3.1 THERMOSTATIC EXPANSION VALVES
The thermostatic expansion valve controls the flow of liquid refrigerant entering the evaporator in response to the superheat of gas leaving the evaporator. It keeps the evaporator active without allowing liquid to return through the suction line to the compressor. This is done by controlling the mass flow of refrigerant entering the evaporator so it equals the rate at which it can be completely vaporized in the evaporator by heat absorption. Because this valve is operated by superheat and responds to changes in superheat, a portion of the evaporator must be used to superheat refrigerant gas.
Unlike the constant-pressure valve, the thermostatic expansion valve is not limited to constant-load applications. It is used for controlling refrigerant flow to all types of direct-expansion evaporators in air-conditioning and in commercial (medium-temperature), low-temperature, and ultralow-temperature refrigeration applications.
Figure 10 shows a schematic cross section of a typical thermostatic expansion valve, with the principal components identified. The following pressures and their equivalent forces govern thermostatic expansion valve operation:
| P1 = pressure of thermostatic element (a function of bulb’s charge and temperature), which is applied to the top of diaphragm and acts to open valve |
| P2 = evaporator pressure, which is applied under the diaphragm through an equalizer passage and acts to close valve |
| P3 = pressure equivalent of superheat spring force, which is applied underneath the diaphragm and is also a closing force |
At any constant operating condition, these pressures (forces) are balanced and P1 = P2 + P3.
An additional force, which is small and not considered fundamental, arises from the pressure differential across the valve port. To a degree, it can affect thermostatic expansion valve operation. For the configuration shown in Figure 10, the force resulting from port imbalance is the product of pressure drop across the port and the area of the port; it is an opening force in this configuration. In other designs, depending on the direction of flow through the valve, port imbalance may result in a closing force.
The principal effect of port imbalance is on the stability of valve control. As with any modulating control, if the ratio of the diaphragm area to the port is kept large, the unbalanced port effect is minor. However, if this ratio is small or if system operating conditions require, a balanced port valve can be used. Figure 11 shows a typical balanced port design.
Figure 12 shows an evaporator operating with R-410A at a saturation temperature of 40°F (118 psig). Liquid refrigerant enters the expansion valve, is reduced in pressure and temperature at the valve port, and enters the evaporator at point A as a mixture of saturated liquid and vapor. As flow continues through the evaporator, more of the refrigerant is evaporated. Assuming there is no pressure drop, the refrigerant temperature remains at 40°F until the liquid is entirely evaporated at point B. From this point, additional heat absorption increases the temperature and superheats the refrigerant gas, while the pressure remains constant at 118 psig, until, at point C (the evaporator’s outlet), the refrigerant gas temperature is 50°F. At this point, the superheat is 10°F (50 – 40°F).
An increased heat load on the evaporator increases the temperature of refrigerant gas leaving the evaporator. The bulb of the valve senses this increase, and the thermostatic charge pressure P1 increases and causes the valve to open wider. The increased flow results in a higher evaporator pressure P2, and a balanced control point is again established. Conversely, decreased heat load on the evaporator decreases the temperature of refrigerant gas leaving the evaporator and causes the thermostatic expansion valve to start closing.
The new control point, after an increase in valve opening, is at a slightly higher operating superheat because of the spring rate of the diaphragm and superheat spring. Conversely, decreased load results in an operating superheat slightly lower than the original control point.
These superheat changes in response to load changes are shown by the gradient curve of Figure 13. Superheat at no load, distance 0-A, is called static superheat and ensures sufficient spring force to keep the valve closed during system shutdown. An increase in valve capacity or load is approximately proportional to superheat until the valve is fully open. Opening superheat, represented by the distance A-B, is the superheat increase required to open the valve to match the load; operating superheat is the sum of static and opening superheats.
The factory superheat setting (static superheat setting) of thermostatic expansion valves is made when the valve starts to open. (See ASHRAE Standard 17 for methods of setting the thermostatic expansion valve.) Valve manufacturers establish capacity ratings on the basis of opening superheat, typically from 4 to 8°F, depending on valve design, size, and application. Full-open capacities usually exceed rated capacities by 10 to 40% to allow a reserve, represented by the distance B-C in Figure 13, for manufacturing tolerances and application contingencies.
A valve should not be selected on the basis of its reserve capacity, which is available only at higher operating superheat. The added superheat may have an adverse effect on performance. Because valve gradients used for rating purposes are selected to produce optimum modulation for a given valve design, manufacturers’ recommendations should be followed.
Thermostatic expansion valve capacities are normally published for various evaporator temperatures and valve pressure drops. (See AHRI Standard 750 and ASHRAE Standard 17 for testing and rating methods.) Nominal capacities apply at 40°F evaporator temperature. Capacities are reduced at lower evaporator temperatures, because of the changed refrigerant pressure/temperature relationship at lower temperatures. For example, if R-410A is used, the change in saturated pressure between 40 and 45°F is 11.8 psi, whereas between −20 and –15°F the change is 4.9 psi. Although the valve responds to pressure changes, published capacities are based on superheat change. Thus, the valve opening and, consequently, valve capacity are less for a given superheat change at lower evaporator temperatures.
Pressure drop across the valve port is always the net pressure drop available at the valve, rather than the difference between compressor discharge and compressor suction pressures. Allowances must be made for the following:
Pressure drop through condenser, receiver, liquid lines, fittings, and liquid line accessories (filters, driers, solenoid valves, etc.).
Static pressure in a vertical liquid line. If the thermostatic expansion valve is at a higher level than the receiver, there will be a pressure loss in the liquid line because of the static pressure of liquid.
Distributor pressure drop.
Evaporator pressure drop.
Pressure drop through suction line and accessories, such as evaporator pressure regulators, solenoid valves, accumulators, etc.
Variations in valve capacity related to changes in system conditions are approximately proportional to the following relationship:
where
| q | = | refrigerating effect |
| C | = | thermostatic expansion valve flow constant |
| ρ | = | entering liquid density |
| Δ p | = | valve pressure difference |
| hg | = | enthalpy of vapor exiting evaporator |
| hf | = | enthalpy of liquid entering thermostatic expansion valve |
Thermostatic expansion valve capacity is dependent on vapor-free liquid entering the valve. If there is flash gas in the entering liquid, valve capacity is reduced substantially because
Refrigerant mass flow passing through the valve is significantly diminished because the two-phase flow has a lower density
Flow of the compressible vapor fraction chokes at pressure ratios that typically exist across expansion valves and further restricts liquid-phase flow rate
Vapor passing through the valve provides no refrigerating effect
Flashing of liquid refrigerant may be caused by pressure drop in the liquid line, filter-drier, vertical lift, or a combination of these. If refrigerant subcooling at the valve inlet is not adequate to prevent flash gas from forming, additional subcooling means must be provided.
There are several principal types of thermostatic charges, each with certain advantages and limitations.
Gas Charge. Conventional gas charges are limited liquid charges that use the same refrigerant in the thermostatic element as in the refrigeration system. The amount of charge is such that, at a predetermined temperature, all of the liquid has vaporized and any temperature increase above this point results in practically no increase in element pressure. Figure 14 shows the pressure/temperature relationship of an R-134a gas charge in the thermostatic element. Because of the characteristic pressure-limiting feature of its thermostatic element, the gas-charged valve can provide compressor motor overload protection on some systems by limiting the maximum operating suction pressure (MOP). It also helps prevent floodback (return of refrigerant liquid to the compressor through the suction line) on starting. Increasing the superheat setting lowers the MOP; decreasing the superheat setting raises the MOP because the superheat spring and evaporator pressure balance the element pressure through the diaphragm.
Gas-charged valves must be carefully applied to avoid loss of control from the bulb. The small amount of charge in the bulb condenses at the coldest point. If the diaphragm chamber or connecting tube becomes colder than the bulb, the valve will throttle or close at a superheat different than the evaporator-leaving superheat, as detailed in the section on Application.
Liquid Charge. Straight liquid charges use the same refrigerant in the thermostatic element and refrigeration system. The volumes of the bulb, bulb tubing, and diaphragm chamber are proportioned so that the bulb contains some liquid under all temperatures. Therefore, the bulb always controls valve operation, even with a colder diaphragm chamber or bulb tubing.
The straight liquid charge (Figure 15) results in increased operating superheat as evaporator temperature decreases. This usually limits use of the straight liquid charge to moderately high evaporator temperatures. The valve setting required for a reasonable operating superheat at a low evaporator temperature may cause floodback during cooling at normal ambient temperatures.
Liquid Cross Charge. Liquid cross charges use a volatile liquid that is different from the refrigerant in the system and can be mixed with a noncondensable gas in the thermostatic element. Cross charges have flatter pressure/temperature curves than the system refrigerants with which they are used. Consequently, their superheat characteristics differ considerably from those of straight liquid or gas charges.
Cross charges in the commercial temperature range generally have superheat characteristics that are nearly constant or that deviate only moderately through the evaporator temperature range. This charge, also shown in Figure 15, is generally used in the evaporator temperature range of 40 to 0°F or slightly below.
For evaporator temperatures substantially below 0°F, a more extreme cross charge may be used. At high evaporator temperatures, the valve controls at a high superheat. As the evaporator temperature falls to the normal operating range, the operating superheat also falls to normal. This prevents floodback on starting, reduces load on the compressor motor at start-up, and allows rapid pulldown of suction pressure. To avoid floodback, valves with this type of charge must be set for the optimum operating superheat at the lowest evaporator temperature expected.
Gas Cross Charge. Gas cross charges combine features of the gas charge and liquid cross charge. They use a limited amount of liquid, thereby providing a maximum operating pressure. The liquid used in the charge is different from the refrigerant in the system, and is often mixed with a noncondensable gas, such as dry air or nitrogen. This type of charge provides superheat characteristics similar to those of liquid cross charges (low temperature). Consequently, it provides both the superheat characteristics of a cross charge, and the maximum operating pressure of a gas charge (Figure 15).
Adsorption Charge. Typical adsorption charges depend on the property of an adsorbent, such as silica gel or activated carbon, that is used in the thermostatic element bulb to adsorb and desorb a gas such as carbon dioxide, with accompanying changes in temperature. The amount of adsorption or desorption changes the pressure in the thermostatic element. Because adsorption charges respond primarily to the temperature of the adsorbent material, they are the charges least affected by the ambient temperature surrounding the bulb, bulb tubing, and diaphragm chamber. The comparatively slow thermal response of the adsorbent results in a charge characterized by its stability. Superheat characteristics can be varied by using different charge fluids, adsorbents, and/or charge pressures. The pressure-limiting feature of the gas or gas cross charges is not available with the adsorption charge.
Internal Equalizer. When the refrigerant pressure drop through an evaporator is relatively low (e.g., equivalent to 2°F change in saturation temperature), a thermostatic expansion valve that has an internal equalizer may be used. Internal equalization describes valve outlet pressure transmitted through an internal passage to the underside of the diaphragm (see Figure 10).
Pressure drop in many evaporators is greater than the 2°F equivalent. When a refrigerant distributor is used, pressure drop across the distributor causes pressure at the expansion valve outlet to be considerably higher than that at the evaporator outlet. As a result, an internally equalized valve controls at an abnormally high superheat. Under these conditions, the evaporator does not perform efficiently because it is starved for refrigerant. Furthermore, the distributor pressure drop is not constant, but varies with refrigerant flow rate and therefore cannot be compensated for by adjusting the superheat setting of the valve.
External Equalizer. Because evaporator and/or refrigerant distributor pressure drop causes poor system performance with an internally equalized valve, a valve that has an external equalizer is used. Instead of the internal communicating passage shown in Figure 10, an external connection to the underside of the diaphragm is provided. The external equalizer line is connected either to the suction line, as shown in Figure 16, or into the evaporator at a point downstream from the major pressure drop.
Alternative Construction Types
Pilot-operated thermostatic expansion valves are used on large systems in which the required capacity per valve exceeds the range of direct-operated valves. The pilot-operated valve consists of a piston-type pilot-operated regulator, which is used as the main expansion valve, and a low-capacity thermostatic expansion valve, which serves as an external pilot valve. The small pilot thermostatic expansion valve supplies pressure to the piston chamber or, depending on the regulator design, bleeds pressure from the piston chamber in response to a change in the operating superheat. Pilot operation allows the use of a characterized port in the main expansion valve to provide good modulation over a wide load range. Therefore, a very carefully applied pilot-operated valve can perform well on refrigerating systems that have some form of compressor capacity reduction, such as cylinder unloading. Figure 17 shows such a valve applied to a large-capacity direct-expansion chiller.
The auxiliary pilot controls should be sized to handle only the pilot circuit flow. For example, in Figure 17 a small solenoid valve in the pilot circuit, installed ahead of the thermostatic expansion valve, converts the pilot-operated valve into a stop valve when the solenoid valve is closed.
Equalization Features. When the compressor stops, a thermostatic expansion valve usually moves to the closed position. This movement sustains the difference in refrigerant pressures in the evaporator and the condenser. Low-starting-torque motors require that these pressures be equalized to reduce the torque needed to restart the compressor. One way to provide pressure equalization is to add, parallel to the main valve port, a small fixed auxiliary passageway, such as a slot or drilled hole in the valve seat or valve pin. This opening allows limited fluid flow through the valve, even when the valve is closed, and allows the system pressures to equalize on the off cycle. The size of a fixed auxiliary passageway must be limited so its flow capacity is not greater than the smallest flow that must be controlled in normal system operation. For a drilled hole, the hole’s diameter should be bigger than the maximum allowable particle size circulating in the system, to prevent permanent obstructions. Slots in the seat may be a more robust solution, because any particle obstructing the slot would be flushed when the expansion valve opens fully.
Another, more complex control is available for systems requiring shorter equalizing times than can be achieved with the fixed auxiliary passageway. This control incorporates an auxiliary valve port, which bypasses the primary port and is opened by the element diaphragm as it moves toward and beyond the position at which the primary valve port is closed. Flow capacity of an auxiliary valve port can be considerably larger than that of the fixed auxiliary passageway, so pressures can equalize more rapidly.
Flooded System. Thermostatic expansion valves are seldom applied to flooded evaporators because superheat is necessary for proper valve control; only a few degrees of suction vapor superheat in a flooded evaporator incurs a substantial loss in system capacity. If the bulb is installed downstream from a liquid-to-suction heat exchanger, a thermostatic expansion valve can be made to operate at this point on a higher superheat. Valve control is likely to be poor because of the variable rate of heat exchange as flow rates change (see the section on Application).
Some expansion valves have modified thermostatic elements in which electric heat is supplied to the bulb. The bulb is inserted in direct contact with refrigerant liquid in a low-side accumulator. The contact of cold refrigerant liquid with the bulb overrides the artificial heat source and throttles the expansion valve. As liquid falls away from the bulb, the valve feed increases again. Although similar in construction to a thermostatic expansion valve, it is essentially a modulating liquid-level control valve.
Desuperheating Valves. Thermostatic expansion valves with special thermostatic charges are used to reduce gas temperatures (superheat) on various air-conditioning and refrigeration systems. Suction gas in a single-stage system can be desuperheated by injecting liquid directly into the suction line. This cooling may be required with or without discharge gas bypass used for compressor capacity control. The line upstream of the valve bulb must be long enough so the injected liquid refrigerant can mix adequately with the gas being desuperheated. On compound compression systems, an expansion valve may be used to inject liquid directly into the interstage line upstream of the expansion valve bulb location to provide intercooling.
Hunting is alternate overfeeding and starving of the refrigerant feed to the evaporator. It produces sustained cyclic changes in the pressure and temperature of refrigerant gas leaving the evaporator. Extreme hunting reduces refrigeration system capacity because mean evaporator pressure and temperature are lowered and compressor capacity is reduced. If overfeeding of the expansion valve causes intermittent flooding of liquid into the suction line, the compressor may be damaged.
Although hunting is commonly attributed to the thermostatic expansion valve, it is seldom solely responsible. One reason for hunting is that all evaporators have a time lag. When the bulb signals for a change in refrigerant flow, the refrigerant must traverse the entire evaporator before a new signal reaches the bulb. This lag or time lapse may cause continuous overshooting of the valve both opening and closing. In addition, the thermostatic element, because of its mass, has a time lag that may be in phase with the evaporator lag and amplify the original overshooting.
It is possible to alter the thermostatic element’s response rate by either using thermal ballast or changing the mass or heat capacity of the bulb, thereby damping or even eliminating hunting. A change in valve gradient may produce a similar result.
Slug flow or percolation in the evaporator can also cause hunting. Under these conditions, liquid refrigerant moves in waves (slugs) that fill a portion of the evaporator tube and erupt into the suction line. These unevaporated slugs chill the bulb and temporarily reduce the feed of the valve, resulting in intermittent starving of the evaporator.
On multiple-circuit evaporators, a lightly loaded or overfed circuit also floods into the suction line, chills the bulb, and throttles the valve. Again, the effect is intermittent; when the valve feed is reduced, flooding ceases and the valve reopens.
Hunting can be minimized or avoided in the following ways:
Select the proper valve size from the valve capacity ratings rather than nominal valve capacity; oversized valves aggravate hunting.
Change the valve adjustment. A lower superheat setting usually (but not always) increases hunting.
Select the correct thermostatic element charge. Cross-charged elements are less susceptible to hunting.
Design the evaporator section for even flow of refrigerant and air. Uniform heat transfer from the evaporator is only possible if refrigerant is distributed by a properly selected and applied refrigerant distributor and air distribution is controlled by a properly designed housing. (Air-cooling and dehumidifying coils, including refrigerant distributors, are detailed in Chapter 23 of the 2020 ASHRAE Handbook—HVAC Systems and Equipment.)
Size and arrange suction piping correctly.
Locate and apply the bulb correctly.
Select the best location for the external equalizer line connection.
Bulb Location. Most installation requirements are met by strapping the bulb to the suction line to obtain good thermal contact between them. Normally, the bulb is attached to a horizontal line upstream of the external equalizer connection (if used) at a 3 or 9 o’clock position as close to the evaporator as possible. The bulb is not normally placed near or after suction-line traps, but some designers test and prove locations that differ from these recommendations. A good moisture-resistant insulation over the bulb and suction line diminishes the adverse effect of varying ambient temperatures at the bulb location.
Occasionally, the bulb of the thermostatic expansion valve is installed downstream from a liquid-suction heat exchanger to compensate for a capacity shortage caused by an undersized evaporator. Although this procedure seems to be a simple method of maximizing evaporator capacity, installing the bulb downstream of the heat exchanger is undesirable from a control standpoint. As the valve modulates, the liquid flow rate through the heat exchanger changes, causing the rate of heat transfer to the suction vapor to change. An exaggerated valve response follows, resulting in hunting. There may be a bulb location downstream from the heat exchanger that reduces hunting considerably. However, the danger of floodback to the compressor normally overshadows the need to attempt this method.
Certain installations require increased bulb sensitivity as a protection against floodback. The bulb, if located properly in a well in the suction line, has a rapid response because of its direct contact with the refrigerant stream. Bulb sensitivity can be increased by using a bulb smaller than is normally supplied. However, using a smaller bulb is limited to gas-charged valves. Good piping practice also affects expansion valve performance.
Figure 18 shows the proper piping arrangement when the suction line runs above the evaporator. A lubricant trap that is as short as possible is located downstream from the bulb. The vertical riser(s) must be sized to produce a refrigerant velocity that ensures continuous return of lubricant to the compressor. The terminal end of the riser(s) enters the horizontal run at the top of the suction line; this avoids interference from overfeeding any other expansion valve or any drainback during the off cycle.
If circulated with lubricant-miscible refrigerant, a heavy concentration of lubricant elevates the refrigerant’s boiling temperature. The response of the thermostatic charge of the expansion valve is related to the saturation pressure and temperature of pure refrigerant. In an operating system, the false pressure/temperature signals of lubricant-rich refrigerants cause floodback or operating superheats considerably lower than indicated, and quite often cause erratic valve operation. To keep lubricant concentration at an acceptable level, either the lubricant pumping rate of the compressor must be reduced or an effective lubricant separator must be used.
The external equalizer line is ordinarily connected at the evaporator outlet, as shown in Figure 18. It may also be connected at the evaporator inlet or at any other point in the evaporator downstream of the major pressure drop. On evaporators with long refrigerant circuits that have inherent lag, hunting may be minimized by changing the connection point of the external equalizer line.
In application, the various parts of the valve’s thermostatic element are simultaneously exposed to different thermal influences from the surrounding ambient air and the refrigerant system. In some situations, cold refrigerant exiting the valve dominates and cools the thermostatic element to below the bulb temperature. When this occurs with a gas-charged or gas cross-charged valve, the charge condenses at the coldest point in the element and control of refrigerant feed moves from the bulb to the thermostatic element (diaphragm chamber). Pressure applied to the top of the diaphragm diminishes to saturation pressure at the cold point. Extreme starving of the evaporator, progressing to complete cessation of refrigerant flow, is characteristic. For this reason, gas-charged or gas cross-charged valves should be applied only to multicircuited evaporators that use refrigerant distributors. The distributor typically provides sufficient pressure drop to maintain a saturation temperature at the valve outlet well above the temperature at the bulb location.
Internally equalized gas-charged or gas cross-charged valves should only be considered in very carefully selected applications where the risk of loss of control can be minimized. Some gas cross-charge formulations may be slightly less susceptible to the described loss of control than are straight gas charges, but they are far from immune. Gas-charged and gas cross-charged valves with specially constructed thermostatic power elements that positively isolate the charge fluids in the temperature-sensing element (bulb) have been applied in situations where there was high risk of control loss and the pressure-limiting feature of a gas-charged valve was required.
Gas-charged bulbless valves, frequently called block valves (Figure 19), are practically immune to loss of control because the thermostatic element (diaphragm chamber) is located at the evaporator outlet. The valve is constructed so that the temperature-sensing function of the remote bulb is integrated into the thermostatic element by purposely confining all of the charge fluid to this chamber.
Liquid, liquid cross-charged, and adsorption-charged valves are not susceptible to the same type of loss of control that gas-charged or gas cross-charged valves are. However, exposure to extreme ambient temperature environments causes shifting of operating superheats. The degree of superheat shift depends on the severity of the thermal exposure. High ambient temperatures surrounding thermally sensitive parts of the valve typically lower operating superheats, and vice versa. Gas-charged and gas cross-charged valves, including bulbless or block valves, respond to high ambient exposure similarly but starve the evaporator when exposed to ambient temperatures below evaporator outlet refrigerant temperatures.
3.2 ELECTRIC EXPANSION VALVES
Application of an electric expansion valve requires a valve, controller, and control sensors. The control sensors may include pressure transducers, thermistors, resistance temperature devices (RTDs), or other pressure and temperature sensors. See Chapter 37 in the 2017 ASHRAE Handbook—Fundamentals for a discussion of instrumentation. Specific types should be discussed with the electric valve and electronic controller manufacturers to ensure compatibility of all components.
Electric valves typically have four basic types of actuation:
Heat motor valves may be one of two types. In one type, one or more bimetallic elements are heated electrically, causing them to deflect. The bimetallic elements are linked mechanically to a valve pin or poppet; as the bimetallic element deflects, the valve pin or poppet follows the element movement. In the second type, a volatile fluid is contained within an electrically heated chamber so that the regulated temperature (and pressure) is controlled by electrical power input to the heater. The regulated pressure acts on a diaphragm or bellows, which is balanced against atmospheric air pressure or refrigerant pressure. The diaphragm is linked to a pin or poppet, as shown in Figure 20.
A magnetically modulated (analog) valve functions by modulation of an electromagnet; a solenoid armature compresses a spring progressively as a function of magnetic force (Figure 21). The modulating armature may be connected to a valve pin or poppet directly or may be used as the pilot element to operate a much larger valve. When the modulating armature operates a pin or poppet directly, the valve may be of a pressure-balanced port design so that pressure differential has little or no influence on valve opening.
The pulse-width-modulated valve is an on/off solenoid valve with special features that allow it to function as an expansion valve through a life of millions of cycles (Figure 22). Although the valve is either fully opened or closed, it operates as a variable metering device by rapidly pulsing the valve open and closed. For example, if 50% flow is needed, the valve will be open 50% of the time and closed 50% of the time. The duration of each opening, or pulse, is regulated by the electronics.
A step motor is a multiphase motor designed to rotate in discrete fractions of a revolution, based on the number of signals or “steps” sent by the controller. The controller tracks the number of steps and can offer fine control of the valve position with a high level of repeatability. Step motors are used in instrument drives, plotters, and other applications where accurate positioning is required. When used to drive expansion valves, a lead screw changes the rotary motion of the rotor to a linear motion suitable for moving a valve pin or poppet (Figure 23A). The lead screw may be driven directly from the rotor, or a reduction gearbox may be placed between the motor and lead screw. The motor may be hermetically sealed within the refrigerant environment, or the rotor may be enclosed in a thin-walled, nonmagnetic, pressuretight metal tube, similar to those used in solenoid valves, which is surrounded by the stator such that the rotor is in the refrigerant environment and the stator is outside the refrigerant environment. In some designs, the motor and gearbox can operate outside the refrigerant system with an appropriate stem seal (Figure 23B).
Electric expansion valves may be controlled by either digital or analog electronic circuits. Electronic control gives additional flexibility over traditional mechanical valves to consider control schemes that would otherwise be impossible, including stopped or full flow when required.
The electric expansion valve, with properly designed electronic controllers and sensors, offers a refrigerant flow control means that is not refrigerant specific, has a very wide load range, can often be set remotely, and can respond to a variety of input parameters.