A Fan uses a power-driven rotating impeller to move air. The impeller does work on the air, imparting to it both static and kinetic energy, which vary in proportion, depending on the fan type.
Fans are generally classified as centrifugal, axial, mixed, or cross flow according to the direction of airflow through the impeller. Figure 1 shows the general configuration of a centrifugal fan. The components of an axial-flow fan are shown in Figure 2. Table 1 compares typical characteristics of some of the most common fan types.
Unhoused centrifugal fan impellers are used as circulators in some industrial applications (e.g., heat-treating ovens) and are identified as plug fans. In this case, there is no duct connection to the fan because it simply circulates the air within the oven. In some HVAC installations, the unhoused fan impeller is located in a plenum chamber with the fan inlet connected to an inlet duct from the system. Outlet ducts are connected to the plenum chamber. This fan arrangement is identified as a plenum fan.
2. PRINCIPLES OF OPERATION
All fans produce pressure by altering the airflow’s velocity vector. A fan produces pressure and/or airflow because the rotating blades of the impeller impart kinetic energy to the air by changing its velocity. Velocity change is in the tangential and radial velocity components for centrifugal fans, and in the axial and tangential velocity components for axial-flow fans.
Centrifugal fan impellers produce pressure from the (1) centrifugal force created by rotating the air column contained between the blades and (2) kinetic energy imparted to the air by its velocity leaving the impeller. This velocity is a combination of rotational velocity of the impeller and airspeed relative to the impeller. When the blades are inclined forward, these two velocities are cumulative; when backward, oppositional. Backward-curved blade fans are generally more efficient than forward-curved blade fans.
Axial-flow fan impellers produce pressure principally by the change in air velocity as it passes through the impeller blades, with none being produced by centrifugal force. These fans are divided into three types: propeller, tubeaxial, and vaneaxial. Propeller fans, customarily used at or near free air delivery, usually have a small-hub-to-tip-ratio impeller mounted in an orifice plate or inlet ring. Tubeaxial fans usually have reduced tip clearance and operate at higher tip speeds, giving them a higher total pressure capability than the propeller fan. Vaneaxial fans are essentially tubeaxial fans with guide vanes and reduced running blade tip clearance, which give improved pressure, efficiency, and noise characteristics.
Table 1 includes typical performance curves for various types of fans. These performance curves show the general characteristics of various fans as they are normally used; they do not reflect fan characteristics reduced to common denominators such as constant speed or constant propeller diameter, because fans are not selected on the basis of these constants. The efficiencies and power characteristics shown are general indications for each type of fan. A specific fan (size, speed) must be selected by evaluating actual characteristics.
ANSI/ASHRAE Standard 51 (ANSI/AMCA Standard 210) specifies the procedures and test setups to be used in testing fans and other air-moving devices. The most common type of test uses multiple nozzle inlet or outlet chambers. Figure 3 illustrates a pitot traverse procedure for developing characteristics of a fan. Fan performance is determined from free delivery conditions to shutoff conditions. At shutoff, the fan is completely blocked off; at free delivery, outlet resistance is reduced to zero. Between these two conditions, an auxiliary fan and various airflow restrictions are used to simulate various operating conditions on the fan. Sufficient points are obtained to define the curve between shutoff and free air delivery conditions. For each case, the specific point on the curve must be defined by referring to the airflow rate and corresponding total or static pressure. Other test setups described in ANSI/ASHRAE Standard 51 should produce a similar performance curve, except for fans that produce a significant amount of swirl.
Fans designed for use with duct systems are tested with a length of duct between the fan and measuring station. The length of duct evens out the air velocity profile discharged from the fan outlet to provide stable, uniform airflow conditions at the plane of measurement. Pressure losses of the ductwork and flow straightener between the fan outlet and the plane of measurement are added to the measured pressure at the plane of measurement to determine the actual fan performance. Fans designed for use without ducts, including almost all propeller fans and power roof ventilators, are tested without ductwork.
Not all fan sizes are tested for rating. Test information may be used to calculate performance of larger fans that are geometrically similar, but such information should not be extrapolated to smaller fans. Test information can also be used to calculate the performance at other speeds by applying fan laws. For performance of one fan to be determined from the known performance of another, the two fans must be dynamically similar. Strict dynamic similarity requires that the important nondimensional parameters (those that affect aerodynamic characteristics, such as Mach number, Reynolds number, surface roughness, and gap size) vary in only insignificant ways. [For more specific information, consult the manufacturer’s application manual, engineering data, or Howden Buffalo (1999).]
4. FIELD TESTING OF FANS FOR AIR PERFORMANCE
The aerodynamic performance of a fan as installed almost always differs from the performance determined by laboratory testing. Performance differences primarily derive from system configuration differences between the field and laboratory setup, such as added elbows, obstructions in the path of the airflow, and sudden changes of duct cross-sectional area in the field installation.
Because of the performance differences, it is sometimes necessary to determine the in situ performance of a fan. Typical reasons fan field testing that may be required include the following:
-
A general fan system evaluation to be used as the basis for modifying or adjusting fan drive components or the system to which the fan is attached
-
A fan acceptance test (FAT) per specification in a sales agreement to verify quoted fan performance
-
A proof of performance test in response to a complaint to demonstrate fan performance
In North America, most general fan system evaluations in the field can be accomplished using the guidelines outlined in AMCA Publication 203. When field testing is required and more accurate results are needed to meet a stringent contract, AMCA Standard 803 or ASME Code PTC 11 is often used. In Europe and other areas of the world, ISO Standard 5802 is sometimes used. Because finding a suitable flow measurement plane can often be difficult in the field, it is highly recommended to include provisions for a calibrated flow measuring station near the fan inlet and/or outlet or pressure ports on the fan as part of system design.
The fan laws (see Table 2) relate performance variables for any dynamically similar series of fans. The variables are fan size D, rotational speed N, gas density ρ, volume airflow rate Q, pressure Ptf or Psf, power W, and mechanical efficiency ηt. Fan Law 1 shows the effect of changing size, speed, or density on volume airflow rate, pressure, and power level. Fan Law 2 shows the effect of changing size, pressure, or density on volume airflow rate, speed, and power. Fan Law 3 shows the effect of changing size, volume airflow rate, or density on speed, pressure, and power.
The fan laws apply only to a series of aerodynamically similar fans at the same point of rating on the performance curve. They can be used to predict the performance of any fan when test data are available for any fan of the same series. Fan laws may also be used with a particular fan to determine the effect of speed change. However, caution should be exercised in these cases, because the laws apply only when all flow conditions are similar. Changing the speed of a given fan changes parameters that may invalidate the fan laws.
Unless otherwise identified, fan performance data are based on dry air at standard conditions: 14.696 psi and 70°F (0.075 lb/ft3). In actual applications, the fan may be required to handle air or gas at some other density. The change in density may be caused by temperature, composition of the gas, or altitude. As indicated by the fan laws, fan performance is affected by gas density. With constant size and speed, power and pressure vary in accordance with the ratio of gas density to standard air density.
Figure 4 illustrates the application of the fan laws for a change in fan speed N for a specific-sized fan (i.e., D1 = D2). The computed Ptf curve is derived from the base curve. For example, point E (N1 = 650) is computed from point D (N2 = 600) as follows:
At point D,
Using Fan Law 1a at point E,
Using Fan Law 1b (ρ1 = ρ2),
The total pressure curve Ptf1 at N = 650 rpm may be generated by computing additional points from data on the base curve, such as point G from point F.
If equivalent points of rating are joined, as shown by the dashed lines in Figure 4, they form parabolas, which are defined by the relationship expressed in Equation (2).
Each point on the base Ptf curve determines only one point on the computed curve. For example, point H cannot be calculated from either point D or point F. Point H is, however, related to some point between these two points on the base curve, and only that point can be used to locate point H. Furthermore, point D cannot be used to calculate point F on the base curve. The entire base curve must be defined by test.
6. FAN AND SYSTEM PRESSURE RELATIONSHIPS
As previously stated, a fan impeller imparts static and kinetic energy to the air. This energy is represented in the increase in total pressure and can be converted to static or velocity pressure. These two quantities are interdependent: fan performance cannot be evaluated by considering one alone. Energy conversion, indicated by changes in velocity pressure to static pressure and vice versa, depends on the efficiency of conversion. Energy conversion occurs in the discharge duct connected to a fan being tested in accordance with ANSI/ASHRAE Standard 51, and the efficiency is reflected in the rating.
Fan total pressure rise Ptf is a true indication of the energy imparted to the airstream by the fan. System pressure loss (ΔP) is the sum of all individual total pressure losses imposed by the air distribution system duct elements on both the inlet and outlet sides of the fan. An energy loss in a duct system can be defined only as a total pressure loss. The measured static pressure loss in a duct element equals the total pressure loss only in the special case where air velocities are the same at both the entrance and exit of the duct element. By using total pressure for both fan selection and air distribution system design, the design engineer ensures proper design. These fundamental principles apply to both high- and low-velocity systems. (Chapter 21 of the 2017 ASHRAE Handbook—Fundamentals has further information.)
Fan static pressure rise Psf is often used in low-velocity ventilating systems where the fan outlet area essentially equals the fan outlet duct area, and little energy conversion occurs. When fan performance data are given in terms of Psf, the value of Ptf may be calculated from catalog data.
To specify the pressure performance of a fan, the relationship of Ptf, Psf, and Pvf must be understood, especially when negative pressures are involved. Most importantly, Psf is defined in ANSI/ASHRAE Standard 51 as Psf= Ptf – Pvf. Except in special cases, Psf is not necessarily the measured difference between static pressure on the inlet side and static pressure on the outlet side.
Figures 5 to 8 depict the relationships among these various pressures. Note that, as defined, Ptf = Pt2 – Pt1. Figure 5 illustrates a fan with an outlet system but no connected inlet system. Figure 6 shows a fan with an inlet but no outlet system. Figure 7 shows a fan with both an inlet and an outlet system. In both cases, the measured difference in static pressure across the fan (Ps2 – Ps1) is not equal to the fan static pressure (Psf).
All the systems shown in Figures 5 to 7 have inlet or outlet ducts that match the fan connections in size. Usually the duct size is not identical to the fan outlet or inlet, so that a further complication is introduced. To illustrate the pressure relationships in this case, Figure 8 shows a diverging outlet cone, which is a common type of fan connection. Static pressure in the cone actually increases in the direction of airflow. The static pressure changes throughout the system, depending on velocity. The total pressure, which, as noted in the figure, decreases in the direction of airflow, more truly represents the loss introduced by the cone or by flow in the duct. Only the fan changes this trend. Total pressure, therefore, is a better indication of fan and duct system performance. In this normal fan situation, the static pressure across the fan (Ps2 – Ps1) does not equal the fan static pressure Psf.
7. TEMPERATURE RISE ACROSS FANS
In certain applications, it may be desirable to calculate the temperature rise across the fan. For low pressure rises (<10 in. of water), estimate the temperature rise by the following:
where
|
ΔT
|
=
|
temperature rise across fan, °F
|
|
ΔP
|
=
|
pressure rise across fan, in. of water
|
|
Cp
|
=
|
conversion factor = 5.193 lbf/ft2 ·in. of water
|
|
ρ
|
=
|
density, lbm/ft3
|
|
cp
|
=
|
specific heat = 0.24 Btu/lbm·°F
|
|
J
|
=
|
mechanical equivalent of heat = 778.2 ft·lbf/Btu
|
|
η
|
=
|
efficiency, decimal
|
If the motor is not in the airstream, the efficiency is the fan total efficiency. If the motor is in the airstream, the efficiency is the set efficiency (combined efficiencies of motor and fan).
8. DUCT SYSTEM CHARACTERISTICS
Figure 9 shows a simplified duct system with three 90° elbows. These elbows represent the resistance offered by the ductwork, heat exchangers, cabinets, dampers, grilles, and other system components. A given rate of airflow through a system requires a definite total pressure in the system. If the rate of airflow changes, the resulting total pressure required will vary, as shown in Equation (2), which is true for turbulent airflow systems. HVAC systems generally follow this law very closely.
This chapter covers only turbulent flow (the flow regime in which most fans operate). In some systems, particularly constant- or variable-volume air conditioning, the air-handling devices and associated controls may produce effective system resistance curves that deviate widely from Equation (2), even though each element of the system may be described by this equation.
Equation (2) allows plotting a turbulent flow system’s pressure loss (ΔP) curve from one known operating condition (see Figure 4). The fixed system must operate at some point on this system curve as the volume flow rate changes. As an example, in Figure 10, at point A of curve A, when the flow rate through a duct system such as that shown in Figure 9 is 10,000 cfm, the total pressure drop is 3 in. of water. If these values are substituted in Equation (2) for ΔP1 and Q1, other points of the system’s ΔP curve (Figure 10) can be determined.
For 6000 cfm (Point D on Figure 10):
If a change is made within the system so that the total pressure at design flow rate is increased, the system will no longer operate on the previous ΔP curve, and a new curve will be defined.
For example, in Figure 11, an elbow added to the duct system shown in Figure 9 increases the total pressure of the system. If the total pressure at 10,000 cfm is increased by 1.00 in. of water, the system total pressure drop at this point is now 4.00 in. of water, as shown by point B in Figure 10.
If the system in Figure 9 is changed by removing one of the schematic elbows (Figure 12), the resulting system total pressure drops below the total pressure resistance, and the new ΔP curve is curve C of Figure 10. For curve C, a total pressure reduction of 1.00 in. of water has been assumed when 10,000 cfm flows through the system; thus, the point of operation is at 2.00 in. of water, as shown by point C.
These three ΔP curves all follow the relationship expressed in Equation (2). These curves result from changes in the system itself and do not change fan performance. During design, such system total pressure changes may occur because of alternative duct routing, differences in duct sizes, allowance for future duct extensions, or the design safety factor being applied to the system.
In an actual operating system, these three ΔP curves can represent three system characteristic lines caused by three different positions of a throttling control damper. Curve C is the most open position, and curve B is the most closed. A control damper forms a continuous series of these ΔP curves as it moves from wide open to completely closed and covers a much wider range of operation than is shown here. Such curves can also represent the clogging of turbulent flow filters in a system.
A fan is normally tested under standardized laboratory conditions (e.g., wide-open inlet and a long, straight duct attached to the outlet), which result in uniform flow into the fan and efficient static pressure recovery on the fan outlet. When a fan is installed in an application, laboratory conditions are usually not preserved. Typically, inlet and outlet conditions in installations are not the same as in the testing environment, because the fan discharges to a plenum, the discharge/intake side of the fan is too close to a transition (change in area and direction of flow) or wall, or any other interference in the flow field. This difference affects the actual fan performance tested.
The adverse influences of system connections on fan performance are commonly called system effects. To select and apply the fan properly, the system effects must be considered and the pressure requirements of the fan, as calculated by standard duct design procedures, must be increased accordingly. More importantly, because of the huge potential pressure (and thus energy) losses associated with system effects, great care should be taken in actual air system design and installation to eliminate or minimize system effects.
The magnitudes of system effects are typically called system effect factors, and they are values (usually in terms of pressure) suggested to compensate for the system effects. Chapter 21 of the 2017 ASHRAE Handbook—Fundamentals and ASHRAE’s (2011) Duct Fitting Database provide information on calculating the system effect factors for certain duct fittings. AMCA Publication 201 provides further information on determining system effect factors for various conditions. These calculated system effect factors are only an approximation, however. Fans of different types, and even fans of the same type but supplied by different manufacturers, do not necessarily react to a system in the same way. Therefore, judgment based on experience must be applied to air system design.
To provide improved knowledge and additional test data on system effects, ASHRAE completed a series of research projects to study the inlet system effects on both air and sound for different types of fans. Conclusions from these research projects include the following:
-
Substantial system effects will be induced if the distance between the fan inlet and the cabinet wall is less than 0.5 times of the impeller diameter; hence, it should be avoided as much as possible in actual system design and installation.
-
System effects on sound caused by poor inlet conditions are very pronounced but also very hard to quantify.
For more details, please see Darvennes et al. (2008), Stevens and Schubert (2010), and Swim (1997). ASHRAE research projects RP-1216 and RP-1420 (Guedel et al. 2011, 2014) also provide further information on inlet and discharge installation effects on airfoil centrifugal fans.
After the system pressure loss curve of the air distribution system has been defined, a fan can be selected to meet the system requirements (Graham 1966, 1972). Fan manufacturers present performance data in either graphics (curves) (Figure 13), tabular form (multirating tables), or selection software. Multirating tables usually provide only performance data within the recommended operating range. The optimum selection range or peak efficiency point is identified in various ways by different manufacturers.
One of the most important selection criteria for fans is energy use. In recent years, fan energy consumption has been addressed by several energy codes and regulations. Take care to ensure that fans selected for a particular purpose meet applicable codes and standards. For example, ASHRAE Standard 90.1-2013 requires fans in certain applications to meet a minimum fan efficiency grade (FEG). The FEG is a metric used to characterize fan energy efficiency and is defined in ANSI/AMCA Standard 205-12 and ISO Standard 12759:2010. Fans that do not meet the minimum FEG requirement cannot be considered for selection. The FEG is usually reported with manufacturers’ performance data or electronic selection tools. If not, consult the fan manufacturer. Fans that comply with a minimum FEG requirement must be selected so that the difference between the peak total efficiency and the total efficiency at the selection point is within a prescribed value (e.g., 10 points, as shown in Figure 13).
Codes and regulation may also apply to the extended fan system, which includes a motor and other mechanical or electric components. In Europe, for example, European Directive EU No.327/2011: Ecodesign-Fans requires the extended fan system to meet a minimum efficiency metric that is similar to fan motor efficiency grade (FMEG). The FMEG is a wire-to-air efficiency metric and is defined in ISO 12759:2010 Fans-Efficiency Classification for Fans. Determination of FMEG is based on overall fan system peak efficiency, electrical input power, efficiency category, and fan type.
The FEG and FMEG are separate and distinct metrics for describing fan efficiency. They must only be used to establish compliance with applicable codes or regulations, and not as a means to make fan selections or to quantify actual fan performance in a given application.
Performance data as tabulated in typical manufacturers’ fan performance tables are based on arbitrary increments of flow rate and pressure. In these tables, adjacent data, either horizontally or vertically, represent different points of operation (i.e., different points of rating) on the fan performance curve. These points of rating depend solely on the fan’s characteristics; they cannot be obtained from each other by the fan laws. However, points of operation listed in fan performance tables are usually close together, so intermediate points may be interpolated arithmetically with adequate accuracy for fan selection.
Selecting a fan for a particular air distribution system requires that the fan total pressure characteristic fit the system total pressure characteristic. The system total pressure characteristic must also account for any transition needed between the fan inlet/outlet and the system. Because fan performance can change depending on fan installation (e.g., ducted or unducted inlet or outlet), it is important that the system total pressure characteristic and fan performance characteristic refer to the same installation. Thus, the total system must be evaluated and airflow requirements, resistances, and system effect factors at the fan inlet and outlet must be known (see Chapter 21 of the 2017 ASHRAE Handbook—Fundamentals and Chapter 19 of this volume). Fan speed and power requirements are then calculated, using multirating tables or single or multispeed performance curves or graphs.
Energy usage is a function of fan total pressure. Fan performance and system resistance must be specified as total pressure versus flow for proper selection. For many years, manufacturers often have presented fan performance as static pressure versus flow, leading many engineers to select fans by matching fan static pressure to the sum of system static pressure requirements. Although this practice is long standing, it is incorrect. To ensure the best chance to minimize energy consumption, total pressure must be used. Because many catalogs and selection programs use static pressure, it is necessary to calculate the total pressure: this can be done by adding the fan velocity pressure, which can easily be calculated from the flow and the outlet area, to the static pressure.
Fan manufacturers provide catalogs or electronic tools for making fan selections. Fan performance data (e.g., airflow rate, pressure rise, shaft power) are typically presented over a recommended range of fan operating conditions. When the fan is selected within this recommended range, airflow over the aerodynamic surfaces, such as the inlet cone and impeller blades, smoothly follows the surfaces in a way that results in good aerodynamic efficiency. However, when the fan operates outside of this recommended range, airflow may be unable to follow these surfaces and it breaks away, or separates, resulting in a number of undesirable effects. This condition, generally known as stall, is characterized by extensive regions of separated flow, increased noise, and highly unsteady behavior in the key flow variables (airflow rate, pressure rise, and shaft power). The latter effect is known as surge. Fans operating under these conditions are subject to mechanical damage because of the large unsteady forces involved.
Different fan types exhibit stall and surge to varying degrees. Care must be taken when selecting a fan to ensure that operation does not extend beyond the recommended boundaries provided by the fan manufacturer. Fan manufacturers provide a recommended selection range for each fan to avoid stall and flow pulsations. For further information about stall, refer to Eurovent (2007).
In using curves, the point of operation selected (Figure 14) must represent a desirable point on the fan curve, to attain maximum efficiency and resistance to stall and pulsation. In systems where more than one point of operation is encountered during operation, look at the range of performance and evaluate how the selected fan reacts within this complete range. This analysis is particularly necessary for variable-volume systems, where not only the fan undergoes a change in performance, but the entire system deviates from the relationships defined in Equation (2). In these cases, it is necessary to look at actual losses in the system at performance extremes.
Special attention must be given to selecting the proper motor and also related drive components, such as belts and variable-speed drives, when used. The motor and other component ratings must be sufficient to allow operation at all anticipated points of operation. Fans with overloading power characteristics and fans operating at elevated temperatures present areas of concern. Variable-volume systems may require special consideration if operated before system balancing.
11. PARALLEL FAN OPERATION
When two identical fans with stable performance characteristics throughout the range of their individual performance curves operate in parallel, ideally their combined performance curve can be created by doubling the airflow of a single fan at any pressure level. Examples of such fans include backward-inclined centrifugal fans and axial-flow fans operated with a low pitch blade angle. Figure 15A illustrates a combined performance curve of two fans with stable operating characteristics.
When two fans with unstable performance characteristics (i.e., a pressure reduction to the left of the peak pressure point) operate in parallel, an unstable flow condition may occur if the fans operate too close to the peak pressure point of the combined performance curve. Figure 15B illustrates the combined performance curve of two fans operating in parallel.
Curve A-A of Figure 15B represents the pressure characteristic of a single fan. Curve C-C is the combined performance of two fans operating in parallel. All operating points to the right of point CD, the peak pressure point, are the sum of two times the airflow values for a single fan at the same pressure. The points are along the stable operating range of each fan. All systems with a resistance curve intersecting the combined performance curve to the right of point CD, such as resistance curve D-D, have stable flow characteristics.
Points to the left of point CD are the sum of all airflow values possible at the same pressure level of the fans. The points are along the unstable operating range of each fan. The double-loop shape (∞) seen in Figure 15B to the left of the peak pressure of two-fan operation is formed by summing the multiple airflows possible at a single pressure level. Systems with a resistance curve intersecting the performance curve in this region, to the left of point CD (e.g., resistance curve E-E), have unstable flow characteristics. Unstable flow is shown by the intersection of the system resistance curve at multiple points on the combined fan performance curve, points CE and CE'. The fans oscillate between these two points with random changes in airflow, noise, and vibration levels.
Avoid operating at unstable conditions. Always select fans to operate in their stable range, well to the right of the peak pressure point subject to the guidance in the section on Selection. If possible, plot the combined fan performance curve, including the double loop, and select the fan operating point along the stable portion of the performance curve to the right of the double loop.
When three or more identical fans are installed in parallel, the resulting airflow is the individual fan performance multiplied by the number of fans in the system, for properly selected and installed fans. The designer must ensure that the operating point of each fan is well to the right of the peak to avoid oscillation of any one of the fans. Also, the fan configuration plays a major part in how well the system performs.
Two identical fans operating in series theoretically double the pressure rise without changing airflow (Figure 16). Actual performance of the two fans operating in series will be less than the theoretical, because losses occur in the transition between the two fans and the second fan operates less efficiently. Lack of sufficient spacing and/or straightening of flow between the fans further reduces performance. At fan pressures below 30 in. of water, air compressibility can be neglected. Above that limit, calculation of the operating point, fan material selection, and fan design should consider temperature rise caused by friction and compressible gases.
Fan noise is a function of the fan design, volume airflow rate Q, total pressure Ptf, and efficiency ηt. After the proper type of fan for a given application has been determined (keeping in mind the system effects), the best size selection of that fan is commonly based on efficiency, because the most efficient operating range for a specific line of fans is normally the quietest. Low outlet velocity does not necessarily ensure quiet operation, so selections made on this basis alone are not appropriate. Also, noise comparisons of different types of fans, or fans offered by different manufacturers, made on the basis of rotational or tip speed are not valid. The only valid basis for comparison are the actual sound power levels generated by the different types of fans when they are all producing the required volume airflow rate and total pressure. Obtain octave-band sound power level data from the fan manufacturer for the specific fan being considered.
Sound power levels Lw can be determined using several different methods, such as a reverberant room comparing the sound generated by the fan to the sound generated by a reference source of known sound power; using an anechoic room; or using sound intensity measurements. The reverberant room measuring technique is described in ANSI/AMCA Standard 300; the enveloping surface method, which uses an anechoic room, is described in ISO Standard 13347-3; and the sound intensity method is described in ANSI/AMCA Standard 320. ANSI/ASHRAE Standard 68 (AMCA Standard 330) describes an alternative test to determine the sound power a duct fan radiates into a supply and/or return duct terminated by an anechoic chamber. These standards do not fully evaluate the pure tones generated by some fans; these tones can be quite objectionable when they radiate into occupied spaces. On critical installations, make special allowance by providing extra sound attenuation in the octave band containing the tone.
Discussions of sound and sound control may be found in Chapter 8 of the 2017 ASHRAE Handbook—Fundamentals and Chapter 48 of the 2019 ASHRAE Handbook—HVAC Applications.
Fan vibration is the structural response of a fan to excitations caused by impeller imbalance, unsteady aerodynamic forces, and drive torque pulsations. The magnitude and extent of the structural response, or vibration level, is determined by the stiffness of the fan components, drive alignment, and bearing properties, among other factors.
Excessive vibration levels can lead to premature failure of the fan, produce high noise levels, and transmit undesirable forces into the support structure. Although fan vibration can never be entirely eliminated, acceptable levels can be achieved through proper fan design, manufacture, and application.
Acceptable vibration levels have been established from a long history of practical fan experience. ANSI/AMCA Standard 204 defines recommended fan balance and vibration levels based on the fan application and fan drive power. The fan balance and vibration (BV) category, shown in Table 3, determines acceptable levels for fan balance quality and vibration levels.
Fan balance quality, or balance grade (e.g., G 6.3), is used to establish the maximum residual imbalance specification for a given fan speed and size. Balance grades for each of the BV categories are shown in Table 4.
Acceptable vibration levels, as measured in in/s, are shown in Table 5. These levels are generally obtained using an accelerometer placed in the vicinity of the fan or motor. A newly commissioned fan would be expected to meet the start-up values given in the table. If alarm levels are reached during operation, appropriate steps should be taken to identify, contain, and correct the source of the vibration. The fan should be taken out of service if vibration levels exceed the shutdown values. Operation at these levels can lead to premature failure of the fan.
Acceptable vibration performance at the fan design conditions can be achieved by following these recommendations. However, with the widespread use of variable-speed control, fans may still produce excessive vibration levels at certain critical speeds that correspond to natural frequencies of the fan and/or fan support structure. These critical speeds should be avoided, or eliminated through proper design of the fan components.
The vibration level of a fan changes with fan operating condition and time. Therefore, it is important to monitor, or periodically check, the fan vibration level to ensure safe and reliable operation.
During fan operation, vibration is transmitted to the support structure and building. This can lead to objectionable noise in occupied spaces, or to undesirable vibration in other components of the HVAC system (e.g., the ductwork). Vibration isolation (e.g., coil springs, rubber-in-shear) can be used to attenuate the vibration reaching the building. More information on vibration and application of vibration isolation can be found in Chapter 8 of the 2017 ASHRAE Handbook—Fundamentals and Chapter 48 of the 2019 ASHRAE Handbook—HVAC Applications.
15. ARRANGEMENT AND INSTALLATION
Direction of rotation is determined from the drive side of the fan. On single-inlet centrifugal f ans, the drive side is usually considered the side opposite the fan inlet. The AMCA Standard 99 series defines standard nomenclature for fan arrangements.
For a duct connected to a fan outlet or inlet, a flexible connection should be used to minimize vibration transmission. Provide access to the fan wheel for periodic removal of any accumulations tending to unbalance the rotor. When operating against high resistance or when low noise levels are required, it is preferable to locate the fan in a room away from occupied areas or acoustically treated to prevent sound transmission. The lighter-mass building construction common today makes it desirable to mount fans and driving motors on resilient bases designed to prevent vibration transmission through floors to the building structure. Conduits, pipes, and other rigid members should not be attached to fans. Noise that results from obstructions, abrupt turns, grilles, and other items not connected with the fan may be present. Treatments for such problems, as well as the design of sound and vibration absorbers, are discussed in Chapter 48 of the 2019 ASHRAE Handbook—HVAC Applications.
Many fan applications require the air volume to vary in response to ventilation requirements. Control strategy selection is based on several considerations, including frequency of airflow changes, effects on fan energy consumption, and first cost of control device(s).
Airflow control can be achieved by changing the system characteristic or the fan characteristic. Methods that change the system characteristic have low first cost, but generally consume more energy compared to methods that affect the fan characteristic.
The system characteristic can be altered by installing dampers or orifice plates. This approach reduces airflow by increasing the system restriction. In general, the resulting input power is higher than that of a comparable fan correctly selected for the new airflow operating point. Dampers are usually the lowest-first-cost method of achieving airflow control and are sometimes used in cases where continuous control is needed, although other, more energy-efficient means are available.
Inlet vanes are a form of damper control that offer better energy efficiency. Inlet vanes are typically a series of triangular vanes located in the inlet of a fan. The vanes are controlled through a linkage mechanism, similar to a damper, with one important difference: the vanes are oriented such that incoming flow is turned to provide a preswirl into the fan impeller. In many cases, this can improve fan performance and offset the energy penalty of the vanes. Figure 17 illustrates the change in fan performance with inlet vane control. Curves A, B, C, D, and E are the pressure and power curves for various vane settings between wide open (A) and nearly closed (E).
Changing the fan characteristic (Ptf curve) for airflow control can reduce power consumption. One option is to vary the fan’s rotational speed to produce the desired performance. If the change is infrequent, the speed of belt-driven fans may be adjusted by changing the drive pulley combination. More frequent changes using belt drive can be accomplished with adjustable sheaves that are manually, electrically, or hydraulically actuated. An alternative method for speed control, and the only option for direct-driven fans, is to vary the motor speed with a variable-speed control, such as a variable-frequency drive (VFD) or similar electronic device. Electronic motor speed control is often the best option from an energy consumption standpoint. When using variable-speed controls, the fan characteristic can be calculated with the fan laws.
An alternative to speed control is to change the fan geometry (especially blade setting angles) to optimize aerodynamic efficiency. This approach is more common in axial fans than with centrifugal fans.
Tubeaxial and vaneaxial fans are available with adjustable-pitch blades to allow balancing the airflow system, or to make infrequent adjustments. Vaneaxial fans can also be produced with controllable-pitch blades (i.e., pitch that can be varied while the fan is in operation) for frequent or continuous adjustment. Varying pitch angle retains high efficiencies over a wide range of conditions. The performance shown in Figure 18 is from a typical vaneaxial fan with variable-pitch blades. From the standpoint of noise, variable speed is somewhat better than variable blade pitch. However, both control methods give high operating efficiency and generate less noise than inlet vanes or dampers.
Table 6 summarizes control strategies and their relative energy consumption and first cost.
Further information on fan control as it relates to specific HVAC distribution systems may be found in Chapter 45 of this volume and in Chapter 47 of the 2019 ASHRAE Handbook—HVAC Applications.
|
A
|
=
|
fan outlet area, ft2
|
|
Cp
|
=
|
constant in Equation (1)
|
|
cp
|
=
|
specific heat in Equation (1), Btu/lbm·°F
|
|
D
|
=
|
fan size or impeller diameter
|
|
d
|
=
|
area of inner cylinder
|
|
J
|
=
|
mechanical equivalent of heat, ft·lbf/Btu
|
|
N
|
=
|
rotational speed, revolutions per minute
|
|
Q
|
=
|
volume airflow rate moved by fan at fan inlet conditions, cfm
|
|
Ptf
|
=
|
fan total pressure: fan total pressure at outlet minus fan total pressure at inlet, in. of water
|
|
Pvf
|
=
|
fan velocity pressure: pressure corresponding to average velocity determined from volume airflow rate and fan outlet area, in. of water
|
|
Psf
|
=
|
fan static pressure: fan total pressure diminished by fan velocity pressure, in. of water. Fan static pressure is also the difference between static pressure at outlet and total pressure at inlet.
|
|
Psx
|
=
|
static pressure at given point, in. of water
|
|
Pvx
|
=
|
velocity pressure at given point, in. of water
|
|
Ptx
|
=
|
total pressure at given point, in. of water
|
|
ΔP
|
=
|
pressure change, in. of water
|
|
ΔT
|
=
|
temperature change, °F
|
|
V
|
=
|
fan inlet or outlet velocity, fpm
|
|
Wo
|
=
|
power output of fan: based on fan volume flow rate and fan total pressure, horsepower
|
|
Wi
|
=
|
power input to fan: measured by power delivered to fan shaft, horsepower
|
|
ηt
|
=
|
mechanical efficiency of fan (or fan total efficiency): ratio of power output to power input (ηt = Wo/Wi)
|
|
ηs
|
=
|
static efficiency of fan: mechanical efficiency multiplied by ratio of static pressure to fan total pressure, ηs = (Psf/Ptf) ηt
|
|
ρ
|
=
|
gas (air) density, lb/ft3
|
AMCA. 2011. Fans and systems. Publication 201-02 (R2011). Air Movement and Control Association International, Arlington Heights, IL.
AMCA. 2011. Field performance measurement of fan systems. AMCA Publication 203-90 (R2011). Air Movement and Control Association International, Arlington Heights, IL.
AMCA. 2010. Drive arrangements for centrifugal fans. Standard 99-2404-10. Air Movement and Control Association International, Arlington Heights, IL.
AMCA. 2010. Designation for rotation and discharge of centrifugal fans. Standard 99-2406-10. Air Movement and Control Association International, Arlington Heights, IL.
AMCA. 2010. Motor positions for belt or chain drive centrifugal fans. Standard 99-2407-10. Air Movement and Control Association International, Arlington Heights, IL.
AMCA. 2010. Drive arrangements for tubular centrifugal fans. Standard 99-2410-10. Air Movement and Control Association International, Arlington Heights, IL.
AMCA. 2012. Balance quality and vibration levels for fans. Standard 204-05 (R2012). Air Movement and Control Association International, Arlington Heights, IL.
AMCA. 2012. Energy efficiency classifications for fans. AMCA Standard 205-12. Air Movement and Control Association International, Arlington Heights, IL.
AMCA. 2007. Laboratory methods of testing fans for aerodynamic performance rating. ANSI/AMCA Standard 210-07 (ANSI/ASHRAE Standard 51-2007). Air Movement and Control Association International, Arlington Heights, IL.
AMCA. 2008. Reverberant room method for sound testing of fans. Standard 300-08. Air Movement and Control Association International, Arlington Heights, IL.
AMCA. 2008. Laboratory methods of sound testing of fans using sound intensity. Standard 320-08. Air Movement and Control Association International, Arlington Heights, IL.
AMCA. 1997. Laboratory method of testing to determine the sound power in a duct. ANSI/AMCA Standard 330-97 (ANSI/ASHRAE Standard 68-1997). Air Movement and Control Association International, Arlington Heights, IL.
AMCA. 2008. Industrial process/power generation fans: Site performance test standard. AMCA Standard 803-02 (R2008). Air Movement and Control Association International, Arlington Heights, IL.
ASHRAE. 2007. Laboratory methods of testing fans for aerodynamic performance rating. ANSI/ASHRAE Standard 51-2007 (ANSI/AMCA Standard 210-07).
ASHRAE. 1997. Laboratory method of testing in-duct sound power measurement procedure forms. ANSI/ASHRAE Standard 68-1997 (ANSI/ AMCA Standard 330-86).
ASHRAE. 2013. Energy standard for buildings except low-rise residential buildings. ANSI/ASHRAE/IES Standard 90.1.
ASME. 2008. Fans, performance test codes. ASME Code PTC 11-2008. American Society of Mechanical Engineers, New York, NY.
Darvennes, C., S. Idem, and M.N. Young. 2008. Inlet installation effects on propeller fans, air and sound (RP-1223). ASHRAE Research Project, Final Report.
Graham, J.B. 1966. Fan selection by computer techniques. Heating, Piping and Air Conditioning (April):168.
Graham, J.B. 1972. Methods of selecting and rating fans. ASHRAE Symposium Bulletin SF-70-8, Fan Application—Testing and Selection.
Guedel, A., M. Stevens, and J. Schubert. 2011. Inlet installation effects on BI/airfoil centrifugal fans, air and sound. ASHRAE Research Project RP-1216, Final Report.
Guedel, A., M. Stevens, and P. Zurkowski. 2014. Inlet and discharge installation effects on airfoil (AF) centrifugal plenum/plug fans for air and sound performance. ASHRAE Research Project RP-1420, Final Report.
Howden Buffalo. 1999. Fan engineering, 9th ed. R. Jorgensen, ed. Howden Buffalo, Camden, NJ.
ISO. 2001. Industrial fans—Performance testing in situ. Standard 5802: 2001. International Organization for Standardization, Geneva.
ISO. 2010. Fans—Efficiency classification for fans. Standard 12759:2010. International Organization for Standardization, Geneva.
ISO. 2004. Industrial fans—Determination of fan sound power levels under standardized laboratory conditions—Part 3: Enveloping surface methods. Standard 13347-3. International Organization for Standardization, Geneva.
Stevens, M., and J. Schubert. 2010. Inlet installation effects on forward curved centrifugal fans, air performance and sound. ASHRAE Research Project RP-1272, Final Report.
Swim, W.B. 1997. An experimental study of inlet system effects on the performance and noise of axial fans. ASHRAE Research Project RP-1010, Final Report.