CHAPTER 11. REFRIGERANT CONTROL DEVICES

 

Control of refrigerant flow, temperatures, pressures, and liquid levels is essential in any refrigeration system. This chapter describes a variety of devices and their application to accomplish these important control functions.

Most examples, references, and capacity data in this chapter refer to the more common refrigerants. For further information on control fundamentals, see Chapter 7 of the 2017 ASHRAE Handbook—Fundamentals and 47 of the 2019 ASHRAE Handbook—HVAC Applications.

1. CONTROL SWITCHES

A control switch includes both a sensor and a switch mechanism capable of opening and/or closing an electrical circuit in response to changes in the monitored parameter. The control switch operates one or more sets of electrical contacts, which are used to open or close water or refrigerant solenoid valves; engage and disengage automotive compressor clutches; activate and deactivate relays, contactors, magnetic starters, timers; etc. Control switches respond to a variety of physical changes such as pressure, temperature, and liquid level.

Liquid-level-responsive controls use floats or electronic probes to operate (directly or indirectly) one or more sets of electrical contacts.

Refrigeration control switches may be categorized into three basic groups:

  • Operating controls turn systems on and off (e.g., thermostats).

  • Primary controls provide safe continuous operation (e.g., compressor or condenser fan cycling).

  • Limit controls protect a system from unsafe operation (e.g., high-pressure cutout switch).

1.1 PRESSURE SWITCHES

Pressure-responsive switches have one or more power elements (e.g., bellows, diaphragms, bourdon tubes) to produce the force needed to operate the mechanism. Typically, pressure-switch power elements are all metal, although some miniaturized devices for specific applications, such as automotive air conditioning, may use synthetic diaphragms. Refrigerant pressure is applied directly to the element, which moves against a spring that can be adjusted to control operation at the desired pressure (Figure 1). If the control is to operate in the subatmospheric (or vacuum) range, the bellows or diaphragm force is sometimes reversed to act in the same direction as the adjusting spring.

The force available for doing work (i.e., operating the switch mechanism) in this control depends on the pressure in the system and the area of the bellows or diaphragm. With proper area, enough force can be produced to operate heavy-duty switches. In switches for high-pressure service, the minimum differential is relatively large because of the high-gradient-range spring required.

Typical Pressure Switch

Figure 1. Typical Pressure Switch


Table 1 Various Types of Pressure Switches

Type

Function

High-pressure cutout (HPCO)

Stops compressor when excessive pressure occurs

High-side low-pressure (HSLP)

Prevents compressor operation under low ambient or loss of refrigerant conditions

High-side fan-cycling (HSFC)

Cycles condenser fan on and off to provide proper condenser pressure

Low-side low-pressure (LSLP)

Initiates defrost cycle; stops compressor when low charge or system blockage occurs

Low-side compressor cycling (LSCC)

Cycles compressor on and off to provide proper evaporator pressure and load temperature

Lubricant pressure differential failure (LPDF)

Stops compressor when difference between oil pressure and crankcase pressure is too low for adequate lubrication


Miniaturized pressure switches may incorporate one or more snap disks, which provide positive snap action of the electrical contacts. Snap-disk construction ensures consistent differential pressure between on and off settings (Figure 2); it also substantially reduces electrical contact bounce or flutter, which can damage compressor clutch assemblies, relays, and electronic control modules. Some snap-disk switches are built to provide multiple functions in a single unit, such as high-pressure cutout (HPCO), high-side low-pressure (HSLP), and high-side fan-cycling (HSFC) switches.

Miniaturized Pressure Switch

Figure 2. Miniaturized Pressure Switch


Pressure switches in most refrigeration systems are used primarily to start and stop the compressor, cycle condenser fans, and initiate and terminate defrost cycles. Table 1 shows various types of pressure switches with their corresponding functions.

1.2 TEMPERATURE SWITCHES (THERMOSTATS)

Temperature-responsive switches have one or more metal power elements (e.g., bellows, diaphragms, bourdon tubes, bimetallic snap disks, bimetallic strips) that produce the force needed to operate the switch.

An indirect temperature switch is a pressure switch with the pressure-responsive element replaced by a temperature-responsive element. The temperature-responsive element is a hermetically sealed system comprised of a flexible member (diaphragm or bellows) and a temperature-sensing element (bulb or tube) that are in pressure communication with each other (Figure 3). The closed system contains a temperature-responsive fluid.

The exact temperature/pressure or temperature/volume relationship of the fluid used in the element allows the bulb temperature to control the switch accurately. The switch is operated by changes in pressure or volume that are proportional to changes in sensor temperature.

Indirect Temperature Switch

Figure 3. Indirect Temperature Switch


A direct temperature switch typically contains a bimetallic disk or strip that activates electrical contacts when the temperature increases or decreases. As its temperature increases or decreases, the bimetallic element bends or strains because of the two metals’ different coefficients of thermal expansion, and the linked electrical contacts engage or disengage. The disk bimetallic element provides snap action, which results in rapid and positive opening or closing of the electrical contacts, minimizing arcing and bounce. A bimetallic strip (Figure 4) produces very slow contact action and is only suitable for use in very-low-energy electrical circuits. This type of switch is typically used for thermal limit control because the switch differentials and precision may be inadequate for many primary refrigerant control requirements.

Direct Temperature Switch

Figure 4. Direct Temperature Switch


1.3 DIFFERENTIAL SWITCHES

Differential control switches typically maintain a given difference in pressure or temperature between two pipelines, spaces, or loads. An example is the lubricant pressure differential failure switch used with reciprocating compressors that use forced-feed lubrication.

Figure 5 is a schematic of a differential switch that uses bellows as power elements. Figure 6 shows a differential pressure switch used to protect compressors against low oil pressure. These controls have two elements (either pressure or temperature sensitive) simultaneously sensing conditions at two locations. As shown, the two elements are rigidly connected by a rod, so that motion of one causes motion of the other. The connecting rod operates contacts (as shown). The scale spring is used to set the differential pressure at which the device operates. At the control point, the sum of forces developed by the low-pressure bellows and spring balances the force developed by the high-pressure bellows.

Differential Switch Schematic

Figure 5. Differential Switch Schematic


Instrument differential is the difference in pressure or temperature between the low- and the high-pressure elements for which the instrument is adjusted. Operating differential is the change in differential pressure or temperature required to open or close the switch contacts. It is actually the change in instrument differential from cut-in to cutout for any setting. Operating differential can be varied by a second spring that acts in the same direction as the first and takes effect only at the cut-in or cutout point without affecting the other spring. A second method is adjusting the distance between collars Z-Z on the connecting rod (see Figure 5). The greater the distance between the collars, the greater the operating differential.

Differential Pressure Switch

Figure 6. Differential Pressure Switch


If a constant instrument differential is required on a temperature-sensitive differential control switch throughout a large temperature range, one element may contain a different temperature-responsive fluid than the other.

A second type of differential-temperature control uses two sensing bulbs and capillaries connected to one bellows with a liquid fill. This is known as a constant-volume fill, because the operating point depends on a constant volume of the two bulbs, capillaries, and bellows. If the two bulbs have equal volume, a temperature rise in one bulb requires an equivalent fall in the other’s temperature to maintain the operating point.

1.4 FLOAT SWITCHES

A float switch has a float ball, the movement of which operates one or more sets of electrical contacts as the level of a liquid changes. Float switches are connected by equalizing lines to the vessel or an external column in which the liquid level is to be maintained or monitored. The switch mechanism is generally hermetically sealed. Small heaters can be incorporated to prevent moisture from permeating the polycarbonate housing in cold operating conditions. Other nonmechanical devices, such as capacitance probes, use other methods to monitor the change in liquid level.

Magnetic Float Switch

Figure 7. Magnetic Float Switch


 Operation and Selection

Some float switches (Figure 7) operate from movement of a magnetic armature located in the field of a permanent magnet. Others use solid-state circuits in which a variable signal is generated by liquid contact with a probe that replaces the float; this method is adapted to remote-controlled applications and is preferred for ultralow-temperature applications.

 Application

The float switch can maintain or indicate the level of a liquid, operate an alarm, control pump operation, or perform other functions. A float switch, solenoid liquid valve, and hand expansion valve combination can control refrigerant level on the high- or low-pressure side of the refrigeration system in the same way that high- or low-side float valves are used. The hand expansion valve, located in the refrigerant liquid line immediately downstream of the solenoid valve, is initially adjusted to provide a refrigerant flow rate at maximum load to keep the solenoid liquid valve in the open position 80 to 90% of the time; it need not be adjusted thereafter. From the outlet side of the hand expansion valve, refrigerant passes through a line and enters either the evaporator or the surge drum.

When the float switch is used for low-pressure level control, precautions must be taken to provide a calm liquid level that falls in response to increased evaporator load and rises with decreased evaporator load. The same recommendations for insulation of the body and liquid leg of the low-pressure float valve apply to the float switch when it is used for refrigerant-level control on the low-pressure side of the refrigeration system. To avoid floodback, controls should be wired to prevent the solenoid liquid valve from opening when the solenoid suction valve closes or the compressor stops.

2. CONTROL SENSORS

The control sensor is the component in a control system that measures and signals the value of a parameter but has no direct function control. Control sensors typically require an auxiliary source of energy for proper operation. They may be integrated into electronic circuits that provide the required energy and condition the sensor’s signal to accomplish the desired function control.

2.1 PRESSURE TRANSDUCERS

Pressure transducers sense refrigerant pressure through a flexible element (diaphragm, bourdon tube, or bellows) that is exposed to the system refrigerant pressure. The pressure acts across the flexible element’s effective area, producing a force that causes the flexible element to strain against an opposing spring within the transducer. The transducer uses a potentiometer, variable capacitor, strain gage, or piezo element to translate the flexible element’s movement to a proportional electrical output.

Transducers typically include additional electronic signal processing circuitry to temperature-compensate, modify, amplify, and linearize the final analog electrical output. Typically, the outside of the pressure-sensing flexible element is exposed to atmospheric pressure, and the transducer’s electrical output is proportional to the refrigerant’s gage pressure. Transducers capable of measuring absolute pressure are also available.

Transducers are usually used as control sensors in electronic control systems, where the continuous analog pressure signal provides data to comprehensive algorithm-based control strategies. For example, in automotive air-conditioning systems, engine load management can be significantly enhanced. Based on a correlation between refrigerant pressure and compressor torque requirements, the electronic engine controller uses the transducer signal to regulate engine air and fuel flow, compensating for compressor load variations. This improves fuel economy and eliminates the power drain experienced when the compressor starts. Transducers also provide a signal to electronically controlled variable-displacement compressors to adjust refrigerant flow from the evaporator, preventing excessive cooling of the air and further improving fuel economy.

2.2 THERMISTORS

Thermistors are cost-effective and reliable temperature sensors. They are typically small and are available in a variety of configurations and sheath materials. Thermistors are beads of semiconductor materials with electrical resistances that change with temperature. Materials with negative temperature coefficients (NTCs) (i.e., resistance decreases as temperature increases) are frequently used. NTC thermistors typically produce large changes in resistance with relatively small changes of temperature, and their characteristic curve is nonlinear (Figure 8).

Thermistors are used in electronic control systems that linearize and otherwise process their resistance change into function control actions such as driving step motors or bimetallic heat motors for function modulation. Their analog signal can also be conditioned to perform start/stop functions such as energizing relays, contactors, or solenoid valves.

Typical NTC Thermistor Characteristic

Figure 8. Typical NTC Thermistor Characteristic


2.3 RESISTANCE TEMPERATURE DETECTORS

Resistance temperature detectors (RTDs) are made of very fine metal wire or films coiled or shaped into forms suitable for the application. The elements may be mounted on a plate for surface temperature measurements or encapsulated in a tubular sheath for immersion or insertion into pressurized systems. Elements made of platinum or copper have linear temperature-resistance characteristics over limited temperature ranges. Platinum, for example, is linear within 0.3% from 0 to 300°F and minimizes long-term changes caused by corrosion. RTDs are often mated with electronic circuitry that produces a 4 to 20 mA current signal over a selected temperature range. This arrangement eliminates error associated with connecting line electrical resistance.

2.4 THERMOCOUPLES

Thermocouples are formed by the junction of two wires of dissimilar metals. The electromotive force between the wires depends on the wire material and the junction temperature. When the wires are joined at both ends, a thermocouple circuit is formed. When the junctions are at different temperatures, an electric current proportional to the temperature difference between the two junctions flows through the circuit. One junction, called the cold junction, is kept at a constant known temperature (e.g., in an ice bath). The temperature of the other (hot) junction is then determined by measuring the net voltage in the circuit. Electronic circuitry is often arranged to provide a built-in cold junction and linearization of the net voltage-to-temperature relationship. The resulting signal can then be electronically conditioned and amplified to implement function control.

2.5 LIQUID LEVEL SENSORS

Capacitance probes (Figure 9) can provide a continuous range of liquid-level monitoring. They compare the impedance value of the amount of probe wetted with liquid refrigerant to that in the vapor space. The output can be converted to a variable signal and sent to a dedicated control device with multiple switch points or a computer/programmable logic controller (PLC) for programming or monitoring the refrigerant level. These probes can replace multiple float switches and provide easy level adjustability.

Capacitance Probe in (A) Vertical Receiver and (B) Auxiliary Level Column

Figure 9. Capacitance Probe in (A) Vertical Receiver and (B) Auxiliary Level Column


 Operation and Selection

The basic principle is that the electrical capacitance of a vertical conducting rod, centered within a vertical conducting cylinder, varies approximately in proportion to the liquid level in the enclosure. The capability to accomplish this depends on the significant difference between the dielectric constants of the liquid and the vapor above the liquid surface.

Capacitance probes are available in a variety of configurations, using a full range of refrigerants. Active lengths vary from 6 in. to 13 ft; output signals vary from 0 to 5 or 1 to 6 V, 4 to 20 mA, or digital readout. Operating temperatures range from −100 to 150°F. Both internal and external vessel mountings are available.

3. CONTROL VALVES

Control valves are used to start, stop, direct, and modulate refrigerant flow to satisfy system requirements in accordance with load requirements. To ensure satisfactory performance, valves should be protected from foreign material, excessive moisture, and corrosion by properly sized strainers, filters, and/or filter-driers.

3.1 THERMOSTATIC EXPANSION VALVES

The thermostatic expansion valve controls the flow of liquid refrigerant entering the evaporator in response to the superheat of gas leaving the evaporator. It keeps the evaporator active without allowing liquid to return through the suction line to the compressor. This is done by controlling the mass flow of refrigerant entering the evaporator so it equals the rate at which it can be completely vaporized in the evaporator by heat absorption. Because this valve is operated by superheat and responds to changes in superheat, a portion of the evaporator must be used to superheat refrigerant gas.

Unlike the constant-pressure valve, the thermostatic expansion valve is not limited to constant-load applications. It is used for controlling refrigerant flow to all types of direct-expansion evaporators in air-conditioning and in commercial (medium-temperature), low-temperature, and ultralow-temperature refrigeration applications.

 Operation

Figure 10 shows a schematic cross section of a typical thermostatic expansion valve, with the principal components identified. The following pressures and their equivalent forces govern thermostatic expansion valve operation:

P1 = pressure of thermostatic element (a function of bulb’s charge and temperature), which is applied to the top of diaphragm and acts to open valve
P2 = evaporator pressure, which is applied under the diaphragm through an equalizer passage and acts to close valve
P3 = pressure equivalent of superheat spring force, which is applied underneath the diaphragm and is also a closing force

At any constant operating condition, these pressures (forces) are balanced and P1 = P2 + P3.

An additional force, which is small and not considered fundamental, arises from the pressure differential across the valve port. To a degree, it can affect thermostatic expansion valve operation. For the configuration shown in Figure 10, the force resulting from port imbalance is the product of pressure drop across the port and the area of the port; it is an opening force in this configuration. In other designs, depending on the direction of flow through the valve, port imbalance may result in a closing force.

Typical Thermostatic Expansion Valve

Figure 10. Typical Thermostatic Expansion Valve


The principal effect of port imbalance is on the stability of valve control. As with any modulating control, if the ratio of the diaphragm area to the port is kept large, the unbalanced port effect is minor. However, if this ratio is small or if system operating conditions require, a balanced port valve can be used. Figure 11 shows a typical balanced port design.

Figure 12 shows an evaporator operating with R-410A at a saturation temperature of 40°F (118 psig). Liquid refrigerant enters the expansion valve, is reduced in pressure and temperature at the valve port, and enters the evaporator at point A as a mixture of saturated liquid and vapor. As flow continues through the evaporator, more of the refrigerant is evaporated. Assuming there is no pressure drop, the refrigerant temperature remains at 40°F until the liquid is entirely evaporated at point B. From this point, additional heat absorption increases the temperature and superheats the refrigerant gas, while the pressure remains constant at 118 psig, until, at point C (the evaporator’s outlet), the refrigerant gas temperature is 50°F. At this point, the superheat is 10°F (50 – 40°F).

Typical Balanced Port Thermostatic Expansion Valve

Figure 11. Typical Balanced Port Thermostatic Expansion Valve


An increased heat load on the evaporator increases the temperature of refrigerant gas leaving the evaporator. The bulb of the valve senses this increase, and the thermostatic charge pressure P1 increases and causes the valve to open wider. The increased flow results in a higher evaporator pressure P2, and a balanced control point is again established. Conversely, decreased heat load on the evaporator decreases the temperature of refrigerant gas leaving the evaporator and causes the thermostatic expansion valve to start closing.

Thermostatic Expansion Valve Controlling Flow of Liquid R-410A Entering Evaporator, Assuming R-410A Charge in Bulb

Figure 12. Thermostatic Expansion Valve Controlling Flow of Liquid R-410A Entering Evaporator, Assuming R-410A Charge in Bulb


The new control point, after an increase in valve opening, is at a slightly higher operating superheat because of the spring rate of the diaphragm and superheat spring. Conversely, decreased load results in an operating superheat slightly lower than the original control point.

These superheat changes in response to load changes are shown by the gradient curve of Figure 13. Superheat at no load, distance 0-A, is called static superheat and ensures sufficient spring force to keep the valve closed during system shutdown. An increase in valve capacity or load is approximately proportional to superheat until the valve is fully open. Opening superheat, represented by the distance A-B, is the superheat increase required to open the valve to match the load; operating superheat is the sum of static and opening superheats.

 Capacity

The factory superheat setting (static superheat setting) of thermostatic expansion valves is made when the valve starts to open. (See ASHRAE Standard 17 for methods of setting the thermostatic expansion valve.) Valve manufacturers establish capacity ratings on the basis of opening superheat, typically from 4 to 8°F, depending on valve design, size, and application. Full-open capacities usually exceed rated capacities by 10 to 40% to allow a reserve, represented by the distance B-C in Figure 13, for manufacturing tolerances and application contingencies.

A valve should not be selected on the basis of its reserve capacity, which is available only at higher operating superheat. The added superheat may have an adverse effect on performance. Because valve gradients used for rating purposes are selected to produce optimum modulation for a given valve design, manufacturers’ recommendations should be followed.

Typical Gradient Curve for Thermostatic Expansion Valves

Figure 13. Typical Gradient Curve for Thermostatic Expansion Valves


Thermostatic expansion valve capacities are normally published for various evaporator temperatures and valve pressure drops. (See AHRI Standard 750 and ASHRAE Standard 17 for testing and rating methods.) Nominal capacities apply at 40°F evaporator temperature. Capacities are reduced at lower evaporator temperatures, because of the changed refrigerant pressure/temperature relationship at lower temperatures. For example, if R-410A is used, the change in saturated pressure between 40 and 45°F is 11.8 psi, whereas between −20 and –15°F the change is 4.9 psi. Although the valve responds to pressure changes, published capacities are based on superheat change. Thus, the valve opening and, consequently, valve capacity are less for a given superheat change at lower evaporator temperatures.

Pressure drop across the valve port is always the net pressure drop available at the valve, rather than the difference between compressor discharge and compressor suction pressures. Allowances must be made for the following:

  • Pressure drop through condenser, receiver, liquid lines, fittings, and liquid line accessories (filters, driers, solenoid valves, etc.).

  • Static pressure in a vertical liquid line. If the thermostatic expansion valve is at a higher level than the receiver, there will be a pressure loss in the liquid line because of the static pressure of liquid.

  • Distributor pressure drop.

  • Evaporator pressure drop.

  • Pressure drop through suction line and accessories, such as evaporator pressure regulators, solenoid valves, accumulators, etc.

Variations in valve capacity related to changes in system conditions are approximately proportional to the following relationship:

(1)

where

q=refrigerating effect
C=thermostatic expansion valve flow constant
ρ=entering liquid density
Δ p=valve pressure difference
hg=enthalpy of vapor exiting evaporator
hf=enthalpy of liquid entering thermostatic expansion valve

Thermostatic expansion valve capacity is dependent on vapor-free liquid entering the valve. If there is flash gas in the entering liquid, valve capacity is reduced substantially because

  • Refrigerant mass flow passing through the valve is significantly diminished because the two-phase flow has a lower density

  • Flow of the compressible vapor fraction chokes at pressure ratios that typically exist across expansion valves and further restricts liquid-phase flow rate

  • Vapor passing through the valve provides no refrigerating effect

Flashing of liquid refrigerant may be caused by pressure drop in the liquid line, filter-drier, vertical lift, or a combination of these. If refrigerant subcooling at the valve inlet is not adequate to prevent flash gas from forming, additional subcooling means must be provided.

 Thermostatic Charges

There are several principal types of thermostatic charges, each with certain advantages and limitations.

Pressure/Temperature Relationship of R-134a Gas Charge in Thermostatic Element

Figure 14. Pressure/Temperature Relationship of R-134a Gas Charge in Thermostatic Element


Gas Charge. Conventional gas charges are limited liquid charges that use the same refrigerant in the thermostatic element as in the refrigeration system. The amount of charge is such that, at a predetermined temperature, all of the liquid has vaporized and any temperature increase above this point results in practically no increase in element pressure. Figure 14 shows the pressure/temperature relationship of an R-134a gas charge in the thermostatic element. Because of the characteristic pressure-limiting feature of its thermostatic element, the gas-charged valve can provide compressor motor overload protection on some systems by limiting the maximum operating suction pressure (MOP). It also helps prevent floodback (return of refrigerant liquid to the compressor through the suction line) on starting. Increasing the superheat setting lowers the MOP; decreasing the superheat setting raises the MOP because the superheat spring and evaporator pressure balance the element pressure through the diaphragm.

Gas-charged valves must be carefully applied to avoid loss of control from the bulb. The small amount of charge in the bulb condenses at the coldest point. If the diaphragm chamber or connecting tube becomes colder than the bulb, the valve will throttle or close at a superheat different than the evaporator-leaving superheat, as detailed in the section on Application.

Liquid Charge. Straight liquid charges use the same refrigerant in the thermostatic element and refrigeration system. The volumes of the bulb, bulb tubing, and diaphragm chamber are proportioned so that the bulb contains some liquid under all temperatures. Therefore, the bulb always controls valve operation, even with a colder diaphragm chamber or bulb tubing.

The straight liquid charge (Figure 15) results in increased operating superheat as evaporator temperature decreases. This usually limits use of the straight liquid charge to moderately high evaporator temperatures. The valve setting required for a reasonable operating superheat at a low evaporator temperature may cause floodback during cooling at normal ambient temperatures.

Liquid Cross Charge. Liquid cross charges use a volatile liquid that is different from the refrigerant in the system and can be mixed with a noncondensable gas in the thermostatic element. Cross charges have flatter pressure/temperature curves than the system refrigerants with which they are used. Consequently, their superheat characteristics differ considerably from those of straight liquid or gas charges.

Cross charges in the commercial temperature range generally have superheat characteristics that are nearly constant or that deviate only moderately through the evaporator temperature range. This charge, also shown in Figure 15, is generally used in the evaporator temperature range of 40 to 0°F or slightly below.

Typical Superheat Characteristics of Common Thermostatic Charges

Figure 15. Typical Superheat Characteristics of Common Thermostatic Charges


For evaporator temperatures substantially below 0°F, a more extreme cross charge may be used. At high evaporator temperatures, the valve controls at a high superheat. As the evaporator temperature falls to the normal operating range, the operating superheat also falls to normal. This prevents floodback on starting, reduces load on the compressor motor at start-up, and allows rapid pulldown of suction pressure. To avoid floodback, valves with this type of charge must be set for the optimum operating superheat at the lowest evaporator temperature expected.

Gas Cross Charge. Gas cross charges combine features of the gas charge and liquid cross charge. They use a limited amount of liquid, thereby providing a maximum operating pressure. The liquid used in the charge is different from the refrigerant in the system, and is often mixed with a noncondensable gas, such as dry air or nitrogen. This type of charge provides superheat characteristics similar to those of liquid cross charges (low temperature). Consequently, it provides both the superheat characteristics of a cross charge, and the maximum operating pressure of a gas charge (Figure 15).

Adsorption Charge. Typical adsorption charges depend on the property of an adsorbent, such as silica gel or activated carbon, that is used in the thermostatic element bulb to adsorb and desorb a gas such as carbon dioxide, with accompanying changes in temperature. The amount of adsorption or desorption changes the pressure in the thermostatic element. Because adsorption charges respond primarily to the temperature of the adsorbent material, they are the charges least affected by the ambient temperature surrounding the bulb, bulb tubing, and diaphragm chamber. The comparatively slow thermal response of the adsorbent results in a charge characterized by its stability. Superheat characteristics can be varied by using different charge fluids, adsorbents, and/or charge pressures. The pressure-limiting feature of the gas or gas cross charges is not available with the adsorption charge.

 Type of Equalization

Internal Equalizer. When the refrigerant pressure drop through an evaporator is relatively low (e.g., equivalent to 2°F change in saturation temperature), a thermostatic expansion valve that has an internal equalizer may be used. Internal equalization describes valve outlet pressure transmitted through an internal passage to the underside of the diaphragm (see Figure 10).

Pressure drop in many evaporators is greater than the 2°F equivalent. When a refrigerant distributor is used, pressure drop across the distributor causes pressure at the expansion valve outlet to be considerably higher than that at the evaporator outlet. As a result, an internally equalized valve controls at an abnormally high superheat. Under these conditions, the evaporator does not perform efficiently because it is starved for refrigerant. Furthermore, the distributor pressure drop is not constant, but varies with refrigerant flow rate and therefore cannot be compensated for by adjusting the superheat setting of the valve.

External Equalizer. Because evaporator and/or refrigerant distributor pressure drop causes poor system performance with an internally equalized valve, a valve that has an external equalizer is used. Instead of the internal communicating passage shown in Figure 10, an external connection to the underside of the diaphragm is provided. The external equalizer line is connected either to the suction line, as shown in Figure 16, or into the evaporator at a point downstream from the major pressure drop.

Bulb Location for Thermostatic Expansion Valve

Figure 16. Bulb Location for Thermostatic Expansion Valve


 Alternative Construction Types

Pilot-operated thermostatic expansion valves are used on large systems in which the required capacity per valve exceeds the range of direct-operated valves. The pilot-operated valve consists of a piston-type pilot-operated regulator, which is used as the main expansion valve, and a low-capacity thermostatic expansion valve, which serves as an external pilot valve. The small pilot thermostatic expansion valve supplies pressure to the piston chamber or, depending on the regulator design, bleeds pressure from the piston chamber in response to a change in the operating superheat. Pilot operation allows the use of a characterized port in the main expansion valve to provide good modulation over a wide load range. Therefore, a very carefully applied pilot-operated valve can perform well on refrigerating systems that have some form of compressor capacity reduction, such as cylinder unloading. Figure 17 shows such a valve applied to a large-capacity direct-expansion chiller.

Pilot-Operated Thermostatic Expansion Valve Controlling Liquid Refrigerant Flow to Direct-Expansion Chiller

Figure 17. Pilot-Operated Thermostatic Expansion Valve Controlling Liquid Refrigerant Flow to Direct-Expansion Chiller


The auxiliary pilot controls should be sized to handle only the pilot circuit flow. For example, in Figure 17 a small solenoid valve in the pilot circuit, installed ahead of the thermostatic expansion valve, converts the pilot-operated valve into a stop valve when the solenoid valve is closed.

Equalization Features. When the compressor stops, a thermostatic expansion valve usually moves to the closed position. This movement sustains the difference in refrigerant pressures in the evaporator and the condenser. Low-starting-torque motors require that these pressures be equalized to reduce the torque needed to restart the compressor. One way to provide pressure equalization is to add, parallel to the main valve port, a small fixed auxiliary passageway, such as a slot or drilled hole in the valve seat or valve pin. This opening allows limited fluid flow through the valve, even when the valve is closed, and allows the system pressures to equalize on the off cycle. The size of a fixed auxiliary passageway must be limited so its flow capacity is not greater than the smallest flow that must be controlled in normal system operation. For a drilled hole, the hole’s diameter should be bigger than the maximum allowable particle size circulating in the system, to prevent permanent obstructions. Slots in the seat may be a more robust solution, because any particle obstructing the slot would be flushed when the expansion valve opens fully.

Another, more complex control is available for systems requiring shorter equalizing times than can be achieved with the fixed auxiliary passageway. This control incorporates an auxiliary valve port, which bypasses the primary port and is opened by the element diaphragm as it moves toward and beyond the position at which the primary valve port is closed. Flow capacity of an auxiliary valve port can be considerably larger than that of the fixed auxiliary passageway, so pressures can equalize more rapidly.

Flooded System. Thermostatic expansion valves are seldom applied to flooded evaporators because superheat is necessary for proper valve control; only a few degrees of suction vapor superheat in a flooded evaporator incurs a substantial loss in system capacity. If the bulb is installed downstream from a liquid-to-suction heat exchanger, a thermostatic expansion valve can be made to operate at this point on a higher superheat. Valve control is likely to be poor because of the variable rate of heat exchange as flow rates change (see the section on Application).

Some expansion valves have modified thermostatic elements in which electric heat is supplied to the bulb. The bulb is inserted in direct contact with refrigerant liquid in a low-side accumulator. The contact of cold refrigerant liquid with the bulb overrides the artificial heat source and throttles the expansion valve. As liquid falls away from the bulb, the valve feed increases again. Although similar in construction to a thermostatic expansion valve, it is essentially a modulating liquid-level control valve.

Desuperheating Valves. Thermostatic expansion valves with special thermostatic charges are used to reduce gas temperatures (superheat) on various air-conditioning and refrigeration systems. Suction gas in a single-stage system can be desuperheated by injecting liquid directly into the suction line. This cooling may be required with or without discharge gas bypass used for compressor capacity control. The line upstream of the valve bulb must be long enough so the injected liquid refrigerant can mix adequately with the gas being desuperheated. On compound compression systems, an expansion valve may be used to inject liquid directly into the interstage line upstream of the expansion valve bulb location to provide intercooling.

 Application

Hunting is alternate overfeeding and starving of the refrigerant feed to the evaporator. It produces sustained cyclic changes in the pressure and temperature of refrigerant gas leaving the evaporator. Extreme hunting reduces refrigeration system capacity because mean evaporator pressure and temperature are lowered and compressor capacity is reduced. If overfeeding of the expansion valve causes intermittent flooding of liquid into the suction line, the compressor may be damaged.

Although hunting is commonly attributed to the thermostatic expansion valve, it is seldom solely responsible. One reason for hunting is that all evaporators have a time lag. When the bulb signals for a change in refrigerant flow, the refrigerant must traverse the entire evaporator before a new signal reaches the bulb. This lag or time lapse may cause continuous overshooting of the valve both opening and closing. In addition, the thermostatic element, because of its mass, has a time lag that may be in phase with the evaporator lag and amplify the original overshooting.

It is possible to alter the thermostatic element’s response rate by either using thermal ballast or changing the mass or heat capacity of the bulb, thereby damping or even eliminating hunting. A change in valve gradient may produce a similar result.

Slug flow or percolation in the evaporator can also cause hunting. Under these conditions, liquid refrigerant moves in waves (slugs) that fill a portion of the evaporator tube and erupt into the suction line. These unevaporated slugs chill the bulb and temporarily reduce the feed of the valve, resulting in intermittent starving of the evaporator.

On multiple-circuit evaporators, a lightly loaded or overfed circuit also floods into the suction line, chills the bulb, and throttles the valve. Again, the effect is intermittent; when the valve feed is reduced, flooding ceases and the valve reopens.

Hunting can be minimized or avoided in the following ways:

  • Select the proper valve size from the valve capacity ratings rather than nominal valve capacity; oversized valves aggravate hunting.

  • Change the valve adjustment. A lower superheat setting usually (but not always) increases hunting.

  • Select the correct thermostatic element charge. Cross-charged elements are less susceptible to hunting.

  • Design the evaporator section for even flow of refrigerant and air. Uniform heat transfer from the evaporator is only possible if refrigerant is distributed by a properly selected and applied refrigerant distributor and air distribution is controlled by a properly designed housing. (Air-cooling and dehumidifying coils, including refrigerant distributors, are detailed in Chapter 23 of the 2020 ASHRAE Handbook—HVAC Systems and Equipment.)

  • Size and arrange suction piping correctly.

  • Locate and apply the bulb correctly.

  • Select the best location for the external equalizer line connection.

Bulb Location. Most installation requirements are met by strapping the bulb to the suction line to obtain good thermal contact between them. Normally, the bulb is attached to a horizontal line upstream of the external equalizer connection (if used) at a 3 or 9 o’clock position as close to the evaporator as possible. The bulb is not normally placed near or after suction-line traps, but some designers test and prove locations that differ from these recommendations. A good moisture-resistant insulation over the bulb and suction line diminishes the adverse effect of varying ambient temperatures at the bulb location.

Occasionally, the bulb of the thermostatic expansion valve is installed downstream from a liquid-suction heat exchanger to compensate for a capacity shortage caused by an undersized evaporator. Although this procedure seems to be a simple method of maximizing evaporator capacity, installing the bulb downstream of the heat exchanger is undesirable from a control standpoint. As the valve modulates, the liquid flow rate through the heat exchanger changes, causing the rate of heat transfer to the suction vapor to change. An exaggerated valve response follows, resulting in hunting. There may be a bulb location downstream from the heat exchanger that reduces hunting considerably. However, the danger of floodback to the compressor normally overshadows the need to attempt this method.

Certain installations require increased bulb sensitivity as a protection against floodback. The bulb, if located properly in a well in the suction line, has a rapid response because of its direct contact with the refrigerant stream. Bulb sensitivity can be increased by using a bulb smaller than is normally supplied. However, using a smaller bulb is limited to gas-charged valves. Good piping practice also affects expansion valve performance.

Figure 18 shows the proper piping arrangement when the suction line runs above the evaporator. A lubricant trap that is as short as possible is located downstream from the bulb. The vertical riser(s) must be sized to produce a refrigerant velocity that ensures continuous return of lubricant to the compressor. The terminal end of the riser(s) enters the horizontal run at the top of the suction line; this avoids interference from overfeeding any other expansion valve or any drainback during the off cycle.

If circulated with lubricant-miscible refrigerant, a heavy concentration of lubricant elevates the refrigerant’s boiling temperature. The response of the thermostatic charge of the expansion valve is related to the saturation pressure and temperature of pure refrigerant. In an operating system, the false pressure/temperature signals of lubricant-rich refrigerants cause floodback or operating superheats considerably lower than indicated, and quite often cause erratic valve operation. To keep lubricant concentration at an acceptable level, either the lubricant pumping rate of the compressor must be reduced or an effective lubricant separator must be used.

Bulb Location When Suction Main Is Above Evaporator

Figure 18. Bulb Location When Suction Main Is Above Evaporator


The external equalizer line is ordinarily connected at the evaporator outlet, as shown in Figure 18. It may also be connected at the evaporator inlet or at any other point in the evaporator downstream of the major pressure drop. On evaporators with long refrigerant circuits that have inherent lag, hunting may be minimized by changing the connection point of the external equalizer line.

In application, the various parts of the valve’s thermostatic element are simultaneously exposed to different thermal influences from the surrounding ambient air and the refrigerant system. In some situations, cold refrigerant exiting the valve dominates and cools the thermostatic element to below the bulb temperature. When this occurs with a gas-charged or gas cross-charged valve, the charge condenses at the coldest point in the element and control of refrigerant feed moves from the bulb to the thermostatic element (diaphragm chamber). Pressure applied to the top of the diaphragm diminishes to saturation pressure at the cold point. Extreme starving of the evaporator, progressing to complete cessation of refrigerant flow, is characteristic. For this reason, gas-charged or gas cross-charged valves should be applied only to multicircuited evaporators that use refrigerant distributors. The distributor typically provides sufficient pressure drop to maintain a saturation temperature at the valve outlet well above the temperature at the bulb location.

Internally equalized gas-charged or gas cross-charged valves should only be considered in very carefully selected applications where the risk of loss of control can be minimized. Some gas cross-charge formulations may be slightly less susceptible to the described loss of control than are straight gas charges, but they are far from immune. Gas-charged and gas cross-charged valves with specially constructed thermostatic power elements that positively isolate the charge fluids in the temperature-sensing element (bulb) have been applied in situations where there was high risk of control loss and the pressure-limiting feature of a gas-charged valve was required.

Gas-charged bulbless valves, frequently called block valves (Figure 19), are practically immune to loss of control because the thermostatic element (diaphragm chamber) is located at the evaporator outlet. The valve is constructed so that the temperature-sensing function of the remote bulb is integrated into the thermostatic element by purposely confining all of the charge fluid to this chamber.

Typical Block Valve

Figure 19. Typical Block Valve


Liquid, liquid cross-charged, and adsorption-charged valves are not susceptible to the same type of loss of control that gas-charged or gas cross-charged valves are. However, exposure to extreme ambient temperature environments causes shifting of operating superheats. The degree of superheat shift depends on the severity of the thermal exposure. High ambient temperatures surrounding thermally sensitive parts of the valve typically lower operating superheats, and vice versa. Gas-charged and gas cross-charged valves, including bulbless or block valves, respond to high ambient exposure similarly but starve the evaporator when exposed to ambient temperatures below evaporator outlet refrigerant temperatures.

3.2 ELECTRIC EXPANSION VALVES

Application of an electric expansion valve requires a valve, controller, and control sensors. The control sensors may include pressure transducers, thermistors, resistance temperature devices (RTDs), or other pressure and temperature sensors. See Chapter 37 in the 2017 ASHRAE Handbook—Fundamentals for a discussion of instrumentation. Specific types should be discussed with the electric valve and electronic controller manufacturers to ensure compatibility of all components.

Electric valves typically have four basic types of actuation:

  • Heat motor operated

  • Magnetically modulated

  • Pulse-width-modulated (on/off type)

  • Step-motor-driven

Heat motor valves may be one of two types. In one type, one or more bimetallic elements are heated electrically, causing them to deflect. The bimetallic elements are linked mechanically to a valve pin or poppet; as the bimetallic element deflects, the valve pin or poppet follows the element movement. In the second type, a volatile fluid is contained within an electrically heated chamber so that the regulated temperature (and pressure) is controlled by electrical power input to the heater. The regulated pressure acts on a diaphragm or bellows, which is balanced against atmospheric air pressure or refrigerant pressure. The diaphragm is linked to a pin or poppet, as shown in Figure 20.

A magnetically modulated (analog) valve functions by modulation of an electromagnet; a solenoid armature compresses a spring progressively as a function of magnetic force (Figure 21). The modulating armature may be connected to a valve pin or poppet directly or may be used as the pilot element to operate a much larger valve. When the modulating armature operates a pin or poppet directly, the valve may be of a pressure-balanced port design so that pressure differential has little or no influence on valve opening.

Fluid-Filled Heat-Motor Valve

Figure 20. Fluid-Filled Heat-Motor Valve


The pulse-width-modulated valve is an on/off solenoid valve with special features that allow it to function as an expansion valve through a life of millions of cycles (Figure 22). Although the valve is either fully opened or closed, it operates as a variable metering device by rapidly pulsing the valve open and closed. For example, if 50% flow is needed, the valve will be open 50% of the time and closed 50% of the time. The duration of each opening, or pulse, is regulated by the electronics.

Magnetically Modulated Valve

Figure 21. Magnetically Modulated Valve


Pulse-Width-Modulated Valve

Figure 22. Pulse-Width-Modulated Valve


A step motor is a multiphase motor designed to rotate in discrete fractions of a revolution, based on the number of signals or “steps” sent by the controller. The controller tracks the number of steps and can offer fine control of the valve position with a high level of repeatability. Step motors are used in instrument drives, plotters, and other applications where accurate positioning is required. When used to drive expansion valves, a lead screw changes the rotary motion of the rotor to a linear motion suitable for moving a valve pin or poppet (Figure 23A). The lead screw may be driven directly from the rotor, or a reduction gearbox may be placed between the motor and lead screw. The motor may be hermetically sealed within the refrigerant environment, or the rotor may be enclosed in a thin-walled, nonmagnetic, pressuretight metal tube, similar to those used in solenoid valves, which is surrounded by the stator such that the rotor is in the refrigerant environment and the stator is outside the refrigerant environment. In some designs, the motor and gearbox can operate outside the refrigerant system with an appropriate stem seal (Figure 23B).

Step Motor with (A) Lead Screw and (B) Gear Drive with Stem Seal

Figure 23. Step Motor with (A) Lead Screw and (B) Gear Drive with Stem Seal


Electric expansion valves may be controlled by either digital or analog electronic circuits. Electronic control gives additional flexibility over traditional mechanical valves to consider control schemes that would otherwise be impossible, including stopped or full flow when required.

The electric expansion valve, with properly designed electronic controllers and sensors, offers a refrigerant flow control means that is not refrigerant specific, has a very wide load range, can often be set remotely, and can respond to a variety of input parameters.

4. REGULATING AND THROTTLING VALVES

Regulating and throttling valves are used in refrigeration systems to perform a variety of functions. Valves that respond to and control their own inlet pressure are called upstream, inlet, or back pressure regulators. This type of regulator, when located in an evaporator vapor outlet line, responds to evaporator outlet pressure and is commonly called an evaporator pressure regulator. A special three-way version of an upstream pressure regulator is designed specifically for air-cooled condenser pressure regulation during cold-weather operation. Valves that respond to and control their own outlet pressure are called downstream or outlet pressure regulators. Downstream pressure regulators located in a compressor suction line regulate compressor suction pressure and may also be called suction-pressure regulators, crankcase pressure regulators, or holdback valves; they are typically used to prevent compressor motor overload. A downstream pressure regulator located at an evaporator inlet to feed liquid refrigerant into the evaporator at a constant evaporator pressure is known as a constant-pressure or automatic expansion valve.

A third category of pressure regulator, a differential pressure regulator, responds to the difference between its own inlet and outlet pressures.

Electronically controlled, electrically operated evaporator-pressure-regulating valves have been developed to control temperature in food merchandising refrigerators and other refrigerated spaces (Figure 24). This type of valve regulates evaporator pressure, although it typically responds to temperature in the space or load as well as pressure in the evaporator or suction line, rather than pressure alone. The system consists of a temperature sensor, pressure transducer, an electronic control circuit that has been programmed by the manufacturer with a control strategy or algorithm, and an electrically driven evaporator-pressure-regulating valve. The set point may be set or changed on site or at a remote location through communication software. The valve responds to the difference between set-point temperature and the sensed temperature in the space or load. A sensed temperature above the set point drives the valve further open, thereby reducing evaporator pressure and saturation temperature; a sensed temperature below set point modulates the valve in the closing direction, which increases evaporator pressure. During defrost, the control circuit usually closes the valve. Additional information on the drive and sensing mechanisms used with this valve type is given in the sections on Electric Expansion Valves and on Control Sensors.

Electronically Controlled, Electrically Operated Evaporator Pressure Regulator

Figure 24. Electronically Controlled, Electrically Operated Evaporator Pressure Regulator


Electronically controlled pressure-regulating valves may also be used in various other applications, such as discharge gas bypass capacity reduction, compressor suction throttling, condenser pressure regulation, gas defrost systems, and heat reclaim schemes.

4.1 EVAPORATOR-PRESSURE-REGULATING VALVES

The evaporator pressure regulator is a regulating valve designed to control its own inlet pressure. Typically installed in the suction line exiting an evaporator, it regulates that evaporator’s outlet pressure, which is the regulator’s upstream or inlet pressure. For this reason, evaporator pressure regulators are also called upstream pressure regulators. They are most frequently used to prevent evaporator pressure (and saturation temperature) from dropping below a desired minimum. As declining regulator inlet pressure approaches the regulator set point, the valve throttles, thereby maintaining the desired minimum evaporator pressure (and temperature). Evaporator pressure regulators are often used to balance evaporator capacity with varying load conditions and to protect against freezing at low loads, such as in water chillers.

The work required to drive pilot-operated valves is most commonly produced by harnessing the pressure loss caused by flow through the valve. Direct-operated regulating valves are powered by relatively large changes in the controlled variable (in this case, inlet pressure). Pilot- and direct-operated evaporator pressure regulators may be classified as self powered. Evaporator pressure regulators are sometimes driven by a high-pressure refrigerant liquid or gas flowing from the system’s high-pressure side, as well as electrically. These types are usually considered to be externally powered.

 Operation

Direct-operated evaporator-pressure-regulating valves are relatively simple, as shown in Figure 25. The inlet pressure acts on the bottom of the seat disk and opposes the spring. The outlet pressure acts on the bottom of the bellows and the top of the seat disc. Because the effective areas of the bellows and the port are equal, these two forces cancel each other, and the valve responds to inlet pressure only. When inlet pressure rises above the equivalent pressure exerted by the spring force, the valve begins to open. When inlet pressure falls, the spring moves the valve in the closing direction. In operation, the valve assumes an intermediate throttling position that balances the refrigerant flow rate with evaporator load.

Because both spring and bellows must be compressed through the entire opening valve stroke, a significant change in inlet pressure is required to open the valve to its rated capacity. Inlet pressure changes of 5 to 10 psi or more, depending on design, are typically required to move direct-operated evaporator pressure regulators from their closed position to their rated flow capacity. Therefore, these valves have relatively high gradients and the system may experience significant changes in regulated evaporator pressure when large load changes occur.

Direct-Operated Evaporator Pressure Regulator

Figure 25. Direct-Operated Evaporator Pressure Regulator


Pilot-operated evaporator-pressure-regulating valves are either self powered or driven by high pressure. The self-powered regulator (Figure 26) starts to open when the inlet pressure approaches the equivalent pressure setting of the diaphragm spring. The diaphragm lifts to allow inlet pressure to flow through the pilot port, which increases the pressure above the piston. This increase moves the piston down, causing the main valve to open. Flow through the opening valve relieves evaporator pressure into the suction line. As evaporator pressure diminishes, the diaphragm throttles flow through the pilot port, a bleed hole in the piston relieves pressure above the piston to the low-pressure outlet side of the main valve, and the main spring moves the valve in the closing direction. Balanced flow rates through the pilot port and piston bleed hole establish a stable piston pressure that balances against the main spring. The main valve assumes an intermediate throttling position that allows the refrigerant flow rate required to satisfy the evaporator load. Pilot-operated regulators have relatively low gradients and are capable of precise pressure regulation in evaporators that experience large load changes. Typically, pressure loss of up to 2 psi may be needed to move the valve to its fully open position.

Pilot-Operated Evaporator Pressure Regulator (Self-Powered)

Figure 26. Pilot-Operated Evaporator Pressure Regulator (Self-Powered)


Suction stop service can be provided with this style regulator by adding a pilot solenoid valve in the equalizer flow passage to prevent inlet pressure from reaching the underside of the pressure pilot diaphragm regardless of inlet pressure. Suction stop service is often required to facilitate and control evaporator defrost.

High-pressure-driven pilot-operated regulating valves are of a normally open design and require high-pressure liquid or gas to provide a closing force. One advantage of this design over self-powered regulators is that it does not require any suction-pressure drop across the valve or large inlet pressure change to operate. When valve inlet pressure increases above set point (Figure 27), the diaphragm moves up against the spring, allowing the pilot valve pin spring to move the pilot valve pin, pin carrier, and push rods (not shown) up toward closing the pilot valve port. Gas or liquid from the high-pressure side of the system is throttled by the pilot valve, and pressure in the top of the piston chamber bleeds to the valve’s downstream side through a bleed orifice. As pressure on top of the piston diminishes, the main body spring moves the valve piston in the opening direction.

As inlet pressure diminishes, increased flow of high-pressure liquid or gas through the pilot valve drives the piston down toward a closed position.

Pilot-Operated Evaporator Pressure Regulator (High-Pressure-Driven)

Figure 27. Pilot-Operated Evaporator Pressure Regulator (High-Pressure-Driven)


A solenoid valve may be used to the drive the piston to the closed position for suction stop service, either by closing the bleed orifice or by supplying high pressure directly to the top of the piston chamber. Note that, in the latter arrangement, a continuous but very small flow of liquid or gas from the system high side is discharged into the suction line downstream of the regulator while the valve is closed. In some applications, this bleed may enhance compressor cooling and lubricant return.

 Selection

Selection of evaporator-pressure-regulating valves is based on the flow capacity required to satisfy the load imposed on the evaporator being regulated and the pressure drop available across the regulator. For example, if an evaporator is to be regulated to a pressure of 30 psig and the regulator discharges into a suction line that normally operates or is maintained at 20 psig, the regulator should be selected to satisfy the evaporator load at a 10 psi pressure loss across the valve. To select direct-operated regulators, consider the high gradient of this design; ensure that the variation of inlet pressure that occurs with load changes is acceptable for the application. For example, a direct-operated regulator set at high-load operating conditions to protect against chiller freeze-up may allow evaporator pressure to drop into the freeze-up danger zone at low loads because of the large reduction in inlet pressure needed to throttle the valve to near-closed stroke. Externally powered regulators should be selected to satisfy the flow requirements imposed by the evaporator load at pressure drops compatible with the application.

Grossly oversized regulating valves are very susceptible to unstable operation, which may in turn upset the stability of other controls in the system, significantly degrade system performance, and risk damage to other system components.

 Application

Evaporator pressure regulators are used on air-cooling evaporators to control frosting or prevent excessive dehumidification. They are also used on water and brine chillers to protect against freezing under low-load conditions.

When multiple evaporators are connected to a common suction line, as shown in Figure 28, evaporator pressure regulators may be installed to control evaporator pressure in each individual unit or in a group of units operating at the same pressure. The regulators maintain the desired saturation temperature in evaporators serving the high- and medium-temperature loads; those for low-temperature loads may be directly connected to the suction main. In these systems, the compressor(s) are loaded, unloaded, and cycled to maintain suction main pressure as the combined evaporator loads vary.

The pilot-operated self-powered evaporator pressure regulator, with internal pilot passage, receives its source of pressure to both power the valve and sense the controlled pressure at the regulator inlet connection. A regulator with an external pilot connection allows a choice of remote pressure source for both controlled pressure sensing and driving the valve. The external pilot connection can also facilitate use of remote pressure and solenoid pilot valves. Figure 28 shows a pilot solenoid valve installed in the external pilot line. This arrangement allows the regulator to function as a suction stop valve as well as an evaporator pressure regulator. The suction stop feature is particularly useful on a flooded evaporator to prevent the refrigerant from leaving the evaporator when the load is satisfied and the evaporator is deactivated. The stop feature is also effective during evaporator defrost cycles, especially with gas defrost systems. When regulator inlet pressure is unstable to the point of upsetting regulator performance, the external pilot connection may be used to facilitate use of volume chambers and other non-flow-restricting damping means to smooth the pilot pressure source before it enters the regulator pilot connection.

Evaporator Pressure Regulators in Multiple System

Figure 28. Evaporator Pressure Regulators in Multiple System


A remote pressure pilot installed in the external pilot line can be located to facilitate manual adjustment of the pressure setting when the main regulator must be installed in an inaccessible location.

Multiple pilots, including temperature-actuated pilots, pressure pilots, and solenoid pilot stop valves, may be connected in various parallel-series arrangements to the external pilot connection, thus allowing the main valve to function in different modes and pressure settings, depending on which pilot is selected to control. The controlling pilot is then selected by activating the appropriate solenoid stop valve. Pressure pilots may also be adapted to accept connection to pneumatic control systems, allowing automatic resetting of the pressure pilot as part of a much more comprehensive control strategy.

Although evaporator pressure regulation is the most common use of upstream pressure regulators, they are also used in a variety of other refrigeration system applications. Upstream pressure regulators may be adapted for internal pressure relief, air-cooled condenser pressure regulation during low ambient operation, and liquid receiver pressure regulation.

4.2 CONSTANT-PRESSURE EXPANSION VALVES

The constant-pressure expansion valve is a downstream pressure regulator that is positioned to respond to evaporator pressure changes and meter the mass flow of liquid refrigerant entering the evaporator to maintain a constant evaporator pressure.

 Operation

Figure 29 shows a cross section of a typical constant-pressure expansion valve. The valve has both an adjustable opening spring, which exerts its force on top of the diaphragm in an opening direction, and a spring beneath the diaphragm, which exerts its force in a closing direction. Evaporator pressure is admitted beneath the diaphragm, through either an internal or external equalizer passage, and the combined forces of evaporator pressure and closing spring counterbalance the adjustable opening spring force.

During normal system operation, a small increase in evaporator pressure pushes the diaphragm up against the adjustable opening spring, allowing the closing spring to move the pin in a closing direction. This restricts refrigerant flow and limits evaporator pressure. When evaporator pressure drops below the valve setting (a decrease in load), the opening spring moves the valve pin in an opening direction. As a result, refrigerant flow increases and raises the evaporator pressure, bringing the three primary forces in the valve back into balance.

Constant-Pressure Expansion Valve

Figure 29. Constant-Pressure Expansion Valve


Because constant-pressure expansion valves respond to evaporator load changes inversely, their primary application is in systems that have nearly constant evaporator loading.

 Selection

The constant-pressure expansion valve should be selected to provide the required liquid refrigerant flow capacity at the expected pressure drop across the valve, and should have an adjustable pressure range that includes the required design evaporator (valve outlet) pressure. The system designer should decide whether off-cycle pressure equalization is required.

 Application

Constant-pressure expansion valves overfeed the evaporator as load diminishes, and underfeed as load increases. Their primary function is to balance liquid flow rate with compressor capacity at constant evaporator pressure/temperature as loading varies, protecting against product freezing at low loads and compressor motor overload when evaporator loading increases. Because the valve responds inversely to evaporator load variations, other means to protect the compressor against liquid floodback at low loads and overheating at high loads (e.g., suction-line accumulators, enhanced compressor cooling or liquid injection devices) are needed in systems that experience significant load variation.

Constant-pressure expansion valves are best suited to simple single-compressor/single-evaporator systems when constant evaporator temperature is important and significant load variation does not occur. They are commonly used in drink dispensers, food dispensers, drinking fountains, ice cream freezers, and self-contained room air conditioners. They are typically direct-operated devices; however, they may be pilot-operated for applications requiring very large capacity. They are also used to regulate hot gas in discharge bypass capacity reduction arrangements, as described in the section on Discharge Bypass Valves.

Constant-pressure expansion valves close in response to the abrupt increase in evaporator pressure when the compressor cycles off, preventing flow during the off cycle. A small, fixed auxiliary passageway, described in the section on Thermostatic Expansion Valves, can also be built into constant-pressure expansion valves to provide off-cycle pressure equalization for use with low-starting-torque compressor motors.

4.3 SUCTION-PRESSURE-REGULATING VALVES

The suction-pressure regulator is a downstream pressure regulator positioned in a compressor suction line to respond to and limit compressor suction pressure. Typically, they are used to prevent compressor motor overload from high suction pressure related to warm start-up, defrost termination, and intermittent high evaporator loading.

 Operation

Direct-acting suction-pressure regulators respond to their own outlet or downstream pressure. They are relatively simple devices, as shown in Figure 30. The valve outlet pressure acts on the bottom of the disk and exerts a closing force, which is opposed by the adjustable spring force. The inlet pressure acts on the underside of the bellows and the top of the seat disk. Because the effective areas of the bellows and port are equal, these two forces cancel each other and the valve responds to outlet pressure only. When outlet pressure falls below the equivalent force exerted by the spring, the seat disk moves in an opening direction to maintain outlet pressure. If outlet pressure rises, the seat disk moves in a closing direction and throttles the refrigerant flow to limit the downstream pressure. The proper pressure setting for a specific system is one that is low enough to protect the compressor from overload without unnecessarily compromising system capacity. Because both spring and bellows must be compressed through the entire closing valve stroke, a significant change in outlet pressure is required to close the valve to its minimum capacity. Outlet pressure changes of 5 to 10 psi or more, depending on design, are typically required to move direct-operated downstream pressure regulators from open position to near closed position. Therefore, these valves have relatively high gradients, and regulated suction pressure may change significantly when large changes in load occur.

Direct-Acting Suction-Pressure Regulator

Figure 30. Direct-Acting Suction-Pressure Regulator


Pilot-operated suction-pressure regulators are available for larger systems and applications requiring more precise pressure regulation over wide load and inlet pressure variations. Their design is significantly more complex, because of pilot operation. The method of operation is similar to that described for pilot-operated evaporator pressure regulators. However, in downstream pressure regulators, the pilot is reverse acting and functions similarly to the constant-pressure expansion valve. Suction stop service can also be provided with this type of regulator.

 Selection

The suction-pressure regulator should be selected to provide the required flow capacity at a low pressure loss to minimize system capacity penalty. However, take care to avoid oversizing, which can lead to unstable regulator operation. The significant change in outlet pressure required to stroke direct-operated regulators should also be considered during selection.

Condenser Pressure Regulation (Two-Valve Arrangement)

Figure 31. Condenser Pressure Regulation (Two-Valve Arrangement)


 Application

Suction-pressure-regulating valves are primarily used to prevent compressor motor overload caused by excessive suction pressure related to warm evaporator start-up, defrost termination, or intermittent high-load operation. These regulating valves are typically designed to operate at normal refrigeration system low-side pressures and temperatures. However, similar-type downstream pressure regulators may be modified to include suitable seat materials and high-gradient springs for application in system high-side pressure and temperature conditions. For example, they may be used in a variety of schemes to maintain necessary operating pressures in air-cooled condensers during cold-weather operation. Additionally, modified regulators are used to bypass compressor discharge gas in refrigeration system capacity reduction schemes, as mentioned in the application sections in the Constant-Pressure Expansion Valves and Discharge Bypass Valves sections.

4.4 CONDENSER-PRESSURE-REGULATING VALVES

Various pressure-regulating valves are used to maintain sufficient pressure in air-cooled condensers during cold-weather operation. Both single- and two-valve arrangements have been used for this purpose. See Chapter 1 in this volume and Chapter 39 of the 2020 ASHRAE Handbook—HVAC Systems and Equipmentfor more information.

 Operation

The first valve in the two-valve arrangement shown in Figure 31 is typically an upstream pressure regulator that is constructed and operates similarly to the evaporator-pressure-regulating valves shown in Figures 25 to 27. Pilot-operated regulators are typically used to meet the flow capacity requirements of large systems. They may have special features that make them suitable for high-pressure and high-temperature operating conditions. This control may be installed at either the condenser inlet or outlet; the outlet is usually preferred because a smaller valve can satisfy the system’s flow capacity requirements. It throttles when the condenser outlet or compressor discharge pressure falls as a result of cold-weather operating conditions.

The second valve in the two-valve arrangement is installed in a condenser bypass line. It may be a downstream pressure regulator similar to the suction-pressure regulator in Figure 30, or a differential pressure regulator as in Figure 31. The differential regulator is often preferred for simplicity; however, the minimum opening differential pressure must be greater than the pressure drop across the condenser at full-load summer operating conditions. As the first valve throttles in response to falling compressor discharge or condenser outlet pressure, the second valve opens and allows hot gas to bypass the condenser to mix with and warm the cold liquid entering the receiver, thereby maintaining adequate high-side saturation pressure.

Special-purpose three-way pressure-regulating valves similar to that shown in Figure 32 are also used for condenser pressure regulation. The valve in Figure 32 is a direct-acting pressure regulator with a second inlet that performs the hot-gas bypass function, eliminating the need for the second valve in the two-valve system described previously. The three-way valve simultaneously throttles liquid flow from the condenser and bypasses hot compressor discharge gas to the valve outlet, where it mixes with and warms liquid entering the receiver, thereby maintaining adequate high-side saturated liquid pressure.

In the three-way valve, the lower side of a flexible metal diaphragm is exposed to system high-side pressure, while the upper side is exposed to a noncondensable gas charge (usually dry nitrogen or air). A pushrod links the diaphragm to the valve poppet, which seats on either the upper or lower port and throttles either discharge gas or liquid from the condenser, respectively. Valves that respond to condenser pressure are frequently used; however, valve designs that respond to receiver pressure are available.

Three-Way Condenser-Pressure-Regulating Valve

Figure 32. Three-Way Condenser-Pressure-Regulating Valve


During system start-up in extremely cold weather, the poppet may be tight against the lower seat, stopping all liquid flow from the condenser and bypassing discharge gas into the receiver until adequate system high-side pressure is generated. During stable operation in cold weather, the poppet modulates at an intermediate position, with liquid flow from the condensing coil mixing with compressor discharge gas in the valve outlet and flowing to the receiver. With higher condensing pressure during warm weather, the poppet seats tightly against the upper port, allowing free flow of liquid from condenser to receiver and preventing compressor discharge gas from bypassing the condenser.

The three-way condenser-pressure-regulating valve set point is usually not field adjustable. The pressure setting is established by the pressure of the gas charge placed in the dome above the diaphragm during manufacture. Some designs allow field selection between two factory-predetermined set points.

 Application

Systems using pressure regulators for air-cooled condenser pressure control during cold-weather operation require careful design. Condenser pressure is maintained by partially filling the condenser with liquid refrigerant, reducing the effective condensing surface available. The condenser is flooded with liquid refrigerant to the point of balancing condenser capacity at low ambient with condenser loading. The system must have adequate refrigerant charge and receiver capacity to maintain a liquid seal at the expansion valve inlet while allowing sufficient liquid for head pressure control to accumulate in the condenser. If the system cycles off or otherwise becomes idle during cold weather, the receiver must be kept warm during the off time so that adequate liquid pressure is available at start-up. When receivers are exposed to low temperatures, it may be necessary to provide receiver heaters and insulation to ensure start-up capability. A check valve at the receiver inlet may be advisable.

Because these systems necessarily contain abnormally large refrigerant charges, careful consideration must be given to controlling refrigerant migration during system idle times under adverse ambient temperatures.

4.5 DISCHARGE BYPASS VALVES

The discharge bypass valve (or hot-gas bypass valve) is a downstream pressure regulator located between the compressor discharge line and the system low-pressure side, and responds to evaporator pressure changes to maintain a desired minimum evaporator pressure. Typically, they are used to limit the minimum evaporator pressure during periods of reduced load to prevent coil icing or to avoid operating the compressor at a lower suction pressure than recommended. See Chapter 1 for more information.

 Operation

A typical mechanical discharge bypass valve has the same basic configuration as the constant-pressure expansion valve in Figure 29. Construction materials for the discharge bypass valves are suitable for application at high pressure and temperature.

The equivalent pressure from the adjustable spring is balanced across the diaphragm against system evaporator pressure. When evaporator pressure falls below the valve setting, the spring strokes the valve member in the opening direction.

 Selection

Discharge bypass valves are rated on the basis of allowable evaporator temperature change from closed position to rated opening. This is 6°F for most air-conditioning applications, although capacity multipliers for other changes are available to make the appropriate valve selection. Because several basic system factors are involved in appropriate selection, it is important to know the type of refrigerant, minimum allowable evaporating temperature at the reduced-load condition, compressor capacity at minimum allowable evaporating temperature, minimum evaporator load at which the system is to be operated, and condensing temperature when minimum load exists.

 Application

Refrigeration systems experience load variations to some degree throughout the year and may use discharge bypass valves to balance compressor capacity with system load. Depending on the system size and type of compressor used, this valve type may be used in place of compressor cylinder unloaders or to handle the unloading requirements below the last step of cylinder unloading. Depending on the system components and configuration, hot gas may be introduced (1) directly into the suction line or (2) into the evaporator inlet through a specially designed refrigerant distributor, where it mixes with cold refrigerant from the system thermostatic expansion valve to control suction gas temperature before the gas reaches the compressor. If the hot gas is introduced directly into the suction line, be careful to prevent the compressor from overheating (see Chapter 1 for recommendations).

The location of the discharge bypass valve and necessary accessories depend on the type of system (see Chapter 1). Valve manufacturers’ literature gives proper locations and piping recommendations for their products.

In variable-displacement compressors (widely used in automotive air-conditioning systems), a discharge bypass valve (also called a compressor-control valve) is located between the discharge and crankcase of the compressor. This bypass valve regulates pressure in the crankcase and maintains balance between the suction, discharge, and crankcase pressures, thereby establishing the angular position of the wobble or swash plate (for piston compressors), which results in regulating the compressor’s displacement. The compressor-control valve can be pneumatically driven (bellows) or electronically driven (direct solenoid or solenoid acting on bellows).

4.6 HIGH-SIDE FLOAT VALVES

 Operation

A high-side float valve controls the mass flow of refrigerant liquid entering the evaporator so it equals the rate at which the refrigerant gas is pumped from the evaporator by the compressor. Figure 33 shows a cross section of a typical valve. The refrigerant liquid flows from the condenser into the high-side float valve body, where it raises the float and moves the valve pin in an opening direction, allowing the liquid to pass through the valve port, expand, and flow into the evaporator or low-pressure receiver. Most of the system refrigerant charge is contained in the evaporator or low-pressure receiver at all times.

 Selection

For acceptable performance, the high-side float valve is selected for the refrigerant and a rated capacity neither too large nor too small. The orifice is sized for the maximum required capacity with the minimum pressure drop across the valve. The valve operated by the float may be a pin-and-port construction (Figure 33), a butterfly valve, a balanced double-ported valve, or a sliding gate or spool valve. The internal bypass vent tube allows installation of the high-side float valve near the evaporator and above the condenser without danger of the float valve becoming gas bound. Some large-capacity valves use a high-side float valve for pilot operation of a diaphragm or piston spring-loaded expansion valve. This arrangement can improve modulation over a wide range of load and pressure-drop conditions.

High-Side Float Valve

Figure 33. High-Side Float Valve


 Application

A refrigeration system in which a high-side float valve is typically used may be a simple single evaporator/compressor/condenser system or have a low-pressure liquid receiver with multiple evaporators and compressors. The high-pressure receiver or liquid sump at the condenser outlet can be quite small. A full-sized high-pressure receiver may be required for pumping out flooded evaporator(s) and/or low-pressure receivers. The amount of refrigerant charge is critical with a high-side float valve in simple single evaporator/compressor/condenser systems. An excessive charge causes floodback, whereas insufficient charge reduces system capacity.

4.7 LOW-SIDE FLOAT VALVES

 Operation

The low-side float valve performs the same function as the high-side float valve, but it is connected to the low-pressure side of the system. When the evaporator or low-pressure receiver liquid level drops, the float opens the valve. Liquid refrigerant then flows from the liquid line through the valve port and directly into the evaporator or surge drum. In another design, the refrigerant flows through the valve port, passes through a remote feed line, and enters the evaporator through a separate connection. (A typical direct-feed valve construction is shown in Figure 34.) The low-side float system is a flooded system.

 Selection

Low-side float valves are selected in the same way as the high-side float valves discussed previously.

Low-Side Float Valve

Figure 34. Low-Side Float Valve


 Application

In these systems, the refrigerant charge is not critical. The low-side float valve can be used with multiple evaporators such that some evaporators may be controlled by other low-side float valves and some by thermostatic expansion valves.

The float valve is mounted either directly in the evaporator or surge drum or in an external chamber connected to the evaporator or surge chamber by equalizing lines (i.e., a gas line at the top and a liquid line at the bottom). In the externally mounted type, the float valve is separated from the float chamber by a gland that maintains a calm level of liquid in the float chamber for steady actuation of the valve.

In evaporators with high boiling rates or restricted liquid and gas passages, the boiling action of the liquid raises the refrigerant level during operation. When the compressor stops or the solenoid suction valve closes, boiling of the liquid refrigerant ceases, and the refrigerant level in the evaporator drops. Under these conditions, the high-pressure liquid line supplying the low-side float valve should be shut off by a solenoid valve to prevent overfilling the evaporator. Otherwise, excess refrigerant will enter the evaporator on the off cycle, which can cause floodback when the compressor starts or the suction solenoid valve opens.

When a low-side float valve is used, ensure that the float is in a calm liquid level that falls properly in response to increased evaporator load and rises with decreased evaporator load. In low-temperature systems particularly, it is important that the equalizer lines between the evaporator and either the float chamber or surge drum be generously sized to eliminate any reverse response of the refrigerant liquid level near the float. Where the low-side float valve is located in a nonrefrigerated room, the equalizing liquid and gas lines and float chamber must be well insulated to provide a calm liquid level for the float.

4.8 SOLENOID VALVES

Solenoid valves, also called solenoid-operated valves, are comprised of a soft-iron armature positioned in the central axis of a copper wire coil. When electric current flows through the coil, a magnetic field is created that draws the movable armature to it. The armature opens or closes a valve port as it is moved by the magnetic field. This basic operating mechanism is adapted to a wide variety of valve designs and sizes for refrigerant service.

Solenoid valves for refrigerant service are typically two-position devices (i.e., solenoid energized or deenergized). In energized mode, the armature, sometimes called a plunger or core, is drawn into the coil by the magnetic field. The electromagnetic coil must provide the work required to (1) overcome the spring or gravity as well as (2) open or close the valve. In deenergized mode, the armature is moved to the extended end of its stroke by a spring, or in some designs by gravity.

Refrigerant-service solenoid valves enclose the plunger in a thin-walled nonmagnetic metal tube (usually nonmagnetic stainless steel). One end of the tube is closed pressuretight by welding or brazing a soft-iron-bearing magnetic metal plug into the tube. The open end is adapted to the valve body, usually in axial alignment with the valve port. This construction eliminates the need for a dynamic stem seal between the solenoid operator and the valve. Figure 35 shows a semihermetic construction in which the tube, top plug, and lower nut are welded or brazed together. The tube assembly is threaded to the valve body using a metal-to-metal pressuretight seal that eliminates the need for synthetic materials. Some small valves are made completely hermetic by welding or brazing the valve body to the enclosing tube containing the magnetically movable plunger assembly. Most often, the connection between magnetic assembly and valve body is made pressuretight with synthetic gaskets or O rings, as shown in Figure 36.

The copper wire electromagnetic coil, with its associated electrical insulation system, is closely fitted to the outer diameter of the enclosing tube. This arrangement places the coil and insulation outside the pressurized refrigerant environment. The electromagnetic circuit includes the plunger, top plug, metallic housing surrounding the copper wire coil assembly, and any metal spacers or sleeves used to properly position the coil on the tube, as shown in Figure 35. These components are fabricated of soft-iron-bearing magnetic materials and are absolutely essential to acceptable solenoid valve performance. Combined, they form a well-defined and complete magnetic circuit. Many contemporary designs use molded resin coil assemblies that encapsulate the coil and outer soft-iron housing within the resin. This construction enhances heat dissipation, protects electrical parts from moisture and mechanical damage, and simplifies field assembly.

Normally Closed Direct-Acting Solenoid Valve with Hammer-Blow Feature

Figure 35. Normally Closed Direct-Acting Solenoid Valve with Hammer-Blow Feature


 Operation

Several valve designs can be reliably operated with a relatively low-powered solenoid, which helps to minimize energy consumption. The major force that must be overcome by the solenoid operator to open a normally closed valve or close a normally open valve is related to the port area multiplied by the pressure differential across the valve when it is closed. The maximum pressure differential that a specific solenoid valve will reliably open against is called the maximum operating pressure differential (MOPD). To provide acceptable MOPD for refrigeration applications with reasonably powered solenoids, it is necessary to design valves with small ports. Small-ported valves can satisfy low-flow-capacity requirements and pilot duty applications. Thus, direct-acting solenoid valves are limited to low-capacity or low-MOPD applications. Large-capacity and high-MOPD applications use pilot-operated valves similar to those in Figures 36 and 37.

Normally Closed Pilot-Operated Solenoid Valve with Direct-Lift Feature

Figure 36. Normally Closed Pilot-Operated Solenoid Valve with Direct-Lift Feature


Solenoid valves are divided into two basic categories related to flow capacity and MOPD:

  • Direct-acting valves (see Figure 35) are capable of relatively small flow capacities with MOPDs suitable for most refrigerant applications, are useful as pilots on larger valves, and can be designed for medium flow capacities with low MOPD.

  • Pilot-operated valves (see Figures 36 and 37) are capable of large flow capacities with a full range of MOPDs suitable for refrigerant applications. They have small direct-acting valves embedded in the main valve body that pilot the main valve. Opening the pilot port creates a pressure imbalance within the main valve mechanism, causing it to open.

Normally Closed Pilot-Operated Solenoid Valve with Hammer-Blow and Mechanically Linked Piston-Pin Plunger

Figure 37. Normally Closed Pilot-Operated Solenoid Valve with Hammer-Blow and Mechanically Linked Piston-Pin Plunger


These basic categories are each divided into several subcategories:

  • Two-way normally closed valves have one inlet, one outlet, and one port that is closed when the solenoid is deenergized. This is by far the most common configuration in a wide variety of refrigerant stop services.

  • Two-way normally open valves have one inlet, one outlet, and one port that is open when the solenoid is deenergized. This configuration is particularly useful in applications requiring a valve that will fail to a normally open position.

  • Three-way diverting valves have one inlet and two outlets; each outlet is associated with its own port so that when the solenoid is deenergized, flow from the common inlet exits through outlet 1, and when the solenoid is energized, outlet 1 is stopped and flow exits through outlet 2. This type may be used to divert hot compressor discharge gas from the normal condenser to the heat reclaim heat exchanger.

  • Three-way mixing valves have two inlets and one outlet; each inlet is associated with its own port so that when the solenoid is deenergized, refrigerant flows from inlet 1 to the common outlet, and when the solenoid is energized, refrigerant flows from inlet 2 to the common outlet. This style, in the direct-acting version, may be used to activate compressor cylinder unloading mechanisms or as a pilot for large gas-powered valves that use system high-side pressure to close normally open stop valves.

  • Four-way reversing valves have two inlets and two outlets. One connection always functions as an inlet. Another one of the four always functions as an outlet. Flow in the remaining two connections is reversed when the solenoid is energized or deenergized. This configuration is used almost exclusively to switch heat pumps between cooling and heating modes. The direct-acting version is used to pilot the main valve, and both main and pilot valves are most often hybrid spool valves. Figures 38 and 39 show these valves schematically in deenergized and energized modes, respectively.

Figure 35 shows a direct-acting normally closed two-way valve with a long-stroke solenoid that uses a “lost-motion hammer-blow” mechanism to hit the valve pin and overcome the pressure differential force holding the valve closed. This design, though providing some additional opening capability, is less reliable with respect to MOPD repeatability and has a shorter cyclic life because of the high-momentum impacts between plunger, pin, and top plug. It also relies entirely on gravity to move the valve in the closing direction when the solenoid is deenergized. This reliance limits installation to an upright position with the magnetic assembly on top.

Four-Way Refrigerant-Reversing Valve Used in Heat Pumps (Shown in Heating Mode)

Figure 38. Four-Way Refrigerant-Reversing Valve Used in Heat Pumps (Shown in Heating Mode)


Four-Way Refrigerant-Reversing Valve (Shown in Cooling Mode)

Figure 39. Four-Way Refrigerant-Reversing Valve (Shown in Cooling Mode)


A common design of direct-acting solenoid is the direct-lift type such as the solenoid operator portion of the pilot-operated valve in Figure 36. The short stroke minimizes mechanical damage related to impact of the plunger with the top plug and minimizes inrush current in alternating current systems. The closing spring allows installation in any position. Some solenoids of this short-stroke design can survive extended periods of time in failure mode (i.e., when the coil is energized but the valve fails to open because of excessive pressure, low voltage, or other reasons) without significant damage to the coil.

Figure 36 also shows a pilot-operated valve that uses a semi-flexible diaphragm to operate the main valve. When the solenoid is energized, the pilot port (shown centered over the main port) opens and allows pressure above the diaphragm to diminish as it discharges to low pressure at the valve outlet. The higher valve inlet pressure on the underside of the diaphragm surrounding the main port causes the diaphragm to move up, opening the main port to full flow. The ratio of diaphragm area to port area as well as the relative flow rates of bleed hole D and the pilot port are carefully balanced in the design. This ensures that adequate opening force develops to meet the MOPD requirements of the valve specification. When the solenoid is deenergized, the plunger moves down, closing the pilot port, and inlet pressure flowing through bleed hole D allows pressure above the diaphragm to equalize with valve inlet pressure. The entire top of the diaphragm is exposed to inlet pressure; on the bottom side, only the annular area surrounding the port is exposed to inlet pressure; the center portion is exposed to outlet pressure. The net effect of the pressure and area differences is a force that pushes the diaphragm down to close the main port. The spring in the top of the plunger causes the plunger to follow the falling pilot port, keeping it sealed and providing additional downward push on the diaphragm to help close the main port. In the valve of Figure 36, the pilot operator is centrally located directly over the main port. In this configuration, the diaphragm stroke is limited. When larger diaphragm strokes are required for greater flow capacity, the pilot operator and pilot port are relocated to a point beyond the perimeter of the diaphragm over the main valve outlet connection. Separate flow passages in the valve body are provided to conduct pilot port flow from the top of the diaphragm to the valve outlet. This arrangement is usually called an “offset pilot” and retains the benefits of a short-stroke solenoid operator while allowing a diaphragm stroke commensurate with full flow through the main port.

The pilot-operated valve shown in Figure 37 operates according to the same principles as the diaphragm valve, but uses a piston instead of a diaphragm. The carefully controlled annular clearance between piston and inside bore of the valve body is often used to perform the function of bleed hole D (shown in Figure 36), eliminating the need for a separate bleed hole in the piston. The valve in Figure 37 uses a long-stroke hammer-blow pilot operator, which allows long main valve strokes to accommodate large flow capacity requirements without offsetting the pilot. The centered pilot allows mechanically linking the main piston to the plunger assembly to help hold the valve wide open at near-zero pressure drops in low-temperature suction-line applications.

Figure 38 shows a four-way valve, piloted by a four-way direct acting valve shown in the deenergized (heating) position. The reversing valve can be installed to allow for either heating or cooling when energized, depending on the heat pump designer’s preference; this setup cannot be changed after the system is in operation. While the heat pump compressor operates, the high-pressure refrigerant vapor is pumped into reversing valve tube D. A small amount of the flow is carried by capillary tube K to the direct-acting pilot valve. This pilot valve sends this small flow into chamber E of the reversing valve through capillary tube L. The pilot valve also connects chamber F to reversing valve tube S attached to the compressor suction port by way of capillary tubes M and N. The flows applied to chambers E and F build a pressure difference that moves and holds the reversing valve main slide C in its required position. While in position, slide C allows flow from tube D to go along flow path H and out of the reversing valve through tube B. This tube is connected to the indoor heat exchanger. Refrigerant vapor returning from the outdoor heat exchanger enters tube A of the reversing valve and is directed by slide C along flow path J and out the reversing valve tube S. Tube S is connected to the compressor suction port.

Figure 39 shows the reversing valve in its energized (cooling) position. To reach and maintain this position, the capillary tube flows are now from tube D through capillary tubes K and M to chamber F. There is also a small flow from chamber E going to the compressor suction through capillary tubes L and N. As the reversing valve shifts, refrigerant flow from the compressor follows internal path P going out through tube A and flow to suction follows path Q and out tube S. The outdoor heat exchanger is now the condenser, and the indoor heat exchanger is the evaporator. The system has reversed to cooling mode.

 Application

Solenoid valves are generally vulnerable to particles in the refrigerant stream and should be protected by a strainer or filter-drier.

Attitude-sensitive valves must be carefully oriented and properly supported to ensure reliable operation. Take care to avoid overheating sensitive valve parts when installation involves soldering, brazing, or welding.

Electrical service provided to solenoid operators deserves careful attention. Most solenoid valve performance failures are related to improper or inadequate provision of electric power to the solenoid. Undervoltage when attempting to open seriously compromises MOPD and causes a failure to open. Continued application of power to an alternating current (AC) solenoid coil installed on a valve that is unable to open overheats the coil and may lead to premature coil failure, even at undervoltage. Although direct current (DC) solenoids may tolerate a little more voltage variation, overvoltage leads to overheating, even when the valve successfully opens, and shortens coil life; undervoltage reduces the MOPD.

The probability of experiencing undervoltage at the moment of opening with AC systems increases when a control transformer of limited capacity supplies power to the solenoid. This type of transformer is commonly used to supply power to low-voltage control systems using class 2 wiring. The situation is aggravated when more than one device served by the same transformer is energized simultaneously.

4.9 CONDENSING WATER REGULATORS

Condensing water regulators are used for head pressure control during year-round operation of refrigeration systems. Additional information can be found in Chapter 14 of the 2020 ASHRAE Handbook—HVAC Systems and Equipment, in the section on Chiller Plant Operation Optimization in Chapter 47 of the 2019 ASHRAE Handbook—HVAC Applications, and in Chapter 1 of this volume, under Head Pressure Control for Refrigerant Condensers.

 Two-Way Regulators

Condensing water regulators modulate the quantity of water passing through a water-cooled refrigerant condenser in response to the condensing pressure. They are available for use with most refrigerants, including ammonia (R-717). Most manufacturers stress that these valves are designed for use only as operating devices. Where system closure, improper flow, or loss of pressure caused by valve failure can result in personal injury, damage, or loss of property, separate safety devices must be added to the system.

These devices are used on vapor-cycle refrigeration systems to maintain satisfactory condensing pressure. The regulator automatically modulates to correct for both variations in temperature or pressure of the water supply and variations in the quantity of refrigerant gas being pumped into the condenser.

Operation. The condensing water regulator consists of a valve and an actuator linked together, as shown in Figure 40. The actuator consists of a metallic bellows and adjustable spring combination connected to the system high side.

After a compressor starts, the compressor discharge pressure begins to rise. When the opening pressure setting of the regulator spring is reached, the bellows moves to open the valve disk gradually. The regulator continues to open as condenser pressure rises, until water flow balances the required heat rejection. At this point, the condenser pressure is stabilized. When the compressor stops, the continuing water flow through the regulator causes the condenser pressure to drop gradually, and the regulator becomes fully closed when the opening pressure setting of the regulator is reached.

Two-Way Condensing Water Regulator

Figure 40. Two-Way Condensing Water Regulator


Selection. The regulator should be selected from the manufacturer’s data on the basis of maximum required flow, minimum available pressure drop, water temperature, and system operating conditions to avoid hunting or internal erosion caused by high pressure drops through an oversized valve because it operates only partially open for most of its duty cycle. Also, depending on the specific refrigerant being used, special components may be required (e.g., stainless steel rather than brass bellows for ammonia).

The water flow required depends on condenser performance, temperature of available water, quantity of heat that must be rejected to the water, and desired operating condenser pressure. For a given opening of the valve, which corresponds to a given pressure rise above the regulator opening point, the flow rate handled by a given size of water regulator is a function of the available water-pressure drop across the valve seat.

Application. Because there are two types of control action available (direct- or reverse-acting), these regulators can be used for various applications (e.g., water-cooled condensers, bypass service on refrigeration systems, ice machines, heat pump systems that control water temperature). For equipment with a large water flow requirement, a small regulator is used as a pilot valve for a diaphragm main valve.

Manufacturers of these types of devices have technical literature to help in applying their products to specific systems.

 Three-Way Regulators

These regulators are similar to two-way regulators, but they have an additional port, which opens to bypass water around the condenser as the port controlling water flow to the condenser closes (Figure 41). Thus, flow through the cooling tower decking or sprays and the circulating pump is maintained, although the water supply to individual or multiple condensers is modulated for control.

Operation. The three-way regulator operates similar to the two-way regulator. Low refrigerant head pressure, which may result from low cooling-tower water temperature, decreases the refrigeration system’s cooling ability rapidly. The three-way regulator senses the compressor head pressure and allows cooling water to flow to the condenser, bypass the condenser, or flow to both the condenser and bypass line to provide correct refrigerant head pressures.

Three-Way Condensing Water Regulator

Figure 41. Three-Way Condensing Water Regulator


The regulator allows water flow to the tower through the bypass line, even though the condenser does not require cooling. This provides an adequate head of water at the tower at all times so the tower can operate efficiently with minimum maintenance on nozzles and wetting surfaces.

Selection. Selection considerations are the same as for two-way regulators, including the cautions about oversizing.

Application. Pressure-actuated three-way regulators are used for condensing units cooled by atmospheric or forced-draft cooling towers requiring individual condenser pressure control. They may be used on single or multiple condenser piping arrangements to the tower to provide the most economical and efficient use.

These regulators must be supplemented by other means if cooling towers are to be operated in freezing weather. An indoor sump is usually required, and a temperature-actuated three-way water control valve diverts condenser leaving water directly to the sump when the water becomes too cold.

Strainers are not generally required with water regulators.

4.10 CHECK VALVES

Refrigerant check valves are normally used in refrigerant lines in which pressure reversals can cause undesirable reverse flows. A check valve is usually opened by a portion of the pressure drop. Closing usually occurs either when pressure reverses or when the pressure drop across the check valve is less than the minimum opening pressure drop in the normal flow direction.

The conventional large check valve uses piston construction in a globe-pattern valve body, whereas in-line designs are common for 2 in. or smaller valves. Either design may include a closing spring; a heavier spring gives more reliable and tighter closing but requires a greater pressure differential to open. Conventional check valves may be designed to open at less than 1 psi, but they may not be reliable below −25°F because the light closing springs may not overcome viscous lubricants.

 Seat Materials

Although precision metal seats may be manufactured nearly bubbletight, they are not economical for refrigerant check valves. Seats made of synthetic elastomers provide excellent sealing at medium and high temperatures, but may leak at low temperatures because of their lack of resilience. Because high temperatures deteriorate most elastomers suitable for refrigerants, plastic materials have become more widely used, despite being susceptible to damage by large pieces of foreign matter.

 Applications

In compressor discharge lines, check valves are used to prevent flow from the condenser to the compressor during the off cycle or to prevent flow from an operating compressor to an idle compressor. Although a 2 to 6 psi pressure drop is tolerable, the check valve must resist pulsations caused by the compressor and the temperature of discharge gas. Also, the valve must be bubbletight to prevent liquid refrigerant from accumulating at the compressor discharge valves or in the crankcase.

In liquid lines, a check valve prevents reverse flow through the unused expansion device on a heat pump or prevents back-up into the low-pressure liquid line of a recirculating system during defrosting. Although a 2 to 6 psi pressure drop is usually acceptable, the check-valve seat must be bubbletight.

In the suction line of a low-temperature evaporator, a check valve may be used to prevent transfer of refrigerant vapor to a lower-temperature evaporator on the same suction main. In this case, the pressure drop must be less than 2 psi, the valve seating must be reasonably tight, and the check valve must be reliable at low temperatures.

In hot-gas defrost lines, check valves may be used in the branch hot-gas lines connecting the individual evaporators to prevent crossfeed of refrigerant during the cooling cycle when defrost is not taking place. In addition, check valves are used in the hot-gas line between the hot-gas heating coil in the drain pan and the evaporator to prevent pan coil sweating during the refrigeration cycle. Tolerable pressure drop is typically 2 to 6 psi, seating must be nearly bubbletight, and seat materials must withstand high temperatures.

Be careful when sizing check valves, because oversized check valves may chatter or pulsate.

4.11 RELIEF DEVICES

A refrigerant relief device has either a safety or functional use. A safety relief device is designed to relieve positively at its set pressure for one crucial occasion without prior leakage. Relief may be to the atmosphere or to the low-pressure side.

A functional relief device is a control valve that may be required to open, modulate, and close with repeatedly accurate performance. Relief is usually from a portion of the system at higher pressure to a portion at lower pressure. Design refinements of the functional relief valve usually make it unsuitable or uneconomical as a safety relief device

 Safety Relief Valves

These valves are most commonly a pop-type design, which open abruptly when the inlet pressure exceeds the outlet pressure by the valve setting pressure (Figure 42). Seat configuration is such that once lift begins, the resulting increased active seat area causes the valve seat to pop wide open against the force of the setting spring. Because the flow rate is measured at a pressure of 10% above the setting, the valve must open within this 10% increase in pressure.

Pop-Type Safety Relief Valves

Figure 42. Pop-Type Safety Relief Valves


This relief valve operates on a fixed pressure differential from inlet to outlet. Because the valve is affected by back pressure, a rupture disk must not be installed at the valve outlet.

Relief valve seats are made of metal, plastic, lead alloy, or synthetic elastomers. Elastomers are commonly used because they have greater resilience and, consequently, reseat more tightly than other materials. Some valves that have lead-alloy seats have an emergency manual reseating stem that allows reforming the seating surface by tapping the stem lightly with a hammer. Advantages of the pop-type relief valve are simplicity of design, low initial cost, and high discharge capacity.

Capacities of pressure-relief valves are determined by test in accordance with the provisions of the ASME Boiler and Pressure Vessel Code. Relief valves approved by the National Board of Boiler and Pressure Vessel Inspectors are stamped with the applicable code symbol(s). (Consult the Boiler and Pressure Vessel Code for specific text and marking details.) In addition, the pressure setting and capacity are stamped on the valve.

When relief valves are used on pressure vessels of 10 ft3 internal gross volume or more, a relief system consisting of a three-way valve and two relief valves in parallel is required.

Pressure Setting. The maximum pressure setting for a relief device is limited by the design working pressure of the vessel to be protected. Pressure vessels normally have a safety factor of 5. Therefore, the minimum bursting pressure is five times the rated design working pressure (design pressure). The relief device must have enough discharge capacity to prevent pressure in the vessel from rising more than 10% above its design pressure. Because the capacity of a relief device is measured at 10% above its stamped setting, the setting cannot exceed the design pressure of the vessel.

To prevent loss of refrigerant through pressure-relief devices during normal operating conditions, the relief setting must be substantially higher than the system operating pressure. For rupture members, the setting should be 50% above a static system pressure and 100% above a maximum pulsating pressure. Failure to provide this margin of safety causes fatigue of the frangible member and rupture well below the stamped setting.

For relief valves, the setting should be 25% above maximum system pressure. This provides sufficient spring force on the valve seat to maintain a tight seal and still allow for setting tolerances and other factors that cause settings to vary. Although relief valves are set at the factory to be close to the stamped setting, the variation may be as much as 10% after the valves have been stored or placed in service.

Discharge Piping. The size of the discharge pipe from the pressure-relief device or fusible plug must not be less than the size of the pressure-relief device or fusible plug outlet. The maximum length of discharge piping can be obtained using the table or formula provided in section 9.7.9 of ASHRAE Standard 15-2016.

Selection and Installation. When selecting and installing a relief device,

  • Select a relief device with sufficient capacity for code requirements and suitable for the type of refrigerant used.

  • Use the proper size and length of discharge tube or pipe.

  • Do not discharge the relief device before installation or when pressure-testing the system.

  • For systems containing large quantities of refrigerant, use a three-way valve and two relief valves.

  • Design pressure vessels and piping to allow the relief valve to be set at least 25% above maximum system pressure.

 Functional Relief Valves

Functional relief valves are usually of the diaphragm type: system pressure acts on a diaphragm that lifts the valve disk from the seat (Figure 43). The other side of the diaphragm is exposed to both the adjusting spring and atmospheric pressure. The ratio of effective diaphragm area to seat area is high, so outlet pressure has little effect on the operating point of the valve.

Because the diaphragm’s lift is not great, the diaphragm valve is frequently built as the pilot or servo of a larger piston-operated main valve to provide both sensitivity and high flow capacity. Construction and performance are similar to the previously described pilot-operated evaporator pressure regulator, except that diaphragm valves are constructed for higher pressures. Thus, they are suitable for use as defrost relief from evaporator to suction pressure, as large-capacity relief from a pressure vessel to the low side, or as a liquid refrigerant pump relief from pump discharge to the accumulator to prevent excessive pump pressures when some evaporators are valved closed.

Diaphragm Relief Valve

Figure 43. Diaphragm Relief Valve


 Other Safety Relief Devices

Fusible plugs and rupture disks (Figure 44) provide similar safety relief. The former contains a fusible member that melts at a predetermined temperature corresponding to the safe saturation pressure of the refrigerant, but is limited in application to pressure vessels with internal gross volumes of 3 ft3 or less and internal diameters of 6 in. or less. The rupture member contains a preformed disk designed to burst at a predetermined pressure. These devices may be used as stand-alone devices or installed at the inlet to a safety relief valve.

When these devices are installed in series with a safety relief valve, the chamber created by the two valves must have a pressure gage or other suitable indicator. A rupture disk will not burst at its design pressure if back pressure builds up in the chamber.

Safety Relief Devices

Figure 44. Safety Relief Devices


The rated relieving capacity of a relief valve alone must be multiplied by 0.9 when it is installed in series with a rupture disk (unless the relief valve has been rated in combination with the rupture disk).

Discharge Capacity. The minimum required discharge capacity of the pressure-relief device or fusible plug for each pressure vessel is determined by the following formula, specified by ASHRAE Standard 15:

(2)

where

C=minimum required air discharge capacity of relief device, lb/min
D=outside diameter of vessel, ft
L=length of vessel, ft
f=factor dependent on refrigerant, as shown in Table 2

Equation (2) determines the required relief capacity for a pressure vessel containing liquid refrigerant. See ASHRAE Standard 15 for other relief device requirements, including relief of overpressure caused by compressor flow rate capacity.

5. DISCHARGE-LINE LUBRICANT SEPARATORS

The discharge -line lubricant separator removes lubricant from the discharge gas of helical rotary (screw) and reciprocating compressors. Lubricant is separated by (1) reducing gas velocity, (2) changing direction of flow, (3) impingement on baffles, (4) mesh pads or screens, (5) centrifugal force, or (6) coalescent filters. The separator reduces the amount of lubricant reaching the low-pressure side, helps maintain the lubricant charge in the compressor sump, and muffles the sound of gas flow.

Table 2 Values of f for Discharge Capacity of Pressure Relief Devices

Refrigerant

f

On the low side of a limited-charge cascade system:

  R-13, R-13B1, R-503

2.0

  R-14

2.5

  R-23, R-170, R-508A, R-508B, R-744, R-1150

1.0

Other applications:

  R-11, R-32, R-113, R-123, R-142b, R-152a, R-290, R-600, R-600a, R-764

1.0

  R-12, R-22, R-114, R-124, R-134a, R-401A, R-401B, R-401C, R-405A, R-406A, R-407C, R-407D, R-407E, R-409A, R-409B, R-411A, R-411B, R-411C, R-412A, R-414A, R-414B, R-500, R-1270

1.6

  R-115, R-402A, R-403B, R-404A, R-407B, R-410A, R-410B, R-502, R-507A, R-509A

2.5

  R-143a, R-402B, R-403A, R-407A, R-408A, R-413A

2.0

  R-717

0.5

  R-718

0.2

Notes:

  1. Listed values of f do not apply if fuels are used within 20 ft of pressure vessel. In this case, use methods in API (2014, 2015) to size pressure-relief device.

  2. When one pressure-relief device or fusible plug is used to protect more than one pressure vessel, required capacity is the sum of capacities required for each pressure vessel.

  3. For refrigerants not listed, consult ASHRAE Standard 15.


Figure 45 shows one type of separator incorporating inlet and outlet screens and a high-side float valve. A space below the float valve allows for dirt or carbon sludge. When lubricant accumulates it raises the float ball, then passes through a needle valve and returns to the low-pressure crankcase. When the level falls, the needle valve closes, preventing release of hot gas into the crankcase. Insulation and electric heaters may be added to prevent refrigerant from condensing when the separator is exposed to low temperatures. Many types of horizontal and vertical flow separators are manufactured with centrifuges, baffles, wire mesh pads, and/or cylindrical filters.

 

 Selection

Separators are usually given capacity ratings for several refrigerants at several suction and condensing temperatures. Another method rates capacity in terms of compressor displacement volume. Some separators also show a marked reduction in separation efficiency at some stated minimum capacity. Because compressor capacity increases when suction pressure rises or condensing pressure drops, system capacity at its lowest compression ratio should be the criterion for selecting the separator.

Discharge-Line Lubricant Separator

Figure 45. Discharge-Line Lubricant Separator


 Application

Discharge-line lubricant separators are commonly used for ammonia or hydrocarbon refrigerant systems to reduce evaporator fouling. With lubricant-soluble halocarbon refrigerants, only certain flooded systems, low-temperature systems, or systems with long suction lines or other lubricant return problems may need lubricant separators. (See Chapters 1 and 2 for more information about lubricant separators.)

6. CAPILLARY TUBES

The capillary tube is popular for smaller single-compressor/single-evaporator systems such as household refrigerators and freezers, dehumidifiers, and room air conditioners. Capillary tube use may extend to larger single-compressor/single-evaporator systems, such as unitary air conditioners up to 10 tons capacity.

The capillary operates on the principle that liquid passes through it much more readily than vapor. It is a length of drawn copper tubing with a small inner diameter. (The term “capillary tube” is a misnomer because the inner bore, though narrow, is much too large to allow capillary action.) When used for controlling refrigerant flow, it connects the outlet of the condenser to the inlet of the evaporator. In some applications, the capillary tube is soldered to the suction line and the combination is called a capillary-tube/suction-line heat exchanger system. Refrigeration systems that use a capillary tube without the heat exchanger are often referred to as adiabatic capillary tube systems.

A high-pressure liquid receiver is not normally used with a capillary tube; consequently, less refrigerant charge is needed. In a few applications (e.g., household refrigerators, freezers, room air conditioners, heat pumps), a suction-line accumulator may be used. Because the capillary tube allows pressure to equalize when the refrigerator is off, a compressor motor with a low starting torque may be used. A capillary tube system does not control as well over as wide a range of conditions as does a thermostatic expansion valve; however, a capillary tube may be less expensive and may provide adequate control for some systems.

 

 Theory

A capillary tube passes liquid much more readily than vapor because of the latter’s increased volume; as a result, it is a practical metering device. When a capillary tube is sized to allow the desired flow of refrigerant, a liquid seal develops at its inlet. If the system becomes unbalanced, some vapor (uncondensed refrigerant) enters the capillary tube. This vapor reduces the mass flow of refrigerant considerably, which increases condenser pressure and causes subcooling at the condenser exit and capillary tube inlet. The result is increased mass flow of refrigerant through the capillary tube. If properly sized for the application, the capillary tube compensates automatically for load and system variations and gives acceptable performance over a limited range of operating conditions.

A common flow condition is to have subcooled liquid at the entrance to the capillary tube. Bolstad and Jordan (1948) described the flow behavior from temperature and pressure measurements along the tube (Figure 46) as follows:

Pressure and Temperature Distribution along Typical Capillary Tube (Bolstad and Jordan 1948)

Figure 46. Pressure and Temperature Distribution along Typical Capillary Tube (Bolstad and Jordan 1948)


With subcooled liquid entering the capillary tube, the pressure distribution along the tube is similar to that shown in the graph. At the entrance to the tube, section 0-1, a slight pressure drop occurs, usually unreadable on the gauges. From point 1 to point 2, the pressure drop is linear. In the portion of the tube 0-1-2, the refrigerant is entirely in the liquid state, and at point 2, the first bubble of vapor forms. From point 2 to the end of the tube, the pressure drop is not linear, and the pressure drop per unit length increases as the end of the tube is approached. For this portion of the tube, both the saturated liquid and saturated vapor phases are present, with the percent and volume of vapor increasing in the direction of flow. In most of the runs, a significant pressure drop occurred from the end of the tube into the evaporator space.

With a saturation temperature scale corresponding to the pressure scale superimposed along the vertical axis, the observed temperatures may be plotted in a more efficient way than if a uniform temperature scale were used. The temperature is constant for the first portion of the tube 0-1-2. At point 2, the pressure has dropped to the saturation pressure corresponding to this temperature. Further pressure drop beyond point 2 is accompanied by a corresponding drop in temperature, the temperature being the saturation temperature corresponding to the pressure. As a consequence, the pressure and temperature lines coincide from point 2 to the end of the tube.

Li et al. (1990) and Mikol (1963) showed that the first vapor bubble is not generated at the point where the liquid pressure reaches the saturation pressure (point 2 on Figure 46), but rather the refrigerant remains in the liquid phase for some limited length past point 2, reaching a pressure below the saturation pressure. This delayed evaporation, often referred to as a metastable or superheated liquid condition, must be accounted for in analytical modeling of the capillary tube, or the mass flow rate of refrigerant will be underestimated (Kuehl and Goldschmidt 1991; Wolf et al. 1995).

The rate of refrigerant flow through a capillary tube always increases with an increase in inlet pressure. Flow rate also increases with a decrease in external outlet pressure down to a certain critical value, below which flow does not change (choked flow). Figure 46 shows a case in which outlet pressure inside the capillary tube has reached the critical value (point 3), which is higher than the external pressure (point 4). This condition is typical for normal operation. The point at which the first gas bubble appears is called the bubble point. The preceding portion of capillary tube is called the liquid length, and that following is called the two-phase length.

 System Design Factors

A capillary tube must be compatible with other components. In general, once the compressor and heat exchangers have been selected to meet the required design conditions, capillary tube size and system charge are determined. However, detailed design considerations may be different for different applications (e.g., domestic refrigerator, window air conditioner, residential heat pump).

Capillary tube size and system charge together are used to determine subcooling and superheat for a given design. Performance at off-design conditions should also be checked. Capillary tube systems are generally much more sensitive to the amount of refrigerant charge than expansion valve systems.

The high-pressure side must be designed for use with a capillary tube. To prevent rupture in case the capillary tube becomes blocked, the high-side volume should be sufficient to contain the entire refrigerant charge. A sufficient refrigerant storage volume (e.g., additional condenser tubes) may also be needed to protect against excessive discharge pressures during high-load conditions.

Pressure equalization during the off period is another concern in designing the high side. When the compressor stops, refrigerant continues to pass through the capillary tube from the high side to the low side until pressures are equal. If liquid is trapped in the high side, it will evaporate during the off cycle, pass through the capillary tube to the low side as a warm gas, condense, and add latent heat to the evaporator. Therefore, good liquid drainage to the capillary tube during this equalization interval should be provided. Liquid trapping may also increase the time for the pressure to equalize after the compressor stops. If this interval is too long, pressures may not be sufficiently equalized to allow low-starting-torque motor compressors to start when the thermostat calls for cooling.

The maximum quantity of refrigerant is in the evaporator during the off cycle and the minimum during the running cycle. Suction piping should be arranged to reduce the adverse effects of the variable-charge distribution. A suitable suction-line accumulator is sometimes needed.

 Capacity Balance Characteristic

Selection of a capillary tube depends on the application and anticipated range of operating conditions. One approach to the problem involves the concept of capacity balance. A refrigeration system operates at capacity balance when the capillary tube’s resistance is sufficient to maintain a liquid seal at its entrance without excess liquid accumulating in the high side (Figure 47). Only one such capacity balance point exists for any given compressor discharge pressure. A curve through the capacity balance points for a range of compressor discharge and suction pressures (as in Figure 48) is called the capacity balance characteristic of the system. Ambient temperatures for a typical air-cooled system are shown in Figure 48. A given set of compressor discharge and suction pressures associated with condenser and evaporator pressure drops establish the capillary tube inlet and outlet pressures.

Effect of Capillary Tube Selection on Refrigerant Distribution

Figure 47. Effect of Capillary Tube Selection on Refrigerant Distribution


Capacity Balance Characteristic of Capillary System

Figure 48. Capacity Balance Characteristic of Capillary System


The capacity balance characteristic curve for any combination of compressor and capillary tube may be determined experimentally by the arrangement shown in Figure 49. Although Figure 49 shows the capillary tube suction-line heat exchanger application, a similar test setup without heat exchange would be used for adiabatic capillary tube systems. This test arrangement makes it possible to vary suction and discharge pressures independently until capacity balance is obtained. The desired suction pressure may be obtained by regulating heat input to the low side, usually by electric heaters. The desired discharge pressure may be obtained by a suitably controlled water-cooled condenser. A liquid indicator is located at the entrance to the capillary tube. The usual test procedure is to hold high-side pressure constant and, with gas bubbling through the sight glass, slowly increase suction pressure until a liquid seal forms at the capillary tube entrance. Repeating this procedure at various discharge pressures determines the capacity balance characteristic curve similar to that shown in Figure 48. This equipment may also be used as a calorimeter to determine refrigerating system capacity.

Test Setup for Determining Capacity Balance Characteristic of Compressor, Capillary, and Heat Exchanger

Figure 49. Test Setup for Determining Capacity Balance Characteristic of Compressor, Capillary, and Heat Exchanger


 Optimum Selection and Refrigerant Charge

Always investigate whether initial capillary tube selection and charge are optimum for the unit, even in simple applications such as a room air-conditioning unit. The refrigerant charge in the unit can be varied using a small refrigerant bottle (valved off and sitting on a scale) connected to the circuit. The interconnecting line must be flexible and arranged so that it is filled with vapor instead of liquid. The charge is brought in or removed from the unit by heating or cooling the bottle.

The only test for varying capillary tube restriction is to remove the tube, install a new capillary tube, and determine the optimum charge, as outlined previously. Occasionally, pinching the capillary tube is used to determine whether increased resistance is needed.

The refrigeration system should be operated through its expected range of conditions to determine power requirements and cooling capacity for any given selection and charge combination.

 Application

Processing and Inspection. To prevent mechanical clogging by foreign particles, a strainer should be installed ahead of the capillary tube. Also, all parts of the system must be evacuated adequately to eliminate water vapor and noncondensable gases, which may cause clogging by freezing and/or corrosion. The lubricant should be free from wax separation at the minimum operating temperature.

The interior surface of the capillary tube should be smooth and uniform in diameter. Although plug-drawn copper is more common, wire-drawn or sunk tubes are also available. Life tests should be conducted at low evaporator temperatures and high condensing temperatures to check the possibility of corrosion and plugging. Material specifications for seamless copper tube are given in ASTM Standard B75, and for hard-drawn copper tubes in ASTM Standard B360.

Establish a procedure to ensure uniform flow capacities, within reasonable tolerances, for all capillary tubes used in product manufacture. The following procedure is a good example:

  1. Remove the final capillary tube, determined from tests, from the unit and rate its airflow capacity using the wet-test meter method described in ASHRAE Standard 28.

  2. Produce master capillary tubes using the wet-test meter airflow equipment, to provide maximum and minimum flow capacities for the particular unit. The maximum-flow capillary tube has a flow capacity equal to that of the test capillary tube, plus a specified tolerance. The minimum-flow capillary tube has a flow capacity equal to that of the test capillary tube, less a specified tolerance.

  3. Send one sample of the maximum and minimum capillary tubes to the manufacturer, to be used as tolerance guides for elements supplied for a particular unit. Also send samples to the inspection group for quality control.

Considerations. In selecting a capillary tube for a specific application, practical considerations influence the length. For example, the minimum length is determined by geometric considerations such as the physical distance between the high and low sides and the length of capillary tube required for optimum heat exchange. It may also be dictated by exit velocity, noise, and the possibility of plugging with foreign materials. Maximum length may be determined primarily by cost. It is fortunate, therefore, that flow characteristics of a capillary tube can be adjusted independently by varying either its bore or its length. Thus, it is feasible to select the most convenient length independently and then (within certain limits) select a bore to give the desired flow. An alternative procedure is to select a standard bore and then adjust the length, as required.

Mass Flow Rate of R-134a Through Capillary Tube (Capillary tube ID is 0.034 in. and length is 130 in.)

Figure 50. Mass Flow Rate of R-134a Through Capillary Tube (Capillary tube ID is 0.034 in. and length is 130 in.)


Flow Rate Correction Factor ϕ for R-134a

Figure 51. Flow Rate Correction Factor ϕ for R-134a


ASTM Standard B360 lists standard diameters and wall thicknesses for capillary tubes. Many nonstandard tubes are also used, resulting in nonuniform interior surfaces and variations in flow.

6.1 ADIABATIC CAPILLARY TUBE SELECTION PROCEDURE

Wolf et al. (1995) developed refrigerant-specific rating charts to predict refrigerant flow rates through adiabatic capillary tubes. The methodology involves determining two quantities from a series of curves, similar to rating charts for R-12 and R-22 developed by Hopkins (1950). The two quantities necessary to predict refrigerant flow rate through the adiabatic capillary tube are a flow rate through a reference capillary tube and a flow factor ϕ, which is a geometric correction factor. These two quantities are multiplied together to calculate the flow rate.

Mass Flow Rate of R-410A Through Capillary Tube (Capillary tube ID is 0.034 in. and length is 130 in.)

Figure 52. Mass Flow Rate of R-410A Through Capillary Tube (Capillary tube ID is 0.034 in. and length is 130 in.)


Figures 50 and 51 are rating charts for pure R-134a through adiabatic capillary tubes. Figure 50 plots the capillary tube flow rate as a function of inlet condition and inlet pressure for a reference capillary tube geometry of 0.034 in. ID and 130 in. length. Figure 51 is a geometric correction factor. Using the desired capillary tube geometry, ϕ may be determined and then multiplied with the flow rate from Figure 50 to determine the predicted capillary tube flow rate. Note: For quality inlet conditions for R-134a, an additional correction factor of 0.95 is necessary to obtain the proper results.

Flow Rate Correction Factor ϕ for R-410A for Subcooled Condition at Capillary Tube Inlet

Figure 53. Flow Rate Correction Factor ϕ for R-410A for Subcooled Condition at Capillary Tube Inlet


Flow Rate Correction Factor ϕ for R-410A for Two-Phase Condition at Capillary Tube Inlet

Figure 54. Flow Rate Correction Factor ϕ for R-410A for Two-Phase Condition at Capillary Tube Inlet


Figures 52 to 54 present the rating charts for pure R-410A through adiabatic capillary tubes. The method of selection from these charts is identical to that previously presented for R-134a, except that an additional correction factor for quality inlet conditions is not used. A separate flow factor chart (Figure 54), however, is provided to determine the value of the geometric correction factor for quality inlet conditions. The same methodology using Figures 55, 56, and 57 can be used to determine the mass flow rate of R-22 through adiabatic capillary tubes. Wolf et al. (1995) developed additional rating charts for R-152a.

Mass Flow Rate of R-22 Through Capillary Tube (Capillary tube diameter is 0.066 in. ID and length is 60 in.)

Figure 55. Mass Flow Rate of R-22 Through Capillary Tube (Capillary tube diameter is 0.066 in. ID and length is 60 in.)


Flow Rate Correction Factor ϕ for R-22 for Subcooled Condition at Capillary Tube Inlet

Figure 56. Flow Rate Correction Factor ϕ for R-22 for Subcooled Condition at Capillary Tube Inlet


Wolf et al. (1995) also presented limited performance results for refrigerants R-134a, R-22, and R-410A with 1.5% lubricant. Though these results did indicate a 1 to 2% increase in refrigerant mass flow through the capillary tubes, this was considered insignificant.

Generalized Prediction Equations. Based on tests with R-134a, R-22, and R-410A, Wolf et al. (1995) developed a general method for predicting refrigerant mass flow rate through a capillary tube. In this method, the Buckingham π theorem was applied to the physical factors and fluid properties that affect capillary tube flow rate. Physical factors include capillary tube diameter and length, capillary tube inlet pressure, and refrigerant inlet condition; fluid properties included specific volume, viscosity, surface tension, specific heat, and latent heat of vaporization. The result of this analysis was a group of eight dimensionless π terms shown in Table 3.

Flow Rate Correction Factor ϕ for R-22 for Two-Phase Condition at Capillary Tube Inlet

Figure 57. Flow Rate Correction Factor ϕ for R-22 for Two-Phase Condition at Capillary Tube Inlet


Table 3 Capillary Tube Dimensionless Parameters

π Term

Definition

Description

π1

Lc/dc

Geometry effect

π2

dc2hfg/vf2μf 2

Vaporization effect

π3

dcσ/vf μf2

Bubble formation

π4

dc2Pin/vfμf2

Inlet pressure

π5 (subcooled)

dc2cpΔtsc/vf2μf 2

Inlet condition

π5 (quality)

x

Inlet condition

π6

vg/vf

Density effect

π7

(μf – μg)/μg

Viscous effect

π8

ṁ/dcμf

Flow rate

where

cp=liquid specific heat
dc=capillary tube diameter
hfg=latent heat or vaporization
Lc=capillary tube length
ṁ=mass flow rate
x=quality (decimal)
Δtsc=degree of subcooling
μf=liquid viscosity
μg=vapor viscosity
νf=liquid specific volume
νg=vapor specific volume
Pin=capillary tube inlet pressure
σ=surface tension


All fluid properties for respective π terms, both liquid and vapor, are evaluated at the saturation state using the capillary tube inlet temperature. Separate π5 terms are presented for subcooled and two-phase refrigerant conditions at the capillary tube entrance. Note: The bubble formation term π3 is statistically insignificant and, therefore, does not appear in prediction Equations (3) and (4).

Regression analysis of the refrigerant flow rate data for the subcooled inlet results produced the following equation for subcooled inlet conditions:

(3)

where π5 = dc2cpΔtsc/νf2μf2 and 2°F < Δtsc < 30°F.

The following includes the π5 term that only includes the quality x.

(4)

where π5 = quality x from 0.03 < x < 0.25.

Wolf et al. (1995) compared these equations to R-134a results by Dirik et al. (1994) and R-22 results by Kuehl and Goldschmidt (1990). Wolf et al. also compared experimental results with R-152a and predictions by Equations (3) and (4) and found agreement within 5%. In addition, less than 1% of the R-134a, R-22, and R-410A experimental results used by Wolf et al. to develop correlation Equations (3) and (4) were outside ±5% of the flow rates predicted by the equations.

 Sample Calculations

Example 1.

Determine mass flow rate of R-134a through a capillary tube of 0.030 in. ID, 140 in. long, operating without heat exchange at 180 psia inlet pressure and 10°F subcooling.


Solution: From Figure 50 at 180 psia and 10°F subcooling, the flow rate of HFC-134a for a capillary tube 0.034 in. ID and 130 in. long is 13 lb/h. The flow factor ϕ from Figure 51 for a capillary tube of 0.030 in. ID and 140 in. long is 0.73. The predicted R-134a flow rate is then 13 × 0.73 = 9.49 lb/h.



Example 2.

Determine the mass flow rate of R-134a through a capillary tube of 0.042 in. ID, 100 in. long, operating without heat exchange at 200 psia inlet pressure and 10% vapor content at the capillary tube inlet.


Solution: From Figure 50, at 200 psia and 10% quality, the flow rate of R-134a for a capillary tube 0.034 in. ID and 130 in. long is 7.9 lb/h. The flow factor ϕ from Figure 51 for a capillary tube of 0.042 in. ID and 100 in. long is 2.0. The predicted R-134a flow rate is then 0.95 × 7.9 × 2.0 = 15.0 lb/h, where 0.95 is the additional correction factor for R-134a quality inlet conditions.



Example 3.

Determine the mass flow rate of R-410A through a capillary tube of 0.040 in. ID, 140 in. long, operating without heat exchange, 350 psia inlet pressure, and 15°F subcooling at the capillary tube inlet.


Solution: From Figure 52, at 350 psia and 15°F subcooling, the flow rate of R-410A for a capillary tube of 0.034 in. ID and 130 in. long is 22.4 lb/h. The flow factor ϕ from Figure 53 for a capillary tube of 0.040 in. ID and 140 in. long is 1.5. The predicted R-410A flow rate is then 22.4 × 1.5 = 33.6 lb/h.



Example 4.

Determine the mass flow rate of R-22 through a capillary tube of 0.080 in. ID, 50 in. long, operating without heat exchange, 250 psia inlet pressure, and 5% vapor content at the capillary tube inlet.


Solution: From Figure 55, at 250 psia and 5% quality, the flow rate of R-22 for a capillary tube of 0.066 in. ID and 60 in. long is 99.5 lb/h. The flow factor ϕ from Figure 57 for a capillary tube of 0.080 in. ID and 50 in. long is 1.75. The predicted R-22 flow rate is then 99.5 × 1.75 = 174 lb/h.


6.2 CAPILLARY-TUBE/SUCTION-LINE HEAT EXCHANGER SELECTION PROCEDURE

In some refrigeration applications, a portion of the capillary tube is soldered to or in contact with the suction line such that heat exchange occurs between warm fluid in the capillary tube and relatively cooler refrigerant vapor in the suction line. The addition of the capillary-tube/suction-line heat exchanger to the refrigeration cycle can have several advantages. For some refrigerants, the addition increases the system’s COP and volumetric capacity. Domanski et al. (1994) reported that this is not the case for all refrigerants and that some refrigeration systems may decrease in COP, depending on the particular refrigerant in the system. In typical household refrigerators, the suction line is soldered to the capillary tube so that heat exchanged with the suction line prevents condensation on the surface of the suction line during operation. The capillary-tube/suction-line heat exchanger also ensures that superheated refrigerant vapor exists at the compressor inlet and eliminates the possibility of liquid refrigerant returning to the compressor.

When a suction-line heat exchanger is used, the excess capillary length may be coiled and located at either end of the heat exchanger. Although more heat is exchanged with the excess coiled at the evaporator, system stability may be enhanced with the excess coiled at the condenser. Coils and bends should be formed carefully to avoid local restrictions. The effect of forming on the restriction should be considered when specifying the capillary.

Inlet Condition Rating Chart for R-134a

Figure 58. Inlet Condition Rating Chart for R-134a


Capillary Tube Geometry Correction Factor for Subcooled R-134a Inlet Conditions

Figure 59. Capillary Tube Geometry Correction Factor for Subcooled R-134a Inlet Conditions


 Capillary Tube Selection

Wolf and Pate (2002) developed refrigerant-specific rating charts to predict refrigerant flow rates through capillary-tube/suction-line heat exchangers. The methodology involves determining four quantities (three for quality inlet conditions) from a series of curves and multiplying the results together to obtain the flow rate prediction. The calculation procedure is very similar to the adiabatic capillary tube selection process, with the exception of the additional flow rate factors. Figures 58 to 62 are the rating charts for pure R-134a through capillary-tube/suction-line heat exchangers. Figure 58 plots refrigerant flow rate as a function of capillary tube inlet pressure and inlet condition for a reference heat exchanger configuration (Dc = 0.034 in., Lc = 130 in., and Lhx = 60 in.). The thermodynamic state of the refrigerant vapor at the suction-line inlet to the heat exchanger has also been fixed (24 psia and 20°F superheat). Figure 59 plots flow rate correction factor ϕ1 as a function of capillary tube diameter and length for subcooled inlet conditions at the capillary tube inlet. Figure 60 plots flow rate correction factor ϕ2 as a function of suction-line inlet pressure and superheat level at the inlet to the suction line for subcooled inlet conditions at the capillary tube inlet. Figure 61 plots flow rate correction factor ϕ3 as a function of heat exchange length for subcooled inlet conditions at the capillary tube inlet. Figure 62 is the capillary tube geometry correction factor for quality inlet conditions at the capillary tube inlet, and Figure 63 is the suction-line condition correction factor for quality inlet conditions at the capillary tube inlet. There is no ϕ3 correction factor for heat exchange length for quality inlet conditions. In general, heat exchange length delays the onset of vaporization of the refrigerant inside the capillary tube. However, without recondensation in the capillary tube as a result of the heat exchange effect, there is no vaporization for two-phase conditions at the capillary tube inlet.

Suction-Line Condition Correction Factor for R-134a Subcooled Inlet Conditions

Figure 60. Suction-Line Condition Correction Factor for R-134a Subcooled Inlet Conditions


Heat Exchange Length Correction Factor for R-134a Subcooled Inlet Conditions

Figure 61. Heat Exchange Length Correction Factor for R-134a Subcooled Inlet Conditions


Capillary Tube Geometry Correction Factor for R-134a Quality Inlet Conditions

Figure 62. Capillary Tube Geometry Correction Factor for R-134a Quality Inlet Conditions


To predict refrigerant mass flow rate for other conditions and geometries, multiply the necessary correction factors by the reference flow rate from Figure 58. Additional design variables examined by Wolf and Pate (2002) were the adiabatic upstream entrance length and inner diameter of the suction-line tubing. For adiabatic entrance lengths from 6 to 24 in., there was no observed effect. There was also no effect observed that could be attributed to the inner diameter of the suction line. Because of their lack of effect, these two design variables are not included when predicting refrigerant flow rate.

Suction-Line Condition Correction Factor for R-134a Quality Inlet Conditions

Figure 63. Suction-Line Condition Correction Factor for R-134a Quality Inlet Conditions


 Generalized Prediction Equations

Based on tests with R-134a, R-22, R-410A, and R-600a, Wolf and Pate (2002) developed a general method for predicting refrigerant mass flow rate through a capillary-tube/suction-line heat exchanger. In this method, the Buckingham π theorem was applied to the physical factors and fluid properties that affect capillary tube flow rate through a capillary-tube/suction-line heat exchanger. Physical factors included capillary tube diameter, capillary tube length, suction-line diameter, heat exchange length, adiabatic entrance length of the capillary tube, capillary tube inlet pressure and condition, and suction-line inlet pressure and condition. Fluid properties included specific volume, viscosity, specific heat, and latent heat of vaporization. The result of this analysis was a group of 15 dimensionless π parameters, shown in Table 4.

All fluid properties for the respective π terms are evaluated at the capillary tube inlet temperature. Separate π7 terms are presented for subcooled and quality inlet conditions to the capillary tube. The π terms in Table 4 that do not appear in Equations (5) and (6) were statistically insignificant and were not included in the final correlations.

Table 4 Capillary-Tube/Suction-Line Heat Exchanger Dimensionless Parameters

π Parameter

Definition

Description

π1

Lc/Dc

Geometry effect

π2

Li/Dc

Geometry effect

π3

Lhx/Dc

Geometry effect

π4

Ds/Dc

Geometry effect

π5

Pcapin Dc2/μf c2νf cT

Inlet pressure

π6

Psuctin Dc2/μf c2νf c

Inlet pressure

π7 (subcooled)

ΔTscCpf c Dc2/μf c2νf c2

Inlet condition

π7 (quality)

1 – x

Inlet condition

π8

ΔTshCpf c Dc2/μf c2νf c2

Inlet condition

π9

ṁ/Dcμfc

Flow rate

π10

νgc /νfc

Density effect

π11

(μf c – μgc)/μ f c

Viscous effect

π12

hfgc Dc2/μf c2νf c2

Vaporization effect

π13

μgs /μf c

Viscous effect

π14

νg s /νf c

Density effect

π15

Cp g s /Cp f c

Specific heat effect

where

Cpfc=capillary inlet liquid specific heat
Cpgs=suction inlet vapor specific heat
Dc=capillary tube inside diameter (0.026 to 0.042 in.)
Ds=suction line inside diameter (0.194 to 0.319 in.)
hfgc=capillary inlet latent heat of vaporization
Lc=capillary tube length (80 to 180 in.)
Lhx=heat exchange length (20 to 100 in.)
Li=adiabatic entrance length (6 to 24 in.)
ṁ=mass flow rate
Pcapin=capillary tube inlet pressure
Psuctin=suction line inlet pressure
x=quality (2 to 10%)
ΔTsc =capillary tube inlet subcool level (2 to 30°F)
ΔTsh=suction line inlet superheat (6 to 40°F)
μfc=capillary inlet liquid viscosity
μgc=capillary inlet vapor viscosity
μgs=suction inlet vapor viscosity
νfc=capillary inlet liquid specific volume
νgc=capillary inlet vapor specific volume
νgs= suction inlet vapor specific volume

Regression analysis of refrigerant flow rate data for subcooled inlet conditions produced the following equation:

(5)

where π7 = ΔTscCpfc Dc2/μfc2 νfc2 and 2°F < ΔTsc < 30°F.

Equation (6) is valid for quality inlet conditions and contains the quality inlet term π7 = 1 – x.

(6)

where x = quality (decimal) from 0.02 < x < 0.10.

Wolf and Pate (2002) compared these equations to R-152a test results as well as published R-134a, R-152a, and R-12 data. Excellent agreement (±10%) was observed in nearly all cases. The only exception was the R-134a results by Dirik et al. (1994). Equation (5) overpredicted these results by an average of 45%. However, the adiabatic entrance length used was approximately 134 in., indicating that very long adiabatic entrance lengths may decrease refrigerant flow rates.

For further information on other refrigerants, please see the Bibliography.

 Sample Calculations

Example 5.

Determine the mass flow rate of R-134a through a capillary tube of 0.040 in. ID and 160 in. long operating with heat exchange at 160 psia capillary inlet pressure and 20°F subcooling. The heat exchange length is 70 in., and suction-line inlet conditions are 16 psia and 20°F superheat.

Solution: From Figure 58, at 160 psia and 20°F subcooling, the flow rate for a capillary tube 0.034 in. ID and 130 in. long is 22.5 lb/h. The capillary tube geometry correction factor from Figure 59 is 1.3. The suction-line inlet correction factor from Figure 60 is 1.033, and the heat exchange length factor from Figure 61 is 1.01. The predicted mass flow rate is then 22.5 × 1.37 × 1.033 × 1.01 = 32.2 lb/h.


Example 6.

Determine the mass flow rate of R-134a through a capillary tube of 0.030 in. ID and 80 in. long operating with heat exchange at 140 psia capillary inlet pressure and 6% quality. The heat exchange length is 55 in., and suction-line inlet conditions are 20 psia and 10°F superheat.

Solution: From Figure 58, at 140 psia and 6% quality, the flow rate for a capillary tube 0.034 in. ID and 130 in. long is 9.5 lb/h. The capillary tube geometry correction factor from Figure 62 is 0.90. The suction-line inlet correction factor from Figure 63 is 1.09. There is no heat exchange length correction factor for quality inlet conditions, so the predicted mass flow rate is then 9.5 × 0.90 × 1.09 = 9.3 lb/h.


7. SHORT-TUBE RESTRICTORS

 Application

Short-tube restrictors are widely used in residential air conditioners and heat pumps. They offer low cost, high reliability, ease of inspection and replacement, and potential elimination of check valves in the design of a heat pump. Because of their pressure-equalizing characteristics, short-tube restrictors allow the use of a low-starting-torque compressor motor.

Short-tube restrictors, as used in residential systems, are typically 3/8 to 1/2 in. in length, with a length-to-diameter (L/D) ratio greater than 3 and less than 20. Short-tube restrictors are also called plug orifices or orifices, although the latter is reserved for restrictors with an L/D ratio less than 3. Capillary tubes have an L/D ratio much greater than 20.

An orifice tube, a type of short-tube restrictor, is commonly used in automotive air conditioners. Its L/D ratio falls between that of a capillary tube and a short-tube restrictor. Most automotive applications use orifice tubes with L/D ratios between 21 and 35 and inside diameters from 0.04 to 0.08 in. An orifice tube allows the evaporator to operate in a flooded condition, which may improve performance on some systems. To prevent liquid from flooding the compressor, an accumulator/dehydrator is installed to separate liquid from vapor and to allow a small amount of lubricant to return to the compressor. However, the accumulator/dehydrator does cause a pressure drop penalty on the suction side.

Schematic of Movable Short-Tube Restrictor

Figure 64. Schematic of Movable Short-Tube Restrictor


R-22 Pressure Profile at Various Downstream Pressures with Constant Upstream Conditions: L = 0.5 in., D = 0.053 in., Subcooling 25°F (Adapted from Aaron and Domanski 1990)

Figure 65. R-22 Pressure Profile at Various Downstream Pressures with Constant Upstream Conditions: L = 0.5 in., D = 0.053 in., Subcooling 25°F (Adapted from Aaron and Domanski 1990)


There are two basic designs for short-tube restrictors: stationary and movable. Movable short-tube restrictors consist of a piston that moves within its housing (Figure 64). A movable short-tube restrictor restricts refrigerant flow in one direction. In the opposite direction, the refrigerant pushes the restrictor off its seat, opening a larger area for the flow. The stationary design is used in units that cool only; movable short-tube restrictors are used in heat pumps that require different flow restrictions for cooling and heating modes. Two movable short-tube restrictors, installed in series and faced in opposite directions, eliminate the need for check valves, which would be needed for capillary tubes and thermostatic expansion valves.

The refrigerant mass flow rate through a short-tube restrictor depends strongly on upstream subcooling and upstream pressure. For a given inlet pressure, inlet subcooling, and downstream pressure below the saturation pressure corresponding to the inlet temperature, flow has a very weak dependence on the downstream pressure, indicating a nearly choked flow. This flow dependence is shown in Figure 65, which presents R-22 test data obtained on a 0.5 in. long, laboratory-made short-tube restrictor at three different downstream pressures and the same upstream pressure.

R-22 Mass Flow Rate Versus Condenser Pressure for Reference Short Tube: L = 0.5 in., D = 0.053 in., Sharp-Edged (Adapted from Aaron and Domanski 1990)

Figure 66. R-22 Mass Flow Rate Versus Condenser Pressure for Reference Short Tube: L = 0.5 in., D = 0.053 in., Sharp-Edged (Adapted from Aaron and Domanski 1990)


A significant drop in downstream pressure from approximately 170 psia to 70 psia produces a smaller increase in the mass flow rate than does a modest change of downstream pressure from 190 psia to 170 psia. Pressure drops only slightly along the length of the short-tube restrictor. The large pressure drop at the entrance is caused by rapid fluid acceleration and inlet losses. The large pressure drop in the exit plane, typical for heat pump operating conditions and represented in Figure 65 by the bottom pressure line, indicates that choked flow nearly occurred.

Among geometric parameters, the short-tube restrictor diameter has the strongest influence on mass flow rate. Chamfering the inlet of the short-tube restrictor may increase the mass flow rate by as much as 25%, depending on the L/D ratio and chamfer depth. Chamfering the exit causes no appreciable change in mass flow rate.

Although refrigerant flow inside a short tube is different from flow inside a capillary tube, choked flow is common for both, making both types of tubes suitable as metering devices. Systems equipped with short-tube restrictors, as with capillary tubes, must be precisely charged with the proper amount of refrigerant. Inherently, a short-tube restrictor does not control as well over a wide range of operating conditions as does a thermostatic expansion valve. However, its performance is generally good in a properly charged system.

 Selection

Figures 66 to 69, from Aaron and Domanski (1990), can be used for preliminary evaluation of the mass flow rate of R-22 at a given inlet pressure and subcooling in air-conditioning and heat pump applications (i.e., applications in which downstream pressure is below the saturation pressure of refrigerant at the inlet). The method requires determination of mass flow rate for the reference short tube from Figure 66 and modifying the reference flow rate with multipliers that account for the short-tube geometry according to the equation

(7)

where

ṁ=mass flow rate for short tube
ṁr=mass flow rate for reference short tube from Figure 66
ϕ1=correction factor for tube geometry from Figure 67
ϕ2=correction factor for L/D versus subcooling from Figure 68
ϕ3=correction factor for chamfered inlet from Figure 69

Correction Factor for Short-Tube Geometry (R-22) (Adapted from Aaron and Domanski 1990)

Figure 67. Correction Factor for Short-Tube Geometry (R-22) (Adapted from Aaron and Domanski 1990)


Correction Factor for L/D Versus Subcooling (R-22) (Adapted from Aaron and Domanski 1990)

Figure 68. Correction Factor for L/D Versus Subcooling (R-22) (Adapted from Aaron and Domanski 1990)


Aaron and Domanski (1990) also provide a more accurate correlation than the graphical method. Neglecting downstream pressure on the graphs may introduce an error in the prediction as compared to the correlation results; however, this discrepancy should not exceed 3% because of the choked-flow condition at the tube exit. Note: The lines for 0 and 40°F subcooling in Figure 66 were obtained by extrapolation beyond the test data and may carry a large error.

Additional research has been done to add several other refrigerants’ capacity ratings to this section. However, only data for R-410A and R-407c have been published in ASHRAE Transactions (Payne and O’Neal 1998, 1999).

Correction Factor for Inlet Chamfering (R-22) (Adapted from Aaron and Domanski 1990)

Figure 69. Correction Factor for Inlet Chamfering (R-22) (Adapted from Aaron and Domanski 1990)


Example 7.

Determine the mass flow rate of R-22 through a short-tube restrictor 0.375 in. long, of 0.06 in. ID, and chamfered 0.01 in. deep at an angle of 45°. The inlet pressure is 240 psia, and subcooling is 10°F.

Solution: From Figure 66, for 240 psia and 10°F subcooling, the flow rate for the reference short tube is 240 lb/h. The value for ϕ1 from Figure 67 is 1.62. The value for ϕ2 from Figure 68 for 10°F subcooling and L/D = 0.375/0.06 = 6.25 is 0.895. The value of ϕ3 from Figure 69 for L/D = 6.25 and a chamfer depth of 0.01 in. is 1.098. Thus, the predicted mass flow rate through the restrictor is 240 × 1.62 × 0.895 × 1.098 = 382 lb/h.


REFERENCES

ASHRAE members can access ASHRAE Journal articles and ASHRAE research project final reports at technologyportal.ashrae.org. Articles and reports are also available for purchase by nonmembers in the online ASHRAE Bookstore at www.ashrae.org/bookstore.

Aaron, D.A., and P.A. Domanski. 1990. Experimentation, analysis, and correlation of Refrigerant-22 flow through short tube restrictors. ASHRAE Transactions 96(1):729-742.

AHRI. 2016. Performance rating of thermostatic refrigerant expansion valves. AHRI Standard 750-2016. Air-Conditioning and Refrigeration Institute, Arlington, VA.

API. 2014. Sizing, selection, and installation of pressure-relieving devices, Part I—Sizing and selection, 9th ed. Standard 520, Part 1. American Petroleum Institute, Washington, D.C.

API. 2015. Sizing, selection, and installation of pressure-relieving devices, Part II—Installation, 6th ed. Standard 520, Part 2. American Petroleum Institute, Washington, D.C.

ASHRAE. 2016. Safety standard for refrigeration systems. ANSI/ASHRAE Standard 15-2016.

ASHRAE. 2015. Method of testing capacity of thermostatic refrigerant expansion valves. ANSI/ASHRAE Standard 17-2015.

ASHRAE. 2010. Method of testing flow capacity of refrigerant capillary tubes. ANSI/ASHRAE Standard 28-1996 (RA2010).

ASME. 2015. Boiler and pressure vessel code. American Society of Mechanical Engineers, New York.

ASTM. 2011. Standard specification for seamless copper tube. Standard B75-11. American Society for Testing and Materials, West Conshohocken, PA.

ASTM. 2015. Standard specification for hard-drawn copper capillary tube for restrictor applications. Standard B360-15. American Society for Testing and Materials, West Conshohocken, PA.

Bolstad, M.M., and R.C. Jordan. 1948. Theory and use of the capillary tube expansion device. Refrigerating Engineering (December):519.

Dirik, E., C. Inan, and M.Y. Tanes. 1994. Numerical and experimental studies on adiabatic and non-adiabatic capillary tubes with HFC-134a. Proceedings of the International Refrigeration Conference, Purdue University, West Lafayette, IN.

Domanski, P.A., D.A. Didion, and J.P. Doyle. 1994. Evaluation of suction line-liquid line heat exchange in the refrigeration cycle. International Journal of Refrigeration 17(7):487-493.

Hopkins, N.E. 1950. Rating the restrictor tube. Refrigerating Engineering (November):1087.

Kuehl, S.J., and V.W. Goldschmidt. 1990. Steady flow of R-22 through capillary tubes: Test data. ASHRAE Transactions 96(1):719-728.

Kuehl, S.J., and V.W. Goldschmidt. 1991. Modeling of steady flows of R-22 through capillary tubes. ASHRAE Transactions 97(1):139-148.

Li, R.Y., S. Lin, Z.Y. Chen, and Z.H. Chen. 1990. Metastable flow of R-12 through capillary tubes. International Journal of Refrigeration 13(3): 181-186.

Mikol, E.P. 1963. Adiabatic single and two-phase flow in small bore tubes. ASHRAE Journal 5(11):75-86.

Payne, W.V., and D.L. O’Neal. 1998. Mass flow characteristics of R-407c through short tube orifices. ASHRAE Transactions 104(1).

Payne, W.V., and D.L. O’Neal. 1999. Multiphase flow of refrigerant 410A through short tube orifices. ASHRAE Transactions 105(2).

Wolf, D.A., and M.B. Pate. 2002. Performance of a suction line/capillary-tube heat exchanger with alternative refrigerants. ASHRAE Research Project RP-948, Final Report.

Wolf, D.A., R.R. Bittle, and M.B. Pate. 1995. Adiabatic capillary tube performance with alternative refrigerants. ASHRAE Research Project RP-762, Final Report.

BIBLIOGRAPHY

Bittle, R.R., and M.B. Pate. 1996. A theoretical model for predicting adiabatic capillary tube performance with alternative refrigerants. ASHRAE Transactions 102(2):52-64.

Bittle, R.R., D.A. Wolf, and M.B. Pate. 1998. A generalized performance prediction method for adiabatic capillary tubes. International Journal of HVAC&R Research (now Science and Technology for the Built Environment) 4(1):27-43.

Kuehl, S.J., and V.W. Goldschmidt. 1990. Transient response of fixed area expansion devices. ASHRAE Transactions 96(1):743-750.

Marcy, G.P. 1949. Pressure drop with change of phase in a capillary tube. Refrigerating Engineering (January):53.

Pate, M.B., and D.R. Tree. 1987. An analysis of choked flow conditions in a capillary tube–suction line heat exchanger. ASHRAE Transactions 93(1):368-380.

Schulz, U. 1985. State of the art: The capillary tube for, and in, vapor compression systems. ASHRAE Transactions 91(1):92-105.

Whitesel, H.A. 1957a. Capillary two-phase flow. Refrigerating Engineering (April):42.

Whitesel, H.A. 1957b. Capillary two-phase flow—Part II. Refrigerating Engineering (September):35.

Wijaya, H. 1991. An experimental evaluation of adiabatic capillary tube performance for HFC-134a and CFC-12, pp. 474-483. Proceedings of the International CFC and Halon Alternatives Conference. Alliance of Responsible CFC Policy, Arlington, VA.



The preparation of this chapter is assigned to TC 8.8, Refrigerant System Controls and Accessories.