Because task/ambient design requires a high degree of individual control, it is not covered in this
chapter; see Chapter 20 of the 2021 ASHRAE Handbook—Fundamentals for
details. Guidance is also provided by ASHRAE (2013).
2. FULLY MIXED AIR DISTRIBUTION
In mixed air systems, high-velocity supply jets from air outlets maintain comfort by mixing room air with supply air. This air mixing,
heat transfer, and resultant velocity reduction should occur outside the occupied zone. Occupant
comfort is maintained not directly by motion of air from outlets, but from secondary air motion from
mixing in the unoccupied zone. Comfort is maximized when uniform temperature distribution and
average room air velocities of less than 0.25 m/s are maintained in the occupied zone.
Maintaining average velocities less than 0.25 m/s in the occupied zone is often
overlooked by designers, but is critical to maintaining comfort. The outlet’s selection,
location, supply air volume, discharge velocity, and air temperature differential determine the
resulting air motion in the occupied zone.
Mixed systems generally provide comfort by entraining room air into discharge jets located
outside occupied zones, mixing supply and room air. Ideally, these systems generate low-velocity
air motion (less than 0.25 m/s) throughout the occupied zone to provide uniform
temperature gradients and velocities. Proper selection of an air outlet is critical for proper
air distribution; improper selection can result in room air stagnation, unacceptable temperature
gradients, and unacceptable velocities in the occupied zone, possibly leading to occupant
discomfort or poor air quality.
The location of a discharge jet relative to surrounding surfaces is important. Discharge jets
attach to parallel surfaces, given sufficient velocity and proximity. When a jet is attached,
the throw increases by about 30% over a jet discharged in an open area. This difference is
important when selecting an air outlet. For detailed discussion of the surface effect on
discharge jets, see Chapter 20 of the 2021
ASHRAE
Handbook—Fundamentals.
Space Ventilation and Contaminant
Removal
These systems are intended to maintain acceptable indoor air quality by mixing supply and room
air (dilution ventilation). Supply air is typically a conditioned mixture of ventilation and
recirculated air. Outlet type and discharge velocity determine the mixing rate of the space and
should be a design consideration. The room’s return or exhaust air carries away diluted
air contaminants. Space air ventilation rates are mandated under ASHRAE Standard 62.1, but supply airflow rates are often higher because of
thermal loads.
Benefits of fully mixed systems include the following:
-
Most office applications can use lower supply dry-bulb temperatures, for smaller
ductwork and lower supply air quantities.
-
Air can be supplied at a lower moisture content, possibly eliminating the need for a
more complex humidity control system.
-
Vertical temperature gradients are lower for cooling applications with high internal
heat gains, which may improve thermal comfort.
-
Mixed systems are the most common design for air distribution systems, because
designers and installers are familiar with the required system components and
installation.
Limitations of mixed systems include the following:
-
Partial-load operation in variable-air-volume (VAV) systems may reduce outlet
velocities, reducing room air mixing and compromising thermal comfort. Designers
should consider this when selecting outlets.
-
Cooling and heating with the same ceiling or high-sidewall diffuser may cause
inadequate performance in heating mode and/or excessive velocity in cooling mode.
-
Ceilings more than 4 m high may require special design considerations to
provide acceptable comfort in the occupied zone. Care should be taken to select the
proper outlet for these applications.
-
Because mixed systems typically use high-velocity jets of air, any obstructions in
the space (e.g., bookshelves, wall partitions, furniture) can reduce comfort.
-
Lighter-than-air contaminants are uniformly mixed in the space and typically result
in higher contaminant concentrations, which may compromise indoor air quality.
Mixed air systems typically use either ceiling or sidewall outlets discharging air horizontally,
or floor- or sill-mounted outlets discharging air vertically. They are the most common method of
air distribution.
Inlet Conditions to Air Outlets
The way an airstream approaches an outlet is important. For good air diffusion, the inlet
configuration should create a uniform discharge velocity profile from the outlet, or the outlet
may not perform as intended.
The outlet usually cannot correct effects of improper duct approach. Many sidewall outlets are
installed either at the end of vertical ducts or in the side of horizontal ducts, and most
ceiling outlets are attached either directly to the bottom of horizontal ducts or to special
vertical takeoff ducts that connect the outlet with the horizontal duct. In all these cases,
devices for directing and equalizing the airflow may be necessary for proper direction and
diffusion of the air.
ASHRAE research project RP-1335 (Landsberger et al. 2011) determined that a wide-open damper
installed in the neck of a diffuser could add up to 8 NC to the cataloged NC value, depending on
diffuser and damper types. Significantly closed balancing dampers can add more than 10 NC,
depending on duct pressure and how far upstream it is installed. Table 2 gives forward throw
asymmetries for various diffuser types, and Figure 2
compares the total pressure ratio of a diffuser with no damper versus a neck-mounted damper that
is increasingly throttled.
Effects of Typical Field
Installations on Common Ceiling Diffusers.
Ceiling air outlets are tested using ideal installation conditions described in ASHRAE Standard 70: a minimum of three straight equivalent duct diameters
before the diffuser inlet.
Field installations are often not ideal because of ceiling plenum limitations, architectural
design, structural supports of the building, etc. ASHRAE research project RP-1335 (Landsberger
et al. 2011) developed some useful application data that can be used by design engineers to
predict throw, pressure drop, and sound caused by non-ideal installations. Tables 2, 3, and 4 give a
general summary of application data from RP-1335. The multipliers provided in these tables may
be applied to diffuser performance data measured from tests compliant with ASHRAE Standard 70-2006.
Space Temperature Gradients and
Airflow Rates
A fully mixed system creates homogeneous thermal conditions throughout the space. As such,
thermal gradients should not exist in the occupied zone. Improper selection, sizing, or
placement may prevent full mixing and can result in stagnant areas, or having high-velocity air
entering the occupied zone.
Supply airflow requirements to satisfy space sensible heat gains or losses are inversely
proportional to the temperature difference between supply and return air. The following equation
can be used to calculate space airflow requirements (at standard conditions):
where
| Q = required supply airflow rate to meet sensible load,
L/s
|
| qs = net sensible heat gain in the space,
W
|
| tr = return or exhaust air temperature,
°C
|
| ts = supply air temperature, °C
|
For fully mixed systems with conventional ceiling heights, the return (or exhaust) and room air
temperatures are the same; for example, a room with a set-point temperature of
24°C has, on average, a 24°C return or exhaust air
temperature.
The objective of air diffusion is to create the proper combination of room air temperature,
humidity, and air motion to provide thermal comfort and acceptable indoor environmental quality
in the occupied zone. There are three recommended methods of selecting outlets for mixed air
systems using manufacturers’ data:
-
By appearance, flow rate, and sound data
-
By isovels (lines of constant velocity) and mapping
-
By comfort criteria
These selection methods are not meant to be independent. It is the designer’s choice as to
which to start with, but it is recommended that at least two methods be used for any design.
Variation from accepted thermal limits (ASHRAE Standard 55), lack of
uniform thermal conditions in the space, or excessive fluctuation of conditions in one part of
the space may produce discomfort. Thermal discomfort can also arise from any of the following
conditions:
-
Excessive air motion (draft)
-
Excessive room air temperature stratification (horizontal, vertical, or both)
-
Failure to deliver or distribute air according to load requirements at different
locations
-
Rapid fluctuation of room temperature
Selection by Appearance, Flow Rate, and Sound Data.
For a given appearance, flow rate, pressure drop, and sound level criteria, designers can select
outlets from manufacturers’ catalogs, using the following steps:
-
Determine air volumetric flow requirements based on load and room size. For VAV
systems, evaluation should include the range of flow rates from minimum occupied to
design load. Consider both cooling and heating mode requirements.
-
Determine acceptable outlet noise criterion (NC); consult Chapter 49 of this
volume, or Chapter 8 in the 2021
ASHRAE
Handbook—Fundamentals.
-
Locate a range of products from manufacturers’ catalogs that meet the airflow
and NC requirements. Multiple outlets in a space at the same cataloged NC, and other
design considerations, may result in actual sound levels greater than cataloged
values. Manufacturers’ data are obtained using ideal inlet conditions, and may
vary from field installations. From experience,
-
For identical outlets 3 m or more apart, the cataloged NC
rating applies.
-
Identical outlets within 3 m of each other add no more than
3 dB to the sound pressure level.
-
For continuous linear outlets, only the sound produced by the closest
3 m need be considered.
-
Select air terminals from manufacturers’ catalogs that meet aesthetic and
physical needs.
Although these selections may meet the sound requirements for a project, the results do not fully
address occupant comfort. Without evaluating the throw of the outlets or room air mixing, this
selection method may result in excessive air velocities in the occupied zone, or limited mixing
and resultant stagnation. It is recommended that the designer consider selection by isovel
mapping or by comfort criteria in addition to selection by appearance, flow rate, and sound
data. Either of these methods addresses resulting air motion in the occupied zone and occupant
comfort.
Selection by Isovels and Mapping. Using
manufacturers’ catalog throw data, a designer can predict the path of an outlet’s
discharge jet. Most manufacturers’ catalogs list the distance a jet travels to reach a
terminal velocity of 0.75 to 0.25 m/s. With this information, the designer can map
the path of the discharge jet for a given outlet. This evaluation can prevent problems such as
excessively high air velocities in the occupied zone, or stagnation in a given area. Note that
most manufacturers’ throw data are based on isothermal supply air; the supply jet
temperature is equal to the room air temperature. When using this mapping method, consider the
positive or negative buoyancy of nonisothermal (heated or cooled) supply air. In both heating
and cooling, a discharge jet should travel the distance shown in the catalog to a terminal
velocity of 0.75 m/s without much influence from buoyancy. When evaluating a jet at
lower terminal velocities (e.g., 0.5 to 0.25 m/s), consider buoyancy’s effect
on the distance the jet will travel.
Horizontal Throw. A cooled confined air jet projecting along a
horizontal surface travels a shorter distance than the equivalent volumetric isothermal air jet
traveling the same path. If an outlet is selected so that the cooled horizontal jet does not
have enough velocity to reach a vertical surface, the jet can separate from the horizontal
surface and project down into the occupied zone, causing drafts and discomfort.
A heated confined air jet projecting along a horizontal surface travels farther than the
equivalent volumetric isothermal jet traveling the same path. If an outlet is selected so that
the heated, horizontal jet does not have enough velocity to reach a vertical surface, the jet
can pool at the ceiling level, causing stagnation (no mixing) within the occupied space and
resulting in high levels of contaminants, thermal stratification, and discomfort.
In a free jet scenario, expect similar results as for a confined jet, but if isothermal
performance is based on confined jet installation, a 30% reduction in throw length from
isothermal performance will occur, along with buoyancy effects.
Vertical Throw. A cooled air jet projecting vertically upward travels
a shorter distance than the equivalent volumetric isothermal air jet traveling the same path. A
heated air jet projecting upward travels farther than the equivalent volumetric isothermal air
jet traveling the same path. For both cooled and heated air jets, the opposite is true for
downward projection.
Mapping with acoustical selection. Combining selection by isovels
allows discharge jet location and intensity in a space to be predicted. Outlet selection should
be evaluated at the space’s typical operating points (i.e., maximum heating and cooling,
and minimum heating and cooling).
The following steps may be used:
-
Identify the occupied zone for the space, as defined by ASHRAE Standard 55-2020.
-
Select outlet(s) that meet design NC, pressure drop, and flow rate requirements.
Identify the supply jet location using cataloged throw data.
-
Evaluate air jet mapping to ensure terminal velocities in the occupied zone do not
exceed 0.25 m/s.
-
For overhead heating applications, Δt ×
8.5 K (see Chapter
20 of the 2021 ASHRAE
Handbook—Fundamentals), evaluate the diagram to ensure that
jet
velocities 1.4 m from the floor are at least 0.75 m/s.
Other design considerations include the following:
-
In multiple-outlet applications, jets should not collide to cause a downward
projection of air resulting in velocities greater than 0.25 m/s in
the occupied zone.
-
For VAV applications, consider both minimum and maximum flow conditions.
Example 1.
For a 6 by 12 m zone, with a 2.7 m ceiling, with uniform
loading of 31.5 W/m2 or 700 W, and air volumetric flow of
5 L/s per square metre or 378 L/s for a dual-outlet configuration, use
isovel mapping to select an appropriate diffuser option that meets a sound criteria of
NC 35.
Solution:
-
The occupied zone is defined as a height of 1.8 m off the floor,
0.3 m from interior walls, and 1 m from exterior
walls.
See ASHRAE Standard 55 for the most current
definition of occupied zone.
-
One manufacturer suggests that a single 0.6 × 0.6 m plaque
diffuser with a0.2 m inlet at 189 L/s yields an NC
30 and an isothermal throw of 3.6 m at a terminal velocity of
0.25 m/s.
-
With an air jet characteristic length of 3 m, and 0.9
m between ceiling and start of the occupied zone, the velocity of
the colliding jets can be assumed to not exceed 0.25 m/s in the
occupied zone. Verify that resulting diffuser pressure drop and aesthetics
meet requirements.
-
If one or more of the walls are exterior in this example, even with
additional throw length due to warmer supply air, additional air volume may
be required to meet 1.4 m above the floor at 0.75
m/s.
Evaluate other diffuser types for similar or better performance criteria.
Selection by Comfort Criteria T0.25/L. Selection by isovels and mapping is effective at predicting the path of the discharge jet from
an outlet and evaluating resultant occupant comfort. However, there is an established method to
quantify occupant comfort for both cooling and heating conditions, based on space dimensions and
isothermal catalog throw data. This method can be used to predict a space’s resulting air
diffusion performance index (ADPI).
The comfort criteria T0.25/L method was developed to predict occupant comfort using
manufacturers’ isothermal catalog throw data (T, usually for
0.25 m/s terminal velocity) and the dimensions available for throw L on the plan view of a mechanical drawing. By using the ratio of
T0.25/L, the designer can predict the level of comfort with a single rating
number, ADPI, which can provide further information about the comfort level in a space for
results obtained from the NC and mapping selection methods.
Air Distribution Performance
Index (ADPI). The air distribution performance index was developed as a way to
quantify the comfort level in heating and cooling for a space conditioned by a mixed air system.
ADPI uses the effective draft temperature collected at an array of points taken within the
occupied zone to predict comfort. ADPI is the percentage of points in a space where the
effective draft temperature is between –1.7 and +1.1 K for cooling and
–2.2 and +2 K for heating. The acceptable air velocity is less than
0.36 m/s for heating and cooling. In addition, the acceptable vertical temperature
gradient should be less than 3 K/m. High ADPI values generally correlate to high
space thermal comfort levels with the maximum obtainable value of 100. Selecting outlets to
provide a minimum ADPI value of 80 generally results in a well-mixed space.
The effective draft temperature provides a quantifiable indication of comfort at a discrete point
in a space by combining the physiological effects of air temperature and air motion on a human
body. The effective draft temperature ted (the difference
in temperature between any point in the occupied zone and the control condition) can be
calculated using the following equation for the cooling condition, proposed by Rydberg and
Norback (1949) and modified by Straub (Straub and Chen 1957; Straub et al. 1956) in discussion
of a paper by Koestel and Tuve (1955):
where
| ted =effective draft temperature, K
|
| tx =local airstream dry-bulb temperature,
°C
|
| tc =average (control) room dry-bulb temperature,
°C
|
| Vx =local airstream centerline velocity,
m/s
|
Liu and Novoselac (2015) developed an effective draft temperature ted for the heating condition based on predicted mean vote
(PMV) model specified in ASHRAE Standard 55. A high vertical
temperature gradient occurs during heating when throws are insufficient, resulting in stagnation
of supply air and unacceptable ventilation to the breathing zone.
where
| ted =effective draft temperature, K
|
| tx =local airstream dry-bulb temperature,
°C
|
| tc =average (control) room dry-bulb temperature,
°C
|
| Vx =local airstream centerline velocity,
m/s
|
T0.25/L Selection
Method. This method uses the ratio of cataloged isothermal throw data at 0.25
m/s to the characteristic length for a given device (Table
5).
Each type of diffuser has different performance characteristics and therefore may provide a
different ADPI value for the same conditions. Calculating T0.25/L for a given
outlet can predict the level of comfort for a space. Using Tables
6A and 6B,
the designer can optimize not only the type of diffuser to select but also the size and capacity
for both cooling and heating. The maximum ADPI listed in Tables
6A and 6B
reflects the optimal value expected for the given outlet type and location. The maximum ADPI
T50/L represents the ratio
corresponding with that maximum ADPI value.
Using T0.25/L helps designers maximize space cooling comfort; however, this method
is not meant to, nor may it be practical to, evaluate T0.25/L values for each outlet on a project. The design guidelines in Tables
6A and 6B
were developed from laboratory experiments in chambers lower than 3 m, with test
diffusers symmetrically distributed (Liu and Novoselac 2014; Liu et al. 2016; Miller and Nash
1971). Therefore, attention should be paid to ceiling height of buildings (e.g., airport
terminals) or highly asymmetric diffuser layouts.
Design Procedures. T0.25/L can be used as a general tool to evaluate cooling comfort levels in
a space, at the beginning of design to optimize outlet selection (as shown in the following
steps), or at the end of the process to predict comfort levels in spaces designed using NC and
mapping methods:
-
Determine air volumetric flow requirements based on load and room size. For VAV
systems, evaluation should include both minimum occupied and maximum design flow
rates.
-
Select tentative diffuser type and location in room.
-
Determine room’s characteristic length L (Table
5).
-
Select recommended T0.25/L ratio from Tables
6A and 6B.
-
Calculate throw distance T0.25 by multiplying
recommended T0.25/L ratio from Tables
6A and 6B
by available length L.
-
Locate appropriate outlet size from manufacturer’s catalog.
-
Ensure that this outlet meets other imposed specifications (e.g., noise, static
pressure loss).
Example 2.
For a 6 by 3.7 m room, with 2.7 m ceiling, with uniform loading
of 31.5 W/m2 or 700 W and air volumetric flow of 5 L/s per
square metre or 110 L/s for one outlet, find the size for a 0° deflection
horizontal blade, high sidewall grille located at center of 3.7 m end wall,
225 mm from ceiling.
Solution:
-
Constant-volume system, 110 L/s, high sidewall grille, located at
center of 3.7 m end wall, 225 mm from ceiling
-
Characteristic length L = 6 m
(length of room: Table
5)
-
Recommended maximum,
-
Throw to 0.25 m/s,
To satisfy both modes of operation, choose one or find a common throw
distance that resides within the overall ADPI range of both modes and base
product selection off chosen criteria. Further evaluation may be required if
air volumetric flow changes based on mode of operation.
-
Refer to the manufacturer’s catalog for a size that gives this
isothermal throw to 0.25 m/s. One manufacturer recommends the
following sizes, when vanes are straight, discharging at 110
L/s: 400 by 100 mm, 300 by 125 mm, or 250 by 150 mm.
There are many other considerations to be made when designing a fully mixed system. For more
information, see Rock and Zhu (2002).
Horizontal Discharge Cooling with Ceiling-Mounted
Outlets. Ceiling-mounted outlets typically use the surface effect to
transport supply air in the unoccupied zone. The supply air projects across the ceiling and,
with sufficient velocity, can continue down wall surfaces and across floors, as shown in Figure 5. In this application,
supply air should remain outside the occupied zone until it is adequately mixed and tempered
with room air. Air motion in the occupied zone is generated by room air entrainment into the
supply air (Nevins 1976).
Overhead outlets may also be installed on exposed ducts, in which case the surface effect does
not apply. Typically, if the outlet is mounted 300 mm or more below a ceiling
surface, discharge air will not attach to the surface. The unattached supply air has a shorter
throw and can project downward, resulting in high air velocities in the occupied zone. Some
outlets are designed for use in exposed duct applications. Typical outlet performance data
presented by manufacturers are for outlets with surface effect; consult manufacturers for
information on exposed duct applications.
Vertical-Discharge Cooling or Heating with Ceiling-Mounted
Outlets. Vertically projected outlets are typically selected for
high-ceiling applications that require forcing supply air down to the occupied zone. It is
important to keep cooling supply air velocity below 0.25 m/s in the occupied zone.
There are outlets specifically designed for vertical projection, and it is important to review
the manufacturer’s performance data notes to understand how to apply catalog data. Throws
for heating and cooling differ and also vary depending on the difference between supply and room
air temperatures.
Cooling with Sidewall Outlets. Sidewall outlets are
usually selected when access to the ceiling plenum is restricted. Sidewall outlets that are
within 300 mm of a ceiling and set for horizontal or a slightly upward projection
provide a discharge pattern that attaches to the ceiling and travels in the unoccupied zone.
This pattern entrains air from the occupied zone to provide mixing.
In some applications, the outlet must be located 0.5 to 1.25 m below the ceiling.
When set for horizontal projection, the discharge at some distance from the outlet may drop into
the occupied zone. Most devices used for sidewall application can be adjusted to project the air
pattern upwards toward the ceiling. This allows the discharge air to attach to the ceiling,
increasing throw distance and minimizing drop. This application provides occupant comfort by
inducing air from the occupied zone into the supply air.
Some outlets may be more than 1.25 m below the ceiling (e.g., in high-ceiling
applications, the outlet may be located closer to the occupied zone to minimize the volume of
the conditioned space). Most devices used for sidewall applications can be adjusted to project
the air pattern upward or downward, which allows the device’s throw distance to be
adjusted to maximize performance.
When selecting sidewall outlets, it is important to understand the manufacturer’s data.
Most manufacturers offer data for outlets tested with surface effect, so they only apply if the
device is set to direct supply air toward the ceiling. When the device is 1.25 m or
more below a ceiling, or supply air is directed horizontally or downward, the actual throw
distance of the device is typically 30% shorter. Many sidewall outlets can be adjusted to change
the spread of supply air, which can significantly change throw distance. Manufacturers usually
publish throw distances based on specific spread angles.
Cooling with Floor-Mounted Air Outlets. Although not
typically selected for nonresidential buildings, floor-mounted outlets can be used for fully and
partially mixed-system cooling applications. In this configuration, room air from the occupied
zone is induced into the supply air, providing mixing. When cooling, the device should be
selected to discharge vertically along windows, walls, or other vertical surfaces. Typical
nonresidential applications include lobbies, long corridors, and houses of worship. See also the
description of underfloor air distribution in the Partially Mixed Air Distribution section of
this chapter.
It is important to select a device that is specially designed for floor applications. It must be
able to withstand both the required dynamic and static structural loads (e.g., people walking,
loaded carts rolling across). Also, many manufacturers offer devices designed to reduce the
possibility of objects falling into the device. It is strongly recommended that obstructions are
not located above these in-floor air terminals, to avoid restricting their air jets.
Long floor-mounted grilles generally have both functioning and nonfunctioning segments. When
selecting air outlets for floor mounting, it is important to note that the throw distance and
sound generated depend on the length of the active section. Most manufacturers’ catalog
data include correction factors for length’s effects on both throw and sound. These
corrections can be significant and should be evaluated. Understanding manufacturers’
performance data and corresponding notes is imperative.
Cooling with Sill-Mounted Air Outlets. Sill-mounted
air outlets are commonly used in applications that include unit ventilators and fan-coil units.
The outlet should be selected to discharge vertically along windows, walls, or other vertical
surfaces, and project supply air above the occupied zone.
As with floor-mounted grilles, when selecting and locating sill grilles, consider selecting
devices designed to reduce the nuisance of objects falling inside them. It is also recommended
that sills be designed in a way that prevents their use as shelves.
Perimeter Control Techniques. In many cases, it is
advantageous to decouple perimeter and interior supply air sources, especially as new buildings
trend toward full glazing exteriors. Often, interior spaces require cooling all year round due
to personnel, electronic equipment, and lighting load requirements. Perimeter spaces, however,
are more susceptible to the outside environmental conditions and can have major effects on
interior space loads if not properly managed.
Heating and Cooling with Perimeter Ceiling-Mounted Outlets. When air outlets are used at the perimeter with vertical
projection for heating and/or cooling, they should be located near the perimeter surface, and
selected so that the published 0.75 m/s isothermal throw extends at least halfway
down the surface or 1.4 m above the floor, whichever is lower. In this manner,
during heating, warm air mixes with the cool downdraft on the perimeter surface, to reduce or
even eliminate drafts in the occupied space.
If a ceiling-mounted air outlet is located away from the perimeter wall, in cooling mode, the
high-velocity cool air reduces or overcomes the thermal updrafts on the perimeter surface. To
accomplish this, the outlet should be selected for horizontal discharge toward the wall. Outlet
selection should be such that isothermal throw with terminal velocity of 0.75 m/s
should include the distance from the outlet to the perimeter surface. For heating, the supply
air temperature should not exceed 8.5 K above the room air temperature.
Be conscious of room design. If there are shelves or desks against or near the perimeter surface
the high velocity air jet could disturb items on the surfaces or result in drafts.
Perimeter Heating with Floor/Sill-Mounted Outlets. The outlets used
in this configuration must be located near the perimeter surface. In heating mode, it is
important to select a vertical throw such that it overcomes the down draft produced by a cold
perimeter surface. The amount of heat generated from the outlet must be enough to overcome or
mix with this down draft airstream to avoid ankle-level draft issues in the occupied space.
3. FULLY STRATIFIED AIR DISTRIBUTION
Fully stratified air distribution systems are characterized by a vertical temperature gradient
throughout the space, where the coolest temperature is at the floor level, and the warmest
temperature is at the ceiling height. Displacement ventilation (DV) systems are the most common
example of a fully stratified air distribution
system. DV systems typically use floor or low sidewall diffusers delivering low-velocity, cool air
across the floor. The low-velocity air, in conjunction with room loads and buoyancy effects, creates
the characteristic vertical thermal stratification.
Displacement diffusers may be mounted above the occupied zone but are generally intended for
spot-cooling applications and perform similar to laminar flow diffusers.
DV systems (Figure
6) use very low discharge velocities, with diffusers typically sized to provide outlet
velocities between 0.20 and 0.35 m/s. In addition to the low velocity discharge,
the temperature of the supply air is also different from a fully mixed system, with temperatures
generally above 16°C; lower temperatures may be used in industrial
applications, exercise or sports facilities, and transient areas where comfort concerns are
minimal. This cool supply air is more dense than the ambient air and drops to the floor after
discharge, whether from floor, low sidewall, or ceiling mounted locations, spreading across the
lower level of the space (typically less than 0.2 m in height).
As convective heat sources (Figure
6) in the space transfer heat to the cooler air around them, natural convection currents
form and rise along the heat transfer boundary. Without significant room air movement, these
currents rise to form a convective heat plume (thermal plume) around and above the heat source;
as the plume rises, it expands by entraining surrounding air. Its growth and velocity are
proportional to the heat source’s size and sensible load, as well as the temperature of
the ambient air above it. As the plume rises, ambient air from below and around the heat source
fills the void. An occupant in a DV system entrains the cool, conditioned air directly into
their breathing zone. As the occupant exhales, the spent air, being warmer and more humid than
the ambient air, is pulled out of the breathing zone by the rising plume. Convective heat from
sources located above the occupied zone has little effect on occupied-zone air temperature.
At a certain height, where plume temperature equals ambient temperature, the plume dissipates and
spills horizontally. Two distinct zones are thus formed in the room: a lower occupied zone with
little or no recirculation flow (close to displacement flow), and an upper zone with
recirculation flow. The boundary between these two zones is often called the shift zone (or stratification height). The height of this boundary
layer between the upper and lower zones is determined based on the convection flow rates of the
thermal plumes in relation to the airflow rate supplied by the diffusers. In a DV system,
increasing the airflow rate reduces stratification and raises the boundary layer height, with a
decrease in airflow providing the opposite effect. Actual and simplified representations of the
temperature gradient in the space are shown in Figure
6.
DV systems can be modeled as shown in Figure 7. A
thin layer of conditioned supply air (typically between 100 and 200 mm) lies
adjacent to the floor. Directly above this layer of conditioned air is the lower zone, in which
both ambient air temperature and contaminant concentration levels increase with height; this
relationship is mostly linear. As the air transitions through the boundary layer, the upper,
unoccupied zone contains a pool of warm, used, and/or contaminated air. This upper zone may or
may not form, depending on the supplied airflow rate in proportion to the volume of thermal
plumes rising through the space.
Space Ventilation and Contaminant
Removal
Thermal plumes created by heat sources, in conjunction with thermal stratification within the
space, allow DV to be very effective at removing airborne contaminants that are equal to or
lighter than the ambient air (e.g., respiratory-produced contaminants, tobacco smoke). The
upward momentum of room air created by thermal plumes from heat sources drive an overall upward
momentum of air, which displace contaminants out of the breathing zone. This typically results
in a concentration of contaminants above the occupied zone greater than that in the breathing
zone. This has been recognized in ASHRAE Standard 62.1-2022, which
allows DV systems to have a zone air distribution effectiveness EZ value of 1.2, compared to maximum values of 1.0 for
mixed air systems. Thus, the designer can decrease the required outdoor air by 17% when using a
DV system, which may result in energy savings for the system. Care should be taken when
selecting DV systems when it is known that there will be hazardous airborne contaminants that
are heavier than the ambient air. In these systems, a fully mixed system or dilution ventilation
may be recommended.
Figure
8 shows thermal temperature gradients that might be expected for a classroom with a
3 m ceiling, served by DV. If loads are typical to the application and proper space
airflow is supplied, Skistad et al. (2002) indicate that approximately 50% of the total
temperature difference between supply air and return or exhaust air is dissipated in clear
zone(s) next to the outlet(s). The other half of the temperature gradient is the space temperature gradient (STG), assumed to be linear
with air temperature, increasing gradually from floor to ceiling. For applications where
contaminant control and removal are a primary concern, refer to the Application Guidelines
section of this chapter.
For stationary, low-activity occupants, keep supply air temperatures above 16°C.
When occupants are very near outlets (e.g., in underseat delivery), it is recommended to keep
supply air temperatures at or above 18°C.
Displacement outlets are designed for average outlet velocities between 0.20 to 0.35
m/s, and are typically mounted in a low sidewall or floor location. Returns or
exhausts should be located as high as possible in the space to promote upward momentum of the
air, and should efficiently remove as much of the stratified zone as possible; they also should
be equally distributed throughout the space to encourage equal air movement and discourage cross
flow in the stratified zone. Intensive heat sources may benefit from having returns located
directly above them to quickly remove generated heat from the room.
Displacement outlets are available in a number of configurations and sizes. Some models are
designed to fit in corners or along sidewalls, or stand freely as columns. It is important to
consider the degree of flow equalization the outlet achieves, because use of the entire outlet
surface for air discharge is paramount to minimizing clear zones and maintaining acceptable
temperatures at the lower levels of the space.
Stationary occupants should not be subjected to discharge velocities exceeding around 0.25
m/s because air at the ankle level within this velocity envelope tends to be quite
cool. As such, most outlet manufacturers define an adjacent
zone (also called a clear
zone) in which locating stationary, low-activity occupants is strongly
discouraged, but transient occupancy, such as in corridors or aisles, is allowed. Occupants with
high activity levels may also find the clear zone acceptable.
For a typical space, a single displacement diffuser can penetrate around 8 to 9 m.
Spaces that are wider than this or have high load densities should look at providing
displacement diffusers on multiple walls, or free standing (e.g., around columns) for even
airflow distribution. A computational fluid analysis (CFD) may be warranted for more complex
spaces to validate the design. Contact the diffuser manufacturer for further diffuser selection
assistance.
Benefits of displacement ventilation systems include the following:
-
Flexibility: as load distribution changes
in the space, the buoyancy forces drive/pull where the conditioned air will go.
Thus, a DV system can work effectively in an evenly distributed load space, as well
as a space with concentrated loads. A mixing system may cause drafts, or have
stagnant zones in similar loading circumstances.
-
Low noise: due to the low velocities
associated with DV diffusers, the generated noise is typically very low (<20 NC
for most applications).
-
Fewer drafts: lower turbulence intensity
can reduce draft-related complaints.
-
Indoor air quality improvements: properly
designed DV systems displace higher concentrations of contaminants above the
occupied zone than in the breathing zone.
-
Energy savings: due to a supply air
temperature typically above 16°C (more typically
18°C), significantly less energy may be used in certain climates
due to an increase in free cooling hours. Less outdoor air is required to meet
ASHRAE Standard 62.1 requirements, meaning less outdoor
air needs to be conditioned.
Some applications do not favor the use of DV systems. Small offices, especially with perimeter
exposures, often do not have room for the large outlets that may be required. The following
types of areas may be better served by a mixed system:
-
Spaces with ceiling heights less than 2.7 m
-
Some spaces with exceptionally high occupied zone heat loads.
-
Spaces in hot and humid climates that may result in higher dehumidification and
reheat energy usage
-
Spaces with ceiling heights below 3 m that are subjected to significant
room air disturbances
-
Applications where hazardous contaminants are heavier and/or colder than ambient air.
Unlike mixed systems, outlets in thermal displacement systems discharge air at very low
velocities, resulting in very little mixing. As such, design of these systems primarily involves
determining a supply airflow rate to manage the thermal gradients in the space in accordance
with ASHRAE comfort guidelines. ASHRAE Standard 55 recommends that
the vertical temperature difference between the ankle and head levels of seated occupants be no
more than 3 K and 4 K for standing occupants to maintain an acceptable
degree of occupant satisfaction.
Similar to mixing system diffusers, inlet conditions (including presence of dampers, elbows, flex
duct, etc.) can have a negative effect on performance, primarily noise (NC) and pressure drop.
Inlet conditions should match ASHRAE Standard 70 testing conditions
as closely as possible to mimic catalogue performance data. DV diffusers are typically designed
with internal baffles or nozzles, which should not be affected by inlet conditions at relatively
low plenum velocities.
DV system design is somewhat different than for mixing ventilation. For mixing ventilation
systems, where air is mixed relatively evenly throughout the space, the return/exhaust air
temperature is assumed to equal the space temperature. In displacement ventilation systems, the
space is divided into two vertical zones. The desired space air temperature is maintained only
in the lower zone and is always higher in the upper zone because of the temperature
stratification created by natural convection.
ASHRAE research project RP-949 (Chen et al. 1999) developed a calculation method for determining
supply air volume, air temperature, and other design parameters specifically for DV systems.
Using these calculations, the maximum temperature stratification, as outlined in ASHRAE Standard 55, is not exceeded. Example 4 uses the calculations outlined
in RP-949 and the procedure presented by Chen & Glicksman (2003). This research project is
intended for use with typical office and classroom spaces; for larger spaces such as atriums and
theaters, careful consideration is necessary, and a computational fluid dynamic (CFD) analysis
is recommended to verify design. The Federation of European Heating and Air Conditioning
Associations (REHVA) also developed two procedures for calculation of air volume in DV systems;
see the REHVA design guide for further information on these methods.
Example 4.
Determine the supply air temperature, supply air flow rate, and face area for a
displacement diffuser for a small office room (3 × 3.7 × 2.7 m)
with the following characteristics:
| qo = occupant load, 150 W
|
| qe = computer/equipment load, 120
W |
| qoe=qo + qe = 270 W |
| ql = lighting load, 180 W
|
| qex = exterior load, 350 W
|
| tset point = 24°C |
Step 1. Determine total cooling load:
Step 2. Determine airflow rate to meet cooling
load. ASHRAE RP-949 (Chen et al. 1999) allows applying factors to each heat load based
on how much they contribute to room stratification. The factors identified in their
research are as follows:
Equipment and occupant loads Foe: 0.295
Lighting loads Fl: 0.132
External loads Fex: 0.185
The individual space heat gains can then be multiplied by these factors to establish an
effective sensible heat gain (ESHG) for the space.
where
| cp = specific heat, 1.005
kJ/kg · K |
| ρ = density of air, 1.225 kg/m3 |
| Δthf =maximum head-to-foot
temperature differential for a seated occupant, 3 °C (per
ASHRAE Standard 55-2020) |
Step 3. Determine minimum outdoor air
requirement per ASHRAE Standard 62.1-2022:
where
| Rp = outdoor air rate per person,
2.3 L/s-person per ASHRAE Standard
62.1-2022
|
| Pz = zone population (number of people in
zone during typical usage), 2 |
| Ra = area outdoor air rate, 0.3
(L/s) · m2 per Standard
62.1 |
| Az = zone floor area, 11.1
m2 |
| Ez = ventilation effectiveness, 1.2 (per
Standard 62.1 for DV systems)
|
Therefore, the total supply air volume Qs for
cooling is determined by the cooling load and is 35 L/s.
Step 4. Calculate supply air temperature. The
following formula assumes thermostat is located 1 m from the floor:
Step 5. Determine return air temperature:
Step 6. Adjust airflow for new supply
temperature. DV systems typically use warmer supply air temperatures than mixing
systems. The supply air temperature should be at least 16°C, or
5.5 K less than the room set point, whichever is higher. Supply airflow
should maintain the same return temperature:
Therefore, in order to condition this particular office using a DV system, it is
necessary to deliver 17°C, air at an airflow rate of 34
L/s.
Step 7. Size diffuser. Assume a maximum
diffuser face velocity of 0.25 m/s to obtain acceptable thermal comfort.
This recommendation is based on the nominal diffuser size.
A single diffuser that is 450 × 610 mm will meet this minimum area
requirement to maintain comfort. Check with the manufacturer’s performance data to
ensure diffuser selection meets noise and comfort requirements.
Space temperature gradient (STG) is affected by the strength and location of heat sources in the
space, heat exchange by radiation between surfaces in the space, and supply airflow. The design
procedure presented in this section is based on Skistad et al.’s (2002) simplified method
of estimating temperature gradient (Figure
8). This method is applicable for typical spaces with a ceiling height up to 3.7
m, such as classrooms, office spaces, and meeting rooms. When designing more complex
spaces, computational fluid dynamics (CFD) software programs may be used (see Chapter 13 of the
2021 ASHRAE Handbook—Fundamentals for more
information).
The thermal gradient relationships illustrated in Figure
8 can be used to establish an acceptable supply-to-return air temperature differential
ΔtSR from which the supply airflow rate is
calculated. Because the space temperature gradient is assumed to be linear, the occupied
gradient in the occupied zone is proportional to the volume of the space it represents. For
example, if return height is located at height 3 m and the occupied zone is
1.2 m high, its gradient comprises 40% of the space temperature gradient. The
temperature difference between room air at the top of the occupied zone and the supply air is
therefore 70% of ΔtSR.
Determining an acceptable ΔtSR should consider both
the room-to-supply temperature differential and the occupied zone temperature gradient (as
limited by ASHRAE Standard 55).
In general, high-ceiling applications allow larger supply-to-return air temperature
differentials, because the occupied zone is a smaller percentage of total room air volume.
However, the differential may be reduced by limitations on supply air temperature, as shown in
Example 5.
The supply airflow rate Q to achieve a given ΔtSR is calculated from Equation (1).
Example 5.
A classroom with a 3 m ceiling is to be cooled by displacement ventilation.
The supply air temperature is 17°C and room temperature is maintained
at 24°C at 1.2 m level. The total sensible heat gain of
the space is 6450 W.
Calculate the (1) overall temperature differential between supply and return airflow and
(2) required space airflow. Identify return air temperature and temperature at
occupants’ ankle level.
Solution: Using the relationships in Figure
8, the supply-to-return temperature differential ΔtSR and return air temperature can be predicted as
follows:
The value is then added to the supply air temperature to estimate a return air
temperature.
To ensure a high level of thermal comfort, the occupied-zone temperature gradient
Δtoz should not exceed 3 K. For
this application, the occupied zone gradient is acceptable:
From Equation
(1), the airflow required to maintain this gradient is
The ankle-level temperature will be midway between the supply and return temperatures, or
22°C. This results in a head-to-foot temperature gradient Δthf of 1.9 K, which is well within the
recommendations of ASHRAE Standard 55.
Thermal displacement ventilation systems typically have higher return air temperatures than mixed
systems. Thus, they may allow extended periods of air- or water-side economizer operation,
especially in mild, relatively dry climates.
Thermal displacement ventilation systems are commonly used in applications such as
-
Restaurants
-
Casinos
-
Classrooms/education facilities
-
Large open-plan offices, classrooms, lecture halls, and meeting rooms
-
Theaters and auditoriums
-
Industrial spaces
-
Hospitals and cleanrooms
-
Other spaces with high ceilings
DV systems rely on buoyancy of the cool supply air and thermal plumes of the heat sources to
drive stratification in the space. Due to this, DV is typically a cooling-only method of room
air distribution. When heating is required, the warmer (more buoyant) air, in conjunction with
the low discharge velocity, can mean that the air may not effectively condition the occupied
zone, or may completely bypass the occupied zone to the returns. This can have a negative effect
on both the thermal comfort and indoor air quality in the space. Limited heating differentials
may be acceptable depending on a number of factors. ASHRAE Standard
62.1-2019 prov ides effectiveness guidance, and ASHRAE research project RP-1373 (Jiang and Chen
2009) explores the ventilation effectiveness of various DV systems in heating and cooling
scenarios.
For heating in cold climates, a separate decoupled system is generally recommended. Displacement
ventilation can be used successfully in combination with perimeter fan coils, hydronic systems,
or radiators and convectors installed at exterior walls to offset space heat losses. Radiant
heating panels and heated floors can also be used. Using this hybrid approach, the DV diffusers
can provide adequately cool ventilation air, with the auxiliary devices handling the heating
load.
Displacement diffusers with integrated heat typically have a separate heating plenum featuring a
heating coil and are often used for perimeter applications. Heat/cool changeover diffusers can
also be used. For this design, the heating portion of the diffuser will not provide a
displacement pattern, so in this case ventilation effectiveness is compromised.
Care is also needed when using DV systems in high perimeter cooling load applications. DV
diffuser mounting locations should be carefully considered to minimize the risk of conditioned
air being drawn toward the strong thermal plume of the exterior surface. It may be better to
place diffusers along an interior surface to ensure that the conditioned air reaches interior
occupants before conditioning the exterior envelope loads.
Considerations Unique to
Displacement Ventilation Systems
Thermal displacement ventilation systems can be either constant (CV) or variable air volume
(VAV). A thermostat in a representative location in the space or return plenum should determine
the delivered air volume or temperature. If the time-averaged requirements of ASHRAE Standard 62.1-2019 are met, intermittent on/off airflow control can be
used.
Avoid using DV and mixed air systems in the same space, because mixing destroys the natural
stratification that drives the thermal displacement ventilation system. DV systems can be
complemented by hydronic systems such as chilled floors. Use caution when combining chilled
ceilings, beams, or panels with fully stratified systems, because cold surfaces in the upper
zone of the space may recirculate contaminants stratified in the upper zone back into the
occupied zone.
It is often beneficial to couple DV systems with hydronic products. Displacement chilled beams
are available that integrate sensible heating and cooling coils. for more information about
chilled beams, see the Chilled Beams section of this chapter.
Another common application is to use DV systems to provide only the space ventilation and
cooling, while a complementary hydronic system satisfies the majority of the cooling load. In
this case, passive (not active) sensible cooling devices (e.g., passive beams, radiant ceiling
panels) should be used to minimize the disruption of the natural stratification that drives the
DV system.
When thermal displacement systems are used in humid climates, it may be necessary to dehumidify
and reheat supply air to a temperature that will sufficiently maintain the desired space
conditions. As with all HVAC air systems’ design, a psychrometric analysis is advised.
Chen and Glicksman (2003) provide additional information on fully stratified air distribution
systems.
4. PARTIALLY MIXED AIR DISTRIBUTION
A partially mixed system’s characteristics fall
between a fully mixed system and a fully stratified system. It includes both a high-velocity mixed
air zone and a low-velocity stratified zone where room air motion is caused by thermal forces. For
example, floor-based outlets, when operating in a cooling mode with relatively high discharge
velocities (>0.75 m/s), create mixing, thus affecting the amount of stratification
in the lower portions of the room. In the upper portions of the room, away from the influence of
floor outlets, room air often remains thermally stratified in much the same way as displacement
ventilation systems.
Supply air is discharged, usually vertically, at relatively high velocities and entrains room air
in a similar fashion to outlets used in mixed air systems. This entrainment, as shown in Figure
9, reduces the temperature and velocity differentials between supply and ambient room
air. This discharge results in a vertical plume that rises until its velocity is reduced to
about 0.25 m/s. At this point, its kinetic energy is insufficient to entrain much
more room air, so mixing stops. Because air in the plume is still cooler than the surrounding
air, the supply air spreads horizontally across the space, where it is entrained by rising
thermal plumes generated by nearby heat sources.
Research and experience have shown that the amount of room air stratification varies depending on
design, commissioning, and operation. Control of stratification includes the following
considerations:
-
By reducing airflow and mixing in the occupied zone, fan energy can be reduced and
stratification can be increased, approaching a reasonable target at 1.5 to 2.5
K temperature difference from head level to ankle level, which satisfies
ASHRAE Standard 55-2020.
-
By increasing airflow and mixing in the occupied zone, excessive stratification can
be avoided, thereby improving thermal comfort.
In practice, successful installation requires an optimal balance of these issues (Webster and
Bauman 2006).
Figure
9 shows one example of the resulting room air distribution in which the room air is
mixed in the lower mixed zone, which is bounded by
the floor and the elevation (throw height) at which
the 0.25 m/s terminal velocity occurs. At this elevation, stratification begins to
occur and a linear temperature gradient, similar to that found in thermal displacement systems,
forms and extends through the stratified zone. As
with thermal displacement ventilation, convective heat plumes from space heat sources draw
conditioned air from the lower (mixed) level through the stratified zone and to the overhead
return location. A third zone, referred to as the upper mixed
zone, may exist where the volume of rising heat plumes terminate.
Although velocities in this area are quite low, the air tends to be mixed.
Space Ventilation and Contaminant
Removal
Partially mixed systems’ ventilation and contaminant removal efficiencies vary
considerably. Restricting mixed conditions to below the breathing level results in most
respiratory-associated contaminants being conveyed directly to the overhead return by heat
plumes rising from occupants. If the lower mixed zone extends above the breathing level,
contaminants are entrained and horizontally transmitted across occupied levels of the space, as
occurs in mixed air (dilution ventilation) systems.
According to ASHRAE Standard 62.1, these systems may have zone air
distribution effectiveness EZ values that exceed those of
fully mixed systems. For applications where contaminant control and removal are a primary
concern, see the section on Application Guidelines.
One outlet type is a swirl diffuser with a
high-induction core, which induces large amounts of room air to quickly reduce supply to ambient
air velocity and temperature differentials. Supply air is injected into the room as a swirling
vertical plume close to the outlet. Properly selected, these outlets produce a limited vertical
projection of the supply air plume, restricting mixing to the lower portions of the space. Most
of these outlets allow occupants to adjust the outlet airflow rate easily. Other versions
incorporate automatically controlled dampers that are repositioned by a signal from the space
thermostat and/or central control system.
Another category includes more conventional floor
grilles designed for directional discharge of supplied airflow. These
grilles may be either linear or modular in design, and may allow occupants to adjust the
discharge air pattern by repositioning the core of the outlet. Most floor grilles include an
integral actuated damper or other means to automatically throttle the volume of air in response
to the zone conditioning requirements.
Room air induction allows UFAD diffusers to comfortably deliver supply air a few degrees cooler
than possible with outlets used for thermal displacement ventilation outlets. Keeping clear or
adjacent zones above and around the diffusers, where stationary occupants should not reside, is
recommended. Outlet manufacturers typically identify such restrictive areas in their product
literature.
Partially mixed systems are commonly used in applications such as the following:
Many UFAD systems can be classified as partially
mixed systems. These systems are popular because of their relocation flexibility when used in
conjunction with raised-access flooring systems. Outlet accessibility also allows easy occupant
adjustment of space airflow delivery. The cavity beneath the access floor tiles is generally
pressurized and used as a supply air plenum. Supply outlets placed in access floor tiles are
commonly tapped directly into the pressurized plenum, but may be ducted from a fan-assisted
terminal unit mounted beneath the floor.
Benefits of UFAD systems include the following:
-
Using a raised floor system may substantially reduce air distribution ductwork and
terminal requirements.
-
Possibility of lowering deck-to-deck dimensions.
-
Central fan energy consumption may be lower.
-
The space service flexibility of the access floor platform is extended to include
HVAC services as well. Nonducted outlets can be easily added or relocated.
-
Because most outlets are sized to handle loads typical to an interior single-occupant
office or workstation, they can be placed within the workstation to give occupants
thermal control over their individual work environment. This makes higher individual
occupant comfort levels possible.
-
Air- and water-side economizer opportunities are extended, especially in mild and
relatively dry climates.
Limitations to consider are
-
Applications where contaminants are heavier and/or colder than ambient air may be
better served by a mixed air system.
-
As with thermal displacement systems, partially stratified systems in humid climates
require that outdoor air be sufficiently dehumidified to satisfy space latent
requirements. The temperature of dehumidified air must often be increased before
introduction to the occupied space.
-
Uncontrolled air can leak from pressurized underfloor plenums. Proper design and
installation can minimize or eliminate this.
-
Plenum air temperature can degrade in relation to distance traveled from the supply
air source.
As with thermal displacement systems, design involves determining a supply airflow rate that
limits thermal gradients in the occupied zone in accordance with ASHRAE Standard 55 guidelines; that is, the vertical temperature difference
between the ankle and head level of space occupants should be no more than 3 K if a
high degree (>95%) of occupant comfort is to be maintained.
UFAD systems usually pressurize the open plenum space under the access floor, this way the
diffusers do not need to have an inlet. If linear floor diffusers with plenum boxes are
utilized, they are usually made with very large rectangular inlets that are the same size as the
linear length of those plenums. For ducted installations, use the same inlet criteria as the
other air distribution systems.
The design of partially mixed air distribution systems requires identifying both thermal and
contaminant removal objectives:
-
The desired space temperature, the elevation to which it applies, and an appropriate
supply air temperature must be identified.
-
The supply air temperature for UFAD systems served by a pressurized or neutral
pressure floor plenum should be limited to that which results in a relative humidity
level below 80% in the floor cavity, to minimize the threat of mold or fungus
growth.
-
Supply air temperatures tend to rise as air moves through the floor cavity;
therefore, supply air temperature varies with its distance traveled. When
determining space airflow requirements, supply temperatures should be modified
accordingly to avoid undercooling the occupied space. This subject is discussed
further in ASHRAE’s UFAD Guide (2013).
-
If the objective is to provide displacement ventilation of respiratory contaminants
in the stratified zone, mixing must be limited to below the breathing level of most
space occupants.
-
Outlets should be located far enough from stationary occupants to ensure that they
are not subjected to drafts that might cause thermal discomfort. Outlet
manufacturers generally prescribe clear zones that quantify this separation
distance.
There are several ways to provide perimeter air distribution using a partially mixed air system.
Air distribution in the perimeter zone is highly influenced by weather and solar loads at the
building envelope; this means that different amounts of cooling or heating may be needed at
different times, independent of interior zone load needs. The most common scenario is when
cooling is needed at the interior zone and heating is needed at the perimeter zone; both
internal and perimeter loads can be met using a zone divider or a dedicated plenum system. See
ASHRAE (2013) for more information on how to handle perimeter zone applications.
Space Temperature Gradients and
Airflow Rates
The objective of partially mixed systems is to condition the air in the occupied zone while
allowing stratification to naturally occur. By allowing this stratification, some of the space
heat gain can be removed by return or exhaust instead of by supply air delivery to the space. If
the supply airflow rate and sensible heat gains affecting the lower zone are balanced, an
acceptable temperature gradient (<3 K) can be achieved in the occupied zone.
Supply airflow beyond that required by these heat gains reduces the degree of stratification
shown in Figure
9. If the supply airflow rate is insufficient, excessive vertical space temperature
gradients may occur.
Accurate calculation of the space design supply airflow rate requires analysis of all space
sensible heat gains to determine their contribution to the lower zone. Although there is not yet
a single recognized procedure for calculating these airflow rates, most UFAD equipment
manufacturers offer guidance.
Considerations Unique to
Underfloor Air Distribution Systems
The ASHRAE UFAD Guide (2013) includes a thorough discussion of issues
involved in the design, application, and commissioning of UFAD systems. Some considerations
include the following:
-
Supply temperatures in the access floor cavity should be kept at
16°C or above, to minimize the risk of condensation and subsequent
mold growth.
-
Most UFAD outlets can be adjusted automatically by a space thermostat or other
control system, or manually by the occupant. In the latter case, outlets should be
located within the workstation they serve.
-
Use of manually adjusted outlets should be restricted to open office areas where
cooling loads do not tend to vary considerably or frequently. Perimeter areas and
conference rooms require automatic control of supply air temperatures and/or flow
rates because their thermal loads are highly transient.
-
Heat transfer to and from the floor slab affects discharge air temperature and should
be considered when calculating space airflow requirements. Floor plenums should be
well sealed to minimize air leakage, and exterior walls should be well insulated and
have good vapor retarders. Night and holiday temperature setbacks should likely be
avoided, or at least reduced, to minimize plenum condensation and thermal mass
effect problems. With air-side economizers, using enthalpy control rather than
dry-bulb control can help reduce hours of admitting high-moisture-content air, thus
also reducing the potential for condensation in the floor plenums.
-
Avoid using stratified and mixed air systems in the same space, because mixing
destroys the natural stratification that drives the stratified system.
-
Return static pressure drop should be relatively equal throughout the spaces being
served by a common UFAD plenum. This reduces the chance of unequal pressurization in
the UFAD plenum.
5. AIR DISPERSION SYSTEMS
The design methodologies provided in this section cover textile air dispersion systems, though
the same principles can be applied to systems constructed with metal. Textile air dispersion
systems are low pressure extended plenum systems with pressurized tubing and air distributed
along the path of least resistance. Suggestions are provided for material selection and
dispersion style, support and structure of the textile air dispersion system, and sizing/venting
locations of the system. Consult with the manufacturer and specific product data and performance
information when designing and specifying textile air dispersion systems.
These systems can also be found designed into the plenum space of raised floor applications. In
these applications, the designer must consider that the system is exposed in the space that it
is conditioning and delivering air to. Air outlet throws of the textile air dispersion system
must be designed for the plenum space in which they are located.
A version of these systems is also being used for return air (negative pressure). This requires a
sturdy framework that holds the outer walls of the product open to prevent the restriction from
becoming too great and restricting airflow beyond design intent. Maximum internal velocity of
5 m/s and –31 Pa static pressure
Air Dispersion System Supply Air
Outlet Styles
Various supply air outlet styles are available: porous fabric weave used as an outlet,
microperforations, linear vents, orifices, and nozzles. Many of these air outlet styles can be
used together to achieve specific results.
Porous Fabric Weave (Figure
10). Air is delivered through the weave of the fabric. This can
result in air velocities of less than 0.15 m/s at the material surface. The ability
to achieve such a low face velocity makes this the preferred dispersion style where displacement
ventilation is needed. This dispersion style is ideal for food processing, cleanrooms, and
laboratory environments where elimination of drafts and uniform air distribution is required,
and can be used in combination with other types of air outlets to achieve the specified room
airflow. Cool air drops to the floor and then spreads across the lower level of the space.
Porous fabric ducts can be used in combination with most linear vents and orifice applications.
Air throw distance is generally lower than with linear vents, and may not be appropriate for
heated supply air applications.
Microperforation Outlets (Figure
11). Air is delivered through laser-cut microperforations,
generally smaller than 0.4 mm. As with porous fabric, air velocities of less than 0.15
m/s can be realized 0.61 m from the duct. Microperforations offer
low-velocity distribution in the occupied zone without forcing the majority of the air through
the weave of the material. Further, the microperforations can be uniformly located along
360°, or within a specific area or side of the air dispersion device, allowing designers to
disperse air exactly where it is needed. This method can be used for displacement ventilation
and isothermal/makeup air, but is limited for heating applications (when using directed
microperforations for heating, consult manufacturer for throw data). This dispersion style is
also ideal for food processing, cleanrooms, and laboratory environments where elimination of
drafts and lower-velocity air is required. Cool air can be more evenly distributed in the space
using directed microperforations rather than dropping or “dumping” due to buoyancy,
directly below the diffuser. Microperforations can be used in combination with most other flow
models to modify throw and velocity to meet design requirements.
Linear Vent Outlet (Figure
12). Air is delivered through a linear vent outlet, which
generally consists of many small outlets in a linear pattern. This provides uniform airflow with
throw suitable for commercial and retail spaces, schools, and theaters. Generally, medium air
throw distance can be achieved.
Orifice and Nozzle Outlets (Figure
13). Air is delivered through orifices or venturi-shaped nozzles
providing jet-type air distribution for applications such as gymnasiums, pools and manufacturing
facilities. This style generally has a higher air throw distance than other outlet styles.
Nozzles can direct air perpendicularly away from the surface of the duct. Adjustable nozzles
allow for changing the direction and/or flow rate and throw. Nozzles generally have the least
entrainment of longer-throw outlets. Manufacturers have many specific options for this style of
air outlet, and the manufacturer’s data must be consulted.
Air Dispersion System Shapes
Three shapes are commonly available: cylindrical, half circle (D-shape), and the quarter circle,
as shown in Figure 14. Cylindrical systems
are typical for open ceiling spaces and are mounted using a tension cable or suspended aluminum
track suspension system. The half circle can be installed against a ceiling or wall.
Manufacturers also have many custom shapes that can be used to solve installation challenges.
Air dispersion system ducts, classified by Underwriters Laboratories as an air distribution
device, should have a Class 1 rating per UL Standard 723. The
maximum flame spread/smoke developed index is currently 25/50.
Additional important properties in selecting a material for air dispersion systems are durability
and aesthetics. Durability includes not only the environment, but the design. Supports and
static pressure must hold fabric air dispersion system materials in tension to prevent fabric
wear and tear. The maximum velocity in a system should not exceed the manufacturer’s rated
velocity; excessive air velocities cause fabrics to fail prematurely. The International Mechanical Code® (ICC 2018) and the Uniform Mechanical Code (IAPMO 2018) require that air dispersion
systems be listed and labeled in compliance to UL Standard 2518.
The use of a slightly permeable material allows dispersion of air below dew point without the
risk of condensation forming on the fabric air dispersion system. The duct is pressurized, and
air is forced through the surface of the material, forming an insulating barrier of cooler air
around the duct, preventing warm moist air from contacting the cold surface of the air
dispersion system and thereby preventing water droplets from forming on the surface. The
permeated air is often induced by outlets on the system and entrained into the supply air
exiting the outlets.
Nonpermeable materials can be used where risk of condensation is low and applied in a way similar
to uninsulated single wall metal ducts. These are often used in dryer climates or for extensive
systems.
Polyester is typically the preferred material for fabric air dispersion systems because it has
very low hygroscopic properties, is a synthetic material that is not a food source for
organisms, and is easy to launder. Several manufacturers offer materials with complementary
properties, such as antimicrobial treatment (to prevent microbial growth), antistatic for use
around sensitive electronics and in explosion proof facilities, and fabrics that do not
“shed” filament particles for use in cleanrooms and critical laboratories.
Textile air dispersion system manufacturers offer many different types of suspension systems to
address the various applications in which they are used (Figure 15). Typical
types include
-
Clips sewn to the top of the air dispersion system and clipped onto a tensioned
horizontal cable
-
Sliders or continuous keder cord sewn to the top of the air dispersion system and
slid into a metal track (the track could be mounted directly to the ceiling or
suspended a distance below it)
-
Sliders or continuous keder cord sewn to the top corners of a half or quarter circle
air dispersion system and slid into a metal track (the track could be mounted
directly to the ceiling or suspended a distance below it)
-
Direct suspension from an internal frame system
Hold-Open and Fabric Retension Systems (Figure
16). Textile air dispersion systems can also be held open
(restricting their potential to collapse onto themselves when the HVAC unit is not providing
airflow) with rings, hoops, and arcs.
Fabric Tension Systems (Figure
17). Fabric tensioning systems hold the fabric in place
regardless of whether the system is pressurized. These systems increase fabric longevity by
reducing movement of the fabric. Some hold the fabric in such a way that air velocities in the
product can be increased to a higher maximum (which results in smaller diameter sizes) without
the fabric wall being unstable and fluttering, which could lead to premature failure.
A fabric air dispersion system performs as both a duct and a diffuser. When designing a textile
air dispersion system, keep the layout as simple as possible, preferably with straight runs.
Because porous fabric duct, linear vents, and orifice outlets can be integrated into all
sections, system design may vary significantly while providing adequate air dispersion.
Metal ductwork before the fabric inlet should have the same air velocity as the fabric duct, and,
when possible, it is recommended to use 3× the diameter of straight metal duct. If there
is a transition preceding the fabric inlet, it is recommended to use 1.5× the diameter
radius elbows and turning vanes in sheet metal transitions before fabric. High velocity (8
m/s) and turbulent conditions immediately before the system can cause excessive
fabric movement and premature wear.
There is little need to reduce diameters because air dispersion systems are essentially extended
plenums that can maintain static pressure due to continuously occurring static regain. Custom
fittings should be coordinated with the manufacturer. It is recommended that end caps be one
diameter from a wall to maintain clearance for systems and allow for movement and ease of
installation.
Fittings. Straight duct lengths and fittings are
connected together using a circumference zipper, which is affixed with its start/stop typically
located at the top center, and includes a circumferential fabric overlap to conceal the zipper.
Typical lengths of zippered sections are sized for easy laundering and installation. Longer
sections are broken into multiple lengths.
Elbows. The typical centerline radius of an elbow is
figured by multiplying the cross-sectional diameter by 1.5. For example, a
610 mm diameter air dispersion system elbow would have a centerline radius of
914 mm. The number of gores depends on the angle of the turn, as shown by Figure 18.
Transitions. Reducing transitions are available in
concentric, top flat, or bottom flat configurations (Figure 19).
Transition length varies and is based on the change in diameter, such that the total angle does
not exceed 30°.
Tees. Tees are saddle type, and the branch requires a
zipper for attachment. Typical tee arrangement is shown in Figure 20. It is
recommended that tees be located at least 1.5× the outlet diameter from end caps (Figure 21).
Cross, Capped. See Figure 22 for the capped
cross, which is SD5-20 in the ASHRAE (2017a) Duct Fitting Database
(DFDB).
Dampers and Static Regain Devices. These fittings are
used to address multiple objectives. The fittings offer engineered resistance to balance airflow
in multiple runs and branches, reduce turbulence, reduce inflation pop, reduce noise, reduce
movement from abrupt start-ups, and balance static regain. Locate flow devices at (1) inlet
collars, (2) one-third point of a straight section, and (3) after take-offs and elbows. A flow
device at the inlet collar reduces fluttering due to turbulent airflow entering the air
dispersion system. At the first zipper, the flow device reduces the force of initial inflation
and reduces “pop;” a fabric tensioning system can also eliminate any movement,
deflation, or noise due to the HVAC system cycling on and off. Straightening out velocity
profiles also reduces wear in a fabric duct system. Examples of dampers and static regain
devices are shown in Figure 23.
Cylindrical Air Dispersion Systems. The recommended
design velocity is 8.1 m/s for a system without fittings, and 7.1 m/s
for a system with fittings. Use lower velocity (5.1 to 6.1 m/s) for noise sensitive
areas. If the diameter is too large, design the system for multiple runs.
Half Circle (D-Shape) Air Dispersion Systems.
D-shape air dispersion systems should be sized so that the fabric duct velocity does not exceed
the rigid supply duct velocity. The maximum velocity for a straight run is 5.1 m/s.
For a system with a fitting, the recommended velocity is 4.1 m/s. A lower inlet
velocity to the fabric duct reduces stress and noise.
Flow can be any split (e.g., for a top inlet in the middle, split is 50/50; for a top inlet a
third of the distance from one end, split is 33/67), including flow from the end. The D-shape
diameters and the duct diameters are good for a split to 38 to 62%. For a greater split, the
inlet duct diameter needs to be reduced so the branch duct velocity does not exceed the design
inlet duct velocity (4.1 or 5.1 m/s).
To design air dispersion systems, follow the steps below:
.
Step 1. Lay out the system. Keep as simple as
possible.
Step 2. Given the system airflow requirement,
determine the fabric duct size.
Step 3. Assuming an inlet static pressure
(ISP) to each section of the air dispersion system, calculate the average static
pressure.
Step 4. In each section, use Equation (12), and
use the DFDB (ASHRAE 2017a) to calculate Δptx. Equation (12) is an
empirical equation based on experience gained by air dispersion system designers.
Leverette et al. (2014) state that this equation is approximately correct. Most often,
the ISP to the air dispersion system is approximately 125 Pa.
where
| psx,avg = average static pressure in
section x, Pa |
| psx = ISP to section x, Pa |
| pvx = inlet velocity pressure to section
x, Pa
|
| Δptx = total pressure loss of
section x, Pa |
The component of total pressure drop Δptx of
a fabric duct that is dispersing air equally along its length can be estimated using the
DFDB (ASHRAE 2017a; fitting CD11-1) and 35% of the duct length, where 35% is an
approximation (because typical systems have a constant diameter from inlet to endcap).
The absolute roughness for a system with an internal support frame is 1.69
mm, and for an unsupported system (no internal frame) is 0.11 mm
(Kulkarni et al. 2012). These values are based on a 368 mm nonporous
polyester fabric duct with an acrylic/urethane coating.
Step 5. Airflow through porous material of
length L is calculated by Equation (13):
where
| Qmaterial = airflow diffused through
porous material, L/s |
| D = system duct diameter, mm |
=
material porosity, L/s per m2 at 125 Pa |
| L = length of system duct, m |
| psx,avg = average static pressure in
section x, Pa |
| K1 = 1000 |
| K2 = reference SP, 125 |
Step 6. Calculate the airflow required though
the fabric duct outlets (vents or orifices):
where
| Qoutlet = total outlet airflow,
L/s
|
| Qsystem = system airflow,
L/s
|
| Qmaterial = airflow through material,
L/s
|
Step 7. Determine the length of vent or number
of orifices, orientation of outlets (Figure 24), and
throw. Typically there is a 1.2 m void (no outlets) near the inlet or after
any fitting within a system to reduce wear. This is manufacturer dependent. Consider the
following when selecting the orientation of air outlets:
-
11 and 1, 10 and 2, and 3 and 9 o’clock (Figure
24): Primarily chosen for cooling or ventilating, these locations
direct the exiting air upward and/or outward from the air dispersion system.
Throw should reach the exterior walls or fill the gaps between parallel air
dispersion ducts.
-
4 and 8, 5 and 7, and 6 o’clock (Figure
24): Primarily chosen for applications with heating, but can also be
used for cooling or ventilating, these location direct the exiting air
downward and/or outward from the air dispersion system. Throw requirements
can be critical in these locations because the air is directed towards the
occupied space.
Determine throw:
where
| T = required throw, m |
| H = distance between bottom of duct and floor,
m
|
| KT = 1.8 |
| K5 = 2.0 for 4 and 8 o’clock |
| 1.15 for 5 and 7 o’clock |
| 1.0 for 6 o’clock |
For linear vent outlets, select vent size using manufacturer data. Terminal velocity is
the maximum airstream velocity at end of throw.
For orifice outlets, select orifice diameter using manufacturer data. Terminal velocity
is the maximum airstream velocity at end of throw.
Filtration. It is essential to filter incoming air
before it reaches the textile air dispersion system. An efficient filtration system means less
cleaning, resulting in a longer product life. Higher filtration (MERV 8) is recommended for
low-velocity outlets (porous fabric and microperforations). Textile air distribution systems are
launderable.
Pressure Required for Inflation. For proper inflation,
the static pressure at the inlet to a fabric air distribution system should be no less than
1.3× the inlet velocity pressure.
6. AIR TERMINAL UNITS (ATUS)
Designers have various systems (ATUs and their associated controls) to choose from when designing a
building. The owner’s needs must be met for installation, application, and cost of operation.
The designer must consider performance, capacity, reliability, energy consumption, sustainability,
and spatial requirements and restrictions. The following guidelines describe different types of
equipment and their general uses, restrictions, and limitations. Table 9
summarizes the different types of ATUs and their suitability for particular commercial building
applications.
Single-Duct ATUs. Single-duct ATUs are used to
regulate airflow to a conditioned space. Primary air is ducted from an air handler. The basic
single-duct unit consists of an airflow regulator and may also include an actuator, an
airflow-measuring device, selected controls, and heating coils.
Table 9 Suitability of Terminal Units for Various Applications
|
Terminal Types
|
Facility Type
|
|
Office Space, Educational, and Institutional
Buildings
|
|
Hospitals, Cleanrooms, and Laboratories
|
|
Noise-Sensitive Applications
|
|
Other Facilities
|
|
Large
|
|
Small
|
Patient Areas
|
Operating Areas
|
Laboratory Space
|
Broadcast Studios
|
Theaters
|
Libraries
|
Public Use
|
Shopping Centers
|
Mixed Use
|
|
Interior Zone
|
Exterior Zone
|
Low Temperature
|
Interior Zone
|
Exterior Zone
|
|
Single-duct
|
| |
VAV without reheat
|
•
|
•
|
•
|
|
•
|
•
|
|
•
|
N
|
•
|
|
•
|
•
|
•
|
|
•
|
•
|
•
|
| |
VAV with reheat
|
•
|
•
|
•
|
|
•
|
•
|
|
•
|
P
|
P
|
|
•
|
•
|
•
|
|
•
|
•
|
•
|
|
Dual-duct
|
| |
VAV no mixing
|
•
|
•
|
N
|
|
N
|
N
|
|
N
|
N
|
N
|
|
•
|
•
|
•
|
|
•
|
•
|
•
|
| |
VAV with mixing
|
•
|
•
|
N
|
|
N
|
N
|
|
•
|
•
|
N
|
|
•
|
•
|
•
|
|
•
|
•
|
•
|
| |
Constant volume
|
•
|
•
|
N
|
|
N
|
N
|
|
P
|
P
|
•
|
|
P
|
•
|
•
|
|
•
|
N
|
•
|
|
Exhaust terminal
|
•
|
•
|
N
|
|
N
|
N
|
|
P
|
P
|
P
|
|
•
|
•
|
•
|
|
•
|
•
|
•
|
|
Induction terminal
|
| |
VAV with heat
|
•
|
•
|
•
|
|
•
|
•
|
|
•
|
N
|
•
|
|
•
|
•
|
•
|
|
•
|
•
|
•
|
| |
VAV without heat
|
•
|
•
|
•
|
|
•
|
•
|
|
N
|
N
|
N
|
|
•
|
•
|
•
|
|
•
|
•
|
•
|
|
Fan-powered
|
| |
Parallel with heat
|
N
|
•
|
•
|
|
N
|
•
|
|
N
|
N
|
N
|
|
N
|
•
|
•
|
|
P
|
•
|
•
|
| |
Series without heat
|
P
|
•
|
•
|
|
•
|
•
|
|
N
|
N
|
N
|
|
P
|
P
|
P
|
|
P
|
P
|
P
|
| |
Series with heat
|
•
|
P
|
•
|
|
•
|
•
|
|
•
|
N
|
•
|
|
P
|
P
|
P
|
|
P
|
P
|
P
|
| |
Low-temperature
|
•
|
•
|
P
|
|
•
|
•
|
|
N
|
N
|
N
|
|
N
|
N
|
N
|
|
N
|
N
|
N
|
|
Bypass
|
N
|
N
|
N
|
|
•
|
N
|
|
N
|
N
|
N
|
|
N
|
N
|
N
|
|
N
|
N
|
N
|
|
Single-duct ATUs can be applied to pressure-dependent or -independent systems. Pressure-dependent units consist, at minimum, of an
airflow regulator, thermostat, and actuator. The thermostat dictates the damper position based
on room demand, which is independent of system pressure. Using pressure-dependent ATUs can cause
system pressure fluctuation, which must be considered. Current ventilation requirements may
preclude the use of pressure-dependent ATUs.
Pressure-independent units consist of, at minimum, an
airflow regulator, airflow measuring device, controller, room sensor, and actuator. This is a
closed-loop control system that measures and regulates airflow based on room demand.
Pressure-independent ATUs allow a minimum airflow set point to be established to enable proper
ventilation to the zone.
Pressure-independent single-duct ATUs can be used for constant- or variable-volume applications.
Variable-volume applications often include controls that limit maximum and minimum airflow set
points determined by load, acoustical, and zone ventilation requirements.
Dual-Duct ATUs. Dual-duct ATUs function similarly to
single-duct terminals but are composed of two sets of airflow regulators merging two airstreams
into a single mixed airstream. These are typically used to mix cold and hot primary air ducts to
a single warm discharge air duct.
Series Fan-Powered ATUs. These fan-powered ATUs have a
continuously operating fan during occupied mode, supplying either a constant or variable volume
of air to the space, and they are typically installed in the ceiling plenum. Primary air is
ducted from an air handler. Induction air is either from the ceiling plenum or ducted from the
space. The fan and damper are aligned so that all primary air and all induced air independently
enter the mixing section and go through the fan to be delivered to the space. The mixing space
is between the VAV air valve and the fan.
Parallel Fan-Powered ATUs. These ATUs have an
intermittently operating fan and are typically installed in the ceiling plenum. Primary air is
ducted from an air handler and flows directly to the zone in a variable-volume cooling mode. Fan
air is induced from the ceiling plenum or may be ducted from the space. The fan should run in
heating and dead-band mode. In dead band and heating mode, the supply air is a combination of
primary and induced air. The fan and damper are arranged so that all induced air enters the fan,
and primary air bypasses the fan. Any mixing of primary air with the induced plenum air occurs
on the discharge side of the fan. A backdraft damper inhibits air from exiting the unit through
the fan when it is not running.
Fan-powered ATUs applied with underfloor air distribution systems differ from conventional
overhead systems in that the ATUs are mounted in a supply air plenum rather than a return air
plenum. The ASHRAE UFAD Guide (2013) addresses these ATUs in detail.
DOAS ATUs. ATUs may be used in conjunction with
dedicated outdoor air systems (DOAS) to provide ventilation air (and in many cases latent
cooling) to individual zones. The ATUs could be single-duct VAV, dual-duct, or fan-powered.
Single ATUs can work in parallel with sensible cooling devices (e.g., passive chilled beams,
radiant cooling ceilings) to handle latent loads and meet ventilation requirements. Dual-duct
ATUs can blend ventilation air with conditioned building air to meet ventilation requirements.
Series-fan-powered ATUs designed with chilled-water sensible cooling coils on the induction
inlets are specifically designed to work with DOAS applications. The chilled-water coils are
intended to perform sensible cooling only, thus the entering chilled-water temperature should be
warm enough to prevent condensate formation. The entire zone latent load is satisfied by an
outdoor air handler providing preconditioned air to the fan-powered chilled-water ATU.
Single-Duct ATUs. Benefits: Typically produce very low sound levels and can be used for
both VAV and CV applications. With the addition of an inlet-mounted thermistor, these units can
also provide VAV heating and cooling from a central air handler.
Limitations: The central air handler must provide adequate inlet
static pressure to supply air to the box, overcome any pressure drop of the unit and any
integral coils, and move air to the zone. Any heating coils integral to the unit must be treated
as reheat. Only remote heating devices located in the occupied space such as finned-tube
elements or radiant panels that could be operated by unit controls would be treated as heat.
Dual-Duct ATUs. Benefits:
Allow centralized heating and cooling in the facility. They can provide very high comfort at
relatively low sound levels.
Limitations: Dual-duct systems generally have higher initial costs
and operating costs.
Series Fan-Powered ATUs. Benefits: Make use of
free heat in the form of return air for reduced heating requirement. Typically provide constant
air motion and low noise levels in the zone for improved air circulation and occupant comfort.
The constant fan operation recirculates return air from the plenum, returning unvitiated air and
reducing outdoor air requirements. Low inlet static pressure requirements can reduce fan energy
at the air handler. Energy savings can be maximized with electronically commutated motor (ECM).
Fans with ECMs can modulate the supply air based on zone sensible load, reducing the amount of
plenum air sent to the occupied space during cooling and nearly eliminating motor heat in the
supply air stream (John et al. 2018). Unit fan allows night setback heating capability on a
zone-by-zone basis without need to operate the air handler during unoccupied mode.
Limitations: Some states still allow permanent split
capacitor (PSC) motors to be used. Such applications send excess plenum heat to the space in
cooling. PSC motors are not efficiently modulated and are difficult to control when attempting
to track part-load conditions.
Parallel Fan-Powered ATUs. Benefits. Make use of free heat in the form of return air for reduced
heating requirement. Fan only runs during heating and dead band modes, and fan is sized to only
handle heating airflow. Unit fan allows night setback heating capability on a zone-by-zone basis
without need to operate the air handler during unoccupied mode.
Limitations: VAV turndown must be considered when selecting
diffusers. Sudden changes in airflow cause noticeable changes in sound levels in the space,
which is generally annoying to occupants. Casing and backdraft damper air leakage during cooling
severely affects overall efficiency of these units (Sardoueinasab et al. 2018) and measurably
limits the amount of heat to be reclaimed in the ceiling plenum.
Fan-Powered Chilled-Water ATUs with Sensible Cooling
Coils. Benefits: Make use of free heat in
the form of return air for reduced heating requirement. Typically provides constant air motion
and sound level in the zone for improved air circulation and occupant comfort. Low inlet static
pressure requirements can reduce fan energy at the air-handling unit. DOAS allows for reduced
ventilation air volumes. Energy savings can be maximized with ECMs. Unit fan allows night
setback heating capability on a zone-by-zone basis without need to operate the air handler
during unoccupied mode.
Limitations: Units must be selected and operated to keep local
cooling 100% sensible. Units should not be allowed to condense water on the coils.
Sizing ATUs. For primary air inlets, select an inlet
size that meets the minimum and maximum airflows desired from the recommended primary airflow
range table in the manufacturer’s catalog. Selecting terminals near the top of their range
increases velocity, sound, and air handler fan energy. Oversizing single-duct terminals reduces
control accuracy and stability, and may result in higher sound levels. Transducer fidelity at
the low end varies by manufacturer and must be considered in combination with the airflow sensor
signal at the minimum airflow rate when selecting an inlet size. To maximize performance, size
the terminal’s maximum airflow limit for 70 to 85% of its rated capacity (approximately
10 m/s) in accordance with the catalog recommendations. For accurate control, the
minimum setting guideline should not be lower than 2 m/s inlet neck velocity for
units using inlet velocity sensors. Other minimum guidelines may apply for units with specialty
controls.
Select terminals based on recommended air volume ranges. A pressure-independent terminal’s
main feature is its ability to accept factory-recommended minimum and maximum airflow limits
that correspond to the designer’s space load and ventilation requirements for a given
zone. A common misconception is that oversizing a terminal makes the unit’s operation
quieter. In reality, the oversized terminal damper must operate in a near-closed condition most
of the time, which may actually increase noise levels to the space. Control accuracy may suffer
because the terminal is only using a fraction of its total damper travel or stroke. In addition,
the low inlet velocities may be insufficient to produce a reliable signal for the velocity
pressure measuring device and reset controller. This means minimum settings may not hold, with a
resultant loss of control accuracy and undesirable hunting.
Oversizing the discharge duct may create low static conditions, requiring the fan to operate
outside its recommended operating range.
Oversizing terminals with electric heat can lead to insufficient total pressure, which can
occasionally trip the airflow safety switch.
Environmental Factors. Environmental factors play an
important role in system selection. They include the climate and air conditions both indoors and
outdoors. They also include legislative requirements such as outdoor air ventilation rates and
local building codes. When high ventilation rates are required, such as in critical hospital
spaces and clean rooms, reheat is often required to maintain human comfort. Fan-powered ATUs are
usually used in noncritical spaces where the thermal load changes significantly and heating is
required. Single-duct ATUs are frequently applied in the interior, where the thermal load is
normally stable.
Building Use. Before specifying equipment types, the
designer must consider the building’s intended use. Office buildings with daily
operational schedules frequently use fan-powered ATUs. Usually, fan-powered ATUs with auxiliary
heaters (supplementary heat) are used in perimeter zones; these units allow the greatest
flexibility for individual zones while also allowing the central system to be turned off during
unoccupied periods. During unoccupied periods, the fan-powered ATUs maintain the minimum or
setback temperature levels without the help of the central air-conditioning equipment.
In institutional, medical, or campus buildings, systems that provide pressurization differences
between interior areas may be required.
Buildings with centralized heating and cooling plants sometimes use dual-duct ATUs.
Building Size. In large buildings, central air
handlers deliver large quantities of air to many zones with different needs. Interior zones may
not require heat; therefore, they may be served by single-duct or fan-powered ATUs with no heat.
Unless the building is located in a mild heating climate, the perimeter zones require heat,
typically electric or hot water. These are usually included with the ATUs, but sometimes
separate heating systems are used (such as baseboard heat). The static pressure in the ducts
should be lowered to the minimum pressure in accordance with ASHRAE Standard 90.1, which allows at least one VAV damper to remain near
full open. Interior zones in these buildings can use fan-powered ATUs to keep the static
pressure low. Buildings with parallel-type fan-powered ATUs usually use single-duct ATUs in the
interior zones and require higher system static pressures.
In small buildings, such as shopping malls and other low-rise buildings where each tenant area is
small, it is common to use small packaged air conditioners. If ATUs are used on these systems,
single-duct or bypass units are usually selected. A variation of this system, variable-volume
variable-temperature (VVT), uses pressure-dependent single-duct units with a main bypass air
valve in the supply duct. The bypass damper is regulated by static pressure in the supply duct.
A near constant pressure can be maintained, allowing the packaged units to operate at constant
volume and the individual zones to be pressure-dependent VAV.
Building Controls. The type of control system depends
somewhat on the size and type of building.
-
Electric controls are pressure dependent
where the air valve responds to a single control input. For example, the thermostat
sends a signal to the air valve to open or close based solely on room sensible
temperature.
-
Pneumatic controls are usually used for
building renovation or expansion where the base building already has a pneumatic
system installed. They can be pressure dependent or independent. They require
regular system maintenance and may need to be periodically rebalanced.
-
Analog controls are often applied to
smaller buildings that do not have a building automation system. Typically, these
controls do not communicate with other zones or other equipment in the building.
-
Digital controls are typically used on
buildings that have a building automation system. These controls provide individual
zone control and communication to the building management system.
Cost Factors. Consider costs before finalizing system
selection. Installation, operation, and maintenance all contribute to total cost. Often, one of
these costs overrides the others. Electric heaters usually have a lower installed cost than
hot-water coils, but they may have a higher operating cost. Research local utility rates and
building codes to arrive at the correct decision before making the final selection.
Acoustical Considerations. ATUs and room air
distribution devices are typical sound sources. However, they are not the only equipment
affecting room acoustics. See Chapter 49 of this volume,
Chapter 4 of ASHRAE (2017b), AHRI Standard 885, and other standards
for guidance on space acoustics. Broadcast studios, theaters, libraries, and other acoustically
sensitive applications require careful consideration, because equipment selection and location
are important. Radio-frequency interference (RFI) and electromagnetic interference (EMI) should
also be considered when designing broadcast studios.
Sound levels are affected by primary air valve and/or fan-generated sound. The maximum sound
generated by a given primary air valve size is determined by the difference between the highest
inlet static pressure and external static pressure at the design cooling airflow for a
non-fan-powered ATU and parallel fan-powered ATUs. For series fan-powered ATUs, the highest air
valve sound level usually occurs at the highest inlet static pressure; however, the fan usually
sets the room noise levels for series ATUs. To determine fan noise levels, fan airflow (adjusted
within its range by the speed controller) and external static pressure conditions are required.
Acoustical performance data are presented in formats for both the parallel and series ATUs,
because their sequence of operation differs. With a parallel ATU, air valve and fan operation
are evaluated separately. With a series ATU, air valve and fan are evaluated together. Series
fan-powered ATU sound levels are more consistent compared to ambient background sound levels
than those of the parallel fan-powered ATU, which has a cycling fan.
From the performance data, determine the sound power levels and predicted room noise criteria for
discharge and radiated paths under the appropriate operating conditions. Use care, because some
published room noise criteria are based on certain path attenuation assumptions that may not
correspond to specific applications. To minimize these differences, AHRI Standard 885, Appendix E, provides specific values to apply to sound
power levels for NC calculations. These may not match any specific space, but yield comparable
NC values between different manufacturers. For a complete description of these processes, see
AHRI Standard 885 and Chapter 4 in ASHRAE (2017b). Both of these sources provide guides to apply specific attenuation
values for a specific space to predict actual room noise criteria. However, the attenuation
values depend on the room furnishing and finish, as well as the sound power levels generated by
the ATU.
It is necessary for the architect and the engineer to recognize all factors in the building
specifications that affect sound attenuation. This is necessary to properly evaluate the room
noise criteria and ensure the finished levels do not exceed the design goal in the occupied
space. An ideal specification identifies maximum allowed discharge and radiated sound power by
octave band, rather than just catalog based NC values.
A sound-sensitive occupied space (e.g., conference room, private office, music studio, concert
hall, classroom) may require more discharge sound attenuation than less sound-sensitive spaces.
Usually some internal lining in the discharge duct can accomplish this. Occasionally, a
discharge attenuator or silencer may be attached to the ATU. Care must be taken to not increase
the discharge pressure enough to increase fan speed, generating additional noise that may be
greater than the attenuated value.
Installation and Operational
Considerations
Space Restrictions. During design, try to ensure that
terminals are located for ease of installation, optimum performance, and maintenance
accessibility.
Optimizing Inlet Conditions.
-
The type of duct and its approach may have a large and adverse impact on both
pressure drop and control accuracy. Although multipoint velocity pressure measuring
devices can compensate to a large degree, good design practice should always
prevail. Wherever possible, a straight duct inlet connection with a minimum length
of three duct diameters and the same internal diameter as the inlet should be
provided. Flex duct runouts at the ATU inlets are generally good attenuators.
-
Terminal collars are undersized to suit nominal ductwork dimensions. The inlet duct
slips over the terminal inlet collar and is fastened and sealed in accordance with
job specifications. Never insert a duct inside the inlet collar, or control
calibration will be adversely affected.
-
Sometimes space restrictions make it impossible to provide an ideal inlet condition.
In this case, field adjustment of the airflow settings may be required to compensate
for error in the flow measurement. Using flow-straightening or velocity equalizing
devices (equalizing grids) is recommended after short-radius elbows that are
immediately ahead of the terminal and where terminals are unavoidably tapped
directly off the main duct. Use of these devices typically increases sound levels.
-
The balancing contractor should validate flow rates as best as possible. See ASHRAE
Standard 111.
Zoning Requirements. Correctly sizing terminals with
regard to the physical conditions of the occupied space is vital to ensure acceptable
performance. One large terminal serving a space with divided work areas may result in the single
thermostat only providing acceptable temperature control for the area where the thermostat is
located. The other area(s) served may be too cold or too hot if they have differing space load
requirements.
Optimizing Discharge Conditions. Poor discharge duct
connections may have an adverse effect on pressure drop. Try to avoid installing tees,
transitions, and elbows close to the unit discharge. Avoid long runs of flex, and keep short
flex runs as straight as possible. Make curves as shallow as possible, and ensure that the
entrance condition to diffuser outlet is straight. Discharge ducts should be designed for a
maximum velocity of 5 m/s. Flex duct runouts at the diffuser inlets are generally a
good attenuator.
Compliance with Applicable Building Codes. Some local
jurisdictions have more exacting codes than the minimum requirements of national codes and
standards such as the International Code Council’s (ICC) International Building Code® (IBC). One example is the
primary fusing required of the power circuit in some areas.
Power Source Compatibility. Terminals with an
electrical power supply (e.g., fan-powered terminals, single-duct terminals with electric heat)
should be checked for compatibility with source. Voltage, phase, and frequency must match.
Fan Interlocks. Typically, series fan-powered ATUs are
designed to run continuously. Usually, they are energized only during occupied periods or when
needed for emergency heating during unoccupied periods. Use care to interlock the unit fan with
building’s air handlers to ensure that the ATU fans start during occupied periods.
Series-unit fans should be started prior to the air handler to prevent backflow into the plenum
and backward rotation of the fan.
Fan Shift in Fan-Powered ATUs. Before adjusting the
fan, the possibility of fan shift must be considered. This occurs when the blower is subjected
to variations in pressure or airflow patterns. As the primary airflow changes, pressure drop and
changes in local jets may cause the fan to shift its performance as it rides the fan curve.
Consequences vary from building to building and zone to zone. Noise levels may change greatly as
the volume changes, and this may be annoying. Design ventilation rates can also vary, sometimes
by more than 20%. This can be aggravated by undersizing the ATU.
Avoiding Excessive Air Temperature Rise. ATUs with
electric or hot-water reheat coils should be designed to satisfy load conditions, but attention
should be paid to the temperature differential Δt between the
supply air temperature and room air temperature. Hart and Int-Hout (1980) and Lorch and Straub
(1983) recommend a maximum Δt of 8.5 K to avoid
possible stratification when heating from overhead caused by the excessive buoyancy of the warm
air. This ensures good room mixing and temperature equalization. Exceeding a Δt of 8.5 K requires an increase of 25% in the ventilation
air per ASHRAE Standard 62.1. Absolute maximum discharge air
temperature is 49°C. Although this temperature will probably keep the equipment
on line, it will not provide comfortable temperatures in the space.
Correctly Supporting Terminals. Although the basic
single-duct terminal is light enough that it usually can be supported by the ductwork in which
it is installed, these units should be independently supported. When accessory modules such as
heating coils, attenuators, or multiple-outlet plenums are included, the assembly must be
supported independently. Larger terminals such as fan-powered ATUs should always be
independently supported, secured to building structure, and may require isolation mounting. Be
careful not to block access panels with straps, thread rods, or trapeze supports. Be sure to
comply with all building and local codes regarding seismic restraints (see Chapter 56).
Minimizing Duct Leakage. To prevent excess air leakage
and minimize energy waste, all joints should be sealed with a UL-approved duct sealer. Most
leakage can be avoided by practicing good fabrication and installation techniques, particularly
upstream of the terminal, which may be required to hold significantly higher pressures than
downstream of the terminal.
Acoustic Design and Installation. To help ensure an
acceptable room noise level in the occupied space, engineers can minimize the sound contribution
of air terminals by taking into account the following precautions:
-
Avoid locating terminals near return air openings or light fixtures to decrease the
potential of direct paths for radiated sound to enter the space without the benefit
of ceiling attenuation.
-
To avoid possible aerodynamic noise, keep airflow velocities below 5 m/s
in branch ducts, and below 4 m/s in runouts to air outlet devices.
-
Design systems to operate at low (minimum) supply static pressure at the primary air
inlet. This reduces the generated sound level, provides more energy-efficient
operation, and allows the central fan to be downsized. Excessive static pressure
generates noise.
-
Use of metal ducts before the inlet can reduce breakout noise from the air valve.
Between the ATU and the air outlet, flexible duct can be more effective than lined
duct at reducing ATU noise. Flexible duct can also generate sound if bends or
sagging are present. Sometimes, flexible couplers can reduce vibration passed from
the ATU to the duct connections.
-
Select air valves in ATUs to operate at or below 10 m/s or less. Larger
inlets reduce velocity (and therefore noise) in low-pressure applications, but may
increase noise in higher-pressure applications. For fan-powered ATUs, lower fan
speeds generally produce lower sound levels, but care must be taken to ensure that
the minimum airflows are met. Sound emissions are sometimes lower when fan-speed
controllers are used to reduce fan rotational speed rather than using mechanical
dampers to restrict airflow. AC induction motors can generate pure tones that are
unacceptable when thyristor controls are used. Mechanical dampers will not reduce
fan rotational speeds or sound levels when applied to systems with ECMs.
-
When required, locate terminals above noncritical areas that are less sensitive to
noise, such as corridors, copy rooms, or storage/file rooms. This isolates critical
areas from potential radiated noise. Locating fan-powered series ATUs closer to the
mechanical room increases the amount of heat and unvitiated air that can be
reclaimed.
-
Locate terminals in the largest ceiling plenum space available to maximize radiated
noise reduction. Install ATUs at the highest practical point above ceiling to
optimize radiated sound dissipation.
-
When required, locate ATUs to allow use of lined discharge ductwork to help attenuate
discharge sound.
-
In large spaces, consider using a larger number of smaller air outlets to minimize
outlet-generated sound.
-
Insulated flexible duct on diffuser runouts reduces room noise levels.
-
Using ceilings with a high sound transmission loss classification helps reduce
radiated sound.
Maintenance and Accessibility.
Typical Applications. Terminal units are typically not easily
accessible after building occupation; they should be selected and located with consideration for
required maintenance. Review the applicable building codes (e.g., ICC [2009]) for required
access. Fan-powered ATUs do not require filters, per section 307.2 of International Code
Council’s (ICC) International Mechanical Code®
(ICC 2018) and ASHRAE Standard 62.1. Many fan-powered terminals are
manufactured with construction filters that must be removed after construction is complete and
are not suggested to be replaced.
Critical Environments. Some applications, such as cleanrooms and
operating theaters, require high levels of reliability from ATUs because of the difficulty and
cost associated with servicing or maintaining the equipment. In a cleanroom, for example, if the
ceiling must be opened, the space may require disinfection before it can be used again.
Associated costs might include lost production time as well as the cost for wipedown and/or
disinfecting the room and/or equipment. In cases like these, consider locating the equipment
outside of the clean space or using highly reliable, very-low-maintenance, very basic equipment
and controls. ATUs may require access to internal components for cleaning in the case of
contamination.
Fan Airflow Control of Fan-Powered
Terminal Units
Fan-powered ATUs nearly always use single-phase motors, either ECMs, PSC motors with electronic
fan speed control (sometimes called wave choppers,
thyristor controllers, or silicon-controlled rectifiers [SCRs]), or PSC motors
with three-speed switches combined with electronic fan speed control.
Electronically Commutated Motor (ECM). Currently,
ASHRAE Standard 90.1 and ICC’s 2021 International Energy Conservation Code® (IECC) require
ECMs in fan-powered ATUs. ECMs provide superior controllability. They can be
pressure-independent devices that calculate airflow, and can respond to a signal from a local
controller or a remote signal from the building management system (BMS).
Electronic Fan Speed Control (PSC Motors). Electronic
fan speed controls use a thyristor to adjust the fan’s electrical input ac voltage. This
is called phase proportioning or wave chopping. Some units may suffer from large changes
in amp draw that significantly affect the motor efficiency and operating characteristics. The
PSC motor is a pressure-dependent device with a single setting.
ECM versus PSC in Parallel and
Series Fan-Powered ATUs
ECMs provide significant energy savings over PSC motors, especially in part-load conditions
(Edmondson et al. 2011). The part-load savings are primarily achieved by reducing airflow and
taking advantage of the increased fan efficiency at below-design airflows. PSC motors have a
limited amount of turndown available, but they also lose efficiency at or sometimes above the
savings that can be achieved by the blowers. ECMs have a very small decrease in efficiency when
they are operating at reduced speeds, and consequently they allow for nearly all of the improved
blower efficiency to be captured in the operating system costs. PSC motor inefficiency manifests
itself in the motor heat that is added to the supply air. Generally, PSC motors in fan-powered
VAV ATUs can add 0.6 to 1.7 K to the airstream (Davis et al. 2007).
Nameplate Ratings. UL Standard 1995 covers fan-powered ATU nameplate ratings. This standard
relates to equipment manufacturers and not field issues (which are covered in international and
local codes). Nameplate ratings on the unit usually do not match the nameplate ratings on the
motor. Amperage can be above or below the motor nameplate. Differences between the motor label
and the unit label may be significant in some cases. Refer to the unit nameplate ratings and not
the motor nameplate ratings when determining supply circuit requirements. These ratings are set
at the safest possible condition. Static pressure and set points vary on each unit, so
performance may not match what is on the unit nameplate.
Series. At typical design airflows, the ECM uses about 70% less
energy than the PSC (Edmondson et al. 2011). At reduced airflows during part-load conditions,
the overall energy savings is greater. Additionally, the reduced plenum air during cooling saves
as much or more energy than the motor due to reduced cooling requirements.
Parallel. Default programming in digital controllers run the fan in
the parallel ATU during dead band and heating. Because both conditions can suffer from
overcooling in the occupied zone due to cold air supplying the required outdoor airflows, the
PSC motor heat is used to augment the heat in the induced air to the zone. If ECMs are used,
heat may need to be supplied from some other source to offset the overcooling potential during
dead band and short cycling during heating. The heat source may be more efficient than the PSC
motor heat generation, but overall energy savings is nearly negated by the motor heat loss.
Series. Most direct digital controllers (DDCs) provide an optional
output that may be used for controlling fan airflow by the BMS if an ECM is used. This allows
dynamic fan volume control, which may be either modulating or multiple-speed operation from a
single-speed motor. The fan must be sized to match the maximum airflow to be supplied to the
zone.
The sequence for series constant volume is as follows:
the fan runs constantly at maximum design fan airflow during all occupied periods. On a call for
cooling, the controls modulate the primary air valve toward maximum airflow, delivering primary
air to the mixing chamber. If the fan is set at the same airflow as the primary air at maximum
cooling, no air is induced from the plenum. If the fan is at a higher airflow than the primary
air (e.g., as in a low-temperature application), air is constantly induced from the plenum.
As cooling demand decreases, the primary air valve modulates toward minimum airflow, reducing the
flow of primary air into the mixing chamber. This increases the volume of warmer induced air
into the mixing chamber. The increased percentage of induced plenum air causes the discharge
temperature to rise to approach the plenum temperature, taking advantage of recaptured heat. Figure 28 demonstrates
operation of a typical series constant-volume ATU (Reid et al. 2016).
On a call for heating, the controls automatically energize the supplemental heat (optional
equipment), which can be either electric or hot-water coils. The discharge temperature increases
as heat is applied. As the temperature increases in the zone, the sequence reverses.
For series variable volume, the sequence is the same,
except that the fan modulates.
As cooling demand decreases, the primary air valve and the fan modulate toward minimum airflow
with the primary air valve reducing airflow more quickly than the fan.
On a call for heating, the fan modulates toward maximum heating airflow set point. On a further
increase in heating demand, the controls energize the supplemental heat (optional equipment),
which can be either electric or hot-water coils. Figure 29 illustrates
the operation of a typical series variable-volume ATU (Yin et al. 2018); see ASHRAE Guideline 36 for control sequence.
Parallel. In the heating and dead-band modes, the fan supplies a
relatively constant volume of induced air to the space. The fan must be sized to supply the
required heating airflow to the zone, which requires overcoming the pressure created in the
mixing chamber caused by the inclusion of primary air. Figure 30 shows the
operation of a typical parallel constant-volume ATU (Yin et al. 2016).
Parallel Variable-Volume Sequence. On a call for cooling, the
controls modulate the air valve toward maximum airflow while the fan is off. Variable-volume,
constant-temperature air is then discharged into the space. On a decreasing call for cooling,
the sequence reverses.
In dead band, the controls energize the fan. Fan air and primary air are blended in the mixing
chamber on the fan’s discharge side. The increased plenum air causes the discharge
temperature to rise. Constant-volume, constant-temperature air is delivered to the space.
On a call for heating, the controls automatically energize the supplemental heat (optional
equipment), which can be either electric or hot-water coils. Figure 31 shows the
operation of a typical parallel variable-volume ATU (Yin and O’Neal 2018).
Fan-powered VAV ATUs take advantage of typical VAV savings at the air handler and chiller during
cooling periods, and even more savings are realized when heating is required. Fan-powered
terminals induce warm plenum air from the ceiling and blend it with the primary air at minimum
ventilation requirements. This recaptures much of the heat created in the zone and plenum. If
additional heating is required, supplemental heat is added to the sequence, thereby complying
with ASHRAE Standard 90.1 during the heating sequence. The unit
saves energy by warming blended air, for example, at 22°C rather than reheating
primary cooled air at 13°C, saving the cost of 9 K at the heating
airflow. According to ASHRAE research project RP-1292 (Davis et al. 2007; Furr et al. 2007),
there is very little difference in total building energy use between series and parallel units
when both are equipped with permanent split-capacitor (PSC) motors. However, each type of unit
consumes that energy in different ways. ASHRAE (2017b) explains these differences in greater
detail.
Series. Series units are designed for very low inlet static
pressures. This saves energy at the air handler compared to a parallel unit for a similar zone.
RP-1292 identified the PSC motor as the biggest energy user in a series unit (Davis et al. 2007;
Furr et al. 2007). The fan energy raises the air temperature across the motor by 0.6 to
1.7 K. When modeling energy consumption for this unit, it is important to model the
energy consumption and heat generated by the fan motor for both unoccupied and occupied periods
(Davis et al. 2007; Furr et al. 2007). This means that total energy use can be reduced if the
fan energy is reduced. Using ECMs can significantly increase motor lifetimes and provide
significant energy savings. Warm air induced from the plenum at part load conditions increases
the cooling requirement because of the increased air temperature in the mixing chamber of the
ATU. The combination of motor and plenum heat can equal or exceed the energy consumed by the PSC
motor.
Because the fan cabinet is neutral or negative during operation, the casing leakage does not
affect energy consumption of series units. All the primary air injected into the unit is
delivered to the occupied zone. This causes ceiling plenum temperatures to be warmer for
installations with series units than those with parallel units, and more heat can be reclaimed
from the ceiling plenum when the unit is in heating mode.
Parallel. More energy is required at the air handler in a parallel
ATU system due to the higher inlet static pressure requirement. When just one duct path is
designated as the critical path for static pressure set point, system pressure (and thus energy
usage) can increase compared to a building with series units. However, ASHRAE Standard 90.1 procedures reset the system static pressure to always
drive at least one VAV air valve to its nearly full-open position, making the increased static
pressure required for parallel units lesser.
According to RP-1292, the largest single energy usage is leakage in the parallel unit even with
dynamic reset at the air handler (Davis et al. 2007; Furr et al. 2007). Leakage is typically
between 5 and 12% of the total primary airflow through the parallel unit, and it is highest at
full cooling. This does not account for other casing leakage like seams and penetrations. Thus,
parallel units may need to be oversized to cover the total load to the occupied zone. Due to the
leakage, ceiling plenums are cooler with parallel units than with series units, reducing or
eliminating the amount of free heat that can be reclaimed in heating mode. Per ASHRAE (2017b),
casing leakage was calculated at $3.91 per L/s per year. When modeling energy
consumption for this unit, it is important to model casing and backdraft damper leakage as well
as fan energy consumption for both the ATU and the air handler during operation. Motor heat
should also be included in heating mode calculation.
Since the motor runs in dead band and heating modes, any heat generated by the motor is delivered
to the occupied space. Because of this, using more efficient motors (which run cooler) will not
measurably improve the unit’s energy consumption.
Inlet Static Pressure Requirements
Series. The inlet static pressure is the pressure required to push
the conditioned air across the air valve into the mixing section.
Parallel. The inlet static pressure is the pressure required to push
the conditioned air across the damper, through the mixing section, through the discharge duct,
and across the diffuser(s) into the space.
Sizing Fan-Powered Terminals
Selection of fan-powered ATUs involves three elements: primary inlet, fan size, and heating coil.
Selection of these elements and their interactive effects determine the overall performance of
the units.
Primary Air Inlet Selection. See the section on
Single-Duct Primary Air Inlet Selection. Note: casing leakage is an
important issue for parallel fan-powered ATUs and must be taken into account when determining
actual airflow supplied to and from the ATU.
Fan Size. Series fan-powered ATUs require the fan to
be sized to handle the maximum design airflow. Fan airflow must be at least equal to primary
airflow to ensure the mixing chamber in the terminal does not become positively pressurized,
resulting in primary air short-circuiting into the ceiling plenum through the induction port(s).
The external static pressure requirements are the sum of the ductwork and diffusers at design
airflow plus an applicable hot-water coil or electric heater and optional filter, if required.
When fan airflow and external static pressure have been determined, select the fan size from the
fan curves provided by the manufacturer. Upsizing the fan and operating it at a reduced speed
can result in quieter operation, but pay attention to fan stability at very low airflows.
Parallel fan airflow is determined by calculating the difference between the total discharge
design heating airflow and minimum primary airflow. If minimum airflow is zero, then fan airflow
is the heating airflow. In most applications of a parallel ATU, a minimum primary airflow is
required to meet ventilation requirements. This primary airflow contributes to the total
external static pressure experienced by the fan and should be accounted for along with all
components, such as heaters, ductwork, diffusers, and optional filters.
Heating coils on ATUs are generally either electric or hot water coils. Sometimes steam may be
used. Electric heaters are always encased for safety. Water coils may or may not be encased.
Heating coils on single-duct ATUs are located on the discharge where the duct is attached. They
are almost always not encased and are generally sized to be the same size as the discharge duct.
If the ATU is internally lined, the internal diameter of the ATU will be smaller than the coil
face area. Multiple outlet plenums or silencers may be mounted downstream of the coil. Sometimes
the coils are mounted at the discharge end of the silencers. Access doors may be located
upstream and/or downstream of the coils. Heating coils on single-duct ATUs are always reheat
coils and must be designed to heat the air from the leaving air temperature at the air handler
to the desired entering air temperature at the occupied space. Heating coils are usually either
electric or hot water finned tube type.
Heating coils on series fan-powered ATUs are mounted on the discharge where the duct is attached.
If the ATU is properly controlled, these coils provide supplemental heat and not reheat. Water
coils may or may not be encased. Discharge ducts may have access doors to allow access to the
coil. Coils should be designed to heat the mixed air in the ATU mixing chamber. The mixed air is
a blend of the minimum primary airflow and the induced plenum air at the point where the heater
is energized.
Heating coils on parallel fan-powered ATUs may be mounted on the discharge of the unit or at the
induction inlet upstream of the fan. Heating coils on the induction port must be sized to heat
the fan airflow to a temperature high enough to mix with colder primary air, achieving the
required entering air temperature for the occupied space. The resulting air temperature must not
exceed that of the motor(s) rated operating temperature. Coils mounted on the ATU discharge must
be sized to heat the blended air from the mixing chamber to the required leaving air
temperature. On ATUs with coils on their discharge, discharge ducts may have access doors to
allow access to the coil. Coils may or may not be encased.
To avoid compromising zone ventilation effectiveness (ASHRAE Standard
62.1), the discharge temperature should not be more than 8 K warmer than the room
temperature it serves.
Use manufacturers’ catalog data or ASHRAE (2017b) for details on sizing coils.
Additional Fan Guidelines
When selecting a unit for a particular set of conditions, ensure that the air delivery is
designed to meet the room’s sound criteria and the system’s static requirements.
Specific sound data are provided by manufacturers for various airflow deliveries for each unit
and should be the guiding factor in selecting unit sizes. Avoid selecting equipment near the
maximum or minimum of the fan curves. Selecting fans at these points may limit flexibility for
future changes. When designing air systems and using fan-powered ATUs, it is important to match
the fan air and primary air capacities to the space requirements. Series units require precise
adjustment of fan airflow in relation to the primary air to ensure proper discharge air
temperatures and to protect against short circuiting of primary air into the plenum.
ATUs for Cold-Air Systems. These systems often involve
ice storage and can provide supply air typically colder than 9°C, below that
supplied by conventional systems. To reduce the chances of condensation on outer surfaces, keep
the following in mind:
-
Select insulating materials with vapor barriers to provide adequate thermal and
moisture protection throughout the cold-air path. Internal and external insulation
must be sufficient to prevent any outer exposed surfaces from dropping below the
dew-point temperature of the surrounding environment.
-
Single-duct, dual-duct, and parallel fan-powered ATUs have a higher potential for
downstream condensation because they handle the coldest air during cooling
operation.
-
Series fan-powered ATUs have the lowest potential for condensation because, in most
operations, they mix warmer return air with primary air (i.e., air delivered to the
ATU through supply duct to satisfy all or part of ventilation, latent, and sensible
load). Fan-powered series flow ATUs are sometimes used to mix return air during
occupied mode to deliver supply air at more conventional temperatures to the
occupied space. This may help to avoid occupant comfort issues caused by excessive
vertical drop from air outlets, and possible condensation at outlet devices.
Several other design and operational considerations can also minimize the possibility of
condensation and related issues:
-
Ceiling plenum returns are recommended for cold-air systems. Return air circulating
throughout the ceiling plenum can prevent uncontrolled humidity or temperature
extremes that can occur in attic spaces of fully ducted systems.
-
To control humidity and prevent condensation problems, it is always good practice to
limit outdoor air infiltration. Design and construct buildings to operate under
positive pressure, and limit the amount of uncontrolled outdoor air that infiltrates
occupied and unoccupied spaces.
-
Cold-air systems should follow start-up procedures that gradually reduce the supply
air temperature. This prevents moisture trapped in new construction or previously
unoccupied buildings from condensing and possibly causing damage to ceilings and
other finished surfaces.
ATU Critical Environment Considerations. Hospitals,
cleanrooms, and laboratories pose special challenges. Protective isolation spaces such as
operating rooms, bone marrow transplant patient rooms, immunocompromised patient areas, and
cleanrooms require positively pressurized environments. Infectious isolation spaces such as
tuberculosis patient rooms require negatively pressurized environments. See ASHRAE Standard 170 for details on room pressurization, Chapter 9 for specifics on health
care requirements, and Chapter 19 for details on clean spaces.
Hospital rooms and cleanrooms frequently require constant high ventilation rates, which tend to
favor single- or dual-duct ATUs. Pressure-independent, variable-speed motor technology has led
to the development of fan-powered pressurization units.
To minimize entrainment of fibers into the airstream, either do not use internal insulation or
use nonfibrous liners in the ATUs and duct systems. Insulations can be isolated from the
airstream by metal, foil, or polymer liners inside silencers and ATUs. All of these liners have
different thermal, acoustic, and other physical properties and should be evaluated for each
application.
See Chapter 12 of ASHRAE (2017b) for more information on health care facilities.
Designers have various fan-coil systems to choose from when designing a building. Choosing which one
to use depends on meeting the owner’s needs for installation, application considerations,
first cost, and cost of operation. The designer must consider performance, capacity, reliability and
spatial requirements and restrictions. The following guidelines describe different types of fan-coil
equipment and their general uses, restrictions, and limitations.
Fan-Coil Types. Vertical
Stack: A vertical stack fan-coil uses a fan and a water coil to condition air within
a space by regulating tempered water flow through the coil. Designed for free-blow or ducted,
concealed, or painted cabinet applications. This fan-coil model usually uses a riser piping
system to deliver the chilled and hot water to the coil. This type of unit is typically used in
high-rise hotels, condominiums, dormitories, and residential buildings.
Vertical: A standard vertical fan-coil uses a fan and a water coil to
condition air within a space by regulating tempered water flow through the coil. These units
either are concealed in the wall or have a painted metal cabinet built around them. This type of
fan-coil is commonly used in hallways, dormitories, small apartments, etc.
Horizontal (Blow-Through): A horizontal unit is normally mounted
overhead and contains a fan and a water coil to condition air in a space by regulating tempered
water flow through the coil. The fan blows air into the coil and then discharges into the space.
These units may be built in or have decorative housings installed.
Horizontal (Draw-Through): A horizontal unit is normally mounted
overhead and contains a fan and a water coil to condition air in a space by regulating tempered
water flow through the coil. The fan draws air across the coil and then discharges into the
space. These units may be built in or have decorative housings installed.
Water Piping Distribution Systems. For fan-coil units
requiring chilled and/or hot water, the piping arrangement determines the performance quality,
ease of operation, operating cost, and initial cost of the system.
Two-Pipe Changeover Without Electric Heat: In this system,
either hot or cold water is supplied through the same piping. The fan-coil unit has a single
coil. The most common system change-over scheme with the lowest initial cost is the two-pipe
changeover scheduled by outdoor temperatures. The outdoor changeover temperature is set at some
predetermined set point. If a thermostat is used to control water flow, it must reverse its
action depending on whether hot or cold water is available.
The two-pipe system cannot simultaneously heat and cool, which is required for most projects
during intermediate seasons when the morning hours may need heat and the afternoon hours likely
require cooling. In intermediate seasons when the boiler is not on, two-pipe systems without
supplemental electric heat cannot meet heating demands.
Two-Pipe Changeover with Partial Electric
Strip Heat: This arrangement can provide electric heating in some zones and cooling
in other zones in intermediate seasons by using a small electric strip heater in the fan-coil
unit. The unit can handle heating requirements in mild weather while continuing to circulate
chilled water to handle any cooling requirements. When the outdoor temperature drops
sufficiently to require heating beyond the electric strip heater capacity, the water system must
be changed over to hot water. The designer should consider the disadvantages of the two-pipe
system carefully; many installations of this type increase operational cost, and can be
unsatisfactory if climates temperatures vary widely from morning to afternoon.
Two-Pipe Nonchangeover with Full Electric Strip Heat: This system
should be closely evaluated due to the escalated operational cost of electric heat compared to
hot-water heat. It may be practical in areas with small heating requirements.
Three-Pipe Distribution: Three-pipe distribution uses separate hot-
and cold-water supply pipes. A common return pipe carries both hot and cold water back to the
central plant. The fan-coil unit control introduces hot or cold water to the common unit coil
based on the need for heating or cooling. This type of distribution is not recommended because
of its energy inefficiency and does not comply with most recognized energy codes.
Four-Pipe Distribution of Chilled and Hot Water: This system has
dedicated supply and return pipes for chilled and hot water. It generally has a high initial
cost compared to a two-pipe system. Four-pipe systems have better performance because of
all-season availability of heating and cooling at each unit, no summer/winter changeover
requirement, and simpler operation. It can be controlled to maintain a dead band between heating
and cooling during shoulder season.
Variable-Refrigerant-Flow (VRF) Systems. The zone side
of these systems is a fan-coil unit. Further information is available in Chapter 18 of the 2020
ASHRAE Handbook—HVAC Systems and Equipment.
Vertical Stack. Benefits:
These units take advantage of the multi-story feature to plumb the water piping vertically floor
to floor to conserve space.
Limitations: These units occupy floor space in the room. Because the
units are traditionally located in the space, noise can be a problem if the fan and motor are
not sized properly or if noise is not considered during design.
Vertical. Benefits: These
units traditionally condition air directly in the space. Return air is typically drawn in the
bottom and discharged out the top, directly back into the space.
Limitations: These units occupy floor space in the room. Because the
units are traditionally located in the space, noise can be a problem if the fan and motor are
not sized properly or if noise is not considered during design.
Horizontal (Blow-Through). Benefits: These units do not occupy floor space in the room, and can
be manufactured with a lower profile.
Limitations: The velocity profile may not be evenly distributed
across the cooling coil.
Horizontal (Draw-Through). Benefits: These units do not occupy floor space in the room, and
generally have evenly distributed airflow across the cooling coil, resulting in greater heat
transfer and lower noise.
Limitations: Any condensate blow-off caused by airflow over the coil
has the potential to land on electrical components, including the fan motor.
Sizing Fan-Coil Units. How fan-coil units are selected
and how they interact with the rest of the system determine the overall performance of the
units.
General Sizing Guidelines: Select fan-coil based on recommended air
volume ranges. A common misconception is that oversizing a fan-coil makes the unit operate more
efficiently. On the contrary, an oversized fan-coil reduces run times, making the room air
stratified and humidity more difficult to maintain at comfortable levels.
The recommended selection for maximizing performance is to size the fan-coil maximum airflow
limit for 70 to 85% of its rated capacity in accordance with the catalog recommendations.
Do not exceed 2.5 m/s air velocity through the coil section of a chilled-water
fan-coil. Exceeding this limit could cause condensate blow-off from the fin material,
potentially causing damage to surrounding materials and reduces the latent cooling capacity of
the unit.
Select water flow rates that will not exceed a velocity of 2.4 m/s in the coil
tubing, because this velocity can erode the copper and cause pinholes, which could result in
water leakage and potential damage to material and property.
Fan Size Selection: Fan-coil units require the fan to be sized to
handle the maximum design airflow. The external static pressure requirements are the sum of the
ductwork, diffusers, and filters at design airflow. When fan airflow and external static
pressure have been determined, select the fan size from the fan curves or the selection software
provided by the manufacturer. Vertical fan-coils with one return and one supply grille integral
to the cabinet have no appreciable external static pressure requirements. This style of vertical
fan-coil must deliver the design airflow for the application between 0 and 124 Pa.
Oversizing the fan and operating it at a reduced speed can result in quieter operation, but pay
attention to fan stability at very low airflows.
ASHRAE research project RP-1741, Understanding Fan Coil Components and How They Relate to Energy
Consumption and Energy Modeling, analyzed energy modeling of fan-coils. RP-1741 benchmarked the
energy savings from air and water modulation control relative to conventional on-off control of
hydronic fan-coil units. Similar to other HVAC equipment, hydronic fan-coil units are generally
oversized to be able to meet peak cooling and heating loads. Consequently, fan-coil units rarely
operate at their full load for an extended time. Running fans and pumps at part-load conditions
could allow energy savings. The modulation control of air and water flow based on thermal loads
can take advantage of oversized equipment and operate them at part-load conditions for energy
savings. Building energy simulation conducted in RP-1741 showed that modulation control could
save over 50% of the fan-coil units’ fan energy compared with cycling on and off.
Modulation control can also maintain an higher chilled-water ΔT
at part-load conditions, leading to over 50% savings in pump energy and more efficient chiller
staging. The total HVAC system savings ranges from 5 to 15% compared with the conventional
on-off control.
Environmental Factors: Environmental factors include the climate and
air conditions, indoors as well as outdoors. They also include legislative requirements such as
outdoor air ventilation rates and local building codes. Fan-coil units receive ventilation air
from a penetration in the outer wall or from a central air handler. Units that have outdoor air
ducted to them from an aperture in the building envelope are not suitable for commercial
buildings because wind pressure allows no control over the amount of outdoor air admitted.
Ventilation rates can be affected by stack effect and by wind direction and speed. Also, freeze
protection may be required in cold climates.
Fan-coils are, however, often used in residential construction because of their simple operation
and low first cost, and because residential rooms are often ventilated by opening windows or by
outer wall apertures, if not handled by a central system. Operable windows can cause imbalance
in a ducted ventilation air system.
When outdoor air is introduced from a central ventilation system, it may be connected to the
inlet plenum of the fan-coil or introduced directly into the space. If introduced directly,
ensure that this air is pretreated, dehumidified, filtered, and held at the room’s
temperature so as not to cause occupant discomfort when the fan-coil unit is off. One way to
prevent air leakage is to provide a spring-loaded motorized damper that closes off ventilation
air when the unit’s fan is off.
Building Size: In large buildings, where a central air handler(s) is
not practical and where individual power costs are the responsibility of each space owner, a
fan-coil is generally the system of choice for temperature and humidity control. These systems
require a central water supply and a water transport system. If the initial cost and cost of
operation of central chilled- and hot-water-generating equipment make more economical sense, the
hydronic fan-coil comfort system is a good choice.
Cost Factors: Costs should be considered before the final system
selection is made. Installation, operation, and maintenance all contribute to total cost.
Sometimes one of these costs is more important than others. Electric heaters usually have a
lower installed cost than hot-water coils, but may have a higher operating cost. Local rates and
codes should be researched to arrive at the correct decision before making the final selection.
See Chapters 13 and 46 of the 2020 ASHRAE
Handbook—HVAC Systems and
Equipment, Chapter 22 of
the 2021 ASHRAE
Handbook—Fundamentals, and Chapter 51 of this volume for more
information on piping systems.
Acoustical Considerations. Since fan coils are often located within
the occupied space, extra consideration should be given to avoid generating noise near
occupants. For fan coils located outside the occupied space, the acoustical considerations are
very similar to those of terminal units. Refer to the Acoustical Considerations portion of the
section on Terminal Units for more information.
Installation and Operational Considerations. Space Restrictions. During the design phase, ensure the fan-coils are
located for ease of installation, optimum performance, and maintenance accessibility.
Optimizing Inlet Conditions. Fan-coils should be located to optimize
the inlet return air and discharge grilles or duct work. Proper location and size of grille and
duct contribute to the overall effectiveness of air mixing and efficiency.
Locating a return grille in an area that does not properly serve the entire conditioned space can
lead to poor performance of the coil and hot or cold spots within the occupied space.
Zoning Requirements. Correctly sizing fan-coils with regard to the
physical conditions of the occupied space is vital to ensure acceptable performance. One large
fan-coil serving a space with divided work areas may result in the single thermostat only
providing acceptable temperature control where the thermostat is located. The other space(s)
served may be too cold or too hot if they have differing space load requirements.
Optimizing Discharge Conditions. Poor discharge duct connections may
have an adverse effect on pressure drop. Avoid installing tees, transitions, or elbows close to
the unit discharge. Avoid long runs of flex duct, and keep short flex runs as straight as
possible. Make curves as shallow as possible, and ensure entrance condition to diffuser outlet
is straight. Discharge ducts should be designed for a maximum velocity of 5 m/s.
Noncompliance with Local Electric Codes. Some local jurisdictions
have more exacting codes than the minimum requirements of national codes and standards such as
IBC, the National Fire Protection Association’s National Electrical
Code® (NEC®; NFPA Standard 70), UL, and Canadian Standards Association (CSA) standards.
One example is the primary fusing required of the power circuit in some areas.
Power Source Compatibility. Fan-coils with electric heat should be
checked for compatibility with source. Voltage, phase, and frequency must match. Where motor
voltage differs, the single-phase voltage requirement may have to be tapped from a three-phase
(4 wire wye) power source.
Fan Interlocks. When an electric heat source is used, a fan interlock
is required to ensure the fan is on during the call for heat.
Avoiding Excessive Air Temperature Rise. Fan-coils with electric
heaters or hot-water coils should be designed to satisfy load conditions, but attention should
be paid to the temperature differential Δt between the supply
air and room air. Exceeding Δt of 8.5 K requires
an increase of 25% in the ventilation air per ASHRAE Standard 62.1.
Absolute maximum discharge air temperature is 48.9°C per UL standards. Although
this temperature will probably keep the equipment on line, it will probably not provide
comfortable temperatures in the space.
Correctly Supporting Fan Coils. Fan-coil units should always be
independently supported and secured to building structure, using the proper isolation mounting.
Be careful not to block access panels with straps, thread rods, or trapeze supports. Where codes
require seismic restraints, be sure to comply with all building and local codes.
Minimize Duct Leakage. To prevent excess air leakage and minimize
energy waste, all joints should be sealed with a UL approved duct sealer. Most leakage can be
avoided by practicing good fabrication and installation techniques
Acoustic Design and Installation. To help ensure an acceptable room
noise level in the occupied space, engineers can minimize the sound contribution of a fan-coil
by taking into account several design considerations and by using the following guidelines for
good design practice:
-
Design systems to operate at low (minimum) external static pressure. This reduces the
generated sound level and provides more energy-efficient operation. Excessive static
pressure generates noise.
-
Between the fan-coil unit and the air outlets of a ducted system, flexible duct can
be more effective than lined duct at reducing unit noise. Flexible duct can also
generate sound if bends or sagging is present. Sometimes, flexible couplers can
reduce vibration passed from the fan-coil unit to the duct connections.
-
Select fan-coils to operate toward the middle area of their operating range. Larger
return air inlets reduce velocity across coils and hence, noise. Lower fan speeds
produce lower sound levels. Sound emissions can be lower when using an ECM motor
blower combination.
-
Whenever possible, locate horizontal fan-coils above noncritical areas that are less
sensitive to noise, such as corridors, copy rooms, or storage/file rooms. This
isolates critical areas from potential radiated noise.
-
Locate fan-coils in the largest ceiling plenum space available to maximize radiated
noise reduction. Install fan-coils at highest practical point above ceiling to
optimize radiated sound dissipation.
-
Avoid locating fan-coils near return air openings or light fixtures. This decreases
the potential for direct paths for radiated sound to enter the space without the
benefit of ceiling attenuation.
-
Locate fan-coils to allow the use of lined discharge ductwork to help attenuate
discharge sound.
-
In large spaces, consider using a larger number of smaller air outlets to minimize
outlet generated sound. Insulated flexible duct on diffuser run-outs provides
excellent attenuation performance.
-
Using ceilings with a high sound transmission loss classification will help reduce
radiated sound.
Control of Fan Coil Units
Fan Airflow Control of Fan-Coil Units. Three-speed permanent split
capacitor (PSC) motors are the standard motor option for most fan-coils.
These motors have high, medium, and low speeds. These motors are likely be phased out because of
minimum efficiency requirements in ASHRAE Standard 90.1.
The availability of electronically commutated motors
(ECMs) for fan-coil units is rapidly growing, and most manufacturers
offer a model. These motors often provide significant energy savings, improved controllability,
and wider operating range in fan-coil units.
ECM versus PSC Motors in Fan-Coil Units. Three-Speed PSC: When a PSC motor is used in a fan-coil, the fan motor
is switched on and off by a thermostat. This control scheme does not allow precise control of
temperature and humidity levels in the conditioned space, and can cause comfort issues and
increased energy cost.
Multispeed ECM: When a multispeed ECM is used in a fan-coil, the fan
motor is switched on and off by a thermostat. The control scheme can be identical to that of a
PSC but with the added benefit of a higher-efficiency motor, thus lower operating cost.
Generally, an ECM is a 24 V control, and the motor can be energized directly from the thermostat
or through a specially designed ECM fan control board, which could offer additional features.
Fully Modulating ECM: When used in the fan-coil with a more
sophisticated control (e.g., analog control or DDC), this sequence of operation can provide a
higher level of comfort and energy savings. Typically, an analog signal (0 to 10 V DC) from a
controller is used to remotely vary the speed of the ECM. The dead-band differential between no
call for heating/cooling and the energized state is generally much smaller in this type of
control scheme. The water flow can also be modulated along with airflow modulation to avoid
overcooling or overheating. This approach provides minimal swings in temperature and humidity
levels in the conditioned space, which can provide superior comfort and reduced energy costs.
Basic Control Types. Electric
Thermostat: Traditionally, the most common control type for fan-coils is a room
thermostat. These thermostats come in both line voltage (i.e., same voltage as motor) and 24 V,
which require a Class 2 step-down transformer (typically provided with the fan-coil).
When using a line voltage thermostat, the blower motor speed taps (three-speed) are connected
directly to the thermostat. In this configuration, the water control valve is also line voltage.
This type of thermostat is limited, and is generally used only on smaller motors because of
ampacity limitations and thermostat ratings. In much of the United States, these thermostat
leads must be run in a conduit between the fan-coil and thermostat.
When using a 24 V thermostat, fan relays, rated for the current of the motor, are used to switch
each speed of the motor on and off. In this configuration, the water control valve is also
typically 24 V. In most of the United States, these thermostat leads are not required to be run
in a conduit between the fan-coil and thermostat.
Analog Stand-Alone: Another control type for fan-coils is an analog
control combined with a room sensor. This control type is powered with 24 V thermostats, which
require a Class 2 step-down transformer (typically provided with the fan-coil).
An analog controller is used when the fan-coil has modulating components such as an ECM and
modulating water valves. The analog controller provides the appropriate outputs, based on room
demand, to modulate the fan and water valves, if equipped.
This type of control can provide improved comfort over a simple electric thermostat. Depending on
the features of the analog controller, the cost is generally higher than a room thermostat
without set back features.
Direct Digital Control (DDC): This control type, paired with a room
sensor, is powered with 24 V; these thermostats require a Class 2 stepdown transformer
(typically provided with the fan-coil).
A DDC controller can be used for both types of fan-coil sequences described previously.
A DDC has both digital and analog inputs and outputs. The controller is programmable to provide
many operation sequences, depending on the application. Generally, these controls can provide
anything from a simple control sequence to a more sophisticated application. In some cases, DDC
can control features and components outside the fan-coil, such as humidifiers, baseboard heat,
bathroom ventilators, or lights, and can be programmed for occupied and unoccupied modes for
energy savings.
Some DDCs can communicate through building automation systems (BASs) in several different
protocols, such as BACnet™, Lonworks™, and Modbus®.
This type of control can provide improved comfort over a simple electric thermostat or
stand-alone analog controls. Depending on the features, cost for a DDC is typically higher than
for a room thermostat or analog controls.
Basic Control Sequences. Three-Speed Motor with Two-Position Valves: Thermostats are available
with many features beyond the purview of this explanation, but the simplest sequence is as
follows.
On a call for cooling, the fan is energized at the speed (high, medium, or low) selected by the
occupant or by the thermostat. The chilled-water control valve opens fully. On reaching the room
set point, the fan de-energizes and the chilled-water control valve closes.
On a call for heating, the fan is energized at the speed (high, medium, or low) selected by the
occupant or by the thermostat. The hot-water control valve opens fully. On reaching the room
set-point, the fan de-energizes and the hot-water control valve closes. For a fan-coil with
electric resistance heat, a heater control, like a contactor or heater sequencer, is energized
on and off by the thermostat based on room demand for heating.
Consult the manufacturers’ catalog or installation and operating instructions for specific
applications.
Modulating Motor with Modulating Valves: Controllers for fan-coils
with modulating components are available with many additional features, but a basic sequence is
as follows.
On a call for cooling, the chilled-water valve opens to a position consistent with the controls
algorithm based on room demand, and the fan modulates toward the maximum cooling airflow set
point. At a full call for cooling, the chilled-water valve is wide open and the fan is at the
maximum cooling airflow set point. When approaching the room set point, the fan airflow reduces
and the chilled-water control valve modulates toward the closed position. On reaching the room
temperature setting, the valve closes completely and the fan modulates to the dead-band fan
airflow set point.
Dead Band: Fan is off or running at a minimum airflow to circulate
air through the space. On a call for heat, the hot-water valve opens to a position based on room
demand, and the fan modulates toward the maximum heating airflow set point. At a full call for
heating, the hot-water valve is wide open and the fan is at the maximum heating airflow set
point. When approaching the room set point, the fan airflow reduces and the hot-water control
valve modulates toward the closed position. Similar to the case of a fan-coil with electric
resistance heat, a heater control, like a contactor or heater sequencer, is energized on and off
by the room demand for heating. An SCR heater control can modulate the resistance heater by an
analog output from the controller similar to the hot-water valve operation described above. Figure
32 shows the operation of a typical fan-coil unit with hydronic cooling and electric
heating in modulation control.
Consult the manufacturers’ catalog or installation and operating instructions for specific
needs.
The designer must consider the intended building use when determining the type of fan-coil
equipment to be used. Fan-coil systems are best applied where individual space temperature
control or cross-contamination prevention is needed. Suitable applications are shown in Table 10.
An active chilled
beam is an air diffusion device that introduces conditioned air to the
space for ventilation and temperature control purposes. Primary air, conditioned at the air
handling unit to meet the ventilation and latent requirements of the space, is delivered through
a series of nozzles, creating induction of room air through a unit-mounted sensible heat
transfer coil. This primary air often also contributes to sensible cooling of the space and
drives the induction function through the coil. Depending on their nozzle size and
configuration, active beams typically induce two to five parts of room air for every part of
primary air they deliver to the space. When heating is required, warm water can be circulated
through the coil.
Passive chilled beams rely on the natural buoyancy of
air currents associated with convective heat sources to transport warm air to the upper portion
of the space. On contact with the beam’s integral sensible heat transfer coil, this air is
cooled and falls back into the space. Primary air must be delivered to the space via a separate
system for the purposes of ventilation and dehumidification.
Application Considerations
Chilled-beam systems must be designed to treat sensible and latent space heat loads,
provide adequate space ventilation, conform to space acoustical requirements, and maintain
occupant comfort in conformance with ASHRAE Standard 55 and other
applicable codes.
In general, chilled beams offer the opportunity to capitalize on the benefits of decoupled
ventilation systems with beam coils being responsible for most of the sensible load in the zone
and the primary air satisfying ventilation and latent load.
Benefits. Heat extraction or addition by the coil
often allows for significant reduction in primary airflow requirements over all-air systems.
Energy to transport cooling and/or heating media can be significantly reduced because of
water’s high specific heat and density. As a result, chilled-beam systems require less
space for the mechanical services, because of smaller ductwork and air-handling unit sizes. This
reduction in mechanical service space requirements may make it possible to reduce the
floor-to-floor height of a multistory building.
Water-side economizer opportunities may be extended as a result of the higher beam chilled-water
temperatures, and provide an improved selection of available system options (e.g., geothermal,
dry coolers, closed-circuit fluid coolers). Chilled-beam systems may offer opportunities to
enhance chiller efficiencies and provide broader evaporator ranges.
Chilled beams require minimal maintenance. Vacuuming the beam coils is occasionally required and
is typically guided by the needs of the space. Often, it is expected that service intervals
could extend to three to five years. The lack of moving parts in chilled beams produces an
inherently highly reliable system.
Chilled beams may be considered beneficial for the following applications/spaces:
-
Environments with moderate to high sensible heat ratios, such as offices, hotels, and
other spaces with significant imbalances between sensible loads and ventilation
requirements
-
Heat-driven laboratories where ventilation (100% outdoor air) requirements are
relatively low (4 to 8 ach) but sensible gains are often 125 to 190
W/m2, resulting in supply airflow rates in all-air systems
that are significantly higher (12 to 18 ach).
-
Hospital patient rooms where ventilation requirements severely limit the turndown
ratio with all-air (VAV) systems, and thus require significant amounts of parasitic
reheat to balance the cooling delivery with the actual room cooling demand. See
ASHRAE Standard 170 for additional detail.
-
Classrooms where outdoor air ventilation rates are significantly lower than the space
sensible cooling requirements. Chilled beams typically provide at least half of the
space sensible heat removal by way of their chilled-water coil, thus allowing ducted
airflow rates to be reduced to a level near the classroom ventilation rate. This
facilitates the use of dedicated outdoor air (DOAS) units for classroom
applications.
-
Retrofits, because of minimal mechanical space requirements, and in cases of suitable
envelope construction.
-
Passive chilled beams can provide a very efficient means of perimeter-area
temperature control when coupled with underfloor air distribution (UFAD) systems.
Limitations. Space humidity levels must be managed
closely because of the limited dehumidification capability of the primary air. This is
particularly important where operable windows are used or high infiltration levels are
encountered in a humid climate.
Chilled beams may be inappropriate for the following applications/spaces:
-
Environments with high latent gains such as kitchens, bathrooms, or locker rooms
-
Natatoriums and sauna areas
-
Poor building envelopes or buildings with unmanageable latent loads
-
Mixed-mode ventilation (operable windows) without proper condensation safeguards
The objective of chilled-beam system design is to minimize primary airflow rates. When
chilled-beam systems are applied, the minimum primary airflow rate is typically the greater of
that required for ventilation and for space dehumidification. In cases where these values are
similar (differing by no more than about 25%), consider using a dedicated outdoor air system
(DOAS). Laboratories and health care may require or benefit from the use of a DOAS, which uses
chilled beams efficiently.
In cases where the sensible cooling requirements require significantly more than the minimum
primary airflow rate, air-handling units that mix return and outdoor air volumes may be
considered for use with chilled beams.
Chilled beams are generally intended to operate without condensation. Consequently, active
chilled-beam supply water temperatures should be maintained at or above the room dew-point
temperature to prevent condensation on the coil and its supply water piping. Passive
chilled-beam water supply temperatures should be kept slightly (1.2 to 1.7 K) above
the room dew-point temperature. In both cases, the chilled-water piping must be adequately
insulated to prevent condensation on the pipe itself. Where adequate control of space humidity
levels cannot be ensured, higher supply water temperatures and/or condensation controls should
be considered. This is discussed in the following sections.
Terminal filtration and condensate pans are not required with a properly designed and operated
primary air system with chilled-water temperatures maintained above the room dew point. Heating
coils provide sensible heat only, and thus filtration and condensate capture devices are not
necessary. Chilled-beam systems designed with noncondensing (dry) coils should be treated
similarly. Beams with sensible-only cooling coils do not require filters per ASHRAE Standard 170 and section 307.2 of the International Code
Council’s International Mechanical Code® (ICC
2018).
Heating is limited to active chilled-beam systems; heating with overhead passive chilled beams is
not effective.
The hot water serving the active beam’s coil must be chosen to limit the discharge air
temperature to less than 8.5 K above the room design set point. Additionally, to
ensure proper room air distribution, the discharge velocity should be selected in accordance
with guidance presented previously.
Alternatively, resetting the primary air temperature with a duct-mounted heating coil allows the
primary air serving the interior spaces to continue to provide cooling, while the perimeter duct
adds heating capability through this reset. Assuming the active chilled beams are the primary
heating system, the beams should be located parallel to the curtain wall, to ensure air movement
across these surfaces in order to promote a comfortable environment.
Six-port zone control valves may be used to eliminate a significant amount of zone runout piping
and allow more efficient heating across active chilled beam coils.
When ceiling-based active beams are the primary space heating source, their primary air supply
must be maintained to project the warm air into the space.
Chilled-beam systems are designed to optimize delivery of cooling to the space, but the paramount
consideration in sizing and locating beams in the room should focus on occupant thermal comfort.
ASHRAE Standard 55 defines limits on local air temperatures and
velocities that maintain acceptable levels of occupant thermal comfort.
Properly applied passive chilled beams have a limited effect on occupant thermal comfort;
however, their complementary primary air supply system often does. Stratified or partially mixed
air diffusion strategies are commonly used with passive beams because of their minimal influence
on the natural buoyancy-driven air patterns associated with the chilled-beam operation. The
secondary air circulation through the passive beam transports upper-level air back to the
occupied zone, possibly altering the level of stratification in the space.
Active chilled beams directly supply a mixture of primary and secondary air to the space and
should therefore be treated like the other air distribution devices used in fully mixed air
distribution systems. Because the temperature of the chilled water supplying the coil must be at
(or above) the space dew-point temperature, it is typically 13 to 16°C; thus,
reconditioned air leaving the coil is typically several degrees warmer than the primary air with
which it is subsequently mixed. This results in beam design discharge air temperatures that are
above 16°C, thus warmer than those normally used by conventional all-air
systems. Because of warmer discharge temperatures, larger active beam discharge air volumes are
required.
Chilled-beam system primary airflow rates are much closer to the space ventilation rates than
those of all-air systems, so primary control of the space temperature is normally accomplished
by throttling the chilled-water flow. Simple on/off operation of two-position water valves
provides adequate control of active chilled beams. Proportional valves are recommended for
passive beams and active beams in applications where more precise space temperature control is
required.
In applications where primary air is supplied at conventional temperatures (13 to
16°C) to spaces with significant sensible load variations, it may also be
necessary to reset the primary airflow rate or temperature during low-load conditions. One
approach is to vary the primary airflow rate in reaction to thermal demands and/or occupancy of
the space.
Although many chilled-beam applications involve a constant-volume supply of primary air, chilled
beams can also be served by varying primary airflow rates. For example, classrooms and
conference rooms where occupancy levels may vary considerably can be fitted with demand control
ventilation (DCV) provisions. In such cases, the primary air supply to the beams can be varied
according to occupancy, while a space dew point override ensures that the primary air volume
reduction does not compromise room humidity levels. Water flow through the coil remains
controlled by the space thermostat, resulting in the ability to control space temperature levels
independent of the primary airflow rate.
When chilled-beam systems are used to condition spaces with widely varying sensible cooling
requirements (e.g. perimeter spaces), consider using a variable-air-volume (VAV) terminal to
vary the primary airflow rate to beams in the zone. This allows the primary airflow rate to be
throttled in response to the zone’s sensible cooling requirements. The minimum flow limit
on the VAV terminal is set at the minimum primary airflow rate required to ensure proper space
ventilation, adequate room air induction, and humidity control.
Thermal zoning of chilled-beam systems should be performed in a manner generally consistent with
other HVAC systems. Each thermal zone consists of a space thermostat, a chilled- (and, where
applicable, hot-) water control valve, and multiple chilled beams.
Chilled beams may be exposed or integrated with an acoustical ceiling system. Active chilled
beams may be of either open or closed design. Closed
beams induce secondary air from below, whereas open beams induce through their top or sides within a
ceiling plenum. When passive or open active beams are applied, an adequate air path must be
provided for secondary air to enter the beam.
For sizing and selection purposes, secondary air entering an active chilled beam should generally
be considered at an equal temperature to that maintained within the occupied zone, unless solid
evidence indicates otherwise. For passive beams, the entering air temperature is higher than
that in the occupied zone due to room air stratification. The actual placement of the beam with
respect to space heat sources often affects the entering air temperature.
Most active chilled beam suppliers offer various nozzle sizes and configurations. Nozzle
configuration affects the beam’s primary air pressure requirement and acoustical
performance as well as its induction rate. Active beams with adjustable discharge or nozzle
patterns may also allow for field alteration of the beam’s air distribution
characteristics. This may also affect the beam’s cooling capacity, so changes should be
made with caution.
Beam sizing and location must consider cooling capacity, acoustics, thermal comfort, and
integration with other equipment and services. Active beams use a horizontal discharge of their
supply air mixture through linear openings along their perimeter, and thus display room air
diffusion characteristics similar to those of linear slot diffusers. As such, active beams
should be selected and located such that velocities within the occupied zone are limited to
0.25 m/s or less if compliance with ASHRAE Standard 55
is the design intent. Mapping techniques (see the sections on Fully and Partially Mixed Air
Distribution) and/or selecting active beam throw values from Table
6 may be used to estimate compliance with these comfort recommendations.
Locating stationary occupants directly below passive beams can result in thermal discomfort. Care
must be taken to ensure that the velocity and temperature of the descending airstream entering
the occupied zone comply with the thermal comfort requirements of ASHRAE Standard 55.
Operational Considerations
Water supply service to active and passive beams should not be activated until space dew-point
temperatures are at or below the chilled water’s supply temperature.
Where maintenance of adequate space dew-point temperatures cannot be ensured, some type of
condensation detection and mitigation strategy should be used. There are various methods of
accomplishing this, including the following:
-
Sensors may be attached to the supply water pipe to detect formation of surface
moisture and discontinue chilled-water flow until the moisture has evaporated. This
method is relatively inexpensive but also reactive, and halts induced air cooling
through the sensible water coil while conditions favoring the possibility of
condensation formation exist.
-
Dew-point calculation and reset of the chilled-water supply temperature is a
proactive strategy that does not fully suspend secondary cooling. This method can be
applied on a room-by-room basis, but calculation on a floor-by-floor basis is
usually sufficient and less costly.
-
In spaces with operable windows or doors, occupants and staff should be educated on
the effect these have on their thermal environment.
-
In some applications, condensate trays may be used to collect temporary and
infrequent condensation. When used, trays must have adequate condensate removal
and/or water flow modification provisions.
The designer must consider the intended building use when determining the type of chilled beams
to be used. General recommendations for chilled beam applications are shown in Table 11.
An air curtain unit acts as a controlled barrier for environmental and thermal separation and wind
resistance when a building’s doors or windows are opened. As an environmental separation
barrier, it repels airborne dust, dirt, fumes, odors, and flying insects from entering a building or
a protected indoor area. As a thermal barrier, it reduces cross migration of warm, lighter air
flowing through the upper part of the opening and cold, heavier air flowing through the lower part
of the opening. As a wind resistance barrier, it minimizes the effect of outdoor wind blowing into a
building’s openings.
A properly applied air curtain can maintain environmental integrity between two distinct areas while
allowing unobstructed access between the areas. Energy savings are possible when the air curtain
separates areas of different temperatures.
An air curtain unit operates on the principles of air entrainment, velocity vector, and pressure.
Because the airstream entrains a volume of air as it travels across an opening, it can maintain
separation of environments by returning these air volumes back to their respective areas when
the airstream splits, thereby minimizing losses.
Air curtain unit energy effectiveness is defined by the amount of energy saved (i.e., the energy
loss prevented through an opening with an air curtain), divided by the amount of energy that
would have been lost without an air curtain. It is represented as a percentage, and the amount
of energy saved is reduced by the energy consumed by the unit. Research (e.g., Pappas and Tassou
[2003]) shows that air curtains have a range of effectiveness from 60 to 90%, depending on the
type and application.
To fully realize benefits of using an air curtain unit, make sure that equipment is properly
sized, installed, adjusted, and maintained.
Application Considerations
Air curtain unit selection depends on the opening’s width and height. To maximize
effectiveness, the air curtain unit must at least cover or slightly overlap the entire opening,
and have a minimum velocity projection of 2 m/s at the target surface (Wang and
Zhong 2014). The unit is usually mounted above or beside a door or window opening. When mounted
above the opening, the horizontal air curtain unit discharges its air vertically down across the
opening. When mounted next to the opening, the vertical air curtain unit discharges air
horizontally across the opening. On wide openings, two vertically mounted, lower-air-velocity
units can be used as an alternative to a single horizontally mounted, higher-air-velocity unit.
The air curtain unit discharge must have a free and clear path to the entire opening for optimum
performance. AMCA Publication 222 is an application manual for air curtains that provides
detailed considerations for unit selection, installation, and construction.
Air curtain units are classified into two different types of construction: non-recirculating and
recirculating. A non-recirculating system draws air into the unit directly from the surrounding
environment in both horizontal and vertical applications (see Figures
33, 34,
35,
and 36).
An air curtain equipped with inlet ductwork, which draws air from outside the surrounding
environment, is also considered to be non-recirculating (Figure 37). A recirculating system
draws air from ductwork that primarily collects and returns the discharge air back to the inlet.
Applications often use a plenum with a floor return connected to the inlet with ductwork (Figure
38). An alternative construction includes horizontal flow that discharges and returns from side
to side (Figure 39).
Building Design Considerations
Non-recirculating air curtain units comprise the majority of systems built today. There are few
limitations to where they can be installed, they have little effect on the construction or
design of the building opening, and they are less expensive to install and maintain. In
buildings with high ceilings, they can aid in destratification.
Recirculating air curtain systems have a higher effectiveness and are more expensive than
non-recirculating systems. They are typically limited to commercial or cold storage applications
where doorways have high traffic or are open for extended periods of time. They require careful
integration into the building’s construction and design and have door height limitations.
Air curtain units use various electrical and mechanical means to control airflow rate and
temperature to achieve environmental separation, mitigate wind conditions, and repel flying
insects.
General applications of air curtain units include the following:
-
Exterior environmental separation:
protects an exterior opening from unwanted infiltration of outdoor air and the
escape of indoor air caused by effects of natural wind and/or temperature
differences.
-
Interior environmental separation:
provides protection between interior rooms connected by a common opening. This
application is intended to prevent the unwanted infiltration of unconditioned air or
the loss of conditioned air from one room to another caused by temperature
differential. Typically, this can be controlled by an air curtain unit that has an
air performance requirement much smaller than the air performance requirement for
exterior applications.
-
Flying insect control: protects an opening
or doorway, usually exterior, from the unwanted entry of flying insects. This is a
common requirement in facilities that produce, process, or serve foods (e.g.,
kitchens, cafeterias). This application typically requires an air curtain unit with
a higher airstream velocity to repel flying insects. When units are selected with a
higher airstream velocity to improve resistance against insect penetration, the
energy effectiveness will be reduced.
-
Coolers/chill rooms and freezers/cold
stores: prevents loss of refrigerated air through openings
and/or doorways in coolers and freezers. Three types of applications exist: cooler
to freezer, ambient to cooler, and ambient to freezer. These types of installations
are generally (but not limited to) indoor applications; therefore, the air curtain
unit is only required to overcome airflow caused by temperature differential and not
wind pressure. Air curtain units are typically horizontally mounted on the warm side
of the doorway, so that the airstream split created can balance against the air
trying to leave the cold room. Cold storage installations can be difficult to
balance and may require a vertical or cold-side mount, dampers, and/or multispeed
motors to effectively protect the opening.
-
Ovens: protects against loss of heated air
through openings and/or doorways in ovens. Air curtain units are normally mounted
horizontally over the oven opening and angled slightly inward toward the oven to
prevent hot air from escaping through the top of the opening. These types of
installations are generally indoor applications; thus, the air curtain unit is only
required to overcome airflow caused by temperature differential and not wind
pressure. The heating process in ovens is typically designed to maintain a neutral
pressure with the surrounding environment. The air curtain unit should be adjusted
to only entrain and “turn back” the heated air to avoid creating an
unbalanced condition by forcing air into the oven. The mounting location of the air
curtain unit should also provide adequate protection from exposure to hot air that
would escape the oven in the event the air curtain unit is shut down.
-
Negative building pressure: Air curtain
units installed on an opening where a negative pressure exists require special
consideration. When the building is underpressurized, standard air curtain airflow
rate will not be able to overcome the artificial deflection created by the negative
condition. In special cases, airflow may be increased to overcome a slight negative
condition. For proper operation of the air curtain, the building should be neutral
or positively pressurized.
-
Special/custom: other applications include
protection against dust infiltration, water removal in drying processes, smoke and
odor containment, and defrosting doorways. In these cases, effectiveness is defined
by the application criteria.
Optional Features and Controls
Optional features for air curtain units include heating, cooling, filters, and special controls.
A combination of special components, casing materials, and casing coatings may be required for
outdoor mounting, hazardous locations, or harsh environmental applications. Supplemental
heating/cooling can be provided by an air curtain unit to reduce the zone load on unitary HVAC
equipment, but it should not be seen as the primary source for conditioning internal areas. The
energy effectiveness of an air curtain unit is not enhanced when it provides conditioned air.
Heating methods can include steam, hot water, electricity, and fuel gas. Cooling methods can
include chilled water or direct expansion.
Applications in dusty or dirty areas may benefit from air curtain units equipped with inlet air
filters to reduce maintenance and maintain optimal performance. Note that the aerodynamic
performance of an air curtain unit will be reduced if filters are not properly sized, cleaned,
or changed. Air curtain unit electrical controls that monitor door position and temperature, or
BMS interfaces are required to provide the design velocity, temperature, and operation of the
air curtain. They are also used to minimize unnecessary energy usage and overconditioning of the
building opening.
The discharge of an air curtain unit adjusts the direction of the air curtain for proper
protection. This adjustment may include (but is not limited to) the following types:
-
Pivot mount: the ACU cabinet is capable of
pivoting on its mounting so that it may direct the air curtain at the proper angle
to protect the opening.
-
Adjustable nozzle: the ACU discharge
nozzle is capable of pivoting within the ACU so that it may direct the air curtain
at the proper angle to protect the opening.
-
Adjustable nozzle vane(s): the ACU
discharge nozzle employs a vane, or vanes, that are capable of pivoting within the
nozzle so that it may direct the air curtain at the proper angle to protect the
opening.
-
Both adjustable nozzle and vanes: the ACU
employs a combination of the adjustable nozzle and adjustable nozzle vanes.
-
Diverter nozzle: the ACU employs an
apparatus within the nozzle that is capable of diverting the air curtain at the
proper angle to protect the opening.
Performance and Safety Standards
Air curtain unit performance data can be used to select and/or compare different products.
ANSI/AMCA Standard 220 defines the test methods that can be used to
generate data for the typical types of non-recirculating air curtain aerodynamic performance.
ANSI/AMCA Standards 300, 301, and 320 are sound standards that can be
used to rate air curtains units are.
For insect control applications, use ANSI/NSF Standard 37 to
determine criteria for air curtain unit air performance, construction, design, and material
type. An air curtain unit that complies with this standard is considered by the food service
industry to provide effective flying insect protection to an entryway by deterring flying
insects from entering through the opening or nesting in the air curtain unit.
Safety standards that can be applied to air curtain units are UL Standards 507, 1995, and 2021.
Energy codes and standards such as ASHRAE Standard 189.1-2020 and the
IECC define air curtain unit air performance and operation requirements for energy sustainable
structures.
Maintenance and Accessibility
Whether the unit will be mounted horizontally or vertically, and inside or outside the opening,
obstructions surrounding the opening will require special installation considerations. Typical
obstructions may include beams, piping, ductwork, electrical conduit, door hardware, etc.
Accessibility for maintenance should also be considered. Each manufacturer provides specific
instructions for their products; carefully follow the specific instructions regarding safety,
installer qualifications and recommended work practices.