In air distribution systems, special control and acoustical equipment is frequently required to introduce conditioned air into a space properly. Airflow controls for these systems consist principally of terminal units (historically called “VAV boxes”), with which the airflow can be varied by modulating valves, fan controls, or both. Terminal units such as those listed here are supplied with or without cooling, fans, heat, or reheat, and having either constant or variable primary airflow rate. Terminal units may use plenum or room air induction to affect space temperature control while maintaining a constant or variable discharge airflow rate and/or temperature. Terminal units may include sound reduction devices, heaters, reheaters, fans, diffusers, or cooling coils.
This section discusses control equipment for forced air-conditioning systems. Chapter 48 of the 2019 ASHRAE Handbook—HVAC Applications includes information on sound control in air-conditioning systems and sound rating for air outlets.
Terminal units are factory-made assemblies for air distribution. A terminal unit manually or automatically performs one or more of the following functions: (1) controls air velocity, airflow rate, pressure, or temperature; (2) mixes primary air from the duct system with air from the treated space or from a secondary duct system; and (3) heats or cools the air. To achieve these functions, terminal unit assemblies are made from an appropriate selection of the following components: casing, mixing section, manual or automatic air control device, heat exchanger, induction section (with or without fan), sound reduction devices, and flow controller.
Terminal units are typically classified as constant- or variable-volume devices. They are further categorized as either pressure-dependent, where airflow through the assembly varies in response to changes in system pressure, or pressure-independent (pressure-compensating), where airflow through the device does not vary in response to changes in system pressure.
Variable-air-volume (VAV) reset controllers regulate airflow to a constant, fixed amount or to a variable, modulating amount calculated by room demand. These controllers can be electric (pressure dependent), analog or digital electronic (pressure independent), or pneumatic (pressure dependent or pressure independent). Pressure-independent controllers require an indication of actual airflow to reset the VAV airflow control device. Temperature inputs are also required for calculating room demand for comfort conditioning.
Terminal unit controls are categorized as (1) system-powered, in which the airflow control device derives the energy necessary for operation from supply air within the distribution system; or (2) externally powered, in which the airflow control device derives its energy from a pneumatic or electric outside source. Terminal units may be furnished with all necessary controls for their operation, including actuators, regulators, motors, and thermostats or space temperature sensors, or the controls may be furnished by someone other than the manufacturer.
The unit’s flow control device can be adjusted manually or automatically. If the unit is adjusted automatically, it is actuated by a control signal from a controller, thermostat, flow regulator, or building management system (BMS), depending on the desired function of the terminal unit.
Single-Duct Terminal Units
Single-duct terminal units can be cooling only, cooling/heating if the primary air unit provides both or reheat if a heater is present. Reheat terminal units add sensible heat to the supply air. Water or steam coils or electric resistance heaters are placed in or attached directly to the air discharge of the unit. This type of equipment can provide local individual reheat.
The basic single-duct unit consists of an insulated casing, airflow regulator, and possibly also an actuator, airflow-measuring device, and selected controls. Accessory discharge attenuators, silencers, and multiple outlet attenuators are also common.
Typical applications include
-
Where the supply air system is not tasked with the space heating requirements
-
With VVT or other auto-changeover controls
-
Constant air volume
-
Constant pressure control
A single-duct unit with reheat has an added heating coil (hot water or electric). They are typically applied in zones where heat losses create a need for heating. The terminal unit usually reheats at the minimum airflow setting. An auxiliary higher heating setting may be available as an option with additional controls.
Interior zones, where ventilation requirements may be larger than the desired heating airflow, may require additional reheat.
A single-duct exhaust consists of an insulated casing, airflow regulator, and possibly also an actuator, airflow-measuring device, and selected controls. Accessory inlet attenuators or silencers are sometimes used. Specialty materials may be needed for corrosion resistance. The designer should consider pressure drop and system effects.
Dual-duct terminal units are typically controlled by a room thermostat. They receive warm, cold, return, or ventilation air from separate air supply ducts to provide desired room control. Volume-regulated units have individual airflow control devices to regulate the amount of warm and cool air. Dual-duct units use reheat when they simultaneously provide heating and cooling air to the space. When a single temperature control device regulates the relative amounts of both warm and cold air to control temperature, a separate airflow control device may function to control and limit airflow. Specially designed baffles may be required inside the unit or at its discharge to mix varying amounts of warm and cold air and/or to provide uniform temperature distribution downstream. Dual-duct units can be equipped with constant- or variable-flow control. These are typically pressure independent, to provide precise volume and temperature control. Dual-duct terminals may also be used with dedicated outdoor air supplied to the terminals such that the outdoor air inlet is used to control and maintain the required volumetric flow of ventilation air into the space. Dual-duct units with cooling and outdoor air may need a local heating device.
A nonmixing dual-duct unit is effectively two single-duct terminal units side by side. The basic unit incorporates separate cold and hot (sometimes neutral) air inlets. They are usually applied in exterior zones in buildings where overhead heating and cooling are desired but not auxiliary heat, and zero minimum flow is acceptable during changeover between heating and cooling. Proper discharge configurations are required to reduce the likelihood of improper mixing.
A mixing dual-duct unit is the same, with an integral mixing/attenuator section on the downstream end of the terminal unit to minimize temperature stratification in the discharge airstream. They are often used in interior and exterior zones in buildings (e.g., hospitals) where overhead heating and cooling are desired but an auxiliary heating coil is not, and zero minimum flow is unacceptable during changeover between heating and cooling. Evaluate mixing performance to fit the application, and consider the additional pressure drop of mixing/attenuators sections.
Air-to-Air Induction Terminal Units
Induction terminals supply primary air or a mixture of primary and recirculated air to the conditioned space. They achieve this function with a primary air jet that induces air from the ceiling plenum or individual rooms (via a return duct). Cool primary air is ducted to the terminal unit and used as the inducing energy source. The induction unit contains devices that are actuated in response to a thermostat to modulate the mixture of cool primary air and induced air. Reheat coils may be required to meet interior load requirements.
Fan-Powered Terminal Units
Fan-powered terminal units are used in HVAC systems as secondary-level air handlers, and are typically installed in return air plenums. They differ from air-to-air induction units in that they include a blower, driven by a small motor, which draws air from the conditioned space, ceiling plenum, or floor plenum, that may be mixed with the cool air from the main air handler. The characteristics of fan-powered units are (1) in heating mode, the primary air is mixed with warmer plenum air to increase the air temperature entering the heater, thus reducing or eliminating reheat; (2) downstream air pressure can be boosted to deliver air to areas that otherwise would be short of airflow; (3) perimeter zones can be heated without operating the main air handler when building cooling is not required; (4) main air handler operating pressure can be reduced with series units compared to other terminal units, reducing the air distribution system’s energy consumption; and (5) in thermal storage and other systems with relatively low supply air temperatures, series fan-powered terminal units may be used to mix supply air with induced return or plenum air, to moderate the discharge air temperature. Some units are equipped with special insulation and a vapor barrier to prevent condensation with these low supply temperatures.
Fan-powered terminal units can be divided into two categories: (1) series, with all primary and induced air passing through a blower operating continuously during the occupied mode; and (2) parallel, in which the blower operates only on demand when induced air or heat is required.
A series unit typically has two inlets, one for cool primary air from the central fan system and one for secondary or plenum air. All air delivered to the space passes through the blower. The blower operates continuously whenever the primary air fan is on and can be cycled to deliver heat as required when the primary fan is off. As cooling load decreases, an airflow control device throttles the amount of primary air delivered to the blower. The blower makes up for this reduced amount of primary air by drawing air in from the conditioned space or ceiling plenum through the return or secondary air opening. Sometimes a series unit has two ducted inlets, like a dual-duct terminal unit, in addition to the induction air inlet. The second duct is typically used for dedicated outdoor air systems. Fan airflow and primary air can be varied when the units are in part-load condition, but fan airflow should never be less than the total amount of air supplied by the ducted inlets.
Fan-Powered Series Flow.
The basic unit consists of a single-duct unit, blower/motor, and selected controls where the motor and primary damper are arranged such that mixing occurs upstream of the blower. They also have been called
constant-volume or
constant-fan units. Supplemental heating coils (hot water or electric) are generally required. Electric heaters are typically located on the discharge of the unit; water coils may be on the discharge or the induction port. Heating coils on the induction port increase ambient temperature at the motor and decrease motor life. Supplemental cooling coils are sometimes located on the induction port for some applications like when utilized in conjunction with dedicated outdoor air systems.
Fan-powered series-flow units generally are used in the following situations:
-
Exterior zones where heating and cooling loads may vary considerably
-
Buildings where heating is desired when the central system is shut down during unoccupied hours
-
To allow lower central system static pressure
-
Where occupant comfort can be optimized, because the high- (sometimes constant-) volume variable-temperature air delivery produces consistent air distribution, acoustics, and ventilation
Low-Profile Fan-Powered Series.
Similar in construction to the standard series flow terminal, these units are typically less than
12 in. high for all sizes, to minimize the depth of ceiling space required. Unlike standard fan-powered terminals, the fan/motor assembly is installed flat on its side with the wheel rotating in a horizontal plane.
Typical applications are the same as for regular series, but low-profile versions are commonly used where zoning requirements limit building height and the architect wishes to maximize the number of floors, because these units fit in a shallow ceiling plenum. Designers should pay special attention to available space and unit heights.
Ventilation Air Inlet Fan-Powered Series Flow.
These units are similar in construction to the standard series-flow terminal, but have an additional air inlet that provides a direct connection to the terminal unit for ventilation air. They are commonly used in buildings where ventilation air is piped in a dedicated ventilation duct system to each terminal unit; this is generally done where it is desirable to monitor ventilation air quantities to each zone.
Low-Temperature Fan-Powered Series Flow.
These units are the same as fan-powered series flow, but have special construction to minimize the potential for condensation. They can be used with cold-water/ice storage systems that provide low-temperature central system air distribution to the zone terminals when there is potential for condensation, or where standard terminals may be exposed to high humidity.
Underfloor Fan-Powered Series Flow.
This unit is a fan-powered series flow terminal designed to fit between the pedestal support grids of a raised- or access-floor HVAC system without modifying the floor. They are available in several unit sizes, but with limited height and width.
Primary and induction ports, if any, to the unit may or may not be ducted. Typically, air under the raised floor is cool air supplied directly to the space, although heated air may also be ducted to the unit. In these cases, a control system is required to select the proper damper sequence to control room air distribution to maintain the proper ambient conditions in the occupied space.
Parallel fan-powered terminal units supply the cool primary air directly to the mixing plenum, bypassing the fan, so that the primary air flows directly to the space. The blower section draws in plenum air and is mounted in parallel with the primary airflow control device. A backdraft damper is included to limit the amount of primary air flowing through the blower section when the blower is not energized. The blower in these units is generally energized after the primary airflow has reached the minimum flow rate. Typically, the parallel unit provides constant-volume heating and variable-volume cooling. Parallel units are typically limited to one ducted supply inlet.
One weakness in parallel fan-powered terminals is uncontrolled leakage of primary air through the fan’s backdraft damper and the mixing chamber housing. ASHRAE research project RP-1292 (David et al. 2007) demonstrated that much of the energy saving associated with intermittent fan cycling is offset, and in fact may be significantly less than the energy loss caused by uncontrolled leakage.
Fan-Powered Parallel Flow.
Sometimes called
variable-volume or
intermittent-fan units, these consist of a single-duct unit, blower/motor, backdraft damper, and selected controls; the motor and primary damper are arranged such that mixing occurs downstream of the blower. Supplemental heating coils (either hot water or electric) are generally required. Electric heaters are typically located on the discharge of the unit. Water coils may be on the discharge or the induction port, although the discharge location adds to the supply air system’s static pressure requirements and increases leakage through the backdraft damper, as shown in ASHRAE research project RP-1292 (Davis et al. 2007). Heating coils on the induction port increase ambient temperature at the motor and decrease motor life.
Fan-powered parallel-flow units are used in exterior zones where heating and cooling loads may vary considerably, and in buildings where heating is needed when the central system is shut down during unoccupied hours.
Bypass Terminal Units.
A bypass terminal unit handles a constant supply of primary air through its inlet. The unit bypasses primary air to the ceiling plenum or to ducts leading to the air handler’s return to meet the needs of the conditioned space. Primary air, diverted into the ceiling plenum, will return to the central air handler. This method provides a low first cost with minimum controls, but it is energy inefficient compared to other systems.
The basic bypass terminal consists of a diverter-type damper, actuator, bypass port, and selected pressure-dependent controls. A balancing damper is recommended ahead of the inlet. Reheat coils are discouraged, and electric reheat should be prohibited because of the potential fire hazard.
Bypass terminals are used primarily with packaged rooftop air conditioning equipment with a direct-expansion (DX) coil where zoning is desired, but relatively constant airflows across the system components (e.g., coils, fans) are required to minimize the potential for freeze-up. The system offers an economical VAV supply design with low first cost. It does not provide the energy-saving advantages of variable fan volume, but avoids the expense of a more sophisticated system.
Active (Figure 5A) and passive (Figure 5B) beams are room air recirculation devices that transfer sensible heat to/from the space using water. In addition, active beams deliver conditioned air from the central air-handling unit. The primary air must satisfy the ventilation and latent requirements of the space. Chilled-water inlet temperatures should be maintained at or above the air dew point to prevent condensation on the heat transfer coil(s).
Active beams are ceiling-mounted induction terminals that consist of a primary air duct connection, series of induction nozzles, hydronic heat transfer coil(s), supply outlet(s), and air inlet section. Primary air discharged through the induction nozzles entrains air from the room or from above the suspended ceiling, through the inlet section, and across chilled- and/or hot-water coil(s), where it is conditioned before being mixed with primary air. The mixture of primary and reconditioned induced air is then discharged to the space. This mixture’s temperature and/or flow rate is modulated in accordance with the space demand and control strategy. Active beams generally produce a fully mixed room air distribution.
Passive beams consist of a coil (heat exchanger), a casing, and sometimes a face plate. They provide cooling mainly by convection. The coil provides heat exchange between the chilled water and room air. When cool water is circulated through the coil, air between the fins is cooled and falls naturally into the room, drawing air through the coil behind it. As long as cool water circulates through the coil, sensible cooling continues. Space ventilation, dehumidification, and heating needs must be provided by complementary systems.
Beam Types and Configurations.
Overhead beams may be integrated with acoustic ceilings, or independently mounted. Although active beams are usually installed in the upper part of the space, they can also be located in side walls. Both active and passive chilled beams can be configured with additional space services (e.g., lighting, fire protection) as required.
There are two basic types of passive beams: exposed and recessed. Exposed passive beams are commonly used in spaces with low ceiling heights or when there is a wish to create a perception of an extra-high ceiling.
Recessed passive beams are generally integrated into a suspended ceiling system. When passive beams are installed above a ceiling, a minimum clearance between the top of the beam and any surface above it should be provided to ensure a sufficient return air path. Shadow gaps, dummy beam sections, and/or transfer grilles are recommended for creating the return air path.
Detailed information on active and passive beams can be found in REHVA/ASHRAE (2014).
This section discusses the use of hydronic and direct-expansion (DX) fan-coil units to control the volume and temperature of air delivered to the space as required to maintain occupant thermal comfort and/or ventilation. Chapter 5 discusses how fan-coil units are integrated into the design of the building.
Designers have various fan-coil systems to choose from when designing a building. Choosing which one to use depends on the owner’s needs (e.g., installation, application, operational cost, sustainability, thermal and acoustic performance, capacity, reliability, spatial requirements, code restrictions, water or refrigerant piping distribution, maintenance, and unit accessibility).
Fan-coil units are factory-made assemblies. The fan-coil performs some combination of the following functions: (1) temperature and humidity control, (2) ventilation of the conditioned space, (3) filtration, and (4) room air distribution. Fan-coil units are available in various configurations, including vertical or horizontal airflow paths and exposed or concealed mounts. A temperature control device regulates the fan-coil airflow and discharge air temperature.
As shown in Figure 6, the basic components of fan-coil units are a heating or cooling coil, filter, fan, and temperature control device. The fan recirculates air from the conditioned space through the coil, which then transfers heat to or from the air. Heat transfer devices include finned-tube coils (chilled or hot water, DX, or steam) or electric resistance elements. A filter at the unit’s inlet captures and minimizes particulates in the air downstream of the filter. The fan and motor assembly are generally arranged for quick removal for servicing. If the unit includes a dehumidifying cooling coil, it should be equipped with an insulated drain pan. Fan-coil casings are typically galvanized steel, and may be painted. The casing may be internally insulated for both thermal and acoustic considerations.
Additional components are offered on fan-coil units for specific applications. Sophisticated fan controls are available [e.g., modulating fan controls, thyristor control, electronically commutated motors (ECMs)]. The coil’s water valve piping package can include such components as flow controls (manual or automatic), pressure-independent water valves, strainers, unions, pressure-temperature ports, air vents, hose connections, drains, and balancing valves. The coil in a DX system includes an expansion device such as a fixed orifice device or thermal expansion valve. Electric heating controls include magnetic contact closure or solid state relays.
Fan-coil units are generally available in nominal sizes from 200 to 2400 cfm or 0.5 to 6 tons, with direct-drive or belt-driven permanent split capacitor (PSC) fan motors or ECMs for a wide range of applications. These units can be used in ducted or nonducted single or multiroom applications. They typically have multiple-row cooling, and may have single- or multiple-row heating coils. The hydronic heating and cooling coils may be separate or contained in a single fin pack (excluding steam). In a DX system, the coil uses multiple rows and circuits for refrigerant distribution in cooling and heating.
Fan-coil unit systems
-
Require less building interstitial space, because the water/refrigerant delivery system has a higher energy density per unit volume than an all-air system
-
Provide individual-zone temperature and humidity control
-
Enable retrofits to expand capacity beyond that of an existing air system
-
Allow individual dwellings in multifamily buildings to have individual electrical meters
-
Provide independent dwellings with independent temperature control (e.g., in residential, commercial, and industrial spaces)
DX fan-coil systems also eliminate the need for a central chiller plant. However, for DX fan-coil units in high-rise buildings, the space required for mounting condensing units and the lift required for oil in refrigerant lines must be considered.
Two- and Four-Pipe Hydronic Distribution Systems.
When the heating and cooling media are supplied to a common coil, it is called a two-pipe system (one supply and one return pipe) or a heating/cooling changeover system. A four-pipe distribution system has dedicated supply and return piping for each coil or each circuit within a common coil. The four-pipe system generally has a higher initial cost; however, it provides (1) all-season availability of heating and cooling at each unit, (2) no summer/winter changeover requirement, (3) controllability to maintain a dead band between heating and cooling, and (4) heating coil arrangements for either preheat or reheat.
A two-pipe system can only heat or cool, depending on the supply water temperature. During intermediate seasons or when the building requires simultaneous heating and cooling, supplemental electric heat is usually provided. The coil is typically sized for cooling, so careful consideration of the heating water temperature is required. For these reasons, the designer should consider the limitations of the two-pipe system carefully; many installations of this type waste energy, and have been unsatisfactory in climates where temperatures vary widely from morning to afternoon.
Motors and Controls.
When selecting a motor type, consider features such as control type, control scheme, and sequence of operation. The differences between a permanent split capacitor (PSC) versus an electronically commutated motor (ECM) affect the sequence of operation, which in turn dictates type of room thermostats, controls, and water valves. When an ECM is used in a fan-coil, both the fan motor and water control valve are typically modulated by a controller based on room demand. This can provide superior comfort levels and improved energy efficiency.
The most common control for fan-coils is a room thermostat. These thermostats come in both line voltage (i.e., same voltage as motor) and 24 V. They offer simple on/off or multispeed control of fan motors and open/close control of water control valves.
Analog controllers provide a higher level of control, modulating components such as ECMs, water valves, and silicon-controlled rectifier (SCRs). The most advanced level of building control is provided by direct digital control (DDC), which adds communication ability through a building automation system (BAS).
Additional information on fan-coil unit motors and controls can be found in Chapter 57 of the 2019 ASHRAE Handbook—HVAC Applications.
Unit Types and Configurations.
Fan-coil units are available in many different configurations; however, not all configurations discussed here are available for all types of units. Orientation of airflow from return to supply, unit features, and dimensional characteristics constitute the major differences between configurations. Outdoor air can be mixed with return air at the fan-coil unit or delivered directly to the space. Changes in industry standards have increased the use of coupling ventilation air to fan-coil units. The outdoor air can be pretreated or unconditioned, and ducted or nonducted. Fan-coil units are available with a variety of options to handle outdoor air, such as mixing boxes, outdoor air duct collars, air measuring devices, or air control devices.
Vertical Units. Low-profile vertical fan-coil units (sill units) are typically used beneath or adjacent to windows in concealed or exposed cabinets. The low silhouette sometimes limits filter area, serviceability, capacity, and cabinet geometry. Air is discharged vertically through grilles mounted on the top face of the enclosure. This type of fan-coil unit is available for rooms with lower window sills. Controls and water valves are typically located in the enclosure, with access from the room for maintenance.
Vertical, high-output fan-coil units are designed for larger spaces or multiple rooms. The units are typically located in a closet, where a door allows easy access. Ducted discharge air supplies multiple outlets located throughout the space. The return is typically located near the floor of the closet and may or may not be ducted. Typically one thermostat controls the air supplied to all the spaces.
Floor-to-ceiling, vertical stack fan-coil units are typically supplied with chilled- and/or hot-water risers and a condensate drain riser. Vertical stack fan-coils with integral prefabricated risers directly one above the other can reduce installation labor. Evaluation of floor-to-ceiling centerlines is critical for riser and unit heights.
Vertical stack fan-coil units (Figure 7) are typically mounted in walls of the conditioned space. Air is discharged into the space from high sidewall grilles or ducted to outlets throughout the zone. Multiple stack units may be connected to a common set of risers to serve adjacent spaces. The pipes can be located in a cavity protected by a fire-rated wallboard partition separating multiple adjacent zones.
Horizontal Units. Horizontal overhead units may be concealed or exposed, and some have discharge or return ducts. Discharge ducts may supply several outlets in one or more rooms. Ducted units must be designed to handle higher external static pressure. Horizontal models conserve floor space, but when located in furred ceilings, consideration should be given to access and condensate removal.
Figure 8 shows a typical low-profile horizontal fur-down fan-coil unit. Horizontal fur-down units are generally less than 11 in. in height, and mounted in a fur-down below the ceiling level or in a soffit area. The return is nonducted; the interstitial area of the soffit is the return plenum. Horizontal fan-coil types are generally used in space-constrained applications. A variation of the horizontal fur-down unit includes a return plenum, which has filter accommodations and may be ducted to a return grille. Addition of the return plenum with an externally finished cabinet allows the unit to be installed below the ceiling. Pay careful attention to the plenum pressure drop and grille locations.
High-capacity, horizontal fan-coil units are generally 15 to 18 in. tall and mounted above the ceiling in a return air plenum. These models have a higher capacity than fur-down low-profile units, and generally serve multiple rooms with a ducted supply. The unit may have multiple plenum arrangements, like fur-down models do, but the interstitial area is typically the return plenum.
Maintenance.
Fan-coil systems require maintenance, which is generally done in occupied areas. Unit accessibility is important when performing routine maintenance such as filter replacement, coil cleaning, and motor servicing. For this reason, fan-coil units should be selected and located with consideration for required maintenance.
Air curtain units are local ventilation devices that supply a high-velocity planar stream of air to reduce airflow through apertures in building shells (Asker 1970; Powlesland 1971, 1973; Stroiizdat 1992; Strongin 1993) and in process equipment (Bintzer and Malehom 1976; Goodfellow 1985; Ivanitskaya et al. 1986; Strongin and Nikulin 1991). An air curtain unit’s primary purpose is to act as a controlled barrier for environmental and thermal separation and wind resistance when a building’s doors or windows are opened.
As an environmental separation barrier, air curtains are used to minimize migration of gaseous and/or airborne particulate near their sources, and to convey contaminants toward local exhaust systems (Posokhin 1985; Posokhin and Broida 1980; Stoler and Savelyev 1977). They are also used to deter flying insects from entering a building or a protected indoor area.
As a thermal barrier, the air curtain reduces cross migration of warm, lighter air flowing through the upper part of the opening and cold, heavier air flowing through the lower part of the opening. As a wind resistance barrier, it minimizes the effect of outdoor wind blowing into a building’s openings. An air curtain can reduce the energy consumption of HVAC systems when areas of different temperatures are separated.
Air curtain unit energy effectiveness is defined by the amount of energy saved (i.e., the energy loss through an opening prevented with an air curtain) divided by the amount of energy that would have been lost without an air curtain. It is represented as a percentage, and the amount of energy is reduced by the energy consumed by the unit. Research has demonstrated that air curtains can range in effectiveness from 60% to 90%, depending on the type of unit and application. See the updated online version of Chapter 57 of the 2019 ASHRAE Handbook—HVAC Applications for more information.
Construction uses a motor and fan, or a system of motors and fans, mounted inside a cabinet. The fan draws air in through a ducted or nonducted intake, and discharges it at a high velocity as an air curtain.
The unit is usually mounted above or beside a door or window opening. Discharge across the opening is either vertically (when the unit is mounted above the opening) or horizontally (when the unit is mounted beside the opening).
Unit Types and Configurations.
Air curtain units are classified by two different types of construction: non-recirculating and recirculating. The major differences between the two systems are the airflow path, cabinet construction, range of effectiveness, and purchase and installation costs.
A non-recirculating system draws air into the unit directly from the surrounding environment in both horizontal and vertical applications (Figure 9). An air curtain equipped with inlet ductwork, which draws air from outside the surrounding environment, is also considered to be non-recirculating. This configuration is recommended for doorways that open frequently (e.g., 10 times per hour or a total of an hour per day). Flying insect control applications use this type of unit exclusively because of its ability to generate a high-velocity airstream. It is the most commonly used system for environmental separation, because of its low initial purchase and installation costs. Non-recirculating systems are typically used for special applications, owing to their flexibility in construction and installation.
A recirculating system draws air from ductwork, which primarily collects and returns the discharge air back to the inlet (Figure 10). Applications often use a plenum with a floor return that is connected to the inlet with ductwork. An alternative construction includes horizontal flow, which discharges and returns from side to side. These systems are recommended for doorways that are opened for extended periods of time, with a high rate of traffic. Although its effectiveness rating is higher, this system is only suitable for thermal separation applications. Recirculating systems use lower velocities and are perceived as less obtrusive than non-recirculating systems.
Non-recirculating systems are normally self-contained systems that can be easily installed or retrofitted to existing openings with minimal planning and impact to the opening and its sequence of operation. Recirculating systems require preplanning and comprise a combination of components, including discharge and return plenums, which require integration into the construction of the opening and its sequence of operation.
Typically, the range of effectiveness for non-recirculating systems is 60 to 80%, whereas recirculating systems range between 80 to 90%. Non-recirculating systems also have a relatively low purchase and installation cost; recirculating systems can have significantly higher installed cost.
Optional features available for air curtain units include heating, cooling, filters, and special controls. Special casing material and/or casing coatings may be required for outdoor mounting or harsh environmental applications.
Air curtain units may be offered with various heating and cooling options, depending on the intended application and cabinet construction. Note that a heating or cooling option may not improve the air curtain’s effectiveness: it generally serves as an enhancement to the application, independent of the protection provided by the airstream. A heat source may be added for use as supplemental heat to reduce the windchill effect of the air curtain.
The most common heating types are
-
Electric heating coils: open (helical) or fin-tube element
-
Hydronic coil: hot water or steam
-
Indirect gas-fired: furnace uses heat exchanger to separate combustion air from heated air curtain
-
Direct gas-fired: burner fires directly into airstream being heated
-
DX evaporator coil: direct-expansion vapor compression refrigeration cycle system
Cooling options are used for the same general reasons as the heating options: usually for customer comfort, supplemental cooling, or dehumidifying. Special care is needed in cooling applications to remove the condensate generated in the cooling apparatus. The most common types are
Factors that Influence Selection.
Air curtains are typically considered for four different applications:
-
Energy savings: indoor applications where doors or windows are used for pedestrian traffic or the transporting of goods where they would be open for a period of time long enough to impact the designed load of the HVAC system. Examples include front or customer entry doors, loading docks, service windows, ovens, and coolers or freezers.
-
Insect control (sanitation): indoor applications where doors or windows could allow for the entrance of flying insects that would create an unsanitary environment.
-
Code requirements: buildings that are being constructed to meet a jurisdictional code requirement.
-
Process/special application: applications where the separation of two distinct environments is required to prevent cross contamination, fume/odor control or a process that requires a direct stream of air to accomplish a specified task. Examples include cleanrooms, car washes, and assembly line drying.
The updated online version of Chapter 57 of the 2019 ASHRAE Handbook—HVAC Applications provides details on these categories.
Product Selection.
Air curtain unit selection is dependent on the width and height of the opening. To maximize effectiveness, the air curtain unit at a minimum must cover the entire opening and if possible should slightly overlap. On wide openings, two vertically mounted, low-air-velocity units can be used as an alternate solution to a single horizontally mounted, high-air-velocity unit. The air curtain unit discharge must have a free and clear path to the entire opening for optimum performance.
Recent studies suggest that the minimum air velocity required at the floor to create an effective barrier is 400 ft/min (Wang and Zhong 2014). When selecting air curtains, commercially available products are offered and designed specifically based on the opening size and application. Manufacturers’ performance data should be consulted to determine the suitability of the air curtain units used. Data to determine air curtain unit performance should be obtained from recognized test standards such as ANSI/AMCA Standard 220.
Principles of Air Curtain Design.
The velocity of the supplied air can be calculated from the following equation:
where
|
Vo
|
=
|
velocity of supply air, fpm
|
|
Δp
|
=
|
average pressure difference between indoor and outdoor air near the aperture with the air curtain turned on, in. of water
|
|
f
|
=
|
ratio of area Aap of air supply slots to door area Ao; for air curtains with heated air or unheated indoor air and for combined air curtains, f = 10 to 20; for those supplying outdoor air or protecting air-conditioned spaces, f = 20 to 40
|
|
βo
|
=
|
Boussinesq coefficient (describes uniformity of air velocity in opening cross section); for air curtain supply nozzle, βo = 1.05 to 1.1
|
|
ρ
|
=
|
density of air supplied by air curtain, lbm/ft3
|
|
E
|
=
|
coefficient of air curtain dynamic efficiency (given in Table 2)
|
|
g
|
=
|
acceleration of gravity = 32.2 ft/s2
|
Airflow Go (lb/min) supplied by shutter-type air curtains can be calculated from the following equation:
where Ao is the door area in ft2.
The temperature to of the supplied air can be estimated from the heat balance equation for the aperture under consideration:
where
|
tmix
|
=
|
normative air mixture temperature, °F
|
|
Δtout
|
=
|
leaving air temperature, °F
|
|
t
|
=
|
air temperature in occupied zone, °F
|
|
m1, m2
|
=
|
coefficients for air curtain (Table 3)
|
Controls.
Air curtain unit controls are essential to provide the correct air curtain velocity, temperature, and depth. They are also used to prevent unnecessary energy usage and overheating in the building entrance. Although supplemental heating can be provided by an air curtain unit, it should not be seen as the primary heat source for warming internal areas. If an air curtain unit is used for supplemental heating or cooling, the energy consumed during these control sequences should not be considered in the effectiveness rating of the unit. For convenience, user-operated controls are normally remotely mounted and configured to satisfy the building occupants’ needs. At the simplest level of control, only manual operation of the fan(s), fan speed, and heat output may be required; however, more advanced control options may be included, such as
Besides the inputs, where these control options are connected, the control unit may also have outputs for signaling failures. For instance, the control unit can also provide for the correct communication between the air curtain units and the central heating system, sliding door system, variable-refrigerant-flow (VRF) system (e.g., heat pump), etc. Air curtain units can be equipped with controls as simple as a mechanical multispeed switch, or as sophisticated as an integrated interface (printed circuit board) with a touchpad or LCD panel. The LCD panel can display values such as discharge speed and temperature, room temperature, failures, and filter contamination level.
Maintenance.
Air curtain units require annual periodic maintenance, which may increase based on the application. Some designs may have motors and bearings that require periodic lubrication. Many designs use motors with sealed bearings and have fan impellers mounted directly on the motor shafts, which do not require periodic lubrication. Air curtain units require only occasional cleaning of the blower impeller(s) and heating apparatus as well as filter change-out (if so equipped).