CHAPTER 10. SMALL FORCED-AIR HEATING AND COOLING SYSTEMS

This chapter describes the basics of design and component selection of small forced-air heating and cooling systems, explains their importance, and describes the system’s parametric effects on energy consumption. It also gives an overview of test methods for thermal distribution system efficiency, and considers the interaction between the building thermal/pressure envelope and the forced-air heating and cooling system, which is critical to the energy efficiency and cost-effectiveness of the overall system. This chapter pertains to residential and certain small commercial systems; large commercial systems are beyond the scope of this chapter. Applicable standards are listed in the Standards section at the end of the chapter.

1. COMPONENTS

Forced-air systems are heating and/or cooling systems that use motor-driven blowers to distribute heated, cooled, and otherwise treated air to multiple outlets for the comfort of individuals in confined spaces. A typical residential or small commercial system includes (1) a heating and/or cooling unit, (2) supply and return ductwork (including registers and grilles), (3) accessory equipment, and (4) controls. These components are described briefly in the following sections and are illustrated in Figure 1.

 Heating and Cooling Units

Three types of forced-air heating and cooling devices are (1) furnaces, (2) air conditioners, and (3) heat pumps.

Heating and Cooling Components

Figure 1. Heating and Cooling Components


Furnaces are the basic component of most forced-air heating systems (see Chapter 33). They are manufactured to use specific fuels such as oil, natural gas, or liquefied petroleum gas, and are augmented with an air-conditioning coil when cooling is included. The fuel used dictates installation requirements and safety considerations.

Common air-conditioning systems use a split configuration with an air-handling unit, such as a furnace. The air-conditioning evaporator coil (indoor unit) is installed on the discharge air side of the air handler. The compressor and condensing coil (outdoor unit) are located outside the structure, and refrigerant lines connect the outdoor and indoor units.

Self-contained air conditioners contain all necessary air-conditioning components, including circulating air blowers, and may or may not include fuel-fired heat exchangers or electric heating elements.

Heat pumps cool and heat using the refrigeration cycle. They are available in split and packaged (self-contained) configurations. Generally, air-source heat pumps require supplemental heating; therefore, electric heating elements are usually included with the heat pump as part of the forced-air system. Heat pumps offer high efficiency at mild temperatures, but may be combined with fossil-fuel furnaces to minimize heating cost. Heat pump supplemental heating also may be provided by thermostat-controlled gas heating appliances (e.g., fireplaces, free-standing stoves).

Ground-source heat pumps (GSHPs) are becoming more common in residential housing, especially in colder climates. Because underground temperatures are mild year-round, GSHPs typically do not use supplemental heating except in emergency mode (i.e., when the heat pump does not provide enough heat).

 Ducts

Ducts convey air to and from the fan in a heating or cooling unit. Registers and grilles are perforated covers over the openings where ductwork meets room walls, ceilings, or floors. In the extreme, a single return grille may connect directly to the fan cabinet. Supply registers often allow control of flow volume and direction. Dampers act as adjustable valves to control flow volume; turning vanes help redirect the flow around sharp bends. Duct systems can have very significant impacts on system efficiency and occupant comfort, and should be carefully designed, not just constructed by rules of thumb.

 Accessory Equipment

Forced-air systems may be equipped with accessories that further condition the air. They may modify humidity, remove contaminants, mix outdoor air with the recirculating air, or transfer energy in other ways. Disposable air filters on the return side of forced-air systems are so common that they are not considered accessories.

 Humidifiers.
 Humidifiers add moisture to the airstream directly as steam or an atomized spray, or by evaporation from heated pans or porous media. Chapter 22 of this volume contains more information on humidifiers.
 Dehumidifiers.
 Dehumidifiers remove moisture from the airstream, typically by cooling it below the condensation point. Also see the section on Dehumidifiers in Chapter 1 of the 2019 ASHRAE Handbook—HVAC Applications.
 Electronic Air Cleaners.
 Far more effective than the passive filters normally found in forced-air systems, these units use static electricity to capture fine dust, smoke, and other particles. Electronic air cleaners usually have a washable prefilter to trap lint and larger particles as they enter the unit. The remaining particles take on an electric charge in a charging section, then travel to the collector section where they are drawn to and trapped on the oppositely charged collecting plates. These plates must be washed periodically. See Chapter 29 for more information on air cleaners.
 Ultraviolet Lamp Sterilizers.
 Short-wavelength ultraviolet lamps in the fan cabinet can kill organisms in the circulating air and prevent mold build-up on the wet cooling coil. See Chapter 17 for details.
 Energy/Heat Recovery Ventilators.
 These devices provide ventilation air to the conditioned space and recover energy/heat from the air being exhausted outdoors. They can be operated as stand-alone devices or as part of the forced-air distribution system.
 Economizer Controls.
 These devices monitor outdoor temperature and humidity and automatically shut down the air-conditioning unit when a preset outdoor condition is met. Damper motors open outdoor return air dampers, letting outdoor air enter the system to provide comfort cooling. When outdoor air conditions are no longer acceptable, the outdoor air dampers close and the air-conditioning unit comes back on.
 Custom Accessories.
 Solar collectors, off-peak storage, and other custom systems are not covered in this chapter. However, their components may be classified as system accessories.

 Controls

A simple thermostat controlling on/off cycling of central equipment may be all that is used or needed for temperature control. Such thermostats typically have a switch for automatic or continuous fan operation, and another to choose heating, cooling, or neither.

More complex systems may provide control features for timed variations (from simple night setback to a weekly schedule of temperatures); multiple independent zones, power stages, or fan speeds; influence of outdoor sensors; humidity; automatic switching between heating and cooling modes, etc. (see Chapter 47 of the 2019 ASHRAE Handbook—HVAC Applications). Energy conservation has increased the importance of control, so methods that once were considered too expensive for small systems may now be cost-effective.

2. COMMON SYSTEM PROBLEMS

An idealized forced-air heating or cooling system would be virtually unnoticed by occupants. It would maintain a comfortable indoor environment at all times, with negligible noise, no noticeable odors, no circulating allergens or other pollution, and no localized temperature differences. In addition, it would need no maintenance, would never fail in any way, and would be extremely efficient.

Real systems, of course, can vary from this ideal in every way.

One of the most common problems is an oversized cooling system that does not need to run very long to cool the air, so it does not have time to remove much moisture. High humidity is uncomfortable, and also can encourage mold growth.

Too-small ducts create high resistance to airflow that can cause excess power consumption, high pressures, and low flow rates, especially if combined with an oversized system. High pressures can increase noise from airflow and from the fan itself, and can make it difficult to balance the system for appropriate distribution to all rooms. Low flow rates can result in ice formation on the cooling coil (possibly shutting off flow completely) and even on refrigerant piping; when that ice eventually melts, water can enter places that should stay dry. Long ducts running to perimeter walls not only increase resistance, but often run through unconditioned space where they can be exposed to extreme temperatures. Leaky ducts are, unfortunately, very common. Leaks not only reduce efficiency, they can draw in humidity, dust, pollen, etc. Leaks also can allow relatively humid indoor air to leak out to cold surfaces where the water can condense, causing staining, mold, rot, and other problems. In cold climates, an air leak in the attic can result in ice formation and the potential for significant damage. Ducts should be in the conditioned space.

Poor installation practices primarily affect duct systems, but condensate removal also can be a problem area. Air leakage problems as described previously, come from failure to seal properly all openings in an air-handling cabinet, joints in the duct system, joints where ducts meet register flares, and openings where register flares penetrate the room. Crude duct-taped joints sometimes come apart after a few years. Flexible ductwork is easy to install, but is also easy to install sloppily, with kinks and unnecessary bends that restrict flow.

Cooling systems installed above ground level commonly have a gravity drain for condensate, and a catch pan under the unit as a backup, with its own gravity drain. Sometimes an installed drain that is nearly horizontal actually runs uphill. If the main condensate drain runs uphill, the problem becomes evident almost immediately. If the problem is with the catch pan drain, it may be years before a major freeze-up generates enough water to overflow the pan and cause significant damage. Over time, mold and dirt can build up enough to block a drain line. Periodic cleaning may be necessary.

Dirty filters are common because homeowners neglect to clean or replace them. This may be from a lack of homeowner education or from the filters not being readily accessible (e.g., if the air handler filter rack is in the attic). They are not merely an air cleanliness problem; they can cut down airflow enough to raise fan power and even cause cooling coils to freeze up.

Air-source heat pumps in colder climates typically are equipped with auxiliary electric heat strips. Since resistance heating normally is much less efficient than a heat pump, less-sophisticated control systems can result in unnecessary electric resistance heating and higher electric bills. The resistance heating is necessary when continuous operation of the heat pump is insufficient to maintain indoor temperature; however, it may also come on when the thermostat setting is raised (manually, or automatically after night setback). Control systems may turn on resistance heating each time the system is reversed to defrost the outdoor coil, in order to prevent indoor cold blow.

This is by no means an exhaustive list of the types of problems to watch out for in forced air heating and cooling systems, but it should alert designers to some of the most common ones.

3. SYSTEM DESIGN

The size and performance characteristics of components are interrelated, and the overall design should proceed in the organized manner described. For example, furnace selection depends on heat gain and loss and is also affected by duct location (attic, basement, etc.), duct materials, night setback, and humidifier use. Here is a recommended procedure:

  1. Estimate heating and cooling loads, including target values for duct losses.

  2. Determine preliminary ductwork location and materials of ductwork and outlets.

  3. Determine heating and cooling unit location.

  4. Select accessory equipment. Accessory equipment is not generally provided with initial construction; however, the system may be designed for later addition of these components.

  5. Select control components.

  6. Select heating/cooling equipment.

  7. Determine maximum airflow (cooling or heating) for each supply and return location.

  8. Determine airflow at reduced heating and cooling loads (two-speed and variable-speed fans).

  9. Finalize heating/cooling equipment.

  10. Finalize control system.

  11. Finalize duct design and size.

  12. Select supply and return grilles.

  13. When the duct system is in place, measure duct leakage and compare results with target values used in step 1.

This procedure requires certain preliminary information such as location, weather conditions, and architectural considerations. The following sections cover the preliminary considerations and discuss how to follow this recommended procedure.

 Estimating Heating and Cooling Loads

Design heating and cooling loads can be calculated by following the procedures outlined in Chapters 17, 18, and 19 of the 2017 ASHRAE Handbook—Fundamentals When calculating design loads, heat losses or gains from the air distribution system must be included in the total load for each room. In residential and commercial applications, local codes often require outdoor air ventilation, which is added to the building load. Target values for duct losses may be set by codes, voluntary programs, or other recommendations. If ducts are located in the conditioned space, losses can be reduced essentially to zero. If this is not possible, losses should be limited to 10% of the heating or cooling load.

 Locating Outlets, Returns, Ducts, and Equipment

The characteristics of a residence determine the appropriate type of forced-air system and where it can be installed. The presence or absence of particular areas in a residence directly influences equipment and duct location. The structure’s size, room or area use, and air-distribution system determine how many central systems will be needed to maintain comfort temperatures in all areas.

For maximum energy efficiency, ductwork and equipment should be installed in the conditioned space. ASHRAE Standard 90.2 gives a credit for installation in this location. The next best location is in a full basement. If a residence has an insulated, unvented, and sealed crawlspace, the ductwork and equipment can be located there (with appropriate provision for combustion air, if applicable), or the equipment can be placed in a closet or utility room. Vented attics and vented crawlspaces are the least preferred locations for ductwork and HVAC equipment. The equipment’s enclosure must meet all fire and safety code requirements; adequate service clearance must also be provided. In a home built on a concrete slab, equipment could be located in the conditioned space (for systems that do not require combustion air), in an unconditioned closet, in an attached garage, in the attic space, or outdoors. Ductwork normally is located in a furred space, in the slab, or in the attic. Cummings et al. (2003) tested air leakage in 30 air handler cabinets and at connections to supply and return ductwork and found leakage rates averaged 6.3% of overall system airflow.

Duct construction must conform to local code requirements, which often reference NFPA Standard 90B or the Residential Comfort System Installation Standards Manual (SMACNA 1998).

Weather should be considered when locating equipment and ductwork. Packaged outdoor units for houses in severely cold climates must be installed according to manufacturer recommendations. Most houses in cold climates have basements, making them well-suited for indoor furnaces and split-system air conditioners or heat pumps. In mild and moderate climates, ductwork frequently is located in the attic or crawlspace, but the conditioned space still is best.


 Locating and Selecting Outlets and Returns.
Although the principles of air distribution discussed in Chapter 20 of this volume and Chapter 20 of the 2017 ASHRAE Handbook—Fundamentals apply in forced-air system design, simplified methods of selecting outlet size and location generally are used.

Supply outlets fall into four general groups, defined by their air discharge patterns: (1) horizontal high, (2) vertical nonspreading, (3) vertical spreading, and (4) horizontal low. Straub and Chen (1957) and Wright et al. (1963) describe these types and their performance characteristics under controlled laboratory and actual residence conditions. Table 1 lists the general characteristics of supply outlets. It includes the performance of various outlet types for cooling as well as heating, because one of the advantages of forced-air systems is that they may be used for both heating and cooling. However, as indicated in Table 1, no single outlet type is best for both heating and cooling.

The best outlets for heating traditionally have been located near the floor at outer walls and provide a vertical spreading air jet, preferably under windows, to blanket cold areas and counteract cold drafts. Called perimeter heating, this arrangement mixes warm supply air with both cool air from the area of high heat loss and cold air from infiltration, preventing drafts. In newer, more energy-efficient homes having well-insulated envelopes with low air leakage rates, it is no longer necessary to locate outlets near exterior walls. Instead, locating outlets as close as possible to the heating/cooling equipment allows for shorter duct runs, reducing duct leakage and pressure losses. This is especially important if it is not possible to locate the ducts in the conditioned space. See the section on Detailing the Duct Configuration for further information.

If outlets are located on the floor or low on the wall, avoid locations likely to be blocked by furnishings or opened doors.

The best outlet types for cooling are located in the ceiling and have a horizontal air discharge pattern. For year-round systems, supply outlets are located to satisfy the more critical load.

Table 1. General Characteristics of Supply Outlets

Group

Outlet Type

Outlet Flow Pattern

Conditioning Mode

Most Effective Application

Selection Criteria

1

Ceiling and high sidewall

Horizontal

Cooling

Ceiling outlets

 

Full-circle or widespread type

Select for throw equal to distance from outlet to nearest wall at design flow rate and pressure limitations.

Narrow spread type

Select for throw equal to 0.75 to 1.2 times distance from outlet to nearest wall at design flow rate and pressure limitations.

Two adjacent ceiling outlets

Select each so that throw is about 0.5 times distance between them at design flow rate and pressure limits.

High sidewall outlets

Select for throw equal to 0.75 to 1.2 times distance to nearest wall at design flow rate and pressure limits. If pressure drop is excessive, use several smaller outlets rather than one large one to reduce pressure drop.

2

Floor diffusers, baseboard, and low sidewall

Vertical, nonspreading

Cooling and heating

 

Select for 6 to 8 ft throw at design flow rate and pressure limitations.

3

Floor diffusers, baseboard, and low sidewall

Vertical, spreading

Heating and cooling

 

Select for 4 to 6 ft throw at design flow rate and pressure limitations.

4

Baseboard, and low sidewall

Horizontal

Heating only

 

Limit face velocity to 300 fpm.


The stagnant layer develops near the floor during heating and near the ceiling during cooling. Returns help remove air from this region if the return face is placed in the stagnant zone. Thus, for heating, returns should be placed low; for cooling, returns should be placed high. However, in a year-round heating and cooling application, a compromise must be made by placing returns where the largest stagnant zone develops. With low supply outlets, the largest stagnant zone develops during cooling, so returns should be placed high or opposite the supply locations. Conversely, high supply outlets do not perform as well during heating; therefore, returns should be placed low to be of maximum benefit.

If central return is used, the airflow between supply registers and the return should not be impeded even when interior doors are closed. This can be accomplished by undercutting doors or by providing alternative paths such as louvers or crossover ducts.

 Selecting Heating and Cooling Equipment

Furnace heating output should match or slightly exceed the estimated design load. The Air Conditioning Contractors of America (ACCA Manual S) recommends a 40% limit on oversizing for fossil fuel furnaces. This limit minimizes venting problems associated with oversized equipment and improves part-load performance. Note that the calculated load must include duct loss, humidification load, and night setback recovery load, as well as building conduction and infiltration heat losses. Chapter 33 has detailed information on how to size and select a furnace.

To help conserve energy, manufacturers have added features to improve furnace efficiency. Electric ignition has replaced the standing pilot; vent dampers and more efficient motors are also available. Furnaces with fan-assisted combustion systems (FACSs) and condensing furnaces also improve efficiency. Two-stage heating and cooling, variable-speed heat pumps, and two-speed and variable-speed blowers are also available.

Research on the effect of blower performance on residential forced-air heating system performance suggested reductions of 180 to 250 kWh/yr for automatic furnace fan operation and 2600 kWh/yr for continuous fan operation by changing from permanent split capacitor (PSC) blower motors to brushless permanent electronically commutated magnet motors (ECMs) (Phillips 1998).

A system designed to both heat and cool and that cycles cooling equipment on and off by sensing dry-bulb temperature alone should be sized to match the design heat gain as closely as possible. Oversizing under this control strategy could lead to higher-than-desired indoor humidity levels. Chapter 17 of the 2017 ASHRAE Handbook—Fundamentals recommends that cooling units not be oversized. Other sources suggest limiting oversizing to 15% of the sensible load. A heat pump should be sized for the cooling load with supplemental heat provided to meet heating requirements. Size air-source heat pumps in accordance with the equipment manufacturer recommendations. ACCA Manual S can also be used to assist in the selection and sizing of equipment.

 Determining Airflow Requirements

After equipment is selected and before duct design, the following decisions must be made:

  1. Determine air quantities required for each room or space during heating and cooling based on each room’s heat loss or heat gain. The air quantity selected should be the greater of the heating or cooling requirement.

  2. Determine number of supply outlets needed for each space to supply the selected air quantity, considering discharge velocity, spread, throw, terminal velocity, occupancy patterns, location of heat gain and loss sources, and register or diffuser design.

  3. Determine type of return (multiple or central), availability of space for grilles, filtering, maximum velocity limits for sound, efficient filtration velocity, and space use limitations.

 Finalize Duct Design and Size

Duct design too often is ignored in residences, and simply is left to a contractor to install in the traditional way. Because of the significant effect ducts can have on system efficiency, this topic is discussed extensively here.

 Selecting Supply and Return Grilles and Registers

Grilles and registers are selected from a manufacturer’s catalog with appropriate engineering data after the duct design is completed. Avoid rule-of-thumb selection. Carefully determine the suitability of the register or grille selected for each location according to its performance specification for the quantity of air to be delivered and the discharge velocity from the duct.

Generally, in small commercial and residential applications, selection and application of registers and grilles is particularly important because system size and air-handling capacity are small in energy-efficient structures. Proper selection ensures satisfactory delivery of heating and/or cooling. Table 1 summarizes selection criteria for common types of supply outlets. Pressure loss is usually limited to 0.03 in. of water or less.

Return grilles are usually sized to provide an exit velocity at their face of 400 to 600 fpm, or 2.7 to 4.1 cfm per square inch of free area. Some central return grilles are designed to hold an air filter. This design allows the air to be filtered close to the occupied area and also allows easy access for filter maintenance. Easy access is important when the furnace is in a remote area such as a crawlspace or attic. The air velocity through a filter grille should not exceed 300 fpm, which means that the volume of air should not exceed 2.1 cfm per square inch of free filter area. Free area may range from 30 to 70% of total grille area.

4. DETAILED DUCT DESIGN

 Detailing the Duct Configuration

The next major decision is to select a generic duct system. In order of decreasing efficiency, the three main types are

  1. Ducts in conditioned space

  2. Minimum-area ductwork (minimum run length results in minimum surface area)

  3. Traditional designs

Ductwork costs and system energy use can be reduced when the home designer/architect, builder, subcontractors, and HVAC installer collaborate to place ducts in conditioned spaces and minimize duct runs. Residential duct systems in unconditioned spaces can lose a significant percent of the energy in the air they distribute. These losses can be almost entirely eliminated simply by locating ducts in the conditioned space (insulated building envelope), which is a cost-effective way to increase heating and cooling equipment efficiency and lower utility bills (Modera 1989). Benefits include improved comfort, improved indoor air quality, and lower utility bills and equipment cost.

Any losses (air or conductive) from ducts in conditioned space still provide space conditioning. Ducts in conditioned space are also subjected to much less severe conditions, reducing conductive losses and the effect of return air leaks. There are a number of approaches that can be used to accomplish this:

  • Trunks and branches can be located between floors of a two-story residence or along the wall-ceiling intersections in a single-story dwelling. Care must be taken to seal the rim joist between floors, and/or the wall-to-ceiling intersection.

  • In some houses, the ceiling in a central hallway can be lowered. The air barrier is still provided at the higher level, bringing the space between the ceiling and air barrier into conditioned space. Ducts are installed in this space, with supply registers located on the walls of adjacent spaces. The ceiling can be dropped in closets, bathrooms, or, if necessary, a soffit to get ducts to rooms that are not adjacent to the central hallway. Figures 2A and 2B illustrate the planning required for locating ductwork between floors in a two-story residence and in a townhouse.

  • A slab-on-grade foundation is common in mild or moderate climates. With this type of foundation, supply air ducts are typically located in the attic. During the winter, attic air temperatures tend to match outdoor air temperatures. During the summer, solar heat gains can raise attic air temperatures over 150°F. These temperature extremes increase heat losses and gains from conduction and radiation and decrease duct efficiency. In addition, any conditioned air that leaks out of the duct is lost into the attic. If return ducts also are in the attic, return leaks pull unconditioned air into the system (particularly detrimental in hot, humid climates).

  • Figures 3A, 3B, and 3C show that constructing a ceiling plenum in the hallway allows ducts to be located in the conditioned space. Air temperatures in this location are typically between 55 and 85°F, which minimizes conduction and radiation losses. Air that leaks out of the ducts goes into the conditioned space.

  • Attics can be included in the conditioned space by relocating the thermal barrier to the roof and eliminating ridge and soffit vents to provide an air barrier at the roof line. Insulation can be installed at the roofline by, for example, installing netting material between trusses, and installing blown-in cellulose insulation. Ductwork can then be installed in the attic in conditioned space. In cold climates, care must be taken to avoid condensation on the inside of the roof deck; in hot climates, the lack of roof venting may argue against using asphalt-shingle roofing. One roofing option is a composite board consisting of thick, rigid foam insulation, vertically aligned spacing strips, and a solid plywood upper layer, fastened with very long screws onto the roof trusses. The spacing strips allow airflow under the main deck (but above the insulation) from soffits to ridge vents. It is important that no gaps be left between the insulation slabs of adjacent boards.

  • A plenum space can be created in the attic by using roof trusses that do not have a traditional flat bottom chord. A modified scissors truss design, which provides space between the bottom chord of the truss and the top chord of the wall framing, provides a duct space that can be brought into conditioned space. The bottom chord of the trusses is used to install an air barrier, with insulation blown in on top. Ductwork is installed in the plenum space, with supply registers located near interior walls (because the space may not extend all the way to the exterior walls).

  • It is important that the ducts be located inside thermal and air barriers, and that the air barrier be well sealed to minimize air communication with the outdoors. The duct space is rarely completely in conditioned space (other than in exposed ductwork systems). When there is an air barrier between the ducts and the occupied space, some fraction of air and thermal losses from the duct system goes to the outdoors rather than to the occupied space. High-quality air sealing on the exterior air barrier minimizes these losses to the outdoors.

Many new buildings have well-insulated envelopes or sufficient thermal integrity so that supply registers do not have to be located next to exterior walls. Placing registers in interior walls can reduce duct surface area by 50% or more, with similar reductions in leakage and conductive losses. This option also offers significant first-cost savings. Minimum-area ductwork systems are used in most houses built with ducts in conditioned space, including those using a dropped ceiling.

Sample Floor Plans for Locating Ductwork in Second Floor of (A) Two-Story House and (B) Townhouse (Hedrick 2002)

Figure 2. Sample Floor Plans for Locating Ductwork in Second Floor of (A) Two-Story House and (B) Townhouse
(Hedrick 2002)


Figures 2 and 3 are improved duct designs for new energy-efficient residential construction. These residences are designed with tighter envelopes/ducts, increased insulation, and high-performance windows, resulting in wall, window, floor, and ceiling temperatures that are warmer in winter and cooler in summer, and are more comfortable and less drafty.

In traditional designs for standard residential construction, supply ducts are typically run in unconditioned spaces, with supplies located near the perimeter of a house to offset drafts from cold exterior surfaces, especially windows. (Compare Figures 4A and 4B with 3B and 3C). Because this is the least efficient option overall, take particular care to seal and insulate the ductwork. Any air leaks on the supply side of the system allow conditioned supply air to escape to the outdoors. Return-side leaks draw air at extreme temperatures into the system instead of tempered room air. Return leaks can also have indoor air quality effects if the return ducts are located in garages or other spaces where contaminants may be present. In humid climates, return leaks bringing in humid outdoor air can raise the humidity in the space, increasing the risk of mold and mildew.

Sample Floor Plans for One-Story House with (A) Dropped Ceilings, (B) Ducts in Conditioned Spaces, and (C) Right-Sized Air Distribution in Conditioned Spaces (EPA 2000)

Figure 3. Sample Floor Plans for One-Story House with (A) Dropped Ceilings, (B) Ducts in Conditioned Spaces, and (C) Right-Sized Air Distribution in Conditioned Spaces
(EPA 2000)


(A) Ducts in Unconditioned Spaces and (B) Standard Air Distribution System in Unconditioned Spaces (EPA 2000)

Figure 4. (A) Ducts in Unconditioned Spaces and (B) Standard Air Distribution System in Unconditioned Spaces
(EPA 2000)


 Detailing the Distribution Design

The major goal in duct design is to provide proper air distribution throughout a residence. To achieve this in an energy-efficient manner, ducts must be sized and laid out to facilitate airflow and minimize friction, turbulence, and heat loss and gain. The optimal air distribution system has “right-sized” ducts, minimal runs, the smoothest interior surfaces possible, and the fewest possible direction and size changes. Figure 3C provides an example of right-sized ducts design.

The required airflow and the blower’s static pressure limitation are the parameters around which the duct system is designed. The heat loss or gain for each space determines the proportion of the total airflow supplied to each space. Static pressure drop in supply registers should be limited to about 0.03 in. of water. The required pressure drop must be deducted from the static pressure available for duct design.

The flow delivered by a single supply outlet should be determined by considering the (1) space limitations on the number of registers that can be installed, (2) pressure drop for the register at the flow rate selected, (3) adequacy of air delivery patterns for offsetting heat loss or gain, and (4) space use pattern.

Manufacturers’ specifications include blower airflow for each blower speed and external static pressure combination. Determining static pressure available for duct design should include the possibility of adding accessories in the future (e.g., electronic air cleaners or humidifiers). Therefore, the highest available fan speed should not be used for design.

For systems that heat only, the blower rate may be determined from the manufacturer’s data. The temperature rise of air passing through the heat exchanger of a fossil-fuel furnace must be within the manufacturer’s recommended range (usually 40 to 80°F). The possible later addition of cooling should also be considered by selecting a blower that operates in the midrange of the fan speed and settings.

For cooling only, or for heating and cooling, the design flow can be estimated by the following equation:

(1)

where

Q

=

flow rate, cfm

qs

=

sensible load, Btu/h

ρ

=

air density assumed to equal 0.075 lb/ft3

cp

=

specific heat of air = 0.24 Btu/lb · °F

Δt

=

dry-bulb temperature difference between air entering and leaving equipment, °F

U

=

unit conversion factor, 1 h/60 min

Replacing all constant values gives the simplified equation in the given units.


(2)

 

For preliminary design, an approximate Δt is as follows:

Sensible Heat Ratio (SHR)

Δt, °F

0.75 to 0.79

21

0.80 to 0.85

19

0.85 to 0.90

17

SHR = Calculated sensible load/Calculated total load

For example, if calculation indicates the sensible load is 23,000 Btu/h and the latent load is 4900 Btu/h, the SHR is calculated as follows:

and

This value is the estimated design flow. The exact design flow can only be determined after the cooling unit is selected. The unit that is ultimately selected should supply an airflow in the range of the estimated flow, and must also have adequate sensible and latent cooling capacity when operating at design conditions.

 Duct Design Recommendations

Residential construction duct design should be approached using duct calculators and the friction chart (see Figure 9 in Chapter 21 of the 2017 ASHRAE Handbook—Fundamentals). Chapters 8 to 11 of the ACCA Residential Duct System Manual D provide step-by-step duct sizing calculation examples and worksheets. Hand calculators and computer programs simplify the calculations required.

The ductwork distributes air to spaces according to the space heating and/or cooling requirements. The return air system may be single, multiple, or any combination that returns air to the equipment within design static pressure and with satisfactory air movement patterns (Table 2).

Some general rules in duct design are as follows:

  • Keep main ducts as straight as possible.

  • Include turning vanes at supply and return plenums if plenums do not go straight into the air handler.

  • Streamline transitions.

  • Design elbows with an inside radius of at least one-third the duct width. If this inside radius is not possible, include turning vanes.

  • Seal ducts to limit air leakage.

  • Insulate and/or line ducts, where necessary, to conserve energy and limit noise.

  • Locate branch duct takeoffs at least 4 ft downstream from a fan or transition, if possible.

  • Include dampers in branch ducts to enable system balancing.

  • Isolate air-moving equipment from the duct using flexible connectors to isolate noise.

Large air distribution systems are designed to meet specific noise criteria (NC) levels. Small systems should also be designed to meet appropriate NC levels; however, acceptable duct noise levels can often be achieved by limiting air velocities in mains and branches to the following:

Main ducts

700 to 900 fpm

Branch ducts

600 fpm

Branch risers

500 fpm

Considerable difference may exist between the cooling and heating flow requirements. Because many systems cannot (or will not) be rebalanced seasonally, a compromise must be made in the duct design to accommodate the most critical need. For example, a kitchen may require 165 cfm for cooling but only 65 cfm for heating. Because the kitchen may be used heavily during design cooling periods, the cooling flow rate should be used. Normally, the maximum design flow should be used, as register dampers do allow some optional reduction in airflows.

 Zone Control for Small Systems

In residential applications, some complaints about rooms that are too cold or too hot are related to the system’s limitations. No matter how carefully a single-zone system is designed, problems occur if the control is unable to accommodate the various load conditions that occur simultaneously throughout the house at any time of day and/or during any season.

Single-zone control works as long as the various rooms are open to each other. In this case, room-to-room temperature differences are minimized by convection currents between the rooms. For small rooms, an open door is adequate. For large rooms, openings in partitions should be large enough to ensure adequate air interchange for single-zone control.

When rooms are isolated from each other, temperature differences cannot be moderated by convection currents, and conditions in the room with the thermostat may not be representative of conditions in the other rooms. In this situation, comfort can be improved by continuous blower operation, but this strategy reduces efficiency and may not completely solve the problem.

Zone control is required (or at least desired) when conditions at the thermostat are not representative of all the rooms. This situation will almost certainly occur if any of the following conditions exists:

  • House has more than one level

  • One or more rooms are used for entertaining large groups

  • One or more rooms have large glass areas

  • House has an indoor swimming pool and/or hot tub

  • House has a solarium or atrium

In addition, zoning may be required when several rooms are isolated from each other and from the thermostat. This situation is likely to occur when

  • House spreads out in many directions (wings)

  • Some rooms are distinctly isolated from rest of house

  • Envelope only has one or two exposures

  • House has a room or rooms in a finished basement or attic

  • House has one or more rooms with slab or exposed floor

Zone control can be achieved by installing

  • Discrete heating/cooling ducts for each zone requiring control

  • Automatic zone damper in a single heating/cooling duct system

The rate of airflow delivered to each room must be able to offset the peak room load during cooling. The peak room load can be determined using Chapter 17 of the 2017 ASHRAE Handbook—Fundamentals. The same supply air temperature difference used to size equipment can be substituted into Equation (1) to find airflow. The design flow rate for any zone is equal to the sum of the peak flow rates of all rooms assigned to a zone.

Table 2. Recommended Division of Duct Pressure Loss

 

System Characteristics

Supply, %

Return, %

A

Single return at blower

90

10

B

Single return at or near equipment

80

20

C

Single return with appreciable return duct run

70

30

D

Multiple return with moderate return duct system

60

40

E

Multiple return with extensive return duct system

50

50


 Duct Sizing for Zone Damper Systems

The following guidelines are proposed in ACCA Manual D to size various duct runs.

  1. Use the design blower airflow rate to size a plenum or a main trunk that feeds the zone trunks. Size plenum and main trunk ducts at 800 fpm.

  2. Use zone airflow rates (those based on the sum of the peak room loads) to size the zone trunk ducts. Size all zone trunks at 800 fpm.

  3. Use the peak room airflow rate (those based on the peak room loads) to size the branch ducts or runouts. Size all branch runouts at a friction rate of 0.10 in. of water per 100 ft. For commercial systems, use 0.08 in. of water per 100 ft.

  4. Size return ducts for 600 fpm air velocity.

 Box Plenum Systems Using Flexible Duct

In some climates, an overhead duct with a box plenum feeding a series of individual, flexible-duct, branch runouts is popular. The pressure drop through a flexible duct is higher than through a rigid sheet metal duct, however. Recognizing this larger loss is important when designing a box plenum/flexible duct system.

Design of the box plenum is critical to avoid excessive pressure loss and to minimize unstable air rotation in the plenum, which can change direction between blower cycles. This in turn may change air delivery through individual branch takeoffs. Unstable rotation can be avoided by having air enter the box plenum from the side and by using a special splitter entrance fitting.

Gilman et al. (1951) proposed box plenum dimensions and entrance fitting designs to minimize unstable conditions as summarized in Figures 5 and 6. For residential systems with less than 2250 cfm capacity, pressure loss through the box plenum is approximately 0.05 in. of water. This loss should be deducted from the available static pressure to determine the static pressure available for duct branches. In terms of equivalent length, add approximately 50 ft to the measured branch runs.

 Embedded Loop Ducts

In cold climates, floor slab construction requires that the floor and slab perimeter be heated to provide comfort and prevent condensation. The temperature drop (or rise) in the supply air is significant, and special design tables must be used to account for the different supply air temperatures at distant registers. Because duct heat losses may cause a large temperature drop, feed ducts need to be placed at critical points in the loop.

Entrance Fittings to Eliminate Unstable Airflow in Box Plenum

Figure 5. Entrance Fittings to Eliminate Unstable Airflow in Box Plenum


Dimensions for Efficient Box Plenum

Figure 6. Dimensions for Efficient Box Plenum


A second aspect of a loop system is installation. The building site must be well drained and the surrounding grade sloped away from the structure. A vapor retarder must be installed under the slab. The bottom of the embedded duct must not be lower than the finished grade. Because a concrete slab loses heat from its edges outward through the foundation walls and downward through the earth, the edge must be properly insulated.

A typical loop duct is buried in the slab 2 to 18 in. from the outer edge and about 2.5 in. beneath the slab surface. If galvanized sheet metal is used for the duct, it must be coated on the outside to comply with Federal Specification SS-A-701. Other special materials used for ducts must be installed according to the manufacturer’s instructions. In addition, care must be taken when the slab is poured not to puncture the vapor retarder or to crush or dislodge the ducts.

5. SMALL COMMERCIAL SYSTEMS

The duct design procedure described in this chapter can be applied to small commercial systems using residential equipment, if the application does not include moisture sources that create a large latent load.

In commercial applications that do not require low noise, air duct velocities may be increased to reduce duct size. Long throws from supply outlets are also required for large areas, and higher velocities may be required for that reason.

Commercial systems with significant variation in airflow for cooling, heating, and large internal loads (e.g., kitchens, theaters) should be designed in accordance with Chapters 20 and 21 of the 2017 ASHRAE Handbook—Fundamentals, Chapters 5 and 33 in the 2015 ASHRAE Handbook—HVAC Applications, and Chapters 19 to 21 of this volume.

 Air Distribution in Small Commercial Buildings

According to Andrews et al. (2002), forced-air thermal distribution systems in small commercial buildings tend to be similar in many ways to those in residential buildings. As in most residential systems, there is often a single air handler that transfers heat or cooling from the equipment to an airstream that is then circulated through the building by means of ducts. Two major differences, however, may affect the performance of small commercial buildings: (1) significant (and often multiple) connections with outdoor air, and (2) the ceiling-space configuration.

 Outdoor Air Connections.
 In small commercial buildings, many forced-air systems have an outdoor-air duct leading from the outdoors to the return side of the ductwork, used to provide ventilation. Ventilation may also be provided by a separate exhaust-air system consisting of a duct and fan blowing air out of the building. Finally, there may also be a makeup air system blowing air into the building, used to balance out all the other airflows. A malfunction in any of these components can compromise the energy efficiency and thermal comfort performance of the entire system.
 Ceiling Space Configuration.
 Knowing the layout of the ceiling space is key to understanding uncontrolled airflows. The overhead portions of the air and thermal barriers can either be together, at the ceiling or at the roof, or separate, with the thermal barrier at the ceiling and the air barrier at the roof.

One configuration, typical of residential buildings but uncommon in commercial buildings, has a tight gypsum-board ceiling with insulation directly above and a vented attic. Ductwork is often placed in the vented attic space, though it may be elsewhere (e.g., under the building, outdoors). Such ducts are outside both the air and thermal barriers.

A more common configuration is similar except that it has a suspended T-bar ceiling instead of gypsum board. Air leakage through this type of ceiling tends to be quite high because the (usually leaky) suspended ceiling and attic vent provide an easy airflow path between the building and the outdoors. Efficiency is also compromised by duct placement in a very hot and humid location. Because of these two factors, uncontrolled airflows can strongly affect energy use, ventilation rates, and indoor humidity. This configuration should be avoided.

A third configuration is also similar, except that the ceiling space is not vented. This puts the ducts inside the air barrier (desirable) but outside the thermal barrier (undesirable). During the cooling season, the ceiling space tends to be very hot and dry. Uncontrolled airflows increase energy use but not ventilation rates or humidity levels.

The best configuration has insulation at the roof plane, leaving the space below the roof unvented, with or without a dropped ceiling. This design is very forgiving of uncontrolled airflow as long as the ductwork is inside the building. Duct leakage and unbalanced return air have little effect on energy use, ventilation rates, and indoor humidity, because conditions in the space below the roof deck are not greatly different from those in the rooms.

 Controlling Airflow in New Buildings

Airflow control should be a key objective in designing small commercial buildings. Designers and builders can plan for proper airflows at the outset. The following design goals are recommended:

  • Design the building envelope to minimize effects of uncontrolled airflows. Place the air and thermal barriers together in the roof, with ducts inside the conditioned zone. There are several good options for placing insulation at the roof level, including sprayed polymer foam, rigid insulation board on the roof deck beneath a rubber membrane, and insulating batts attached to the underside of the roof.

  • Minimize duct leakage to outdoors. Make sure as much ductwork is in the conditioned envelope as possible. Do not vent the ceiling space. If possible, dispense with the dropped ceiling altogether and use exposed ductwork. Avoid using building cavities as part of the air distribution system.

  • Minimize unbalanced return air. The best way is to provide a ducted return for each zone, and then balance these with the supply ducts serving the respective zones. Where that is not possible, transfer ducts or grilles may be provided to link a zone without a return duct to another zone with a return duct, provided that these have a minimum of 70 in2 of net free area per 100 cfm of return airflow. This approach should be used only if the thermal and air barriers are in the same plane (roof or ceiling).

  • Minimize unbalanced airflows across building envelope. Design the exhaust system with the smallest airflow rates necessary to capture and remove targeted air contamination sources and meet applicable standards. Ensure that the sum of makeup and outdoor airflow rates exceeds the exhaust airflow rate, not only for the building as a whole but also for any zones that can be isolated. Unconditioned makeup air should equal 75 to 85% of exhaust airflow, where possible. In buildings where continuous ventilation is required and the climate is especially humid, special design options may be needed (e.g., a dedicated makeup air unit could be provided with its own desiccant dehumidifier).

  • Ensure proper operation of outdoor air dampers. Outdoor air dampers on air handlers or rooftop air-conditioning units are frequently stuck or rusted shut, even on recently installed equipment. Proper performance helps ensure proper air quality and thermal comfort. Inspect space conditioning equipment annually to ensure proper operation of these dampers.

Further information can be found in Andrews et al. (2002).

6. TESTING FOR DUCT EFFICIENCY

ASHRAE Standard 152-2014 describes ways of measuring duct leakage and of calculating the impact of all sorts of energy transfer mechanisms. It applies to single-family detached and attached residences with independent thermal distribution systems.

A major complication in the standard’s lengthy development effort was the fact that, in contrast to heating or cooling units, which are mass-produced, duct systems are one of a kind. When determining the efficiency of a home duct system, it is therefore not possible to use the result of a laboratory test on a sample of the same model. Tests on a duct system must be performed in situ. The task before the committee was to produce a procedure that would be credibly accurate yet not too time-consuming to apply. A detailed history of the standard’s development is given in Andrews (2003).

ASHRAE Technical Committee 6.3, which is responsible for the standard, investigates possible revisions and extensions on an ongoing basis.

ASHRAE and other research organizations have conducted significant research and published numerous articles about methods for testing, and measured performance of the design and seasonal efficiencies of residential duct systems in the heating and cooling modes. A compilation of this research is provided in the Bibliography.

Although duct leakage is a major cause of duct inefficiency, other factors, such as heat conduction through duct walls, influence of fans on pressure in the house, and partial regain of lost heat, must also be taken into account. Following is a summary of information needed to evaluate the efficiency of a duct system using Standard 152 and a description of the results that the test method provides.

 Data Inputs

Variables that are known or can be measured to provide the basis for calculating duct system efficiency include the following:

  Local Climate Data.
 Three outdoor design temperatures are needed to describe an area’s climate: one dry-bulb and one wet-bulb temperature for cooling, and one dry-bulb for heating.
  Dimensions of Living Space.
The volume of the conditioned space must be known to estimate the impact of the duct system on air infiltration. Typical, average values have been developed and if default options are used, the floor area of the conditioned space must be known.
  Surface Areas of Ducts and R-Values of Insulation.
The total surface area of supply and return ducts and the insulation R-value of each are needed for calculating conductive heat losses through the duct walls. Also needed is the fraction of supply and return ducts in each type of buffer zone (e.g., an attic, basement, or crawlspace).
  Fan Flow Rate.
 Standard 152 allows a choice between two ways of measuring this quantity. An adjustable, calibrated fan flowmeter is the most accurate device for measuring airflow. The alternative method in the standard is to use a calibrated flow grid.
  Duct Leakage to Outdoors.
 Air leakage from supply ducts to the outdoors and from the outdoors and buffer spaces into return ducts is another major factor that affects efficiency. Typically, 17% or more of the total airflow is leakage.

 Data Output

Distribution efficiency is the main output of Standard 152. This figure of merit is the ratio of the input energy that would be needed to heat or cool the house if the duct system had no losses to the actual energy input required. Distribution efficiency also accounts for the effect the duct system has on equipment efficiency and the space conditioning load. Thus, distribution efficiency differs from delivery effectiveness, which is the simple output-to-input ratio for a duct system.

Four types of distribution efficiencies are considered. They relate to efficiency during either heating or cooling and for either design conditions or seasonal averages.

  • Design distribution efficiency, heating

  • Seasonal distribution efficiency, heating

  • Design distribution efficiency, cooling

  • Seasonal distribution efficiency, cooling

Design values of distribution efficiency are peak-load values that should be used when sizing equipment. Seasonal values should be used for determining annual energy use and subsequent costs.

 STANDARDS

 AHRI

Standard 260 Sound Rating of Ducted Air Moving and Conditioning Equipment
Standard 610 Performance Rating of Central System Humidifiers for Residential Applications

 ASHRAE

Standard 90.2 Energy Efficient Design of New Low-Rise Residential Buildings
Standard 103 Methods of Testing for Annual Fuel Utilization Efficiency of Residential Central Furnaces and Boilers
Standard 152 Method of Test for Determining the Design and Seasonal Efficiencies of Residential Thermal Distribution Systems

 ASTM

Standard E1554 Standard Test Methods for Determining External Air Leakage of Air Distribution Systems by Fan Pressurization

 NFPA

Standard 90A Standard for the Installation of Air-Conditioning and Ventilating Systems
Standard 90B Standard for the Installation of Warm Air Heating and Air-Conditioning Systems
Standard 501 Standard for Manufactured Housing

 ACCA

Manual D Residential Duct Systems
Manual J Residential Load Calculations
Manual S Residential Equipment Selection

REFERENCES

Andrews, J.W. 2003. A history of ASHRAE Standard 152P. Report BNL-72080-2004-IR. Available from www.osti.gov/bridge.

Andrews, J.W., J.B. Cummings, and M.P. Modera. 2002. Controlling airflow: Better air distribution for small commercial buildings. U.S. Department of Energy, Building Technologies Program.

Cummings, J.B., C. Withers. J. McIlvaine, J. Sonne, and M. Lombardi. 2003. Air handler leakage: Field testing results in residences. CH-03-73. Presented at the 2003 ASHRAE Winter Meeting, Chicago.

EPA. 2000. Duct insulation. EPA 430-F-97-028. U.S. Environmental Protection Agency, Washington, D.C.

Federal Specification. 1974. Asphalt, petroleum (primer, roofing, and waterproofing). SS-A-70.

Gilman, S.F., R.J. Martin, and S. Konzo. 1951. Investigation of the pressure characteristics and air distribution in box-type plenums for air conditioning duct systems. University of Illinois Engineering Experiment Station Bulletin 393 (July), Urbana-Champaign.

Hedrick, R.L. 2002. Alternative design details for building houses with ducts in conditioned space. Prepared by Gard Analytics for New Buildings Institute on behalf of California Energy Commission, Public Interest Energy Research (PIER) Program.

Modera, M.P. 1989. Residential duct system leakage: Magnitude, impacts, and potential for reduction. ASHRAE Transactions 95(2). Paper VA-89-05-5.

Phillips, B.G. 1998. Impact of blower performance on residential forced-air heating system performance. ASHRAE Transactions 104(1B):1817-1825. Paper SF-98-30-2.

SMACNA. 1998. Residential comfort system installation standards manual, 7th ed. Sheet Metal and Air Conditioning Contractors’ National Association, Chantilly, VA.

Straub, H.E., and M. Chen. 1957. Distribution of air within a room for year-round air conditioning—Part II. University of Illinois Engineering Experimental Station Bulletin 442 (March), Urbana-Champaign.

Wright, J.R., D.R. Bahnfleth, and E.G. Brown. 1963. Comparative performance of year-round systems used in air conditioning research no. 2. University of Illinois Engineering Experimental Station Bulletin 465 (January), Urbana-Champaign.

BIBLIOGRAPHY

Abushakra, B., I.S. Walker, and M.H. Sherman. 2002. A study of pressure losses in residential air distribution systems. Proceedings of the 2002 ACEEE Summer Study on Energy Efficiency in Buildings, pp. 1.1-1.14.

ACCA. 2009. Air distribution basics for residential and small commercial buildings. Manual T. Air Conditioning Contractors of America, Washington, D.C.

ACCA. 2003. Residential duct diagnostics and repair. Air Conditioning Contractors of America, Washington, D.C.

AHRI. Updated annually. AHRI certification programs; unitary air-conditioner equipment; unitary heat pump equipment. Air-Conditioning and Refrigeration Institute, Arlington, VA. Available from www.ahrinet.org/ahri+certification+programs.aspx.

Andrews, J.W. 1992. Optimal forced-air distribution in new housing. Proceedings of the 1992 ACEEE Summer Study on Energy Efficiency in Buildings, pp. 2.1-2.4.

Andrews, J.W. 1996. Field comparison of design and diagnostic pathways for duct efficiency evaluation. Proceedings of the ACEEE 1996 Summer Study on Energy Efficiency in Buildings, pp. 1.21-1.30. Washington, D.C.

Andrews, J.W. 2000. Reducing measurement uncertainties in duct leakage testing. Proceedings of the 2000 ACEEE Summer Study on Energy Efficiency in Buildings, vol. 1, pp. 13-28.

Andrews, J.W. 2002. Laboratory evaluation of the delta Q test for duct leakage. Proceedings of the 2002 ACEEE Summer Study on Energy Efficiency in Buildings, pp. 1.15-1.28.

Andrews, J.W. 2003. Effect of airflow and heat input rates on duct efficiency. ASHRAE Transactions 109(2):413-421. Paper KC-03-01-5.

Andrews, J.W. 2003. Future directions for thermal distribution standards. Report BNL-72081-2004-IR. Available from www.osti.gov/bridge.

Andrews, J.W., and M.P. Modera. 1991. Energy savings potential for advanced thermal distribution technology in residential and small commercial buildings. Report LBL-31042.

Andrews, J.W., R. Hedrick, M. Lubliner, B. Reid, B. Pierce, and D. Saum. 1998. Reproducibility of ASHRAE Standard 152P: Results of a round-robin test. ASHRAE Transactions 104(1):1376-1388. Paper SF-98-17-3.

Andrews, J.W., R.F. Krajewski, and J.J. Strasser. 1996. Electric co-heating in the ASHRAE standard method of test for thermal distribution efficiency: Test results in two New York state homes. ASHRAE Transactions 102(1). Paper AT-96-13-3.

Asiedu, Y., R.W. Besant, and P. Gu. 2000. A simplified procedure for HVAC duct sizing. ASHRAE Transactions 106(1):124-142. Paper 4329.

ASTM. 2007. Standard test methods for determining external air leakage of air distribution systems by fan pressurization. ASTM Standard E1554-07. American Society for Testing and Materials, Philadelphia.

Axley, J. 1999. Passive ventilation for residential air quality control. ASHRAE Transactions 105(2):864-876. Paper SE-99-11-3.

Baskin, E., and E.A. Vineyard. 2003. Thermal comfort assessment of conventional and high-velocity systems for cooling season. ASHRAE Transactions 109(1):513-519. Paper CH-03-07-5.

Bouchelle, M., D.S. Parker, M.T. Anello, and K.M. Richardson. 2000. Factors influencing space heat and heat pump efficiency from a large-scale residential monitoring study. Proceedings of 2000 Summer Study on Energy Efficiency in Buildings, American Council for an Energy-Efficient Economy, Washington, D.C.

Bullock, C. 1978. Energy savings through thermostat setback with residential heat pumps. ASHRAE Transactions 84(2):352-363. Paper AL-78-01-3.

Caffey, G. 1979. Residential air infiltration. ASHRAE Transactions 85(1). Paper PH-2512.

Crisafulli, J.C., R.A. Cudnik, and L.R. Brand. 1989. Investigation of regional differences in residential HVAC system performance using the SP43 simulation model. ASHRAE Transactions 95(1):915-929. Paper CH-89-14-3.

CEE. 2000. Specification of energy efficient installation practices for residential HVAC systems. Consortium for Energy Efficiency, Boston.

Colto, F., and G. Syphers. 1998. Are your ducts all in a row? Duct efficiency testing and analysis for 150 new homes in northern California. Proceedings of the 1998 ACEEE Summer Study on Energy Efficiency in Buildings, pp. 1.33-1.41.

Conlin, F. 1996. An analysis of air distribution system losses in contemporary HUD-code manufactured homes. Proceedings of the 1996 ACEEE Summer Study on Energy Efficiency in Buildings, pp. 1.53-1.59.

CSA. 2012. Gas-fired central furnaces. ANSI Standard Z21.47-2012/CSA Standard 2.3-2012. Canadian Standards Association International, Cleveland, OH.

Cummings, J.B., and J.J. Tooley, Jr. 1989. Infiltration and pressure differences induced by forced air systems in Florida residences. ASHRAE Transactions 95(2).

Cummings, J.B., J.J. Tooley, Jr., and R. Dunsmore. 1990. Impacts of duct leakage on infiltration rates, space conditioning energy use, and peak electrical demand in Florida homes. Proceedings of the ACEEE 1990 Summer Study on Energy Efficiency in Buildings, Washington, D.C.

Cummings, J., and C. Withers, Jr. 1998. Building cavities used as ducts: Air leakage characteristics and impacts in light commercial buildings. ASHRAE Transactions 104(2):743-752. Paper TO-98-08-4.

Cummings, J.B., and C.R. Withers, Jr. 2006. Unbalanced return air in residences: Causes, consequences, and solutions. ASHRAE Transactions 112(1):650-655. Paper CH-06-10-2.

Cummings, J.B., C.R. Withers, Jr., and N. Moyer. 2000. Evaluation of the duct leakage estimation procedures of ASHRAE Standard 152P. ASHRAE Transactions 106(2). Paper MN-00-12-2.

Cummings, J.B., C.R. Withers Jr., N.A. Moyer, P.W. Fairey, and B.B. McKendry. 1996. Field measurement of uncontrolled airflow and depressurization in restaurants. ASHRAE Transactions 102(1):859-869. Paper AT-96-13-2.

Cummings, J.B., C.R. Withers, Jr., J. McIlvaine, J.K. Sonne, and M.J. Lombardi. 2003. Air handler leakage: field testing results in residences. ASHRAE Transactions 109(1):496-502. Paper CH-03-07-3.

Davis, B., J. Siegel, and L. Palmiter. 1996. Field measurements of heating system efficiency and air leakage in energy-efficient manufactured homes. Proceedings of the ACEEE 1996 Summer Study on Energy Efficiency in Buildings, Washington, D.C.

Delp, W.W., N.E. Matson, and M.P. Modera 1998. Exterior exposed ductwork: Delivery effectiveness and efficiency. ASHRAE Transactions 104(2):709-721. Paper TO-98-08-1.

Delp, W.W., N.E. Matson, E. Tschudy, M.P. Modera, and R.C. Diamond. 1998. Field investigation of duct system performance in California light commercial buildings. ASHRAE Transactions 104(2):722-731. Paper TO-98-08-2.

Dickerhoff, D., I. Walker, and M. Sherman. 2004. Validating and improving the delta-Q duct leakage test. ASHRAE Transactions 110(2):741-751. Paper NA-04-6-5.

DOE. 2002. Controlling airflow: Better air distribution for small commercial buildings. Office of Energy Efficiency and Renewable Energy, Building Technologies Program, U.S. Department of Energy. Written and prepared by J.W. Andrews, J.B. Cummings, and M.P. Modera.

Downey, T. and J. Proctor. 2002. What can 13,000 air conditioners tell us? Proceedings of the 2002 ACEEE Summer Study on Energy Efficiency in Buildings, pp. 1.53-1.67.

Ebbing, C., and W. Blazier. 1998. Application of manufacturers’ sound data. ASHRAE.

Ellison, R.D. 1977. The effects of reduced indoor temperature and night setback on energy consumption of residential heat pumps. ASHRAE Journal.

Fischer, R.D., and R.A. Cudnik. 1993. The HOUSE-II computer model for dynamic and seasonal performance simulation of central forced-air systems in multi-zone residences. ASHRAE Transactions 99(1):614-626. Paper 3681.

Fischer, R.D., F.E. Jakob, L.J. Flanigan, D.W. Locklin, and R.A. Cudnik. 1984. Dynamic performance of residential warm-air heating systems—Status of ASHRAE Project SP43. ASHRAE Transactions 90(2B):573-590. Paper KC-84-10-2.

Francisco, P.W., and L. Palmiter. 1998. Measured and modeled duct efficiency in manufactured homes: Insights for Standard 152P. ASHRAE Transactions 104(1B):1389-1401. Paper SF-98-17-4.

Francisco, P.W., and L. Palmiter. 1999. Field validation of ASHRAE Standard 152. Final Report, ASHRAE Research Project RP-1056.

Francisco, P.W., and L. Palmiter. 2000. Field validation of Standard 152P. ASHRAE Transactions 106(2). Paper MN-00-12-1.

Francisco, P.W., and L. Palmiter. 2000. Performance of duct leakage measurement techniques in estimating duct efficiency: Comparison to measured results. Proceedings of the ACEEE 2000 Summer Study on Energy Efficiency in Buildings, Washington, D.C.

Francisco, P.W., and L.S. Palmiter. 2001. The nulling test: A new measurement technique of estimating duct leakage in residential homes. ASHRAE Transactions 107(1):297-303. Paper 4447.

Francisco, P.W., and L. Palmiter. 2003. Field evaluation of a new device to measure air handler flow. ASHRAE Transactions 109(2):403-412. Paper KC-03-01-4.

Francisco, P.W., L. Palmiter, and B. Davis. 1998. Modeled vs. measured duct distribution efficiency in six forced-air gas-heated homes. Proceedings of the 1998 ACEEE Summer Study on Energy Efficiency in Buildings, pp. 1.103-1.114.

Francisco, P.W., L. Palmiter, and B. Davis. 2002. Field performance of two new residential duct leakage measurement techniques. Proceedings of the 2002 ACEEE Summer Study on Energy Efficiency in Buildings, pp. 1.69-1.80.

Francisco, P.W., L. Palmiter, and B. Davis. 2003. Insights into improved ways to measure residential duct leakage. ASHRAE Transactions 109(1):485-495. Paper CH-03-07-2.

Francisco, P.W., D. Baylon, B. Davis, and L. Palmiter. 2004. Heat pump system performance in northern climates. ASHRAE Transactions 110(1): 442-451. Paper AN-04-05-3.

Francisco, P.W., L. Palmiter, E. Kruse, and B. Davis. 2004. Evaluation of two new duct leakage measurement methods in 51 homes. ASHRAE Transactions 110(2):727-740. Paper NA-04-6-4.

FSEC. 2001. Factors influencing space heat and heat pump efficiency from a large-scale residential monitoring study. Report FSEC-PF362-01. Florida Solar Energy Center, Cocoa.

GAMA. Updated annually. Consumer’s directory of certified efficiency ratings for residential heating and water heating equipment. Gas Appliance Manufacturers Association, Arlington, VA.

Gammage, R.B., A.R. Hawthorne, and D.A. White. 1984. Parameters affecting air infiltration and air tightness in thirty-one east Tennessee homes. Proceedings of the ASTM Symposium on Measured Air Leakage Performance of Buildings, Philadelphia.

Griffiths, D., R. Aldrich, W. Zoeller, and M. Zuluaga. 2002. An innovative approach to reducing duct heat gains for a production builder in a hot and humid climate—How we got there. Proceedings of the 2002 ACEEE Summer Study on Energy Efficiency in Buildings, pp. 1.81-1.90.

Griffiths, D., and M. Zuluaga. 2004. An analysis of the effective R-value for insulation buried attic ducts. ASHRAE Transactions 110(2):721-726. Paper NA-04-6-3.

Gu, L., J.E. Cummings, P.W. Fairey, and M.V. Swami. 1998. Comparison of duct computer models that could provide input to the proposed thermal distribution standard method of test (ASHRAE Research Project RP-852). ASHRAE Transactions 104(1):1349-1359. Paper SF-98-17-1.

Gu, L., M.V. Swami, and P.W. Fairey. 2003. System interactions in forced-air heating and cooling systems, part I: Equipment efficiency factors. ASHRAE Transactions 109(1):475-484. Paper CH-03-07-1.

Gu, L., M.V. Swami, and P.W. Fairey. 2003. System interactions in forced-air heating and cooling systems, part II: Continuous fan operation. ASHRAE Transactions 109(2):371-379. Paper KC-03-01-1.

Guyton, M.L. 1993. Measured performance of relocated air distribution systems in an existing residential building. ASHRAE Transactions 99(2). Paper DE-93-12-2.

Hales, D., A. Gordon, and M. Lubliner. 2003. Duct leakage in new Washington State residences: Findings and conclusions. ASHRAE Transactions 109(2):393-402. Paper KC-03-01-3.

Hammarlund, J., J. Proctor, G. Kast, and T. Ward. 1992. Enhancing the performance of HVAC and distribution systems in residential new construction. Proceedings of the 1992 ACEEE Summer Study on Energy Efficiency in Buildings, pp. 2.85-2.88.

Hedrick, R.L. 2003. Building homes with ducts in conditioned space. Draft Report to the California Energy Commission, Public Interest Energy Research (PIER) Program.

Hedrick, R.L., M.J. Witte, N.P. Leslie, and W.W. Bassett. 1992. Furnace sizing criteria for energy-efficient setback strategies. ASHRAE Transactions 98(1):1239-1246. Paper AN-92-17-1.

Herold, K.E., F.E. Jakob, and R.D. Fischer. 1986. The SP43 simulation model: Residential energy use. Proceedings of ASME Conference, Anaheim, pp. 81-87.

Herold, K.E., R.A. Cudnik, L.J. Flanigan, and R.D. Fischer. 1987. Update on experimental validation of the SP43 simulation model for forced-air heating systems. ASHRAE Transactions 93(2):1919-1933. Paper NY-87-20-3.

Herold, K.E., R.D. Fischer, and L.J. Flanigan. 1987. Measured cooling performance of central forced-air systems and validation of the SP43 simulation model. ASHRAE Transactions 93(1):1443-1457. Paper NY-87-16-1.

Hise, E.C. and A.S. Holman. 1977. Heat balance and efficiency measurements of central, forced-air, residential gas furnaces. ASHRAE Transactions 83(1):865-880. Paper CH-77-14-3.

IRC. 2012. International residential code® for one- and two-family dwellings (IRC®). International Code Council, Washington, D.C.

Jakob, F.E., R.D. Fischer, L.J. Flanigan, D.W. Locklin, K.E. Harold, and R.A. Cudnik. 1986. Validation of the ASHRAE SP43 dynamic simulation model for residential forced-warm air systems. ASHRAE Transactions 92(2B):623-643. Paper PO-86-13-1.

Jakob, F.E., D.W. Locklin, R.D. Fischer, L.J. Flanigan, and R.A. Cudnik. 1986. SP43 evaluation of system options for residential forced-air heating. ASHRAE Transactions 92(2B):644-673. Paper PO-86-13-2.

Jakob, F.E., R.D. Fischer, and L.J. Flanigan. 1987. Experimental validation of the duct submodel for the SP43 simulation model. ASHRAE Transactions 93(1):1499-1515. Paper NY-87-16-5.

Jump, D.A., I.S. Walker, and M.P. Modera. 1996. Field measurements of efficiency and duct retrofit effectiveness in residential forced-air distribution systems. Proceedings of the ACEEE 1996 Summer Study on Energy Efficiency in Buildings, Washington, D.C.

Kendall, M.A. 2004. Energy-saving opportunities in residential air-handler efficiency. ASHRAE Transactions 110(1):425-430. Paper AN-04-05-1.

Locklin, D.W., K.E. Herold, R.D. Fischer, F.E. Jakob, and R.A. Cudnik. 1987. Supplemental information from SP43 evaluation of system options for residential forced-air heating. ASHRAE Transactions 93(2):1934-1958. Paper NT-87-20-4.

Lubliner, M., R. Kunkle, J. Devine, and A. Gordon. 2002. Washington state residential ventilation and indoor air quality code (VIAQ): Whole house ventilation systems field research report. Proceedings of the 2002 ACEEE Summer Study on Energy Efficiency in Buildings, pp. 1.115-1.130.

Lubliner, M., D.T. Stevens, and B. Davis. 1997. Mechanical ventilation in HUD-code manufactured housing in the Pacific northwest. ASHRAE Transactions 103(1):693-705. Paper PH-97-08-2.

Matthews, T.G., C.V. Thompson, K.P. Monar, and C.S. Dudney. 1990. Impact of heating and air-conditioning system operation and leakage on ventilation and intercompartmental transport: Studies in occupied and unoccupied Tennessee Valley homes. Journal of the Air Waste Management Association 40:194-198.

Modera, M.P., J. Andrews, and E. Kweller. 1992. A comprehensive yardstick for residential thermal distribution efficiency. Proceedings of the 1992 ACEEE Summer Study on Energy Efficiency in Buildings, Washington, D.C.

Modera, M.P., D. Dickerhoff, O. Nilssen, H. Duquette, and J. Geyselaers. 1996. Residential field testing of an aerosol-based technology for sealing ductwork. Proceedings of the 1996 ACEEE Summer Study on Energy Efficiency in Buildings, pp. 1.169-1.175.

Oppenheim, P. 1992. Energy-saving potential of a zoned forced-air heating system. ASHRAE Transactions 98(1):1247-1257. Paper AN-92-17-2.

Palmiter, L., and T. Bond. 1992. Impact of mechanical systems on ventilation and infiltration in homes. Proceedings of the ACEEE 1992 Summer Study on Energy Efficiency in Buildings, Washington, D.C.

Palmiter, L., and P.W. Francisco. 1994. Measured efficiency of forced-air distribution systems in 24 homes. Proceedings of the ACEEE 1994 Summer Study on Energy Efficiency in Buildings, Washington, D.C.

Palmiter, L., and P.W. Francisco. 1996. A practical method for estimating the thermal efficiency of residential forced-air distribution systems. Proceedings of the ACEEE 1996 Summer Study on Energy Efficiency in Buildings, Washington, D.C.

Palmiter, L., and P.W. Francisco. 1998. Modeled duct distribution efficiency: Insights for heat pumps. Proceedings of the 1998 ACEEE Summer Study on Energy Efficiency in Buildings, pp. 1.223-1.234.

Palmiter, L., and P.W. Francisco. 2000. A new device for field measurement of air handler flows. Proceedings of the ACEEE 2000 Summer Study on Energy Efficiency in Buildings, Washington, D.C.

Palmiter, L., and P.W. Francisco. 2002. Measuring duct leakage with a blower door: Field results. Proceedings of the 2002 ACEEE Summer Study on Energy Efficiency in Buildings, pp. 1.207-1.218.

Palmiter, L.S., I.A. Brown, and T.C. Bond. 1991. Measured infiltration and ventilation in 472 all-electric homes. ASHRAE Transactions 97(2):979-987. Paper IN-91-15-3.

Parker, D.S. 1989. Evidence of increase levels of space heat consumption and air leakage associated with forced air heating systems in houses in the Pacific northwest. ASHRAE Transactions 95(2):527-533. Paper VA-89-05-1.

Parker, D.S., J.R. Sherwin, and B. Hibbs. 2005. Development of high-efficiency air conditioner condenser fans. ASHRAE Transactions 111(2): 511-520. Paper DE-05-04-3.

Proctor, J. 1998. Monitored in-situ performance of residential air-conditioning systems. ASHRAE Transactions 104(1B):1833-1840. Paper SF-98-30-4.

Proctor, J.P. 1998. Verification test of ASHRAE Standard 152P. ASHRAE Transactions 104(1B):1402-1412. Paper SF-98-17-5.

Proctor, J.P., and R.K. Pernick. 1992. Getting it right the second time: Measured savings and peak reduction from duct and appliance repairs. Proceedings of the ACEEE 1992 Summer Study on Energy Efficiency in Buildings, Washington, D.C.

Rittelmann, W.D. 2006. Effects of return air inlet locations on cooling season thermal comfort in an energy-efficient home. ASHRAE Transactions 112(1):641-649. Paper CH-06-10-1.

Robison, D.H., and P.E. Lambert. 1989. Field investigation of residential infiltration and heating duct leakage. ASHRAE Transactions 95(2):542-550. Paper VA-89-05-3.

Rutkowski, H., and J.H. Healy. 1990. Selecting residential air-cooled cooling equipment based on sensible and latent performance. ASHRAE Transactions 96(2):851-856. Paper SL-90-15-1.

Rudd, A.F., and J.W. Lstiburek. 2000. Measurement of ventilation and interzonal distribution in single-family houses. ASHRAE Transactions 106(2):709-718. Paper MN-00-10-3.

Sachs, H.M., T. Kubo, S. Smith, and K. Scott. 2002. Residential HVAC fans and motors are bigger than refrigerators. Proceedings of the 2002 ACEEE Summer Study on Energy Efficiency in Buildings, pp. 1.261-1.272.

Sachs, H.M., and S. Smith. 2004. How much energy could residential furnace air handlers save? ASHRAE Transactions 110(1):431-441. Paper AN-04-05-2.

Saunders, D.H., T.M. Kenney, and W.W. Bassett. 1992. Factors influencing thermal stratification and thermal comfort in four heated residential buildings. ASHRAE Transactions 98(1):1258-1265. Paper AN-92-17-3.

Saunders, D.H., T.M. Kenney, and W.W. Bassett. 1993. Evaluation of the forced-air distribution effectiveness in two research houses. ASHRAE Transactions 99(1):1407-1419. Paper CH-93-19-1.

Sherman, M., I. Walker, and D. Dickerhoff. 2000. Stopping duct quacks: Longevity of residential duct sealants. Proceedings of the 2000 ACEEE Summer Study on Energy Efficiency in Buildings, vol. 1, pp. 273-284.

Siegel, J.A., J.A. McWilliams, and I.S. Walker. 2003. Comparison between predicted duct effectiveness from proposed ASHRAE Standard 152P and measured field data for residential forced-air systems. ASHRAE Transactions 109(1):503-512. Paper CH-03-07-4.

Springer, D.A., L.I. Rainer, and W.L. Dakin. 2005. Development and testing of an integrated residential night ventilation cooling system. ASHRAE Transactions 111(2):501-510. Paper DE-05-04-2.

Strunk, P.R. 2000. Validation of ASHRAE Standard 152P in basement warm-air distribution systems. ASHRAE Transactions 106(2). Paper MN-00-12-3.

Temple, K.A. 2004. Field observations of room air distribution performance in a high-performance home. ASHRAE Transactions 110(2):699-708. Paper NA-04-6-1.

Temple, K.A. 2005. Field performance of a zoned forced-air cooling system in an energy efficient home. ASHRAE Transactions 111(2):487-500. Paper DE-05-04-1.

Treidler, B., and M.P. Modera. 1996. Thermal performance of residential duct systems in basements. ASHRAE Transactions 102(1):847-858. Paper AT-96-13-1.

Treidler, B., M.P. Modera, R.G. Lucas, and J.D. Miller. 1996. Impact of residential duct insulation on HVAC energy use and life-cycle costs to consumers. ASHRAE Transactions 102(1):881-894. Paper AT-96-13-4.

Tutu, N.K., C.R. Krishna, and T. Butcher. 2004. Characterization of airflows at the exit of registers using laser Doppler velocimetry (LDV). ASHRAE Transactions 110(2):709-721. Paper NA-04-6-2.

Walker, I.S. 1998. Technical background for default values used for forced-air systems in proposed ASHRAE Standard 152P. ASHRAE Transactions 104(1B):1360-1375. Paper SF-98-17-2.

Walker, I.S. 1999. Distribution system leakage impacts on apartment building ventilation rates. ASHRAE Transactions 105(1):943-950. Paper CH-99-14-2.

Walker, I.S., and M.P. Modera. 1996. Energy effectiveness of duct sealing and insulation in two multifamily buildings. Proceedings of the 1996 ACEEE Summer Study on Energy Efficiency in Buildings, pp. 1.247-1.254.

Walker, I.S., and M.P. Modera. 1998. Field measurements of interactions between furnaces and forced-air distribution systems. ASHRAE Transactions 104(1B):1805-1816. Paper SF-98-30-1.

Walker, I.S., D.J. Dickerhoff, and M.H. Sherman. 2002. The delta Q method of testing the air leakage of ducts. Proceedings of the 2002 ACEEE Summer Study on Energy Efficiency in Buildings, pp. 1.327-1.338.

Walker, I.S., and C.P. Wray. 2003. Evaluation of flow capture techniques for measuring HVAC grille airflows. ASHRAE Transactions 109(2):380-392. Paper KC-03-01-2.

Withers, C.R., and J.B. Cummings. 2006. Unbalanced return air in commercial buildings. ASHRAE Transactions 112(1):656-664. Paper CH-06-10-3.

Wray, C., I. Walker, and M. Sherman. 2002. Accuracy of flow hoods in residential applications. Proceedings of the 2002 ACEEE Summer Study on Energy Efficiency in Buildings, pp. 1.339-1.350.

Withers, C.W., Jr. and J.B. Cummings. 1998. Ventilation, humidity, and energy impacts of uncontrolled airflow in a light commercial building. ASHRAE Transactions 104(2):733-742. Paper TO-98-08-3.



The preparation of this chapter is assigned to TC 6.3, Central Forced Air Heating and Cooling Systems.