The basic air-handling system is an all-air, single-zone HVAC system consisting of an air-handling unit and an air distribution system. The air-handling unit may be designed to supply constant or variable air volume for low-, medium-, or high-velocity air distribution. Normally, the equipment is located outside the conditioned area in a basement, penthouse, or service area. The equipment can be adjacent to the primary heating and refrigeration equipment or at considerable distance, with refrigerant, chilled water, hot water, or steam circulated to it for energy transfer.
All treated and untreated air must be well mixed for maximum performance of heat transfer surfaces and for uniform temperatures in the airstream. Stratified, parallel paths of treated and untreated air must be avoided, particularly in the vertical plane of systems using double-inlet or multiple-wheel fans. Because these fans may not completely mix the air, different temperatures can occur in branches coming from opposite sides of the supply duct. Poor mixing in units with high outdoor percentages can also result in freezing temperatures at the coils. Single or dual plenum fans can improve mixing conditions as well as reduce space requirements between upstream or downstream unit coils.
1.2 AIR-HANDLING UNIT COMPONENTS
The following sections describe many commonly available air-handling unit components. Not all of these components will necessarily be used in any one system.
To determine the system’s air-handling requirement, the designer must consider the function and physical characteristics of the space to be conditioned, and the air volume and thermal exchange capacities required. Then, the various components may be selected and arranged by considering the fundamental requirements of the central system.
Figure 1 shows two basic arrangements of air-handling unit components for a single-zone, all-air central system suitable for year-round air conditioning. These arrangements allow close control of temperature and humidity. Most of the components in Figure 1 are available from many manufacturers completely assembled or in subassembled sections that can be bolted together in the field. When selecting central system components, specific design parameters must be evaluated to balance cost, controllability, operating expense, maintenance, noise, and space. The sizing and selection of primary air-handling units substantially affect the results obtained in the conditioned space.
The equipment must be adequate, accessible for easy maintenance, and not overly complex in its arrangement and control to provide the required conditions. Further, the designer should consider economics in component selection. Both initial and operating costs affect design decisions. For example, the designer should not arbitrarily design for a 500 fpm face velocity, which has been common for selecting cooling coils and other components. Filter and coil selection at 300 to 400 fpm, with resultant lower pressure loss, could produce a substantial payback on constant-volume systems. Chapter 37 of the 2019 ASHRAE Handbook—HVAC Applications has further information on energy and life-cycle costs.
A return air fan is optional on small systems, but is essential for proper operation of air economizer systems for free cooling from outdoor air if the return path has a significant pressure drop (greater than approximately 0.3 in. of water). It provides a positive return and exhaust from the conditioned area, particularly when mixing dampers allow cooling with outdoor air in intermediate seasons and winter. The return air fan ensures that the proper volume of air returns from the conditioned space. It prevents excess building pressure when economizer cycles introduce more than the minimum quantity of outdoor air, and reduces the static pressure against which the supply fan must work. The return air fan should handle a slightly smaller amount of air to account for fixed exhaust systems, such as toilet exhaust, and to ensure a slight positive pressure in the conditioned space. Chapter 47 of the 2019 ASHRAE Handbook—HVAC Applications provides design details; also, see ASHRAE Guideline 16.
In many situations, a relief (or exhaust) air fan may be used instead of a return fan. A relief air fan relieves ventilation air introduced during air economizer operation and operates only when this control cycle is in effect. When a relief air fan is used, the supply fan must be designed for the total supply and return pressure losses in the system. During economizer mode, the relief fan must be controlled to ensure a slight positive pressure in the conditioned space, as with the return air fan system. The section on Economizers describes the required control for relief air fans.
The section on Mixing Plenums discusses conditions that must be considered when choosing, sizing, and locating automatic dampers for this critical mixing process. These dampers throttle the air with parallel- or opposed-blade rotation. These two forms of dampers have different airflow throttling characteristics (see Chapter 7 of the 2017 ASHRAE Handbook—Fundamentals). Pressure relationships between various sections of this mixing process must be considered to ensure that automatic dampers are properly sized for wide-open and modulating pressure drops. See ASHRAE Guideline 16 for additional detail.
Relief openings in large buildings should be constructed similarly to outdoor air intakes, but may require motorized or self-acting backdraft dampers to prevent high wind pressure or stack action from causing airflow to reverse when the automatic dampers are open. Pressure loss through relief openings should be 0.10 in. of water or less. Low-leakage dampers, such as those for outdoor intakes, prevent rattling and minimize leakage. The relief air opening should be located so that air does not short-circuit to the outdoor air intake. Damper relief openings may also be used in conjunction with area pressure control.
Negative pressure in the outdoor air intake plenum is a function of the resistance or static pressure loss through the outdoor air louvers, damper, and duct. Positive pressure in the relief air plenum is likewise a function of the static pressure loss through the relief damper, the relief duct between the plenum and outdoors, and the relief louver. The pressure drop through the return air damper must accommodate the pressure difference between the positive-pressure relief air plenum and the negative-pressure outdoor air plenum. Proper sizing of this damper facilitates better control and mixing. An additional manual damper may be required for proper air balancing.
Resistance through outdoor air intakes varies widely, depending on construction. Frequently, architectural considerations dictate the type and style of louver. The designer should ensure that the louvers selected offer minimum pressure loss, preferably not more than 0.10 in. of water. High-efficiency, low-pressure louvers that effectively limit carryover of rain are available. Flashing installed at the outer wall and weep holes or a floor drain will carry away rain and melted snow entering the intake. Cold regions may require a snow baffle to direct fine snow to a low-velocity area below the dampers. Outdoor air dampers should be low-leakage types with special gasketed edges and endseals. A separate damper section and damper operator are strongly recommended for ensuring minimum ventilation. The maximum outdoor air damper controls the air needed for economizer cycles.
Carefully consider the location of intake and exhaust louvers; in some jurisdictions, location is governed by codes. Louvers must be separated enough to avoid short-circuiting air. Furthermore, intake louvers should not be near a potential source of contaminated air, such as a boiler stack or hood exhaust. Relief air should also not interfere with other systems. If heat recovery devices are used, intake and exhaust airstreams may need to be run in parallel, such as through air-to-air plate heat exchangers.
A common complaint in buildings is a lack of outdoor air. This problem is especially a concern in VAV systems where outdoor air quantities are established for peak loads and are then reduced in proportion to the air supplied during periods of reduced load. A simple control added to the outdoor air damper can eliminate this problem and keep the amount of outdoor air constant, regardless of VAV system operation. However, the need to preheat outdoor air must be considered if this control is added.
An air-side economizer uses outdoor air to reduce refrigeration requirements. Whereas a logic circuit maintains a fixed minimum of ventilation outdoor air in all weather, the air-side economizer is an attractive option for reducing energy costs when weather conditions allow. The air-side economizer takes advantage of cool outdoor air either to assist mechanical cooling or, if outdoor air is cool enough, to provide total system cooling. When weather allows, temperature controls systems can modulate outdoor air and return air in the correct proportion to produce desired supply air temperatures without the use of mechanical heating or cooling. Designers should evaluate drying of the conditioned space when using economizers.
To exhaust the extra outdoor air brought in by the economizer, a method of variable-volume relief must be provided. The relief volume may be controlled by modulating the relief air dampers in response to building space pressure. Another common approach is opening the relief/exhaust and outdoor air intake dampers simultaneously, although this alone does not address space pressurization. A powered relief or return/relief fan may also be used. The relief system is off and relief dampers are closed when the air-side economizer is inactive. Intake dampers must be low leakage.
Advantages and disadvantages of air-side economizers are discussed in Chapter 2.
Mixing plenums provide space for airstreams with different properties to mix as they are introduced into a common section of ductwork or air-handling unit, allowing the system to operate as intended. If the airstreams are not sufficiently mixed, the resulting stratification adversely affects system performance. Some problems associated with stratification are nuisance low-temperature safety cutouts, frozen cooling coils, excess energy use by the preheat coil, inadequate outdoor air, control hunting, and poor outdoor air distribution throughout occupied spaces.
A common example of a mixing plenum is the air-handling unit mixing box, in which outdoor and recirculated airstreams are combined. In air-handling units, mixing boxes typically have one inlet, with control dampers, for each airstream.
There are no performance standards for mixing boxes or mixing plenums. Thus, it is difficult to know whether a particular mixing box design will provide sufficient mixing. In the absence of performance data, many rules of thumb have been developed to increase the mixing provided by mixing boxes. It is important to note that few supporting data exist; the following suggestions are based largely on common-sense solutions and anecdotal evidence:
The minimum outdoor air damper should be located as close as possible to the return air damper.
An outdoor air damper sized for 1500 fpm gives good control.
Low-leakage outdoor air dampers minimize leakage during system shutdown.
A higher velocity through the return air damper facilitates air balance and may increase mixing.
Parallel-blade dampers may aid mixing. Positioning the dampers so that the return and outdoor airstreams are deflected toward each other may increase mixing.
Placing the outdoor air damper above the return air damper increases mixing by density differences: denser, cold outdoor air mixes as it drops through the warm, less dense return air.
Mixing dampers should be placed across the full width of the unit, even if the location of the return duct makes it more convenient to return air through the side. Return air entering through the side of an air-handling unit can pass through one side of a double-inlet fan while outdoor air passes through the other side. This same situation can exist whenever two parallel fans are used in an air-handling unit receiving two different airstreams. Wherever there are two fans and two airstreams, an air mixer should be used.
Field-built baffles may be used to create additional turbulence and to enhance mixing. Unfortunately, the mixing effectiveness and pressure drop of field-built solutions are unknown.
If stratification is anticipated in a system, then special mixing equipment that has been tested by the manufacturer (see the section on Static Air Mixers) should be specified and used in the air-handling system.
Static air mixers are designed to enhance mixing in the mixing plenum to reduce or eliminate problems associated with stratification. These devices have no moving parts and create turbulence in the airstream, which increases mixing. They are usually mounted between the mixing box and the heating or cooling coil; the space required depends on the amount of mixing that is required. Typical pressure loss for these devices is 0.10 to 0.30 in. of water.
There are no performance standards for air mixers. Thus, manufacturers of air mixers and air-handling units should demonstrate that their devices provide adequate mixing.
A system’s overall performance depends heavily on the filter. Unless the filter is regularly maintained, system resistance increases and airflow diminishes. Accessibility for replacement is an important consideration in filter arrangement and location. In smaller air-handling units, filters are often placed in a slide-out rack for side-access replacement. In larger units and built-up systems with internal or front-loading access, there should be at least 3 ft between the upstream face of the filter bank and any obstruction. Other requirements for filters can be found in Chapter 29 and in ASHRAE Standard 52.2.
Good mixing of outdoor and return air is also necessary for good filter performance. A poorly placed outdoor air duct or a bad duct connection to the mixing plenum can cause uneven filter loading and poor distribution of air through the coil section.
Particulate filters are rated according to ASHRAE Standard 52.2’s minimum efficiency rating value (MERV) system, a numeric ranking from 1 (least) to 20 (highest). A particulate filter bank of at least MERV 6 should be placed upstream of the first coil, to maintain coil cleanliness. Depending on the spaces served, many applications demand higher-efficiency filters. Some studies suggest filters up to MERV 14 can pay for themselves in reduced coil maintenance and better heat transfer effectiveness. Where higher-MERV filters are used, many designers specify a lower-MERV prefilter as an inexpensive sacrificial filter to capture bulk particulate and extend the life of the more expensive final filter.
Filter bank(s) location may be governed by codes. For example, many prevailing health care codes mandate a prefilter upstream of all fans, coils, and humidifiers, plus a final filter bank downstream of all fans, coils, and humidifiers.
Designers are not limited to particulate filters. Electronic air cleaners and gaseous-phase (e.g., activated carbon) filters are available for added protection. For example, ASHRAE Standard 62.1 requires use of gaseous-phase filters for certain, usually urban, regions where outdoor air quality has been measured to exceed threshold values for ozone or other gaseous contaminants. Odor control using activated carbon or potassium permanganate as a filter medium is also available. Chapters 11 and 12 of the 2017 ASHRAE Handbook—Fundamentals have more information on odor control.
Preheat coils are heating coils placed upstream of a cooling coil; they can use steam, hot water, or electric resistance as a medium. Some air-handling units do not require a preheat coil at all, particularly if the percentage of outdoor air is low and if building heating is provided elsewhere (e.g., perimeter baseboard). Where used, a preheat coil should have wide fin spacing, be accessible for easy cleaning, and be protected by filters. If a preheat coil is located in the minimum outdoor airstream rather than in the mixed airstream as shown in Figure 11, it should not heat the air to an exit temperature above 35 to 45°F; preferably, it should become inoperative at outdoor temperatures above 45°F. For use with steam, inner distributing tube or integral face-and-bypass coils are preferable. Hot-water preheat coils should be piped for counterflow so that the coldest air contacts the warmest part of the coil surface first. Consider a constant-flow recirculating pump if the local climate and anticipated percentage of outdoor air may result in freezing conditions at a hot-water preheat coil. Chapter 27 provides more detailed information on heating coils.
Sensible and latent heat are removed from the air by the cooling coils. The cooling medium can be either chilled water or refrigerant, in which case the refrigerant coil serves as the evaporator in a vapor-compression refrigeration cycle. The psychrometrics of cooling and dehumidification were described previously.
In all finned coils, some air passes through without contacting the fins or tubes. The amount of this bypass can vary from 30% for a four-row coil at 700 fpm, to less than 2% for an eight-row coil at 300 fpm. The dew point of the air mixture leaving a four-row coil might satisfy a comfort installation with 25% or less outdoor air (10% for humid climates), a small internal latent load, and sensible temperature control only. For close control of room conditions for precision work, a deeper coil may be required. Chapter 23 provides more information on cooling coils and their selection.
Coil freezing can be a serious problem with chilled-water coils. Full-flow circulation of chilled water during freezing weather, or even reduced flow with a small recirculating pump, minimizes coil freezing and eliminates stratification. Further, continuous full-flow circulation can provide a source of off-season chilled water in air-and-water systems. Antifreeze solutions or complete coil draining also prevent coil freezing. However, because it is difficult (if not impossible) to drain most cooling coils completely, caution should be used if this option is considered.
Another design consideration is the drain pan. ASHRAE Standard 62.1 calls for drain pans to be sloped to a drain, to avoid holding standing water in the air-handling unit. Because of the constant presence of moisture in the cooling coil drain pan and nearby casing, many designers require stainless steel construction in that portion of the air-handling unit.
Reheat coils are heating coils placed downstream of a cooling coil. Reheat systems are strongly discouraged, unless recovered energy is used (see ASHRAE Standard 90.1). Positive humidity control is required to provide comfort conditions for most occupancies. Either reheat or desiccant is usually required to dehumidify outdoor air. Reheating is necessary for laboratory, health care, or similar applications where temperature and relative humidity must be controlled accurately. Heating coils located in the reheat position, as shown in Figure 11, are frequently used for warm-up, although a coil in the preheat position is preferable. Hot-water coils provide a very controllable source of reheat energy. Inner-distributing-tube coils are preferable for steam applications. Electric coils may also be used. See Chapter 27 for more information.
Humidifiers may be installed as part of the air-handling unit, or in terminals at the point of use, or both. Where close humidity control of selected spaces is required, the entire supply airstream may be humidified to a low humidity level in the air-handling unit. Terminal humidifiers in the supply ducts serving selected spaces bring humidity up to the required levels. For comfort installations not requiring close control, moisture can be added to the air by mechanical atomizers or point-of-use electric or ultrasonic humidifiers.
Steam grid humidifiers with dew-point control usually are used for accurate humidity control. Air to a laboratory or other space that requires close humidity control must be reheated after leaving a cooling coil before moisture can be added. Humidifying equipment capacity should not exceed the expected peak load by more than 10%. If humidity is controlled from the room or return air, a limiting humidistat and fan interlock may be needed in the supply duct. This tends to minimize condensation and mold or mildew growth in the ductwork. Humidifiers add some sensible heat that should be accounted for in the psychrometric evaluation. See Chapter 22 for additional information.
An important question for air-handling unit specifiers is where to place the humidification grid. Moisture cannot be successfully added to cold air, so placement is typically downstream of a preheat coil. For general building humidification, one satisfactory location is between a preheat coil and cooling coil.
Another consideration is absorption distance (i.e., distance required for steam to be absorbed into the airstream). This can vary from 18 in. to 5 ft and must be allowed for in the layout and dimensioning of the air-handling unit.
For most routine applications in dry or limited-cooling climates, such as offices, residences, and schools, the air-handling unit’s cooling coil provides adequate dehumidification. For humid climates, separate dehumidifiers or some form of reheat or desiccant is usually necessary. Where a specialty application requires additional moisture removal, desiccant dehumidifiers are an available accessory. Dust can be a problem with solid desiccants, and lithium contamination is a concern with spray equipment. Chapter 23 discusses dehumidification by cooling coils, and Chapter 24 discusses desiccant dehumidifiers.
Energy recovery devices are in greater demand as outdoor air percentage increases along with increasing HVAC efficiency requirements. With some exceptions, ASHRAE Standard 90.1 requires energy recovery devices for air-handling units exceeding 5000 cfm and 70% or more outdoor air. They are used extensively in research and development facilities and in hospitals and laboratories with high outdoor air requirements. Many types are available, and the type of facility usually determines which is most suitable. Choices include heat pipes, runaround loops, fixed-plate energy exchangers, and rotary wheel energy exchangers. See Chapter 26 for details. Select these devices with care, and minimize the differential pressure between airstreams.
Most manufacturers of factory-packaged air-handling units offer optional energy recovery modules for both small and large unit applications. Many countries with extreme climates provide heat exchangers on outdoor/relief air, even for private homes. This trend is now appearing in both modest and large commercial buildings worldwide. Under certain circumstances, heat recovery devices can save energy and reduce the required capacity of primary cooling and heating plants by 20% or more.
Where noise control is important, air-handling units can be specified with a noise control section, ranging from a plenum lined with acoustic duct liner to a full bank of duct silencers. This option is available in the smallest to largest units. Sound attenuation can be designed into the discharge (supply) end of the air-handling unit to reduce ductborne fan noise. Remember to consider ductborne noise traveling backward down the return or outdoor air paths in a noise-sensitive application, and use a sound attenuation module if necessary at the inlet end of an air-handling unit. See Chapter 48 of the 2019 ASHRAE Handbook—HVAC Applications for details.
Axial-flow, centrifugal, or plenum (plug) fans may be chosen as supply air fans for straight-through flow applications. In factory-fabricated units, more than one centrifugal fan may be tied to the same shaft. If headroom allows, use a single-inlet fan when air enters at right angles to the flow of air through the equipment. This allows direct airflow from the fan wheel into the supply duct without abrupt change in direction and loss in efficiency. It also allows a more gradual transition from the fan to the duct and increases static regain in the velocity pressure conversion. To minimize inlet losses, the distance between casing walls and fan inlet should be at least the diameter of the fan wheel. With a single-inlet fan, the length of the transition section should be at least half the width or height of the casing, whichever is longer. If fans blow through the equipment, analyze air distribution through the downstream components, and use baffles to ensure uniform air distribution. See Chapter 21 for more information.
Two placements of the supply fan section are common. A supply fan placed downstream of the cooling coil is known as a draw-through arrangement, because air is drawn, or induced, across the cooling coil. Similarly, a supply fan placed upstream of the cooling coil is called the blow-through position. Either arrangement is possible in both small and large air-handling units, and in factory-packaged and custom field-erected units.
A draw-through system (illustrated in Figure 1) draws air across the coils. A draw-through system usually provides a more even air distribution over all parts of the coil. However, some fan heat is added to the airstream after the air has crossed the cooling coil and must be taken into account when calculating the desired supply air temperature. A draw-through arrangement has a higher dehumidification (latent cooling) effect for a given leaving air temperature, because it overcools the air and reheats it with fan heat. If a typical cooling coil drops the wet-bulb temperature 12°F and the motor heat rise is 3°F, then the latent cooling is 12 − 3 = 9°F. This can help with jobs that need higher dehumidification levels.
A blow-through system (illustrated in Figure 1) requires some caution on the part of the designer, because the blast effect of the supply fan outlet can concentrate a high percentage of the total air over a small percentage of the downstream coil surfaces. Air diffusers or diverters may be required. Consequently, blow-through air-handling units may tend to be longer overall than comparable draw-through units. This arrangement offers the advantage of placing the fan before the cooling coil, allowing the cooling coil to remove fan heat from the system. The blow-through arrangement is mandatory where natural-gas-fired heat exchangers are used for heating.
In either arrangement, consider the system effect of the fan arrangement in the unit. Refer to AMCA Standard 210/ASHRAE Standard 51 for details.
Vibration and sound isolation equipment is required for many central fan installations. Standard mountings of fiberglass, ribbed rubber, neoprene mounts, and springs are available for most fans and prefabricated units. The designer must account for seismic restraint requirements for the seismic zone in which the project is located (see Chapter 55 of the 2019 ASHRAE Handbook—HVAC Applications). In some applications, fans may require concrete inertia blocks in addition to spring mountings. Steel springs require sound-absorbing material inserted between the springs and the foundation. Horizontal discharge fans operating at a high static pressure frequently require thrust arrestors. Ductwork connections to fans should be made with fireproof fiber cloth sleeves having considerable slack, but without offset between the fan outlet and rigid duct. Misalignment between the duct and fan outlet can cause turbulence, generate noise, and reduce system efficiency. Electrical and piping connections to vibration-isolated equipment should be made with flexible conduit and flexible connections.
Equipment noise transmitted through ductwork can be reduced by sound-absorbing units, acoustical lining, and other means of attenuation. Sound transmitted through the return and relief ducts should not be overlooked. Acoustical lining sufficient to adequately attenuate objectionable system noise or locally generated noise should be considered. Chapter 48 of the 2019 ASHRAE Handbook—HVAC Applications, Chapter 8 of the 2017 ASHRAE Handbook—Fundamentals, and ASHRAE Standard 68 have further information on sound and vibration control. Noise control, both in occupied spaces and outdoors near intake or relief louvers, must be considered. Some local ordinances may limit external noise produced by these devices.