A heat pump extracts heat from a source and transfers it to a sink at a higher temperature. According to this definition, all pieces of refrigeration equipment, including air conditioners and chillers with refrigeration cycles, are heat pumps. In engineering, however, the term heat pump is generally reserved for equipment that heats for beneficial purposes, rather than that which removes heat for cooling only. Dual-mode heat pumps alternately provide heating or cooling. Heat reclaim heat pumps provide heating only, or simultaneous heating and cooling. An applied heat pump requires competent field engineering for the specific application, in contrast to the use of a manufacturer-designed unitary product. Applied heat pumps include built-up heat pumps (field- or custom-assembled from components) and industrial process heat pumps. Most modern heat pumps use a vapor compression (modified Rankine) cycle or absorption cycle. Any of the other refrigeration cycles discussed in Chapter 2 of the 2017 ASHRAE Handbook—Fundamentals are also suitable. Although most heat pump compressors are powered by electric motors, limited use is also made of engine and turbine drives. Applied heat pumps are most commonly used for heating and cooling buildings, but they are gaining popularity for efficient domestic and service water heating, pool heating, and industrial process heating.
Compressors in large systems vary from one or more reciprocating or screw types to staged centrifugal types. A single or central system is often used, but in some instances, multiple heat pump systems are used to facilitate zoning. Heat sources include the ground, well water, surface water, gray water, solar energy, the air, and internal building heat. Compression can be single-stage or multistage. Frequently, heating and cooling are supplied simultaneously to separate zones.
Decentralized systems with water-loop heat pumps are common, using multiple water-source heat pumps connected to a common circulating water loop. They can also include ground coupling, heat rejectors (cooling towers and dry coolers), supplementary heaters (boilers and steam heat exchangers), loop reclaim heat pumps, solar collection devices, and thermal storage. The initial cost is relatively low, and building reconfiguration and individual space temperature control are easy.
Community and district heating and cooling systems can be based on both centralized and distributed heat pump systems.
2.2 HEAT SOURCES AND SINKS
Table 1 shows the principal media used as heat sources and sinks. Selecting a heat source and sink for an application is primarily influenced by geographic location, climate, initial cost, availability, and type of structure. Table 1 presents various factors to be considered for each medium.
Outdoor air is a universal heat source and sink medium for heat pumps and is widely used in residential and light commercial systems. Extended-surface, forced-convection heat transfer coils transfer heat between the air and refrigerant. Typically, the surface area of outdoor coils is 50 to 100% larger than that of indoor coils. The volume of outdoor air handled is also greater than the volume of indoor air handled by about the same percentage. During heating, the temperature of the evaporating refrigerant is generally 10 to 20°F less than the outdoor air temperature. Air heating and cooling coil performance is discussed in more detail in Chapters 23 and 27.
When selecting or designing an air-source heat pump, two factors in particular must be considered: (1) the local outdoor air temperature and (2) frost formation.
As the outdoor temperature decreases, the heating capacity of an air-source heat pump decreases. This makes equipment selection for a given outdoor heating design temperature more critical for an air-source heat pump than for a fuel-fired system. Equipment must be sized for as low a balance point as is practical for heating without having excessive and unnecessary cooling capacity during the summer. A procedure for finding this balance point, which is defined as the outdoor temperature at which heat pump capacity matches heating requirements, is given in Chapter 49.
When the surface temperature of an outdoor air coil is 32°F or less, with a corresponding outdoor air dry-bulb temperature 4 to 10°F higher, frost may form on the coil surface. If allowed to accumulate, frost inhibits heat transfer; therefore, the outdoor coil must be defrosted periodically. The number of defrosting operations is influenced by the climate, air-coil design, and the hours of operation. Experience shows that, generally, little defrosting is required when outdoor air conditions are below 17°F and 60% rh. This can be confirmed by psychrometric analysis using the principles given in Chapter 23. However, under very humid conditions, when small suspended water droplets are present in the air, the rate of frost deposit may be about three times as great as predicted from psychrometric theory and the heat pump may require defrosting after as little as 20 min of operation. The loss of available heating capacity caused by frosting should be considered when sizing an air-source heat pump.
Following commercial refrigeration practice, early designs of air-source heat pumps had relatively wide fin spacing of 4 to 5 fins/in., based on the theory that this would minimize defrosting frequency. However, experience has shown that effective hot-gas defrosting allows much closer fin spacing and reduces the system’s size and bulk. In current practice, fin spacings of 10 to 20 fins/in. are widely used.
In many institutional and commercial buildings, some air must be continuously exhausted year-round. This exhaust air can be used as a heat source, although supplemental heat is generally necessary.
High humidity caused by indoor swimming pools causes condensation on ceiling structural members, walls, windows, and floors and causes discomfort to spectators. Traditionally, outdoor air and dehumidification coils with reheat from a boiler that also heats the pool water are used. This is ideal for air-to-air and air-to-water heat pumps because energy costs can be reduced. Suitable materials must be chosen so that heat pump components are resistant to corrosion from pool treatment chemicals and high humidity.
Water can be a satisfactory heat source, subject to the considerations listed in Table 1. City water is seldom used because of cost and municipal restrictions. Groundwater (well water) is particularly attractive as a heat source because of its relatively high and nearly constant temperature. Water temperature depends on source depth and climate, but, in the United States, generally ranges from 40°F in northern areas to 70°F in southern areas. Frequently, sufficient water is available from wells (water can be reinjected into the aquifer). This use is nonconsumptive and, with proper design, only the water temperature changes. Water quality should be analyzed, and the possibility of scale formation and corrosion should be considered. In some instances, it may be necessary to separate the well fluid from the equipment with an additional heat exchanger. Special consideration must also be given to filtering and settling ponds for specific fluids. Other considerations are the costs of drilling, piping, pumping, and a means for disposal of used water. Information on well water availability, temperature, and chemical and physical analysis is available from U.S. Geological Survey offices in many major cities. For further information on water quality, groundwater heat pumps, or surface water heat pumps, see Chapter 34 in the 2015 ASHRAE Handbook—HVAC Applications, or Kavanaugh and Rafferty (2014).
Heat exchangers may also be submerged in open ponds, lakes, or streams. When surface or stream water is used as a source, the temperature drop across the evaporator in winter may need to be limited to prevent freeze-up.
In industrial applications, waste process water (e.g., spent warm water in laundries, plant effluent, warm condenser water) may be a heat source for heat pump operation.
Sewage, which often has temperatures higher than that of surface or groundwater, may be an acceptable heat source. Secondary effluent (treated sewage) is usually preferred, but untreated sewage may be used successfully with proper heat exchanger design (Phetteplace and Ueda 1989).
Use of water during cooling follows the conventional practice for water-cooled condensers.
Water-to-refrigerant heat exchangers are generally direct-expansion or flooded water coolers, usually shell-and-coil or shell-and-tube. Brazed-plate heat exchangers may also be used. In large applied heat pumps, the water is usually reversed instead of the refrigerant.
The ground is used extensively as a heat source and sink, with heat transfer through buried coils. Soil composition, which varies widely from wet clay to sandy soil, has a predominant effect on thermal properties and expected overall performance. The heat transfer process in soil depends on transient heat flow. Thermal diffusivity is a dominant factor and is difficult to determine without local soil data. Thermal diffusivity is the ratio of thermal conductivity to the product of density and specific heat. The soil’s moisture content influences its thermal conductivity.
There are three primary types of ground-source heat pumps: (1) groundwater, which is discussed in the previous section; (2) direct-expansion, in which the ground-to-refrigerant heat exchanger is buried underground; and (3) ground-coupled (also called closed-loop ground-source), in which a secondary loop with a brine connects the ground-to-water and water-to-refrigerant heat exchangers (see Figure 5).
Ground loops can be placed either horizontally or vertically. A horizontal system consists of single or multiple serpentine heat exchanger pipes buried 3 to 6 ft apart in a horizontal plane at a depth 3 to 6 ft below grade. Pipes may be buried deeper, but excavation costs and temperature must be considered. Horizontal systems can also use coiled loops referred to as slinky coils. A vertical system uses a concentric tube or U-tube heat exchanger. Design of ground-coupled heat exchangers is covered in Chapter 34 of the 2019 ASHRAE Handbook—HVAC Applications and Kavanaugh and Rafferty (2014).
Solar energy may be used either as the primary heat source or in combination with other sources. Air, surface water, shallow groundwater, and shallow ground-source systems all use solar energy indirectly. The principal advantage of using solar energy directly is that, when available, it provides heat at a higher temperature than the indirect sources, increasing the heating coefficient of performance. Compared to solar heating without a heat pump, the collector efficiency and capacity are increased because a lower collector temperature is required.
The direct system places refrigerant evaporator tubes in a solar collector, usually a flat-plate type. A collector without glass cover plates can also extract heat from the outdoor air. The same surface may then serve as a condenser using outdoor air as a heat sink for cooling.
An indirect system circulates either water or air through the solar collector. When air is used, the collector may be controlled in such a way that (1) the collector can serve as an outdoor air preheater, (2) the outdoor air loop can be closed so that all source heat is derived from the sun, or (3) the collector can be disconnected from the outdoor air serving as the source or sink.
For the most part, the components and practices associated with heat pumps evolved from work with low-temperature refrigeration. This section outlines the major components and discusses characteristics or special considerations that apply to heat pumps in combined room heating and air-conditioning applications or in higher temperature industrial applications.
The principal types of compressors used in applied heat pump systems are briefly described in this section. For more details on these compressor types and others, refer to Chapter 38.
Centrifugal compressors. Most centrifugal applications in heat pumps have been limited to large water-to-water or refrigerant-to-water heat pump systems, heat transfer systems, storage systems, and hydronically cascaded systems. With these applications, the centrifugal compressor allows heat pump use in industrial plants, as well as in large multistory buildings; many installations have double-bundle condensers. The transfer cycles allow low pressure ratios, and many single- and two-stage units with various refrigerants are operational with high coefficients of performance (COPs). Centrifugal compressor characteristics do not usually meet the needs of air-source heat pumps. High pressure ratios, or high lifts, associated with low gas volume at low load conditions cause the centrifugal compressor to surge.
Screw compressors. Screw compressors offer high pressure ratios at low to high capacities. Capacity control is usually provided by variable porting or sliding vanes. Generally, large oil separators are required, because many compressors use oil injection. Screw compressors are less susceptible to damage from liquid spillover and have fewer parts than do reciprocating compressors. They also simplify capacity modulation.
Rotary vane compressors. These compressors can be used for the low stage of a multistage plant; they have a high capacity but are generally limited to lower pressure ratios. They also have limited means for capacity reduction.
Reciprocating compressors. These compressors are the most common for 0.5 to 100 ton systems.
Scroll compressors. These are a type of orbital motion positive-displacement compressor. Their use in heat pump systems is increasing. Their capacity can be controlled by varying the drive speed or the compressor displacement. Scroll compressors have low noise and vibration levels.
Compressor Selection.
A compressor used for comfort cooling usually has a medium clearance volume ratio (the ratio of gas volume remaining in the cylinder after compression to the total swept volume). For an air-source heat pump, a compressor with a smaller clearance volume ratio is more suitable for low-temperature operation and provides greater refrigerating capacity at lower evaporator temperatures. However, this compressor requires somewhat more power under maximum cooling load than one with medium clearance.
More total heat capacity can be obtained at low outdoor temperatures by deliberately oversizing the compressor. This allows some capacity reduction for operation at higher outdoor temperatures by multispeed or variable-speed drives, cylinder cutouts, or other methods. The disadvantage is that the greater number of operating hours that occur at the higher suction temperatures must be served with the compressor unloaded, which generally lowers efficiency and raises annual operating cost. The additional initial cost of the oversized compressor must be economically justified by the gain in heating capacity.
One method proposed for increasing heating output at low temperatures uses staged compression. For example, one compressor may compress from −30°F saturated suction temperature (SST) to 40°F saturated discharge temperature (SDT), and a second compressor compresses the vapor from 40°F SST to 120°F SDT. In this arrangement, the two compressors may be interconnected in parallel, with both pumping from about 45°F SST to 120°F SDT for cooling. Then, at some predetermined outdoor temperature on heating, they are reconnected in series and compress in two successive stages.
Figure 6 shows the performance of a pair of compressors for units of both medium and low clearance volume. At low suction temperatures, the reconnection in series adds some capacity. However, the motor for this case must be selected for the maximum loading conditions for summer operation, even though the low-stage compressor has a greatly reduced power requirement under the heating condition.
Compressor Floodback Protection.
A suction line separator, similar to that shown in
Figure 7, combined with a liquid-gas heat exchanger can be used to minimize migration and harmful liquid floodback to the compressor. The solenoid valve should be controlled to open when the compressor is operating, and the hand valve should then be adjusted to provide an acceptable bleed rate into the suction line.
Refrigerant-to-air and refrigerant-to-water heat exchangers are similar to heat exchangers used in air-conditioning refrigeration systems.
Defrosting Air-Source Coils.
Frost accumulates rather heavily on outdoor-air-source coils when the outdoor air temperature is less than approximately
40°F, but lessens somewhat with the simultaneous decrease in outdoor temperature and moisture content. Most systems defrost by reversing the cycle.
Another method of defrosting is spraying heated water over an outdoor coil. The water can be heated by the refrigerant or by auxiliaries.
Draining Heat Source and Heat Sink Coils.
Direct-expansion indoor and outdoor heat transfer surfaces serve as condensers and evaporators. Both surfaces, therefore, must have proper refrigerant distribution headers to serve as evaporators and have suitable liquid refrigerant drainage while serving as condensers.
Flooded systems use the normal float control to maintain the required liquid refrigerant level.
Liquid Subcooling Coils.
A refrigerant subcooling coil can be added to the heat pump cycle (
Figure 8) to preheat ventilation air during heating and, at the same time, to lower the liquid refrigerant temperature. Depending on the refrigerant circulation rate and quantity and temperature of ventilation air, heating capacity can be increased as much as 15 to 20%, as indicated in
Figure 9.
Refrigerant piping, receivers, expansion devices, and refrigeration accessories in heat pumps are usually the same as components found in other types of refrigeration and air-conditioning systems.
A reversing valve changes the system from cooling to heating mode. This changeover requires using a valve(s) in the refrigerant circuit, except where the change occurs in fluid circuits external to the refrigerant circuit. Reversing valves are usually pilot-operated by solenoid valves, which admit compressor head and suction pressures to move the operating elements.
The expansion device for controlling the refrigerant flow is normally a thermostatic expansion valve, which is described in Chapter 11 of the 2014 ASHRAE Handbook—Refrigeration. The control bulb must be located carefully. If the circuit is arranged so that the refrigerant line on which the control bulb is placed can become the compressor discharge line, the resulting pressure developed in the valve power element may be excessive, requiring a special control charge or pressure-limiting element. When a thermostatic expansion valve is applied to an outdoor air coil, a special cross-charge to limit the superheat at low temperatures allows better use of the coil. In its temperature-sensing element, a cross-charged thermostatic expansion valve uses a fluid, or mixture of fluids, that is different from the refrigerant. An electronic expansion valve improves control of refrigerant flow.
A capillary tube (used as a metering device for an air-source heat pump that operates over a wide range of evaporating temperatures) may pass refrigerant at an excessive rate at low back pressures, causing liquid floodback to the compressor. Suction line accumulators or charge-control devices are sometimes added to minimize this effect. Suction line accumulators may also prevent liquid refrigerant that has migrated to the evaporator from entering the compressor on start-up.
When separate metering devices are used for the two heat exchangers, a check valve allows refrigerant to bypass the metering device of the heat exchanger serving as the condenser.
A refrigerant receiver, which is commonly used to store liquid refrigerant, is particularly useful in a heat pump to take care of the unequal refrigerant requirements of heating and cooling. The receiver is usually omitted on heat pumps used for heating only.
Defrost Control.
A variety of defrosting control schemes can sense the need for defrosting air-source heat pumps and initiate (and terminate) the defrost cycle. The cycle is usually initiated by demand rather than a timer, though termination may be timer-controlled.
Defrost can also be terminated by either a control sensing the coil pressure or a thermostat that measures the temperature of liquid refrigerant in the outdoor coil. Completion of defrosting is ensured when the temperature (or corresponding saturation pressure) of the liquid leaving the outdoor coil rises to about 70°F.
A widely used means of starting the defrost cycle on demand is a pressure control that reacts to the air pressure drop across the coil. When frost accumulates, airflow is reduced and the increased pressure drop across the coil initiates the defrost cycle. This method is applicable only in a clean outdoor environment where fouling of the air side of the outdoor coil is not expected.
Another method for sensing frost formation and initiating defrosting on demand involves a temperature differential control and two temperature-sensing elements. One element is responsive to outdoor air temperature and the other to the temperature of the refrigerant in the coil. As frost accumulates, the temperature differential between the outdoor air and the refrigerant increases, initiating defrost. The system is restored to operation when the refrigerant temperature in the coil reaches a specified temperature, indicating that defrosting has been completed. When outdoor air temperature decreases, the differential between outdoor air temperature and refrigerant temperature decreases because of reduced heat pump capacity. Thus, unless compensation is provided, the defrost cycle is not initiated until a greater amount of frost has built up.
The following controls may be used to change from heating to cooling:
Conditioned space thermostats on residences and small commercial applications.
Outdoor air thermostats (with provision for manual overriding for variable solar and internal load conditions) on larger installations, where it may be difficult to find a location in the conditioned space that is representative of the total building.
Manual changeover using a heat/off/cool position on the indoor thermostat. A single thermostat is used for each heat pump unit.
Sensing devices, which respond to the greater load requirement, heating or cooling, are generally used on simultaneous heating and cooling systems.
Dedicated microcomputers to automate changeover and perform all the other control functions needed, and to simultaneously monitor the performance of the system. This may be a stand-alone device, or it may be incorporated as part of a larger building automation system.
On the heat pump system, it is important that space thermostats are interlocked with ventilation dampers so that both operate on the same cycle. During the heating cycle, the outdoor air damper should be positioned for the minimum required ventilation air, with the space thermostat calling for increased ventilation air only if the conditioned space becomes too warm. Fan and/or pump interlocks are generally provided to prevent the heat pump system from operating if the accessory equipment is not available. On commercial and industrial installations, some form of head pressure control is required on the condenser when cooling at outdoor air temperatures below 60°F.
Heating needs may exceed the heating capacity available from equipment selected for the cooling load, particularly if outdoor air is used as the heat source. When this occurs, supplemental heating or additional compressor capacity should be considered. The additional compressor capacity or the supplemental heat is generally used only in the severest winter weather and, consequently, has a low usage factor. Both possibilities must be evaluated to determine the most economical selection.
When supplemental heaters are used, the elements should always be located in the air or water circuit downstream from the heat pump condenser. This allows the system to operate at a lower condensing temperature, increasing heating capacity and improving the COP. Controls should sequence the heaters so that they are energized after all heat pump compressors are fully loaded. An outdoor thermostat is recommended to limit or prevent energizing heater elements during mild weather when they are not needed. Where 100% supplemental heat is provided for emergency operation, it may be desirable to keep one or more stages of the heaters locked out whenever the compressor is running. In this way, the cost of electrical service to the building is reduced by limiting the maximum coincidental demand.
A flow switch should be used to prevent operation of the heating elements and heat pump when there is no air or water flow.
2.5 INDUSTRIAL PROCESS HEAT PUMPS
Heat recovery in industry offers numerous opportunities for applied heat pumps. The two major classes of industrial heat pump systems are closed-cycle and open-cycle. Factory-packaged, closed-cycle machines have been built to heat fluids to 120°F and as high as 220°F. Skid-mounted open- and semi-open-cycle machines have been used to produce low-level saturated and superheated steam.
The original closed-cycle machines used in designs into the 1990s used old CFC refrigerants such as CFC-11, CFC-12, CFC-113, and CFC-114. However, the Montreal Protocol discontinued these refrigerants, and useful output temperatures of these systems dropped to the 120 to 130°F range. Manufacturers sometimes limited their offerings of closed-cycle systems because sales volumes were so low compared to chillers with the new refrigerants. However, with newer refrigerants such as R-134a, R-410A, and R-410B, output temperatures for closed-cycle machines have returned to the necessary industrial levels (160 to 180°F), and coupling new compressors with these refrigerants has increased efficiencies.
Industrial heat pumps are generally used for process heating rather than space heating. Each heat pump system must be designed for the particular application. Rather than being dictated by weather or design standards, the selection of size and output temperature for a system is often affected by economic restraints, environmental standards, or desired levels of product quality or output. This gives the designer more flexibility in equipment selection because the systems are frequently applied in conjunction with a more traditional process heating system such as steam.
ASHRAE research project RP-656 (Cane et al. 1994) gathered information on energy performance, economics of operation, operating difficulties, operator and management reactions, and design details for various heat recovery heat pump (HRHP) systems. The most common reason given for installing HRHP systems was reducing energy cost. Other reasons cited were
Need to eliminate bacterial growth in storage tanks
Need to increase ammonia refrigeration system capacity
Reduction of makeup water use
Need for flexibility in processing
Year-round processing (drying) possible
Superior drying quality compared with conventional forced-air kilns
Process emissions eliminated without the need for costly pollution control equipment
Recovery and reuse of product from process
Reduced effluent into the environment
Economics associated with energy reductions were calculated for most of the test sites. Economic justifications for the other reasons for installation were difficult to estimate. Only half the survey sites reported actual payback periods. Half of these had simple paybacks of less than 5 years. These findings still apply today: the new heat pumps have restored the original machine capabilities, and often improved them.
The most frequently cited problem was widely fluctuating heat source or sink flow rates or temperatures. Considerable differences between design parameters and actual conditions were also mentioned frequently. In some cases, the difference resulted in oversizing, which caused poor response to load variation, nuisance shutdowns, and equipment failure. Other problems were significant process changes after installation and poor placement of the HRHP.
The number of projects that had overstated savings based on overstated run hours demonstrated the need for accurate prediction methods. Although the low hours of use in some cases resulted from first-year start-up and balancing issues, in most cases it was due to plant capacity reductions, process modifications, or other factors that were not understood during the design phase. It is recommended that water flows and temperatures be measured and then compared to actual process activities during the test period. These numbers can be used to predict future needs compared to projected process requirements. Adding surge and storage tanks also reduces this issue, because they allow for leveling of batch process variations.
Closed-cycle systems use a suitable working fluid, usually a refrigerant in a sealed system. They can use either absorption or vapor compression Heat is transferred to and from the system through heat exchangers similar to refrigeration system heat exchangers. Closed-cycle heat pump systems are often classed with industrial refrigeration systems except that they operate at higher temperatures.
Heat exchangers used must comply with federal and local codes. For example, a double separation between potable water and refrigerant is usually required. However, some applications need local interpretation of potable versus service definitions, such as water used in food preparation (e.g., poultry scalders, equipment cleanup).
Heat exchangers must also be resistant to corrosion and fouling conditions of the source and sink fluids. The refrigerant and oil must be (1) compatible with component materials and (2) mutually compatible at the expected operating temperatures. In addition, the viscosity and foaming characteristics of the oil and refrigerant mixtures must be consistent with the lubrication requirements at the specific mechanical load imposed on the equipment. Proper oil return and heat transfer at the evaporators and condensers must also be considered.
The specific application of a closed-cycle heat pump frequently dictates the selection considerations. In this section, the different types of closed-cycle systems are reviewed, and factors important to the selection process are addressed.
Air-to-air heat pumps or dehumidification heat pumps (Figure 10) are most frequently used in industrial operations to dry or cure products. For example, dehumidification kilns are used to dry lumber to improve its value. Compared to conventional steam kilns, the heat pump provides two major benefits: improved product quality and reduced percent degrade. With dehumidification, lumber can be dried at a lower temperature, which reduces warping, cracking, checking, and discoloration. The system must be selected according to the type of wood (i.e., hard or soft) and the required dry time. Dehumidification heat pumps can also be used to dry agricultural products; poultry, fish, and meat; textiles; and other products.
Air-to-water heat pumps or heat pump water heaters (Figure 11) are a special application of closed-cycle systems that are usually used to dehumidify indoor air where humidity is generated from some activity or process. Typical applications are indoor pools, large commercial kitchens, and industrial laundries. In many tropical climates, the ambient air can also be used to heat water economically where power systems are costly and local natural gas is scarce (e.g., on islands). In most of these applications, the air coil is usually wet and may require coated coils or special metallurgy. See Chapter 49 of this volume and Chapter 50 of the 2019 ASHRAE Handbook—HVAC Applications for more information.
Water-to-water heat pumps may have the most widespread application in industry. They can use cooling tower water, effluent streams, and even chilled-water makeup streams as heat sources. The output hot water can be used for product rinse tanks, equipment cleanup water systems, and product preheaters. The water-to-water heat pump system may be simple, such as that shown in Figure 12, which recovers heat from a process cooling tower to heat water for another process. Figure 12 also shows the integration of a heat exchanger for preheating the process water. Typically, the heat pump COP is in the range of 4 to 6, and the system COP reaches 8 to 15.
Water-to-water heat pump systems may also be complicated, such as the cascaded HRHP system (Figure 13) for a textile dyeing and finishing plant. Heat recovered from various process effluent streams is used to preheat makeup water for the processes. The effluent streams may contain materials, such as lint and yarn, and highly corrosive chemicals that may foul the heat exchanger; therefore, special materials and antifouling devices may be needed for the heat exchanger for a successful design.
Most food-processing plants, which use more water than a desuperheater or a combination desuperheater/condenser can provide, can use a water-to-water heat pump (Figure 14). A water-cooled condenser recovers both sensible and latent heat from the high-pressure refrigerant. Water heated in the condenser is split into two streams: one as a heat source for the water-to-water heat pump, the other to preheat the makeup, process, or cleanup water. Preheated water is blended with hot water from the storage tank to limit the temperature difference across the heat pump condenser to about 20°F, which is standard for many chiller applications. The heated water is then piped back to the storage tank, which is typically sized for 1.5 to 5 h of holding capacity. Because the refrigeration load may be insufficient to provide all the water heating required, existing water heaters (usually steam) provide additional heat and control for process water at the point of use.
Three major tasks must be addressed when adding heat recovery to existing plant refrigeration systems: (1) forcing the hot-gas refrigerant to flow to the desired heat exchanger, (2) scheduling the refrigeration processes to provide an adequate heat source over time while still meeting process requirements, and (3) integrating water-cooled condensers with evaporative condensers. The refrigerant direction can be controlled either by series piping of the two condenser systems or by three pressure-regulating valves (PRVs): one to the hot-gas defrost (lowest-pressure setting), one to the recovery system (medium-pressure setting), and one to the evaporative condensers (highest-pressure setting). PRVs offer good control but can be mechanically complicated. Series piping is simple but can cost more because of the pipe size required for all the hot gas to pass through the water-cooled condenser.
Each refrigeration load should be reviewed for its required output and production requirements. For example, ice production can frequently be scheduled during cleanup periods, and blast freezing for the end of shifts.
In multisystem integration, as in expanded system integration, equalization lines, liquid lines, receivers, and so forth must be designed according to standard refrigeration practices.
Ammonia compressors in a condensing (Figure 15) or cascaded system sometimes can also be used where plant refrigerant gas is compressed further to generate the needed temperature. This option is strongly influenced by the plant refrigeration and compressor systems, because pressure requirements may require high-pressure compressors. Consult the ammonia compressor manufacturer if considering this option.
Process-fluid-to-process-fluid heat pumps can be applied to evaporation, concentration, crystallization, and distillation process fluids that contain chemicals that would destroy a steam compressor. A closed-cycle vapor compression system (Figure 16) is used to separate a solid and a liquid in an evaporator system and to separate two liquids in a distillation system. Both systems frequently have COPs of 8 to 10 and have the added benefit of cooling tower elimination. These systems can frequently be specified and supplied by the column or evaporator manufacturer as a value-added system.
The benefits of water-to-water, refrigerant-to-water, and other fluid-to-fluid systems may include the following:
Lower energy costs because of the switch from fuel-based water heating to heat recovery water heating
Reduced costs for water-treatment chemicals for the boiler because of the switch from a steam-based system
Reduced emissions of NOx, SOx, CO, CO2, and other harmful chemicals because of reduced boiler loading
Decreased effluent temperature, which improves the effectiveness of the water treatment process that breaks down solids
Increased production because of the increased water temperature available at the start of process cycles (for processes requiring a cooler start temperature, preheated water may be blended with ambient water)
Higher product quality from rinsing with water at a higher temperature (blending preheated water with ambient water may be necessary if a cooler temperature is required)
Reduced water and chemical consumption at cooling towers and evaporative condensers
More efficient process cooling if heat recovery can be used to reduce refrigeration pressure or cooling tower return temperature
Reduced scaling of heat exchangers because of the lower surface temperatures in heat pump systems compared to steam coils, forced-air gas systems, and resistance heaters
Open-Cycle and Semi-Open-Cycle Heat Pump Systems
Open- and semi-open-cycle heat pump systems use process fluid to raise the temperature of available heat energy by vapor compression, thus eliminating the need for chemical refrigerants. The most important class of applications is steam recompression. Compression can be provided with a mechanical compressor or by a thermocompression ejector driven by the required quantity of high-pressure steam. The three main controlling factors for this class of systems are vapor quality, boiling point elevation, and chemical makeup.
Recompression of boiler-generated process steam (Figure 17) has two major applications: (1) large facilities with substantial steam pressure drop due to line losses and (2) facilities with a considerable imbalance between steam requirements at low, medium, and high levels. Boiler-generated process steam usually conforms to cleanliness standards that ensure corrosion-free operation of the compression equipment. Evaluation of energy costs and steam value can be complicated with these applications, dictating the use of analytical tools such as pinch technology.
Application of open-cycle heat pumps to evaporation processes is exceptionally important. Single-effect evaporators (Figure 18) are common when relatively small volumes of water and solid need to be separated. The most frequent applications are in the food and dairy industries. The overhead vapors of the evaporator are compressed, and thus heated, and piped to the system heater (i.e., calandria). The heat is transferred to the dilute solution, which is then piped to the evaporator body. Flashing occurs upon entry to the evaporator body, sending concentrate to the bottom and vapors to the top. System COPs reach 10 to 20, and long-term performance of the evaporator improves as less of the product (and thus less build-up) occurs in the calandria because of lower operating temperatures. Multiple-effect evaporators (Figure 19), usually applied in the paper and chemical industries, use the same principles, only on a much larger scale. The multiple evaporator bodies can be piped in series or in parallel. System COPs can exceed 30.
Using open-cycle heat pumps in distillation processes (Figure 20) is similar to evaporation. However, compression of flammable gaseous compounds can be dangerous, so great care must be taken. The overhead vapors are compressed to a higher pressure and temperature, and then condensed in the reboiler. This eliminates the need for boiler steam in the reboiler and reduces overall energy consumption. As the pressure of the condensed vapor is reduced through the expansion valve, some of the liquid at a lower temperature is returned to the column as reflux, and the balance forms the overhead product, both as liquid and as vapor. Vapor is recycled as necessary. System COPs can reach 30 or 40.
Process emission-to-steam heat pump systems can be used for cooking, curing, and drying systems that operate with low-pressure saturated or superheated steam. The vapors from a cooking process, such as at a rendering plant, can be recovered to generate the steam required for cooking (Figure 21). The vapors (cooking exhaust) are compressed with a screw compressor because noncondensable materials removed from the process by the vapor could erode or damage reciprocating or centrifugal compressors. Compressed steam is then supplied to the cooker, but may require some makeup water to desuperheat the steam. The steam condenses in the cooking process, and the condensate is then used to heat process water using a heat exchanger for additional heat recovery. The system condensate cannot be recirculated to the compressor because of contaminants; instead, it is sent to the system scrubbers or cleanup system where noncondensables are usually scrubbed or incinerated, and the water is treated or discharged to a sewer.
Contaminants in some processes require the use of a semi-open-cycle heat pump (Figure 22). This system uses a heat exchanger, frequently called a reboiler, to recover heat from the stack gases. The reboiler produces low-pressure steam, which is compressed to the desired pressure and temperature. A clean-in-place (CIP) system may be used if the volume of contaminants is substantial.
Variable-speed drives can be specified with all these systems for closer, more efficient capacity control. Additional capacity for emergencies can be made available by temporarily overspeeding the drive, while sizing for nominal operating conditions to retain optimal efficiency. Proper integration of heat pump controls and system controls is essential.
Heat Recovery Design Principles
Apply the following basic principles when designing heat recovery systems:
Use second-law, pinch technology, or other thermodynamic analysis methods, especially for complex processes, before detailed design to ensure proper thermodynamic placement of the HRHP.
Design for base-load conditions. Heat recovery systems are designed for reduced operating costs. Process scheduling and thermal storage (usually hot water) can be used for better system balancing. Existing water-heating systems can be used for peak load periods and for better temperature control.
Exchange heat first, and then apply heat pumps. If a heat exchanger is to provide the thermal work in a system, it should be used by itself. If additional cooling of the heat source stream and/or additional heating of the heat sink stream are needed, then a heat pump should be added.
Do not expect a heat pump to solve a design problem. A design problem such as an unbalanced refrigeration system may be exacerbated by adding a heat pump.
Make a complete comparison of the heat exchanger system and the heat pump system. Compared to heat exchange alone, a heat pump system has additional first and operating costs. If feasible, heat exchange should be added to the front end of the heat pump system.
Evaluate the cost of heat displaced by the heat pump system. If the boiler operation is not changed, or if it makes the boiler less efficient, the heat pump may not be economical.
Investigate standard fuel-handling and heat exchanger systems already used in an industry before designing the heat pump. Many industries have developed fuel-handling and heat exchanger systems designed specifically for their unique chemical and contaminant conditions.
Industrial processes follow production loads instead of weather conditions and, therefore, the flow and temperature profile of both the heat source and heat sink over an extended period of time need to be collected and understood. The data may help prevent overestimating the requirements, thus adversely affecting the system’s economics.
Investigate future process changes that may affect the thermal requirements and/or availability of the system. Determine whether the plant is changing to a cold-water cleanup system or to a process to produce less effluent at lower temperatures.
Design the system to give plant operators the same or better control. Thoroughly review manual versus automatic controls. Often, existing systems can provide peaking and control energy if left in series with the new HRHP.
Determine whether special material specifications are needed for handling any process flows. Obtain a chemical analysis for any flow of unknown makeup.
Inform equipment suppliers of the full range of ambient conditions to which the equipment will be exposed and the expected loading requirements.
ASHRAE research project RP-807 (Caneta Research 1998) produced guidelines for evaluating environmental benefits (e.g., energy, water, plant emission reductions) of heat recovery heat pumps. Calculation procedures for energy and water savings and plant emission reductions were outlined. Other, less easily quantified benefits were also documented. Evaluation guidelines were provided for a heat pump water heater in a hospital kitchen; a heat recovery heat pump at a resort with a spa, pool, and laundry service building; heat recovery from refrigeration compressor superheat for makeup water heating; and various drying processes using heat pumps and concentration processes. These guidelines can be used to quantify energy, water, and emission reductions and help justify using heat recovery systems in commercial, institutional, and industrial buildings.