1. INITIAL BUILDING CONSIDERATIONS
Private refrigerated space is usually adjacent to or in the same building with the owner’s
other operations.
Public space should be located to serve a producing area, a transit storage point, a large consuming
area, or various combinations of these to develop a good average occupancy. It should also have the
following:
-
Convenient location for producers, shippers, and distributors, considering the present
tendency toward decentralization and avoidance of congested areas
-
Good railroad switching facilities and service with minimum switching charges from all
trunk lines to plant tracks if a railhead is necessary to operate the business
profitably
-
Easy access from main highway truck routes as well as local trucking, but avoiding
location on congested streets
-
Ample land for trucks, truck movement, and plant utility space plus future expansion
-
Location with a reasonable land cost
-
Adequate power and water supply
-
Provisions for surface, waste, and sanitary water disposal
-
Consideration of zoning limitations and fire protection
-
Location away from residential areas, where noise of outdoor operating equipment (i.e.,
fans and engine-driven equipment on refrigerated vehicles) would be objectionable
-
External appearance that is not objectionable to the community and meets municipal
requirements
-
Minimal tax and insurance burden
-
Plant security
-
Favorable undersoil bearing conditions and good surface drainage
Plants are often located away from congested areas or even outside city limits, where the cost of
increased trucking distance is offset by better plant layout possibilities, a better road network,
better or lower-priced labor supply, or other economies of operation.
Configuration and Size Determination
Building configuration and size of a cold-storage facility are determined by the following factors:
-
Is receipt and shipment of goods to be primarily by rail or by truck? Shipping practices
affect the platform areas and internal traffic pattern.
-
What relative percentages of merchandise are for cooler and for freezer storage? Products
requiring specially controlled conditions, such as fresh fruits and vegetables, may
justify or demand several individual rooms. Seafood, butter, and nuts also require
special treatment. Where overall occupancy may be reduced because of seasonal
conditions, consider providing multiple-use spaces.
-
Will room usage change in the future? For example, if a room may need to switch from
cooler to freezer, it can be significantly less expensive to incorporate this ability
during design and installation than as a retrofit.
-
What percentage is anticipated for long-term storage? Products that are stored long term
can usually be stacked more densely.
-
Will the product be primarily in small or large lots? The drive-through rack system or a
combination of pallet racks and a mezzanine have proved effective in achieving efficient
operation and effective use of space. Mobile or moving rack systems are also valid
options.
-
How will the product be palletized? Dense products such as meat, tinned fruit, drums of
concentrate, and cases of canned goods can be stacked very efficiently. Palletized
containers and special pallet baskets or boxes effectively hold meat, fish, and other
loose products. The slip sheet system, which requires no pallets, eliminates the waste
space of the pallet and can be used effectively for some products. Pallet stacking racks
make it feasible to use the full height of the storage and palletize any closed or boxed
merchandise.
-
Will rental space be provided for tenants? Rental space usually requires special
personnel and office facilities. An isolated area for tenant operations is also
desirable. These areas are usually leased on a unit area basis, and plans are worked
into the main building layout.
The owner of a prospective refrigerated facility may want to obtain advice from specialists in
product storage, handling, and movement systems.
Typically, the height of refrigerated spaces is at least 28 to 35 ft or more. Some
modern high-bay cold storage facilities can be as tall as 148 ft. Clear space is
required between the floor and structural steel to allow forklift operation. The practical height
for stacking pallets without racks is 15 to 18 ft. Pallet rack systems are used when
greater stacking height is desired. Clear space above the pallet stacks is used for air units, air
distribution, lighting, and sprinkler lines. Generally, 6 to 10 ft minimum clear height
is desired from top of product to bottom of support structure to ensure there is no interference
with drain pan and drain lines of air units. Greater clear heights are usually required if automated
or mechanized equipment is used. Overhead space is relatively inexpensive, and because the
refrigeration requirement for extra height is not significant in the overall plant cost, consider
allowing ample space for clearance between product and refrigeration equipment or piping. Greater
heights are valuable if automated or mechanized material handling equipment is contemplated. The
effect of high stacking arrangements on insurance rates should be investigated.
Floor area in a facility where diverse merchandise is to be stored can be calculated on the basis of
8 to 10 lb per gross cubic foot, to allow about 40% for aisles and space above the
pallet stacks. In special-purpose or production facilities, products can be stacked with less aisle
and open space, with an allowance factor of about 20%.
Most refrigerated facilities are single-story structures. Small columns on wide centers allow
palletized storage with minimal lost space. This type of building usually provides additional
highway truck unloading space. The following characteristics of single-story design must be
considered: (1) horizontal traffic distances, which to some extent offset the vertical travel
required in a multistory building; (2) difficulty of using the stacking height with many commodities
or with small-lot storage and movement of goods; (3) necessity for treating the floor below freezers
to give economical protection against possible ground heaving; and (4) high land cost for building
capacity. A one-story facility with moderate or low stacking heights has a high cost per unit area
because of the high ratio of construction costs and added land cost to product storage capacity.
However, first cost and operating cost are usually lower than for a multistory facility.
Figure 1 shows
the layout of a one-story –10°F freezer that complies with current practices.
The following essential items and functions are considered:
-
Refrigeration machinery room
-
Refrigerated shipping docks with seal-cushion closures on the doors
-
Automatic doors
-
Batten doors or strip curtains
-
Low-temperature storage held at –10°F or lower
-
Pallet-rack systems to facilitate handling of small lots and to comply with first-in,
first-out inventory, which is required for some products
-
Blast freezer or separate sharp freezer room for isolation of products being frozen
-
Cooler or convertible space
-
Space for brokerage offices
-
Space for empty pallet storage and repair
-
Space for shop and battery charging
-
Automatic sprinklers in accordance with National Fire Protection Association (NFPA)
regulations
-
Trucker/employee break area
-
Valve stations for underfloor heating
-
Evaporative condenser(s) location
Other areas that must be in a complete operable facility are
A modified one-story design is sometimes used to reduce horizontal traffic distances and land costs.
An alternative is to locate nonproductive services (including offices and the machinery room) on a
second-floor level, usually over the truck platform work area, to allow full use of the ground floor
for production work and storage. However, potential vibration of the second floor from equipment
below must be considered.
One-story design or modification thereof gives the maximum capacity per unit of investment with a
minimum overall operating expense, including amortization, refrigeration, and labor. Mechanization
must be considered, as well. In areas where land availability or cost is a concern, a high-rise
refrigerated storage building may be a viable option.
Designs that provide minimum overall costs restrict office facilities and utility areas to a minimum.
They also include ample dock area to ensure efficiency in loading and unloading merchandise.
Shipping and Receiving Docks
Temperature control regulations for all steps of product handling have led to designing the trucking
dock as a refrigerated anteroom to the cold storage area. Dock refrigeration is an absolute
necessity in humid and warm climates. Typically, separate work crews handle loading and unloading
transport vehicles: one crew moves the product in and out of the vehicles, and a warehouse crew
moves the product in and out of the refrigerated storage. This procedure may allow merchandise to
accumulate on the shipping dock. Maintaining the dock at 34 to 45°F offers the
following advantages:
-
Refrigeration load in the low-temperature storage area, where energy demand per unit
capacity of refrigeration is higher, is reduced.
-
Less ice or frost forms in the low-temperature storage because less humid and warm air
infiltrates the area.
-
Refrigerated products held on the dock maintain a more favorable temperature, thus
maintaining product quality.
-
Packaging remains in good condition because it stays drier. Facility personnel are more
comfortable because temperature differences are smaller.
-
Less maintenance on forklifts and other equipment is required because condensation is
reduced.
-
Need for anterooms or vestibules to the freezer space is reduced or eliminated.
-
Floor areas stay drier, particularly in front of freeze door areas. This assists in
housekeeping and improves safety.
Space for a general office, locker room, and machinery room is needed. A superintendent’s
office and a warehouse records office should be located near the center of operations, and a
checker’s office should be in view of the dock and traffic arrangement. Rented space should be
isolated from warehouse operations.
The machinery room should include ample space for refrigeration equipment and maintenance, adequate
ventilation, standby capacity for emergency ventilation, and adequate segregation from other areas.
Separate exits are required by most building codes. A maintenance shop and space for parking,
charging, and servicing warehouse equipment should be located adjacent to the machinery room.
Electrically operated material-handling equipment is used to eliminate inherent safety hazards of
combustion-type equipment. Battery-charging areas should be designed with high roofs and must be
ventilated, because of the potential for combustible fumes from charging.
Specialized Storage Facilities
Material handling methods and storage requirements often dictate the design of specialized storage
facilities. Automated material handling in the storage, particularly for high stack piling, may be
integral to the structure or require special structural treatments. Controlled-atmosphere and
minimal-air-circulation rooms require special building designs and mechanical equipment to achieve
design requirements. Drive-in and/or drive-through rack systems can improve product inventory
control and can be used in combination with stacker cranes, narrow-aisle high stacker cranes, and
automatic conveyors. Mobile racking systems may be considered where space is at a premium.
In general, specialized storage facilities may be classified as follows:
-
Public refrigerated facility with several chambers designed to handle all commodities.
Storage temperatures range from 35 to 60°F (with or without humidity
control) and to –20°F (without humidity control).
-
Refrigerated facility area for case and break-up distribution, automated to varying
degrees. The area may incorporate racks with pallet spaces to facilitate distribution.
-
Facility designed for a processing operation with bulk storage for frozen ingredients and
rack storage for palletized outshipment of processed merchandise. A common, efficient
adaptation is to adjoin the refrigerated facility to the processing plant.
-
Public refrigerated facility serving several production manufacturers for storing and
inventorying products in lots and assembling outshipments.
-
Mechanized refrigerated facility with stacker cranes, racks, infeed and outfeed
conveyors, and conveyor vestibules. Such a facility may have an interior ceiling
60 to 100 ft high. Evaporators should be mounted in the highest internal
area to help remove moisture from outdoor air infiltration. A penthouse to house the
evaporators can be accessed through doorways on the roof for maintenance, providing a
means to control condensate drip, and allowing added rack storage space in the freezer
area.
Controlled-Atmosphere Storage Rooms
Controlled-atmosphere (CA) storage rooms may be required for storing some commodities, particularly
fresh fruits and vegetables that respire, consuming oxygen (O2) and producing carbon
dioxide (CO2) in the process. The storage life of such products may be greatly lengthened
by a properly controlled environment, which includes control of temperature, humidity, and
concentration of noncondensable gases (O2, CO2, and nitrogen). Hermetically
sealing the room to provide such an atmosphere is challenging, often requiring special gastight
seals. Although information is available for some commodities, the desired atmosphere usually must
be determined experimentally for the commodity as produced, in the specific geographic location
where the storage room is.
Commercial application of controlled-atmosphere storage has historically been limited to fresh fruits
and vegetables that respire. Storage spaces may be classified as having either (1) product-generated
atmospheres, in which the room is sufficiently well sealed that the fruit’s natural oxygen
consumption and CO2 generation balance infiltration of O2 and exhaust of
CO2 into and out of the space; or (2) externally generated atmospheres, in which nitrogen
generators, CO2 scrubbers, or O2 consumers supplement normal respiration of
the fruit to create the desired atmospheric composition. The second type of system can cope with a
poorly sealed room, but the cost of operation may be high; even with the external gas generator
system, a hermetically sealed room is desired.
In most cases, a CO2 scrubber is required, unless the total desired O2 and
CO2 content is 21%, which is the normal balance between O2 and CO2
during respiration. Carbon dioxide may be removed by (1) passing room air over dry lime that is
replaced periodically; (2) passing air through wet caustic solutions in which the caustic (typically
sodium hydroxide) is periodically replaced; (3) using water scrubbers, in which CO2 is
absorbed from the room air by a water spray and then desorbed from the water by outdoor air passed
through the water in a separate compartment; (4) using monoethanolamine scrubbers, in which the
solution is regenerated periodically by a manual process or continuously by automatic equipment; or
(5) using dry adsorbents automatically regenerated on a cyclic basis.
Systems of room sealing to prevent outdoor air infiltration include (1) galvanized steel lining the
walls and ceiling of the room and interfaced into a floor sealing system; (2) plywood with an
impervious sealing system applied to the inside face; and (3) carefully applied sprayed urethane
finished with mastic, which also serves as a fire retardant.
A room is considered sufficiently sealed if, under uniform temperature and barometric conditions, 1 h
after the room is pressurized to 1 in. of water (gage), 0.1 to 0.2 in. remains. A room
with external gas generation is considered satisfactorily sealed if it loses pressure at double the
above rate, and the test prescribed for a room with product-generated atmosphere is about one air
change of the empty room in a 30 day period.
Extreme care in all details of construction is required to obtain a seal that passes these tests.
Doors are well sealed and have sills that can be bolted down; electrical conduits and special seals
around pipe and hanger penetrations must allow some movement while keeping the hermetic seal intact.
Structural penetrations through the seal must be avoided, and the structure must be stable.
Controlled-atmosphere rooms in multifloor buildings, where the structure deflects appreciably under
load, are extremely difficult to seal.
Gasket seals are normally applied at the cold side of the insulation, so that they may be easily
maintained and points of leakage can be detected. However, this placement causes some moisture
entrapment, and the insulation materials must be carefully selected so that this moisture causes
minimal damage. In some installations, cold air with a dew point lower than the inner surface
temperature is circulated through the space between the gas seal and the insulation to provide
drying of this area. Chapters 35 and 37 have
additional information on conditions required for storage of various commodities in
controlled-atmosphere storage rooms.
Automated warehouses usually contain tall, fixed rack arrangements with stacker cranes under fully
automatic, semiautomatic, or manual control. The control systems can be tied into a computer system
to retain a complete inventory of product and location.
The following are some of the advantages of automation:
-
First-in, first-out inventory can be maintained.
-
Enclosure structure is high, requiring a minimum of floor space and providing favorable
cost per cubic foot.
-
Product damage and pilfering are minimized.
-
Direct material handling costs are minimized.
The following are some of the disadvantages:
-
First cost of the racking system and building are very high compared to conventional
designs.
-
Access may be slower, depending on product flow and locations.
-
Cooling equipment may be difficult to access for maintenance, unless installed in a
penthouse.
-
Air distribution must be carefully evaluated.
Refrigerated rooms may be appropriate for long-term storage at temperatures other than the
temperature of the main facility, for bin storage, for controlled-atmosphere storage, or for
products that deteriorate with active air movement. Mechanically cooled walls, floors, and ceilings
may be economical options for controlling the temperature. Embedded pipes or air spaces through
which refrigerated air is recirculated can provide the cooling; with this method, heat leakage is
absorbed into the walls and prevented from entering the refrigerated space.
The following must be considered in the initial design of the room:
-
Initial cooldown of the product, which can impose short-term peak loads
-
Service loads when storing and removing product
-
Odor contamination from products that deteriorate over long periods
-
Product heat of respiration
Supplementary refrigeration or air-conditioning units in the refrigerated room that operate only as
required can usually alleviate such problems.
Cold storage, more than most construction, requires correct design, high-quality materials, good
workmanship, and close supervision. Design should ensure that proper installation can be
accomplished under various adverse job site conditions. Materials must be compatible with each
other. Installation must be done by careful workers directed by an experienced, well-trained
superintendent. Close cooperation between the general, roofing, insulation, and other contractors
increases the likelihood of a successful installation.
Enclosure construction methods can be classified as (1) insulated structural panel, (2) mechanically
applied insulation, or (3) adhesive or spray-applied foam systems. These construction techniques
seal the insulation within an airtight, moisturetight envelope that must not be violated by major
structural components.
Three methods are used to achieve an uninterrupted vapor retarder/insulation envelope. The first and
simplest is total encapsulation of the structural system by an exterior vapor retarder/insulation
system under the floor, on the outside of the walls, and over the roof deck (Figure 2). This
method typically results in fewer penetrations through the vapor retarder, as well as the lowest
cost.
The second method is an entirely interior system in which the vapor retarder envelope is placed
within the room, and insulation is added to the walls, floors, and suspended ceiling (Figure 3). As
with an exterior system, the moisture barrier is best applied to the outside of the enclosures. This
technique is used where walls and ceilings must be washed, where an existing structure is converted
to refrigerated space, or for smaller rooms that are located within large coolers or unrefrigerated
facilities or are part of a food-processing facility. Special-purpose rooms require separate
analysis to determine proper moisture barrier location.
The third method is interior/exterior construction (Figure 4),
which involves an exterior curtain wall of masonry or similar material tied to an interior
structural system. Adequate space allows the vapor retarder/insulation system to turn up over a roof
deck and be incorporated into a roofing system, which serves as the vapor retarder. This method is a
viable alternative, although it allows more interruptions in the vapor retarder than the exterior
system.
The total exterior vapor retarder system (see Figure 2) is
best because it has the fewest penetrations and the lowest cost. Areas of widely varying temperature
should be divided into separate envelopes to retard heat and moisture flow between them (Figure
5).
Space Adjacent to Envelope
Condensation at the envelope is usually caused by high humidity and inadequate ventilation. Poor
ventilation occurs most often within a dead air space such as a ceiling plenum, hollow masonry unit,
through-metal structure, or beam cavity. All closed air spaces should be eliminated, except those
large enough to be ventilated adequately. Ceiling plenums, for instance, are best ventilated by
mechanical vents that move air above the envelope, or with mechanical dehumidification. See the
section on Suspended Ceilings and Other Interstitial Spaces for more information.
If possible, the insulation envelope and vapor retarder should not be penetrated. All steel beams,
columns, and large pipes that project through the insulation should be vapor sealed and insulated
with a 4 ft wrap of insulation. Conduit, small pipes, and rods should be insulated
at four times the regular wall insulation thickness. In both cases, the thickness of insulation on
the projection should be half that on the regular wall or ceiling. Voids within metal projections
should be filled. Where practicable, the wrap insulation should be located, and the metal projection
sealed, on the warm side. Vapor sealing on the inside of conduits prevents moisture flow through the
conduits.
Other considerations include the following:
-
Vapor retardants should be placed on the warm side of insulation systems.
-
Prefabricated, self-locking wall panels also serve as vapor barriers.
-
Roof vapor membranes are often used; these large rubber sheets are laid over roof
insulation, overlapped, sealed, and attached to the roof with nonpenetrating fasteners
or covered with small stone ballast, which is light-colored to help reflect solar heat.
Air/Vapor Treatment at Junctions
Air and vapor leakage at wall/roof junctions is perhaps the predominant construction problem in cold
storage facilities.
When a cold room of interior/exterior design (see Figure 4) is
lowered to operating temperature, the structural elements (roof deck and insulation) contract and
can pull the roof away from the wall. The air outside the refrigerated room generally has a much
higher moisture content than the air in the room. Air with a higher moisture content has a higher
water vapor pressure, which can force water vapor through any break in the vapor barrier. Negative
pressure inside the room further increases this moisture infiltration. Depending on room
temperature, water, frost, or ice may collect near a vapor leak. Therefore, proper design and
construction of the air/vapor seal is critical.
An air/vapor flashing sheet system (a transition from the roof vapor retarder to the exterior wall
vapor retarder) is best for preventing leakage. A good corner flashing sheet must be flexible,
tough, airtight, and vaportight. Proper use of flexible insulation at overlaps, mastic adhesive, and
a good mastic sealer ensure leak-free performance. To remain airtight and vaportight during the life
of the facility, a properly constructed vapor retarder should
-
Be flexible enough to withstand building movements that may occur at operating
temperatures
-
Allow for thermal contraction of the insulation as the room is pulled down to operating
temperature
-
Be constructed with a minimum of penetrations that might cause leaks (wall ties and
structural steel that extend through the corner flashing sheet may eventually leak no
matter how well sealed during construction; minimize these, and make them accessible for
maintenance)
-
Have corner flashing sheet properly lapped and sealed with adhesive and mechanically
fastened to the wall vapor retarder
-
Have corner flashing sealed to roof without openings
-
Have floor to exterior vapor retarders that are totally sealed
The interior/exterior design (see Figure 4) is
likely to be unsuccessful at the wall/roof junction because it is extremely difficult to maintain an
airtight or vaportight environment.
The practices outlined for the wall/roof junction apply for other insulation junctions. The
insulation manufacturer and designer must coordinate details of the corner flashing design.
Poor design and shoddy installation cause moist air leakage into the facility, resulting in frost and
ice formation, energy loss, poor appearance, loss of useful storage space, and, eventually,
expensive repairs.
Refrigerated facilities held above freezing need no special underfloor treatment. A below-the-floor
vapor retarder is needed in facilities held below freezing, however. Without underfloor heating, the
subsoil eventually freezes; any moisture in this soil also freezes and causes floor frost heaving.
In warmer climates, underfloor tubes vented to ambient air may be sufficient to prevent heaving.
Artificial heating, either by air circulated through underfloor ducts or by glycol circulated
through plastic pipe, is the preferred method to prevent frost heaving. Electric heating cables
installed under the floor can also be used to prevent frost formation. The choice of heating method
depends on energy cost, reliability, and maintenance requirements. Air duct systems should be
screened to keep rodents out and sloped for drainage to remove condensation.
Future facility expansion must be considered when underfloor heating systems are being designed.
Wearing-slab heating under the dock area in front of the freezer doors helps eliminate moisture at
the door and floor joints.
When an adhesive is used, the surface against which the insulating material is to be applied should
be smooth and dust free. Where room temperatures are to be below freezing, masonry walls should be
leveled and sealed with cement back plaster. Smooth poured concrete surfaces may not require back
plastering.
No special surface preparation is needed for a mechanical fastening system, assuming that the surface
is reasonably smooth and in good repair.
The surface must be warm and dry for a sprayed-foam system. Any cracks or construction joints must be
prepared to prevent projection through the sprayed insulation envelope. All loose grout and dust
must be removed to ensure a good bond between the sprayed foam insulation and the surface. Very
smooth surfaces may require special bonding agents.
No special surface preparation is needed for insulated panels used as a building lining, assuming the
surfaces are sound and reasonably smooth. Grade beams and floors should be true and level where
panels serve as the primary walls.
Insulated structural panels with metal exteriors and metal or reinforced plastic interior faces are
prevalent for both coolers and freezers. They keep moisture from the insulation, leaving only the
joints between panels as potential areas of moisture penetration. They are also available with
surface finishes that meet government requirements.
For sanitary washdowns, a scrubbable finish is sometimes required. Such finishes generally have low
permeance; when one is applied on the inside surface of the insulation, a lower-permeance treatment
is required on the outside of the insulation.
All insulated walls and ceilings should have an interior finish. The finish should be impervious to
moisture vapor and should not serve as a vapor retarder, except for panel construction. The
permeance of the in-place interior finish should be significantly greater than the permeance of the
in-place vapor retarder.
To select an interior finish to meet the installation’s in-use requirements, consider the
following factors: (1) fire resistance, (2) washdown requirements, (3) mechanical damage, (4)
moisture and gas permeance, and (5) government requirements. All interior walls of insulated spaces
should be protected by bumpers and curbs wherever there is a possibility of damage to the finish.
Suspended Ceilings and Other
Interstitial Spaces
It is not uncommon to have interstitial spaces above or adjacent to cold spaces in refrigerated
facilities. The reason for the space may be design (e.g., an older facility with an air space used
as insulation, a drop ceiling, or a production space that requires a cleanable ceiling surface), or
facility expansion (e.g., adding freezer space next to an existing freezer that cannot structurally
support what would be the common wall). Regardless, if air in the space has no ventilation or
conditioning, moisture in the air will condense onto the cold surface, and can lead to structural
failure of the envelope through corrosion, frost penetration in the cold space, or other forms of
deterioration.
Several methods are available to deal with the moisture. The space could be sealed airtight, with a
dehumidifier inside to maintain a low dew point in the space. This method is preferable in warm and
humid climates. The sealed space could also be heated to ensure the cold surface is always above the
air’s dew point. This is uncommon because of the heat load it transmits to the refrigerated
space.
The most common method used to prevent condensation is continuously ventilating outdoor air into the
interstitial space. This keeps the insulated surface temperature above the interstitial
space’s dew point, thus preventing moisture condensing from the air on the surface.
Roof-mounted exhaust fans and uniformly spaced vents around the perimeter of the plenum are
typically used to ventilate suspended ceilings; similar arrangements can be used for other spaces.
Be certain, though, that fan and inlet louvers are placed to provide good air distribution across
the entire cold surface. The cold surface should also be covered with a vapor retarder attached with
flashing to the wall insulation on the top or warm side. Finally, beware of overventilating the
space: this only reduces the insulation effect of the dead air space.
Suspended ceilings are often designed for light foot traffic for inspection and maintenance of piping
and electrical wiring. Fastening systems for ceiling panels include spline, U channel, and camlock.
To minimize problems with ceiling penetrations during both installation and ongoing maintenance,
wall panel penetrations may be preferable when possible.
If possible, avoid using floor drains, particularly in freezers. If they are necessary, they should
have short, squat dimensions and be placed high enough to allow the drain and piping to be installed
above the insulation envelope.
Electrical wiring should be brought into a refrigerated room through as few locations as possible
(preferably one), piercing the wall vapor retarder and insulation only once. Plastic-coated cable is
recommended for this service where codes allow. If codes require conduit, the last fitting on the
warm side of the run should be explosionproof and sealed to prevent water vapor from entering the
cold conduit. Light fixtures in the room should not be vapor sealed but should allow free passage of
moisture. Take care to maintain the vapor seal between the outside of the electrical service and the
cold-room vapor retarder.
Heat tracing is suggested inside the freezer only from the air-handling unit drain outlet panel to
the insulated wall panel. Heat tracing within the wall could be a possible fire hazard and also
cannot be serviced. If required, drain tracing can continue external to the freezer on a separate
electrical circuit.
Cold-room product suspension tracking, wherever possible, should be erected and supported within the
insulated structure, entirely independent of the building itself. This eliminates flexure of the
roof structure or overhead members and simplifies maintenance.
Doors should be strong yet light enough for easy opening and closing. Hardware should be of good
quality, so that it can be set to compress the gasket uniformly against the casing. All doors to
rooms operating below freezing should be equipped with heaters.
In-fitting doors are not recommended for rooms operating below freezing unless they are provided with
heaters, and they should not be used at temperatures below 0°F with or without
heaters.
See the subsection on Doors in the section on Applying Insulation for more information.
All metal hardware, whether within the construction or exposed to conditions that will rust or
corrode the base metal, should be heavily galvanized, plated, or otherwise protected. It is best to
choose materials not subject to corrosion or rust from exposure to vapor condensation and cleaning
agents used in the facility.
The purpose of the refrigerated facility (e.g., distribution, in-transit storage, or seasonal
storage) dictates the loading dock requirements. Shipping docks and corridors should provide liberal
space for (1) movement of goods to and from storage, (2) storage of pallets and idle equipment, (3)
sorting, and (4) inspecting. The dock should be at least 30 ft wide. Commercial-use
facilities usually require more loading dock space than specialized storage facilities because of
the variety of products handled.
Floor heights of refrigerated vehicles vary widely but are often greater than those of unrefrigerated
vehicles. Rail dock heights and building clearances should be verified by the railroad serving the
plant. A dock height of 54 in. above the rail is typical for refrigerated rail cars.
Three to five railroad car spots per million cubic feet of storage should be planned.
Truck loading dock heights must comply with the requirements of fleet owners and clients, as well as
the requirements of local delivery trucks. Trucks generally require a 54 in. height
above the pavement, although local delivery trucks may be much lower. Some reefer trucks are up to
58 in. above grade. Adjustable ramps at some truck spots will partly compensate for
height variations. If dimensions allow, seven to ten truck spots per million cubic feet
should be provided in a public refrigerated facility.
Many factors affect the load of a refrigerated dock:
-
Dock temperature
-
Outdoor air temperature
-
Temperature of rooms connecting to the dock
-
Frequency and duration of door openings to adjacent rooms and the outer dock doors
-
Efficiency of loading dock door seals
-
Diligence of warehouse staff to promptly close doors when trucks are not loading and
unloading.
Because of these factors, the dock cooling load can vary greatly, so it is recommended that an actual
load calculation should be done according to ASHRAE methodology (see Chapter 24). Cushion-closure seals
around the truck doorways reduce infiltration of outdoor air. Be sure to avoid gaps, particularly
beneath the leveling plate between the truck and the dock. An inflatable or telescoping enclosure
can be extended to seal the space between a railcar and the dock. Insulated doors for docks must be
mounted on the indoor side of walls. The relatively high costs of doors, cushion closures, and
refrigeration influence dock size and number of doors.
The Schneider system, and modifications thereof, is a cold-storage construction and insulation method
primarily used in the western United States, with most of the installations in the Pacific
Northwest. It is an interior/exterior vapor retarder system, as shown in Figure 4. The
structure uses concrete tilt-up walls and either glue-laminated wood beams or bowstring trusses for
the roof. Glass fiber batts coupled with highly efficient vapor retarders and a support framework
are used to insulate the walls and roof. The floor slab construction, insulation, and underfloor
heat are conventional for refrigerated facilities.
The key to success for the Schneider system is an excellent vapor retarder system that is
professionally designed and applied, with special emphasis on the wall/roof junction. Glass fiber
has a high permeability rating and loses its insulating value when wet. It is therefore absolutely
essential that the vapor retarder system perform at high efficiency. Typical wall vapor retarder
materials include aluminum B foil and heavy-gage polyethylene, generously overlapped and adhered to
the wall with a full coating of mastic. The roofing materials act as a vapor retarder for the roof.
The vapor retarder at the wall/roof junction is usually a special aluminum foil assembly installed
to perform efficiently in all weather conditions.
Glass fiber insulation applied to the wall is usually 10 to 12 in. thick for
freezers and 6 to 8 in. for coolers. It is retained by offset wood or fabricated glass
fiber/aluminum sheathed studs on 24 in. centers. Horizontal girts are used at
intervals for bracing. The inside finish is 1 in. thick perforated higher-density glass
fiber panels that can breathe to allow any moisture that passes through the vapor retarder to be
deposited as frost on the evaporator coils.
Glass fiber insulation applied to the roof structure is usually 12 to 14 in. thick for
freezers and 8 to 10 in. for coolers, and is applied between 2 by 12 in. or 2 by
14 in. joists that span the glue-laminated wood beams, purlins, or trusses. The exterior
finish is the same as described for walls. Battens attached to the underside of the joists hold the
finish panels and insulation in place.
Advantages of the Schneider system over insulated panels, assuming equal effectiveness of the vapor
retarder/insulation envelopes over time, include lower first cost for structures over 40,000
ft2, lower operating cost, and fewer interior columns. Disadvantages include a
less clean appearance, unsuitability where washdown is required, impracticality where a number of
smaller rooms are required, and a smaller number of capable practitioners (i.e., architects,
engineers, contractors) available.
Types of Refrigeration Systems
Refrigeration systems can be broadly classified as unitary or applied. In this context, unitary systems are designed by manufacturers, assembled in
factories, and installed in a refrigerated space as prepackaged units. Heat rejection and
compression equipment is either within the same housing as the low-temperature air-cooling coils or
separated from the cooling section. (The latter are commonly called split systems.) In the past,
such units normally used chlorofluorocarbons (CFCs) or hydrochlorofluorocarbons (HCFCs); however,
these refrigerants have been phased out because of their ozone-depletion potential (ODP). Currently,
most installations use hydrofluorocarbon (HFC) refrigerants, although concerns about their global
warming potential (GWP) raise questions about their long-term use.
Applied units are field-engineered and -erected systems
and form the vast majority of large refrigerated (below-freezing) facility systems. Installations
generally have a central machinery room or series of machinery rooms convenient to electrical
distribution services, outdoor service entrance, etc., located as close to the refrigerated space as
possible to reduce piping losses (pressure drop), piping costs, refrigerant charge, and thermal
losses. Essentially made to order, applied systems are generally designed and built from standard
components obtained from one or more suppliers. Key components include compressors, motors, fan-coil
units, receivers, pump circulation systems, controls, refrigerant condensers (evaporative and
shell-and-tube), pressure vessels, valving, and interconnecting piping.
The refrigeration system for a refrigerated facility should be selected in the early stages of
planning. If the facility is a single-purpose, low-temperature storage building, most types of
systems can be used. However, if commodities to be stored require different temperatures and
humidities, a system must be selected that can meet the demands using isolated rooms at different
conditions.
Using factory-built packaged unitary equipment may have merit for the smallest structures and for a
multiroom facility that requires a variety of storage conditions. Conversely, the central compressor
room has been the accepted standard for larger installations, especially where energy conservation
is important.
Direct refrigeration, either a flooded or pumped recirculation system serving fan-coil units, is a
dependable choice for a central compressor room. Refrigeration compressors, programmable logic
controllers, and microprocessor controls complement the central engine room refrigeration equipment.
Refrigerant choice is very important. Typically, ammonia (R-717) has been used extensively in larger
facilities, particularly in the food and beverage industries, but CFC and HCFC refrigerants such as
R-502 or R-22 were also used. Starting in the mid-1990s, some low-temperature facilities used HFC
refrigerants such as R-507A or R-404A, which were non–ozone-depleting alternatives to R-502 or
R-22. More recently, lower-GWP HFC–HFO blend refrigerants have been used, such as R-448A or
R-449A, but these require direct-expansion evaporators. Some facilities are also choosing carbon
dioxide (R-744) instead of a halocarbon refrigerant, particularly in colder climates or when a
larger quantity of high-grade heat is advantageous. Carbon dioxide may be installed in a cascade
arrangement with ammonia or a halocarbon refrigerant on the high side. However, transcritical
installations are now frequently installed instead of a fluorinated refrigerant, and are more
prevalent in cold climates or when a larger quantity of high-grade heat is advantageous. Factors to
consider when choosing refrigerants include
-
Cost
-
Safety code issues, (e.g., code requirements regarding the use of refrigerant in certain
types of occupied spaces)
-
System refrigerant charge requirements [e.g., charges above 10,000 lb
of NH3 may require government-mandated process safety management (PSM) and
risk management plan (RMP)]
-
State and local codes, which may require full- or part-time operators with a specific
level of expertise
-
Effects on global warming and ozone depletion (ammonia has no effect on either)
Cooling loads for refrigerated facilities of the same capacity vary widely. In addition to cooling,
in some instances heating may be required, particularly on docks in cold climates. Many factors,
including building design, indoor and outdoor temperatures, and especially the type and flow of
goods expected and the daily freezing capacity, contribute to the load. Therefore, no simple design
rules apply. Experience from comparable buildings and operations is valuable, but any projected
operation should be analyzed. Compressor and room cooling equipment should be designed for maximum
daily requirements, which will be well above any monthly average.
Load factors to be considered include
-
Heat transmission through insulated enclosures
-
Heat and vapor infiltration load from warm air passing into refrigerated space and
improper air balance
-
Heat from pumps or fans circulating refrigerant or air, power equipment, personnel
working in refrigerated space, product-moving equipment, and lights
-
Heat removed from goods in lowering their temperatures from receiving to storage
temperatures
-
Heat removed in freezing goods received unfrozen
-
Heat produced by respiration of fruits and vegetables
-
Other loads, such as office air conditioning, car precooling, or special operations
inside the building
-
Refrigerated shipping docks
-
Heat released from automatic defrost units by fan motors and defrosting, which increases
overall refrigerant system requirements
-
Blast freezing or process freezing
High humidity, warm temperatures, or manual product handling may dramatically affect design,
particularly that of the refrigeration system.
A summation of the average proportional effect of the load factors is shown in Table
1 as a percentage of total load for a facility in the southern United States. Both the size
and the effect of the load factors are influenced by the facility design, usage, and location.
Heat leakage or transmission load can be calculated using the known overall heat transfer coefficient
of various portions of the insulating envelope, the area of each portion, and the temperature
difference between the lowest cold-room design temperature and highest average air temperature for
three to five consecutive days at the building location. For freezer storage floors on ground, the
average yearly ground temperature should be used.
Heat infiltration load varies greatly with the size of room, number of openings to warm areas,
protection on openings, traffic through openings, and cold and warm air temperatures and humidities.
Calculation should be based on experience, remembering that most of the load usually occurs during
daytime operations. Chapter 24 presents a complete
analysis of refrigeration load calculation.
Heat from goods received for storage can be approximated from the quantity expected daily and the
source. Generally, 10 to 20°F of temperature reduction can be expected, but for
some newly processed items and for fruits and vegetables direct from harvesting,
60°F or more temperature reduction may be required. For general public cold
storage, the load may range from 4 to 8 tons of cooling capacity per million
cubic feet to allow for items received direct from harvest in a producing area.
The freezing load varies from zero for the pure distribution facility, where the product is received
already frozen, to the majority of the total for a warehouse near a producing area. The freezing
load depends on the commodity, temperature at which it is received, and method of freezing. More
refrigeration is required for blast freezing than for still freezing without forced-air circulation.
Heat is produced by many commodities in cooler storage, principally fruits and vegetables. Heat of
respiration is a sizable factor, even at 32°F, and is a continuing load throughout
the storage period. Refrigeration loads should be calculated for maximum expected occupancy of such
commodities.
Manual product handling may add 30 to 50% more load to a facility in tropical areas because of
constant interruption of the cold barriers at doors and on loading docks.
Fan-Coil
Units. These units may have direct-expansion, flooded, or recirculating
liquid evaporators with either finned or wetted coil surfaces. Most installations currently use
finned coils. Storage temperature, packaging method, type of product, etc., must be considered when
selecting a unit. Coil surface area, temperature difference between refrigerant coil and return air,
and volumetric airflow depend on the application. Although not common, wetted-coil surface systems
may be used to circulate a glycol solution over the coil to prevent frost formation on the coil.
Filtration and regeneration equipment are located outside controlled-temperature areas.
Manufacturers claim these units can reduce microbial levels to help protect product from
contamination. The units work well if they are maintained, but can be more expensive to purchase and
operate and require additional room for the regeneration equipment. They do not add defrost heat to
the room, but heat must be added at the regenerator to boil off the collected moisture. These units
can be placed above doorways to remove moisture to help keep infiltration down to tolerable levels.
Failure to maintain units can lead to contamination from dust, odor, and biological pollutants.
Fans are normally of the axial propeller type, but may be centrifugal if a high static discharge loss
is expected. In refrigerated facilities, fan-coil units are usually draw-through (i.e., room air is
drawn through the coil and discharged through the fan). Blow-through units are used in special
applications, such as fruit storages, where refrigerant and air temperatures must be close. Heat
from the motor is absorbed immediately by the coil on a blow-through unit and does not enter the
room. Motor heat must be added to the room load with both draw-through and blow-through units. Figure
6 shows fan-coil units commonly used in refrigerated facility construction.
When selecting fan-coil units, consider the throw, or distance air must travel to cool the farthest
area. Failure to properly consider throw and unit location can result in areas of stagnant air and
hot spots in the refrigerated space (Crawford et al. 1992). Consult manufacturers’
recommendations in all cases. Do not rely on guesses or rules of thumb to select units with proper
airflow. Units vary widely in fan type, design of the diffuser leaving the fan-coil, and coil air
pressure drop. Some installations now vary fan speed to conserve fan energy, so additional care is
needed to ensure that the minimum fan speed used is adequate to still provide the required air throw
and resulting air distribution in the room.
Defrosting.
All fan-coils normally operate below room dew-point conditions. Fan-coils operating below
approximately 38°F will require some defrosting. Common methods of defrost in rooms
36°F and above include
-
Air defrost
-
Hot-gas defrost
-
Electric defrost
-
Water or glycol defrost
Rooms colder than 36°F normally use
-
Hot-gas defrost
-
Electric defrost
Units located above entrances to a refrigerated space tend to draw in warm, moist air from adjacent
spaces and frost the coil quickly. If this occurs, more frequent defrosting is required to maintain
the efficiency of the cooling coil. When the coil approach line crosses into the supersaturated
region, a particularly unfavorable frost almost immediately clogs the coil, very rapidly decreasing
performance (Sherif et al. 2001). Cleland and O’Hagan (2003) developed criteria to estimate
when this will occur, providing a way to avoid this problem through redesign of the coil and/or the
facility (e.g., so the load has a higher sensible heat ratio).
A properly engineered and installed system can be automatically defrosted successfully with hot gas,
desiccant dehumidifier, water, or electric heat.
Condensate Drains. When coils defrost, condensate that has
formed as ice or frost on the coils melts. This new condensate collects in a pan beneath the coil
and flows into collection drains outside of the freezer space. Because the space is cold, condensate
pans are connected to the hot-gas defrost system or otherwise heated to prevent ice formation.
Likewise, all condensate drain lines must be wrapped in heat-tracing tape and trapped outside of the
refrigerated space to ensure that condensate can drain unrestricted.
Valve
Selection. Refer to Chapter 11 and
manufacturers’ literature for specific information on control valve type and selection
(sizing).
Valving Arrangements. Proper refrigerant feed valve, block
valve, and defrosting valve arrangements are critical to the performance of all fan-coil units.
Various valve piping schemes are used. See Chapter 2 for typical piping
arrangements.
Valve Location. Good valve location ensures convenient
maintenance of control and service block valves. The owner/designer has some options in most plants.
If penthouse units are used, all valves are generally located outside the penthouse and are
accessible from the roof. Fan-coil units mounted in the refrigerated space are generally hung from
the ceiling and must be accessed via personnel lift cage on a forklift or other service vehicle. It
is recommended that valve stations be located outside the freezer storage area if possible to ensure
that refrigerant leaks do not enter storage areas and also to facilitate maintenance.
System Considerations. For refrigerated temperatures below
–25°F, the allowable compression limits of the compressor must be considered.
With ammonia, either single-stage economized or two-stage compression is used, whereas HFC systems
commonly use single-stage uneconomized. Compound compressors with capacity control on each stage may
be used. For variable loads, separate high- and low-stage (or booster) compressors, each with
capacity control or of different capacities, may provide better operation. Depending on the degree
of capacity redundancy desired, two or more compressors can be selected at each suction temperature
level. This also allows shutting one or more compressors down during colder months when load is
reduced. Redundancy can also be provided on many systems by cross-connecting the piping such that a
nonoperating high-stage compressor can also be run as a temporary low-stage single-stage compressor
in case a booster compressor is down. Other combinations of cross connection are possible. If blast
freezers are included, pipe connections should be arranged so that sufficient booster capacity for
the blast freezers can be provided by the low-stage suction pressure compressor, while the other
booster is at higher suction pressure for the freezer room load. Interstage pressure and
temperatures are usually selected to provide refrigeration for loading dock cooling and for rooms
above 32°F.
In a two-stage system, liquid refrigerant should be precooled at the high-stage suction pressure
(interstage) to reduce the low-stage load. For systems operating with a subatmospheric low-side
pressure, an automatic purger to remove air and other noncondensable gases is essential.
Almost all compressors used in the refrigeration industry for facility designs use oil for
lubrication. The compressor should have a good discharge oil separator, but these compressors will
still pass some oil on to the condenser and the low side of the system. Both halocarbon and ammonia
plants should have ways recover oil from all low-side vessels and heat exchangers where oil tends to
accumulate. This includes low-pressure receivers, suction accumulators, pumper drums, shell-and-tube
evaporators, surge tanks on gravity recirculation systems, intercoolers, subcoolers, and
economizers. Oil recovery methods are different for halocarbons and ammonia. With ammonia systems,
oil is usually recovered manually and then discarded; however, some systems now use automatic oil
return. With halocarbon systems, oil can be recovered manually or is automatically usually reused in
the system. See Chapters 1 to
4, 6, 7,
12, and 13 in this volume
for more information. Oil logs should be kept to record the amounts of oil added to and removed from
the system.
Use of commercial, air-cooled condenser, packaged halocarbon refrigerant, or factory preassembled
units is common, especially in smaller facilities. These units have lower initial cost, smaller
space requirements, and no need for a special machinery room. However, they use more energy, have
higher operating and maintenance costs, and have a shorter life expectancy for components (usually
compressors) than central refrigeration systems.
Multiple
Installations. To distribute air without ductwork, installations of multiple
fan-coil units have been used. For single-story buildings, air-handling units installed in
penthouses with ducted or nonducted air distribution arrangements have been used to make full use of
floor space in the storage area (Figure 7). Either prefabricated units or
fan-coil units connected to a central plant can be incorporated in penthouse design.
When units are located in a penthouse, the distributing ductwork is projected through the penthouse
floor into the refrigerated space below. Return air passes up through the penthouse floor grille.
This system avoids the interference of fan-coil units hung below the ceiling in the refrigerated
space, and makes maintenance access easier.
Condensate drain piping typically passes through the penthouse insulated walls and onto the main
storage roof. Refrigerant mains and electrical conduit can be run over the roof on suitable supports
to the central compressor room or to packaged refrigeration units on the adjacent roof. For
convenience, controls and other electrical equipment may be housed in the penthouse.
A personnel access door to the penthouse is required for convenient equipment service. The inside
insulated penthouse walls and ceiling must be vaportight to keep condensation from deteriorating the
insulation and to maintain the integrity of the building vapor retarder. Some primary advantages of
penthouses are
-
Cooling units, catwalks, and piping do not interfere with product storage space and are
not subject to physical damage from stacking truck operations.
-
Service to all cooling equipment and controls can be handled by one individual from a
grated floor or roof deck location.
-
Maintenance and service costs are minimized.
-
Main piping, control devices, and block valves are typically located outside the
refrigerated space for easier service.
-
When control and block valves are located outside the penthouse, the risk of refrigerant
leaks inside the refrigerated space is greatly reduced.
Freezers within refrigerated facilities are generally
used to freeze products or to chill products from some higher temperature to storage temperature.
Failure to properly cool the incoming product transfers the product cooldown load to the facility,
greatly increasing facility operating costs. Of perhaps greater concern is that dormant storage in a
cold area may not cool the product fast enough to prevent bacterial growth, which causes product
deterioration. In addition, other stored, already frozen products may be affected by localized
warming.
For this reason, many refrigerated facilities have a blast freezer that producers
can contract to use. Blast freezing ensures that the products are properly frozen in minimum time
before they are put into storage and that their quality is maintained. Modern control systems can
allow sampling of inner core product temperatures and printout of records that customers may
require. The cost of blast freezer service can be properly apportioned to its users, allowing higher
efficiency and lower cost for other cold-storage customers.
Although there are many types of freezers, including belt, tray, contact plate, spiral, and other
packaged types, the most common arrangement used in refrigerated facilities is designed to accept
pallets of products from a forklift. The freezing area is large and free from obstructions, and has
large doors. See Chapter 29 for more
information on freezing systems.
Figure 8 shows a typical batch-style blast
freezer used in a refrigerated facility. Air temperatures are normally about
–30°F, but may be higher or lower, depending upon the product being frozen.
Once the room is filled to design capacity, it is sealed and the system is started. The
refrigeration process time can be controlled by a time clock, by manual termination, or by measuring
internal product temperature and stopping the process once the control temperature is reached. The
last method gives optimum performance. Once the product is frozen, the pallets are transferred to
general refrigerated storage areas.
Because the blast freezer normally operates intermittently, freezer owners may choose to operate it
when energy cost is lowest. Unfortunately, food products must be frozen as quickly as possible, and
products are usually delivered during times of peak electrical rates. Depending on the availability
of electricity, alternative power sources such as natural gas engines or diesel drives have been
used. Although these normally have first cost and maintenance cost premiums, they are not subject to
time-varying energy rates and may offer savings.
Defrost techniques for blast freezers are similar to normal defrost methods for refrigerated facility
fan-coil units. Coils can often be defrosted after the product cooling cycle is completed or while
the freezer is being emptied for the next load.
Pumped refrigerant recycling systems and flooded surge drum coils have both been used with success.
Direct-expansion coils may be used, but the designer should be careful with expansion valve systems
to address coil circuitry, refrigerant liquid overfeed, oil return, defrost, shutdown liquid
inventory management, and so forth. Oil removal must be considered on flooded coil systems, because
the blast freezer is normally the lowest-temperature system in the facility and may accumulate oil
over time. Construction materials for systems operating below –20°F and
subject to ASME code conformance should comply with the latest ASME Standard B31.5. See Chapter 49
for further information on low-temperature materials. Floor heating may be convenient if products
are damp or wet during loading.
Most blast freezers are accessed from a refrigerated space, so that products can be moved directly
from the freezer to storage racks. Also, blast freezers can be used for storage when not operating.
The term controls refers to any mechanism or device used to start, stop,
adjust, protect, or monitor the operation of a moving or functional piece of equipment. Controls for
any system can be as simple as electromechanical devices such as pressure switches and timer relays
or as complex as a complete digital control system with analog sensors and a high-speed
communications network connected to a supervisory computer station. Because controls are required in
every industry, there is a wide variety from which to choose. In recent years, the industrial
refrigeration industry has moved away from the use of electromechanical devices and toward the use
of specialized microprocessors and programmable logic controllers for unit and system control.
Electromechanical devices for control will continue to be used for some time and may never be
replaced entirely for some critical control functions (e.g., use of relays for electrical high
current isolation and float switches for refrigerant high-level shutdowns). See Chapter 11 for more information.
Microprocessor controls and electronic sensors generally offer the following advantages over
electromechanical control:
-
More accurate readings and therefore more accurate control
-
Easier operation
-
Greater flexibility through adjustable set points and operating parameters
-
More sophisticated control sequencing (e.g., varying sequencing of defrosts or
compressor, depending on loading)
-
More information concerning operating conditions, alarms, failures, and troubleshooting
-
Capability for interfacing with remote operator stations
There are four main areas of control in all refrigerated facility systems with a central compressor
room:
-
Compressor package control. Minimum
requirements: orderly start-up, orderly shutdown, capacity control to maintain suction
pressure, alarm monitoring, and safety shutdown.
-
Condenser control. Minimum requirements: fan
and water pump start and stop to maintain a reasonable constant or floating refrigerant
discharge pressure.
-
Evaporator control. Minimum requirements:
control of air unit fans and refrigerant liquid feed to maintain room air temperatures
and staging of air unit refrigerant valve stations to provide automatic coil defrosts.
-
Refrigerant flow management. Minimum
requirements: maintenance of desired refrigerant levels in vessels, control of valves
and pumps to transfer refrigerant as needed between vessels and air units in the system,
and proper shutdowns in the event of refrigerant overfeed or underfeed.
Other areas of control, such as refrigerant leak detection and alarm, sequencing of multiple
compressors for energy efficiency, and underfloor freeze protection, may be desired.
Because of the wide variety and fast-changing capabilities of control components and systems
available, it is impossible to define or recommend an absolute component list. However, it is
possible to provide guidelines for the design and layout of the overall control system, regardless
of the components used or the functions to be controlled. This design or general layout can be
termed a control system architecture.
All control systems consist of four main building blocks:
-
Controller(s): Microprocessor with control
software
-
Input/outputs (I/Os): Means of connecting
devices or measurements to the controller
-
Operator interface(s): Means of conveying
information from the controller to a human being [often called man/machine interface
(MMI) or human/machine interface (HMI)]
-
Interconnecting media: Means of transferring
information between controllers, I/Os, and operator interfaces
The control system architecture defines the quantity, location, and function of these basic
components. The architecture determines the reliability, expandability, operator interface
opportunities, component costs, and installation costs of a control system. Therefore, the
architecture should be designed before any controls component manufacturers or vendors are selected.
The following are the basic steps in designing a refrigerated facility control system:
Step 1. Define the control tasks. This step should provide
a complete and detailed I/O listing, including quantity and type. With this list and a little
experience and knowledge of available hardware, the type, quantity, and processing power of the
necessary controllers can be determined.
Step 2. Determine physical locations of controlled devices
and measurements to be taken. If remote I/Os or multiple controllers are located close to the
devices and sensors, field wiring installation costs can be reduced. To avoid extra costs or
impracticalities, the environments of the various locations must be compared with the environmental
specifications of the hardware to be placed in them. Maintenance requirements can also affect the
selection of physical location of the I/Os and controller.
Step 3. Determine control task integration requirements.
Control tasks that require and share the same information (e.g., a discharge pressure reading for
starting both a condenser fan and a condenser water pump) must be accomplished either with the same
controller or with multiple controllers that share information via interconnecting media. Tasks that
do not share information can be performed by separate controllers. Using multiple controllers
minimizes the chance of catastrophic control failures. With multiple controllers that share
information, the interconnecting media must be robust, with minimal chance of failure for critical
tasks. In particular, the speed of data transfer between controllers must be suitable to maintain
the control accuracy required.
Step 4. Determine operator interface requirements. This
includes noting which controllers must have a local or remote interface, how many remote interface
stations are required, and defining the hardware and software requirements of the interfaces.
Step 5. Select the interconnecting media between
controllers and their remote I/Os, between different controllers, and between controllers and
operator interfaces. The interconnecting medium to remote I/Os is typically defined by the
controller manufacturer; it must be robust and high-speed, because controllers’ decisions
depend on real-time data. The interconnecting medium between controllers themselves is also
typically defined by the controller manufacturer; speed requirements depend on the tasks being
performed with the shared information. For media connecting controllers and operator interfaces,
speed is typically not as critical because the control continues even if the connection fails. For
the operator interface connection, speed of accessing a controller’s data is not as critical
as having access to all the available data from the controller.
Step 6. Evaluate the architecture for technical merit. The
first five steps should produce a list of controllers, their locations, their operator interfaces,
and their control tasks. Once the list is complete, the selected controllers should be evaluated for
both processor memory available for programming and processor I/O capacity available for current and
future requirements. The selected interconnecting media should be evaluated for distance and speed
limitations. If any weaknesses are found, a different model, type, or even manufacturer of the
component should be selected.
Step 7. Evaluate the architecture for software
availability. The best microprocessor is of little good if no software exists to make it operate. It
must be ascertained that software exists or can easily be written to provide (1) information
transfer between controllers and operator interfaces; (2) the programming functions needed to
perform the control tasks; and (3) desired operator interface capabilities such as graphics,
historical data, reports, and alarm management. Untested or proprietary software should be avoided.
Step 8. Evaluate the architecture for failure conditions.
Determine how the system will operate with a failure of each controller. If the failure of a
particular controller would be catastrophic, more controllers can be used to further distribute the
control tasks, or electromechanical components can be added to allow manual completion of the tasks.
For complex tasks that are impossible to control manually, it is essential that spare or back-up
control hardware be in stock and that operators be trained in troubleshooting and reinstallation of
control hardware and software.
Step 9. Evaluate the proposed architecture for cost,
including field wiring, components, start-up, training, downtime, and maintenance costs. All these
costs must be considered together for a fair and proper evaluation. If budgets are exceeded, then
steps 1 to 8 must be repeated, removing any nonessential control tasks and reducing the quantity of
controllers, I/Os, and operator interfaces.
Once the control system architecture is designed, specifics of software operation should be
determined. This includes items such as set points necessary for a control task, control algorithms
and calculations used to determine output responses, graphic screen layouts, report layouts, alarm
message wording, and so forth. More detail is necessary, but excessive time spent determining the
details of software operation may be better applied to further definition and refinement of the
system architecture. If the system architecture is solid, the software can always be modified as
needed. With improper architecture, functional additions or corrections can be costly, time
consuming, and sometimes impossible.
For more information on controls and their design and application, see Chapter 7 of the 2025 ASHRAE Handbook—Fundamentals and Chapters 42 and 47 of the 2023
ASHRAE Handbook—HVAC Applications.
The two main functions of an insulation envelope are to
reduce the refrigeration requirements for the refrigerated space and to prevent condensation. See Chapter 10 for further
information.
The primary concern in the design of a low-temperature facility is the vapor retarder system, which
should be as close to 100% effective as is practical. The success or failure of an insulation
envelope is due entirely to the effectiveness of the vapor retarder system in preventing water vapor
transmission into and through the insulation.
The driving force behind water vapor transmission is the difference in vapor pressure across the
vapor retarder. Once water vapor passes a vapor retarder, a series of detrimental events begins.
Water migrating into the insulation may condense or solidify, which diminishes the thermal
resistance of the insulation and eventually destroys the envelope. Ice formation inside the envelope
system usually grows and physically forces the building elements apart to the point of failure.
Another practical function of the vapor retarder is to stop air infiltration, which can be driven by
a higher vapor pressure in the air outside the refrigerated space, or a pressure variation in the
space.
After condensing or freezing, some water vapor in the insulation revaporizes or sublimes and is
eventually drawn to the refrigeration coil and disposed of by the condensate drain, but the amount
removed is usually not sufficient to dry out the insulation unless the vapor retarder break is
located and corrected.
The vapor retarder must be located on the warm side of the insulation. Each building element inside
the prime retarder must be more permeable than the last to allow moisture to move through it, or it
becomes a site of condensation or ice. This precept is abandoned for the sake of sanitation at the
inside faces of coolers. However, the inside faces of freezers are usually allowed to breathe by
leaving the joints uncaulked in panel construction, or by using less permeable surfaces for other
forms of construction. Factory-assembled insulation panels endure this double vapor retarder problem
better than other types of construction.
In walls with insufficient insulation, the temperature at the inside wall surface may, during certain
periods, reach the dew point of the migrating water vapor, causing condensation and freezing. This
can also happen to a wall that originally had adequate insulation but, through condensation or ice
formation in the insulation, lost part of its insulating value. In either case, ice deposited on the
wall gradually pushes the insulation and protective covering away from the wall until the insulation
structure collapses.
It is extremely important to properly install vapor retarders and seal joints in the vapor retarder
material to ensure continuity from one surface to another (i.e., wall to roof, wall to floor, or
wall to ceiling). Failure of vapor retarder systems for refrigerated facilities is almost always
caused by poor installation. The contractor must be experienced in installation of vapor retarder
systems to be able to execute a vaportight system.
Condensation on the inside of the cooler is unacceptable because (1) the wet surface provides a
culture base for bacterial growth, and (2) any dripping onto the product gives cause for
condemnation of the product in part or in whole.
Stagnant or dead air spots behind beams or inside metal roof decks can allow localized condensation.
This moisture can be from within the cooler or freezer (i.e., not necessarily from a vapor retarder
leak).
No vapor retarder system is 100% effective. A system is successful when the rate of moisture
infiltration equals the rate of moisture removal by refrigeration, with no detectable condensation.
Rigid Insulation. Insulation materials, such as
polystyrene, polyisocyanurate, polyurethane, and phenolic material, have proven satisfactory when
installed with the proper vapor retarder and finished with materials that provide fire protection
and a sanitary surface. Selection of the proper insulation material should be based primarily on the
economics of the installed insulation, including the finish, sanitation, and fire protection.
Panel Insulation. Use of prefabricated insulated panels
for insulated wall and roof construction is widely accepted. These panels can be assembled around
the building structural frame or against masonry or precast walls. Panels can be insulated at the
factory with either polystyrene or urethane. Other insulation materials do not lend themselves to
panelized construction.
The basic advantage, besides economics, of using insulated panel construction is that repair and
maintenance are simplified because the outer skin also serves as the vapor retarder and is
accessible. This is of great benefit if the structure is to be enlarged in the future. Proper vapor
retarder tie-ins then become practical.
Foam-in-Place Insulation. This application method has
gained acceptance as a result of developments in polyurethane insulation and equipment for
installation. Portable blending machines with a spray or frothing nozzles feed insulation into the
wall, floor, or ceiling cavities to fill without joints the space provided for monolithic insulation
construction. This material does not provide significant vapor resistance; its application in floor
construction should be limited.
Precast Concrete Insulation Panels. This specialized form
of construction has been successful when proper vapor retarder and other specialized elements are
incorporated. As always, vapor retarder continuity is the key to a successful installation.
The R-value of insulation required varies with the temperature held in the refrigerated space and the
conditions surrounding the room. Table 2 shows recommended R-values
for different types of facilities. The range in R-values is due to variations in energy cost,
insulation materials, and climatic conditions. For more exact values, consult a designer and/or
insulation supplier. Insulation with R-values lower than those shown should not be used.
The method and materials used to insulate roofs, ceilings, walls, floors, and doors need careful
consideration.
The suspended ceiling method of construction is preferred for attaining a complete thermal and vapor
envelope. Insulating materials may be placed on the roof or floor above the refrigerated space
rather than adhered to the structural ceiling. If this type of construction is not feasible, and the
insulation must be installed under a concrete or other ceiling, then the vapor retarder, insulation,
and finish materials should be mechanically supported from the structure above rather than relying
on adhesive application only. Suspending a wood or metal deck from the roof structure and applying
insulation and a vapor retarder to the top of the deck is another method of hanging ceiling
insulation. Skillful application and attention to positive air and vapor seals are essential to
continued effectiveness.
Suspended insulated ceilings, whether built-up or prefabricated, should be adequately ventilated to
maintain near-ambient conditions in the plenum space; this minimizes both condensation and
deterioration of vapor retarder materials (see the section on Suspended Ceilings). Permanent sealing
is needed around insulating hanger rods, columns, conduit, and other penetrations.
The structural designer usually includes roofing expansion joints when installing insulation on top
of metal decking or concrete structural slabs for a building larger than 100 by 100 ft.
Because the refrigerated space is not normally subject to temperature variations, structural framing
is usually designed without expansion or contraction joints if it is entirely enclosed within the
insulation envelope. Board insulation laid on metal decking should be installed in two or more
layers with the seams staggered. An examination of the coefficients of linear expansion for typical
roof construction materials shows the need for careful attention to this phase of the building
design.
Although asphalt built-up roofs have been used, loosely laid membrane roofing has become popular and
requires little maintenance.
Wall construction must be designed so that as few structural members as possible penetrate the
insulation envelope. Insulated panels applied to the outside of the structural frame prevent
conduction through the framing. Where masonry or concrete wall construction is used, structural
framing must be independent of the exterior wall. The exterior wall cannot be used as a bearing wall
unless a suspended insulated ceiling is used.
Where interior insulated partitions are required, a double-column arrangement at the partition
prevents structural members from penetrating the wall insulation. For satisfactory operation and
long life of the insulation structure, envelope construction should be used wherever possible.
Governing codes for fire prevention and sanitation must be followed in selecting a finish or panel.
For conventional insulation materials other than prefabricated panels, a vapor retarder system
should be selected.
Abrasion-resistant membranes, such as 10 mil thick black polyethylene film with a
minimum of joints, are suitable vapor retarders. Rigid insulation can then be installed dry and
finished with plaster or sheet finishes, as the specific facility requires. In refrigerated
facilities, contraction of the interior finish is of more concern than expansion because
temperatures are usually held far below installation ambient temperatures.
Freezer buildings have been constructed without floor insulation, and some operate without
difficulty. However, the possibility of failure is so great that this practice is seldom
recommended.
Underfloor ice formation, which causes heaving of floors and columns, can be prevented by heating the
soil or fill under the insulation. Heating can be by air ducts, electric heating elements, or pipes
through which a liquid is recirculated (see the section on Floor Construction).
The air duct system works well for smaller storages. For a larger storage, it should be supplemented
with fans and a source of heat if the pipe is more than 100 ft long. End openings
should be screened to keep out rodents, insects, and any material that might close off the air
passages. Ducts must be sloped for drainage to remove condensed moisture. Perforated pipes should
not be used.
The electrical system is simple to install and maintain if the heating elements are run in conduit or
pipe so they can be replaced; however, operating costs may be very high. Adequate insulation should
be used because it directly influences energy consumption.
The pipe grid system, shown in Figure
9, is usually best because it can be designed and installed to warm where needed and can
later be regulated to suit varying conditions. Extensions of this system can be placed in vestibules
and corridors to reduce ice and wetness on floors. The underfloor pipe grid also facilitates future
expansion. A heat exchanger in the refrigeration system, steam, or gas engine exhaust can provide a
source of heat for this system. The temperature of the recirculated fluid is controlled at 50
to 70°F, depending on design requirements. Almost universally, the pipes are made of
plastic.
The pipe grid system is usually placed in the base concrete slab directly under the insulation. If
the pipe is metal, a vapor retarder should be placed below the pipe to prevent corrosion. The fluid
should be an antifreeze solution such as propylene glycol with the proper corrosion inhibitor.
The amount of warming for any system can be calculated and is about the same for medium-sized and
large refrigerated spaces regardless of ambient conditions. For simplicity, it is generally assumed
that any heat gain from the deeper or adjacent soil around the building is negligible. The
calculated heat input is then simply the heat transfer through the floor insulation based on the
temperature difference between the underfloor ground temperature (typically about
40°F) and the room temperature (e.g., a 50°F temperature
difference for a –10°F storage room). Be sure to allow for a safety factor,
because the R-value of the insulation will degrade somewhat if there is moisture absorption from the
subsoil and the heating system may not always be available to provide heat.
An important factor in warehouse productivity is maintaining safe working conditions at doorways in
high-usage freezers. At doorways, infiltration air mixes with air inside the freezer, forming
airborne ice crystals. These crystals can accumulate on walls, ceilings, and nearby appurtenances,
and can cause icy conditions on the floor. Consequences include danger to pedestrians, damage from
skidding vehicles, premature frost clogging of nearby evaporators, and decreased productivity.
A freezer vestibule is any small room or airlock device
with properly designed air curtains that impose little restriction on traffic flow but still counter
adverse effects by reducing outdoor air infiltration.
Electrically heated traffic doors effectively eliminate doorway frost and ice.
Whether freezer vestibules or electrically heated doors are used, to calculate loads properly, see
the section on Infiltration Air Load in Chapter 24 for door-open time per
doorway pass-through and for time required to reach fully established flow upon each door opening.
Selection and application of cold-storage doors are a fundamental part of cold-storage facility
design and have a strong bearing on the overall economy of facility operation. The trend is to have
fewer and better doors. Manufacturers offer many types of doors supplied with the proper thickness
of insulation for the intended use. Four basic types of doors are swinging, horizontal sliding,
vertical sliding, and double-acting. Door manufacturers’ catalogs give detailed illustrations
of each. Doors used only for personnel cause few problems. In general, a standard swinging personnel
door, 3 ft wide by 6.5 ft high and designed for the temperature and
humidity involved, is adequate.
The proper door for heavy traffic areas should provide maximum traffic capacity with minimum loss of
refrigeration and require minimum maintenance.
When selecting cold storage doors, consider the following factors:
-
Automatic doors are a primary requirement with forklift and automatic conveyor
material-handling systems.
-
Careless forklift operators are a hazard to door operation and effectiveness. Guards can
be installed but are effective only when the door is open. Photoelectric and ultrasonic
beams across the doorway or proximity loop control on both sides of the doorway can
provide additional protection by monitoring objects in the door openings or approaches.
These systems can also control door opening and closing.
-
Selection of automatic door systems to suit traffic requirements and building structure
may require experienced technical guidance.
-
To ensure continuous door performance, the work area near the doors must be supervised,
and the doors must have planned maintenance.
-
Cooled or refrigerated shipping platforms increase door efficiency and reduce door
maintenance, because the humidity and temperature difference across the doorway is
lower. Icing of the door is lessened, and fogging in traffic ways is reduced.
Biparting and Other Doors. Air curtains, plastic or rubber
strip curtains, and biparting doors give varied effectiveness. Strip curtains are not accepted by
USDA standards if open product moves through the doorway. Often, the curtain seems to the forklift
driver to be a substitute for the door, so the door is left open with a concurrent loss of
refrigerated air. Quick-operating powered doors of fabric or rigid plastic are beneficial for draft
control.
Swinging and Sliding Doors. A door with hinges on the
right edge (when observed from the side on which the operating hardware is mounted) is called a
right-hand swing. A door that slides to the right to open (when observed from the side of the wall
on which it is mounted) is called a right-slide door.
Vertical Sliding Doors. These doors, which are hand- or
motor-operated with counterbalanced springs or weights, are used on truck receiving and shipping
docks.
Refrigerated-Room Doors. Doors for pallet material
handling are usually automatic horizontal sliding doors, either single-slide or biparting.
Metal or Plastic Cladding. Light metal cladding or a
reinforced plastic skin protects most doors. Areas of abuse must be further protected by heavy
metal, either partial or full height.
Heat. To prevent ice formation and resultant faulty door
operation, doors are available with automatic electric heat, not only in the sides, head, and sill
of the door or door frame, but also in switches and cover hoods of power-operated units. Such
heating elements are necessary on all four edges of double-acting doors in low-temperature rooms.
Safe devices that meet electrical codes must be used.
Bumpers and Guard Posts. Power-operated doors require
protection from abuse. Bumpers embedded in the floor on both sides of the wall and on each side of
the passageway help preserve the life of the door. Correctly placed guard posts protect sliding
doors from traffic damage.
Buck and Anchorage. Effective door operation is impossible
without good buck and anchorage provisions. Recommendations of the door manufacturers should be
coordinated with wall construction.
Door Location. Doors should be located to accommodate safe
and economical material handling. Irregular aisles and blind spots in trafficways near doors should
be avoided.
Door Size. A hinged insulated door opening should provide
at least 1 ft clearance on both sides of a pallet. Thus, 6 ft should be
the minimum door width for a 4 ft wide pallet load. Double-acting doors should be
8 ft wide. Specific conditions at a particular doorway can require variations from this
recommendation. A standard height of 10 ft accommodates all high-stacking forklifts.
Sill. A concrete sill minimizes the rise at the door sill.
A thermal break should be provided in the floor slab at or near the plane of the front of the wall.
Power Doors. Horizontal sliding doors are standard when
electric operation is provided. The two-leaf biparting unit keeps opening and closing time to a
minimum, and the door is out of the way and protected from damage when open. Also, because leading
edges of both leaves have safety edges, personnel, doors, trucks, and product are protected. A pull
cord is used for opening, and a time-delay relay, proximity-loop control, or photoelectric cell
controls closing. Potential for major door damage may be reduced by proper location of pull-cord
switches. Doors must be protected from moisture and frost with heat or baffles. Preferably,
low-moisture air should be introduced near door areas. Automatic doors should have a preventive
maintenance program to check gaskets, door alignment, electrical switches, safety edges, and heating
circuits. Safety releases on locking devices are necessary to prevent entrapment of personnel.
Fire-Rated Doors. Available in both swinging and sliding
types, fire-rated doors are also insulated. Refrigerated buildings have increased in size, and their
contents have increased in value, so insurance companies and fire authorities are requiring fire
walls and doors.
Large Door Openings. Door openings that can accommodate
forklifts with high masts, two-pallet-high loads, and tractor-drawn trailers are large enough to
cause appreciable loss of refrigeration. Infiltration of moisture is objectionable because it forms
as condensate or frost on stacked merchandise and within the building structure. Door heights up to
10 or 12 ft are frequently required, especially where drive-through racks are used.
Refrigeration loss and infiltration of moisture can be particularly serious when doors are located
in opposite walls of a refrigerated space and cross flow of air is possible. It is important to
reduce infiltration with enclosed refrigerated loading docks and, in some instances, with one-way
traffic vestibules.
Because of the low temperatures in freezer facilities, contraction of structural members in these
spaces will be substantially greater than in any surrounding ambient or cooler facilities.
Therefore, contraction joints must be properly designed to prevent structural damage during facility
pulldown.
The first stage of temperature reduction should be from ambient down to 35°F at
whatever rate of reduction the refrigeration system can achieve.
The room should then be held at that temperature until it is dry. Finishes are especially subject to
damage when temperatures are lowered too rapidly. Portland cement plaster should be fully cured
before the room is refrigerated.
If there is a possibility that the room is airtight (most likely for small rooms, 20 by 20
ft maximum), swinging doors should be partially open during pulldown to relieve the
internal vacuum caused by the cooling of the air, or vents should be provided. Permanent air relief
vents are needed for continual operation of defrosts in small rooms with only swinging doors. Both
conditions of possible air heating during defrost and cooling should be considered in design of air
vents and reliefs.
The concrete slab will contract during pulldown, causing slab/wall joints, contraction joints, and
other construction joints to open. At the end of the holding period (i.e., at
35°F), any necessary caulking should be done.
An average time for drying is 72 h. However, indicators that may be used include watching the rate of
frost formation on the coils or measuring the rate of moisture removal by capturing the condensation
during defrost.
After the refrigerated room is dry, the temperature can then be reduced again at whatever rate the
refrigeration equipment can achieve until the operating temperature is reached. Rates of
10°F per day have been used in the past, but if care has been taken to remove all
the construction moisture in the previous steps, faster rates are possible without damage.
Material-Handling Equipment
Both private and public refrigerated facilities can house high-volume, year-round operations with
fast-moving order pick areas backed by in-transit bulk storage. Distribution facilities may carry
300 to 3000 items or as many as 30, 000 lots. Palletized loads stored either in
bulk or on racks are transported by forklifts or high-rise storage/retrieval machines in a 0
to –20°F environment. Standard battery-driven forklifts that can lift up to
25 ft can service one-deep, two-deep reach-in, drive-in, drive-through, or gravity flow
storage racks. Special forklifts can lift up to 60 ft.
Automated storage/retrieval machines make better use of storage volume, require fewer personnel, and
reduce the refrigeration load because the facility requires less roof and floor area. This equipment
operates in a height range of 23 to 100 ft to service one-deep, two-deep reach-in, two-
to twelve-deep roll pin, or gravity flow pallet storage racks. Computers and bar code identification
allow a system to automatically control the retrieval, transfer, and delivery of products. In
addition, these systems can record product location and inventory and load several delivery trucks
simultaneously from one order pick conveyor and sorting device.
A refrigerated plant may have two or more material-handling systems if the storage area contains
fast- and slow-moving reserve storage, plus slow-moving order pick. Fast-moving items may be
delivered and order-picked by a conventional forklift pallet operation with up to 30 ft
stacking heights. In the fast-moving order pick section, the storage room internal height is raised
to accommodate storage/retrieval machines; reserve pallet storage; order pick slots; multilevel
palletizing; and the infeed, discharge, and order pick conveyors. Mezzanines may be considered to
provide maximum access to the order pick slots. Intermediate-level fire protection sprinklers may be
required in the high rack or mezzanine areas above 14 ft high.
Ordinary wet sprinkler systems can be applied to refrigerated spaces above freezing. In rooms below
freezing, entering water freezes if a sprinkler head malfunctions or is mechanically damaged. If
this occurs, the affected piping must be removed. In lower-temperature spaces, a dry air or
nitrogen-charged system should be selected.
Designing a dry sprinkler system operating in areas below 32°F requires special
knowledge and should not be undertaken without expert guidance. Freezer storage with rack storages
30 ft high or higher may require special design, and the initial design should be shown
to the insuring company.
Local regulations may require ceiling isolation smoke curtains and smoke vents near the roof in large
refrigerated spaces. These features allow smoke to escape and help firefighters locate the fire. If
the building does not have a sprinkler system, central reporting or warning systems are available
for hazardous areas.
Inspection and Maintenance
Buildings dimensions can change because of settling, temperature change, and other factors; thus,
cold-storage facilities should be inspected regularly to spot problems early, so that preventive
maintenance can be performed in time to avert serious damage.
Inspection and maintenance procedures fall into two areas: basic system (floor, wall, and
roof/ceiling systems); and apertures (doors, frames, and other access to cold storage rooms).
Basic System
-
Stack pallets at a sufficient distance (18 in.) from walls or ceiling to
permit air circulation.
-
Examine walls and ceiling at random every month for frost build-up. If build-up persists,
locate the break in the vapor retarder.
-
For insulated ceilings below a plenum, inspect the plenum areas for possible roof leaks
or condensation.
-
If condensation or leaks are detected, make repairs immediately.
Apertures
-
Remind personnel to close doors quickly to reduce frosting in rooms.
-
Check the rollers and door travel periodically to ensure that the seal at the door edge
is effective. If leaks are detected, adjust the door to restore a moisture- and airtight
condition.
-
Check doors and door edges to detect damage from forklifts or other traffic. Repair any
damage immediately to prevent door icing or motor overload caused by excessive friction.
-
Lubricate doors according to the maintenance schedule from the door manufacturer to
ensure free movement and complete closure.
-
Periodically check seals around openings for ducts, piping, and wiring in the walls and
ceiling.
Aldrich, D.F., and R.H. Bond. 1985. Thermal performance
of rigid cellular foam insulation at subfreezing temperatures. In Thermal
performance of the exterior envelopes of buildings III, pp. 500-509. ASHRAE.
Baird, C.D., J.J. Gaffney, and M.T. Talbot. 1988. Design
criteria for efficient and cost effective forced air cooling systems for fruits and vegetables.
ASHRAE Transactions 94(1):1434-1454.
Ballou, D.F. 1981. A case history of a frost heaved
freezer floor. ASHRAE Transactions 87(2):1099-1105.
Beatty, K.O., E.B. Birch, and E.M. Schoenborn. 1951.
Heat transfer from humid air to metal under frosting conditions. Journal of
the ASRE (December):1203-1207.
Becker, B., and B. Fricke. 2005. Design essentials for refrigerated storage facilities. ASHRAE.
Cole, R.A. 1989. Refrigeration load in a freezer due to
hot gas defrost and their associated costs. ASHRAE Transactions
95(2):1149-1154.
Coleman, R.V. 1983. Doors for high rise refrigerated
storage. ASHRAE Transactions 89(1B):762-765.
Corradi, G. 1973. Air cooling units for the
refrigerating industry and new equipment. Revue generale du froid
1(January):45-51.
Courville, G.E., J.P. Sanders, and P.W. Childs. 1985.
Dynamic thermal performance of insulated metal deck roof systems. In Thermal performance of the exterior envelopes of buildings III, pp.
53-63. ASHRAE.
D’Artagnan, S. 1985. The rate of temperature
pulldown. ASHRAE Journal 27(9):36.
Downing, C.G., and W.A. Meefert. 1993. Effectiveness of
cold storage infiltration protection devices. ASHRAE Transactions
99(2):356-366.
Duminil, M., A. Ionov, B. Gazinski, and G. Cano-Munoz.
2002. Insulation and airtightness of cold rooms. International
Institute of Refrigeration, Paris.
Hampson, G.R. 1981. Energy conservation opportunities in
cold storage warehouses. ASHRAE Transactions 87(2):845-849.
Hendrix, W.A., D.R. Henderson, and H.Z. Jackson. 1989.
Infiltration heat gains through cold storage room doorways. ASHRAE
Transactions 95(2):1155-1168.
Holske, C.F. 1953. Commercial and industrial defrosting:
General principles. Refrigerating Engineering 61(3):261-262.
Kerschbaumer, H.G. 1971. Analysis of the influence of
frost formation on evaporators and of the defrost cycles on performance and power consumption of
refrigerating systems. Proceedings of the 13th International Congress of
Refrigeration, pp. 1-12.
Kurilev, E.S., and M.Z. Pechatnikov. 1966. Patterns of
airflow distribution in cold storage rooms. Bulletin of the International
Institute of Refrigeration, Annex 1966-1, pp. 573-579.
Lehman, D.C., and J.E. Ferguson. 1982. A modified
jacketed cold storage design. ASHRAE Transactions
88(2):228-334.
Lotz, H. 1967. Heat and mass transfer and pressure drop
in frosting finned coils: Progress in refrigeration science and technology. Proceedings of the 12th International Congress of Refrigeration,
Madrid, vol. 2.
Niederer, D.H. 1976. Frosting and defrosting effects on
coil heat transfer. ASHRAE Transactions 82(1):467-473.
Paulson, B.A. 1988. Air distribution in freezer areas.
International Institute of Ammonia Refrigeration 10th Annual
Meeting, pp. 261-271.
Powers, G.L. 1981. Ambient gravity air flow stops
freezer floor heaving. ASHRAE Transactions 87(2):1107-1116.
Reindl, D., R. Love, and T. Jekel. 2017. Introducing the
Guide for sustainable refrigerated facilities and refrigeration
systems (1634-RP). Seminar 72. Presented at the 2017
ASHRAE Winter Conference.
Sainsbury, G.F. 1985. Reducing shrinkage through
improved design and operation in refrigerated facilities. ASHRAE
Transactions 91(1B):726-734.
Sastry, S.K. 1985. Factors affecting shrinkage of foods
in refrigerated storage. ASHRAE Transactions 91(1B):683-689.
Shaffer, J.A. 1983. Foundations and superstructure
systems for stacker crane high-rise freezers and coolers. ASHRAE
Transactions 89(1):753-756.
Sherman, M.H., and D.T. Grimsrud. 1980.
Infiltration-pressurization correlation: Simplified physical modeling. ASHRAE Transactions 86(2):778-807.
Soling, S.P. 1983. High rise refrigerated storage. ASHRAE Transactions 89(1B):737-761.
Stoecker, W.F. 1960. Frost formations on refrigeration
coils. ASHRAE Transactions 66:91-103.
Stoecker, W.F. 1988. Industrial
refrigeration technical principles and practices text book. Industrial Refrigeration,
Business News Publishing.
Stoecker, W.F., J.J. Lux, and R.J. Kooy. 1983. Energy
considerations in hot-gas defrosting of industrial refrigeration coils. ASHRAE Transactions 89(2A):549-568.
Treschel, H.R., P.R. Achenbach, and J.R. Ebbets. 1985.
Effect of an exterior air infiltration barrier on moisture condensation and accumulation within
insulated frame wall cavities. ASHRAE Transactions
91(2A):545-559.
Tye, R.P., J.P. Silvers, D.C. Brownell, and S.E. Smith.
1985. New materials and concepts to reduce energy losses through structural thermal bridges. In
Thermal performance of the exterior envelopes of buildings III, pp.
739-750. ASHRAE.
Voelker, J.T. 1983. Insulating considerations for
stacker crane high rise freezers and coolers. ASHRAE Transactions
89(1B):766-768.
Wang, I.H., and Touber. 1987. Prediction of airflow
pattern in cold stores based on temperature measurements. Proceedings of
Commission D, International Congress of Refrigeration, Vienna, pp. 52-60.