Refrigeration systems for retail food applications fall under two general categories: remote and self contained. Remote refrigeration systems are used in retail establishments where the noise and/or heat of the condensing units from multiple cabinets and storage rooms would be objectionable (e.g., grocery stores, supermarkets). Remote systems can take advantage of cool ambient air and provide lower condensing temperatures, which allows more efficient operation of the refrigeration system. Additional discussion on the types of remote systems is presented in the section on Typical Systems.
Self-contained systems can be either air or liquid cooled. Air-cooled units reject condenser heat into the ambient environment, which can be the sales area of a store. Liquid-cooled systems use a refrigerant-to-fluid condenser. This system is discussed further in the section on Typical Systems.
Remote Design Considerations
Food stores sell all types of perishable foods that require a variety of refrigeration systems to best preserve and most effectively display each product. Moreover, the refrigerating system must be highly reliable because it must operate 24 h per day for 10 or more years, to protect the large investment in highly perishable foods. Temperature controls vary greatly, from a produce preparation room (which may operate with a wet coil) requiring no defrost to the ice cream refrigerator requiring induced heat to defrost the coil periodically.
When selecting refrigeration equipment to operate display refrigerators and storage rooms for food stores, consider (1) cost/space limitations, (2) reliability, (3) maintainability and complexity, and (4) operating efficiency. Solutions span from the very simple (one compressor and associated controls on one refrigerator) to the complex (central refrigeration plant operating all refrigerators in a store).
Suction Groups. Various refrigerators have different evaporator pressure/SST temperature requirements. Produce preparation areas and meat wrapping rooms have the highest design temperature requirements of all the refrigeration loads in a typical supermarket, and may approach the suction pressures used in air-conditioning applications. Ice cream display units have the lowest design temperature requirements. Open vertical ice cream display freezers may have suction pressures corresponding to temperatures as low as −40°F, but they are only found in older stores in need of remodel. New store designs use either vertical glass door or single-deck island display freezers for ice cream display. These two styles have suction pressures corresponding to approximately −22°F. All other refrigerators and coolers fall between these extremes.
Refrigeration Loads. Refrigerator requirements are often given as refrigeration load per unit length. A lower value is sometimes allowed for more complex parallel systems, because peak loads are smaller with the reserve capacity present in multiple-compressor rack systems, making refrigerator temperature recovery after defrost less of a strain than on a single-compressor system.
Published refrigerator load requirements allow for extra capacity for temperature pulldown after defrost, per ASHRAE Standard 72. Ratings for open multideck refrigerators are typically for shelves in the flat position. Door cases follow the door opening sequence found in Standard 72. Heavily shopped stores may use more energy. The industry considers a standard store ambient condition to be 75°F and 55% rh, which should be maintained with air conditioning. Part of this air-conditioning load is carried by the open refrigerators, and credit for heat removed by them should be considered in sizing the air-conditioning system.
Equipment Selection. The designer matches the load requirements of the refrigerator lineups to the capacity of the chosen refrigeration system. Manufacturers publish load ratings to help match the proper refrigeration system with the fixture loads. For single-compressor applications only, the ratings can be stated (for selection convenience) as the capacity the condensing unit must deliver at an arbitrary suction pressure (evaporator temperature). In general, manufacturers of display refrigerators use ASHRAE Standard 72, which specifies standard methods of testing open and closed refrigerators for food stores. These standards establish refrigeration load requirements at rated ambient conditions of 75°F and 55% rh in the sales area with specific door-opening patterns. Display refrigerators for similar applications are commercially available from many manufacturers. Manufacturers’ recommendations must be followed to achieve proper results in both efficiency and product integrity.
Appropriate equipment selection depends on several factors.
Life-Cycle Cost. The total cost elements of the refrigeration system include not only the purchase price but also the operating cost (energy), cost of installation and commissioning, cost of maintenance and service, and the environmental cost.
Space Limitations. Store size, location, and price per square foot play a role in determining the type and location of equipment. Locations can include an equipment room at the back of the store, on a mezzanine, in a machine house on the roof, or distributed throughout or on top of the store.
Refrigerants and Fluids. Selection of a suitable refrigerant for food stores has been affected by international concern about the potential negative effects on the environment, particularly refrigerants’ ozone depletion potential (ODP) and global warming potential (GWP). Under international treaty, chlorofluorocarbon refrigerants are no longer produced, and hydrochlorofluorocarbon (HCFC) refrigerants (e.g., R-22) are being phased out under schedules that vary by country.
In the United States, R-22 and its blends are still used in existing equipment, but manufacture and import for use in new equipment stopped in 2010, and manufacture and import for servicing existing equipment will be banned in 2020.
In the United States and most other countries, the majority of new systems manufactured after January 2010 used some form of hydrofluorocarbon (HFC) refrigerants, such as R-404A, R-134a, and R-507.
At the time of writing, there have been several significant changes and reversals in the United States regarding the status Environmental Protection Agency (EPA) regulations affecting the use of certain high-GWP refrigerants that have been commonly used in commercial refrigeration applications.
Background and Timeline. A historical overview of actions over the past few years follows.
June 25, 2013: Presidential Climate Action Plan released, which specifically referenced the future of commonly used HFC refrigerants. The plan supported a phasedown (not phaseout) of production and consumption of HFC refrigerants in the context of the Montreal Protocol over the next 30 years. Additionally, it called for immediate efforts to move away from HFCs to more environmentally friendly alternatives. This was to be implemented by the EPA using the Significant New Alternatives Policy (SNAP).
August 5, 2014: EPA original proposal for changing status of certain refrigerants used in specific applications. The change of status was from acceptable for use (listed) to unacceptable for use (de-listed) in certain and specific applications.
July 20, 2015: The EPA issued its final rule changing the status of certain refrigerants used in specific applications, using Section 612 of the Clean Air Act as the source of its statutory authority to implement these rules and changes. Its changes included the following:
Effective June 20, 2016: because of their elevated GWPs, HFCs R-404A and R-507 were delisted for refrigerant conversions in supermarket and remote condensing units applications.
Effective January 1, 2017: because of their elevated GWPs, HFCs R-404A and R-507 were delisted for all new supermarket applications.
Effective January 1, 2018: because of their elevated GWP, HFCs R-404A and R-507 were delisted for all new remote condensing unit applications.
In February 2017, a suit was brought against the EPA in the U.S. Court of Appeals (D.C. Circuit), stating that section 612 of the Clean Air Act did not grant the EPA the statutory authority to delist refrigerants with global warming potential. In August 2017, the court decided for the petitioner and against the EPA, resulting in a nullification of all regulations involving the delisting of HFC refrigerants.
A petition was filed with the D.C. Circuit Court of Appeals for a rehearing of the decision, but in January 2018, the court announced its decision to deny this petition.
As a result of the proposed regulatory changes, commercial refrigeration equipment manufacturers dedicated significant budgetary expenditures for research and development of equipment compatible with, and rated for, lower-GWP alternative refrigerants. The available nonnatural refrigerant choices have been limited to HFC blends or HFC/HFO blends with lower GWPs. Although the list of available HFC blends with lower GWP is long, R-407A has become the predominant choice in new supermarket applications (GWP approximately 50% of R-404A and R-507). Newer HFC/HFO blends such as R-448A, R-449A, and R-449B (with GWPs approximately 32% of R-404A and R-507) are seeing interest in some new supermarket applications.
Future Legislation. A bill (The American Innovation and Manufacturing Act) has been introduced in the U.S. Senate that, if passed, would entitle the EPA to phase down HFCs used in refrigeration and air conditioning, in consultation with the HVAC&R industry. The proposed bill would operate in accordance with the guidelines set forth in the 2015 Kigali Amendment to the Montreal Protocol. Although the United States has not ratified the Kigali Amendment at the time of this writing, the U.S. State Department issued a statement (November 23, 2017) that is had initiated the process to consider ratification of the amendment.
Use in the Field. Some natural refrigerants see limited use in the marketplace (ASHRAE 2009). Carbon dioxide is used in transcritical and cascade systems, and as the secondary refrigerant in secondary refrigerant systems. R-290 (propane) has been used in self-contained refrigerated display cases since 2012. In some European countries, R-290 and R-717 (ammonia) are used as primary refrigerants in secondary systems. For details on these and other refrigerants, see ASHRAE Standard 34.
Retrofit recommendations have been developed by equipment and refrigerant manufacturers to guide stores in converting from ozone-depleting and/or high-GWP substances to more environmentally friendly alternatives. Many of the new refrigerants produce discharge temperatures in higher ranges that could lead to possible chemical decomposition. System manufacturers may require compressor options such as liquid injection or demand cooling to keep discharge temperatures within acceptable levels. Close consultation with equipment manufacturers is necessary to stay current on this issue.
Compressor performance and material compatibility were two major concerns in selecting new refrigerants to replace chlorinated refrigerants. Neoprene seals swell in the presence of refrigerants, and at higher rates when chlorinated refrigerants are present. Thus, after converting a system from a CFC or HCFC to an HFC blend or HFC/HFO blend, neoprene seals will effectively shrink (swell less). Industry recommendations require replacing all neoprene seals when undertaking a refrigerant conversion.
Secondary loop systems and fluid-cooled, self-contained systems require appropriate secondary fluids, because viscosity and heat transfer properties directly affect system performance. Secondary fluids are often divided into two categories: single phase and two phase. Single-phase secondary fluids absorb heat by means of sensible heat transfer, meaning that they change temperature as heat is added. Examples include water; propylene and ethylene glycols; and salt solutions or brines such as potassium formate, potassium acetate, sodium chloride, and calcium chloride. Two-phase secondary fluids absorb heat by means of changing phase rather than changing temperature. The phase change may be from solid to liquid, or from liquid to vapor. Examples include ice slurries (solid to liquid) and CO2 (liquid to vapor). Ice slurries typically comprise two materials, either water/glycol or water/ethanol mixtures; application of these materials has been limited. CO2 has seen wider use in both commercial and industrial applications. For further information, see the sections on specific operations and applications; additional information on selection of single-phase secondary fluids can be found in Chapter 13. More information on refrigerants, secondary fluids, and their properties can be found in the 2017 ASHRAE Handbook—Fundamentals.
Refrigerant Lines. Sizing liquid and suction refrigerant lines is critical in most refrigeration installations, because of the typically long horizontal runs and frequent use of vertical risers. Correct liquid-line sizes are essential to eliminate unnecessary frictional pressure loss, which could hinder the system’s ability to provide a full feed of liquid to the expansion valve. In addition, oversizing must be avoided so the system does not contain unnecessary refrigerant charge; not only will this reduce the carbon footprint of the equipment, but it ensures that the liquid receiver provided with the equipment will be of sufficient capacity to allow for a complete system pumpdown.
Proper suction-line sizing is required to ensure adequate oil return to the compressor without excessive pressure drop. Oil separates in the evaporator and moves toward the compressor more slowly than the refrigerant. Unless the suction line is properly sized and installed, oil can accumulate in low places, causing problems such as compressor damage from oil slugging or insufficient lubrication. Undersized suction lines result in excessive pressure drop between the refrigerated fixture and the compressor(s), requiring the compressor(s) to operate at a suction pressure lower than design to maintain the design refrigerated fixture temperature, thereby reducing reduced compressor (and system) capacity. To prevent these problems, horizontal suction lines must pitch down as gas flows toward the compressor, the bottoms of all suction risers must be trapped, and refrigerant speed in suction risers must be maintained according to piping practices described in Chapters 1 and 2. To overcome the larger pressure drop necessary in suction risers, suction lines may be oversized on long horizontal runs; however, they still must pitch down toward the compressor for good oil return.
The modern supermarket is a complex system, and will be subject to periods where the actual load is lower than design. In particular, because use of glass door refrigerators is widespread, limited or nonexistent customer activity during off-peak hours may result in extended periods where the doors remain closed and result in below-design load conditions. Open cases that use a night curtain also experience low loads during off hours. These circumstances could result in the suction riser being oversized at low load, impeding oil return (because of reduced refrigerant velocity). A double suction riser is an option in applications where low/reduced load might impede oil return.
Manufacturers’ recommendations and appropriate line sizing charts should be followed to avoid adding heat to either suction or liquid lines. In large stores, both types of lines can be insulated profitably, particularly if subcooling is used.
Refrigeration systems in use today can generally be categorized into one of the following types: single (a single compressor connected to one or more evaporator loads), multiplex (or parallel compressor) rack, loop, distributed, and secondary refrigerant. Each type has distinct advantages and disadvantages, and may be chosen based on the weight a designer assigns to the different components of equipment life-cycle cost.
The most common compressors used in a typical supermarket refrigeration system include reciprocating, scroll, and screw compressors, which are discussed in Chapter 38 of the 2020 ASHRAE Handbook—HVAC Systems and Equipment. Planning load management and sizing the compressors are very important to a successful refrigeration installation. Factory assembly of the necessary compressor systems with either a direct air-cooled condenser or any style of remote condenser is common practice. Both single and parallel systems can be housed, prepiped, and prewired at the factory. The complete unit is then delivered to the job site for placement on the roof or beside the store.
Many supermarket designers choose to have compressor equipment installed in factory-prefabricated housing, commonly called a mechanical center, to reduce real estate costs for the building. The time requirements for installation of piping and wiring may also be reduced with prefabrication. Most of the rooms are modular and prewired and include some refrigeration piping. Their fabrication in a factory setting should offer good quality control of the assembly. They are usually put into operation quickly upon arrival at the site.
Single System. A single-compressor/single-evaporator system is sometimes referred to as a conventional system. Each compressor may be piped to an individual condenser, or several single compressors may be piped to a larger condenser with multiple circuits. Some single-compressor systems are connected to two or more evaporator systems, in which case each evaporator system uses its own liquid and suction lines and is controlled independently.
A solid-state pressure control for single systems can help control excess capacity when ambient temperature drops. The control senses the pressure and adjusts the cutout point to eliminate short cycling, which ruins many compressors in low-load conditions. This control also saves energy by maintaining a higher suction pressure than would otherwise be possible and by reducing overall running time. Some applications might benefit from the addition some form of compressor capacity control, to more closely match the compressor capacity to the actual load at any given point in time. Some of the more common methods are (1) mechanical compressor unloading, (2) digital unloading for semihermetic or scroll compressors, and (3) variable-frequency drive (VFD).
Multiplex System. Another common refrigeration technique couples two or more compressors in parallel (multiplex compressor rack), piped together with a common suction manifold (header) and common discharge manifold (header). The compressors share a common oil management system and usually operate connected to one or more large condensers. The condensers are usually remote air cooled or evaporative cooled, but they can also be built as part of the compressor rack assembly. The multiplex rack system has several evaporator systems, each individually controlled and individually piped to the compressor rack’s common liquid and suction line.
Multiple-evaporator systems are usually designed such that each evaporator system operates at a different saturated suction temperature (pressure). Because all of the evaporator systems are connected to one common suction manifold, the compressors are forced to operate at the saturated suction temperature (pressure) required to maintain the design temperature of the coldest operating evaporator system. The obvious result is a sacrifice in compressor efficiency. Running all the equipment at the low suction pressure required for ice cream (on low-temperature systems) or for fresh meat (on medium-temperature systems) causes all the other compressors to operate at lower suction pressures than are necessary. To overcome this inefficiency, large parallel systems frequently isolate the suction piping from the lowest operating suction group (such as ice cream on low-temperature compressor racks, or fresh meat on medium-temperature compressor racks) and connect it to an independent satellite compressor. The satellite compressor has its own independent suction connection to the specified load, but shares the rack system’s common discharge piping and oil management system. Similarly, split-suction manifolds are often used for larger loads where two different suction pressure groups are combined and connected to a single compressor rack. The compressors suction groups are isolated, and piped to the suction header of their respective compressor group, but all compressors discharge into a common header and share the oil management system.
Consult manufacturers to determine the appropriate suction pressure (temperature) at the fixture and the load that each system adds to the total. The multiplex rack system must then be designed to deliver the total of all the loads at a common suction pressure no higher than the lowest system pressure requirement less the suction line pressure drop. Individual evaporator systems designed to operate at suction pressures higher than the common must use some means of suction line regulation to prevent higher-temperature evaporators from operating at temperatures below what is necessary to maintain product temperatures.
Suction pressure can be regulated in one of two ways:
Mechanical evaporator pressure regulating (EPR) valves. When sized according to manufacturers’ recommendations, these valves cause minimal (0.5 psi) pressure drop in the full-open position. When regulating, they create pressure drop to maintain fixtures at their design condition above the common rack suction pressure. EPRs come in two main designs: (1) larger pilot-operated valves, normally open and using discharge pressure to pilot the valve; or (2) internally piloted, with the controlled pressure (upstream or evaporator pressure) used to pilot the valve. Although each type has advantages and disadvantages, electric valves are more popular because of their ability to communicate with the rack’s energy management system.
Electric evaporator pressure regulating (EEPR) valves. These electronically controlled electric step motor suction regulators do not maintain a constant evaporator pressure as a true EPR valve would, and therefore they are not technically true evaporator pressure regulators. They respond to discharge air temperature, which is sensed by a discharge air temperature sensor and relayed to the electronic controller. As required, the controller throttles the EEPR to a more open position (lowering evaporator pressure) or more closed position (raising evaporator pressure), to maintain a constant evaporator discharge air temperature. In actuality, they maintain a constant evaporator discharge air temperature by varying the evaporator pressure (and corresponding refrigerant saturated suction temperature in the evaporator), in response to the changes in the refrigerated load at any given point in time.
In conventionally piped multiplex systems (individual liquid and suction lines for each evaporator system), EPRs, EEPRs, and liquid solenoid valves can be installed either at the rack header of near the refrigerator lineups.
The suction gas temperature leaving display fixtures should be superheated to ensure that only vapor enters the compressor suction intake. Be careful to avoid excessive temperature of suction vapor returning to the compressor, because this yields a less dense vapor and reduces the compressor’s mass flow pumping capacity. This is particularly crucial on low-temperature fixtures, because the suction line vapor temperature increase from heat gained from the store ambient (or outdoor ambient, for remote roof piping runs) can be substantial, not only adversely affecting compressor capacity, but also elevating compressor discharge vapor temperature. This must be considered for system design.
One method of ensuring that suction vapor temperature is not abnormally high is to simply set the system thermostatic expansion valves (TEVs) to their design superheat set point. If the TEV is underfeeding, the resulting high superheat at the evaporator outlet contributes to higher-than-normal suction vapor temperature at the compressor inlet. In addition, using sufficiently sized insulation on the suction piping between the refrigerated fixture outlet and the compressor inlet can help keep the suction vapor temperature at acceptable temperatures. If the suction vapor temperature is too high after these two practices are followed, then a desuperheating expansion valve can be used to inject a quantity of saturated liquid refrigerant into the suction line upstream of the compressor inlet, to lower the suction vapor temperature. This method for controlling liquid injection can maintain either a constant suction vapor temperature or a constant discharge vapor temperature.
To ensure proper thermostatic expansion valve operation, the engineer should verify that liquid entering the fixture is subcooled. For systems without a mechanical subcooler, some amount of natural subcooling is required to ensure that the liquid entering the thermostatic expansion valve is vapor free. For system designs with mechanical subcooling, liquid-line insulation is required to ensure that the liquid entering the thermostatic expansion valve is at the design liquid temperature condition.
Parallel operation is also applied in two-stage or compound systems for low-temperature applications. Two-stage compression includes interstage gas cooling before the second stage of compression to avoid excessive discharge temperatures. A multiplex rack system with multiple compressors of equivalent capacity is called an even parallel system; with compressors of different capacities, it is called an uneven parallel system.
Parallel compressor systems must be designed to maintain proper refrigerator temperatures under peak summer load. During the rest of the year, store conditions can be easily maintained at a more ideal condition, and refrigeration load is lower. In the past, refrigeration systems operated at 90°F condensing conditions or above to maintain enough high-side pressure to feed the refrigerated display fixture expansion valves properly. When outdoor ambient conditions allow, current technology allows the condensing temperature to follow the ambient down to about 70°F or less. When proper liquid-line piping practices and thermostatic expansion valve (TEV) or electric expansion valve (EEV) selection guidelines are followed, the expansion valves feed the evaporators properly under these varying condensing pressures (temperatures) between the summer and winter conditions.
TEV/EEV capacity is based on (1) the available liquid refrigerant ΔP across the valve’s port, with the lower condensing temperature (pressure) in the winter reducing valve capacity, and the higher condensing temperature (pressure) in the summer increasing valve capacity; and (2) the temperature of the liquid refrigerant entering the valve. In applications without mechanical subcooling, the reduced liquid refrigerant temperature during lower-condensing-temperature operation increases valve capacity, closely offsetting the capacity reduction caused by the lower condensing pressure. Likewise, the higher liquid refrigerant temperature during higher-condensing-temperature operation decreases valve capacity, closely offsetting the capacity increase caused by the higher condensing pressure. In applications where a mechanical subcooler is used, the constant liquid temperature under both lower- and higher-condensing-temperature operation does not counteract the varying condensing pressure in these two ambient extremes. As such, the lower condensing pressure during lower-condensing-temperature operation results in a substantial capacity loss to the TEV or EEV. TEV/EEV capacity should be verified in both summer and winter design conditions to ensure that adequate capacity is available in the winter (lower condensing) condition, and capacity is not excessive in the summer (higher condensing) condition.
Multiple compressors may be controlled or staged based on a drop in system suction pressure. If the compressors are equal in size, a mechanical device can turn off one compressor at a time until only one is running. The suction pressure will be perhaps 5 psi or more below optimum. Microprocessors are the standard control for multiple compressor systems and offer the option of remote control and system operation for all types of compressors, managing compressor cycling and run time for each compressor, and ensuring the common suction pressure is optimized. Satellite compressors can be controlled accurately with one control that also monitors other components, such as oil pressure and alarm functions. To match changing evaporator loads, rack capacity can be varied by cycling compressors, varying the speed of one or more compressors, and/or unloading compressor cylinders by closing valves or moving ports on screw compressors.
Unequally sized compressors can be staged to obtain more steps of capacity than is possible with the same number of equally sized compressors. Figure 23 shows seven stages of capacity from a 5, 7, and 10 hp compressor parallel arrangement. In addition, using a lead compressor with digital unloading capability further enhances the microprocessor controller’s ability to maintain precisely consistent common suction pressure.
In the multiplex system design, a typical supermarket includes one or more medium-temperature parallel compressor systems for meat, deli, dairy, and produce refrigerators and medium-temperature walk-in coolers. The system may have a satellite compressor for meat or deli refrigerators, or all units may have a single compressor. Energy efficiency ratios (EERs) typically range from 8 to 9 Btu/h per watt for the main load. Low-temperature refrigerators and coolers are grouped on one or more parallel systems, with ice cream refrigerators on a satellite or on a single compressor. EERs range from 4 to 5 Btu/h per watt for frozen-food units to as low as 3.5 to 4.0 Btu/h per watt for ice cream units. Cutting and preparation rooms are most economically placed on a single unit because the refrigeration EER is nearly 10 Btu/h per watt. Air-conditioning compressors are also separate because their EERs can range up to 11 Btu/h per watt (Figure 24).
Controls. Refrigerant systems increasingly use electronic microprocessor control systems. The microprocessor controls all of the major components and valves in the refrigeration system. Algorithms control evaporator temperatures, defrosts, condensers, and compressors, and optimize performance and reduce energy. Many systems allow remote computer access and data logging. Systems can be designed with a central process or with a supervisor that monitors individual control boards for the components. Typically, the individual control boards can maintain operation if the supervisor fails.
Loop Systems. A loop system is simply multiplex rack system with a variation in the piping layout. Rather than each evaporator system (or circuit) having its own individual liquid and suction line connecting it to the compressor rack, a single suction and liquid loop is piped out to the store for each common suction pressure group. Individual branch circuits are then connected to the loop near the fixtures. If EPRs, EEPRs, and solenoid valves are used, they must be installed in the branch circuit, near the refrigerator lineups for easy access.
Secondary Loop Systems. In secondary coolant systems, heat is removed from refrigerated spaces and display cabinets by circulating a chilled fluid in a secondary loop cooled by a primary refrigeration system. Fluid circulation is typically provided by a centrifugal pump(s) designed for the flow rate and pressure drop required by the system load and piping arrangement.
Performance Characteristics. Secondary coolant systems have several advantages. Because primary refrigeration piping is located almost wholly within the machine room, the amount of piping and refrigerant required can be reduced by as much as 80 to 90%. Because field piping of the primary system is typically limited to only a few joints, the majority of the primary system piping joints are factory installed. Factory-installed joints are generally of higher quality than field-installed joints, because they are formed in controlled conditions by skilled labor, using nitrogen and a variety of pressure-testing and leak-identification methods. Higher-quality joints combined with a lower refrigerant charge can significantly lower refrigerant leakage rates, reducing the environmental effects associated with the primary refrigerant. The compressors and evaporator are close coupled, so suction line pressure losses and heat gains are minimized, enhancing system performance. Secondary coolant systems are inherently less complex than direct-expansion types, requiring fewer and less complicated valves and control devices. Less expensive nonmetallic piping systems and components can also be used for the secondary fluid piping circuit if that system’s operating pressure is low (typically less than 60 psig). Service of the refrigeration system is basically limited to the machine room area, and maintenance costs can be reduced. Because a fluid loop is used, thermal storage may be applied to reduce peak power demands and take advantage of lower off-peak utility rates. Ambient or free cooling may be used in areas with colder climates. Secondary systems have reduced refrigerant charge and can use primary refrigerants not typically suitable for direct-expansion systems with large refrigerant charge requirements, including ammonia and hydrocarbons (where local codes allow).
Disadvantages of secondary systems include thermodynamic loss inherent in the additional step of heat transfer in the chiller, as well as the energy consumed by the fluid pump and the heat it transfers to the circulating fluid. Insulation must also be applied to both coolant supply and return lines to minimize heat gain.
Secondary Fluid Selection. The secondary fluid is critical to system efficiency because viscosity and heat transfer properties directly affect system performance. Characteristics of secondary fluids are discussed in the Design Considerations section, in the subsection on Refrigerant and Fluids. Additional information regarding selection of single-phase secondary fluids can be found in Chapter 4 of this volume, and physical properties of selected fluids can be found in Chapter 31 of the 2017 ASHRAE Handbook—Fundamentals.
For medium-temperature commercial refrigeration applications, the chosen secondary fluid is most often the single-phase fluid inhibited propylene glycol. Propylene glycol systems operate at low pressure and are designed in the same manner as hydronic systems for air-conditioning applications. Flow rates are controlled using various flow control valves and/or pump control strategies. System components and heat exchangers in the refrigerated spaces must be carefully designed to avoid both high flow rates and high pressure drops, which can significantly affect pumping power and system energy consumption. Figures 25 and 26 illustrate basic schematics of a conventional direct-expansion system and a system designed for a single-phase secondary coolant such as propylene glycol.
Low-temperature secondary coolant systems using potassium-based brines have been used since the 1990s; however, concerns remain about material compatibility and corrosion with materials common to commercial refrigeration equipment construction. Recently, plastic piping networks have been used to reduce corrosion issues. CO2 is also used as a secondary coolant, operating at a higher pressure; concerns about material compatibility have been eliminated and energy consumption has been improved because of the two-phase operation of CO2 and the associated dramatically lower mass flow rates, which reduce both pumping power and the distribution line sizes. In these systems, the CO2 is pumped from the refrigeration system to the evaporators as a pure liquid and is only partially evaporated in heat exchangers inside the display cases and walk-ins. The liquid/vapor mixture returns to the refrigeration system. Figure 27 shows a basic schematic of secondary system designed for use with CO2.
Heat Exchangers. Heat can be removed from the secondary fluid using a chiller of any design, but often a plate type is used for highest efficiency. Coils engineered to remove heat effectively from refrigerated spaces are generally designed differently from those for volatile refrigerants. For single-phase applications, liquid should enter the bottom of the coil, leave at the top, and be circuited to avoid trapping air. Drain and vent valves must also be equipped to assist air removal and service.
System Application. Typically, the entire refrigeration system for supermarkets is divided into two temperature groups: low (frozen food, ice cream) and medium (meat, dairy, produce, preparation rooms). To increase efficiency, the systems may be further subdivided, though often at a higher capital cost. Temperature is controlled by regulating flow using a balance valve, or cycling flow around a set point using a solenoid valve. Piping may be in circuited or loop arrangement, or a combination of the two. Circuited systems have the advantage of containing most of the control valves in a central location, but at the cost of a greater amount of installed piping.
Charge and Leak Rate Reduction. Secondary coolant systems have several advantages, the most prominent being reduction of primary refrigerant charge and resulting leakage rates. Because primary refrigerant piping is located almost wholly within the machine room, the amount of refrigerant and refrigeration piping required can be reduced by 60 to 90%. Because field piping of the primary system is typically limited to only a few joints, most of the primary system piping joints are factory installed; these joints are generally of higher quality than field-installed joints, because they are formed in controlled conditions by skilled labor, using nitrogen and a variety of pressure-testing and leak-identification methods. Higher-quality joints combined with a lower refrigerant charge can significantly lower refrigerant leakage rates, which reduces the environmental effects associated with the primary refrigerant.
Performance Characteristics. The compressors and evaporator are close coupled, so suction line pressure losses and heat gains are minimized, enhancing system performance. Secondary coolant systems are inherently less complex than direct-expansion types, requiring fewer and less complicated valves and control devices. Less expensive nonmetallic piping systems and components can also be used, because the system operating pressure is low, typically less than 60 psig. Service of the refrigeration system is basically limited to the machine room area, and maintenance costs can be reduced. Because a fluid loop is used, thermal storage may be applied to reduce peak power demands and take advantage of lower off-peak utility rates. Ambient or free cooling may be applied in areas with colder climates. Secondary systems also can use primary refrigerants not typically suitable for direct-expansion systems, including ammonia and hydrocarbons.
Disadvantages of secondary systems include thermodynamic loss inherent in the additional step of heat transfer in the chiller, as well as the energy consumed by the fluid pump and the heat it transfers to the circulating fluid. Insulation must also be applied to both coolant supply and return lines to minimize heat gain. System first cost is higher, though this can be offset by refrigerant charge reductions and reduced system maintenance.
Systems Using CO2 as a Refrigerant. Carbon dioxide has gained renewed use as a refrigerant in commercial refrigeration, domestic and commercial water heating, and mobile air conditioning. Widely applied in European supermarket systems, and to a lesser degree in North America, CO2 can be used in a number of system types and configurations. Primary drivers for use of CO2 in refrigeration systems include reduced emission of global warming gases, higher volumetric cooling capacity (which results in reduced compressor displacement and smaller pipe diameters), and excellent heat transfer properties. In addition, as a two-phase heat transfer secondary fluid, it allows smaller pumps and piping. System operating pressure has been considered the primary barrier to implementation of this natural refrigerant; however, the introduction of R-410A systems and alternative materials has largely overcome this barrier.
CO2 systems are generally divided into two categories: subcritical and transcritical. The critical point is the point on a phase diagram at which the liquid and vapor phases of a substance have the same density (i.e., they are indistinguishable). The critical temperature is the maximum temperature at which a vapor can be converted into a liquid by increasing the vapor’s pressure. If the vapor is above the critical temperature, it cannot exist in the liquid state. Although every refrigerant has a critical point, the commonly used refrigerants (other than CO2) never come close to conditions where the system is operating near the critical point. For example, the critical temperature for R-22 is 205.1°F, with a corresponding pressure of 723.7 psia. This condition will never exist in the normal operation of an R-22 system. In contrast, the critical temperature for CO2 is 87.9°F, with critical pressure at about 1070 psia. Therefore, a CO2 system operating with an air-cooled condenser, selected with a 10°F TD, will reach its critical temperature when the outdoor ambient temperature reaches 77.9°F. This property of CO2 does not allow many locations to use CO2 without planning for transcritical operation.
Most subcritical systems use cascading, with CO2 in the lower cascade and an HFC, HFO/HFC blend, or a natural refrigerant (e.g., HC, ammonia) in the upper cascade to reject heat to ambient. Transcritical systems typically use CO2 as the only refrigerant contained in the system, and reject heat directly to ambient, albeit at much higher pressures. CO2 systems can be configured in a wide array of combinations with other systems, depending on application, including single-phase and CO2 secondary systems.
Cascade Systems. CO2 cascade systems are most often subcritical systems which provide low-temperature (LT) refrigeration and reject heat to an upper cascade. DX cascade-subcritical CO2 systems are similar to a typical vapor compression cycle, with CO2 as the refrigerant; the difference is that the heat transfer capacity necessary to condense the high-temperature/high-pressure CO2 vapor leaving the compressor into a high-pressure/high-temperature liquid is provided by an HFC refrigeration system, with the heat transfer occurring in a cascade evaporator/condenser. Electric expansions valves (EEVs) are the preferred method of expansion device used in all CO2 DX systems. The upper cascade system may be dedicated to the low-temperature (LT) CO2 system only, as shown in Figure 28, or it may provide medium-temperature refrigeration to other loads. A common example of a combined system is one where the CO2 receiver of the subcritical system also functions as a liquid/vapor separator for a medium-temperature CO2 secondary system, though many variations and combinations have been successfully used.
The system in Figure 29 combines CO2 secondary liquid overfeed and CO2 LT DX cascade-subcritical CO2. The MT liquid overfeed portion requires the receiver to be of the liquid/vapor separator design. Liquid from the separator is pumped to both the LT and MT evaporator systems. The MT evaporator systems operate as flooded evaporators, using a thermostat and liquid solenoid valve to maintain fixture temperature. The LT evaporator systems are fitted with EEVs, and operate as DX evaporators. Temperature control can be accomplished with a thermostat and liquid solenoid valve, or with an EEPR. The liquid/vapor mixture leaving the MT evaporators is piped into the top of the liquid/vapor separator, where the liquid mixes with the existing liquid in the vessel, and the vapor is eventually drawn to the colder surface of the condenser/evaporators. Discharge vapor leaving the LT compressors is piped to the inlet of the condenser-evaporators, where the vapor changes state into a liquid. The liquid then enters the liquid/vapor receiver.
Advantages of cascade systems include smaller line sizes and slight improvements in system efficiency compared to conventional technologies. Also, compared to transcritical CO2 systems, cascade systems operate at much lower CO2 pressures. System first cost is generally considered the primary disadvantage.
Transcritical Systems. CO2 transcritical systems operate both above and below the critical pressure and are used for refrigerating medium-temperature systems and rejecting heat directly to ambient. Low-temperature refrigeration can be accomplished by applying the transcritical system as the upper cascade in a cascade system, or by applying two-stage (compound) systems. Two-stage compressors are also available.
Figure 30 shows a two-stage (compound) compression system that compresses the CO2 vapor from the low-temperature evaporator systems in two stages, allowing for greater compressor efficiency by reducing the operating compression ratio of all compressors. Vapor from the LT evaporator systems enters the LT compressors, which raise the pressure from low to intermediate, corresponding with the MT vapor pressure. Discharge vapor from the LT compressors flows through an oil separator and then enters the suction manifold to the MT compressors, where it joins vapor leaving the MT evaporator systems, and the entire system mass flow then enters the MT compressors.
Discharge vapor leaving the MT compressors flows through an oil separator before entering the gas cooler. If the ambient conditions are such that the saturated condensing temperature (SCT) is less than 87.9°F, the CO2 vapor will condense into a liquid. In this condition, the system will operate similarly to a typical vapor compression cycle, with the liquid leaving the gas cooler flowing into the receiver, and supplying the liquid header as needed. When the SCT is above 87.9°F, the gas cooler transfers heat from the discharge vapor without a change of state taking place. The refrigerant then enters the flash tank, where the flash tank high-pressure control valve vents the high pressure to the suction manifold of the MT compressors. This allows sufficient reduction in pressure/temperature to move the refrigerant below the critical point, and allows the CO2 to revert to a saturated condition, with both liquid and vapor phases present. From here, the liquid is supplied to the liquid header, supplying liquid to the various liquid feeds to each evaporator system as needed.
Gas coolers rejecting heat to ambient can operate at pressures of 1200 to 1600 psia and must be made of higher-strength materials such as steel or stainless steel, or use microchannel technologies suitable for high-pressure operation. Recently available copper-iron alloy piping might offer alternatives in the future. Gas coolers are also well suited for water heating applications and have been widely used for this purpose in Asia.
Advantages of transcritical systems include eliminating the need for HFC systems or other natural refrigerants that are toxic and/or flammable, and increased availability of heat for heat reclaim systems. Disadvantages include the following:
Because of the higher condensing temperature and pressure, the higher compression ratio results in a less efficient compression process.
Refrigerant quality (% vapor) after the expansion process is greater, so greater mass flow is required to provide the same mass flow of liquid at the evaporator inlet.
Some MT compressor capacity is dedicated to bringing the transcritical refrigerant mass in the flash tank back into a subcritical state, thereby reducing system efficiency and requiring extra compressor capacity to meet the design load condition, beyond what would be required for subcritical operation. As such, this system is better suited to climates where transcritical operation is likely to be limited.
Higher first cost.
Work continues on improving efficiency of transcritical operation, including using parallel compressor systems for flash compression, and using ejectors to transfer medium-temperature suction gas to the flash tank without using a compressor.
Distributed Systems. Distributed systems eliminate the long lengths of piping needed to connect display fixtures with compressor racks in back-room parallel compressor systems. The compressors are located in cabinets, close-coupled to the display refrigerator lineups, placed either at the end of the refrigerator lineup or, more often, behind the refrigerators around the store’s perimeter.
Distributed systems are typically located in the store to provide refrigeration to a particular food department, such as meat, dairy, or frozen food. With this arrangement, the saturated suction temperature (SST) for each rack closely matches the evaporator temperature of the display refrigerators and walk-in coolers. This is not always the case for parallel-rack direct-exchange (DX) systems, because a single rack often serves display refrigerators with three or four different evaporator temperatures, and the parallel-rack DX system must operate at an SST that satisfies the requirements of the lowest-temperature one connected. Better evaporator temperature matching with distributed systems can decrease the system’s overall energy consumption.
Distributed systems typically require a much lower refrigerant charge than parallel-rack DX systems, because of the former’s shorter suction and liquid lines to display refrigerators. Refrigerant piping to remote condensers can be eliminated by using a closed-loop water-cooled system.
Close-coupling the refrigerated display fixtures to the common suction manifold of the distributed system has other ramifications for energy consumption. Shorter suction lines mean that pressure drop between evaporators and the compressor suction manifold is less than with parallel-rack DX systems, so the SST of distributed systems is closer to the display refrigerator evaporator temperature: about 1 to 2°F less than refrigerator evaporator temperature, compared to 2 to 4°F difference with a parallel-rack DX. Shorter suction lines also mean less heat gain.
For a closed-loop water-cooled system, a central pump station contains the circulation pump and all valves needed to control fluid flow between the parallel compressor cabinets and fluid cooler. Inlet and outlet pipes sized for the entire system flow are provided to and from the fluid cooler and pump station. Flow to each distributed system is branched from these central supply and return pipes at a continuous rate; flow to each distributed compressor system is controlled by manual balancing valves set at installation to ensure proper flow to each cabinet.
Liquid-Cooled, Self-Contained Systems. In these systems, refrigeration condensing units connected (underneath, behind, above, or in a nearby enclosure) to one or more refrigerators are located in the display area of the supermarket. A low-temperature fluid or coolant, typically a brine or glycol solution, is pumped through a refrigerant-to-liquid heat exchanger, which serves as the condenser. The heated coolant then flows to a remote refrigeration system or chiller, which removes heat and then pumps the coolant back out to the refrigerator.
As with other systems, there are advantages and disadvantages. As much as 80% less refrigerant charge is needed, there is less potential for refrigerant loss by leakage, and initial equipment costs may be lower. In addition, refrigerators can be performance tested before they are shipped from the factory, and installations may be less labor intensive.
As with secondary cooling systems, the biggest disadvantage is the increased energy requirement from the additional step of heat transfer and the secondary fluid pumps. Noise levels can also be higher, and compressor service must be done in the display area of the supermarket. Advances in compressor technology leading to quieter, more compact, and energy-efficient systems would allow liquid-cooled, self-contained systems to become more feasible low-charge alternatives for widespread applications.