This chapter addresses air-conditioning systems for industrial facilities
such as manufacturing plants, laboratories, processing plants, and power plants. HVAC systems provide
the process environment (including temperature, humidity, air motion, air quality, noise, and
cleanliness) to facilitate industrial processes and provide for the health, safety, and comfort of
personnel.
Many industrial buildings require large amounts of energy, in both manufacturing and maintaining building
environmental conditions. This chapter provides system and building design guidance for energy
conservation by using insulation, ventilation, and waste heat recovery.
Typical temperatures, relative humidities, and specific filtration requirements for storage,
manufacture, and processing of various commodities are listed in Table 1.
Requirements for a specific application may differ from those in the table.
Industrial processes or regulatory requirements may change over time; thus, systems should be able to
provide for future requirements (to the extent practical).
Outdoor design requirements and indoor temperature, humidity, cleanliness, noise, and allowable
variations should be established by agreement with the owner. A compromise between requirements for
product or process conditions and those for comfort may optimize quality and production costs.
An environment that allows a worker to safely perform assigned duties without fatigue caused by
temperature and humidity may enhance performance.
Special Warning: Some industrial spaces may contain
flammable, combustible, and/or toxic concentrations of vapors or dusts under either normal or
abnormal conditions. In spaces such as these, there are safety issues that this chapter may not
completely address. Special precautions must be taken in accordance with requirements of recognized
authorities such as the National Fire Protection Association (NFPA), the Occupational Safety and
Health Administration (OSHA), the American Conference of Governmental Industrial Hygienists (ACGIH),
and the American National Standards Institute (ANSI). In all situations, engineers, designers, and
installers who encounter conflicting codes and standards must defer to the code or standard that
best addresses personnel safety.
The cascade-ventilation-system design for toxic agents or similar hazardous materials is a potential
fit for such facilities. This can include a once-through, “push-pull” system, drawing
air from the highly toxic areas to lower ones, with air change rates varying from 10 to 60 ach;
pressures from –808.6 Pa to –62.2 Pa; and temperatures of
10 to 38°C. Applicable federal, state, and industry codes, and standards must be
applied in the design of these facilities.
The supply system includes air-handling units (AHUs) with steam and hot water
heating and chilled water cooling coils, ductwork, dampers, and accessories.
Transfer air (TA) assemblies consist of ductwork,
dampers, blast valves, fast-actuating dampers, and accessories.
The exhaust air filtration system includes exhaust air filter units (EAFUs) with two HEPA filters
and six charcoal filters to capture highly toxic agent vapors, ductwork, dampers, accessories,
and stacks.
The HVAC units are powered by off-site and essential power, and the instrumentation and facility control system (FCS) are
fed from uninterruptible power supply (UPS). FCS is a
safety instrumented system (SIS).
2. PROCESS AND PRODUCT REQUIREMENTS
An industrial product or process may require control of the indoor environment if it affects one or
more of the following factors.
Rate of Chemical Reaction
Some processes require temperature and humidity control to regulate chemical reactions. In rayon
manufacturing, for example, pulp sheets are conditioned, cut to size, and mercerized. The
temperature directly controls the rate of reaction, and the relative humidity maintains the
solution at a constant strength and rate of evaporation.
In drying varnish, oxidizing depends on temperature. Desirable temperatures vary with the type of
varnish. High relative humidity retards surface oxidation and allows internal gases to escape as
chemical oxidizers cure the varnish from within. Thus, a bubble-free surface is maintained with
a homogeneous film throughout.
The cooling rate determines the size of crystals formed from a saturated solution. Both
temperature and relative humidity affect the cooling rate and change the solution density by
evaporation.
In coating pans for pills, a heavy sugar solution is added to the tumbling mass. As water
evaporates, sugar crystals cover each pill. Moving the correct quantity of air over the pills at
the correct temperature and relative humidity forms a smooth, opaque coating. If cooling and
drying are too slow, the coating will be rough, translucent, and have an unsatisfactory
appearance. If the cooling and drying are too fast, the coating will chip through to the
interior.
Rate of Biochemical Reaction
Fermentation requires both temperature and humidity control to regulate the rate of biochemical
reactions. Many fermentation vessels are jacketed to maintain consistent internal temperatures.
Fermentors are held at different temperatures, depending on the process involved. In brewing,
typical fermentor temperatures range from 7 to 11°C. Because of vessel
jacketing, tight control of room temperature may not be required. Usually, space temperatures
should be held as close as practical to the process temperature inside the fermentation vessel.
Designing such spaces should take into account gases and other by-products generated by
fermentation. Typically, carbon dioxide is the most prevalent by-product of fermentation in
brewing and presents the greatest potential hazard if a fermentor overpressurizes the seal.
Provide adequate ventilation in case carbon dioxide escapes the process.
In biopharmaceutical processes, hazardous organisms can escape a fermentor; design of spaces
using those fermentors should allow containment. Heat gains from steam-sparged vessels should
also be accounted for in such spaces.
Product Accuracy and Uniformity
Air temperature and cleanliness affect quality in manufacturing precision instruments, lenses,
and tools. When manufacturing tolerances are within 5 μm, close temperature
control (typically ±2.8 K) prevents expansion and contraction of the
material; constant temperature over time is more important than the temperature level. Usually,
conditions are selected for personnel comfort and to prevent a film of moisture on the surface.
A high-efficiency particulate air (HEPA) or ultralow-penetration air (ULPA) filter may be
required.
Manufacturing pharmaceutical tablets requires close control of humidity for optimum tablet
formation. Tableting typically requires less than 40% rh at 20°C.
Air temperature and relative humidity markedly influence production rate and product mass,
strength, appearance, and quality in manufacturing or processing hygroscopic materials such as
textiles, paper, wood, leather, and tobacco. Moisture in vegetable and animal materials (and
some minerals) reaches equilibrium with moisture in the surrounding air by regain (the percentage of absorbed moisture in a
material compared to that material’s bone-dry mass). For example, if a material sample
with a mass of 2.5 kg has a mass of only 2.25 kg after thorough drying
under standard conditions of 105 to 110°C, the mass of absorbed moisture is
0.25 kg, 10% of the sample’s bone-dry mass. Therefore, the regain is 10%.
Table 2 lists typical regain
values for materials at 24°C in equilibrium at various relative humidities.
Temperature change affects the rate of absorption or drying, which generally varies with the
thickness, density, and nature of the material. Sudden temperature changes cause slight changes
in regain even with fixed relative humidity, but the major change occurs as a function of
relative humidity.
Hygroscopic materials deliver sensible heat to the air in an amount equal to the latent heat of
the absorbed moisture. The amount of heat liberated should be added to the cooling load if it is
significant, but it is usually quite small. Manufacturing economy requires regain to be
maintained at a level suitable for rapid and satisfactory manipulation. Uniform relative
humidity allows high-speed machinery to operate efficiently.
Some materials may be exposed to the required humidity during manufacturing or processing, and
others may be treated separately after conditioning and drying. Conditioning removes or adds
hygroscopic moisture. Drying removes both hygroscopic moisture and free moisture in excess of
that in equilibrium. Drying and conditioning can be combined to remove moisture and accurately
regulate the final moisture content in products such as tobacco and textiles. Conditioning or
drying is frequently a continuous process in which the material is conveyed through a tunnel and
subjected to controlled atmospheric conditions. For more detail, see Chapter 24 of the 2020
ASHRAE Handbook—HVAC Systems and Equipment.
Corrosion, Rust, and Abrasion
In manufacturing metal products, temperature and relative humidity must be kept sufficiently low
to prevent hands from sweating, thus protecting the finished article from fingerprints, tarnish,
and/or etching. Salt and acid in perspiration can cause corrosion and rust in as little as a few
hours. Manufacture of polished surfaces and of steel-belted radial tires usually requires
medium-efficiency to HEPA filtering to prevent surface abrasion.
Each application must be evaluated to determine the filtration needed to counter the adverse
effects on the product or process of dust particles, airborne bacteria, smoke, spores, pollen,
and radioactive particles. These effects include chemically altering production material,
spoiling perishable goods, and clogging small openings in precision machinery. See Chapter 29 of
the 2020 ASHRAE Handbook—HVAC Systems and Equipment
for
details.
Static electricity is often detrimental in processing light materials such as textile fibers and
paper, and extremely dangerous where potentially explosive atmospheres or materials are present.
Static electric charges are generally minimized when relative humidity is above 35%. Room
relative humidity may need to be maintained at 65% or higher because machinery heat raises the
machine ambient temperature well above the room temperature, creating localized areas of low
relative humidity. Such areas could be sources of static electricity. The parts assembly area of
an ammunition plant should have design conditions of 24°C and 40 to 60% rh. In
addition, air-moving equipment (fans) should be spark resistant.
According to NFPA Standard 77, humidification increases a
material’s surface conductivity, but the static electric charge dissipates only if there
is a conductive path to ground.
However, humidification is not a cure-all for static electricity problems. Some insulators do not
adsorb or absorb moisture from the air, and high humidity does not noticeably decrease their
surface resistivity. Examples include uncontaminated surfaces of some polymeric materials (e.g.,
plastic piping and containers, films), and the surface of petroleum liquids. These surfaces can
accumulate static electric charge even when the atmosphere has a humidity of 100%.
3. PERSONNEL REQUIREMENTS
Space conditions required by health and safety standards to avoid excess exposure to high
temperatures and airborne contaminants are often established by the American Conference of
Governmental Industrial Hygienists (ACGIH). In the United States, the National Institute of
Occupational Safety and Health (NIOSH) does research and recommends guidelines for workplace
environments. The Occupational Safety and Health Administration (OSHA) sets standards based on these
guidelines, with enforcement usually assigned to a corresponding state agency.
Standards for safe levels of contaminants in the work environment or in air exhausted from facilities
do not cover everything that may be encountered. Minimum safety standards and design criteria are
available from U.S. Department of Health agencies such as the National Institute of Health, National
Cancer Institute, and Public Health Service. The U.S. Department of Energy and Nuclear Regulatory
Commission establish standards for radioactive substances.
Industrial plants are usually designed for an internal temperature of 16 to 32°C
and a maximum of 60% rh. Tighter controls are often dictated by the specific operations and
processes located in the building. ACGIH (2016) established guidelines to evaluate high
temperature and humidity levels in terms of heat stress (Dukes-Dobos and Henschel 1971). See
Chapter 9 of the 2021 ASHRAE
Handbook—Fundamentals for a more
detailed analysis of work rate, air velocity, rest, and the effects of radiant heat.
Temperature control becomes tighter and more specific if personnel comfort, rather than avoidance
of heat stress, becomes the criterion. Nearly sedentary workers prefer a winter temperature of
22°C and a summer temperature of 26°C at a maximum of 60% rh.
Workers at a high rate of activity prefer 18°C; they are less sensitive to
temperature changes and can be cooled by increasing the air velocity. ASHRAE Standard 55 provides more detailed information.
Contamination Control Levels
Toxic and/or hazardous materials are present in many industrial plants and laboratories. Gases
and vapors are found near acid baths and tanks holding process chemicals. Plating operations,
spraying, mixing, abrasive cleaning, and other processes generate dust, fumes, and mists. Many
animal and laboratory procedures (e.g., grinding, blending, sonication, weighing) generate
aerosols. Air-conditioning and ventilation systems must minimize exposure to these materials.
When airborne, these materials greatly expand their range and potential for affecting more
people. Chapter 11 of the 2021 ASHRAE Handbook—Fundamentals,
OSHA requirements, and ACGIH (2016) give guidance on the health effects of various
materials.
Concentrations of gaseous flammable substances must also be kept below explosive limits.
Acceptable concentrations of these substances are a maximum of 25% of the lower explosive limit.
Chapter 11 of the 2021 ASHRAE Handbook—Fundamentals provides
data on flammable limits and their means of control.
Instruments are available to measure concentrations of common gases and vapors, but specific
monitoring requirements and methods must be developed for uncommon ones.
Required environmental conditions for equipment, process, and personnel comfort must be known before
selecting HVAC equipment. The engineer and owner jointly establish design criteria, including the
space-by-space environment in facilities, process heat loads and exhaust requirements, heat and
cooling energy recovery, load factors and equipment diversity, lighting, cleanliness, etc. Consider
separating dirty processes from areas that require progressively cleaner air.
Insulation should be evaluated for initial cost and operating and energy cost savings. When high
levels of moisture are required in the building, the air-conditioning and structural envelope must
prevent unwanted condensation and ensure a high-quality product. Condensation can be prevented by
eliminating thermal short circuits, installing proper insulation, and using vapor barriers. See
Chapters 25 and 27 of the 2021 ASHRAE
Handbook—Fundamentals for
further details.
Personnel engaged in some industrial processes may be subject to a wide range of activity levels for
which a broad range of temperatures and humidities are desirable. Chapter 9 of the 2021 ASHRAE
Handbook—Fundamentals addresses recommended indoor
conditions for a variety of activity levels.
If layout and construction drawings are not available, a complete survey of existing premises and a
checklist for proposed facilities are necessary (Table
3).
New industrial buildings are typically single story with a flat roof and ample height to distribute
air and utilities without interfering with process operations. Fluorescent fixtures are commonly
mounted at heights up to 4 m, high-output fluorescent fixtures up to 6 m,
and high-pressure sodium or metal halide fixtures above 6 m; LED fixtures are used at
all heights. Lighting design considers light quality, diffusion, room size, mounting height, and
economics. Illumination levels should conform to recommendations of the Illuminating Engineering
Society of North America.
Air-conditioning systems can be located on the roof of the building or (ideally) in an interior
equipment room. Air intakes should not be located too close to loading docks or other sources of
contamination. (See the section on Air Filtration Systems.) HVAC system installation must be
coordinated with other systems and equipment that compete for building space, such as piping
systems, electrical bus, fire sprinklers, lighting, cranes, structural elements, etc.
Operations in the building must also be considered: some require close control of temperature,
humidity, and/or contaminants. A schedule of operations is helpful in determining heating and
cooling loads.
Material Handling (MH) Airlock
Interface
Material handling airlock interfaces can be used in facilities that process toxic agents or
similarly hazardous materials. Each MH conveyor airlock has one in gate and one out gate. These
gates are equipped with position switches that send signals to the FCS to indicate the gate
positions (open/closed). When both gates are closed, continuous air purging is required; when
either of the gates is open, sufficient capture velocity is required to prevent backflow. Both
gates should not be open simultaneously.
Each MH airlock is provided with one set of inlet and outlet transfer air assemblies. The inlet
assembly consists of one big and one small on/off isolation damper. The outlet assembly has a
pressure control damper. The FCS opens both inlet isolation dampers and modulates the outlet
pressure control damper to satisfy the design airlock pressure. When one gate is open, the FCS
adjusts the positions of the isolation and pressure control dampers to allow an airflow rate
that satisfies both ventilation and design capture velocity requirements.
Process Exhaust Interface with Exhaust System. Offgas
treatment (OT) process exhausts are discharged from the process blowers into the HVAC exhaust
air inlet headers. The FCS enables OT blower operation only when HVAC exhaust air inlet headers
are maintained at the set negative pressure. Space pressure controllers of the adjacent rooms
modulate the respective dampers in the supply air ducts to balance airflow and keep the
downstream room at set negative pressure.
System Shutdown. The ventilation/filtration system of
toxic areas is in continuous operation. If negative pressure cannot be maintained because of a
loss of essential power off site, the system is automatically shut down via the FCS, and all
normally open TA isolation dampers in the toxic areas of the cascading airflow paths are closed
to prevent toxic vapor migration. The fast-actuating isolation valves remain open to keep the
blast resistant rooms vented to the EAFUs.
Table 1 and
specific product chapters of this Handbook discuss product requirements. Chapter 18 of the 2021
ASHRAE Handbook—Fundamentals provides appropriate heating
and
cooling load calculation techniques.
The roof load is usually the largest solar load on the envelope. Solar loads on walls are often
insignificant, particularly because modern factory buildings tend to be windowless. Insulating
the building walls and roof almost always benefits HVAC cost and performance. Because roof
surfaces can become dirty, use a dark roof color in load calculations.
Internal heat generated by equipment and processes, as well as products, lighting, people, and
utilities, may satisfy heating load requirements. Understanding equipment operating schedules
allows an appropriate diversity factor to be applied to the actual power consumption. Using
connected loads may greatly oversize the system. Processes tend to operate continuously, but may
be shut down on weekends or at night. Heating to some minimal level without equipment and/or
process load should be considered. Consult ASHRAE research project RP-1104 (White and Pahwa
2003) for further information.
The latent load in most industrial facilities is minimal, with people and outdoor air being the
primary contributors, but some processes and products do generate a latent load, which can
dominate the HVAC system design. Mist collectors serving operations that use heated washers or
water-based coolants operating above the targeted space temperature can contribute excessive
latent loading in wet machining operations. Quantifying the latent impact for each source can
help determine which exhaust streams should be discharged outdoors and not recirculated back to
the space. Moisture condensation on cold surfaces must be managed when the latent load becomes
very large.
The cooling load may be dramatically reduced in a work space that takes advantage of temperature
stratification. A stagnant blanket of warm air directly under the roof has little effect on
occupants or equipment as long as it remains undisturbed. Heat sources near the stagnant air
have little effect on the cooling load. When the ceiling or roof is high, 20 to 60% of the heat
energy rises out of the cooling zone, depending on building construction and the temperature of
heat sources. Switching to a return air location near the roof could be cost effective, because
it takes advantage of higher temperatures at the roof.
Supply and return air ducts should be installed as low as practical to avoid mixing the warm
boundary layers in cooling mode. The location of supply air diffusers generally establishes the
stratified air boundary. Spaces with a low occupant-to-floor-area ratio adapt well to using low
quantities of supply air with spot cooling for personnel.
Makeup air provides ventilation and building pressurization. It must be filtered and conditioned
to blend with return air and then distributed to the conditioned space. The quantity of makeup
air must exceed that of the exhaust air to positively pressurize the building. Makeup air
quantity may be varied to accommodate an exhaust system with intermittently operating elements.
Heat and cooling recovery from the exhaust airstream can substantially reduce the outdoor air
load.
Processes requiring an extensive amount of exhaust air should ideally be placed in an area of the
plant provided with minimal heating and no refrigerated air conditioning. Ventilation air may be
required to reduce the quantity of health-threatening fumes, airborne bacteria, fugitive
aerosols, or radioactive particles. Minimum ventilation rates must meet the requirements of
ASHRAE Standard 62.1. Consult the owner’s industrial hygiene
or engineering representative to determine if ventilation rates in excess of this standard may
be warranted.
Economizers can take advantage of ambient conditions and possibly satisfy HVAC loads without
added heating or cooling for much of the year.
Heat is generated by fans that move and pressurize the air. This heat is not felt by the
occupants but does add to the cooling load. The discharge air temperature of a draw-through
cooling arrangement requires cooler air to the fan to accommodate the temperature increase of
air passing through the fan. The increase is more significant in systems with higher discharge
air pressures.
Room-to-room pressurization is an essential method for contamination control. Without pressurization,
surrounding contamination (e.g., particulates, gases, hot or cold air, moisture) can enter the room
by infiltration through doors, windows, cracks, pass-throughs and penetrations for pipes or ducts,
etc. The cleanest room should have the highest room pressure, with decreasing pressure corresponding
to decreasing cleanliness. A differential pressure around 12.5 or 25 Pa is often used.
Pressurization calculations can be performed by using the procedures and charts in Chapter 18 of the
2021 ASHRAE Handbook—Fundamentals, or those in Chapter 5
of
Spitler (2009). Using the charts in Spitler, calculate the building exfiltration at designated
room
pressurization level. Also, in accordance with ASHRAE Standard 62.1,
determine the required outdoor air rate using the actual number of occupants, and identify the
total
exhaust air volume from the building. The sum of exfiltration air volume plus exhaust rate (or
required outdoor air, whichever is greater) is the total ventilation rate under the designated
building pressurization.
To ensure the designated pressurization level, perform a leak test for exterior and interior walls,
partitions, doors, and windows between two adjacent areas with different pressurization levels,
roof, exterior doors and windows, connections between wall and roof, and any building elements
between two areas with different pressurization levels. All major leaks must be eliminated before
HVAC systems start-up.
If pressurization is a critical attribute for maintaining room cleanliness in areas such as plant
process control rooms, computer rooms, etc., then the crack area may need to be estimated and the
pressurization air quantity calculated using an equation such as Equation (11) or (12) in Chapter 54, where the crack is treated
as an orifice and the required airflow is defined as a function of pressure differential. Adequate
design margins should be incorporated in the pressurization system design to allow for building
envelope seal degradation over the structure’s life. If the pressurization is required for
safety or code compliance, make provisions in the design for periodic surveillance and testing.
Particularly in facilities that process toxic agents and other hazardous materials, the
possibility of explosion should be addressed. Blast valve assemblies are installed at points of
air transfer and exhaust air penetrations through the blast-resistant building envelope. An
explosion-generated pressure wave of 103.5 kPa or greater immediately closes the
affected blast valves (spring balanced pressure disks). The inlet and outlet blast valves close
within 10 ms. The fast-actuating dampers are provided in series with the blast valve assemblies.
On receiving alarms from explosion switches located within the affected blast-resistant rooms,
the FCS automatically closes the corresponding fast-actuating isolation dampers, and
fast-actuating isolation dampers powered by the nitrogen system close within 500 ms.
The blast valves are fully automatic in operation. After an explosion, when the room pressure
decreases to the facility-specific set pressure, the FCS opens the exhaust-side fast-acting
dampers first, and then opens those in the transfer air assemblies when the room pressure
decreases to a lower (facility specific) set pressure, to restore the cascading ventilation
path.
Any room involved in an explosion immediately raises all related upstream room pressures due to
the cascading airflow blockage. Based on the room pressure control, the FCS automatically
throttles the respective pressure dampers installed in the supply air ducts to minimize the
pressure upset in the upstream rooms. The airflow blockage may create a ripple effect that
causes the system header pressure controller to slow the fan speeds of the EAFU and supply AHU.
In some rooms, there is a bypass exhaust pathway open to bypass exhaust to allow venting from
rooms to the exhaust header.
7. SYSTEM AND EQUIPMENT SELECTION
Industrial air-conditioning equipment includes heating and cooling sources, air-handling and
air-conditioning apparatus, filters, and an air distribution system. Components should be selected
and the system designed for long life with low maintenance and operating costs conducive to low
life-cycle cost.
Systems may consist of the following:
-
Heating-only in cool climates, where ventilation air provides comfort for workers
-
Air washer systems, where high humidities are desired and where the climate requires
cooling
-
Heating and evaporative cooling, where the climate is dry
-
Heating and mechanical cooling, where temperature and humidity control are required and
other means of cooling are insufficient
All systems include air filtration appropriate to the contaminant control required.
Careful evaluation should determine zones that require temperature control, especially in large,
high-bay areas where the occupied zone is a small portion of space volume. ASHRAE Standard 55 defines the occupied zones as from the floor to 1.8
m high, more than 1 m from exterior walls or fixed conditioning equipment,
and 0.3 m from interior walls.
Floor heating is often desirable in industrial buildings, particularly in large, high-bay
buildings, garages, and assembly areas where workers must be near the floor, or where large or
fluctuating outdoor air loads make maintaining ambient temperature difficult.
Floors may be tempered to 18 to 21°C by embedded hydronic systems, electrical
resistance cables, or warm air ducts as an auxiliary to the main heating system. Heating
elements may be buried deep in the floor (150 to 450 mm) to allow slab warm-up at
off-peak times, thus using the floor mass as heat storage to save energy during periods of high
use.
Floor heating may be the primary or sole heating means, but floor temperatures above
29°C are uncomfortable, so such use should be limited to small, well-insulated
spaces.
Gas, oil, electric, hot-water, or steam-fired unit heaters with centrifugal or propeller fans are
used for spot heating areas and may be arranged in multiples for heating an entire building.
Temperatures can be varied by individual thermostatic control. Unit heaters should be located so
that the discharge (throw) reaches the floor adjacent to and parallel with the outer wall, and
spaced to produce a ring of warm air moving peripherally around the building. In industrial
buildings with heat-producing processes, heat tends to stratify in high-bay areas. In large
buildings, additional heaters should be placed in the interior so that their discharge reaches
the floor to reduce stratification. Downward-discharge unit heaters in high bays and large areas
may have a revolving discharge. Gas- and oil-fired unit heaters should not be used where
corrosive vapors are present. Furthermore, care must be taken to avoid selecting a unit
configuration wherein return air from the space is drawn through the combustion zone of any
direct-fired gas burners, because unintended byproducts of combustion may result.
Ducted heaters include large direct- or indirect-fired heaters, door heaters, and heating and
ventilating units. They usually have centrifugal fans.
Unit heaters and makeup air heaters commonly temper outdoor air that enters buildings through
open doors. Mixing quickly brings the space temperature back to the desired setting after the
door is closed. The makeup air heater should be applied as a door heater in buildings where the
doors are large and open for extended periods, such as doors for large trucks or railroad cars.
Such large doors often use ductwork drops across the top and along both sides of the door, with
slotted diffusers to induce an air-curtain effect.
Unit heaters are also needed in buildings that have considerable leakage or a sizeable negative
pressure. These units help pressurize the door area, mix the incoming cold air, temper it, and
quickly bring the area back to the desired temperature after the door is closed.
Door heating units that resemble a vestibule operate with airflow down across the opening and
recirculated from the bottom, which helps reduce cold drafts across the floor. These units are
effective on high-usage doors under 3 m tall. Additional information on heating is
given in Chapter 27 of the 2020 ASHRAE Handbook—HVAC Systems and
Equipment.
High-intensity gas, oil, or electric infrared heaters transfer heat directly to the occupants,
equipment, and floor in the space without appreciably warming the air, though some air heating
occurs by convection from objects heated by the infrared heaters. These heaters are classified
as either near- or far-infrared heaters, depending on how close the wavelengths they emit are to
visible light. Near-infrared heaters emit a substantial amount of visible light.
Both vented and unvented gas-fired infrared heaters are available as either individual radiant
panels or as a continuous radiant pipe. Pipe-type heaters include burners 4.5 to 9
m apart and an exhaust vent fan at the end of the pipe. Unvented heaters require
exhaust ventilation to remove flue products from the building and to prevent moisture from
collecting on the walls and ceiling.
Infrared heaters are common in the following applications:
-
High-bay buildings, where heaters are usually mounted 3 to 9 m above the
floor, along outer walls, and tilted to direct maximum radiation to the floor. If
the building is poorly insulated, the controlling thermostat should be shielded to
avoid influence from the radiant effect of the walls and the cold walls.
-
Semi-open and outdoor areas, where people can be comfortably heated directly and
objects can be heated to avoid condensation.
-
Loading docks, where snow and ice can be controlled by strategic placement of
near-infrared heaters.
Additional information on both electric and gas infrared heating is given in Chapter 16 of the
2020 ASHRAE Handbook—HVAC Systems and Equipment.
Common cooling systems include refrigeration equipment, evaporative coolers, and high-velocity
ventilation air.
For manufacturing operations, particularly in heavy industry where mechanical cooling cannot be
economically justified, evaporative cooling systems often provide good working conditions, as
discussed in Chapter 41 of the 2020 ASHRAE Handbook—HVAC Systems and
Equipment. If the operation requires heavy physical work, spot cooling by
ventilation,
evaporative coolers, or refrigerated air can be used. To minimize summer discomfort, high outdoor
ventilation rates may be adequate in some hot-process areas. A mechanical air supply with good
distribution is needed in all these operations.
Refrigerated Cooling Systems
The most commonly used refrigerated cooling systems are roof-mounted, direct-expansion packaged
units. Larger systems may use chilled water distributed to air-handling units.
Central system condenser water rejects heat through a cooling tower. Refrigerated heat recovery
is particularly advantageous in buildings with simultaneous need to heat exterior spaces and
cool interior spaces.
Mechanical cooling equipment should be selected in multiple units. This lets the equipment match
its response to fluctuations in the load and allows maintenance during off-peak operation
periods. Packaged refrigeration equipment commonly uses positive-displacement (reciprocating,
scroll, or screw) compressors with air-cooled condensers. When equipment is on the roof, the
condensing temperature may be affected by warm ambient air, often 5 to 10 K higher
than design outdoor air temperature. ASHRAE Standard 15 provides
rules for the type and quantity of refrigerant in direct air-to-refrigerant exchangers.
Desiccant-based systems should be considered for processes that require dew points below
10°C (e.g., pharmaceutical processing).
Evaporative Cooling Systems
Evaporative cooling systems may be direct or indirect evaporative coolers or air washers.
Evaporative coolers have water sprayed directly on wet surfaces through which air passes. Any
excess water drains off. Air washers recirculate water, and the air flows through a heavily
misted area. Water atomized in the airstream evaporates, cooling the air. For either type, using
refrigerated water simultaneously cools and dehumidifies the air. For spaces that require an air
washer and high relative humidities (e.g., tobacco and textile processing areas), heat provided
to the sump should provide sufficient energy for humidification beyond that recovered in the
return airstream.
Temperature and humidity of the exit airstream may be controlled by varying the temperature of
the chilled water and reheat coil and by varying the quantity of air passing through the reheat
coil with a dew-point thermostat.
It may be necessary to filter air entering the evaporative cooler to ensure that dust or lint
does not accumulate and clog the nozzles or evaporating pads. Chemical treatment of the water
may be necessary to prevent mineral build-up or biological growth on the pads or in the pans.
10. AIR FILTRATION SYSTEMS
Air filtration systems remove contaminants from the building supply or exhaust airstreams. Supply air
filtration at the equipment intake removes particulate contamination that may foul heat exchange
surfaces, contaminant products, or present a health hazard to people, animals, or plants. Gaseous
contaminants must sometimes be removed to prevent exposing personnel to odors or health-threatening
fumes. Return air with a significant potential for carrying contaminants should be recirculated only
if it can be filtered enough to minimize personnel exposure. Return air should be exhausted if
monitoring and contaminant control cannot be ensured.
The supply filtration system usually includes collection media or a filter, a media-retaining device
or filter frame, and a filter housing or plenum. For more on filtration systems, see Chapter 29 of
the 2020 ASHRAE Handbook—HVAC Systems and Equipment.
Exhaust Air Filtration Systems
Exhaust air systems are either (1) general systems that remove air from large spaces or (2) local
systems that capture aerosols, heat, or gases at specific locations in a room and transport them
so they can be collected, inactivated, and safely discharged to the atmosphere. Air in a general
system usually requires minimal or no treatment before being discharged to the atmosphere. Air
from local exhaust systems can sometimes be safely discharged to the atmosphere, but may require
contaminant removal before being discharged. Exhausted air must meet appropriate air quality
standards when defined as a release point based on plant air permitting requirements. Chapters 31 and 32 of this
volume and Chapter 30 of the 2020 ASHRAE Handbook—HVAC Systems and
Equipment have more information on industrial ventilation and exhaust
systems.
In exhaust air emission control, fabric-bag filters, glass-fiber filters, venturi scrubbers, and
electrostatic precipitators all collect particles. Packed-bed or sieve towers can absorb toxic
gases. Activated carbon columns or beds, often with oxidizing agents, are frequently used to
absorb toxic or odorous organics and radioactive gases.
Outdoor air intakes should be carefully located to avoid recirculating contaminated exhaust air.
Wind direction, building shape, and location of effluent source strongly influence concentration
patterns.
Air patterns from wind flowing over buildings are discussed in Chapter 24 of the 2021 ASHRAE Handbook—Fundamentals. The leading edge of the
roof
interrupts smooth airflow, reducing air pressure at the roof and on the lee side. Exhaust
air
must be discharged through either a vertical stack terminating above the building
turbulent-air
boundary or a shorter stack with a high enough discharge velocity to project the effluent
through the air boundary into the undisturbed air passing over the building. The high
discharge
prevents fume damage to both the roof and roof-mounted equipment, and keeps fumes away from
building air intakes. A high vertical stack is the safest, simplest solution to fume
dispersal.
In addition to maintaining thermal conditions, air-conditioning systems should control
contaminant levels to provide a safe and healthy environment, good housekeeping, and quality
control for the processes. Contaminants may include gases, fumes, mists, or airborne particulate
matter. They may be produced by a process in the building or contained in the outdoor air.
Contamination can be controlled by preventing the release of aerosols or gases into the room and
by diluting room air contaminants. If the process cannot be enclosed, it is best to capture
aerosols and gases near their source with a local exhaust system that includes a hood or
enclosure, ducts, fan, motor, and exhaust stack.
Dilution controls contamination in many applications but may not provide uniform safety for
personnel. High local concentrations of contaminants can exist despite a high overall dilution
rate.
An exhaust system draws a contaminant away from its source and removes it from the space. An exhaust
hood surrounding the point of generation contains the contaminant as much as is practical. The
contaminant is transported through ductwork from the space, cleaned as required, and exhausted to
the atmosphere. The hood inlet air quantity is established by the velocities required to convey the
airborne contaminant. Chapter 33 has more
information on local exhaust systems.
Design values for average and minimum face velocities are a function of the characteristics of the
most hazardous material the hood is expected to handle. Minimum values may be prescribed in codes
for exhaust systems. Contaminants with greater mass may require higher face velocities for control.
Design face velocities should be set carefully: too high a velocity can be as hazardous as one too
low. Refer to ACGIH (2016) and ASHRAE Standard 110 for more information.
Exhaust ductwork should be sized to provide velocities high enough to keep contaminants in
suspension. Velocities should exceed the settling velocities for the expected particle size
distribution.
Selection of materials and construction of exhaust ductwork and fans depend on the nature of the
contaminant, ambient temperature, lengths and arrangement of ducts, method of hood fan operation,
and flame and smoke spread ratings. Exhausts containing acids, alkalis, solvents, or oils should
address corrosion, dissolution, and melting.
Condensation in ferrous metal ducts may contribute to corrosion. Consider the dew point of process
gases with respect to the surrounding ambient temperature. Condensation can be managed by reducing
the dew point of the exhaust stream, by vapor barriers, or by using thermal insulation.
12. OPERATION AND MAINTENANCE
Equipment room layout should provide space for cleaning, servicing, and replacing components quickly
to minimize system outages. Maintenance of refrigeration and heat rejection equipment is essential
for proper performance without energy waste. Maintenance includes changing system filters
periodically. Industrial applications are dirty, so proper selection of filters, careful
installation to avoid air bypassing the filter, and prudent filter changing to prevent overloading
and blowout are required. Dirt lodging on the tips of forward-curved fan blades appreciably reduces
air-handling capacity. Fan and motor bearings require lubrication, and fan belts need periodic
inspection. Direct- and indirect-fired heaters should be inspected annually. Steam and hot-water
heaters have fewer maintenance requirements than comparable equipment with gas or oil burners.
For system compatibility, water treatment is essential. Air washers and cooling towers should not be
operated unless the water is properly treated.
13. HEAT RECOVERY AND ENERGY
CONSERVATION
The process industry often presents opportunities to recover heat from the exhaust airstream for use
in preconditioning makeup air. Extreme care must be taken to ensure compatibility of heat exchanger
components and materials with contaminants often found in exhaust streams. For example, brewery
spaces are held between 1.7 and 10°C. Exhaust air passes over a heat recovery wheel
to precondition outdoor makeup air, which in turn controls the level of carbon dioxide
contamination. Coated aluminum heat recovery wheels can be subject to premature failure because of
caustic cleaning materials conveyed in the exhaust system.
Additional consideration should be given to the assessment of risk associated with the heat recovery
strategy. Frequently, downtime in large industrial facilities can exceed millions of dollars per
hour. Costs associated with failure of a heat recovery device can easily overcome savings in energy
costs if the result is a facility shutdown.
Control systems for industrial processes and air-conditioning systems differ from commercial direct
digital control (DDC) systems in important ways. Modern industrial control systems fall into three
categories:
-
Programmable logic controller (PLC) systems.
These systems are chosen for industrial environments because of their inherent
robustness and speed. They are rated to operate in environments of
50°C, as opposed to 40°C for DDC systems. Also,
because the controller does not look up point information from a central database, the
program scan speed is much greater: a total program scan time of less than 0.1 s is not
unusual. Local display screens are available for field panel mounting; however, one of
the following two systems is required to provide overall plantwide data gathering and
reporting.
-
Distributed control systems (DCS). Like
commercial DDC systems, DCS systems are defined as shared logic controllers as opposed
to programmable logic controllers. A shared logic controller shares the resources a
common database of point names to provide point attribute data such as units (% rh,
kPa, etc.), point range (0 to 100% rh, 0 to 690 kPa, etc.),
logical point name, and software address. This information is shared across all
controllers in a given network of controllers and then reported to the user through the
graphical user interface (GUI). DCS systems can provide an embedded GUI like DDC systems
do, or can work seamlessly with a third-party SCADA system.
-
Supervisory control and data acquisition (SCADA)
systems. SCADA systems are typically overlays that acquire and
store data from subordinate DCS, PLC, or other systems. They provide the GUI and display
operating system parameters. By contrast, commercial DDC or building management systems
(BMS) have the graphic engine and data acquisition and storage system embedded into the
base operating system. Industrial requirements typically preclude DDC systems to act as
a SCADA system because of their limited data communication networks and inability to
reliably handle large numbers (>10,000) of input and output points in a given system.
Industrial controllers can be installed, configured, and/or maintained by third-party providers
(known as system integrators) or by the manufacturer
themselves. They have open communication protocols and exchange information over various network
protocols such as Modbus (North America) or Profibus (EU). These protocols allow communication
between different brands of controllers and the overall network, with BACnet®
capability for occasional integration with commercial DDC system where deemed necessary. Industrial
systems also allow Ethernet-based protocol (TCP/IP) for data exchange in high-speed networks as well
as remote Internet-based monitoring and control.
Industrial control systems are documented differently than commercial-based DDC systems. The American
National Standards Institute (ANSI), in cooperation with International Society of Measurement and
Control (ISA), established a standard that defines how engineering documents are prepared (e.g.,
process and instrumentation diagrams [P&IDs], instrument naming or tagging convention).
Commercial systems generally are documented using standards defined by the system manufacturer, who
installs and maintains the systems, and their technicians can operate across several facilities or
in different cities.
Industrial instrumentation is also quite different from commercial DDC systems. Instruments are
typically in housings listed for hazardous environments that also provide excellent protection from
the moisture, dust, and dirt frequently found in an industrial environment. Signal types are usually
4 to 20 mA over the range of 0 to 100% of the transmitter span. Hazardous locations use instruments
listed specifically for the hazard division and group. Intrinsic safety barriers provide a level of
protection by limiting the amount of power consumed by these devices to 1 W or less.
15. LIFE AND PROPERTY SAFETY
Human life and property safety must be thoroughly considered in all types of industrial project
design, construction, installation, start-up, testing, operation, and maintenance. The life and
property safety concern should include (but not be limited to) hazards generated in the property and
related prevention, effective fire and hazardous gas detection and alarm systems, active fire
protection systems, room-to-room pressurization and smoke control, homeland security and emergency
response plans, etc. Refer to related NFPA and ACGIH publications for detailed regulations.
Toxic Agent/Hazardous Materials Processing Facility
Fire. When the fire alarm control panel (FACP) receives
alarm signals from local smoke/heat detectors, it sends signals to shut off the smoke/fire dampers
(BDs) in the affected fire zone. The FACP also sends an alarm signal to the FCS. The position switch
from each BD sends a feedback signal to FCS confirming that the BD has been fully closed; otherwise,
a fault alarm is activated at the FCS. Due to airflow blockage, the cascading system upstream room
pressure increases, and downstream room pressure decreases further. To minimize room pressure
upsets, the FCS automatically throttles the upstream supply air pressure control dampers and
downstream exhaust air pressure control dampers.
During the pressure surge transition, the cascading system pressures may rise at the supply air
plenum and become more negative at the exhaust air inlet headers. FCS pressure feedback control
automatically reduces the fan speed of the AHUs and EAFUs accordingly. If pressure surges are
significant and occur faster than the FCS pressure control response, pressure and vacuum relief
dampers in the supply and exhaust headers automatically open to protect ductwork from damage.
After the fire has been cleared, the smoke/fire dampers are manually reset to the open position from
the FACP. Bypass exhausts are provided within fire zones and located strategically to mitigate
pressure excursion resulting from a fire in critical process rooms. When the bypass mode is
initiated, FCS closes the inlet transfer air isolation dampers to suppress fire spread, which
prevents heat and smoke damage to the EAFUs; activates the bypass exhaust; and places pressure
controllers into automatic pressure control mode to minimize pressure surge and airflow impact to
surrounding rooms.
Loss of Power. During loss of off-site power, essential
power is provided to EAFUs and AHUs by the dedicated generator and the standby generators to
maintain the toxic areas at slight negative pressure relative to ambient to prevent toxic vapor
escaping. The adjustable-speed drives (ASDs) of the fans of EAFUs and AHUs are programmed to allow
fast ramp-up when power is restored. If a dedicated generator starts and standby generators fail,
the FCS continuously monitors and controls the cascading ventilation system to maintain slight
negative pressure with reduced flows. When all the generators fail to start, and the total exhaust
airflow rate drops to 15% of the system design capacity, the FCS starts closing all TA isolation
dampers to prevent toxic vapor migration from highly toxic areas to areas of lower concentrations.
Equalizing System Flows. Equalizing the flow rates of all
the AHUs and EAFUs provides smooth operation of the HVAC supply and exhaust system in a cascade
ventilation system to maintain varying differential pressures in the space. To accomplish this, an
input from the pressure differential value set in the supply plenum and exhaust duct header are
provided to the respective flow-indicating controllers (FICs) of the facility AHUs or EAFUs to
maintain pressure at the supply plenum and the exhaust duct header. This input value going to the
FICs, which is scaled from pressure differential value to flow value, corresponds to the respective
supply plenum or the exhaust duct header pressure value. The outputs of the FICs go to the
respective ASDs that control fan speed to maintain the supply plenum or the exhaust duct header
pressure while equalizing the flow rates of all the AHUs or EAFUs.
Starting System Offline Unit. While starting the offline
unit and shutting down the online unit, the oncoming AHU or EAFU is given a signal by the FCS that
can sometimes cause flow through the unit to overshoot before stabilizing at the design flow rate,
activating high-flow alarms. This can be prevented with following steps:
-
The FCS provides an initial tracking signal for the FIC of the AHU or EAFU during unit
startup.
-
The initial tracking signal is calculated using the average of the FIC outputs of other
operating units. This lower initial tracking signal prevents the oncoming unit from
overshooting and reaching the high flow alarm value.
-
The tracking mode will be released after the oncoming unit’s FIC output remains
constant for set time as determined during testing.
Once the oncoming EAFU or AHU flow is stabilized, then the FIC will transition from the startup
control mode to the operating control mode.
Several types of HVAC commissioning processes are used for industrial HVAC projects: (1) overall HVAC
project commissioning, (2) construction HVAC project commissioning, and (3) existing-building HVAC
commissioning (retrocommissioning). The process described
here applies to both new construction and major renovations.
For new construction, commissioning should start at the project’s inception during the
predesign phase, and continue through design, construction, acceptance, training, operation,
maintenance, and postacceptance.
The owner should retain an HVAC commissioning authority (CA) at the very beginning of the predesign
phase. The CA develops the scope of the commissioning and reviews the design intent during predesign
to ensure the project accommodates the commissioning process. The CA also coordinates with the
owner, design engineer, and HVAC contractor during preparation of project design and construction
documents; this includes the overall project execution schedule, preparation and issue of
commissioning and construction specifications, and review of contractor submittals. This paves the
way for commissioning, and the CA continues to carry out and complete the implementation of the
planning commissioning process.
Participants include the start-up personnel listed during start up, the test and balance company, the
process operators, the owner’s project authorities, and the commissioning personnel.
Commissioning documents include the following:
-
Certificates and warranties of system completion, along with a complete set of as-built
drawings submitted by mechanical, electrical, plumbing, control, and fire protection
contractors.
-
If available, all major equipment installation, operation, and maintenance (IOM) manuals
from equipment manufacturers.
-
Records of significant problems and solutions that occurred during start-up and testing.
-
Certified system test and balance reports, including verified major equipment models and
capacities, and tested performance values conforming to system criteria.
-
A complete room-to-room pressurization map submitted by the test and balance company.
-
A control system IOM submitted by the control contractor.
-
When applicable, a certificate of as-built cleanroom cleanliness. The report should be
based on testing when the cleanroom facility is complete and all services are connected
and functional, but without equipment and operating personnel in the cleanroom.
-
If the contract scope requires, a certificate of cleanroom cleanliness with process
running and with operating personnel in the facility.
-
A commissioning report signed by all attendees.
Commissioning requirements for industrial air-conditioning systems (particularly central heating and
cooling equipment such as chillers, boilers, air compressors, etc., or nonprocess air-handling
systems) often can follow the procedures outlined in ASHRAE Guidelines 0
and 1.1, which use statistical evaluations to define the scope of commissioning activities. Most
industrial applications, however, use full commissioning of each point instead of statistical
evaluation, because of the process requirements for reliability and the basic functional
requirements.
In facilities regulated by government agencies, qualification (or validation) of the air-conditioning systems may be
required. In these cases, use the appropriate government and industry-specific guidelines instead of
ASHRAE Guidelines 0 and 1.1. Qualification follows a more rigorous set
of standards for acceptance than commercial commissioning:
-
Risk assessment determines the level of
qualification that a given system should undergo. It considers the severity the risk
presents (e.g., loss of life or of the system) and the likelihood of occurrence (e.g.,
once during system life, once a year). The highest risks are those that have the
greatest severity as well as the most likely occurrence. In those cases, the
qualification requirements are the highest.
-
Life-cycle assessment is most often used in
industrial control systems. Required documentation typically consists of specifications
for user requirements, functionality, and design, and the system is qualified under an
installation qualification to verify the design specification. An operational
qualification verifies the requirements of the functional specification, and the
performance qualification verifies the requirements of the user requirement
specification.
-
Testing plans and strategies should reflect
the results of the risk assessment and life-cycle assessment. The plans and strategies
should also address the resources required to conduct the qualification, the
documentation to be developed, and the appropriate owner team to accept the results.
Most importantly, it defines the procedure to be followed when a discrepancy is found.
Testing documentation is developed to qualify the system so it can pass an audit by the regulatory
agency or a third party retained by the owner.
For more information on commissioning, see Chapter 44 and ASHRAE Standard 202-2018.