Compressors available for single- and multistage applications include the following:
Rotary vane
Reciprocating
Rotary screw
Rotary vane compressors are typically used for low-stage (booster) compressor applications. Reciprocating and screw compressors can be used as single-stage, low-stage (booster), or high-stage machines and can also be internally compounded to provide multiple compression stages on one compressor body.
The reciprocating compressor is the most common compressor used in small, 75 kW or less, single-stage or multistage systems. The screw compressor is the predominant compressor above 75 kW, in both single- and multistage systems. Various combinations of compressors may be used in multistage systems. Rotary vane and screw compressors are frequently used for the low-pressure stage, where large volumes of gas must be moved. The high-pressure stage may be a reciprocating or screw compressor.
When selecting a compressor, consider the following:
System size and capacity requirements.
Location, such as indoor or outdoor installation at ground level or on the roof.
Equipment noise.
Part- or full-load operation.
Winter and summer operation.
Pulldown time required to reduce the temperature to desired conditions for either initial or normal operation. The temperature must be pulled down frequently for some applications for a process load, whereas a large cold-storage warehouse may require pulldown only once in its lifetime.
Lubricant Cooling. When a reciprocating compressor requires lubricant cooling, an external heat exchanger using a refrigerant or secondary cooling is usually added. Screw compressor lubricant cooling is covered in detail in the section on Screw Compressors.
Compressor Drives. The correct electric motor size(s) for a multistage system is determined by pulldown load. When the final low-stage operating level is −75°C, the pulldown load can be three times the operating load. Positive-displacement reciprocating compressor motors are usually selected for about 150% of operating power requirements for 100% load. The compressor’s unloading mechanism can be used to prevent motor overload. Electric motors should not be overloaded, even when a service factor is indicated. For screw compressor applications, motors should be sized by adding 10% to the operating power. Screw compressors have built-in unloading mechanisms to prevent motor overload. The motor should not be oversized, because an oversized motor has a lower power factor and lower efficiency at design and reduced loads.
Steam turbines or gasoline, natural gas, propane, or diesel internal combustion engines are used when electricity is unavailable, or if the selected energy source is cheaper. Sometimes they are used in combination with electricity to reduce peak demands. The power output of a given engine size can vary as much as 15% depending on the fuel selected.
Steam turbine drives for refrigerant compressors are usually limited to very large installations where steam is already available at moderate to high pressure. In all cases, torsional analysis is required to determine what coupling must be used to dampen out any pulsations transmitted from the compressor. For optimum efficiency, a turbine should operate at a high speed that must be geared down for reciprocating and possibly screw compressors. Neither the gear reducer nor the turbine can tolerate a pulsating backlash from the driven end, so torsional analysis and special couplings are essential.
Advantages of turbines include variable speed for capacity control and low operating and maintenance costs. Disadvantages include higher initial costs and possible high noise levels. The turbine must be started manually to bring the turbine housing up to temperature slowly and to prevent excess condensate from entering the turbine.
The standard power rating of an engine is the absolute maximum, not the recommended power available for continuous use. Also, torque characteristics of internal combustion engines and electric motors differ greatly. The proper engine selection is at 75% of its maximum power rating. For longer life, the full-load speed should be at least 10% below maximum engine speed.
Internal combustion engines, in some cases, can reduce operating cost below that for electric motors. Disadvantages include (1) higher initial cost of the engine, (2) additional safety and starting controls, (3) higher noise levels, (4) larger space requirements, (5) air pollution, (6) requirement for heat dissipation, (7) higher maintenance costs, and (8) higher levels of vibration than with electric motors. A torsional analysis must be made to determine the proper coupling if engine drives are chosen.
Reciprocating Compressors
Piping. Figure 1 shows a typical piping arrangement for two compressors operating in parallel off the same suction main. Suction mains should be laid out with the objective of returning only clean, dry gas to the compressor. This usually requires a suction trap sized adequately for gravity gas and liquid separation based on permissible gas velocities for specific temperatures. A dead-end trap can usually trap only scale and lubricant. As an alternative, a shell-and-coil accumulator with a warm liquid coil may be considered. Suction mains running to and from the suction trap or accumulator should be pitched toward the trap at 10 mm per metre for liquid drainage. It is also good practice to connect compressor suction branch piping above the centerline of the suction main.
In sizing suction mains and takeoffs from mains to compressors, consider how pressure drop in the selected piping affects the compressor size required. First costs and operating costs for compressor and piping selections should be optimized.
Good suction line systems have a total friction drop of 0.5 to 1.5 K pressure drop equivalent. Practical suction line friction losses should not exceed 0.01 K equivalent per metre equivalent length.
A well-designed discharge main has a total friction loss of 7 to 14 kPa. Generally, a slightly oversized discharge line is desirable to hold down discharge pressure and, consequently, discharge temperature and energy costs. Where possible, discharge mains should be pitched (10 mm/m) toward the condenser without creating a liquid trap; otherwise, pitch should be toward the discharge line separator.
High- and low-pressure cutouts and gages and lubricant pressure failure cutout are installed on the compressor side of the stop valves to protect the compressor.
Lubricant Separators. Lubricant separators are located in the discharge line of each compressor (Figure 1A). A high-pressure float valve drains lubricant back into the compressor crankcase or lubricant receiver. The separator can be placed away from the compressor, so any extra pipe length can be used to cool the discharge gas before it enters the separator. This reduces the temperature of the ammonia vapor and makes the separator more effective. A discharge gas heat exchanger may also be used to cool the gas before it enters the oil separator.
Liquid ammonia must not reach the crankcase. Often, a valve (preferably automatic) is installed in the drain from the lubricant separator, open only when the temperature at the bottom of the separator is higher than the condensing temperature. Some manufacturers install a small electric heater at the bottom of a vertical lubricant trap instead. The heater is actuated when the compressor is not operating. Separators exposed to cold must be insulated to prevent ammonia condensation. Venting the high-pressure gas in the oil separator to the crankcase or suction line also helps prevent ammonia condensation.
A filter is recommended in the drain line on the downstream side of the high-pressure float valve.
Lubricant Receivers. Figure 1B shows two compressors on the same suction line with one discharge-line lubricant separator. The separator float drains into a lubricant receiver, which maintains a reserve supply of lubricant for the compressors. Compressors should be equipped with crankcase floats to regulate lubricant flow to the crankcase.
Discharge Check Valves and Discharge Lines. Discharge check valves on the downstream side of each lubricant separator prevent high-pressure gas from flowing into an inactive compressor and causing condensation (Figure 1A).
The discharge line from each compressor should enter the discharge main at a 45° maximum angle in the horizontal plane so the gas flows smoothly.
Unloaded Starting. Unloaded starting is frequently needed to stay within the torque or current limitations of the motor. Most compressors are unloaded either by holding each cylinder’s suction valve open or by external bypassing. Control can be manual or automatic.
Suction Gas Conditioning. Suction main piping should be insulated, complete with vapor retarder to minimize thermal losses, to prevent sweating and/or ice build-up on the piping, and to limit superheat at the compressor. Additional superheat increases discharge temperatures and reduces compressor capacity. Low discharge temperatures in ammonia plants are important to reduce lubricant carryover and because compressor lubricant can carbonize at higher temperatures, which can cause cylinder wall scoring and lubricant sludge throughout the system. Discharge temperatures above 120°C should be avoided at all times. Lubricants should have flash-point temperatures above the maximum expected compressor discharge temperature.
Cooling. Generally, ammonia compressors are constructed with internally cast cooling passages along the cylinders and/or in the top heads. These passages provide space for circulating a heat transfer medium, which minimizes heat conduction from the hot discharge gas to the incoming suction gas and lubricant in the compressor’s crankcase. An external lubricant cooler is supplied on most reciprocating ammonia compressors. Water is usually the medium circulated through these passages (water jackets) and the lubricant cooler at a rate of about 2 mL/s per kilowatt of refrigeration. Lubricant in the crankcase (depending on type of construction) is about 50°C. Temperatures above this level reduce the lubricant’s lubricating properties.
For compressors operating in ambients above 0°C, water flow controlled by a solenoid valve in the inlet line is desirable to automate the system and prevent any refrigerant condensing above the pistons. When the compressor stops, water flow must be stopped to keep residual gas from condensing and to conserve water. A water-regulating valve, installed in the water supply line with the sensing bulb in the water return line, is also recommended. This type of cooling is shown in Figure 2.
The thermostat in the water line leaving the jacket serves as a safety cutout to stop the compressor if the temperature becomes too high.
For compressors where ambient temperatures may be below 0°C, a way to drain the jacket on shutdown to prevent freeze-up must be provided. One method is shown in Figure 3. Water flow is through the inlet line normally closed solenoid valve, which is energized when the compressor starts. Water then circulates through the lubricant cooler and the jacket, and out through the water return line. When the compressor stops, the solenoid valve in the water inlet line is deenergized and stops water flow to the compressor. At the same time, the drain line normally open solenoid valve deenergizes and opens to drain the water out of the low point to wastewater treatment. The check valves in the air vent lines open when pressure is relieved and allow the jacket and cooler to be drained. Each flapper check valve is installed so that water pressure closes it, but absence of water pressure allows it to swing open.
For compressors in spaces below 0°C or where water quality is very poor, cooling is best handled by using an inhibited glycol solution or other suitable fluid in the jackets and lubricant cooler and cooling with a secondary heat exchanger. This method for cooling reciprocating ammonia compressors eliminates fouling of the lubricant cooler and jacket normally associated with city water or cooling tower water.
Rotary Vane, Low-Stage Compressors
Piping. Rotary vane compressors have been used extensively as low-stage compressors in ammonia refrigeration systems. Now, however, the screw compressor has largely replaced the rotary vane compressor for ammonia low-stage compressor applications. Piping requirements for rotary vane compressors are the same as for reciprocating compressors. Most rotary vane compressors are lubricated by injectors because they have no crankcase. In some designs, a lubricant separator, lubricant receiver, and cooler are required on the discharge of these compressors; a pump recirculates lubricant to the compressor for both cooling and lubrication. In other rotary vane compressor designs, a discharge lubricant separator is not used, and lubricant collects in the high-stage suction accumulator or intercooler, from which it may be drained. Lubricant for the injectors must periodically be added to a reservoir.
Cooling. The compressor jacket is cooled by circulating a cooling fluid, such as a water/glycol solution or lubricant. Lubricant is recommended, because it will not freeze and can serve both purposes (Figure 4).
Helical screw compressors are the choice for most industrial refrigeration systems. All helical screw compressors have a constant-volume (displacement) design. The volume index Vi refers to the internal volume ratio of the compressor (i.e., the reduction in volume of the compressed gas from suction to discharge of the compressor). Capacity control is accomplished by use of a slide valve, bypass ports, or by controlling the speed [variable-frequency drive (VFD)]. The slide valve and bypass ports control capacity by only using a portion of the screw(s) for the compression process.
Some compressors are designed with a fixed Vi. When Vi is fixed, the compressor functions most efficiently at a certain compression ratio (CR). In selecting a fixed Vi compressor, consider the average CR rather than the maximum CR. A guide to proper compressor selection is based on the equation Vik = CR, where k = 1.4 for ammonia. For example, a screw compressor operating at 265 kPa suction and 1350 kPa discharge has a CR = 5.09. Therefore, Vi = 3.2 (Vi = CR1/k). Thus, a compressor with the Vi at or close to 3.2 is the best selection. Because ambient conditions vary throughout the year, the average condensing temperature may be 24°C (969 kPa). With the lower discharge pressure, the average compressor CR is 3.65 and the ideal Vi is 2.52. Therefore, a compressor with the Vi at or close to 2.5 is the proper selection to optimize efficiency.
Some compressors are equipped with a variable Vi control. This makes compressor selection simpler, because the volume index can vary for different operating conditions. Therefore, the internal compression ratio can automatically match the external pressure ratio. Typically, screw compressors with variable Vi can control between 2.2 and 5.0 Vi. Variable-Vi compressors are beneficial over a wide range of system pressure ratios to improve efficiency as condensing pressures vary.
Piping. Oil-flooded screw compressors are the most common type of screw compressor used in refrigeration. Introduced in the late 1950s as an alternative to dry compressors with a symmetric rotor profile, oil-flooded compressors rapidly gained acceptance in many conventional reciprocating and small centrifugal applications. These compressors typically have oil supplied to the compression area at a volume rate of about 0.5% of the displacement volume. Some of this oil is used for lubricating the bearings and shaft seal. Typically, paraffinic or naphthenic mineral oils are used, though synthetics are being used more frequently on some applications.
The oil fulfills three primary purposes: sealing, cooling, and lubrication. The oil tends to fill any leakage paths between and around the screws. This provides a good volumetric efficiency even at high compression ratios. Normal volumetric efficiency exceeds 85% even with a compression ratio of 25. The oil sealing also helps maintain good volumetric efficiency with decreased operating speeds. The cooling function of the oil transfers much of the heat of compression from the gas to the oil, keeping typical discharge temperatures below 90°C. This allows high compression ratios without the danger of oil breakdown. The oil’s lubrication function protects the bearings, seals, and screw contact areas.
Oil injection to the screw compressor is normally achieved by one of two methods:
An oil pump operates and builds pressure over compressor discharge pressure for oil injection. The pump may be required when the screw compressor is operating at a low compression ratio or if the compressor bearing design requires oil pressure greater than compressor discharge pressure.
Operation without a pump relies on the differential pressure across the screw compressor as the driving force for the oil injection.
Some screw compressors may use a combination of both methods to achieve proper oil injection. The pump may only operate for a period of time when the compression ratio is below a set value. This option is shown schematically in Figure 5.
Oil injection requires an oil separator to remove the oil from the high-pressure refrigerant. Oil separators are designed to satisfy requirements of system type, refrigerant, and heat transfer equipment being used. Modern separation equipment routinely limits oil carryover to the refrigeration system to less than 5 mg/kg of oil in proportion to the circulated refrigerant.
Because the oil absorbs a significant amount of the heat of compression in oil-flooded operation, oil cooling must be used to maintain low discharge temperatures. Common oil-cooling methods include the following:
Direct injection of liquid refrigerant into the screw compression process. The injected liquid refrigerant amount is normally controlled by sensing the compressor discharge temperature. The refrigerant is modulated with a thermal expansion valve to maintain a constant discharge temperature. Some of the injected liquid mixes with the oil and reduces the amount of internal volume available for suction gas to the compressor. Therefore, the compressor capacity is reduced. In addition, the liquid absorbs heat and expands to vapor, which requires additional power to compress. Screw compressors are normally designed with the liquid injection ports as late as possible in the compression process, to minimize the capacity and power penalties. Refrigerant liquid for liquid-injection oil cooling must come from a dedicated supply. The source may be the system receiver or a separate receiver; a 5 min uninterrupted supply of refrigerant liquid is usually adequate. Refrigerant injection cooling is shown schematically in Figure 6. Depending on the application, this cooling method usually decreases compressor efficiency and capacity but lowers equipment cost.
External water or glycol heat exchangers for oil cooling. With this configuration, heat is removed from the oil by using an external oil cooler. Cooling tower water, a separate evaporative cooler, underfloor glycol, and various other sources of water or glycol are used to circulate through the oil cooler heat exchanger and remove the heat of compression. A three-way oil temperature control valve is typically used in the compressor oil piping to control oil temperature. This method of oil cooling does not affect compressor efficiency or capacity. The external heat exchanger for oil cooling is shown schematically in Figure 7.
External refrigerant heat exchanger for oil cooling (thermosiphon). With this configuration, heat is removed from the oil by using an external oil cooler and high-pressure liquid refrigerant from the system. Indirect or thermosiphon lubricant cooling for low-stage screw compressors rejects the lubricant cooling load to the condenser or auxiliary cooling system; this load is not transferred to the high-stage compressor, thus improving system efficiency. Thermosiphon lubricant cooling is the most common method of oil cooling in refrigeration. In this system, high-pressure refrigerant liquid from the condenser, which boils at condensing temperature/pressure (usually 32 to 35°C design), cools lubricant in a heat exchanger. The thermosiphon oil cooler is also shown schematically in Figure 7. A typical thermosiphon oil-cooling system with multiple heat exchangers is shown schematically in Figure 8. Note that the refrigerant liquid supply to the oil cooler receives priority over the feed to the system low side. It is important that the gas equalizing line (vent) off the top of the thermosiphon receiver be adequately sized to match the oil cooler load to prevent the thermosiphon receiver from becoming gas bound. It is also good practice to slope the two-phase flow return line from the oil cooler to the thermosiphon vessel down in the direction of flow at 20 mm/m. A three-way oil control valve may also be used to control oil temperature to the compressor.
As in all refrigeration systems, the condenser in an ammonia system rejects the heat absorbed in the evaporator, as well as that added by the compression process and other miscellaneous inputs, to a sink. This rejection is usually to atmosphere, but can also be to bodies of water (subject to local environmental restrictions). The most common condenser type is evaporative, which uses a primary surface coil with air and water streams passing over the coil. A variation cools the air before it passes over the coil, reducing water flow. Heat exchangers such as shell-and-tube or plate types have also been used; these typically require a cooling tower to supply the heat exchangers with water. They can also transfer refrigeration system heat to other plant processes that can use a relatively low-temperature (24 to 82°C) heat source, such as boiler water preheat or process and cleanup water heating. Air-cooled condensers can be used where water is scarce and/or cost is high, but they offer sensible cooling only and the refrigeration system design must allow for increased discharge pressures.
Condensers are frequently selected on the basis of total heat rejection at maximum system refrigeration load, but this assumes the relatively steady-state operation found in most refrigerating plants. Installations with seasonal startup or other intermittent operation must allow for pulldown loads, and the heat rejected at the start of pulldown is often several times the amount rejected under normal operating conditions. Compressor unloading or suction throttling can be used to limit the maximum amount of heat rejected during pulldown. If the condenser is not sized for pulldown conditions and compressor capacity cannot be limited during this period, condensing pressure might increase enough to shut down the system.
Condenser and Receiver Piping
It is important to remove the condensed liquid from the condenser continuously to clear the condensing heat transfer surface for fresh vapor. Properly designed piping around the condensers and receivers keeps the condensing surface at its highest efficiency by draining liquid ammonia out of the condenser as soon as it condenses and keeping air and other noncondensables purged.
Horizontal Shell-and-Tube Condenser and Through-Type Receiver. Figure 9 shows a horizontal water-cooled condenser draining into a through (top inlet) receiver. Ammonia plants do not always require controlled water flow to maintain pressure. Usually, pressure is adequate to force the ammonia to the various evaporators without water regulation. Each situation should be evaluated by comparing water costs with input power cost savings at lower condenser pressures.
Evaporative condensers are typically selected based on the desired maximum condensing pressure and the design wet-bulb temperature at the installed location. The 1% design wet bulb is the temperature that will be equaled or exceeded 1% of the year, or 87.6 hours. The resultant condensing pressure only equals or exceeds the design condition 1.0% of the time if the design wet-bulb temperature and peak design refrigeration load occur coincidentally. This peak condition depends less on condenser size and is more a function of how the load is calculated, what load diversity factor exists or is used in the calculation, and what safety factor is used in the calculations.
Location. If an evaporative condenser is located with insufficient space for air movement, the effect is the essentially same as that imposed by an inlet damper, and the fan may not deliver enough air. Such a location may also increase the chances of recirculating evaporative condenser discharge air, which reduces condenser capacity because the recirculated air has an increased wet-bulb temperature. For forced-draft condensers, the high inlet velocity causes a low-pressure region to develop around the fan inlet, inducing flow of discharge air into that region. If the obstruction is from a second condenser, the problem can be even more severe because discharge air from the second condenser flows into the air intake of the first. Induced-draft condensers are theoretically less prone to recirculation; however, inadequate space between multiple induced-draft condensers can still result in recirculation.
Prevailing winds can also contribute to recirculation. In many areas, winds shift with the seasons; wind direction during the peak high-humidity season is the most important consideration.
The tops of condensers should always be higher than any adjacent structure to eliminate downdrafts that might induce recirculation. Where this is impractical, discharge hoods can be used to discharge air far enough away from the fan intakes to avoid recirculation. However, the additional static pressure imposed by a discharge hood must be added to the fan system. Fan speed can be increased slightly to obtain proper air volume.
In areas with ambient temperatures below 0°C, water in the evaporative condenser drain pan and water circuit must be kept from freezing. When the temperature is at or below freezing, the evaporative condenser may be able to operate as a dry-coil unit and still maintain acceptable condensing pressures. In some cases (depending on weather, loads, and amount of condenser capacity), the water pump(s) and piping could be drained and secured for the season.
Another way to keep water from freezing is to drain the water in the condenser sump to an indoor water tank, as shown in Figure 10. When outdoor temperature drops, the condensing pressure drops, and a pressure switch with its sensing element in the discharge pressure line stops the water pump; the water is then drained into the tank. An alternative is to use a thermostat that senses water or outdoor ambient temperature and stops the pump at low temperatures. Exposed piping and any trapped water headers in the evaporative condenser should be drained into the indoor water tank.
Air volume capacity control methods include fan cycling in response to pressure controls, and two-speed or VFD fan motors.
Installation. For a relatively small refrigeration system, a single evaporative condenser used with a through-type (top inlet) receiver can be connected as shown in Figure 11. The receiver must always be at the same pressure as the condensing pressure in the condenser to allow gravity to drain condensed liquid ammonia out of the condenser tube bundle. This is accomplished by locating the receiver below the elevation of the evaporative condenser outlets, by equalizing the receiver to the evaporative condenser inlet piping, and by ensuring that condenser drain line piping velocity is sized for sewer drainage (i.e., only partially full of liquid). For a single condenser circuit, this is accomplished by equalizing through the condenser drain line and limiting velocity to 0.5 m/s.
Liquid Traps. For a through-type (top inlet) receiver, liquid traps are needed at the outlets when two or more condensers or condenser coils are installed so that variations in pressure drop through each condenser circuit do not interrupt continuous liquid draining from the condenser (Figure 12). An equalizer line is also necessary to ensure free drainage from condensers by keeping receiver and condenser pressures equal. For example, assume a 10 kPa pressure drop in the operating condenser in Figure 12, which produces a lower pressure (1290 kPa) at its outlet compared to the idle condenser (1300 kPa) and the receiver (1300 kPa). The trap creates a liquid seal so that a liquid height h of 1700 mm (equivalent to 10 kPa) builds up in the vertical individual condenser drain piping and not in the condenser coil.
The trap must have enough height above the vertical liquid leg to accommodate a liquid height equal to the maximum pressure drop encountered in the condenser. The example shows the extreme case of one unit on and one off; however, the same phenomenon occurs to a lesser degree with two condensers of differing pressure drops when both are in full operation. Substantial differences in pressure drop can also occur between two different brands of the same size condenser or even different models produced by the same manufacturer.
The minimum recommended height of the vertical leg is 1500 mm for ammonia. This vertical dimension h is shown in all evaporative condenser piping diagrams. This height is satisfactory for operation within reasonable ranges around normal design conditions, and is based on the coil’s maximum condensing pressure drop. If service valves are installed at the coil inlets and/or outlets, the pressure drops imposed by these valves must be accounted for by increasing the minimum 1500 mm drop-leg height by an amount equal to the valve pressure drop in height of liquid refrigerant (Figure 13).
Noncondensable gases can accumulate in an ammonia refrigeration system from incomplete evacuation, fluid chemical breakdown, and air entering any portion of the system operating at less than atmospheric pressure. These gases travel with the refrigerant and into the condenser, but do not condense and cannot pass through the liquid refrigerant filling the condenser outlet traps. Unless purged from the condenser circuits, they blanket the heat transfer surface and degrade condenser capability. Purging is accomplished by dedicated equipment connected through solenoid valves to taps located at the top of each condenser outlet. It is important to ensure that each solenoid valve is energized individually and not in combination with another purge solenoid valve on another condenser tube bundle, because this would connect the condenser outlets and bypass the traps.
Figures 14, 15, and 16 show various piping arrangements for evaporative condensers.
Horizontal Shell-and-Tube Condenser and Through-Type Receiver. Figure 9 shows a horizontal water-cooled condenser draining into a through (top inlet) receiver. Ammonia plants do not always require controlled water flow to maintain pressure. Usually, pressure is adequate to force the ammonia to the various evaporators without water regulation. Each situation should be evaluated by comparing water costs with input power cost savings at lower condenser pressures.
Water piping should be arranged so that condenser tubes are always filled with water. Air vents should be provided on condenser heads and should have hand valves for manual purging.
Receivers must be below the condenser so that the condensing surface is not flooded with ammonia. The piping should provide (1) free drainage from the condenser and (2) static height of ammonia above the first valve out of the condenser greater than the pressure drop through the valve.
The drain line from condenser to receiver is designed on the basis of 0.5 m/s maximum velocity to allow gas equalization between condenser and receiver. See Table 2 for sizing criteria.
Parallel Horizontal Shell-and-Tube Condensers. Figure 17 shows two condensers operating in parallel with one through-type (top inlet) receiver. The length of horizontal liquid drain lines to the receiver should be minimized, with no traps allowed. The shells are equalized by keeping liquid velocity in the drain line less than 0.5 m/s. The drain line can be sized from Table 2.
Air-Cooled Condensers. This condensing mode is less common than evaporative, but is receiving more attention as water, chemical treatment and sewer costs rise. Because air-cooled equipment works by sensible heat transfer and the approach between dry-bulb temperature and condensing temperature is unlikely to be less than 11 K, the increase in condensing temperature and compressor power must be factored into any selection process. Piping arrangements and airflow routing are similar to those shown for evaporative condensers, but it is crucial that air-cooled condensing tubes are installed level to drain liquid effectively. A secondary heat transfer surface of plate or spiral fins is common, and fin spacing is usually 1.7 to 3.2 mm. Airflow in blow-through or draw-through configurations deposits any atmospheric contaminants between the fins, and monthly cleaning is usually required. See Figure 7 in Chapter 39 of the 2020 ASHRAE Handbook—HVAC Systems and Equipment for an example of this setup.
Several types of evaporators are used in ammonia refrigeration systems. Fan-coil, direct-expansion evaporators can be used, but they are not generally recommended unless the suction temperature is −18°C or higher. This is partially because of the direct-expansion coil’s relative inefficiency, but more importantly, also because the low mass flow rate of ammonia is difficult to feed uniformly as a liquid to the coil. Instead, ammonia fan-coil units designed for recirculation (overfeed) systems are preferred. Typically, in this type of system, high-pressure ammonia from the system high stage flashes into a large vessel at the evaporator pressure, from which it is pumped to the evaporators at an overfeed rate of 2.5:1 to 4:1. This type of system is standard and very efficient. See Chapter 4 for more details.
Flooded shell-and-tube evaporators are often used in ammonia systems in which indirect or secondary cooling fluids such as water, brine, or glycol must be cooled.
Some problems that can become more acute at low temperatures include changes in lubricant transport properties, loss of capacity caused by static pressure from the depth of the pool of liquid refrigerant in the evaporator, deterioration of refrigerant boiling heat transfer coefficients caused by lubricant logging, and higher specific volumes for the vapor.
The effect of pressure losses in the evaporator and suction piping is more acute in low-temperature systems because of the large change in saturation temperatures and specific volume in relation to pressure changes at these conditions. Systems that operate near or below zero gage pressure are particularly affected by pressure loss.
The depth of the pool of boiling refrigerant in a flooded evaporator exerts a liquid pressure on the lower part of the heat transfer surface. Therefore, the saturation temperature at this surface is higher than that in the suction line, which is not affected by the liquid pressure. This temperature gradient must be considered when designing the evaporator.
Spray shell-and-tube evaporators, though not commonly used, offer certain advantages. In this design, the evaporator’s liquid depth penalty can be eliminated because the pool of liquid is below the heat transfer surface. A refrigerant pump sprays liquid over the surface. Pump energy is an additional heat load to the system, and more refrigerant must be used to provide the net positive suction pressure required by the pump. The pump is also an additional item that must be maintained. This evaporator design also reduces the refrigerant charge requirement compared to a flooded design (see Chapter 4).
Proper evaporator piping and control are necessary to keep the cooled space at the desired temperature and also to adequately protect the compressor from surges of liquid ammonia out of the evaporator. The evaporators shown in this section show some methods used to accomplish these objectives. In some cases, combinations of details on several illustrations have been used.
When using hot gas or electric heat for defrosting, the drain pan and drain line must be heated to prevent the condensate from refreezing. With hot gas, a heating coil is embedded in the drain pan. The hot gas flows first through this coil and then into the evaporator coil. With electric heat, an electric heating coil is used under the drain pan. Wraparound or internal electric heating cables are used on the condensate drain line when the room temperature is below 0°C.
Figure 18 shows a thermostatic expansion valve on a unit cooler using hot gas for automatic defrosting. Because this is an automatic defrosting arrangement, hot gas must always be available at the hot-gas solenoid valve near the unit. The system must contain multiple evaporators so the compressor is running when the evaporator to be defrosted is shut down. The hot-gas header must be kept in a space where ammonia does not condense in the pipe. Otherwise, the coil receives liquid ammonia at the start of defrosting and is unable to take full advantage of the latent heat of hot-gas condensation entering the coil. This can also lead to severe hydraulic shock loads. If the header must be in a cold space, the hot-gas main must be insulated and a high-pressure float drainer installed to remove any accumulated condensate.
The liquid- and suction-line solenoid valves are open during normal operation only and are closed during the defrost cycle. When defrost starts, the hot-gas solenoid valve is opened. Refer to IIAR Bulletin 116 for information on possible hydraulic shock when the hot-gas defrost valve is opened after a defrost.
A defrost pressure regulator maintains a gage pressure of about 480 to 550 kPa in the coil.
Unit Cooler: Flooded Operation
Figure 19 shows a flooded evaporator with a close-coupled low-pressure vessel for feeding ammonia into the coil and automatic water defrost.
The lower float switch on the float column at the vessel controls opening and closing of the liquid-line solenoid valve, regulating ammonia feed into the unit to maintain a liquid level. The hand expansion valve downstream of the solenoid valve should be adjusted so that it does not feed ammonia into the vessel more quickly than the vessel can accommodate while raising the suction pressure of gas from the vessel no more than 7 to 14 kPa.
The static height of liquid in the vessel should be sufficient to flood the coil with liquid under normal loads. The higher float switch is to signal a high level of liquid in the vessel. It should be wired into an alarm circuit or possibly a compressor shutdown circuit if there is no other compressor protection. The float switches and/or columns should be insulated. With flooded coils having horizontal headers, distribution between the multiple circuits is accomplished without distributing orifices.
A combination evaporator pressure regulator and stop valve is used in the suction line from the vessel. During operation, the regulator maintains a nearly constant back pressure in the vessel. A solenoid coil in the regulator mechanism closes it during the defrost cycle. The liquid solenoid valve should also be closed at this time. One of the best means of controlling room temperature is a room thermostat that controls the effective setting of the evaporator pressure regulator.
A spring-loaded relief valve is used around the suction pressure regulator and is set so that the vessel is kept below 860 kPa (gage). Other suction line pressure control arrangements, such as a dual pressure regulator, can be used to eliminate the extra piping of the relief valve.
A solenoid valve unaffected by downstream pressure is used in the water line to the defrost header. The defrost header is constructed so that it drains at the end of the defrost cycle and the downstream side of the solenoid valve drains through a fixed orifice.
Unless the room is kept above 0°C, the drain line from the unit should be wrapped with a heater cable or provided with another heat source and then insulated to prevent defrost water from refreezing in the line.
Water line length in the space leading up to the header and the length of the drain line in the cooled space should be minimized. A flapper or pipe trap on the end of the drain line prevents warm air from flowing up the drain pipe and into the unit.
An air outlet damper may be closed during defrosting to prevent thermal circulation of air through the unit, which affects the temperature of the cooled space. The fan is stopped during defrost. This type of defrosting requires a drain pan float switch for safety control. If the drain pan fills with water, the switch overrides the time clock to stop flow into the unit by closing the water solenoid valve.
There should be a 5 min delay at the end of the water spray part of the defrosting cycle so water can drain from the coil and pan. This limits ice build-up in the drain pan and on the coils after the cycle is completed.
When the cycle finishes, the low-pressure vessel may be at about 517 kPa (gage). When the unit is opened to the much-lower-pressure suction main, some liquid surges out into the main; therefore, it may be necessary to gradually bleed off this pressure before fully opening the suction valve, to prevent thermal shock. Generally, a suction trap in the engine room removes this liquid before the gas stream enters the compressors.
The type of refrigerant control shown in Figure 20 can be used on brine spray units where brine is sprayed over the coil at all times to pick up the condensed water vapor from the airstream. The brine is reconcentrated continually to remove water absorbed from the airstream.
When a system has only one evaporator, a high-pressure float control can be used to keep the condenser drained and to provide a liquid seal between the high and low sides. Figure 20 shows a brine or water cooler with this type of control. The high-side float should be located near the evaporator to avoid insulating the liquid line.
The amount of ammonia in this type of system is critical: the charge must be limited so that liquid will not surge into the suction line under the highest loading in the evaporator. Some type of suction trap should be used. One method is to place a horizontal shell above the cooler, with suction gas piped into the bottom and out the top. The reduction of gas velocity in this shell causes liquid to separate from the gas and drop back into the chiller.
Coolers should include a liquid indicator. A reflex glass lens with a large liquid chamber and vapor connections for boiling liquids and a plastic frost shield to determine the actual level should be used. A refrigeration thermostat measuring chilled-fluid temperature as it exits the cooler should be wired into the compressor starting circuit to prevent freezing.
A flow switch or differential pressure switch should prove flow before the compressor starts. The fluid to be cooled should be piped into the lower portion of the tube bundle and out of the top portion.
For multiple evaporator systems, low-side float valves are used to control the refrigerant level in flooded evaporators. The low-pressure float in Figure 21 has an equalizer line from the top of the float chamber to the space above the tube bundle and an equalizer line out of the lower side of the float chamber to the lower side of the tube bundle.
For positive shutoff of liquid feed when the system stops, a solenoid valve in the liquid line is wired so that it is only energized when the brine or water pump motor is operating and the compressor is running.
A reflex glass lens with large liquid chamber and vapor connections for boiling liquids should be used with a plastic frost shield to determine the actual level, and with front extensions as required. These chambers or columns should be insulated to prevent false levels caused by heat transfer from the surrounding environment.
Usually a high-level float switch is installed above the operating level of the float to shut the liquid solenoid valve if the float should overfeed.
High-Pressure Receivers. Industrial systems generally incorporate a central high-pressure refrigerant receiver, which serves as the primary refrigerant storage location in the system. It handles refrigerant volume variations between the condenser and the system’s low side during operation and pumpdowns for repairs or defrost. Ideally, the receiver should be large enough to hold the entire system charge, but this is not generally economical. The system should be analyzed to determine the optimum receiver size. Receivers are commonly equalized to the condenser inlet and operate at the same pressure as the condenser. In some systems, the receiver is operated at a pressure between the condensing pressure and the highest suction pressure to allow for variations in condensing pressure without affecting the system’s feed pressure. This type is commonly referred to as a controlled-pressure receiver (CPR). Liquid from the condenser is metered through a high-side control as it is condensed. CPR pressure is maintained with a back-pressure regulator vented to an intermediate pressure point. Winter or low-load operating conditions may require a downstream pressure regulator to maintain a minimum pressure.
If additional receiver capacity is needed for normal operation, use extreme caution in the design. Designers usually remove the inadequate receiver and replace it with a larger one rather than install an additional receiver in parallel. This procedure is best because even slight differences in piping pressure or temperature can cause the refrigerant to migrate to one receiver and not to the other.
Smaller auxiliary receivers can be incorporated to serve as sources of high-pressure liquid for compressor injection or thermosiphon, lubricant cooling, high-temperature evaporators, and so forth.
Intercoolers (Gas and Liquid). An intercooler (subcooler/ desuperheater) is the intermediate vessel between the high and low stages in a multistage system. One purpose is to cool discharge gas of the low-stage compressor to prevent overheating the high-stage compressor. This can be done by bubbling discharge gas from the low-stage compressor through a bath of liquid refrigerant or by mixing liquid normally entering the intermediate vessel with the discharge gas as it enters above the liquid level. Heat removed from the discharge gas is absorbed by evaporating part of the liquid and eventually passes through the high-stage compressor to the condenser. Distributing the discharge gas below a level of liquid refrigerant separates out any lubricant carryover from the low-stage compressor. If liquid in the intercooler is to be used for other purposes, such as liquid makeup or feed to the low stage, periodic lubricant removal is imperative.
Another purpose of the intercooler is to lower the liquid temperature used in the low stage of a two-stage system. Lowering refrigerant temperature in the intercooler with high-stage compressors increases the refrigeration effect and reduces the low-stage compressor’s required displacement, thus reducing its operating cost.
Intercoolers for two-stage compression systems can be shell-and-coil or flash. Figure 22 depicts a shell-and-coil intercooler incorporating an internal pipe coil for subcooling high-pressure liquid before it is fed to the low stage of the system. Typically, the coil subcools liquid to within 6 K of the intermediate temperature.
Vertical shell-and-coil intercoolers perform well in many applications using ammonia refrigerant systems. Horizontal designs are possible but usually not practical. The vessel must be sized properly to separate liquid from vapor that is returning to the high-stage compressor. The superheated gas inlet pipe should extend below the liquid level and have perforations or slots to distribute the gas evenly in small bubbles. Adding a perforated baffle across the area of the vessel slightly below the liquid level protects against violent surging. Always use a float switch that shuts down the high-stage compressor when the liquid level gets too high. A means of maintaining a liquid level for the subcooling coil and low-stage compressor desuperheating is necessary if no high-stage evaporator overfeed liquid is present. Electronic level controls (see Figure 30) can simplify the use of multiple float switches and float valves to maintain the various levels required.
The flash intercooler is similar in design to the shell-and-coil intercooler, except for the coil. The high-pressure liquid is flash-cooled to the intermediate temperature. Use caution in selecting a flash intercooler because all the high-pressure liquid is flashed to intermediate pressure. Though colder than that of the shell-and-coil intercooler, liquid in the flash intercooler is not subcooled and is susceptible to flashing from system pressure drop. Two-phase liquid feed to control valves may cause premature failure because of the wire-drawing effect of the liquid/vapor mixture.
Figure 23 shows a vertical shell-and-coil intercooler as piped into a system. The liquid level is maintained in the intercooler by a float that controls the solenoid valve feeding liquid into the shell side of the intercooler. Gas from the first-stage compressor enters the lower section of the intercooler, is distributed by a perforated plate, and is then cooled to the saturation temperature corresponding to intermediate pressure.
When sizing any intercooler, the designer must consider (1) low-stage compressor capacity; (2) vapor desuperheating, liquid makeup requirements for the subcooling coil load, or vapor cooling load associated with the flash intercooler; and (3) any high-stage side loading. The volume required for normal liquid levels, liquid surging from high-stage evaporators, feed valve malfunctions, and liquid/vapor must also be analyzed.
Necessary accessories are the liquid level control device and high-level float switch. Though not absolutely necessary, an auxiliary oil pot should also be considered.
Suction Accumulator. A suction accumulator (also known as a knockout drum, suction trap, etc.) prevents liquid from entering the suction of the compressor, whether on the high or low stage of the system. Both vertical and horizontal vessels can be incorporated. Baffling and mist eliminator pads can enhance liquid separation.
Suction accumulators, especially those not intentionally maintaining a level of liquid, should have a way to remove any build-up of ammonia liquid. Gas boil-out coils or electric heating elements are costly and inefficient.
Although it is one of the more common and simplest means of liquid removal, a liquid boil-out coil (Figure 24) has some drawbacks. Generally, warm liquid flowing through the coil is the heat source for liquid being boiled off. Liquid transfer pumps, gas-powered transfer systems, or basic pressure differentials are a more positive means of removing the liquid (Figures 25 and 26).
Accessories should include a high-level float switch for compressor protection along with additional pump or transfer system controls.
Vertical Suction Trap and Pump. Figure 27 shows the piping of a vertical suction trap that uses a high-pressure ammonia pump to transfer liquid from the system’s low-pressure side to the high-pressure receiver. Float switches piped on a float column on the side of the trap can start and stop the liquid ammonia pump, sound an alarm in case of excess liquid, and sometimes stop the compressors.
When the liquid level in the suction trap reaches the setting of the middle float switch, the liquid ammonia pump starts and reduces the liquid level to the setting of the lower float switch, which stops the liquid ammonia pump. A check valve in the discharge line of the ammonia pump prevents gas and liquid from flowing backward through the pump when it is not in operation. Depending on the type of check valve used, some installations have two valves in a series as an extra precaution against pump backspin.
Compressor controls adequately designed for starting, stopping, and capacity reduction result in minimal agitation, which helps separate vapor and liquid in the suction trap. Increasing compressor capacity slowly and in small increments reduces liquid boiling in the trap, which is caused by the refrigeration load of cooling the refrigerant and metal mass of the trap. If another compressor is started when plant suction pressure increases, it should be brought on line slowly to prevent a sudden pressure change in the suction trap.
A high level of liquid in a suction trap should activate an alarm or stop the compressors. Although eliminating the cause is the most effective way to reduce a high level of excess surging liquid, a more immediate solution is to stop part of the compression system and raise plant suction pressure slightly. Continuing high levels indicate insufficient pump capacity or suction trap volume.
Liquid Level Indicators. Liquid level can be indicated by visual indicators, electronic sensors, or a combination of the two. Visual indicators include individual circular reflex level indicators (bull’s-eyes) mounted on a pipe column or stand-alone linear reflex glass assemblies (Figure 28). For operation at temperatures below the frost point, transparent plastic frost shields covering the reflex surfaces are necessary. Also, the pipe column must be insulated, especially when control devices are attached to prevent false level readings caused by heat influx.
Electronic level sensors can continuously monitor liquid level. Digital or graphic displays of liquid level can be locally or remotely monitored (Figure 29).
Level indicators should have adequate isolation valves, which should incorporate stop check or excess-flow valves for isolation and safety.
Purge Units. A noncondensable gas separator (purge unit) is useful in most plants, especially when suction pressure is below atmospheric pressure. Purge units on ammonia systems are piped to carry noncondensables (air) from the receiver and condenser to the purger, as shown in Figure 30. Suction from the coil should be taken to one of the low-temperature suction vessel inlet mains. Ammonia vapor and noncondensable gas are drawn into the purger, and the ammonia condenses on the cold surface, sorting out the noncondensables. When the drum fills with air and other noncondensables, a level control in the purger opens and allows them to be released. Depending on operating conditions, a trace of ammonia may remain in the noncondensable gases. The noncondensable gases are diverted to a water bottle (generally with running water) to diffuse the pungent odor of the ammonia. Ammonia systems, which are inherently large, have multiple points where noncondensables can collect. Purge units that can automatically sequence through the various points and remove noncondensables are available.
Ammonia’s affinity for water poses another system efficiency concern. The presence of water increases the refrigerant temperature above the saturated pressure. The increased temperature requires lower operating pressures to maintain the same refrigerant temperature. Unlike noncondensable gases, which collect in the system’s high side and result in higher condensing pressures, the presence of water is less obvious. Water collects in the liquid phase and forms an aqua/ammonia solution. Short of a complete system charge removal, distillers (temporary or permanent) can be incorporated. Automatic noncondensable and water removal units can provide continual monitoring of system impurities.
Local codes or ordinances governing ammonia mains should be followed, in addition to the recommendations here.
Because copper and copper-bearing materials are attacked by ammonia, they are not used in ammonia piping systems. Steel or stainless steel piping, fittings, and valves of the proper pressure rating are suitable for ammonia gas and liquid.
Ammonia piping should conform to ASME Standard B31.5, and to IIAR Standard 2, which states the following:
Liquid lines 40 mm and smaller shall be not less than Schedule 80 carbon steel pipe.
Liquid lines 50 to 150 mm shall be not less than Schedule 40 carbon steel pipe.
Liquid lines 200 to 300 mm shall be not less than Schedule 20 carbon steel pipe.
Vapor lines 150 mm and smaller shall be not less than Schedule 40 carbon steel pipe.
Vapor lines 200 to 300 mm shall be not less than Schedule 20 carbon steel pipe.
Vapor lines 350 mm and larger shall be not less than Schedule 10 carbon steel pipe.
All threaded pipe shall be Schedule 80.
Carbon steel pipe shall be ASTM Standard A53 Grade A or B, Type E (electric resistance welded) or Type S (seamless); or ASTM Standard A106 (seamless), except where temperature-pressure criteria mandate a higher specification material. Standard A53 Type F is not permitted for ammonia piping.
Couplings, elbows, and tees for threaded pipe are for a minimum of 21 MPa design pressure and constructed of forged steel. Fittings for welded pipe should match the type of pipe used (i.e., standard fittings for standard pipe and extra-heavy fittings for extra-heavy pipe).
Tongue-and-groove or ANSI flanges should be used in ammonia piping. Welded flanges for low-side piping can have a minimum 1 MPa design pressure rating. On systems located in high ambients, low-side piping and vessels should be designed for 1.4 to 1.6 MPa. The high side should be 1.7 MPa if the system uses water-cooled or evaporative cooled condensing. Use 2.1 MPa minimum for air-cooled designs.
Joints between lengths of pipe or between pipe and fittings can be threaded if the pipe size is 32 mm or smaller. Pipe 40 mm or larger should be welded. An all-welded piping system is superior.
Threaded Joints. Many sealants and compounds are available for sealing threaded joints. The manufacturer’s instructions cover compatibility and application method. Do not use excessive amounts or apply on female threads because any excess can contaminate the system.
Welded Joints. Pipe should be cut and beveled before welding. Use pipe alignment guides and provide a proper gap between pipe ends so that a full-penetration weld is obtained. The weld should be made by a qualified welder, using proper procedures such as the Welding Procedure Specifications, prepared by the National Certified Pipe Welding Bureau (NCPWB).
Gasketed Joints. A compatible fiber gasket should be used with flanges. Before tightening flange bolts to valves, controls, or flange unions, properly align pipe and bolt holes. When flanges are used to straighten pipe, they put stress on adjacent valves, compressors, and controls, causing the operating mechanism to bind. To prevent leaks, flange bolts are drawn up evenly when connecting the flanges. Flanges at compressors and other system components must not move or indicate stress when all bolts are loosened.
Union Joints. Steel (21 MPa) ground joint unions are used for gage and pressure control lines with screwed valves and for joints up to 20 mm. When tightening this type of joint, the two pipes must be axially aligned. To be effective, the two parts of the union must match perfectly. Ground joint unions should be avoided if at all possible.
Piping should be at least 2.3 m above the floor. Locate pipes carefully in relation to other piping and structural members, especially when lines are to be insulated. The distance between insulated lines should be at least three times the thickness of the insulation for screwed fittings, and four times for flange fittings. The space between the pipe and adjacent surfaces should be three-fourths of these amounts.
Hangers located close to the vertical risers to and from compressors keep the piping weight off the compressor. Pipe hangers should be placed no more than 2.4 to 3 m apart, depending on pipe size, and within 0.6 m of a change in direction of the piping. Hangers should be designed to bear on the outside of insulated lines. Sheet metal sleeves on the lower half of the insulation are usually sufficient. Where piping penetrates a wall, a sleeve should be installed, and where the pipe penetrating the wall is insulated, it must be adequately sealed.
Piping to and from compressors and to other components must provide for expansion and contraction. Sufficient flange or union joints should be located in the piping so components can be assembled easily during installation and also disassembled for servicing.
Table 1 presents practical suction line sizing data based on 0.005 K and 0.01 K differential pressure drop equivalent per metre total equivalent length of pipe, assuming no liquid in the suction line. For data on equivalent lengths of valves and fittings, refer to Tables 10, 11, and 12 in Chapter 1. Table 2 lists data for sizing suction and discharge lines at 0.02 K differential pressure drop equivalent per metre equivalent length of pipe, and for sizing liquid lines at 0.5 m/s. Charts prepared by Wile (1977) present pressure drops in saturation temperature equivalents. For a complete discussion of the basis of these line sizing charts, see Timm (1991). Table 3 presents line sizing information for pumped liquid lines, high-pressure liquid lines, hot-gas defrost lines, equalizing lines, and thermosiphon lubricant cooling ammonia lines.
Refrigerant flow controls are discussed in Chapter 11. The following precautions are necessary in the application of certain controls in low-temperature systems.
Many controls available for single-stage, high-temperature systems may be used with some discretion on low-temperature systems. If the liquid level is controlled by a low-side float valve (with the float in the chamber where the level is controlled), low pressure and temperature have no appreciable effect on operation. External float chambers, however, must be thoroughly insulated to prevent heat influx that might cause boiling and an unstable level, affecting the float response. Equalizing lines to external float chambers, particularly the upper line, must be sized generously so that liquid can reach the float chamber, and gas resulting from any evaporation may be returned to the vessel without appreciable pressure loss.
The superheat-controlled (thermostatic) expansion valve is generally used in direct-expansion evaporators. This valve operates on the difference between bulb pressure, which is responsive to suction temperature, and pressure below the diaphragm, which is the actual suction pressure.
The thermostatic expansion valve is designed to maintain a preset superheat in suction gas. Although the pressure-sensing part of the system responds almost immediately to a change in conditions, the temperature-sensing bulb must overcome thermal inertia before its effect is felt on the power element of the valve. Thus, when compressor capacity decreases suddenly, the expansion valve may overfeed before the bulb senses the presence of liquid in the suction line and reduces the feed. Therefore, a suction accumulator should be installed on direct-expansion low-temperature systems with multiple expansion valves.
Controlling Load During Pulldown
System transients during pulldown can be managed by controlling compressor capacity. Proper load control reduces compressor capacity so that energy requirements stay within motor and condenser capacities. On larger systems using screw compressors, a current-sensing device reads motor amperage and adjusts the capacity control device appropriately. Cylinders on reciprocating compressors can be unloaded for similar control.
Alternatively, a downstream, outlet, or crankcase pressure regulator can be installed in the suction line to throttle suction flow if the pressure exceeds a preset limit. This regulator limits the compressor’s suction pressure during pulldown. The disadvantage of this device is the extra pressure drop it causes when the system is at the desired operating conditions. To overcome some of this, the designer can use external forces to drive the valve, causing it to be held fully open when the pressure is below the maximum allowable. Systems using downstream pressure regulators and compressor unloading must be carefully designed so that the two controls complement each other.
Operation at Varying Loads and Temperatures
Compressor and evaporator capacity controls are similar for multi- and single-stage systems. Control methods include compressor capacity control, hot-gas bypass, or evaporator pressure regulators. Low pressure can affect control systems by significantly increasing the specific volume of the refrigerant gas and the pressure drop. A small pressure reduction can cause a large percentage capacity reduction.
System load usually cannot be reduced to near zero, because this results in little or no flow of gas through the compressor and consequent overheating. Additionally, high pressure ratios are detrimental to the compressor if it is required to run at very low loads. If the compressor cannot be allowed to cycle off during low load, an acceptable alternative is a hot-gas bypass. High-pressure gas is fed to the low-pressure side of the system through a downstream pressure regulator. The gas should be desuperheated by injecting it at a point in the system where it is in contact with expanding liquid, such as immediately downstream of the liquid feed to the evaporator. Otherwise, extremely high compressor discharge temperatures can result. The artificial load supplied by high-pressure gas can fill the gap between the actual load and the lowest stable compressor operating capacity. Figure 31 shows such an arrangement.
Microprocessor- and computer-based control systems are the norm for control systems on individual compressors as well as for whole-system control. Almost all screw compressors use microprocessor control systems to monitor all safety functions and operating conditions. These machines are frequently linked together with a programmable controller or computer for sequencing multiple compressors so that they load and unload in response to system fluctuations in the most economical manner. Programmable controllers are also used to replace multiple defrost time clocks on larger systems for more accurate and economical defrosting. Communications and data logging allow systems to operate at optimum conditions under transient load conditions even when operators are not in attendance.
Most lubricants are immiscible in ammonia and separate out of the liquid easily when flow velocity is low or when temperatures are lowered. Normally, lubricants can be easily drained from the system. However, if the temperature is very low and the lubricant is not properly selected, it becomes a gummy mass that prevents refrigerant controls from functioning, blocks flow passages, and fouls heat transfer surfaces. Proper lubricant selection and management is often the key to a properly functioning system.
In two-stage systems, proper design usually calls for lubricant separators on both the high- and low-stage compressors. A properly designed coalescing separator can remove almost all the lubricant that is in droplet or aerosol form. Lubricant that reaches its saturation vapor pressure and becomes a vapor cannot be removed by a separator. Separators that can cool the discharge gas condense much of the vapor for consequent separation. Using lubricants that have very low vapor pressures below 80°C can minimize carryover to 2 or 3 mg/kg. Take care, however, to ensure that refrigerant is not condensed and fed back into the compressor or separator, where it can lower lubricity and cause compressor damage.
In general, direct-expansion and liquid overfeed system evaporators have fewer lubricant return problems than do flooded system evaporators because refrigerant flows continuously at good velocities to sweep lubricant from the evaporator. Low-temperature systems using hot-gas defrost can also be designed to sweep lubricant out of the circuit each time the system defrosts. This reduces the possibility of coating the evaporator surface and hindering heat transfer.
Flooded evaporators can promote lubricant build-up in the evaporator charge because they may only return refrigerant vapor back to the system. In ammonia systems, the lubricant is simply drained from the surge drum. At low temperatures, this procedure is difficult if the lubricant selected has a pour point above the evaporator temperature.
Lubricant Removal from Ammonia Systems. Most lubricants are miscible with liquid ammonia only in very small proportions. The proportion decreases with the temperature, causing lubricant to separate. Ammonia evaporation increases the lubricant ratio, causing more lubricant to separate. Increased density causes the lubricant (saturated with ammonia at the existing pressure) to form a separate layer below the ammonia liquid.
Unless lubricant is removed periodically or continuously from the point where it collects, it can cover the heat transfer surface in the evaporator, reducing performance. If gage lines or branches to level controls are taken from low points (or lubricant is allowed to accumulate), these lines will contain lubricant. The higher lubricant density is at a lower level than the ammonia liquid. Draining lubricant from a properly located collection point is not difficult unless the temperature is so low that the lubricant does not flow readily. In this case, keeping the receiver at a higher temperature may be beneficial. Alternatively, a lubricant with a lower pour point can be selected.
Lubricant in the system is saturated with ammonia at the existing pressure. When the pressure is reduced, ammonia vapor separates, causing foaming.
Draining lubricant from ammonia systems requires special care. Ammonia in lubricant foam normally starts to evaporate and produces a smell. Operators should be made aware of this. On systems where lubricant is drained from a still, a spring-loaded drain valve, which closes if the valve handle is released, should be installed.
Stop Valves. These valves, also commonly called shutoff or isolation valves, are generally manually operated, although motor-actuated units are available. ASHRAE Standard 15 requires these valves in the inlet and outlet lines to all condensers, compressors, and liquid receivers. Additional valves are installed on vessels, evaporators, and long lengths of pipe so they can be isolated in case of leaks and to facilitate pumping out for servicing and evacuation. Sections of liquid piping that can experience hydraulic lockup in normal operation must be protected with a relief device (preferably vented back into the system). Only qualified personnel should be allowed to operate stop valves.
Installing globe-type stop valves with the valve stems horizontal lessens the chance (1) for dirt or scale to lodge on the valve seat or disk and cause it to leak or (2) for liquid or lubricant to pocket in the area below the seat. Wet suction return lines (recirculation system) should use angle valves or globe valves (with their stems horizontal) to reduce the possibility of liquid pockets and reduce pressure drop.
Welded flanged or weld-in-line valves are desirable for all line sizes; however, screwed valves may be used for 32 mm and smaller lines. Ammonia globe and angle valves should have the following features:
Soft seating surfaces for positive shutoff (no copper or copper alloy)
Back seating to allow repacking the valve stem while in service
Arrangement that allows packing to be tightened easily
All-steel construction (preferable)
Bolted bonnets above 25 mm, threaded bonnets for 25 mm and smaller
Consider seal cap valves in refrigerated areas and for all ammonia piping. To keep pressure drop to a minimum, consider angle valves (as opposed to globe valves).
Control Valves. Pressure regulators, solenoid valves, check valves, gas-powered suction stop valves, and thermostatic expansion valves can be flanged for easy assembly and removal. Alternative weld-in line valves with nonwearing body parts are available. Valves 40 mm and larger should have socket- or butt-welded companion flanges. Smaller valves can have threaded companion flanges.
A strainer should be used in front of self-contained control valves to protect them from pipe construction material and dirt.
Solenoid Valves. Solenoid valve stems should be upright, with their coils protected from moisture. They should have flexible conduit connections, where allowed by codes, and an electric pilot light wired in parallel to indicate when the coil is energized.
Solenoid valves for high-pressure liquid feed to evaporators should have soft seats for positive shutoff. Solenoid valves for other applications, such as in suction, hot-gas, or gravity feed lines, should be selected for the pressure and temperature of the fluid flowing and for the pressure drop available.
Relief Valves. Safety valves must be provided in conformance with ASHRAE Standard 15 and Section VIII, Division 1, of the ASME Boiler and Pressure Vessel Code. For ammonia systems, IIAR Bulletin 109 also addresses the subject of safety valves.
Dual relief valve arrangements allow testing of the relief valves (Figure 32). The three-way stop valve is constructed so that it is always open to one of the relief valves if the other is removed to be checked or repaired.
Sections of piping that can be isolated between hand valves or check valves can be subjected to extreme hydraulic pressures if cold liquid refrigerant is trapped in them and subsequently warmed. Additional pressure-relieving valves for such piping must be provided.
Insulation and Vapor Retarders
Chapter 10 covers insulation and vapor retarders. Insulation and effective vapor retarders on low-temperature systems are very important. At low temperatures, the smallest leak in the vapor retarder can allow ice to form inside the insulation, which can totally destroy the integrity of the entire insulation system. The result can significantly increase load and power usage.