2. COMMON SYSTEM PROBLEMS
An idealized forced-air heating or cooling system would be virtually unnoticed by occupants. It would maintain a comfortable indoor environment at all times, with negligible noise, no noticeable odors, no circulating allergens or other pollution, and no localized temperature differences. In addition, it would need no maintenance, would never fail in any way, and would be extremely efficient.
Real systems, of course, can vary from this ideal in every way.
One of the most common problems is an oversized cooling system that does not need to run very long to cool the air, so it does not have time to remove much moisture. High humidity is uncomfortable, and also can encourage mold growth.
Too-small ducts create high resistance to airflow that can cause excess power consumption, high pressures, and low flow rates, especially if combined with an oversized system. High pressures can increase noise from airflow and from the fan itself, and can make it difficult to balance the system for appropriate distribution to all rooms. Low flow rates can result in ice formation on the cooling coil (possibly shutting off flow completely) and even on refrigerant piping; when that ice eventually melts, water can enter places that should stay dry. Long ducts running to perimeter walls not only increase resistance, but often run through unconditioned space where they can be exposed to extreme temperatures. Leaky ducts are, unfortunately, very common. Leaks not only reduce efficiency, they can draw in humidity, dust, pollen, etc. Leaks also can allow relatively humid indoor air to leak out to cold surfaces where the water can condense, causing staining, mold, rot, and other problems. In cold climates, an air leak in the attic can result in ice formation and the potential for significant damage. Ducts should be in the conditioned space.
Poor installation practices primarily affect duct systems, but condensate removal also can be a problem area. Air leakage problems as described previously, come from failure to seal properly all openings in an air-handling cabinet, joints in the duct system, joints where ducts meet register flares, and openings where register flares penetrate the room. Crude duct-taped joints sometimes come apart after a few years. Flexible ductwork is easy to install, but is also easy to install sloppily, with kinks and unnecessary bends that restrict flow.
Cooling systems installed above ground level commonly have a gravity drain for condensate, and a catch pan under the unit as a backup, with its own gravity drain. Sometimes an installed drain that is nearly horizontal actually runs uphill. If the main condensate drain runs uphill, the problem becomes evident almost immediately. If the problem is with the catch pan drain, it may be years before a major freeze-up generates enough water to overflow the pan and cause significant damage. Over time, mold and dirt can build up enough to block a drain line. Periodic cleaning may be necessary.
Dirty filters are common because homeowners neglect to clean or replace them. This may be from a lack of homeowner education or from the filters not being readily accessible (e.g., if the air handler filter rack is in the attic). They are not merely an air cleanliness problem; they can cut down airflow enough to raise fan power and even cause cooling coils to freeze up.
Air-source heat pumps in colder climates typically are equipped with auxiliary electric heat strips. Since resistance heating normally is much less efficient than a heat pump, less-sophisticated control systems can result in unnecessary electric resistance heating and higher electric bills. The resistance heating is necessary when continuous operation of the heat pump is insufficient to maintain indoor temperature; however, it may also come on when the thermostat setting is raised (manually, or automatically after night setback). Control systems may turn on resistance heating each time the system is reversed to defrost the outdoor coil, in order to prevent indoor cold blow.
This is by no means an exhaustive list of the types of problems to watch out for in forced air heating and cooling systems, but it should alert designers to some of the most common ones.
Detailing the Duct Configuration
The next major decision is to select a generic duct system. In order of decreasing efficiency, the three main types are
Ducts in conditioned space
Minimum-area ductwork (minimum run length results in minimum surface area)
Traditional designs
Ductwork costs and system energy use can be reduced when the home designer/architect, builder, subcontractors, and HVAC installer collaborate to place ducts in conditioned spaces and minimize duct runs. Residential duct systems in unconditioned spaces can lose a significant percent of the energy in the air they distribute. These losses can be almost entirely eliminated simply by locating ducts in the conditioned space (insulated building envelope), which is a cost-effective way to increase heating and cooling equipment efficiency and lower utility bills (Modera 1989). Benefits include improved comfort, improved indoor air quality, and lower utility bills and equipment cost.
Any losses (air or conductive) from ducts in conditioned space still provide space conditioning. Ducts in conditioned space are also subjected to much less severe conditions, reducing conductive losses and the effect of return air leaks. There are a number of approaches that can be used to accomplish this:
Trunks and branches can be located between floors of a two-story residence or along the wall-ceiling intersections in a single-story dwelling. Care must be taken to seal the rim joist between floors, and/or the wall-to-ceiling intersection.
In some houses, the ceiling in a central hallway can be lowered. The air barrier is still provided at the higher level, bringing the space between the ceiling and air barrier into conditioned space. Ducts are installed in this space, with supply registers located on the walls of adjacent spaces. The ceiling can be dropped in closets, bathrooms, or, if necessary, a soffit to get ducts to rooms that are not adjacent to the central hallway. Figures 2A and 2B illustrate the planning required for locating ductwork between floors in a two-story residence and in a townhouse.
A slab-on-grade foundation is common in mild or moderate climates. With this type of foundation, supply air ducts are typically located in the attic. During the winter, attic air temperatures tend to match outdoor air temperatures. During the summer, solar heat gains can raise attic air temperatures over 150°F. These temperature extremes increase heat losses and gains from conduction and radiation and decrease duct efficiency. In addition, any conditioned air that leaks out of the duct is lost into the attic. If return ducts also are in the attic, return leaks pull unconditioned air into the system (particularly detrimental in hot, humid climates).
Figures 3A, 3B, and 3C show that constructing a ceiling plenum in the hallway allows ducts to be located in the conditioned space. Air temperatures in this location are typically between 55 and 85°F, which minimizes conduction and radiation losses. Air that leaks out of the ducts goes into the conditioned space.
Attics can be included in the conditioned space by relocating the thermal barrier to the roof and eliminating ridge and soffit vents to provide an air barrier at the roof line. Insulation can be installed at the roofline by, for example, installing netting material between trusses, and installing blown-in cellulose insulation. Ductwork can then be installed in the attic in conditioned space. In cold climates, care must be taken to avoid condensation on the inside of the roof deck; in hot climates, the lack of roof venting may argue against using asphalt-shingle roofing. One roofing option is a composite board consisting of thick, rigid foam insulation, vertically aligned spacing strips, and a solid plywood upper layer, fastened with very long screws onto the roof trusses. The spacing strips allow airflow under the main deck (but above the insulation) from soffits to ridge vents. It is important that no gaps be left between the insulation slabs of adjacent boards.
A plenum space can be created in the attic by using roof trusses that do not have a traditional flat bottom chord. A modified scissors truss design, which provides space between the bottom chord of the truss and the top chord of the wall framing, provides a duct space that can be brought into conditioned space. The bottom chord of the trusses is used to install an air barrier, with insulation blown in on top. Ductwork is installed in the plenum space, with supply registers located near interior walls (because the space may not extend all the way to the exterior walls).
It is important that the ducts be located inside thermal and air barriers, and that the air barrier be well sealed to minimize air communication with the outdoors. The duct space is rarely completely in conditioned space (other than in exposed ductwork systems). When there is an air barrier between the ducts and the occupied space, some fraction of air and thermal losses from the duct system goes to the outdoors rather than to the occupied space. High-quality air sealing on the exterior air barrier minimizes these losses to the outdoors.
Many new buildings have well-insulated envelopes or sufficient thermal integrity so that supply registers do not have to be located next to exterior walls. Placing registers in interior walls can reduce duct surface area by 50% or more, with similar reductions in leakage and conductive losses. This option also offers significant first-cost savings. Minimum-area ductwork systems are used in most houses built with ducts in conditioned space, including those using a dropped ceiling.
Figures 2 and 3 are improved duct designs for new energy-efficient residential construction. These residences are designed with tighter envelopes/ducts, increased insulation, and high-performance windows, resulting in wall, window, floor, and ceiling temperatures that are warmer in winter and cooler in summer, and are more comfortable and less drafty.
In traditional designs for standard residential construction, supply ducts are typically run in unconditioned spaces, with supplies located near the perimeter of a house to offset drafts from cold exterior surfaces, especially windows. (Compare Figures 4A and 4B with 3B and 3C). Because this is the least efficient option overall, take particular care to seal and insulate the ductwork. Any air leaks on the supply side of the system allow conditioned supply air to escape to the outdoors. Return-side leaks draw air at extreme temperatures into the system instead of tempered room air. Return leaks can also have indoor air quality effects if the return ducts are located in garages or other spaces where contaminants may be present. In humid climates, return leaks bringing in humid outdoor air can raise the humidity in the space, increasing the risk of mold and mildew.
Detailing the Distribution Design
The major goal in duct design is to provide proper air distribution throughout a residence. To achieve this in an energy-efficient manner, ducts must be sized and laid out to facilitate airflow and minimize friction, turbulence, and heat loss and gain. The optimal air distribution system has “right-sized” ducts, minimal runs, the smoothest interior surfaces possible, and the fewest possible direction and size changes. Figure 3C provides an example of right-sized ducts design.
The required airflow and the blower’s static pressure limitation are the parameters around which the duct system is designed. The heat loss or gain for each space determines the proportion of the total airflow supplied to each space. Static pressure drop in supply registers should be limited to about 0.03 in. of water. The required pressure drop must be deducted from the static pressure available for duct design.
The flow delivered by a single supply outlet should be determined by considering the (1) space limitations on the number of registers that can be installed, (2) pressure drop for the register at the flow rate selected, (3) adequacy of air delivery patterns for offsetting heat loss or gain, and (4) space use pattern.
Manufacturers’ specifications include blower airflow for each blower speed and external static pressure combination. Determining static pressure available for duct design should include the possibility of adding accessories in the future (e.g., electronic air cleaners or humidifiers). Therefore, the highest available fan speed should not be used for design.
For systems that heat only, the blower rate may be determined from the manufacturer’s data. The temperature rise of air passing through the heat exchanger of a fossil-fuel furnace must be within the manufacturer’s recommended range (usually 40 to 80°F). The possible later addition of cooling should also be considered by selecting a blower that operates in the midrange of the fan speed and settings.
For cooling only, or for heating and cooling, the design flow can be estimated by the following equation:
where
|
Q
|
=
|
flow rate, cfm
|
|
qs
|
=
|
sensible load, Btu/h
|
|
ρ
|
=
|
air density assumed to equal 0.075 lb/ft3
|
|
cp
|
=
|
specific heat of air = 0.24 Btu/lb · °F
|
|
Δt
|
=
|
dry-bulb temperature difference between air entering and leaving equipment, °F
|
|
U
|
=
|
unit conversion factor, 1 h/60 min
|
Replacing all constant values gives the simplified equation in the given units.
For preliminary design, an approximate Δt is as follows:
For example, if calculation indicates the sensible load is 23,000 Btu/h and the latent load is 4900 Btu/h, the SHR is calculated as follows:
and
This value is the estimated design flow. The exact design flow can only be determined after the cooling unit is selected. The unit that is ultimately selected should supply an airflow in the range of the estimated flow, and must also have adequate sensible and latent cooling capacity when operating at design conditions.
Duct Design Recommendations
Residential construction duct design should be approached using duct calculators and the friction chart (see Figure 9 in Chapter 21 of the 2017 ASHRAE Handbook—Fundamentals). Chapters 8 to 11 of the ACCA Residential Duct System Manual D provide step-by-step duct sizing calculation examples and worksheets. Hand calculators and computer programs simplify the calculations required.
The ductwork distributes air to spaces according to the space heating and/or cooling requirements. The return air system may be single, multiple, or any combination that returns air to the equipment within design static pressure and with satisfactory air movement patterns (Table 2).
Some general rules in duct design are as follows:
Keep main ducts as straight as possible.
Include turning vanes at supply and return plenums if plenums do not go straight into the air handler.
Streamline transitions.
Design elbows with an inside radius of at least one-third the duct width. If this inside radius is not possible, include turning vanes.
Seal ducts to limit air leakage.
Insulate and/or line ducts, where necessary, to conserve energy and limit noise.
Locate branch duct takeoffs at least 4 ft downstream from a fan or transition, if possible.
Include dampers in branch ducts to enable system balancing.
Isolate air-moving equipment from the duct using flexible connectors to isolate noise.
Large air distribution systems are designed to meet specific noise criteria (NC) levels. Small systems should also be designed to meet appropriate NC levels; however, acceptable duct noise levels can often be achieved by limiting air velocities in mains and branches to the following:
Considerable difference may exist between the cooling and heating flow requirements. Because many systems cannot (or will not) be rebalanced seasonally, a compromise must be made in the duct design to accommodate the most critical need. For example, a kitchen may require 165 cfm for cooling but only 65 cfm for heating. Because the kitchen may be used heavily during design cooling periods, the cooling flow rate should be used. Normally, the maximum design flow should be used, as register dampers do allow some optional reduction in airflows.
Zone Control for Small Systems
In residential applications, some complaints about rooms that are too cold or too hot are related to the system’s limitations. No matter how carefully a single-zone system is designed, problems occur if the control is unable to accommodate the various load conditions that occur simultaneously throughout the house at any time of day and/or during any season.
Single-zone control works as long as the various rooms are open to each other. In this case, room-to-room temperature differences are minimized by convection currents between the rooms. For small rooms, an open door is adequate. For large rooms, openings in partitions should be large enough to ensure adequate air interchange for single-zone control.
When rooms are isolated from each other, temperature differences cannot be moderated by convection currents, and conditions in the room with the thermostat may not be representative of conditions in the other rooms. In this situation, comfort can be improved by continuous blower operation, but this strategy reduces efficiency and may not completely solve the problem.
Zone control is required (or at least desired) when conditions at the thermostat are not representative of all the rooms. This situation will almost certainly occur if any of the following conditions exists:
House has more than one level
One or more rooms are used for entertaining large groups
One or more rooms have large glass areas
House has an indoor swimming pool and/or hot tub
House has a solarium or atrium
In addition, zoning may be required when several rooms are isolated from each other and from the thermostat. This situation is likely to occur when
House spreads out in many directions (wings)
Some rooms are distinctly isolated from rest of house
Envelope only has one or two exposures
House has a room or rooms in a finished basement or attic
House has one or more rooms with slab or exposed floor
Zone control can be achieved by installing
The rate of airflow delivered to each room must be able to offset the peak room load during cooling. The peak room load can be determined using Chapter 17 of the 2017 ASHRAE Handbook—Fundamentals. The same supply air temperature difference used to size equipment can be substituted into Equation (1) to find airflow. The design flow rate for any zone is equal to the sum of the peak flow rates of all rooms assigned to a zone.
Duct Sizing for Zone Damper Systems
The following guidelines are proposed in ACCA Manual D to size various duct runs.
Use the design blower airflow rate to size a plenum or a main trunk that feeds the zone trunks. Size plenum and main trunk ducts at 800 fpm.
Use zone airflow rates (those based on the sum of the peak room loads) to size the zone trunk ducts. Size all zone trunks at 800 fpm.
Use the peak room airflow rate (those based on the peak room loads) to size the branch ducts or runouts. Size all branch runouts at a friction rate of 0.10 in. of water per 100 ft. For commercial systems, use 0.08 in. of water per 100 ft.
Size return ducts for 600 fpm air velocity.
Box Plenum Systems Using Flexible Duct
In some climates, an overhead duct with a box plenum feeding a series of individual, flexible-duct, branch runouts is popular. The pressure drop through a flexible duct is higher than through a rigid sheet metal duct, however. Recognizing this larger loss is important when designing a box plenum/flexible duct system.
Design of the box plenum is critical to avoid excessive pressure loss and to minimize unstable air rotation in the plenum, which can change direction between blower cycles. This in turn may change air delivery through individual branch takeoffs. Unstable rotation can be avoided by having air enter the box plenum from the side and by using a special splitter entrance fitting.
Gilman et al. (1951) proposed box plenum dimensions and entrance fitting designs to minimize unstable conditions as summarized in Figures 5 and 6. For residential systems with less than 2250 cfm capacity, pressure loss through the box plenum is approximately 0.05 in. of water. This loss should be deducted from the available static pressure to determine the static pressure available for duct branches. In terms of equivalent length, add approximately 50 ft to the measured branch runs.
In cold climates, floor slab construction requires that the floor and slab perimeter be heated to provide comfort and prevent condensation. The temperature drop (or rise) in the supply air is significant, and special design tables must be used to account for the different supply air temperatures at distant registers. Because duct heat losses may cause a large temperature drop, feed ducts need to be placed at critical points in the loop.
A second aspect of a loop system is installation. The building site must be well drained and the surrounding grade sloped away from the structure. A vapor retarder must be installed under the slab. The bottom of the embedded duct must not be lower than the finished grade. Because a concrete slab loses heat from its edges outward through the foundation walls and downward through the earth, the edge must be properly insulated.
A typical loop duct is buried in the slab 2 to 18 in. from the outer edge and about 2.5 in. beneath the slab surface. If galvanized sheet metal is used for the duct, it must be coated on the outside to comply with Federal Specification SS-A-701. Other special materials used for ducts must be installed according to the manufacturer’s instructions. In addition, care must be taken when the slab is poured not to puncture the vapor retarder or to crush or dislodge the ducts.
Abushakra, B., I.S. Walker, and M.H. Sherman. 2002. A study of pressure losses in residential air distribution systems. Proceedings of the 2002 ACEEE Summer Study on Energy Efficiency in Buildings, pp. 1.1-1.14.
ACCA. 2009. Air distribution basics for residential and small commercial buildings. Manual T. Air Conditioning Contractors of America, Washington, D.C.
ACCA. 2003. Residential duct diagnostics and repair. Air Conditioning Contractors of America, Washington, D.C.
AHRI. Updated annually. AHRI certification programs; unitary air-conditioner equipment; unitary heat pump equipment. Air-Conditioning and Refrigeration Institute, Arlington, VA. Available from www.ahrinet.org/ahri+certification+programs.aspx.
Andrews, J.W. 1992. Optimal forced-air distribution in new housing. Proceedings of the 1992 ACEEE Summer Study on Energy Efficiency in Buildings, pp. 2.1-2.4.
Andrews, J.W. 1996. Field comparison of design and diagnostic pathways for duct efficiency evaluation. Proceedings of the ACEEE 1996 Summer Study on Energy Efficiency in Buildings, pp. 1.21-1.30. Washington, D.C.
Andrews, J.W. 2000. Reducing measurement uncertainties in duct leakage testing. Proceedings of the 2000 ACEEE Summer Study on Energy Efficiency in Buildings, vol. 1, pp. 13-28.
Andrews, J.W. 2002. Laboratory evaluation of the delta Q test for duct leakage. Proceedings of the 2002 ACEEE Summer Study on Energy Efficiency in Buildings, pp. 1.15-1.28.
Andrews, J.W. 2003. Effect of airflow and heat input rates on duct efficiency. ASHRAE Transactions 109(2):413-421. Paper KC-03-01-5.
Andrews, J.W. 2003. Future directions for thermal distribution standards. Report BNL-72081-2004-IR. Available from www.osti.gov/bridge.
Andrews, J.W., and M.P. Modera. 1991. Energy savings potential for advanced thermal distribution technology in residential and small commercial buildings. Report LBL-31042.
Andrews, J.W., R. Hedrick, M. Lubliner, B. Reid, B. Pierce, and D. Saum. 1998. Reproducibility of ASHRAE Standard 152P: Results of a round-robin test. ASHRAE Transactions 104(1):1376-1388. Paper SF-98-17-3.
Andrews, J.W., R.F. Krajewski, and J.J. Strasser. 1996. Electric co-heating in the ASHRAE standard method of test for thermal distribution efficiency: Test results in two New York state homes. ASHRAE Transactions 102(1). Paper AT-96-13-3.
Asiedu, Y., R.W. Besant, and P. Gu. 2000. A simplified procedure for HVAC duct sizing. ASHRAE Transactions 106(1):124-142. Paper 4329.
ASTM. 2007. Standard test methods for determining external air leakage of air distribution systems by fan pressurization. ASTM Standard E1554-07. American Society for Testing and Materials, Philadelphia.
Axley, J. 1999. Passive ventilation for residential air quality control. ASHRAE Transactions 105(2):864-876. Paper SE-99-11-3.
Baskin, E., and E.A. Vineyard. 2003. Thermal comfort assessment of conventional and high-velocity systems for cooling season. ASHRAE Transactions 109(1):513-519. Paper CH-03-07-5.
Bouchelle, M., D.S. Parker, M.T. Anello, and K.M. Richardson. 2000. Factors influencing space heat and heat pump efficiency from a large-scale residential monitoring study. Proceedings of 2000 Summer Study on Energy Efficiency in Buildings, American Council for an Energy-Efficient Economy, Washington, D.C.
Bullock, C. 1978. Energy savings through thermostat setback with residential heat pumps. ASHRAE Transactions 84(2):352-363. Paper AL-78-01-3.
Caffey, G. 1979. Residential air infiltration. ASHRAE Transactions 85(1). Paper PH-2512.
Crisafulli, J.C., R.A. Cudnik, and L.R. Brand. 1989. Investigation of regional differences in residential HVAC system performance using the SP43 simulation model. ASHRAE Transactions 95(1):915-929. Paper CH-89-14-3.
CEE. 2000. Specification of energy efficient installation practices for residential HVAC systems. Consortium for Energy Efficiency, Boston.
Colto, F., and G. Syphers. 1998. Are your ducts all in a row? Duct efficiency testing and analysis for 150 new homes in northern California. Proceedings of the 1998 ACEEE Summer Study on Energy Efficiency in Buildings, pp. 1.33-1.41.
Conlin, F. 1996. An analysis of air distribution system losses in contemporary HUD-code manufactured homes. Proceedings of the 1996 ACEEE Summer Study on Energy Efficiency in Buildings, pp. 1.53-1.59.
CSA. 2012. Gas-fired central furnaces. ANSI Standard Z21.47-2012/CSA Standard 2.3-2012. Canadian Standards Association International, Cleveland, OH.
Cummings, J.B., and J.J. Tooley, Jr. 1989. Infiltration and pressure differences induced by forced air systems in Florida residences. ASHRAE Transactions 95(2).
Cummings, J.B., J.J. Tooley, Jr., and R. Dunsmore. 1990. Impacts of duct leakage on infiltration rates, space conditioning energy use, and peak electrical demand in Florida homes. Proceedings of the ACEEE 1990 Summer Study on Energy Efficiency in Buildings, Washington, D.C.
Cummings, J., and C. Withers, Jr. 1998. Building cavities used as ducts: Air leakage characteristics and impacts in light commercial buildings. ASHRAE Transactions 104(2):743-752. Paper TO-98-08-4.
Cummings, J.B., and C.R. Withers, Jr. 2006. Unbalanced return air in residences: Causes, consequences, and solutions. ASHRAE Transactions 112(1):650-655. Paper CH-06-10-2.
Cummings, J.B., C.R. Withers, Jr., and N. Moyer. 2000. Evaluation of the duct leakage estimation procedures of ASHRAE Standard 152P. ASHRAE Transactions 106(2). Paper MN-00-12-2.
Cummings, J.B., C.R. Withers Jr., N.A. Moyer, P.W. Fairey, and B.B. McKendry. 1996. Field measurement of uncontrolled airflow and depressurization in restaurants. ASHRAE Transactions 102(1):859-869. Paper AT-96-13-2.
Cummings, J.B., C.R. Withers, Jr., J. McIlvaine, J.K. Sonne, and M.J. Lombardi. 2003. Air handler leakage: field testing results in residences. ASHRAE Transactions 109(1):496-502. Paper CH-03-07-3.
Davis, B., J. Siegel, and L. Palmiter. 1996. Field measurements of heating system efficiency and air leakage in energy-efficient manufactured homes. Proceedings of the ACEEE 1996 Summer Study on Energy Efficiency in Buildings, Washington, D.C.
Delp, W.W., N.E. Matson, and M.P. Modera 1998. Exterior exposed ductwork: Delivery effectiveness and efficiency. ASHRAE Transactions 104(2):709-721. Paper TO-98-08-1.
Delp, W.W., N.E. Matson, E. Tschudy, M.P. Modera, and R.C. Diamond. 1998. Field investigation of duct system performance in California light commercial buildings. ASHRAE Transactions 104(2):722-731. Paper TO-98-08-2.
Dickerhoff, D., I. Walker, and M. Sherman. 2004. Validating and improving the delta-Q duct leakage test. ASHRAE Transactions 110(2):741-751. Paper NA-04-6-5.
DOE. 2002. Controlling airflow: Better air distribution for small commercial buildings. Office of Energy Efficiency and Renewable Energy, Building Technologies Program, U.S. Department of Energy. Written and prepared by J.W. Andrews, J.B. Cummings, and M.P. Modera.
Downey, T. and J. Proctor. 2002. What can 13,000 air conditioners tell us? Proceedings of the 2002 ACEEE Summer Study on Energy Efficiency in Buildings, pp. 1.53-1.67.
Ebbing, C., and W. Blazier. 1998. Application of manufacturers’ sound data. ASHRAE.
Ellison, R.D. 1977. The effects of reduced indoor temperature and night setback on energy consumption of residential heat pumps. ASHRAE Journal.
Fischer, R.D., and R.A. Cudnik. 1993. The HOUSE-II computer model for dynamic and seasonal performance simulation of central forced-air systems in multi-zone residences. ASHRAE Transactions 99(1):614-626. Paper 3681.
Fischer, R.D., F.E. Jakob, L.J. Flanigan, D.W. Locklin, and R.A. Cudnik. 1984. Dynamic performance of residential warm-air heating systems—Status of ASHRAE Project SP43. ASHRAE Transactions 90(2B):573-590. Paper KC-84-10-2.
Francisco, P.W., and L. Palmiter. 1998. Measured and modeled duct efficiency in manufactured homes: Insights for Standard 152P. ASHRAE Transactions 104(1B):1389-1401. Paper SF-98-17-4.
Francisco, P.W., and L. Palmiter. 1999. Field validation of ASHRAE Standard 152. Final Report, ASHRAE Research Project RP-1056.
Francisco, P.W., and L. Palmiter. 2000. Field validation of Standard 152P. ASHRAE Transactions 106(2). Paper MN-00-12-1.
Francisco, P.W., and L. Palmiter. 2000. Performance of duct leakage measurement techniques in estimating duct efficiency: Comparison to measured results. Proceedings of the ACEEE 2000 Summer Study on Energy Efficiency in Buildings, Washington, D.C.
Francisco, P.W., and L.S. Palmiter. 2001. The nulling test: A new measurement technique of estimating duct leakage in residential homes. ASHRAE Transactions 107(1):297-303. Paper 4447.
Francisco, P.W., and L. Palmiter. 2003. Field evaluation of a new device to measure air handler flow. ASHRAE Transactions 109(2):403-412. Paper KC-03-01-4.
Francisco, P.W., L. Palmiter, and B. Davis. 1998. Modeled vs. measured duct distribution efficiency in six forced-air gas-heated homes. Proceedings of the 1998 ACEEE Summer Study on Energy Efficiency in Buildings, pp. 1.103-1.114.
Francisco, P.W., L. Palmiter, and B. Davis. 2002. Field performance of two new residential duct leakage measurement techniques. Proceedings of the 2002 ACEEE Summer Study on Energy Efficiency in Buildings, pp. 1.69-1.80.
Francisco, P.W., L. Palmiter, and B. Davis. 2003. Insights into improved ways to measure residential duct leakage. ASHRAE Transactions 109(1):485-495. Paper CH-03-07-2.
Francisco, P.W., D. Baylon, B. Davis, and L. Palmiter. 2004. Heat pump system performance in northern climates. ASHRAE Transactions 110(1): 442-451. Paper AN-04-05-3.
Francisco, P.W., L. Palmiter, E. Kruse, and B. Davis. 2004. Evaluation of two new duct leakage measurement methods in 51 homes. ASHRAE Transactions 110(2):727-740. Paper NA-04-6-4.
FSEC. 2001. Factors influencing space heat and heat pump efficiency from a large-scale residential monitoring study. Report FSEC-PF362-01. Florida Solar Energy Center, Cocoa.
GAMA. Updated annually. Consumer’s directory of certified efficiency ratings for residential heating and water heating equipment. Gas Appliance Manufacturers Association, Arlington, VA.
Gammage, R.B., A.R. Hawthorne, and D.A. White. 1984. Parameters affecting air infiltration and air tightness in thirty-one east Tennessee homes. Proceedings of the ASTM Symposium on Measured Air Leakage Performance of Buildings, Philadelphia.
Griffiths, D., R. Aldrich, W. Zoeller, and M. Zuluaga. 2002. An innovative approach to reducing duct heat gains for a production builder in a hot and humid climate—How we got there. Proceedings of the 2002 ACEEE Summer Study on Energy Efficiency in Buildings, pp. 1.81-1.90.
Griffiths, D., and M. Zuluaga. 2004. An analysis of the effective R-value for insulation buried attic ducts. ASHRAE Transactions 110(2):721-726. Paper NA-04-6-3.
Gu, L., J.E. Cummings, P.W. Fairey, and M.V. Swami. 1998. Comparison of duct computer models that could provide input to the proposed thermal distribution standard method of test (ASHRAE Research Project RP-852). ASHRAE Transactions 104(1):1349-1359. Paper SF-98-17-1.
Gu, L., M.V. Swami, and P.W. Fairey. 2003. System interactions in forced-air heating and cooling systems, part I: Equipment efficiency factors. ASHRAE Transactions 109(1):475-484. Paper CH-03-07-1.
Gu, L., M.V. Swami, and P.W. Fairey. 2003. System interactions in forced-air heating and cooling systems, part II: Continuous fan operation. ASHRAE Transactions 109(2):371-379. Paper KC-03-01-1.
Guyton, M.L. 1993. Measured performance of relocated air distribution systems in an existing residential building. ASHRAE Transactions 99(2). Paper DE-93-12-2.
Hales, D., A. Gordon, and M. Lubliner. 2003. Duct leakage in new Washington State residences: Findings and conclusions. ASHRAE Transactions 109(2):393-402. Paper KC-03-01-3.
Hammarlund, J., J. Proctor, G. Kast, and T. Ward. 1992. Enhancing the performance of HVAC and distribution systems in residential new construction. Proceedings of the 1992 ACEEE Summer Study on Energy Efficiency in Buildings, pp. 2.85-2.88.
Hedrick, R.L. 2003. Building homes with ducts in conditioned space. Draft Report to the California Energy Commission, Public Interest Energy Research (PIER) Program.
Hedrick, R.L., M.J. Witte, N.P. Leslie, and W.W. Bassett. 1992. Furnace sizing criteria for energy-efficient setback strategies. ASHRAE Transactions 98(1):1239-1246. Paper AN-92-17-1.
Herold, K.E., F.E. Jakob, and R.D. Fischer. 1986. The SP43 simulation model: Residential energy use. Proceedings of ASME Conference, Anaheim, pp. 81-87.
Herold, K.E., R.A. Cudnik, L.J. Flanigan, and R.D. Fischer. 1987. Update on experimental validation of the SP43 simulation model for forced-air heating systems. ASHRAE Transactions 93(2):1919-1933. Paper NY-87-20-3.
Herold, K.E., R.D. Fischer, and L.J. Flanigan. 1987. Measured cooling performance of central forced-air systems and validation of the SP43 simulation model. ASHRAE Transactions 93(1):1443-1457. Paper NY-87-16-1.
Hise, E.C. and A.S. Holman. 1977. Heat balance and efficiency measurements of central, forced-air, residential gas furnaces. ASHRAE Transactions 83(1):865-880. Paper CH-77-14-3.
IRC. 2012. International residential code® for one- and two-family dwellings (IRC®). International Code Council, Washington, D.C.
Jakob, F.E., R.D. Fischer, L.J. Flanigan, D.W. Locklin, K.E. Harold, and R.A. Cudnik. 1986. Validation of the ASHRAE SP43 dynamic simulation model for residential forced-warm air systems. ASHRAE Transactions 92(2B):623-643. Paper PO-86-13-1.
Jakob, F.E., D.W. Locklin, R.D. Fischer, L.J. Flanigan, and R.A. Cudnik. 1986. SP43 evaluation of system options for residential forced-air heating. ASHRAE Transactions 92(2B):644-673. Paper PO-86-13-2.
Jakob, F.E., R.D. Fischer, and L.J. Flanigan. 1987. Experimental validation of the duct submodel for the SP43 simulation model. ASHRAE Transactions 93(1):1499-1515. Paper NY-87-16-5.
Jump, D.A., I.S. Walker, and M.P. Modera. 1996. Field measurements of efficiency and duct retrofit effectiveness in residential forced-air distribution systems. Proceedings of the ACEEE 1996 Summer Study on Energy Efficiency in Buildings, Washington, D.C.
Kendall, M.A. 2004. Energy-saving opportunities in residential air-handler efficiency. ASHRAE Transactions 110(1):425-430. Paper AN-04-05-1.
Locklin, D.W., K.E. Herold, R.D. Fischer, F.E. Jakob, and R.A. Cudnik. 1987. Supplemental information from SP43 evaluation of system options for residential forced-air heating. ASHRAE Transactions 93(2):1934-1958. Paper NT-87-20-4.
Lubliner, M., R. Kunkle, J. Devine, and A. Gordon. 2002. Washington state residential ventilation and indoor air quality code (VIAQ): Whole house ventilation systems field research report. Proceedings of the 2002 ACEEE Summer Study on Energy Efficiency in Buildings, pp. 1.115-1.130.
Lubliner, M., D.T. Stevens, and B. Davis. 1997. Mechanical ventilation in HUD-code manufactured housing in the Pacific northwest. ASHRAE Transactions 103(1):693-705. Paper PH-97-08-2.
Matthews, T.G., C.V. Thompson, K.P. Monar, and C.S. Dudney. 1990. Impact of heating and air-conditioning system operation and leakage on ventilation and intercompartmental transport: Studies in occupied and unoccupied Tennessee Valley homes. Journal of the Air Waste Management Association 40:194-198.
Modera, M.P., J. Andrews, and E. Kweller. 1992. A comprehensive yardstick for residential thermal distribution efficiency. Proceedings of the 1992 ACEEE Summer Study on Energy Efficiency in Buildings, Washington, D.C.
Modera, M.P., D. Dickerhoff, O. Nilssen, H. Duquette, and J. Geyselaers. 1996. Residential field testing of an aerosol-based technology for sealing ductwork. Proceedings of the 1996 ACEEE Summer Study on Energy Efficiency in Buildings, pp. 1.169-1.175.
Oppenheim, P. 1992. Energy-saving potential of a zoned forced-air heating system. ASHRAE Transactions 98(1):1247-1257. Paper AN-92-17-2.
Palmiter, L., and T. Bond. 1992. Impact of mechanical systems on ventilation and infiltration in homes. Proceedings of the ACEEE 1992 Summer Study on Energy Efficiency in Buildings, Washington, D.C.
Palmiter, L., and P.W. Francisco. 1994. Measured efficiency of forced-air distribution systems in 24 homes. Proceedings of the ACEEE 1994 Summer Study on Energy Efficiency in Buildings, Washington, D.C.
Palmiter, L., and P.W. Francisco. 1996. A practical method for estimating the thermal efficiency of residential forced-air distribution systems. Proceedings of the ACEEE 1996 Summer Study on Energy Efficiency in Buildings, Washington, D.C.
Palmiter, L., and P.W. Francisco. 1998. Modeled duct distribution efficiency: Insights for heat pumps. Proceedings of the 1998 ACEEE Summer Study on Energy Efficiency in Buildings, pp. 1.223-1.234.
Palmiter, L., and P.W. Francisco. 2000. A new device for field measurement of air handler flows. Proceedings of the ACEEE 2000 Summer Study on Energy Efficiency in Buildings, Washington, D.C.
Palmiter, L., and P.W. Francisco. 2002. Measuring duct leakage with a blower door: Field results. Proceedings of the 2002 ACEEE Summer Study on Energy Efficiency in Buildings, pp. 1.207-1.218.
Palmiter, L.S., I.A. Brown, and T.C. Bond. 1991. Measured infiltration and ventilation in 472 all-electric homes. ASHRAE Transactions 97(2):979-987. Paper IN-91-15-3.
Parker, D.S. 1989. Evidence of increase levels of space heat consumption and air leakage associated with forced air heating systems in houses in the Pacific northwest. ASHRAE Transactions 95(2):527-533. Paper VA-89-05-1.
Parker, D.S., J.R. Sherwin, and B. Hibbs. 2005. Development of high-efficiency air conditioner condenser fans. ASHRAE Transactions 111(2): 511-520. Paper DE-05-04-3.
Proctor, J. 1998. Monitored in-situ performance of residential air-conditioning systems. ASHRAE Transactions 104(1B):1833-1840. Paper SF-98-30-4.
Proctor, J.P. 1998. Verification test of ASHRAE Standard 152P. ASHRAE Transactions 104(1B):1402-1412. Paper SF-98-17-5.
Proctor, J.P., and R.K. Pernick. 1992. Getting it right the second time: Measured savings and peak reduction from duct and appliance repairs. Proceedings of the ACEEE 1992 Summer Study on Energy Efficiency in Buildings, Washington, D.C.
Rittelmann, W.D. 2006. Effects of return air inlet locations on cooling season thermal comfort in an energy-efficient home. ASHRAE Transactions 112(1):641-649. Paper CH-06-10-1.
Robison, D.H., and P.E. Lambert. 1989. Field investigation of residential infiltration and heating duct leakage. ASHRAE Transactions 95(2):542-550. Paper VA-89-05-3.
Rutkowski, H., and J.H. Healy. 1990. Selecting residential air-cooled cooling equipment based on sensible and latent performance. ASHRAE Transactions 96(2):851-856. Paper SL-90-15-1.
Rudd, A.F., and J.W. Lstiburek. 2000. Measurement of ventilation and interzonal distribution in single-family houses. ASHRAE Transactions 106(2):709-718. Paper MN-00-10-3.
Sachs, H.M., T. Kubo, S. Smith, and K. Scott. 2002. Residential HVAC fans and motors are bigger than refrigerators. Proceedings of the 2002 ACEEE Summer Study on Energy Efficiency in Buildings, pp. 1.261-1.272.
Sachs, H.M., and S. Smith. 2004. How much energy could residential furnace air handlers save? ASHRAE Transactions 110(1):431-441. Paper AN-04-05-2.
Saunders, D.H., T.M. Kenney, and W.W. Bassett. 1992. Factors influencing thermal stratification and thermal comfort in four heated residential buildings. ASHRAE Transactions 98(1):1258-1265. Paper AN-92-17-3.
Saunders, D.H., T.M. Kenney, and W.W. Bassett. 1993. Evaluation of the forced-air distribution effectiveness in two research houses. ASHRAE Transactions 99(1):1407-1419. Paper CH-93-19-1.
Sherman, M., I. Walker, and D. Dickerhoff. 2000. Stopping duct quacks: Longevity of residential duct sealants. Proceedings of the 2000 ACEEE Summer Study on Energy Efficiency in Buildings, vol. 1, pp. 273-284.
Siegel, J.A., J.A. McWilliams, and I.S. Walker. 2003. Comparison between predicted duct effectiveness from proposed ASHRAE Standard 152P and measured field data for residential forced-air systems. ASHRAE Transactions 109(1):503-512. Paper CH-03-07-4.
Springer, D.A., L.I. Rainer, and W.L. Dakin. 2005. Development and testing of an integrated residential night ventilation cooling system. ASHRAE Transactions 111(2):501-510. Paper DE-05-04-2.
Strunk, P.R. 2000. Validation of ASHRAE Standard 152P in basement warm-air distribution systems. ASHRAE Transactions 106(2). Paper MN-00-12-3.
Temple, K.A. 2004. Field observations of room air distribution performance in a high-performance home. ASHRAE Transactions 110(2):699-708. Paper NA-04-6-1.
Temple, K.A. 2005. Field performance of a zoned forced-air cooling system in an energy efficient home. ASHRAE Transactions 111(2):487-500. Paper DE-05-04-1.
Treidler, B., and M.P. Modera. 1996. Thermal performance of residential duct systems in basements. ASHRAE Transactions 102(1):847-858. Paper AT-96-13-1.
Treidler, B., M.P. Modera, R.G. Lucas, and J.D. Miller. 1996. Impact of residential duct insulation on HVAC energy use and life-cycle costs to consumers. ASHRAE Transactions 102(1):881-894. Paper AT-96-13-4.
Tutu, N.K., C.R. Krishna, and T. Butcher. 2004. Characterization of airflows at the exit of registers using laser Doppler velocimetry (LDV). ASHRAE Transactions 110(2):709-721. Paper NA-04-6-2.
Walker, I.S. 1998. Technical background for default values used for forced-air systems in proposed ASHRAE Standard 152P. ASHRAE Transactions 104(1B):1360-1375. Paper SF-98-17-2.
Walker, I.S. 1999. Distribution system leakage impacts on apartment building ventilation rates. ASHRAE Transactions 105(1):943-950. Paper CH-99-14-2.
Walker, I.S., and M.P. Modera. 1996. Energy effectiveness of duct sealing and insulation in two multifamily buildings. Proceedings of the 1996 ACEEE Summer Study on Energy Efficiency in Buildings, pp. 1.247-1.254.
Walker, I.S., and M.P. Modera. 1998. Field measurements of interactions between furnaces and forced-air distribution systems. ASHRAE Transactions 104(1B):1805-1816. Paper SF-98-30-1.
Walker, I.S., D.J. Dickerhoff, and M.H. Sherman. 2002. The delta Q method of testing the air leakage of ducts. Proceedings of the 2002 ACEEE Summer Study on Energy Efficiency in Buildings, pp. 1.327-1.338.
Walker, I.S., and C.P. Wray. 2003. Evaluation of flow capture techniques for measuring HVAC grille airflows. ASHRAE Transactions 109(2):380-392. Paper KC-03-01-2.
Withers, C.R., and J.B. Cummings. 2006. Unbalanced return air in commercial buildings. ASHRAE Transactions 112(1):656-664. Paper CH-06-10-3.
Wray, C., I. Walker, and M. Sherman. 2002. Accuracy of flow hoods in residential applications. Proceedings of the 2002 ACEEE Summer Study on Energy Efficiency in Buildings, pp. 1.339-1.350.
Withers, C.W., Jr. and J.B. Cummings. 1998. Ventilation, humidity, and energy impacts of uncontrolled airflow in a light commercial building. ASHRAE Transactions 104(2):733-742. Paper TO-98-08-3.