemisphere Publishing, New York.

Shang, W., M. Wawryk, and R.W. Besant. 2001a. Air crossover in rotary wheels used for air-to-air heat and moisture recovery. ASHRAE Transactions 107(2).

Shang, W., H. Chen, R.W. Evitts, and R.W. Besant. 2001b. Frost growth in regenerative heat exchangers: Part I—Problem formulation and method of solution; Part II—Simulation and discussion. Proceedings of ASME International Mechanical Engineering Congress and Expo, November, New York.

Sheng, Y., Y. Zhang, and G. Zhang. 2015. Simulation and energy savings analysis of high temperature heat pump coupling to desiccant wheel air conditioning system. Energy 83:583-596.

Simonson, C.J., W. Shang, and R.W. Besant. 2000. Part-load performance of energy wheels: Part I—Speed control. ASHRAE Transactions 106(1): 286-300.

Sparrow, E.M., J.P. Abraham, and J.C.K. Tong. 2001. An experimental investigation on a mass exchanger for transferring water vapor and inhibiting the transfer of other gases. International Journal of Heat and Mass Transfer 44 (November):4313-4321.

Sultan, M., I.I. El-Sharkawy, T. Miyazaki, B.B. Saha, and S. Koyama. 2015. An overview of solid desiccant dehumidification and air conditioning systems. Renewable and Sustainable Energy Reviews 46:16-29.

Tu, R., X.-H. Liu, and Y. Jiang. 2015a. Lowering the regeneration temperature of a rotary wheel dehumidification system using exergy analysis. Energy Conversion and Management 89:162-174.

Tu, R., Y. Liu, and Y. Jiang. 2015b. Irreversible processes and performance improvement of desiccant wheel dehumidification and cooling systems using exergy. Applied Energy 145:331-344.

Williams, S. 2007. Assessment of liquid desiccant cooling technology. Master’s thesis, The University of Tennessee, Chattanooga.

Yau, Y.H. 2007. Application of a heat pipe heat exchanger to dehumidification enhancement in a HVAC system for tropical climates—A baseline performance characteristics study. International Journal of Thermal Sciences 46(2):164-171.

Yau, Y.H. 2008. The use of a double pipe heat exchanger system for reducing energy consumption of treating ventilation air in an operating theatre—A full year energy consumption model simulation. Energy and Buildings 40(5):917-925.

Wu, X.P., P. Johnson, and A. Akabarzadah. 1997. Application of heat pipe heat exchangers to humidity control in air conditioning systems. Applied Thermal Engineering 17(6):561-568.

Zeng, D.Q., H. Li, Y.J. Dai, and A.X. Xie. 2014. Numerical analysis and optimization of solar hybrid one-rotor two-stage desiccant cooling and heating system. Applied Thermal Engineering 73:474-483.

BIBLIOGRAPHY

AHRI. 2014. Selecting, sizing, and specifying packaged air-to-air energy recovery ventilation equipment. AHRI Guideline W. Air-Conditioning, Heating, and Refrigeration Institute, Arlington, VA.

Andersson, B., K. Andersson, J. Sundell, and P.A. Zingmark. 1992. Mass transfer of contaminants in rotary enthalpy exchangers. Indoor Air 93(3): 143-148.

ASHRAE. 1974. Symposium on heat recovery. ASHRAE Transactions 80(1):302-332.

CSA. 1988. Standard methods of test for rating the performance of heat-recovery ventilators. CAN/CSA-C439-88. Canadian Standards Association, Rexdale, ON.

Ciepliski, D.L., C.J. Simonson, and R.W. Besant. 1998. Some recommendations for improvements to ASHRAE Standard 84-1991. ASHRAE Transactions 104(1B):1651-1665.

Dhamshala, P., and S. Patel. 2016. Use of heat and desiccant wheels in combination with a heat pump to reduce energy cost savings. Master’s thesis, The University of Tennessee, Chattanooga.

Dehli, F., T. Kuma, and N. Shirahama. 1993. A new development for total heat recovery wheels. Energy Impact of Ventilation and Air Infiltration, 14th AIVC Conference, Copenhagen, Denmark, pp. 261-268.

Inoue, T., and M. Monde. 2009. Operating limit of heat transport in two-phase thermosiphon with connecting pipe. International Journal of Heat & Mass Transfer 52:4519-4524.

Jouhara, H., and R. Meskimmon. 2010. Experimental investigation of wraparound loop heat pipe heat exchanger used in energy efficient air handling units. Energy 35(12):4592-4599.

Jeffus, L. 2003. Refrigeration and air conditioning: An introduction to HVAC/R. Pearson Prentice Hall, Upper Saddle River, NJ.

Mathur, G.D. 1990. Indirect evaporative cooling using two-phase thermosiphon loop heat exchangers. ASHRAE Transactions 96(1):1241-1249.

Mathur, G.D., and T.W. McDonald. 1987. Evaporator performance of finned air-to-air two-phase thermosiphon loop heat exchangers. ASHRAE Transactions 98(2):247-257.

Mathur, G.D. 1996. Enhancing performance of an air conditioning unit system with a two-phase heat recovery loop retrofit. Proceedings of Intersociety Energy Conversion Engineering Conference, vol. 3, pp. 2027-2032.

McDonald, T.W., and D. Shivprasad. 1989. Incipient nucleate boiling and quench study. Proceedings of CLIMA 2000 1:347-352. Sarajevo, Yugoslavia.

Ninomura, P.T., and R. Bhargava. 1995. Heat recovery ventilators in multifamily residences in the Arctic. ASHRAE Transactions 101(2):961-966.

Noie-Baghban, S.H., and G.R. Majideian. 2000. Waste heat recovery using heat pipe heat exchanger (HPHE) for surgery rooms in hospitals. Applied Thermal Engineering 20(14):1271-1282.

Shang, W., and R.W. Besant. 2001. Energy wheel effectiveness evaluation: Part I—Outlet airflow property distributions adjacent to an energy wheel; Part II—Testing and monitoring energy wheels in HVAC applications. ASHRAE Transactions 107(2).

Sheng, Y., Y. Zhang, Y. Sun, L. Fang, J. Nie, and L. Ma. 2014. Experimental analysis and regression prediction of desiccant wheel behavior in high temperature heat pump and desiccant wheel air-conditioning system. Energy and Buildings 80:358-365.

Simonson, C.J., and R.W. Besant. 1997. Heat and moisture transfer in desiccant coated rotary energy exchangers: Part I—Numerical model; Part II—Validation and sensitivity studies. International Journal of HVAC&R Research (now Science and Technology for the Built Environment) 3(4): 325-368.

Simonson, C.J., and R.W. Besant. 1998. Heat and moisture transfer in energy wheels during sorption, condensation and frosting. ASME Journal of Heat Transfer 120(3):699-708.

Simonson, C.J., and R.W. Besant. 1998. Energy wheel effectiveness: Part I—Development of dimensionless groups; Part II—Correlations. International Journal of Heat and Mass Transfer 42(12):2161-2186.

Simonson, C.J., D.L. Cieplisky, and R.W. Besant. 1999. Determining performance of energy: Part I—Experimental and numerical methods; Part II—Experimental data and validation. ASHRAE Transactions 105(1): 177-205.

SMACNA. 1978. Energy recovery equipment and systems. Report.

Sparrow, E.M., J.P. Abraham, J.C. Tong, and G.L. Martin. 2001. Air-to-air energy exchanger test facility for mass and energy transfer performance. ASHRAE Transactions 107(2):450-456.

Stauder, F.A., and T.W. McDonald. 1986. Experimental study of a two-phase thermosiphon-loop heat exchanger. ASHRAE Transactions 92(2A):486-497.

Stauder, F.A., G.D. Mathur, and T.W. McDonald. 1985. Experimental and computer simulation study of an air-to-air two-phase thermosiphon-loop heat exchanger. ASME 85-WA/HT-15.



The preparation of this chapter is assigned to TC 5.5, Air-to-Air Energy Recovery.