Overfeed systems force liquid in excess of the amount evaporated, either mechanically or by gas pressure, through organized-flow evaporators, separate it from the vapor, and return it to the evaporators. Mechanically pumped systems usually pump from a vessel at the connected suction pressure (i.e., low-temperature liquid). Gas-operated systems can be configured to deliver either low-temperature liquid directly like the mechanically pumped system, or subcooled liquid from a controlled pressure receiver at an intermediate pressure. With the latter, the accumulated overfed liquid is transferred from the low-pressure receiver back to the controlled-pressure receiver.
Low-pressure receiver. Sometimes referred to as an accumulator or recirculator, this vessel acts as the separator for the mixture of vapor and liquid returning from the evaporators, and as storage for liquid feed to the pumping unit. For receivers that feed liquid to loads, a constant refrigerant level is usually maintained by conventional control devices.
Controlled-pressure receiver. In a gas-operated overfeed system, this vessel is maintained at a pressure sufficient to feed liquid to the loads and receives liquid from the condensers and from the gas-operated transfer units.
Pumping unit. One or more mechanical pumps or gas-operated liquid circulators are arranged to deliver overfeed liquid to the evaporators. The pumping unit is located below the low-pressure receiver.
Transfer unit (dump trap). This gas-operated pumping unit returns overfed low-temperature liquid from the low-pressure receiver to the controlled-pressure receiver.
Wet suction returns. These are connections between the evaporator outlets and low-pressure receiver through which the mixture of vapor and overfeed liquid is drawn back to the low-pressure receiver.
Liquid feeds. These are connections between the pumping unit outlet and evaporator inlets.
Flow control regulators. These devices regulate liquid flow into individual evaporators. They may be needle valves, fixed orifices, calibrated manual regulating valves, or automatic valves designed to provide a fixed liquid rate.
Advantages and Disadvantages
The main advantages of liquid overfeed systems are high system efficiency, easy expandability, and reduced operating expenses. These systems have lower energy cost and fewer operating hours because
The evaporator surface is more effective because overfeeding refrigerant improves heat transfer by completely wetting internal tube surfaces.
Compressors are inherently protected from ingesting liquid slugs caused by fluctuating loads or malfunctioning controls because of liquid separation from suction gas in the low-pressure receiver.
With simple controls, evaporators can be hot-gas defrosted with little disturbance to the system.
Refrigerant feed to evaporators is independent of fluctuating condensing conditions caused by refrigerant load, and of ambient condition variations, thereby allowing reduced-condensing-pressure operation and increasing the efficiency of the refrigeration system. Fixed flow control regulators do not need to be adjusted after initial setting because the improved performance of liquid overfeed evaporators is relatively insensitive to the overfeed rate.
Flash gas resulting from refrigerant throttling losses is removed at the low-pressure receiver before entering the evaporators. This gas is drawn directly to the compressors and eliminated as a factor in system low-side piping design to the evaporators. It does not contribute to increased pressure drops in the liquid feed piping to, or overfeed lines from, the evaporators.
Low-pressure receivers, refrigerant level controls and level indicators, refrigerant pumps, and oil drains (if necessary) are generally located in equipment rooms, which are under operator surveillance or computer monitoring and have limited or controlled access.
Because of ideal entering suction gas conditions, compressor life is extended. There is less maintenance and fewer breakdowns. The oil circulation rate to the evaporators is reduced because of the low compressor discharge superheat and separation at the low-pressure receiver (Scotland 1963).
Liquid feed to the evaporators is more reliable because the liquid state is subcooled (or pressurized), resulting in less possibility of flashing in the liquid feed piping.
Automatic operation is convenient.
The following are possible disadvantages:
In most cases, the total refrigerant charge may be greater than those used in other systems.
Higher refrigerant flow rates to and from evaporators cause liquid feed and wet return lines to be larger in diameter than high-pressure liquid and suction lines for other systems.
Piping insulation is generally required on all feed and return lines to prevent condensation, frosting, and heat gain, and to preserve the piping’s mechanical integrity, increasing capital cost of the system.
Installed cost may be greater, particularly for small systems or those with fewer than three evaporators.
Operation of the pumping unit requires energy, but usually much less than the energy saved by the increased efficiency of the overall system.
Pumping units may require maintenance.
Mechanical pumps are subject to cavitation problems associated with pumping a volatile fluid near its saturation condition (i.e., low available net positive suction head).
If flash gas enters the evaporator, the vapor is likely to bind the hand expansion valve, causing the evaporator to be underfed with refrigerant.
Generally, the more evaporators required, the more favorable the initial costs for liquid overfeed compared to a gravity recirculated or flooded system (Scotland 1970) because of simpler piping and controls at the evaporators. Large liquid overfeed systems compare favorably with thermostatic valve feed systems (e.g., direct- or dry expansion) for the same reason. For small systems, the initial cost for liquid overfeed may be higher than for direct expansion.
Ammonia Systems. For ammonia systems operating below 0°F evaporating temperature, a direct-expansion (DX) system may not be an option: some manufacturers do not supply DX evaporators because of control problems and unsatisfactory refrigerant distribution. Thus, ammonia systems use overfeed at smaller sizes than halocarbon-refrigerant systems do.
1. OVERFEED SYSTEM OPERATION
Figure 1 shows a simplified mechanically pumped overfeed system in which a constant liquid level is maintained in the low-pressure receiver using a mechanical float. A mechanical pump circulates liquid through the evaporator(s). The liquid portion of the two-phase return mixture is separated in the low-pressure receiver. The now-dry vapor is directed to the compressor(s) suction. As the liquid is evaporated at the evaporator, makeup liquid refrigerant from the high-pressure receiver enters the low-pressure receiver by means of a refrigerant metering device controlled by the low-side float.
Figure 2 shows a horizontal low-pressure receiver for pumping saturated low-temperature liquid. In this configuration, the pump moves refrigerant at its saturation condition. To keep the refrigerant from flashing to vapor because of the pressure drop between the vessel and pump suction, the suction piping and valves must be designed for low pressure drop and the pump must have a liquid column above the pump suction to provide static pressure. The pump must have low net positive suction pressure requirements; therefore, most pumps for this duty are centrifugal. Because a centrifugal pump can pass relatively large-diameter solids, there is no need for a strainer in the pump suction; however, a dirt leg should be used to reduce the risk of large solids getting into the pump. Also, a check valve is required on the discharge of the pump to ensure that liquid does not drain back out of the liquid feed piping and flood the low-pressure receiver in the event of a power loss or pump failure.
Generally, minimum pump inlet pressure should be at least double the pump’s net positive suction pressure requirement to avoid cavitation. Liquid velocity in the piping to the pump suction should not exceed 3 fps. Net positive suction head and flow requirements vary with pump type and design; consult the pump manufacturer for specific requirements. The pump should be evaluated over the full range of operation at low and high flow. Centrifugal pumps have a flat curve and have difficulty with systems in which discharge pressure fluctuates.
Figure 3 shows a relatively uncommon basic refrigerant-gas-pumped liquid overfeed system configured to delivery low-temperature liquid directly to the evaporators, with pumping power supplied by gas at condenser pressure. In this system, a level control maintains a liquid level in the low-pressure receiver to feed the pumping vessels or drums. There are two pumper drums; one is filled by the low-pressure receiver, and the other is drained as hot gas pushes liquid from the pumper drum to the evaporator. Pumper drum B drains when hot gas enters the drum through valve B. To function properly, the pumper drums must be correctly vented so they can fill during the fill cycle.
A more common arrangement is shown in Figure 4. In this system, high-pressure liquid is flashed into a controlled-pressure receiver that maintains constant liquid pressure at the evaporator inlets, resulting in continuous liquid feed at constant pressure. Flash gas is drawn into the low-pressure receiver through a receiver pressure regulator. Excess liquid drains into a liquid dump trap from the low-pressure receiver. Check valves and a three-way equalizing valve transfer liquid into the controlled-pressure receiver during the dump cycle. Refined versions of this arrangement are used for multistage systems.
2. REFRIGERANT DISTRIBUTION
To prevent underfeeding and excessive overfeeding of refrigerants and for balancing flow between multiple evaporators, metering devices regulate the liquid feed to each evaporator and/or evaporator circuit. An automatic regulating device continuously controls refrigerant feed to the design value. Other common devices are hand expansion valves, calibrated regulating valves, orifices, and distributors.
It is time-consuming to adjust hand expansion valves to achieve ideal flow conditions. However, they have been used with success in many installations. One factor to consider is that standard hand expansion valves are designed to regulate flows caused by the relatively high pressure differences between condensing and evaporating pressure. In overfeed systems, large pressure differences do not exist, so valves with larger orifices may be needed to cope with the combination of increased refrigerant quantity and relatively small pressure differences. Caution is necessary when using larger orifices because controllability decreases as orifice size increases.
Calibrated, manually operated regulating valves reduce some of the uncertainties involved in using conventional hand expansion valves. To be effective, the valves should be adjusted to the manufacturer’s recommendations. Because refrigerant pressure in the liquid feed lines is above saturation pressure, the lines should not contain flash gas. However, liquid flashing can occur if excessive heat gains by the refrigerant and/or high pressure drops build up in feed lines, in overfeed systems using controlled-pressure liquid feed, or with gas-pumped systems using a controlled-pressure receiver (Figure 4).
Orifices for distribution to each individual evaporator circuit should be carefully designed and selected; once installed, they cannot be adjusted. They are generally used only for top- and horizontal-feed multicircuit evaporators and determined by the evaporator manufacturer. Foreign matter and congealed oil globules can restrict flow; a minimum orifice of 0.1 in. is recommended. With ammonia, the circulation rate may have to be increased beyond that needed for the minimum orifice size because of the small liquid volume normally circulated. Pumps and feed and return lines larger than minimum may be needed. This does not apply to halocarbons because of the greater liquid volume circulated as a result of fluid characteristics.
Conventional multiple-outlet distributors with capillary tubes of the type usually paired with thermostatic expansion valves have been used successfully in liquid overfeed systems using a controlled-pressure receiver. Capillary tubes may be installed downstream of a distributor with oversized orifices to achieve the required pressure reduction and efficient distribution.
Existing gravity-flooded evaporators with accumulators can be connected in parallel with liquid overfeed systems. Changes may be needed only for the feed to the accumulator, with suction lines from the accumulator connected to the system wet return lines. An acceptable arrangement is shown in Figure 5. Generally, gravity-flooded evaporators have different circuiting arrangements from overfeed evaporators. In many cases, the circulating rates developed by thermosiphon action are greater than those used in conventional overfeed systems.
Example 1.
Find the orifice diameter of an ammonia overfeed evaporator with a refrigeration load per circuit of 1.54 tons and a circulating rate of 4. Evaporating temperature is −30°F, pressure drop across the orifice is 5 psi, and the coefficient of discharge for the orifice is 0.61. The circulation per circuit is 0.366 gpm.
Solution: Orifice diameter may be calculated as follows:
where
| d | = | orifice diameter, in. |
| a | = | units conversion, 29.81 |
| Q | = | discharge through orifice, gpm |
| p | = | pressure drop through orifice, psi |
| S | = | specific gravity of fluid relative to water at −30°F |
| = | 5.701/8.336 = 0.6839 |
| Cd | = | coefficient of discharge for orifice |
Note: As noted in the text, use a 0.1 in. diameter orifice to avoid clogging. The resultant pressure drop through the orifice for design conditions will be 2.78 psi.
Despite increasingly efficient oil separators applied to the compressor discharge, oil still finds its way into the low-pressure sides of systems. In ammonia overfeed systems, most of this oil can be drained from low-pressure receivers with suitable oil drainage subsystems (e.g., oil pots). In low-temperature systems, a separate valved and pressure-protected, uninsulated oil drain pot can be placed in a warm space below the accumulator (Figure 6). The oil/ammonia mixture flows by gravity into the pot; the refrigerant evaporates and is vented back to the accumulator, and the oil remains. This arrangement is shown in Figure 6. Because of oil’s low solubility in liquid ammonia, thick oil globules circulate with the liquid and can restrict flow through strainers, orifices, and regulators. To maintain high efficiency, oil should be removed from the system by regular draining.
Except at low temperatures, halocarbons are miscible with oil. Therefore, positive oil return to the compressor must be ensured. There are many methods, including oil stills using both electric heat and heat exchange from high-pressure liquid or vapor. Some arrangements are discussed in Chapter 1. At low temperatures, oil skimmers must be used because oil migrates to the top of the low-pressure receiver.
Build-up of excessive oil in evaporators must not be allowed because it rapidly decreases efficiency. This is particularly critical in evaporators with high heat transfer rates associated with low volumes, such as flake ice makers, ice cream freezers, and scraped-surface heat exchangers. Because refrigerant flow rate is high, excessive oil can accumulate and rapidly reduce efficiency.
In a liquid overfeed system, the circulating number or rate is the mass ratio of liquid pumped (i.e., delivered to the evaporator) to amount of vaporized liquid. The amount of liquid vaporized is based on the latent heat for the refrigerant at the evaporator temperature. The overfeed rate is the ratio of liquid to vapor returning to the low-pressure receiver. When vapor leaves an evaporator at saturated vapor conditions with no excess liquid, the circulating rate is 1 and the overfeed rate is 0. With a circulating rate of 4, the overfeed rate at full load is 3. Most systems are designed for steady flow. With few exceptions, load conditions may vary, causing fluctuating temperatures outside and within the evaporator. Evaporator capacities vary considerably; with constant refrigerant flow to the evaporator, the overfeed rate fluctuates.
For each evaporator, there is an ideal circulating rate for every loading condition that gives the best evaporator efficiency (Lorentzen 1968; Lorentzen and Gronnerud 1967). With very few exceptions, it is impractical to predict ideal circulating rates or to design a plant for automatic adjustment of the rates to suit fluctuating loads. The optimum rate can vary with heat load, pipe diameter, circuit length, and number of parallel circuits to achieve the best performance. High circulating rates can cause excessively high pressure drops through evaporators and wet return lines. Return line sizing (see the section on Line Sizing) can affect the ideal rates. Many evaporator manufacturers specify recommended circulating rates for their equipment. Rates in Table 1 agree with these recommendations.
Because of distribution considerations, higher circulating rates are common with top-feed evaporators. In multicircuit systems, refrigerant distribution is important to provide the best possible results. Incorrect distribution can cause excessive overfeed or starvation in some circuits. Manual or automatic regulating valves can control flow for the optimum or design value.
Halocarbon liquid densities are about twice that of ammonia. If halocarbons R-22, R-134a, and R-502 are circulated at the same rate as ammonia, they require 6 to 8.3 times more energy for pumping to the same height than the less-dense ammonia. Because pumping energy must be added to the system load, halocarbon circulating rates are usually lower than those for ammonia. Ammonia has a relatively high latent heat of vaporization, so for equal heat removal, much less ammonia mass must be circulated compared to halocarbons.
Although halocarbons circulate at lower rates than ammonia, the wetting process in the evaporators is still efficient because of the liquid and vapor volume ratios. For example, at −40°F evaporating temperature, with constant flow conditions in the wet return connections, similar ratios of liquid and vapor are experienced with a circulating rate of 4 for ammonia and 2.5 for R-22, R-502, and R-134a. With halocarbons, some additional wetting is also experienced because of the solubility of the oil in these refrigerants.
Figure 7 provides a method for determining the liquid refrigerant flow (Niederer 1964). The charts indicate the amount of refrigerant vaporized in a 1 ton system with circulated operation having no flash gas in the liquid feed line. The value obtained from the chart may be multiplied by the desired circulating rate and total refrigeration to determine total flow.
Pressure drop through flow control regulators is usually 10 to 50% of the available feed pressure. Pressure at the outlet of the flow regulators must be higher than the vapor pressure at the low-pressure receiver by an amount equal to the total pressure drop of the two-phase mixture through the evaporator, any evaporator pressure regulator, and wet return lines. Pressure loss could be up to 5 psi in a typical system. When using recommended liquid feed sizing practices, assuming a single-story building, the frictional pressure drop from pump discharge to evaporators is about 10 psi. Therefore, a pump for 20 to 25 psi should be satisfactory in this case, depending on the lengths and sizes of feed lines, quantity and types of fittings, and vertical lift involved between the pump discharge and evaporator.
5. PUMP SELECTION AND INSTALLATION
Mechanical pumps, gas-pressure-driven pumping systems, and injector nozzle systems can be used for liquid overfeed systems.
Types of mechanical pump drives include open, semihermetic, magnetic clutch, and hermetic. Rotor arrangements include positive rotary, centrifugal, and turbine vane. Positive rotary and gear pumps are generally operated at slow speeds up to 900 rpm and are used only for liquid transfer because of their high net-positive suction head requirements. Whatever type of pump is used, take care to prevent flashing at the pump suction and/or within the pump itself (i.e., cavitation).
Centrifugal pumps are typically used for systems requiring larger volume flow rates. Regenerative turbines are used with relatively high pressure and large swings in discharge pressure.
Open pumps are fitted with a wide variety of packing or seals. For continuous duty, a mechanical seal with an oil reservoir or a liquid refrigerant supply to cool, wash, and lubricate the seals is commonly used. Experience with the particular application or the recommendations of an experienced pump supplier are the best guide for selecting the packing or seal. The motor and pump can be magnetically coupled instead of shaft coupled to eliminate shaft seals. A small immersion electric heater in the oil reservoir can be used with low-temperature systems to ensure that the oil remains fluid. Motors should have a service factor that compensates for drag on the pump if the oil is cold or stiff.
Considerations include ambient temperatures, heat leakage, fluctuating system pressures from compressor cycling, internal bypass of liquid to pump suction, friction heat, motor heat conduction, dynamic conditions, cycling of automatic evaporator liquid and suction stop valves, action of regulators, gas entrance with liquid, and loss of subcooling by pressure drop. Another factor to consider is the time lag caused by the heat capacity of pump suction, cavitation, and net positive suction head factors (Lorentzen 1963).
The motor and stator of hermetic pumps are separated from the refrigerant by a thin nonmagnetic membrane. The metal membrane should be strong enough to withstand system design pressures. Normally, the motors are cooled and the bearings lubricated by liquid refrigerant bypassed from the pump discharge. Regardless of pump type, it is considered good practice to specify and install two pumps: one operating and one standby.
Installing and Connecting Mechanical Pumps
Because of the sensitive suction conditions (i.e., refrigerant at its boiling point) of mechanical pumps on overfeed systems, the manufacturer’s application and installation specifications must be followed closely. Suction connections should be as short as possible, without restrictions, valves, or elbows. Angle or full-flow ball valves should be used. Installing straight-pattern globe valves with valve spindles in the 3 or 9 o’clock position eliminates possible traps. Gas binding is more likely with high evaporating pressures.
Installing a discharge check valve on centrifugal pumps prevents backflow during pump failure or power interruptions, and subsequent flooding of the low-pressure accumulator. A minimum flow bypass protects the pump from deadheading in the unlikely event that all connected evaporators’ liquid feed solenoids are closed. A hydrostatic relief device should be used with positive-displacement pumps. Strainers are not installed in ammonia pump suction lines because, as they fill, their pressure drop increases and is likely to cause the mechanical pump to cavitate.
Pump suction connections to liquid legs (vertical drop legs from low-pressure receivers) should be made above the bottom of the legs to allow collection space for solids and sludge. Consider using vortex eliminators, particularly when submersion of the suction inlet is insufficient to prevent the entrainment of gas bubbles in liquid flowing to the pump suction. Lorentzen (1963, 1965) gives more complete information.
Sizing the pump suction line is important. The general velocity should be about 3 fps. Small lines cause restrictions and higher pressure drop; oversized lines can cause bubble formation during evaporator temperature decrease because of the heat capacity of the liquid and piping. Oversized lines also increase heat gain from ambient spaces. Oil heaters for the seal lubrication system keep the oil fluid, particularly during subzero operation. Thermally insulating all cold surfaces of pumps, lines, and receivers decreases the likelihood of cavitation and increases the pump’s reliability and stability.
The liquid level in the low-pressure receiver can be controlled by conventional devices such as low-pressure float valves, combinations of float switch and solenoid valve with manual hand expansion valves, thermostatic level controls, combinations of electronic level sensors with a manual or motorized expansion valve or pulse-width-modulating valve, or other proven automatic devices. High-level float switches are recommended for stopping compressors and/or operating alarms, and are mandatory in some areas. Electronic level sensors (e.g., capacitance probes) are commonly used for level control and alarms. The signal can be sent to the computer control system to give operations staff continuous level feedback; however, these systems still use mechanical float switches as high-level compressor (or low-level pump) cutout safeties. Solenoid valves should be installed on liquid lines (minimum sized) feeding low-pressure receivers so that positive shutoff is automatically achieved with system shutdown or power failure. This prevents excessive refrigerant from collecting in low-pressure receivers, which can cause carryover at start-up.
To prevent pumps from operating without liquid, low-level float switches can be fitted on liquid legs or low on the float column. An alternative device, a differential pressure switch connected across pump discharge and suction connections, stops the pump without interrupting liquid flow. Cavitation can also cause this control to operate. When hand expansion valves are used to control the circulation rate to evaporators, the number of turns the valve is opened should be set for operation within the expected pump discharge pressure ranges. Occasionally, with reduced inlet pressure, these valves can starve the circuit or evaporator. Calibrated, manually adjusted liquid flow regulators are available to meter the flow according to the design conditions. Automatic flow-regulating valves specifically for overfeed systems are available.
Liquid feed solenoid and suction stop valves should be selected for refrigerant flow rates by mass or volume, not by refrigeration ratings from capacity tables. Evaporator pressure regulators, if necessary, should be sized according to the manufacturer’s ratings, with allowance for expected overfeed rates. Notify the manufacturer that valves being ordered are for overfeed application, because slight modifications may be required. When evaporator pressure regulators are used on overfeed systems for controlling air defrosting of cooling units (particularly when fed with very-low-temperature liquid), part of the refrigerant heat gain may be achieved by sensible, not latent, effect as the refrigerant temperature increases to the saturation temperature corresponding to the regulator pressure setting. If the difference between the liquid feed and evaporating temperatures is large, consider connecting the units to a different, higher-temperature (or -pressure) liquid source.
When a check valve and a solenoid valve are paired on an overfeed system liquid line, the check valve should be downstream from the solenoid valve. Otherwise, when the solenoid valve is closed, dangerous hydraulic pressure can build up from expansion of the trapped liquid as it absorbs heat from the surrounding space. When evaporator pressure regulators are used with overfed evaporators, entering liquid pressure must be high enough to cause flow into the evaporator.
Multievaporator systems must have minimum flow protection to prevent pump cavitation. Minimum flow may be controlled with a manually set hand expansion valve, orifice, or automatic flow regulator. When some evaporator liquid feed solenoids are closed, excess liquid is bypassed into the low-pressure receiver rather than forced through the evaporators still in operation. This prevents higher evaporating temperatures from pressurizing evaporators and reducing capacities of operating units.
Where low-temperature liquid feeds can be isolated manually, automatically, or during a power failure, a relief device can be installed to prevent damage from excessive hydraulic pressure. Multicircuit systems must have a bypass hydrostatic relief valve in the pump discharge downstream of the pump discharge check valve. The hydrostatic relief valve’s pressure should be set considering the back pressure on the valve from the low-pressure receiver. For example, if the low-pressure receiver is set at 50 psig, the maximum allowable pressure for the pump or piping is 150 psig, and the relief valve opens on a differential pressure, the valve should have 100 psi set pressure. Hydrostatic relief devices, in essence relief regulators, are relatively unaffected by back pressure and can simply be set to open at 150 psig in the previous example.
There is an ideal refrigerant feed and flow system for each evaporator design and liquid feed arrangement. An evaporator designed for gravity-flooded operation cannot necessarily be converted to an overfeed arrangement, and vice versa; neither can systems always be designed to circulate the optimum flow rate under all load conditions.
When top feed is used to ensure good distribution, a minimum quantity per circuit must be circulated, generally about 0.5 gpm. In bottom-feed evaporators, distribution is less critical than in top or horizontal feed because each circuit fills with liquid to equal the pressure loss in other parallel circuits.
Circuit length in evaporators is determined by allowable pressure drop, load per circuit, tubing diameter, overfeed rate, type of refrigerant, and heat transfer coefficients. The most efficient circuiting is determined in most cases through laboratory tests conducted by the evaporator manufacturers. Their recommendations should be followed when designing systems.
Top Feed Versus Bottom Feed
System design must determine whether evaporators are to be top fed or bottom fed, although both feed types can be installed in a single system. Each feed type has its own unique advantages and disadvantages; no arrangement is best for all systems.
Advantages of top feed include
Smaller refrigerant charge
Quicker, simpler defrost valve arrangements
Simpler suction valve trains for evaporators requiring defrost that are regulated in refrigeration mode
For halocarbon systems with greater fluid densities, the refrigerant charge, oil return, and static pressure are very important.
Bottom feed is advantageous in that
Distribution considerations are less critical
Relative locations of evaporators and low-pressure receivers are less important
System design and layout are simpler
Reduced potential of hot-gas bypass at the end of the defrost cycle using top-fed hot gas because of the presence of the distribution orifices
Lower system refrigerant flow rates
The top-feed system is limited by the relative location of components. Because this system sometimes requires more refrigerant circulation than bottom-feed systems, it has greater pumping requirements, resulting in a larger refrigerant pump and possibly larger feed and return lines, and increased line pressure drop penalties. In bottom-feed evaporators, multiple headers with individual inlets and outlets can be installed to reduce static pressure penalties. For high lift of return overfeed lines from the evaporators, dual suction risers can be used to reduce static pressure penalties (Miller 1974, 1979).
Distribution must be considered when using a vertical refrigerant feed, because of static pressure variations in the feed and return header circuits. For example, for equal circuit loadings in a horizontal-airflow unit cooler, using gradually smaller orifices for bottom-feed circuits than for upper circuits can compensate for pressure differences.
When the top-feed arrangement allows for free draining into wet suction return piping, particularly in air, water, or electric defrost units, any liquid remaining in the coils rapidly drains to the low-pressure receiver, allowing a quicker defrost. In this situation, defrost is faster than in a comparable bottom-feed evaporator.
Overfeed systems need more refrigerant than dry expansion systems. Top-feed arrangements have smaller charges than bottom-feed systems. The amount of charge depends on evaporator volume, circulating rate, sizes of flow and return lines, operating temperature differences, and heat transfer coefficients. Generally, top-feed evaporators operate with the refrigerant charge occupying about 25 to 40% of the evaporator volume. The refrigerant charge for the bottom-feed arrangement occupies about 40 to 60% of the evaporator volume, with corresponding variations in the wet returns. Under some no-load conditions in bottom-fed evaporators, the charge may approach 100% of the evaporator volume. In this case, the liquid surge volume from full load to no load must be considered in sizing the low-pressure receiver (Miller 1971, 1974).
Evaporators with high heat transfer rates, such as flake ice makers and scraped-surface heat exchangers, have small charges because of small evaporator volumes. The amount of refrigerant in the low side has a major effect on the size of the low-pressure receiver, especially in horizontal vessels. The cross-sectional area for vapor flow in horizontal vessels is reduced with increasing liquid level. It is important to ascertain the evaporator refrigerant charge with fluctuating loads for correct vessel design, particularly for a low-pressure receiver that does not have a constant level control but is fed through a high-pressure control.
9. START-UP AND OPERATION
All control devices should be checked before start-up. If mechanical pumps are used, the direction of operation must be correct. System evacuation and charging procedures are similar to those for other systems. The system must be operating under normal conditions to determine the total required refrigerant charge. Liquid height is established by liquid level indicators in the low-pressure receivers.
Calibrated, manually operated flow regulators should be set for the design conditions and adjusted for better performance as necessary. When hand expansion valves are used, the system should be started by opening the valves about one-quarter to one-half turn. When balancing is necessary, the regulators should be cut back on units not starved of liquid, to force the liquid through underfed units. The outlet temperature of the return line from each evaporator should be the same as the main return line’s saturation temperature, allowing for pressure drops. Starved units are indicated by temperatures higher than those for adequately fed units. Excessive feed to a circuit increases evaporator temperature because of excessive pressure drop.
The minimum flow bypass from the liquid line to the low-pressure receiver should be adjusted and checked to ensure that it is functioning. During operation, the pump manufacturer’s recommendations for lubrication and maintenance should be followed. Regular oil draining procedures should be established for ammonia systems; the quantities of oil added to and drained from each system should be logged and compared, to determine whether oil is accumulating out in the system. Oil should not be drained in halocarbon systems. Because of oil’s miscibility with halocarbons at high temperatures, it may be necessary to add oil to the system until an operating balance is achieved (Soling 1971; Stoecker 1960).
Operating Costs and Efficiency
Operating costs for overfeed systems are generally lower than for other systems (though not always, because of various inefficiencies that exist from system to system and from plant to plant). For existing dry expansion plants converted to liquid overfeed, the operating hours, power, and maintenance costs are reduced. Efficiency of early gas pump systems has been improved by using high-side pressure to circulate overfeed liquid. This type of system is indicated in the controlled-pressure system shown in Figure 4.
Gas-pumped systems, which use higher-pressure refrigerant gas to pump liquid directly to the evaporators or to return overfed liquid to the controlled-pressure receiver, require additional compressor volume flow rate, from which no useful refrigeration is obtained. These systems may consume 4 to 10% or more of the compressor power to maintain refrigerant flow.
If condensing pressure is reduced as much as 10 psi, the compressor power per unit of refrigeration drops by about 7%. Where outdoor dry- and wet-bulb conditions allow, a mechanical pump can be used to pump liquid with no effect on evaporator performance. Gas-operated systems must, however, maintain the condensing pressure within a much smaller range to reliably pump the liquid and maintain the required overfeed rate.
The liquid feed line to the evaporator and wet return line to the low-pressure receiver cannot be sized by the method described in Chapter 22 of the 2017 ASHRAE Handbook—Fundamentals. Figure 7 can be used to size liquid feed lines. The circulating rate from Table 1 is multiplied by the evaporating rate. For example, an evaporator with a circulating rate of 4 that forms vapor at a rate of 5 lb/min needs a feed line sized for 4 × 5 = 20 lb/min.
Alternative ways to design wet returns include the following:
Use one pipe size larger than calculated for vapor flow alone.
Use a velocity selected for dry expansion reduced by the factor
. This method suggests that the wet-return velocity for a circulating rate of 4 is
, or half that of the acceptable dry-vapor velocity.
Use the design method described by Chaddock et al. (1972). The report includes tables of flow capacities at 2°F drop per 100 ft of horizontal lines for R-717 (ammonia), R-12, R-22, and R-502.
When sizing refrigerant lines, the following design precautions should be taken:
Carefully size overfeed return lines with vertical risers because more liquid is held in risers than in horizontal pipe. This holdup increases with reduced vapor flow and increases pressure loss because of gravity and two-phase pressure drop.
Use double risers with halocarbons to maintain velocity at partial loads and to reduce liquid static pressure loss (Miller 1979).
Add the equivalent of a 100% liquid static height penalty to the pressure drop allowance to compensate for liquid holdup in ammonia systems that have unavoidable vertical risers.
As alternatives in severe cases, provide traps and a means of pumping liquids, or use dual-suction risers.
Install low-pressure drop valves so the stems are horizontal or nearly so (Chisholm 1971).
11. LOW-PRESSURE RECEIVER SIZING
Low-pressure receivers are also called recirculators, liquid separators, suction traps, accumulators, liquid/vapor separators, flash coolers, gas and liquid coolers, surge drums, knockout drums, slop tanks, or low-side pressure vessels, depending on their function and user preference.
Low-pressure receiver sizing is determined by the required liquid holdup (i.e., ballast or reserve) volume and allowable gas velocity. The volume must accommodate fluctuations of liquid in the evaporators and overfeed return lines as a result of load changes (i.e., surge) and defrost periods. It must also handle swelling and foaming of the liquid charge in the receiver, which is caused by boiling caused by heat gain or pressure reduction during load fluxations. At the same time, a liquid seal must be maintained on the supply line for continuous-circulation devices. A separating space must be provided for gas velocity to slow enough to allow the liquid droplets to fall out by gravity and ensure a minimum entrainment of liquid droplets into the piping to the compressor suction. Space limitations and design requirements result in a wide variety of configurations (Lorentzen 1966; Miller 1971; Niemeyer 1961; Scheiman 1963, 1964; Sonders and Brown 1934; Stoecker 1960; Younger 1955).
In selecting a gas-and-liquid separator, adequate volume for the liquid supply and a vapor space above the minimum liquid height for liquid surge must be provided. This requires analysis of operating load variations. This, in turn, determines the maximum operating liquid level. Figures 8 and 9 identify these levels and the important parameters of vertical and horizontal gravity separators.
Vertical separators maintain the same separating area with level variations, whereas separating areas in horizontal separators change with level variations. Horizontal separators should have inlets and outlets separated horizontally by at least the vertical separating distance. A useful arrangement in horizontal separators distributes the inlet flow into two or more connections to reduce turbulence and horizontal velocity without reducing the residence time of the gas flow within the shell (Miller 1971).
In horizontal separators, as the horizontal separating distance increases beyond the vertical separating distance, the residence time of vapor passing through increases so that higher velocities than allowed in vertical separators can be tolerated. As the separating distance reduces, the amount of liquid entrainment from gravity separators increases. Table 2 shows the gravity separation velocities. For surging loads or pulsating flow associated with large step changes in capacity, the maximum steady-flow velocity should be reduced to a value achieved by a suitable multiplier such as 0.75.
The gas-and-liquid separator may be designed with internal baffles or eliminators to separate liquid from the suction gas returning from the top of the shell to the compressor. More often, these additional internal devices are not needed because there is enough separation space above the liquid level in the vessel for gravity to be used as the sole separation method. Such a design is usually of the vertical type, with a separation height above the liquid level of 24 to 36 in. The shell diameter is sized to keep suction gas velocity low enough to allow liquid droplets to separate and not be entrained with the returning suction gas off the top of the shell.
Although separators are made with length-to-diameter (L/D) ratios of 1/1 increasing to 10/1, the least expensive separators usually have L/D ratios between 3/1 and 5/1. Vertical separators are normally used for systems with reciprocating compressors. Horizontal separators may be preferable where vertical height is critical and/or where large volume space for liquid is required. The procedures for designing vertical and horizontal separators are different.
A vertical gas-and-liquid separator is shown in Figure 9. The end of the inlet pipe C1 is capped so that flow dispersion is directed down toward the liquid level. The suggested opening is four times the transverse internal area of the pipe. Height H1 with a 120° dispersion of the flow reaches approximately 70% of the internal diameter of the shell.
An alternative inlet pipe with a downturned elbow or mitered bend can be used. However, the jet effect of entering fluid must be considered to avoid undue splashing. The pipe outlet must be a minimum distance of IDS/5 above the maximum liquid level in the shell. H2 is measured from the outlet to the inside top of the shell. It equals D + 0.5 times the depth of the curved portion of the head.
For the alternative location of C2, determine IDS from the following equation:
The maximum liquid height in the separator is a function of the type of system in which the separator is being used. In some systems this can be estimated, but in others, previous experience is the only guide for selecting the proper liquid height. Accumulated liquid must be returned to the system by a suitable means at a rate comparable to its collection rate.
With a horizontal separator, the vertical separation distance used is an average value. The top part of the horizontal shell restricts gas flow so that the maximum vertical separation distance cannot be used. If Ht represents the maximum vertical distance from the liquid level to the inside top of the shell, the average separation distance as a fraction of IDS is as follows:
The suction connection(s) for refrigerant gas leaving the horizontal shell must be at or above the location established by the average distance for separation. The maximum cross-flow velocity of gas establishes residence time for the gas and any entrained liquid droplets in the shell. The most effective removal of entrainment occurs when residence time is the maximum practical. Regardless of the number of gas outlet connections for uniform distribution of gas flow, the cross-sectional area of the gas space is
where
| Ax | = | minimum transverse net cross-sectional area or gas space, in2 |
| D | = | average vertical separation distance, in. |
| Q | = | total quantity of gas leaving vessel, cfm |
| L | = | inside length of shell, in. |
| V | = | separation velocity for separation distance used, fpm |
For nonuniform distribution of gas flow in the horizontal shell, determine the minimum horizontal distance for gas flow from point of entry to point of exit as follows:
where
| RTL | = | residence time length, in. |
| Q | = | maximum flow for that portion of the shell, cfm |
All connections must be sized for the flow rates and pressure drops permissible and must be positioned to minimize liquid splashing. Internal baffles or mist eliminators can reduce vessel diameter; however, test correlations are necessary for a given configuration and placement of these devices.
An alternative formula for determining separation velocities that can be applied to separators is
where
| v | = | velocity of vapor, fps |
| ρl | = | density of liquid, lb/ft3 |
| ρv | = | density of vapor, lb/ft3 |
| k | = | factor based on experience without regard to vertical separation distance and surface tension for gravity separators |
In gravity liquid/vapor separators that must separate heavy entrainment from vapors, use a k of 0.1. This gives velocities equivalent to those used for 12 to 14 in. vertical separation distance for R-717 and 14 to 16 in. vertical separation distance for halocarbons. In knockout drums that separate light entrainment, use a k of 0.2. This gives velocities equivalent to those used for 36 in. vertical separation distance for R-717 and for halocarbons.
Chaddock, J.B., D.P. Werner, and C.G. Papachristou. 1972. Pressure drop in the suction lines of refrigerant circulation systems. ASHRAE Transactions 78(2):114-123.
Chisholm, D. 1971. Prediction of pressure drop at pipe fittings during two-phase flow. Proceedings of the IIR Conference, Washington, D.C.
Lorentzen, G. 1963. Conditions of cavitation in liquid pumps for refrigerant circulation. Progress Refrigeration Science Technology I:497.
Lorentzen, G. 1965. How to design piping for liquid recirculation. Heating, Piping & Air Conditioning (June):139.
Lorentzen, G. 1966. On the dimensioning of liquid separators for refrigeration systems. Kältetechnik 18:89.
Lorentzen, G. 1968. Evaporator design and liquid feed regulation. Journal of Refrigeration (November-December):160.
Lorentzen, G., and R. Gronnerud. 1967. On the design of recirculation type evaporators. Kulde 21(4):55.
Miller, D.K. 1971. Recent methods for sizing liquid overfeed piping and suction accumulator-receivers. Proceedings of the IIR Conference, Washington, D.C.
Miller, D.K. 1974. Refrigeration problems of a VCM carrying tanker. ASHRAE Journal 11.
Miller, D.K. 1979. Sizing dual suction risers in liquid overfeed refrigeration systems. Chemical Engineering 9.
Niederer, D.H. 1964. Liquid recirculation systems—What rate of feed is recommended. The Air Conditioning & Refrigeration Business (December).
Niemeyer, E.R. 1961. Check these points when designing knockout drums. Hydrocarbon Processing and Petroleum Refiner (June).
Scheiman, A.D. 1963. Size vapor-liquid separators quicker by nomograph. Hydrocarbon Processing and Petroleum Refiner (October).
Scheiman, A.D. 1964. Horizontal vapor-liquid separators. Hydrocarbon Processing and Petroleum Refiner (May).
Scotland, W.B. 1963. Discharge temperature considerations with multicylinder ammonia compressors. Modern Refrigeration (February).
Scotland, W.B. 1970. Advantages, disadvantages and economics of liquid overfeed systems. ASHRAE Symposium Bulletin KC-70-3: Liquid overfeed systems.
Soling, S.P. 1971. Oil recovery from low temperature pump recirculating hydrocarbon systems. ASHRAE Symposium Bulletin PH-71-2: Effect of oil on the refrigeration system.
Sonders, M., and G.G. Brown. 1934. Design of fractionating columns, entrainment and capacity. Industrial & Engineering Chemistry (January).
Stoecker, W.F. 1960. How to design and operate flooded evaporators for cooling air and liquids. Heating, Piping & Air Conditioning (December).
Younger, A.H. 1955. How to size future process vessels. Chemical Engineering (May).