1. SEISMIC-RESISTANT DESIGN
Since most jurisdictions in the United States use a version of the International
Building Code® either as-is or with modifications to set minimum requirements
for building design and construction, it is widely accepted as industry-standard practice to rely on
ASCE Standard ASCE7 to set requirements for seismic resistant designs.
Within Standard ASCE7, Chapter 13 Seismic Restraint for Non-structural
Components, is the primary source of most prescriptive guidelines and requirements that are used with
HVAC&R systems. Due to the detailed and specific manner in which the chapter is written, engineers
and contractors can rely on a consistent and standardized approach to addressing earthquake effects.
Local code officials can likewise count on this standardized approach to help ensure code-compliant
buildings can be expected to meet their performance objectives (e.g., essential facilities will continue
to function after a design-level event). In some instances, local authorities having jurisdiction (AHJs)
over building projects require additional measures to be incorporated into seismic resistant designs, so
as with any project, it is important to know those and include them in the work.
This standardized approach can be and has been applied to other jurisdictions outside of the United
States where acceptable to the local authorities. In places like Canada, which lacks a prescriptive
guideline such as ASCE7, the seismic resistant design for HVAC&R systems is left to the professional
engineer in responsible charge of the work to determine the best course of action that meets the letter
and intent of the applicable building code. Some jurisdictions have established best practices that
borrow elements from ASCE7, NFPA Standard 13, and from older documents such
as SMACNA.
Other sources of information used to help design and install seismic resistance systems include
-
A Practical Guide to Seismic Restraint, 2nd ed. (ASHRAE 2012)
provides useful information in determining and designing seismic resistant systems for
HVAC&R systems. Note that the general guidelines are still useful though the
code-specific direction applies to IBC 2012 and earlier. A third edition is currently being
worked on to bring it up to date.
-
The Vibration Isolation and Seismic Control Manufacturers Association (VISCMA) acting on
behalf of the Federal Emergency Management Agency (FEMA) created a series of three manuals
that are available on both of their websites for download:
-
VISCMA/FEMA 412, Installing Seismic Restraints for
Mechanical Equipment
-
FEMA 413, Installing Seismic Restraints for Electrical
Systems
-
FEMA 414, Installing Seismic Restraints for Duct and
Pipe
-
These manuals provide general guidance and do not include any code-specific requirements.
-
FEMA has published other guidelines to help mitigate various extreme events, including FEMA
E-74, Reducing the Risks of Nonstructural Earthquake Damage—A
Practical Guide (2012).
-
The Canada Standards Association publishes S832 Seismic Risk Reduction
of Operational and Functional Components (OFCs) of Buildings (R2019) which
provides an effective methodology for prioritizing and designing appropriate restraint
systems for HVAC&R components.
-
Seismic Restraint Manual: Guidelines for Mechanical Systems, 3rd
ed. (SMACNA 2008) includes a simplified approach to standardized bracing configurations for
duct, pipe, and conduit. Note, however, that it is based on older versions of building codes
that are no longer used (IBC 2006 and earlier) and some of the guidelines are in conflict
with current code requirements.
-
NFPA Standard 13, Standard for the Installation of Sprinkler
Systems (NFPA 2019) is the primary authoritative document for sprinkler systems in the
United States. Chapter 18 of that standard
determines seismic resistant system design requirements.
-
United Facilities Criteria UFC 3-301-01 with Change 1, Structural
Engineering (DoD 2022) provides the necessary information and requirements for designing
seismic resistance systems for U.S. Department of Defense (DoD) buildings. For the most
part, it uses ASCE7-16 as is, but with some modifications regarding seismic design values
and detailing requirements (e.g., place two nuts on post-installed concrete anchors in some
cases).
-
Requirements for seismic resistant systems for HVAC&R systems in nuclear facilities in
the United States are described in the Department of Energy Standard 1020, Natural Phenomena Hazards Analysis and Design
Criteria for DOE Facilities (2016) and American Society of Mechanical Engineers (ASME) AG-1
Code on Nuclear Air and Gas Treatment (2019). The DOE document
relies heavily on ASCE7-10 for its methodology.
For a number of reasons, the selection and design of seismic restraints is typically performed through a
delegated design process where the mechanical engineer of record for a project stipulates the general
requirements through the contract documents but leaves the technical determination to another engineer
with appropriate expertise in the specialized field. Building codes in North America require the work be
done by a registered professional engineer competent in the calculation of design forces in accordance
with the applicable codes and standards. The delegated design engineer’s work is submitted to the
engineer of record for review before being sent to the installing contractor to carry out. In many
instances, the delegated design engineer is required to sign-off on the installation prior to occupancy
to ensure the designs were properly installed. Additionally, many projects have special inspection
requirements (either from the owner or by code) that stipulate a third-party inspection agency determine
that the seismic restraint installations are code compliant. In all cases, the local authority having
jurisdiction makes the final determination of acceptance.
The design of seismic resistance systems for HVAC&R components on a project using an IBC code
requires a few things to be known, including the risk category (RC) of the building, the seismic design
category (SDC), and the site-specific short-period ground acceleration values (Ss). These three values are all provided by the structural engineer
of record for the project and are made available in the construction documents, typically on one of the
first pages in the drawing set. For projects without a structural engineer, those values can be
approximated following the instructions in the IBC and ASCE7 and by using websites. Projects in Canada
use a similar methodology but with slightly different terminology as described in the National Building
Code and each provincial building code.
Attachment. The physical connection between the restrained
component and its support or its restraint device and building structure using bolts, screws, welds,
or otherwise positive fastening without relying on frictional resistance due to gravity.
Distribution system. Piping, ductwork, and electrical
conduit/cable tray systems.
Effective shear force Veff. Maximum shear force of one restraint or anchorage
point.
Effective tension force Teff. Maximum tension force or pullout force on one
restraint or anchorage point.
Component. Any non-structural element attached to or part
of a building such as a piece of equipment or a distribution system.
Resilient restraint. A device attached to a component that
allows some limited movement.
Resilient support. Static support of a component which is
flexible, such as a vibration isolator.
Response spectra. Relationship between the acceleration
response of the ground and the peak acceleration of the earthquake in a damped single degree of
freedom at various frequencies. The ground motion response spectrum varies with soil conditions.
Rigid restraint. Non-resilient device attached to a
component to restrict its movement.
Rigid support. Static support of a component which is
considered to be non-resilient, such as a steel frame.
Shear force V.Force
generated parallel to the attachment plane.
Seismic restraint. Device designed to withstand seismic
forces and hold a component in place during an earthquake.
Seismic force levels. Design forces on a component
determined using various factors related to its weight, construction, position, contents, and
function and related to the geographic location of a project.
Snubber. Restraint device that includes resilient material
positioned to prevent a component from moving beyond an established gap.
Structure. Load-carrying element of a building, designed
by a structural engineer of record.
Support. An element that holds a component in place; may
be an external element such as a curb or rod hanger, or internal such as the component’s base
frame.
Tension force T. Force
generated axially, either perpendicular to the attachment plane or along the primary axis of a
single-axis restraint such as a cable.
Sample calculations presented here assume that the equipment support is an integrated resilient
support and restraint device. When the two functions of resilient support and motion restraint are
separate or act separately, additional spring loads may need to be added to the anchor load
calculation for the restraint device. Internal loads within integrated devices are not addressed in
this chapter. These devices must be designed to withstand the full anchorage loads plus any internal
spring loads.
Both static and dynamic analyses reduce the force generated by an earthquake to an equivalent
statically applied force, which acts in a horizontal or vertical direction at the component’s
center of gravity. The resulting overturning moment is resisted by shear and tension (pullout)
forces on the tie-down bolts. Static analysis is used for both rigidly mounted and resiliently
mounted equipment.
Dynamic analysis of the isolation and snubber systems may be based on ground-level response
spectra given in the IBC and reference standard ASCE7, which can be used as input for a dynamic
analysis.
Response spectra applied to nonstructural components can be developed from ICC-ES acceptance
criteria AC 156 (ICC-ES 2012). Site-specific ground response spectra developed by a geotechnical
or soils engineer may be used, as well. The computer analysis used must be capable of analyzing
nonlinear supports and site-specific ground motions. This dynamic analysis provides the maximum
seismic input accelerations to the equipment components, allowing comparison to
three-dimensional shock (drop) or shaker test fragility levels to determine equipment
survivability.
Using the response spectra in the code for ground-floor inputs, or the spectra in ATC 29-2 for
upper floors, a dynamic analysis can yield maximum input accelerations to equipment components.
Comparing them to the allowable acceleration values in the table helps the engineer assess
equipment survivability. Dynamic analysis can also provide maximum movement at all connections
and, when added to the floor-to-ceiling code-mandated movements, allows the engineer to design
these flexible connections and avoid pull-out or shear failures at these locations.
Under some conditions, the IBC requires certificates of compliance for components and their
attachments for a component importance factor Ip of 1.0
or 1.5. This is a life-safety issue as well as an essential equipment issue. Essential equipment
with an Ip = 1.5 must have a certificate of compliance.
Issuance of a certificate of compliance to the engineer of record and building official can be
based on dynamic analysis. Most building officials require a stamp by a registered professional
to be part of the calculations and certificate of compliance. Table 1 provides guidance on
type of analysis (static or dynamic) and certificate of compliance documentation required.
Sample dynamic analysis is beyond the scope of this chapter and should be provided by
experienced registered professionals. A common approach assumes an elastic response spectrum.
The results of the dynamic analysis can then be scaled up or down as a percentage of the total
lateral force obtained from the static analysis performed on the building.
Dynamic analysis of distribution systems and equipment reflects the response of the equipment for
all earthquake-generated frequencies. Especially for piping and equipment, when the earthquake
forcing frequencies match the natural frequencies of the system, the resulting applied forces
increase.
Static Analysis as Defined in ASCE7
ASCE7 specifies a design lateral force Fp for
nonstructural components as
but Fp need not be greater than
nor less than
where SDS is determined by
where
| ap = component amplification factor in accordance
with Table 2. |
| SDS = design spectral response acceleration at
short periods. SS is the mapped spectral
acceleration for a specific location and is available at the ASCE website: asce7hazardtool.online. (Note: values
are specific to certain editions of ASCE7, since they are periodically updated.) |
| Fa = function of site soil characteristics and
must be determined in consultation with either project geotechnical (soils) or
structural engineer. Values for Fa for different
soil types are given in Table
3. (Note: Without an approved geotechnical report,
the default site soil classification is assumed to be site class D.) |
| Rp = component response modification factor in
accordance with Table 2. |
| Ip = component importance factor (see ASCE7 Chapter 13 for explanation and
determination of Ip). |
| ( 1 + 2z/h) = height
amplification factor where z is the height of attachment in
the structure and h is the average height of the roof above
grade. The value of z for ground level and below (e.g.,
basements) should be taken as 0 and z/h shall not exceed 1. |
| Wp(D) = operating
weight of component, which includes all items and contents attached or
contained inside.
|
The forces acting on indoor components include the lateral and vertical forces at the center of
gravity resulting from the earthquake movement, the force of gravity, and the forces of the
restraint holding the component in place. Restraints must be designed for a concurrent vertical
force Fpv at the center of gravity, defined as
Seismic coefficient values for both U.S. and Canadian locations can be found at the ASCE website
(www.asce7hazardtool.online) and USGS website (www.USGS.gov). Seismic design values for many
international locations that correspond with the ASCE7 methodology can be found at www.wbdg.org/additional-resources/tools/ufcsldt. Table
4 contains brief listings of historical Ss
factors for international locations that may be used only for general comparisons; they have not
been confirmed or updated for this publication and so should not be used for design purposes.
1.3 APPLYING STATIC ANALYSIS
The prescriptive method in ASCE7 allows that an equivalent static force can be calculated that
represents the dynamic motions of an earthquake. The static forces acting on a piece of equipment
are vertical and lateral forces acting on the center of gravity resulting from the earthquake, the
force of gravity, and forces at the restraints that hold the equipment in place. The analysis
assumes that the equipment moves with the structure during the earthquake and that the relative
accelerations between its center of gravity and the ground generate forces that must be balanced by
reactions at the restraints. Guidance from the code allows equipment to be analyzed as though it
were a rigid component; however, a factor ap is applied in
the computation to address flexibility issues on particular equipment types or flexible mounting
arrangements. (Note: for dynamic analysis, it is common to use a 5%
damping factor for equipment and a 1% damping factor for piping.) Although the basic force
computation is different, the details of load distribution in the examples that follow apply
independently of the code used.
Once the overall seismic forces Fp and Fpv have been determined (as indicated in the section on Static
Analysis as Defined by ASCE7 or per local code requirement), the loads at the restraint points can
be calculated.
The primary forces acting on the restraints include both shear and tensile components. The
application direction of the lateral seismic acceleration can vary and is unknown. Depending on its
direction, it is likely that not all of the restraints will be affected or share the load equally.
It is important to determine the worst-case combination of forces at all restraint points for any
possible direction that the lateral wave front can follow to ensure that the attachment is adequate.
Under some instances (particularly those relating to life-support issues in hospital settings), code
requirements indicate that critical equipment must be seismically qualified to ensure its continued
operation during and after a seismic event. Special care must be taken in these situations to ensure
that equipment has been shake-table-tested or otherwise certified to meet the maximum anticipated
seismic load. Table
5 illustrates some load combination calculations.
1.4 COMPUTATION OF LOADS AT BUILDING
CONNECTION
ASCE Standard 7 is based on load- and
resistance-factor design (LRFD). In the past, building codes have been based
on allowable stress design (ASD). Both are allowed for
seismic restraint design. Load factors and load combinations that must be considered in design are
defined in Chapter 2 of ASCE7 (see Table
5). If a component is anchored with post-installed anchors, the design is usually
accomplished using provisions of LRFD. It is rare now to find components or attachments rated based
on their ASD capacity; nonetheless, it is important to recognize the difference between the two and
apply the appropriate factors based on the design method and component rating system to ensure that
they are consistent.
Restraints holding components in position must withstand shear and tensile forces. Restraint
selection and design requires determining the number of fasteners, such as anchors and bolts, that
are affected by earthquake forces. The lateral seismic design force can be applied in any horizontal
direction and should be evaluated in at least two specific directions, as shown in Figure 1. Note
that as many as all of the attachments, or as few as a single attachment, may be affected, depending
on the restraint configuration and load direction. The simple case example following provides a
basic design method and is made more complicated if the center of gravity (CG) is shifted or if the
anchor spacing is not symmetrical. This basic method is called the polar
method and is the most commonly used for seismic restraint design.
Some restraint designs consider how the mass is distributed and address all possible horizontal
directions with some modification of the ASCE prescriptive design methodology. This is called the
lump mass method.
Remember that vibration-isolated equipment will be restrained by snubbers that incorporate operating
clearances. As the load is applied at all possible angles and the equipment tilts in response to
these loads, not all of the snubbers will make contact and as such not all will be able to
contribute to the resistance of vertical loads. Every restraint arrangement will experience
differing abilities to share these loads, and the worst-case reactions at each restraint point
should account for these factors.
When analyzing rigid equipment, it is reasonable to assume that vertical or horizontal loads will be
shared among all restraints. Typically, the force that is generated by overturning or the rotational
load created by an offset CG is shared among all restraint points. For lateral forces, the amplitude
is equally divided over all the restraints. For rotational motion, the amplitude of the restraint
force at each location is proportional to the distance that restraint point is from the geometric
center of the mounting pattern. The worst-case load for the location at the maximum distance can be
obtained by generating appropriate Ixx and Iyy terms for the restraint pattern and using that as indicated
in the examples below.
When analyzing isolated equipment however, the ability to share rotational or rocking
(compression/tension) loads beyond the four corner locations will become a function of the stiffness
of the equipment. Some equipment, like packaged air handling units, is relatively flexible and will
distort and spread the rotational and overturning loads among a number of restraints. Equipment with
rigid bases, like a concrete inertia base mounted pump, will tend to distribute the load based on
the rotational axis as described previously.
Figure 1
shows a rigid floor-mount installation of a piece of equipment with the center of gravity at the
approximate center of the restraint pattern. To calculate the shear force, the sum of the forces
in the horizontal plane is
The equipment shown in Figure 1 has
two bolts on each side, so that four bolts are in shear. Using a single-axis moment equation to
calculate the tension force, the sum of the moments for overturning results in an overturning
moment (OTM) and resisting moment (RM).
For Figure 1,
two bolts are in tension. See Example 1 for applications of the OTM and RM. See ASCE Standard 7 for load combinations that adjust the D (dead load) and E (earthquake load). If
the equipment is located outdoors, be sure to consider the W (wind
load) forces as well. Shear and tension forces V and T should be calculated independently for both axes, as shown in the
front and side views. See the examples for complete analysis.
The classic method used to distribute seismic loads equally distributes lateral loads among the
restraints and then modifies these loads as a function of the weight eccentricity.
Worst-case weight, vertical seismic load, and overturning components are combined
to determine a maximum vertical load component in two horizontal directions. This polar method is in common use and works well for most
applications.
Equipment can be directly attached to the building structure or to a structural base made of
steel shapes (like angles or I-beams). Using a structural base distributes the seismic loads
more evenly and may reduce the size of the anchors by reducing the peak load. This results in
less stress on the equipment point of attachment, which may not have sufficient strength to
transfer the seismic load to the structure. If vibration isolation devices are used, stresses on
the equipment points of attachment increase which may then require the use of a structural base.
Larger equipment will have more than four anchor points at each of the corners. Depending on the
weight distribution and anchor spacing, the seismic loads at the corners may be lower than the
seismic loads in the middle.
Although only two methods of computing seismic forces are illustrated here, there are likely many
other valid methods that can be used to distribute the restraint forces. It is important that
any method used include the ability to account for equipment weight, seismic uplift
or compression forces, overturning forces, and the impact of any offset of the center of gravity
within the equipment.
Lateral forces are assumed to be equally distributed among the restraints. If the
equipment’s center of gravity does not coincide with its geometric center, a rotational
factor is added to account for the imbalance. This factor is determined in three steps. First,
compute the true chord length in the horizontal plane between the equipment’s center of
gravity and the geometric center of the restraints. Second, multiply the equipment total seismic
lateral force by this length (to obtain a rotational moment). Third, divide this figure by the
number of moment-resisting restraints times their distance from the geometric center. (The
moment-resisting restraints are those farthest and equally spaced from the geometric center.)
The resulting load can then be added to the original (balanced) figure. This method transfers
all imbalance loads to the corner restraints and provides a valid method of restraint as long as
the equipment acts as a rigid body. The assumption that a piece of equipment can transfer these
loads out to the corners becomes less accurate as the equipment becomes less rigid.
Calculation of the tensile/compressive forces at the restraints is more complex than that for
determining the shear loads, and must include weight, vertical seismic force,
overturning forces, and (if isolated) the type of isolator/restraint system used. The total
tensile and compressive forces are the worst-case summation of each of these components. For
clarity, each component is addressed here as a separate entity.
The nominal weight component at each restraint is simply the total operating
weight divided by the number of restraints. The vertical seismic force is simply
the weight component at each location multiplied by the vertical seismic force
factor in terms of the total Fpv load expressed in gs, the gravitational constant (Fpv/Wp, where Fpv is the vertical seismic load component as defined by
the code and Wp is the total operating
weight of the equipment). This can be directed either upward or downward when
summing forces.
In the lump mass method, the total equipment weight is distributed among the
restraints in a manner that reflects the equipment’s actual weight
distribution. There are many methods of determining the distribution analytically or by testing,
although they are not addressed in this section. It is often possible that a weight
distribution can be obtained from the equipment manufacturer, especially for equipment meant to
be hoisted by crane.
Once the static point loads are obtained or computed for each restraint location, they can be
multiplied by the lateral seismic acceleration factor (Fp/Wp) to determine
lateral forces at each restraint point. Thus, if the weight at each restraint point
is Wn, then
This method considers the loads at all the restraints individually and computes the overturning
forces for each in 1° increments for a full 360° of possible approach angles; it is only
practical to perform using a spreadsheet or computer routine. The methodology involves breaking
the seismic force Fp into x-
and y-axis components for each possible approach direction. These
forces are multiplied by the height of the equipment center of gravity above the point of
restraint hcg. The resulting moments are then resolved
into forces at each restraint based on the x- and y-axis moment arms associated with the particular restraint location
and the distance between those restraint elements that will actually make contact to resist the
overturning loads and the geometric center of the restraint layout.
Resilient Support Factors
If the equipment being restrained is isolated, the following three factors must be considered:
-
For all forces that are not directed along the principal axes, only the corner
restraints may be considered to be effective, depending on the rigidity of the
equipment. Thus, for either distribution method, only the corner restraints may be
considered capable of absorbing vertical loads.
-
If the restraints are independent (separate entities) from the spring isolation
elements and if, when exposed to uplift loads, vertical spring forces are not
absorbed within the housing of an integral isolator/restraint assembly, the
weight factor determined in the first step of the vertical load
analysis should be ignored. (This is because any effect that a weight
reduction has on the attachment hardware forces is replaced by an approximately
equal vertical force component from the spring.)
-
If the gap in the restraint element exceeds 1/4 in., the final computed
forces must be doubled as required by the IBC.
The most common attachment arrangements are securing with steel bolts, attaching with lag screws,
welding, or anchoring to concrete using various kinds of post-installed anchors. To evaluate the
combined effective tensile and shear forces that act simultaneously on these connections, a
separate analysis that considers the relationship between the restraint device’s snubbing
element (if vibration isolated) and the structural connection geometry is required.
If the connection to structure is made using concrete anchors, additional factors may affect or
increase seismic loads. See the following section for details on concrete anchors.
If allowable stress design (ASD) capacity data are used to select restraint or attachment
hardware while using the load-resistant factor design (LRFD) IBC codes, the loads may be reduced
by a factor of 1.4. These must be identified at the beginning of the design effort and using the
appropriate load combination equations. If LRFD capacity data is used when selecting hardware,
the 1.4 factor does not apply.
ACI Standard 318 is the basis for sizing concrete anchors. All
allowable capacities used for concrete post-installed anchor bolts selection should be drawn
from ICC-ES test reports. These values reflect test data on a single anchor and anchor capacity
determined from the various configuration arrangements affected by embedment, edge distances,
spacing, and whether the anchor is installed in the soffit (underside) or top side of concrete
on metal deck. Anchor manufacturers have selection software to determine anchor bolt capacities
that consider installation conditions, including presence of other nearby anchors and vertical
offset (as with elevated baseplates with grout infill). Also, note that the values published in
ES reports may be either ASD or LRFD values and may need to be converted for compatibility with
the (LRFD) IBC code being used.
For direct attachment with through bolts using ASD criteria, the design capacity of the attachment
hardware should be based on criteria established in the American Institute of Steel Construction
(AISC) manual. Based on the use of A307 bolts, the basic formula for computing allowable tensile
stress when shear stresses are present is
where Sv is the shear stress in the bolt in psi.
Tallow, the maximum allowable tensile stress, must not exceed
20,500 psi.
However, because these stresses are appropriate for dead- plus live-load combinations, they can be
appropriately inflated by 1.33 when allowable stress design provisions are used and when they are
used to resist wind and seismic loads as well. Peak bolt loads are based on the maximum permitted
stress multiplied by the nominal bolt area.
1.6 LAG SCREWS INTO TIMBER
Acceptable loads for lag screws into timber can be obtained from the National
Design Specification® (NDS®) for Wood
Construction (AWC 2015). Selected fasteners must be secured to solid lumber, not to
plywood or other similar material. Withdrawal force design values are a function of the screw size,
penetration depth, and wood density and can be increased by a factor of 1.6 for short-term seismic
or wind loads. NDS identifies withdrawal forces on a force/embedment depth basis. Note that the
values published in this table are capacities in both ASD and LRFD. In addition, NDS introduces
deration factors for reduced edge distance and bolt spacing.
In timber construction, the interaction formula given in Equation (8) does not apply.
Instead, per the NDS, the equation is
where
| Z′ = shear capacity drawn from Table 9.3A |
| W′ = side grain withdrawal force = 1800G3/2D3/4 |
| G = specific gravity of the timber |
| D = diameter |
| p = embedment depth of screw |
| α = angle of composite force measured flat with surface of timber |
Concrete anchors can be divided into two main categories: cast-in-place and post-installed. The
former are positioned prior to the concrete being poured and can be suitable for wood formwork,
metal deck, or being fixed in place with rebar or other means. Post-installed anchors allow
positioning after the concrete has cured and allow more flexibility in determining attachment point
locations during construction.
Capacities are manufacturer and anchor-type specific and determined through testing using ACI Standard 355.2 or 355.4 for mechanical or adhesive anchors, respectively.
Capacity data should be obtained from the most recent ICC-ES report available from the anchor
manufacturer. The report will provide capacity strengths at specific installation conditions for use
with strength-based design (LRFD) methods. For other installation conditions and for groups of
anchors, special factors are required and American Concrete Institute Standard 318-11 should be consulted.
ASCE7 requires the use of an overstrength factor Ω0, called
“omega-naught” or “omega sub-zero,” applied to the demand side of the
equation for attachments to concrete. This assumes the anchor failure mode may be brittle (a
concrete breakout or pullout failure). The value of this overstrength factor has varied over the
years with different codes. The ASCE7-16 version requires a value of 2 be used for most HVAC&R
equipment with one exception, so-called fin-fans or condensing units that commonly come mounted on
integral cold-formed sheet metal legs require an overstrength factor of 1.5 when attached to
concrete. This factor is applied to Fp at the center of
gravity. For some deep or cast-in-place anchors, the anchor failure mode may be determined to be in
the steel anchor body in which case the overstrength factor need not be applied.
Interaction Formula. To evaluate the combined
effective tension and shear forces that act simultaneously on the bolt, use the either of the
following equations:
or
However, if Teff ≤ 0.2; Tallow ASD the full Teff can equal Tallow
ASD, or if Veff ≤ 0.2; Vallow ASD the full Veff can equal Vallow
ASD.
The engineer must select an anchor for use from a current evaluation report for anchors that
satisfy provisions of ACI 318 Appendix D or ACI 355 (the provisions are the same). From ACI 318,
the capacity of the anchor must be reduced in accordance with the following:
The interaction equation for LFRD is modified as follows:
Types of Concrete Post-Installed
Anchors
There are several types of anchor bolts for use in concrete; each type has different installation
and capacity characteristics. All anchors used to resist seismic loads much be tested and rated
specifically for seismic loads. The manufacturer’s instructions for installing the anchors
must also be followed. Published reports (e.g., ICC-ESRs) have further information on allowable
forces for design. Use all appropriate design factors as required by the published reports and
by applicable codes.
Wedge anchors have an expanding conical portion, or
wedge, at one end with a loose clip around the wedge. After a hole is drilled, the bolt is
inserted and the nut tightened to draw the anchor up. As the nut is tightened to a specific
torque, the wedge expands the small clip, which bites into the concrete.
Undercut anchors expand to seat against a shoulder cut
in the bottom of the anchor hole. These often have the highest capacity of commonly available
anchor types, though since some require an extra operation to cut the shoulder in the hole,
their use on projects can be limited.
Screw anchors are one-piece anchors that have a
concrete cutting thread. These anchors are designed to be installed with a specified torque to
ensure contact at the rated embedment
Adhesive anchors are a combination of rods or rebar
with special chemicals that, when mixed, form a strong bond with concrete. Pure epoxy,
polyester, or vinyl ester resin adhesives are used with a threaded rod supplied by the
contractor or the adhesive manufacturer. Some adhesives have a problem with shrinkage; others
are degraded by heat. However, some adhesives have been tested without protection to
1100°F before they fail (all mechanical anchors will fail at this temperature).
Where required, or if there is a concern, anchors should be protected with fire retardants
similar to those applied to steel decks in high-rise buildings.
Stainless steel anchors (for any of the preceding
types) are required for use in outdoor applications where exposed to weather.
Other common types of post-installed concrete anchors are used in the construction industry, but
are not rated for seismic loads and should only be used with caution.
Drop-in expansion anchors are hollow cylinders with a
tapered end. After they are inserted in a hole, a small rod is driven through the hollow
portion, expanding the tapered end. These anchors are not rated for seismic restraint
applications and are used only for shallow installations because they have no reserve expansion
capacity.
A sleeve anchor is a bolt covered by a threaded,
thin-wall, split tube. As the bolt is tightened, the thin wall expands. Additional load tends to
further expand the thin wall. The bolt must be properly preloaded or friction force will not
develop the required holding force. These anchors are typically not used in seismic applications
because of the limited reserve capacity.
Weld capacities may be calculated to determine the size of welds needed to attach equipment to a
steel plate or to evaluate raised support legs and attachments. A static analysis provides the
effective tension and shear forces. The capacity of a weld is given per unit length of weld based on
the shear strength of the weld material. For steel welds, the allowable shear strength capacity is
21,000 psi on the throat section of the weld. The section length is 0.707 times the
specified weld size.
For a 1/16 in. weld, the length of shear in the weld is 0.707 × 1/16 =
0.0442 in. The allowable weld force (Fw)allow for a 1/16 in. weld is
For a 1/8 in. weld, the capacity is 1400 lb/in.
The effective weld force is the sum of the vectors calculated in terms of effective shear and tension
shall be reduced. Because the vectors are perpendicular, they are added by the method of the square
root of the sum of the squares (SRSS), or
The length of weld required is given by the following equation:
Seismically rated snubbers allow floor-mounted restrained components to move within controlled limits
and to be supported with resilient mounts such as spring or elastomer isolators. Several types of
snubbers are manufactured or field fabricated. All snubber assemblies should meet the following
minimum requirements to avoid imparting excessive accelerations to HVAC&R components:
-
Impact surfaces should include elastomeric materials at least 1/8 in. thick
and be no more than 1/4 in. away.
-
Resilient material should be accessible to inspect for deterioration and damage.
-
Snubber system must provide restraint in all directions.
-
Snubber capacity should be verified either through test (e.g., ASHRAE Standard 171) or by analysis.
Examples of typical snubbers and isolators with integral snubbers are shown as Types A through J in
Figure 2. Types A through D are snubber styles
corresponding to one isolator type referred to in Chapter 49 as Type 4 Restrained
Spring Isolator and are referred to in ASHRAE Standard 171 as
multidirectional, multi-axis, with integral isolation. Note that Table 47 of Chapter 49 uses the letters A
through D to denote base mounting types which should not be confused with the snubber types below.
Snubber Type E is a combination isolator and snubber referred to in that chapter as a Type 2 Rubber
Mount and is also referred to in ASHRAE Standard 171 as
multidirectional, multi-axis, with integral isolation. Typically all hold-down and mounting bolts
are protected from housings and other components using elastomeric grommets and washers to minimize
vibration short-circuiting and reduce seismic acceleration forces. Care must be taken during
installation to ensure these bolts remain out of contact and free to move under normal operation.
Snubbers types F through J are often used in conjunction with isolators that do not have integral
snubbers. Per ASHRAE Standard 171, Types F, G, H, and J are called
multidirectional, multi-axis with operating clearances, and Type I is called single-directional,
single-axis, single angle.
-
Type A. Completely enclosed spring isolator
with elastomeric grommet.
-
Type B. Spring isolator typically used for low
seismic loads and with components with rigid bases; the spring sits on a base plate that
includes hold-down hardware that includes elastomeric grommets.
-
Type C. Housed spring isolator used for low to
high seismic loads with built-in hold-down bolts that act as all-directional restraints.
-
Type D. Housed spring isolator used for low to
moderate seismic loads similar to Type A.
-
Type E. Elastomeric mount capable of
withstanding seismic loads in all directions.
-
Type F. All-directional snubber using a single
bolt attached to a restrained component.
-
Type G. Two-axis snubber.
-
Type H. All-directional snubber using
interlocking steel assemblies lined with elastomeric material.
-
Type I. Single-axis snubber, also called a
bumper.
-
Type J. A heavy-duty version of Type F used
for higher seismic loads.
1.10 SEISMIC RESTRAINTS FOR SUSPENDED
COMPONENTS
For suspended equipment, pipes, ducts, conduits, and raceways, it is necessary to restrain lateral
movement resulting from seismic acceleration applied to the component. Unrestrained, suspended
equipment and related systems may sway violently back and forth, impacting nearby building elements
and possibly overstressing the hanger rod supports or their attachments, leading to collapse. To
prevent this swaying, suspended components are braced or restrained, typically by one of two
methods: a wire rope system, or a rigid brace system using steel struts, angles, or other rigid
elements.
Wire rope restraints are restraint assemblies typically
used for suspended components consisting of galvanized steel wire rope (also known as aircraft
cable). A typical cable restraint system is shown in Figure 3.
Cable restraints should be tested for capacity in accordance with ASHRAE Standard 171. Cables are installed to prevent excessive seismic motion and
arranged so they do not engage during normal operation. Equipment suspended with vibration isolators
must use cable restraints instead of rigid restraints to avoid shorting out or degrading the
isolation. Rod stiffeners are added as necessary, as shown in Figure 4, to
prevent the hanger rods from buckling.
Secure the cable to structure and to the braced component through a bracket or stake eye designed to
meet the cable restraint rated capacity. Cables ends are typically terminated using one of the
following methods:
-
Factory-installed permanent stake eye
-
Looped around thimble through bracket and secured with wire rope clips (also called
Crosby cable clamps), oval compression sleeve (or ferrule or swage sleeve), or other
proprietary securement device
-
Factory brackets with integral cable clamps
When cables are looped through a bracket or support hole, a teardrop-shaped cable thimble matching
the wire size should be used to protect the cable. Some specialty brackets are designed specifically
for allowing a looped cable through without a thimble. Figure 5 shows typical cable
restraint details with various attachment methods. Typical attachment methods to secure rigid braces
to structures and components are shown in Figure 6.
1.11 RESTRAINT OF PIPE AND DUCT RISERS
When piping and ductwork run vertically through a structure, they are identified as risers. They are
subject to the same seismic and (less commonly) wind forces as are piping and ductwork oriented
horizontally. The primary difference is that the forces that act along the axis of the riser are the
summation of the vertical seismic forces and gravity loads, whereas on horizontal systems, the axial
forces are simply the horizontal seismic or wind force.
It is also important to recognize that restraining risers of any significant length and variation in
temperature require support that allows thermally driven changes in the riser’s overall length
to be accommodated. Because the vertical seismic and wind forces are small compared to gravity
forces, axial restraint for the riser can normally be provided with only minor increases in the size
of the specialized components used to support the system. Because of the potential of damage to the
restraint or support systems as the system grows or shrinks due to thermal changes, it is not
recommended that axial restraint systems be fitted to a riser. Instead, the primary support system
should be designed or selected to meet the project design loads.
Risers of significant length are also fitted with some type of stabilization devices. These can be as
simple as snug-fitting holes in the floors that the risers penetrate or specialized brackets or
guiding devices that maintain the alignment of the piping or duct while still allowing it to expand
or contract. As is the case with the vertical forces, the components used for guidance can
frequently be used to provide resistance against seismic or wind events if they are sized and
attached adequately.
If, in the lateral load case, the components used to provide guidance are not adequate to resist the
design seismic or wind load conditions, additional seismically qualified restraint systems should be
fitted to perform this task.
All axial and lateral restraints fitted to risers must be effective against forces that may act in
any horizontal or vertical direction as applicable. In addition, the attachment hardware used must
include seismically qualified components (e.g., anchors), installed in accordance with seismically
qualified procedures.
The following examples should not be considered to cover all installation cases; they are a selection
of simple cases that can be used for illustrative purposes. Many, if not most, cases are more
complex and will require the engineer performing the analysis to consider the details of the
application when creating a model. There are many potential configurations (far more than can be
illustrated here) that impact the load path and add forces/moments at the restraint points. Efforts
have been made in the examples to indicate qualifications and limitations specific to the particular
model being used.
The following examples are provided to assist in the design of component anchorage to resist seismic
forces. For Examples 1 through 4, assume the provisions contained in ASCE7-16 apply, Ip = 1.5, Ss = 0.85,
site soil class is C, and the equipment is located at the top of a 50 ft building. Also
include a vertical force component Fpv = 0.2SDS D where D is the dead load for
all examples. Examples 1 through 5 are solved using the polar method of analysis while Example 6 is
solved by the lump mass method.
Note: These examples assume that Ip = 1.5. This assumes that the component being considered is
required for the continued function an essential facility following an earthquake or contains
hazardous materials. ASCE7-16 Section 13.2.2 requires that this component be certified as being
operable after the design earthquake. Codes based on ASCE7 require that the anchor failure mode be
considered when selecting an appropriate anchor. If, when using the baseline factors indicated
above, it is found that the limiting failure mode of the anchor/restraint component is a brittle
failure associated with the anchor (i.e., a concrete or anchor pullout failure) rather than a
ductile (steel) failure, the analysis of the anchorage needs to be selected with the Fp load increased by the Ω0 factor, which in
most cases is 2. The general math is the same, but the force magnitudes will increase from those
shown in the sample cases.
Example 1.
Anchorage design for equipment rigidly mounted to the structure (see Figure
7). This model is appropriate only for rigid-mounted equipment with four restraint
points and the CG centered geometrically on the restraint point pattern. The equations can
be adjusted when the equipment center of gravity is offset from the geometric center. There
are other examples provided for vibration-isolated equipment.
From Equations
(1) to (4), calculate the lateral seismic force and its vertical
component. For rigidly mounted mechanical equipment (period < 0.06 s or > 16.7 Hz),
ap from Table 2 is 1.0,
otherwise ap = 2.5.
The first step in the load determination process is to determine SDS using the following equation and Fa = 1.1 (from Table
3, site class C). Linear interpolation is allowed and the actual Fa for this application could be reduced to (1.0
– 0.75)/0.25 × 0.1 + 1.0, or 1.06. For this example, though, Fa = 1.1 is used.
Using this value for SDS Equation (1) gives
Equation (2)
shows that Fp need not be greater than
Equation (3)
shows that Fp must not be less than
Therefore Fp = 450 lb.
When considering provisions of LRFD, a vertical acceleration component must be considered per
ASCE7, Section 12.4.2.2.
A simplified method of calculating the resisting moment (RM) involves looking only at the
diagonally opposite corners. For hard-mounted equipment, opposite corners could also be
considered. The simplified method is shown next for both ASD and LRFD cases.
For Allowable Stress Design (ASD)
The load combinations of Section 2.4 of ASCE7-16 must be considered in the design. For
rigidly mounted components, and when looking at worst-case tensile (uplifting) loads on the
restraint component, Combination 8 is generally the critical combination to be considered.
Calculate the overturning moment OTM:
Calculate the resisting moment RM:
Calculate Teff per bolt:
Calculate shear force per bolt:
Load and Resistance Factor Design (LRFD)
The load combinations of Section 2.3 of ASCE7-16 must be considered in the design. For
rigidly mounted components, and when looking at the worst-case tensile (uplifting) loads on
the restraint component, consider the most critical combination.
Case 1. Equipment attached to
a timber structure
Before computing interaction forces, the computed loads must be reduced by a factor of 1.4 to
make them compatible with the capacity data listed in the National
Design Specification® (NDS®) for Wood
Construction (AWC 1997). The lateral load Veff becomes 112.5/1.4 or 80.4
lb per bolt and the pullout load Teff
becomes 103/1.4 = 73.5 lb per bolt. For the capacity of the connection, a
resulting combined load and angle relative to the mounting surface must be computed. The
combined load is
The angle α = arcs in (Teff/Z′α) = 42.5°, where Zα is the allowable lag screw load multiplied by applicable
factors and Z′αα is the factored
allowable lag screw load at angle α from the mounting surface.
Selected fasteners must be secured to solid lumber, not to plywood or other similar material.
The following calculations are made to determine whether a 1/2 in. diameter,
4 in. long lag screw in redwood will hold the required load. For this
computation, it is assumed that bolt spacing, edge distance, temperature, and other factors
do not reduce the bolt capacity (see NDS for further details) and that the load allowable
factor for short-term wind or seismic loads is 1.6.
From Table 9.3A in the NDS, for redwood, G = 0.37, and Z perpendicular to the grain is 512 lb.
From Table 9.2A in the NDS, for G = 0.37 and 3.5 in.
full thread, W = 385 × 3.5 = 1350 lb.
Substituting into the combined load for lag bolts [Equation (9)] gives
Therefore, a 1/2 in. diameter, 4 in. long lag screw can be used at
each corner of the equipment.
Case 2. Equipment attached to
steel
For equipment attached directly to a steel member, analysis is the same as that shown in case
1. Capacities for the attaching bolts are given in the Manual of Steel
Construction (AISC). See Chapter J of the AISC Specification for design
provisions.
For this example Teff/TASD = 125/4410 = 0.02 < 0.2; therefore
a combined tension shear check need not be performed on the connection.
Therefore, 1/2 in. diameter bolts can be used.
Example 2.
Anchorage design for equipment supported by external spring mounts (Figure 8)
and attached to concrete using seismically rated post-installed anchors.
A mechanical or acoustical consultant may choose the type of isolator or snubber or
combination of the two (restrained isolator), typically in collaboration with the product
vendor to should select the actual spring and/or snubber devices appropriate for the
application.
Note that there are different values for Rp and ap in different versions of ASCE7. This example uses Table 1, which is drawn
from ASCE7-16. SDS remains as in Example 1. For
resiliently floor-mounted mechanical equipment, Rp =
2.0 and ap = 2.5.
The basic force equation is then
Equation (2)
indicates that Fp need not be greater than
Equation (3)
indicates that Fp must not be less than
The vertical force Fpv equals
Assume that the center of gravity CG of the equipment coincides with the geometric center of
the isolator group.
If T = maximum tension on a restrained isolator and C = maximum compression on a restrained isolator, then
Note that the above equations hold true for all cases with four or more restraints on rigid
equipment, assuming that the system is vibration isolated. This is because, for a very brief
period of time, there is little or no load sharing with restraints that are not located on
the diagonal corners as any remaining restraints would be operating in the clearance range
of the snubbing elements and there would be no contact that would allow additional
restraints to share the load.
To find maximum T or C, set dT/dθ = 0:
Calculate the shear force per isolator:
This shear force is applied at the centroid of the elevation of the snubbing element in the
restraint device. Uplift tension T on the vibration isolator is
the worst condition for the design of the anchor bolts. The compression force C must be evaluated to check the adequacy of the structure to
resist the loads.
The value of (T2)eff per bolt due to overturning on the isolator is
where d is the distance from edge of isolator base plate to
center of bolt hole.
See Example 1 for the design of the connections to the structural system.
Example 3.
Anchorage design for equipment with a center of gravity different from the geometric center
of the restrained isolator group (Figure
10).
Anchor properties
Angles:
Vertical reactions
Vertical reaction caused by overturning moment
Vertical reaction caused by eccentricity
Vertical reaction caused by Wp
Horizontal reactions
Horizontal reaction caused by rotation
See Example 1 for the design of the connections to the structural system.
The values of Tmin and Vmax are used to design the anchorage of the isolators
and/or snubbers, and Tmax is used to verify the
structure’s adequacy to resist the vertical loads.
Example 4.
Anchorage design for equipment with supports and bracing for suspended equipment (Figure
11). Equipment weight Wp =
500 lb.
Note that post-installed anchors may not withstand published allowable static loads when
subjected to vibratory loads, so vibration isolators may be used between the equipment and
the structure to damp vibrations generated by the equipment.
Anchor properties
Note that Ix and Iy will vary with the number of restraints for
hard-mounted equipment, but since only the corner restraints come into play during initial
contact caused by rocking or rotation, they will remain as indicated for vibration-isolated
systems, no matter how many restraints are present.
Angle
From Equation
(43),
From Equation
(44),
From Equation
(45),
From Equation
(46),
From Equation
(47),
From Equation
(48),
Forces in the hanger rods:
Force in the splay brace =
= 1587 lb at a 1:1 slope.
Because of the force being applied at the critical angle, as in Example 2, only one splay
brace is effective in resisting the lateral load Fp.
Design of hanger rod/vibration isolator and connection to
structure
When post-installed anchors are mounted to the underside of a concrete beam or slab, the
allowable tension loads on the anchors must be reduced to account for cracking of the
concrete. A general rule is to use half the allowable load. Some manufacturers have ICC
reports that provide allowable values for anchors installed under the slab.
Determine whether a 1/2 in. wedge anchor with special inspection provisions will
hold the required load.
Therefore, a 1/2 in. rod and post drill-in anchor should be used at each corner
of the unit.
For anchors installed without special inspection,
Therefore, a larger anchor should be chosen.
Determine if the 1/2 in. hanger rod would require a stiffener if it is 36
in. long.
Design of splay brace and connection to structure
Force in the slack cable = 1587 lb.
Because all of the load must be resisted by a single cable, the forces in the connection to
the structure are
Because the cable forces are relatively small, a 3/8 in. aircraft cable attached
to clips with cable clamps should be used. The clips, in turn, may be attached to either the
structure or the equipment.
The design of a post-installed anchor installation is similar to that shown in Example 1.
Anchors installed through a metal deck will have lower capacities than anchors installed in
a flat slab because of limited embedment depths. Take care to ensure that the design also
satisfies the requirements contained in the evaluation report for the anchor specified.
Example 5.
This example is the same case as Example 1 (Figure
7), except that the lump mass method is used as a basis of analysis. Load
combinations listed here are for LRFD, although the analysis can also be done using ASD in a
similar manner to Example 1. The anchorage design is for equipment attached to concrete
using seismically rated post-installed anchors. This model is also appropriate for vibration
isolated equipment with no more than four restraint points and the CG centered geometrically
on the restraint point pattern. It is not acceptable for systems where the CG is shifted
away from the geometric center of the restraint point pattern.
When using the method, the Fp and Fpv acceleration terms are computed in the manner as
when using the polar analysis; however the weight term would not be present. As such, the
basic SDS Equation (1) gives
Equation (2)
shows that Fp(g) need not be greater than
Equation (3)
shows that Fp(g) must not be less than
Therefore Fp(g) = 0.433 (g).
When considering provisions of LRFD, a vertical acceleration component would still be
considered per ASCE7, Section 12.4.2.2:
The static mass load computation at each restraint location can be computed in many ways or
may be provided by the equipment manufacturer. In this case the equipment is balanced, so
the static mass load at each restraint point would equal the local weight/4:
Horizontal design force.
This is driven by the static mass load; at each of the four corners would be the mass load
× Fp(g):
If the equipment were both vibration isolated and the CG was off center, a Tm component as shown in Equation (44) would be
computed, divided by 4 for the four corners that would split the load and that would be
added to the mass driven load.
Vertical seismic design force.
This is also driven by the static mass load at each of the four corners would be plus or
minus the mass load x Fpv(g):
Dead load terms.
The maximum dead load terms would be the mass load × 1.2 per LRFD (Equation [5]):
The minimum dead load terms would be the mass load × 0.9 per LRFD (Equation [7]):
Overturning forces.
Per code for vertically cantilevered equipment, the overturning forces, must be computed for
each possible seismic wavefront angle (from 0 to 360° in the plan view). This is
accomplished by performing x and y
axis static analyses using forces that are broken from the parent force Fp based on the angle of attack. The reaction forces
for the load components are then summed for each restraint location and the worst-case
upward and downward forces are retained. The method requires a spreadsheet or computer
program to be accomplished efficiently. As such, the math behind a single load point and
angle will be illustrated here.
Sample computation for the restraint in the bottom left hand corner as shown in Figure 8
at a wavefront angle θ = 30 degrees:
The x component of the Fp
force = Fpx = Fp(– cos θ)
Fpx would generate a reaction on the corner restraint
of
Similarly, the y component of the Fp force = Fpy =
Fp × (– sin θ)
Fpy would generate a reaction on the corner restraint
of
Summing, the overturning reaction at this restraint and this angle would be
After all 360° are analyzed an Overturningmax(+) and
Overturningmin(–) would result.
For each restraint point, the peak vertical loads would be
Prescriptive provisions of ASCE7 can be summarized as follows:
-
Formulas for relative displacement of floor and ceiling can be conservatively estimated
at 1% of the floor-to-ceiling height. This displacement must be used to determine the
required horizontal flexibility of the pipe, duct, or electrical connections at the
equipment interface.
-
In ASCE7, using all-directional snubbers with clearance of more than 1/4 in.
increases Fp by a factor of 2.
-
Component supports must be designed to accommodate component movement to prevent pounding
on the structure or other components. This applies to internal isolators and snubbers.
-
Equipment components exposed to seismic impact forces and using nonductile housings must
be designed using 25% of material yield stresses.
-
Nonessential equipment, failure of which can cause essential equipment failure, must be
designed as essential equipment.
-
If the structure’s site class (soil) is not provided in the contract documents,
assume site class D, subject to change by the building official.
-
Pipe and ducts may not be required to have sway braces, depending on size, material
content, and importance factor. These conditions are defined in Chapter 13 of ASCE7.
1.13 INSTALLATION PROBLEMS
The following should be considered when installing seismic restraints.
-
The proximity of anchors to edges and other anchors can significantly reduce their
capacity. Concrete anchors should be located away from edges, stress joints, or existing
fractures. The evaluation report for the chosen anchor should be followed as a guide for
edge distances and center-to-center spacing.
-
Supplementary steel bases and frames, concrete bases, or equipment modifications may void
some manufacturers’ warranties. Snubbers, for example, should be properly attached
to a subframe.
-
Static analysis does not account for the effects of resonant conditions within a piece of
equipment or its components. Because all equipment has different resonant frequencies
during operation and nonoperation, the equipment itself might fail even if the
restraints do not. Equipment mounted inside a housing should be seismically restrained
to meet the same criteria as the exterior restraints.
-
Snubbers used with spring mounts should withstand motion in all directions. Some snubbers
are only designed for restraint in one direction; sets of snubbers or snubbers designed
for multidirectional purposes should be used.
-
Vibration-isolated equipment must be strong enough to withstand the high deceleration
forces developed by generated motion as the equipment oscillates and closes the gap on
the isolated components, resulting in a large deceleration.
-
Flexible connections should be provided between equipment that is braced and piping and
ductwork that need not be braced.
-
Flexible connections should be provided between isolated equipment and braced piping and
ductwork.
-
Bumpers installed to limit horizontal motion should be outfitted with resilient neoprene
pads to soften the potential impact loads of the equipment.
-
Anchor installations must be inspected (usually required for anchors resisting seismic
forces); in many cases, damage occurs because bolts were not properly installed. To
develop the rated restraint, bolts should be installed according to manufacturer’s
recommendations.
-
Brackets in structural steel attachments should be matched to reduce bending and internal
stresses at the joint.
-
Friction that results from gravity forces cannot be considered when evaluating restraint
capacity. With the exception of heavy-duty clamps used to attach longitudinal restraints
to piping systems, cable clamps, or other devices where clamping forces are predictable
and have been verified to be adequate, friction must not be relied on to resist any
load. All connections should be positive and all holes should be tight-fitting or
grouted to ensure minimal clearance at the attachment points.
1.14 CERTIFICATION OF HVAC&R
COMPONENTS FOR SEISMIC
HVAC&R equipment in seismic design Categories C to F require certifications of compliance of
HVAC&R components for seismic resistance. Certification of compliance for components, defined in
ASCE7, Section 13.2.1, is based on analysis, testing, or experience data. These components include
seismic restraint devices or force resisting systems in equipment. Equipment that is defined as
designated seismic systems (essential for operation,
Ip = 1.5) in ASCE7, Section 13.2.2, must meet special
certification requirements. Certification of this essential equipment in seismic design Categories C
through F is as follows (all section references in the following refer to ASCE7):
-
Active mechanical and electrical equipment that must remain operable following the design
earthquake and where there are active parts or energized components shall be certified
by the supplier as operable based exclusively on approved shake table testing per 13.2.5
or experience data per 13.2.6, unless it can be shown that the component is inherently
rugged by comparison with similar seismically qualified components.
-
Components with hazardous contents shall be certified by the supplier as maintaining
containment following the design earthquake by (1) analysis, (2) approved shake table
testing, or (3) experience data.
-
Non-active and non-energized components may be certified through analysis as long as the
demand load uses Rp/Ip equal to 1.0.
IBC Section 1703.5 identifies requirements for certification by an approved agency with in-plant
inspections and labeling. The IBC further describes how the certification for seismically qualified
equipment is supported with the in-plant inspections by an inspector knowledgeable to recognize the
critical characteristics for seismic applications.
Damage done to HVAC&R equipment by both sustained and gusting wind forces has increased concern about
the adequacy of equipment protection defined in design documents. Two main areas of the HVAC&R
system are exposed to wind events: the HVAC&R equipment and the exterior wall-mounted cladding
components, such as intake and exhaust louvers. For HVAC&R equipment, the following calculative
procedure generates the same type of total design lateral force used in static analysis of the seismic
restraint. The value determined for the design wind force Fw can
be substituted for the total design lateral seismic force Fp when
evaluating and choosing restraint devices. For wall-mounted components, a design wind pressure P is determined, which can be used to specify equipment performance levels and
design anchors to adequately brace wall-mounted cladding components to the building structure.
The state of Florida has special wind requirements; for wind-loaded equipment there, design using the
Florida Building Code for the exact location in the state.
The American Society of Civil Engineers’ (ASCE) Standard 7-16 includes
design guidelines for wind, snow, rain, and earthquake loads. Note that the equations, guidelines, and
data presented here only cover nonstructural components. The current standard (200516) includes more
comprehensive and rigorous procedures for evaluating wind forces and wind restraint. Refer to the latest
version of ASCE7 adopted by the local jurisdiction.
Classification. Buildings and other structures are
classified for wind load design exposure according to Table 6.
Basic wind speed. The fastest mile-per-hour
wind speed at 33 ft above the ground of Terrain Exposure C (see Table 6)
having an annual probability of occurrence of 0.02. Data in ASCE Standard 7 or regional climatic data may be used to determine basic wind
speeds. ASCE data do not include all special wind regions (such as mountainous terrains, gorges, and
ocean promontories) where records or experience indicate that the wind speeds are higher than what
is shown in appropriate wind data tables. For these circumstances, regional climatic data may be
used provided that both acceptable extreme-value statistical analysis procedures were used in
reducing the data and that due regard was given to the length of record, averaging time, anemometer
height, data quality, and terrain exposure. One final exclusion is that tornadoes were not
considered in developing the basic wind speed distributions.
Components and Cladding. Elements of the building envelope
that do not qualify as part of the main wind-force resisting system.
Corner Zone. Areas of building walls and roofs adjacent to
building corners that experience increased external pressure from wind.
Design wind force. Equivalent static force that is assumed
to act on a component in a direction parallel to the wind and not necessarily normal to the surface
area of the component. This force varies with respect to height above ground level.
Importance factor I. A factor that accounts for the degree of hazard to human
life and damage to HVAC components (Table 7). For hurricanes,
the value of the importance factor can be linearly interpolated between the ocean line and 100
miles inland because wind effects are assumed negligible at this distance inland.
Gust response factor G. A factor that accounts
for the fluctuating nature of wind and the corresponding additional loading effects on HVAC
components.
Minimum design wind load. The wind load may not be less than 16
lb/ft2 multiplied by the area of the HVAC component projected on a vertical
plane that is normal to the wind direction.
Two procedures are used to determine the design wind load on HVAC components. The analytical procedure, described here, is the most common
method for standard component shapes, based on the requirements in ASCE7. The second method, the
wind-tunnel procedure, is used in the analysis of complex
and unusually shaped components or equipment located on sites that produce wind channeling or
buffeting because of upwind obstructions. The analytical procedure produces design wind forces that
are expected to act on HVAC components for durations of 1 to 10 s. The various factors, pressure,
and force coefficients incorporated in this procedure are based on a mean wind speed that
corresponds to the fastest wind speed.
The design wind force is determined by the following equation:
where
| Fw = design wind force, lb |
| Qz = velocity pressure evaluated at height z above ground level, lb/ft2 |
| G = gust response factor for HVAC components evaluated at
height z above ground level |
| Cf = force coefficient (Table
9) |
| Af = area of HVAC component projected on a plane
normal to wind direction, ft2 |
Certain of the preceding factors must be calculated from equations that incorporate site-specific
conditions that are defined as follows:
Velocity Pressure. The design wind speed must be
converted to a velocity pressure that is acting on an HVAC component at a height z above the ground. The equation is
where
| Kz = velocity pressure exposure coefficient from
Table 11
|
| Kzt = topographic factor = 1.0 |
| Kd = wind directionality factor = 1.0 |
| V = velocity from Figure
11, mph |
| I = importance factor from Table 7 |
The force generated by the wind is calculated by
where
| Fw = design wind force, lb |
| Qz = velocity pressure evaluated at height z above ground level, lb/ft2 |
| G = gust response factor for HVAC components evaluated at
height z above ground level |
| Cf = force coefficient (Table
9) |
| Af = area of HVAC component projected on a plane
normal to wind direction, ft2 |
The following example calculations are for a 400 ton cooling tower:
.
Tower height h = 10 ft
Tower width D = 10 ft
Tower length l = 20 ft
Tower operating weight Wp =
19,080 lb
Tower diagonal dimension =
= 22.4 ft
Area normal to wind direction Af = 10
× 22.4 = 224 ft2
From Table
10, Cf = 1.0 for wind acting along diagonal with
h/D = 10/10 = 1.
Example 5.
Suburban hospital in Omaha, Nebraska. The top of the cooling tower is 100 ft
above ground level. Building width normal to the wind B =
3000 ft, and building height H = 90
ft.
Solution:
From Figure
12, the design wind speed is found to be 90 mph.
From Table 8, use Category IV.
From Table
6, use Exposure B.
From Table 7, I = 1.15.
From Table 11,
Kz = 0.99.
From Figure
13, Kd = 0.9.
From Table 8, G = 0.85.
Substitution into Equation (58) yields
Building height is greater than 60 ft; therefore, Ef = 1.0.
Substitution into Equation (54) yields the design wind force as
Example 6.
Office building in New York City. Top of tower is 600 ft above ground level.
Building wall normal to the wind B = 600 ft and
building height H = 590 ft.
Solution:
From Figure
12, the design wind speed is 120 mph.
From Table 8, use Category II.
From Table
6, use Exposure B.
From Table 7, I = 1.0.
From Figure
13, Kd = 0.9.
Because z > 500 ft, Kz must be determined from Note 2 of Table 11.
From Table 8, α = 7.0,
zg = 1200, and G =
0.85.
Substituting into the first equation in Note 2 yields
Substituting into Equation (55) yields
Building height is greater than 60 ft, therefore Ef = 1.0.
Substituting into Equation (56) yields the design force wind as
The basic wind speed for design based on ASCE7-16 now uses individual maps based on whether a
building is in design category I, II, III, or IV. Figures
12A to 12H
(at the end of this chapter in the Appendix) show the basic wind speeds to be used.
Example 7.
Church in Key West, Florida. The top of the tower is 50 ft above ground
level. Building wall normal to the wind B = 300
ft and building height H = 40 ft.
Solution:
From Figure
12, the design speed is found to be 150 mph.
From Table 8, use Category III.
From Table
5, use Exposure C (as this is a hurricane-prone region).
From Table 15,
I = 1.15.
From Table 16, G = 0.85.
From Table 12, Kd = 0.9.
From Table 11,
Kz = 1.09 (for exp category C).
From Equation
(55):
Building height is less than 60 ft, Af / (B × H) = 224/(300 × 40) = 0.02, therefore, Ef = 1.9
Substituting into Equation (56) gives the design wind force as
2.3 WALL-MOUNTED HVAC&R COMPONENT
CALCULATIONS (LOUVERS)
For many projects, the structural engineer of record will determine the components and cladding wind
pressures provided on the structural notes drawing. If these wind pressures are not provided, the
two following procedures (described previously) are used to determine the design wind load on HVAC
cladding components.
Velocity Pressure. The design wind speed must be
converted to a velocity pressure that is acting on an HVAC component at height z above the ground. This is done using Equation (54). Once the
velocity pressure has been determined, the design wind pressure can be calculated.
Low-Rise Buildings and Buildings with h ≤
60 ft
The design wind pressure for cladding is determined by the following equation:
where
| Pw = design wind pressure,
lb/ft2
|
| Qh = velocity pressure evaluated at mean roof
height h above ground level, lb/ft2
|
| GCp = external pressure coefficient given in Figure
13 |
| GCpi = internal pressure coefficient given in Table 13 |
Buildings with h > 60 ft
The design wind pressure is determined by the following equation:
where
| Pw = design wind pressure,
lb/ft2
|
| Qz = velocity pressure for windward walls
calculated at height z above the ground of the component
being examined |
| Qh = velocity pressure for leeward walls, side
walls and roofs, evaluated at height h of the roof |
| Qi = velocity pressure for windward walls, side
walls, leeward walls, and roofs, evaluated at height h of
the roof |
| GCp = external pressure coefficient given in Figure
14 |
| GCpi = internal pressure coefficient given in Table 13 |
Example 8.
Office building in Houston, Texas. The top of the building is 30 ft above
grade located in a newly developed suburban area. It is necessary to determine the wind
pressures on louver 1 and louver 2 shown on the building elevation in Figure 15.
Solution:
From Figure
12, the design speed is found to be 120 mph.
From Table 8, use Category II.
From Table
6, use Exposure C.
From Table 7, I = 1.0.
From Table 11,
Kz = 0.98, at roof height, h = 30 ft.
From Table 12, Kd = 0.85.
Kzt assumed to be 1.0.
Determine GCp: Building height h is less than 60 ft; therefore, Equation (55) is
used for the pressure evaluations. GCp must be
determined from Figure 15 for each of
the louvers.
Louver 1: from the notes on Figure 15, it is
necessary to determine the a dimension, which establishes
the corner zone 5. The least horizontal dimension coming into the corner is 32
ft from the plan view. Ten percent of this value is 3.2 ft. The
minimum value for the corner dimension is 3 ft. Louver 1 is located 1
ft 2 11/16 in. from the corner and is therefore in corner zone 5.
From Figure 15, GCp = +0.95 or –1.3 for a 20
ft2 wind area. A positive GCp indicates a positive pressure on the windward
side of the building. A negative GCp indicates a
suction pressure on the leeward side of the building. Both cases must be evaluated.
Louver 2: based on the corner calculation, louver 2 is in
noncorner zone 4. From Figure 15, GCp = +0.9 or –1.0 for a 30
ft2 wind area.
Determine GCpi: See Figure
14. Most buildings without significant wall openings are enclosed buildings. For
the purposes of this example, an enclosed building is assumed. GCpi = +0.18 or –0.18. A positive sign
indicates pressure outward on all structure walls. A negative sign indicates pressure
inward on all structure walls.
Determine velocity pressure at roof elevation h from Equation
(55):
Determine design wind pressure P from Equation (56):
Louver 1, case 1: positive external, positive internal
Louver 1, case 2: positive external, negative internal
Louver 1, case 3: negative external, positive internal
Louver 1, case 4: negative external, negative internal
The controlling values for P for louver 1 are 34.7
lb/ft2, – 45.4 lb/ft2 and should be used to
specify equipment performance levels.
Louver 2, case 1: positive external, positive internal
Louver 2, case 2: positive external, negative internal
Louver 2, case 3: negative external, positive internal
Louver 2, case 4: negative external, positive internal
The controlling values for P for louver 2 are 33.2
lb/ft2, – 36.2 lb/ft2 and should be used to
specify equipment performance levels.
2.4 CERTIFICATION OF HVAC&R
COMPONENTS FOR WIND
Some jurisdictions require certifications of performance of HVAC&R components for wind
resistance. These certifications focus on (1) the equipment’s ability to remain intact and/or
(2) the equipment restraints and anchors to keep the item in place during a wind event.
In the United States, the State of Florida and the Building Code Compliance Office of Miami-Dade
County have certification requirements that affect HVAC&R system designers. The HVAC products
may have special requirements for wind performance and may need approval of the State of Florida. In
addition to wind performance, the Florida Building Code (ICC 2007) requires impact resistance and
wind-pressure resistance for items that protect openings in buildings in windborne debris regions.
HVAC products provided for projects located in these regions may be required to have testing and
product certification from the State of Florida before installation. Other states, such as Texas,
also have requirements for wind-pressure and impact testing. To ensure that the HVAC&R equipment
supplied is compliant, designers should contact the local building code official in their project
location.
Flooding is the most common natural hazard in the United States, affecting more than 20,000 local
jurisdictions and representing more than 70 percent of Presidential disaster declarations. Several
evaluations have estimated that 7 to 10 percent of U.S. land area is subject to flooding. Some
communities have very little flood risk, while others lie entirely within areas designated by FEMA as
special flood hazard areas (SFHAs). This section addresses design of HVAC systems to minimize flood
effects before the flood occurs and what items may be required during the flood. This chapter does not
address restoration after the flood.
Flooding events are generally subcategorized as either riverine or coastal. Riverine flooding results
when the volume of rainfall or runoff exceeds the capacity of waterway channels and spreads out over the
adjacent land. Flooding depth, duration, and velocity are functions of many factors, including watershed
size and slope, degree of upstream development, soil types and nature of vegetation, topography, and
characteristics of storms (or depth of snowpack and rate of melting).
In North America, coastal flooding occurs along the Atlantic, Gulf, and Pacific coasts, and along the
shores of the Great Lakes. There is significant flooding throughout many countries. Coastal flooding is
influenced by storm surges associated with tropical cyclonic weather systems (hurricanes, tropical
storms, tropical depressions, typhoons), extratropical systems (nor’easters and other large
low-pressure systems), and tsunamis (surges induced by seismic activity). Coastal flooding is
characterized by wind-driven waves.
The intensity of both riverine and coastal flooding events is measured by the depth and velocity of flood
waters, the duration for which the waters remain above normal levels, and whether any debris damage,
wave action, and erosion or scour occurred.
Overhead lines are generally not at a significant risk for flood damage. Energized power lines are
elevated to prevent people from accidentally coming into contact with them, and the elevation
protects much of an overhead electrical system from flood inundation damage. However, some portions
of an overhead electrical system (most notably substations) are not elevated. Such portions of an
overhead system may be vulnerable to inundation, particularly when located in low-lying areas or in
SFHAs. Structures that support overhead lines can be damaged by moving floodwaters from scour,
erosion, and hydrodynamic loads. Structures can be damaged by floating debris or soil saturation.
Underground portions of power lines are generally resistant to damage from freshwater flooding.
Aboveground components of underground power line systems, such as pad-mounted transformers,
medium-voltage sectionalizing switches, and pad-mounted switchgear, are vulnerable to floods. Like
the supporting structures for overhead lines, pad-mounted equipment can be damaged by hydrostatic
forces, hydrodynamic forces, flood-borne debris impact, scour, and erosion. Submersion can also
short-circuit energized pad-mounted equipment, particularly the older style live-front equipment.
For many facilities, flood poses a risk of damage to building systems and can prevent a facility from
functioning. Major components of buildings systems, such as boilers, electrical service and
distribution equipment, fuel tanks and fuel pumps, other pumps, and IT servers, are often located in
the lowest level of a building, which is the level most vulnerable to flooding. Another area that is
vulnerable to flooding is rooftop equipment that is prone to overturning during high windstorms and
can leave a hole in the roof curbs, thus allowing flooding of the building when it is raining.
The risk of flood damage is particularly high for buildings that were constructed before flood risks
were quantified in the 2006 International Building Code (IBC). The 2006
International Building Code (IBC) is when the code first referenced ASCE
24-05, Flood Resistant Design and Construction (ASCE, 2005). ASCE 24-05
requires that building systems (referred to as “utilities” in that standard) either be
elevated above design flood elevations or provided with flood protection.
Flooding historically has been disastrous for emergency power systems. Floodwater can damage or
inundate fuel tanks that supply diesel generators, fuel oil pumping equipment, and emergency power
distribution equipment, such as transfer switches, panels, and feeders. Many post-flood event
investigations have shown that components of the emergency power and distribution system are often
placed at lower elevations than components of the normal power distribution system and therefore are
more vulnerable to flooding.
Base Flood. A term used in the National Flood Insurance
Program to indicate the minimum size flood to be used by a community as a basis for its floodplain
management regulations; presently required by regulation to be that flood which has a 1% chance of
being equaled or exceeded in any given year. Also known as a 100-year flood or 1% chance flood.
Base Flood Elevation (BFE). The resulting elevation of the
flood water at specific areas within identified in the FEMA flood maps based on the Base Flood.
Base Floodplain. The floodplain that would be inundated by
a 100-year (1% chance) flood.
Critical Facilities. Structure or related infrastructure
that if flooded may result in significant hazards to public health and safety or interrupt essential
services and operations for the community at any time before, during and after a flood.
Deep. Deep flooding is where large amount of water flowing
is restricted by barriers also known as a channel (natural occurring hills or buildings). As the
water flow increases, the water levels raise and increase in water velocities causing major erosion.
FEMA. Federal Emergency Management Agency, the agency
responsible for administering the National Flood Insurance Program (NFIP), or successor agency. FHAD
(Flood Hazard Area Delineation) a flood study often prepared on a watershed basis by the Urban
Drainage and Flood Control District. FHADs are adopted by the State and affected communities like
LOMCs. FHADs are eventually submitted to FEMA as PMRs and become part of the updated FEMA FIRM map.
Flash Flood. Large amount of water is directed into
natural occurring ravines. Flash flooding can be caused by heavy rains, snow melt, ice jams, or when
dams or levees break.
Floatable Materials. Material that is not secured in place
or completely enclosed in a structure, so that it could float off site during the occurrence of a
flood and potentially cause harm to downstream property owners, or that could cause blockage of the
channel or drainageway, a culvert, bridge, or other drainage facility. This includes, without
limitation, lumber, vehicles, boats, equipment, trash dumpsters, tires, drums or other containers,
pieces of metal, plastic or any other item or material likely to float.
Flood Duration. The length of time a stream is above flood
stage or overflowing its banks.
Flood Hazard Boundary Map. An official map of a community
issued by the Federal Insurance Administration on which the boundaries of the floodplain (i.e.,
subject to the 100-year flood), mudslide and/or flood-related erosion areas having special hazards
have been drawn.
Flood Profile. A graph or plot of the water surface
elevation against distance along a channel drawn for a specific flood or level of flooding.
Floodplain Regulations. A general term for the full range
of codes, ordinances, and other regulations relating to the use of land and construction within
stream channels and floodplain areas. The term encompasses zoning ordinances, subdivision
regulations, building and housing codes, encroachment line statutes, open-space regulations, and
other similar methods of control affecting the use and development of these areas.
Ground Water Recharge. The infiltration of water into the
earth. It may increase the total amount of water stored underground or only replenish supplies
depleted through pumping or natural discharge.
Hydrodynamic Loads. Forces imposed on structures by
floodwaters due to the impact of moving water.
Hydrostatic Loads. The infiltration of water into the
earth. It may increase the total amount of water stored underground or only replenish supplies
depleted through pumping or natural discharge.
Letter of Map Amendment (LOMA). A letter from FEMA
officially amending the effective National Flood Insurance Rate Map, which establishes that a
property is not located in a FEMA SFHA.
Obstruction. Any physical barrier, structure, material or
impediment in, along, across or projecting into a watercourse that may alter, impede, retard or
change the direction or velocity of the flow of water, or that may, due to its location, have a
propensity to snare or collect debris carried by the flow of water or to be carried downstream.
Obstruction shall include, but not be limited to, any dam, wall, wharf, embankment, levee, dike,
pile, abutment, protection, excavation, channelization, bridge, conduit, culvert, building, wire,
fence, rock, gravel, refuse, fill, structure, and vegetation in, along, across or projecting into a
watercourse.
Probable Maximum Flood. The most severe flood that may be
expected from a combination of the most critical meteorological and hydrological conditions. It is
used in designing high-risk flood facilities that shall be protected with minimal risk of flooding.
The probable maximum flood is usually much larger than the 100-year flood.
Reservoir. A natural or artificially created pond, lake or
other space used for storage and control of water. May be either permanent or temporary.
Shallow. Shallow flooding is defined as flooding with an
average depth of one to three feet. Shallow flooding usually is where the water flow in the area is
lower and covers more area. Water seepage in the ground is more prevalent and all construction below
water level is subject to water pressure.
Special Flood Hazard Area (SFHA). Land subject to 1% or
greater chance of flooding in any given year (i.e. the 100-year floodplain; see Figure 16
and Table 14). It is the land
area covered by the floodwaters of the base flood on the Flood Insurance Rate Maps. The SFHA is the
area where the National Flood Insurance Program’s floodplain management regulations must be
enforced and the area where the mandatory purchase of flood insurance applies. The SFHA includes
Zones A, AO, AH, AE, A99, AR, AR/AE, AR/AO, AR/AH, and AR/A.
Structural Measures. Flood control works such as dams and
reservoirs, levees and floodwalls, channel alterations, seawalls, and diversion channels which are
designed to keep water away from specific developments and/or populated areas or to reduce flooding
in such areas.
Subsidence. Sinking of the land surface, usually due to
withdrawals of underground water, oil, or coal.
3.2 REGULATIONS AND CODES
FEMA is the main agency that provides insurance for damage associated with flooding. Since this is a
government agency, there are several prerequisites that need to be followed to receive government
funding in terms of insurance coverage. Congress established the NFIP on August 1, 1968, with the
passage of the National Flood Insurance Act (NFIA) of 1968, which has been modified over the years.
The National Flood Insurance Program (NFIP) is managed by the FEMA and is delivered to the public by
independent insurance companies.
Floods can happen anywhere, and just an inch of floodwater can cause significant damage.
Most homeowners’ insurance does not cover flood damage. Flood insurance is a separate policy
that can cover buildings, the contents in a building, or both, so it is important to protect these
important financial assets. FEMA publication 348, Protecting Building Utilities
from Flooding damage, is a good document to help protect HVAC, electrical, and plumbing
systems for flooding. It provides principles and practices for the design and construction of flood
resistant building utility systems.
The NFIP provides flood insurance to property owners, renters, and businesses. They work with
communities required to adopt and enforce floodplain management regulations that help mitigate
flooding effects. Flood insurance is available to anyone living in participating NFIP communities.
Homes and businesses in high-risk flood areas with mortgages from government-backed lenders are
required to have flood insurance. The National Flood Insurance Program's (NFIP) offer guidance on
conducting daily operations for existing and new NFIP sellers and servicers. Information on the
Write-Your-Own program, reinsurance, Risk Rating 2.0, plus the Flood Insurance
Manual and other tools are available online. There also are publications, videos,
graphics, and online tools that help policyholders, agents, and other servicers navigate the flood
insurance process before, during and after disaster.
Most states adopt the FEMA regulations as written without any changes or additional regulations as it
applies to buildings within the FEMA flood maps. Florida is the exception. Starting with the 2010
edition, the Florida Building Code (FBC) includes flood provisions that
meet or exceed the NFIP requirements for buildings and structures. All counties, cities and towns
are required to enforce the FBC. Many Florida communities enforce some higher standards than those
required by the FBC.
The International Building Code® (IBC) has minimal
requirements for flooding. There are two locations that apply to HVAC equipment:
-
1202.4.4, Flood hazard areas. For buildings in
flood hazard areas as established in Section 1612.3, the openings for under-floor
ventilation shall be deemed as meeting the flood opening requirements of ASCE 24
provided that the ventilation openings are designed and installed in accordance with
ASCE 24.
-
G1001.6, Protection of mechanical, plumbing, and electrical
systems. Mechanical, plumbing, and electrical systems, including
plumbing fixtures, shall be elevated to or above the design flood elevation. The
exceptions are electrical systems, equipment and components; heating, ventilating, air
conditioning and plumbing appliances; plumbing fixtures, duct systems and other service
equipment shall be permitted to be located below the design flood elevation provided
that they are designed and installed to prevent water from entering or accumulating
within the components and to resist hydrostatic and hydro-dynamic loads and stresses,
including the effects of buoyancy, during the occurrence of flooding to the design flood
elevation in compliance with the flood-resistant construction requirements of this code.
Electrical wiring systems shall be permitted to be located below the design flood
elevation if they conform to the provisions of NFPA Standard
70.
HVAC and utility systems are a potential target for flooding events. The first design question that
is always the best is if the equipment and systems can be moved above the design flood elevation (DFE). Moving the equipment above
the DFE is preferable. Check the local codes for restrictions when moving the equipment above the
DFE. Moving equipment requires additional space above the DFE that is already assigned to other
priorities. The spaces may require modifications to allow the equipment to be relocated. The design
professionals should be involved with all relocation design application.
HVAC systems have several potential targets for flooding including equipment (boilers, furnaces,
compressors, fans, and filters), piping, ductwork, and penetrations. Table 15 gives some
examples of concerns for various building types. Some equipment that is below the DFE can be sealed
with waterproof materials. Heat exchange or fuel-burning equipment would require barriers that reach
above the DFE. Sealing ductwork is possible but expensive. Any ductwork affected by flood waters and
not sealed would have to be replaced. Cleaning is not recommended because of the potential of
bacterial left by the flood. Flood waters are contaminated, and equipment can be cleaned or
refurbished. Flood waters also contain corrosive material. Most outdoor equipment has waterproof
electrical connections at the compressor, but the controls may not be protected, and new control
boxes needed for the refurbishment.
Penetrations like all normal building construction is not watertight. Even concrete construction has
seams that allow a long-term flooding event to challenge. Normal construct walls are not watertight.
Areas that need to be protected below the DFE will require as best as possible flood waterproofing,
continuous monitoring during a flood (which means access to the areas), and a sump pump that removes
any flood water entering the protected areas. HVAC, electrical, and piping penetrations need to be
sealed.
Potable water systems outside of the buildings are protected by the nature of the piping systems are
sealed. Any water access to the outside from the inside of the buildings and below the DFE may be
contaminated and should be protected with a backflow preventer. The water supply can also be
contaminated by the flooding condition. Contact local authorities for any restrictions on potable
water systems during and after a flood. External piping above grade should be evaluated for
potential impact of debris where water is moving.
Sewage systems are very different form potable water systems. Underground piping systems outside of
the building are not sealed and will be contaminated by the flood conditions. Collection systems
should be located above the DFE or protected with backflow preventers. Plugs or other methods to
seal penetrations (sewage openings) in the building need to be sealed during and may be required
sometime after a flooding event.
Fuel systems need attention for flooding events. Gas piping is sealed and usually protected from
normal underground moisture. Aboveground thick-walled piping is susceptible to degrading from moving
flood waters but will not require any additional special waterproofing treatment. Fuel tanks are
outside and always a target for flooding events. Aboveground tanks need to be anchored to prevent
flotation. Even if the tanks are full, at some time the fuel may be used during the flooding event
and the tank to float. Protecting aboveground tanks from moving debris is also a concern and may
require protection barriers (permanent to temporary).
Tanks installed below grade are anchored for potential water table issues. Waterproofing is usually
performed below grade but not above grade. The access ports in a below grade tank need to be sealed
and there is always a vent that needs to be elevated above the DFE. The other concern is refueling
for long term events. If fuel and the generator/heating systems are required to be operational for
long periods, that only solution is to move all the equipment and fuel tanks to a location that is
above the DFE and accessible for refueling.
Electrical systems have many issues with flooding events. The main potential is short circuiting
equipment, tripping breakers, and taking power supply systems offline. The potential targets are
meters, panels, circuit breakers, appliances, electrical receptacles ground fault protection, and
cables. This equipment is not waterproof and should be protected or moved is possible. Refurbishment
of the electrical systems is required after a flooding event to determine all the devices that need
to be replaced.
Fire protection systems are robust and not susceptible to
damage or malfunction during a flood. Because of flooding, fires may start from the short circuiting
of electrical systems. Design and construction of the electrical system can minimize but may never
mitigate the issues associated with electrical systems and the risk of surges, sparks, and
electrocution. If water is a threat from a flood or other potential water surge in the area, then
the electrical system should be isolated as possible to stop all electrical circuits. Unplug
electrical appliances and HVAC as appropriate. Isolate flammable or chemical substances (tanks and
gas lines).
Emergency power and heating systems may be implemented at
the facility. These items shall be designed and installed with flood mitigation features. These are
in case of major power outages. Main power lines can also cause electrical shorts and fires in the
area which could affect the building systems.
Building wall and floor construction as mentioned
previously may be watertight. This is a rare case, and all construction buildings shall be evaluated
to determine if the structure is worth and/or needs to be protected from flooding with flood
mitigating features. Buildings can be constructed on piers to raise the building above the DFE (ASCE
24).
Wall construction made from standard non-concrete (perishable material) is susceptible to damage
during flooding. These structures are not watertight and all inside contents are subject to water
damage up to the DFE. When the flooding event is over, all material affected by the water damage
must be remediated. This will include wood (structural framing, floors and any cabinetry), drywall,
insulation, electrical (cables and receptacles), and HVAC systems (including ductwork).
Soil considerations in building system construction and
design is important. Most important is when soil is saturated with water, it may heave and cause
damage. No soil will protect building from water saturation and water seeking the DFE water level in
all areas affected by the flood. And cavity (building space) below the DFE will see water seeping
through the ground and into building structure. This water is contaminated and acidic in nature.
Degradation of the building structure below grade is susceptible to damage. Cases have shown water
flowing below grade can eat away metal due to electrolysis. Other considerations are degradation of
the building foundation to be evaluated by design professionals. Soil outside of the building may be
contaminated and treated before planting foliage.
Building categories looks at the different types of buildings and provides insight associated with
that specific building type. Many items associated with systems have been discussed above about the
systems and building construction. This section is in addition to the items previously discussed.
Most hospitals are designated to be functional during a
flooding event. Before a flooding event, all aspects of the HVAC and utility design should have
addressed mitigating the flooding potential effects. The items that need to be functional shall be
protected or are located above the DFE plus 6 ft. Local codes may require more
stringent requirements. Mold resistant materials should be used for the infrastructure HVAC and
utility systems. This will reduce potential mold affects after a flooding event but may not
eliminate all mold issues. All life safety equipment shall be protected including electrical,
phones, data centers, and emergency trauma units. After a flooding event, the HVAC systems shall be
evaluated for cleanliness. All equipment shall be evaluated for functionality. Mold should be
removed and treated with UV systems or other types of removal. This treatment can be permanent or
temporary/portable equipment. See Chapters 62 and 64 for information on UV
and moisture management, respectively.
Clinics are emerging and needs to be reviewed for Flood mitigation as defined by the local authority
having jurisdiction.
Museums are an important part of society and needs to be protected from a flooding event. All
displays shall be moved to an elevation of the DFE plus 12 ft. All displays not being
used shall be stored is a remote area that is not in any flood zone. After an event, all moisture
and mold shall be quickly addressed as discussed in the hospital building category. Any displays
that are susceptible to moisture degradation shall be moved or protected during and after a flooding
event.
Airports, rail stations, and bus stations are in potential flood zones. These have been established
and require flood mitigation evaluations. Before a flooding event airports or facilities (due to
their size) shall have a plan for emergency access and egress. Areas and runways below the DFE need
to be protected by levees (see ASCE 24). Planes, trains, and buses are a capital investment and will
be moved as defined by their air carrier or owner. Alternate airport, train, or bus operation shall
be negotiated prior to the event for continued operation. HVAC and utility systems shall be
evaluated for emergency use during the flooding event. Those items necessary for safe operation of
the airport or facilities shall be moved or protected from the flooding event plus 6 feet. This
includes access to the airport control tower. The infrastructure that support airport operations
such as baggage handling shall be addressed by each airline carrier.
Emergency facilities include incident command centers, emergency call centers, flood shelters, and
potential sport stadiums that will house many displaced people during a flood shall be evaluated for
mitigation during a flooding event. Emergency facilities category includes police stations, prisons,
and detention centers. Before a flooding event emergency facilities shall be evaluated for a
flooding event. HVAC and utility systems shall be evaluated for emergency use during the flooding
event. Those items necessary for safe operation of the facilities shall be moved or protected from
the flooding event plus 6 ft or as defined by the local authority have jurisdiction.
This includes access of emergency personnel and operational personnel to oversee operating
equipment. The infrastructure that support operations of all emergency facility functions shall be
reviewed for mitigation features.
Petrochemical and industrial facilities have unique issues associated with flooding events. Caustic
materials are a potential public hazard if the hazardous material is in contact with flood waters.
Any potential water hazard or other airborne hazard that could be affected by a flooding event shall
be evaluated for mitigation and protection of any toxic release.
Commercial and tall buildings are a potential target for a flooding event. These facilities do not
usually have special requirements except for emergency egress. Some structural elements such as
floating floors (isolation systems) are subject to water damage and should be mold resistant. For
example, wood, plywood, fiberglass, perimeter boards, caulking material, and other elements be
located above the DFE plus 6 ft.
Universities and dormitories have experienced damage from flooding. Each university shall review the
infrastructure and identify the assets that need to be protected from flooding. Many facilities have
the infrastructure HVAC and systems and shall evaluate the need to move or protect these items from
a flooding event.
Residential and condominiums are governed by the local authority have jurisdiction.
3.6 FLOODING RESPONSE PLAN
A flood response plan is the most valuable tool when responding to a flooding event. The plan has
step by step procedures for each facility to be implemented before an event and a timeline for
implementing the procedures. The timeline to accomplish flood mitigation must be less that the
amount of warning that would be received from the national emergency weather service. Each procedure
must be validated so that it can be fully implemented in the time defined. The validation will
identify if the flood doors really fit and if all the potential flooding vulnerabilities are
addressed. The decision to implement the flooding procedures in not done lightly or without
financial penalty. Waiting too long to implement the flooding procedures has a bigger financial
penalty.
The response plan must address the equipment and personnel required to implement the flooding
procedures, address the equipment and personnel that is required during the flood to keep all flood
equipment (pumps and generators) running including delivery of fuel. Shift turnover must be
addressed. The response plan shall address the actions required following a flooding event to
restore the facilities to an operational status.
Flood plans and procedures will address the mitigation features for protecting capital assets and
maintaining emergency functions. All the service within a flood target must be defined and addressed
to ensure they will remain operational during a flooding event. The environment and air filtration
are required to maintain air quality for all occupied areas. Outside areas that require personnel to
be in flood waters shall be protected with personnel safety equipment (ropes and harnesses),
handrails and nets, or elevated walkways.
Areas that are protected in the flood plans address potential entry points for water which include
doors, drains, and any seam in a concrete structures. Permanent or temporary flood barriers are
installed with gaskets, sealing material, and other isomeric products. Active pumping stations are
implemented along with portable electrical power stations to provide power to pumps. Gas and
diesel-driven pumps are usually outdoors and require hourly observation and refilling. Follow all
equipment precautions for operating and refueling for safe operation of the equipment.
Flood plans will address permanent flood mitigation such a levees defined in ASCE 24. Mitigation will
identify permanent or temporary barriers required to protect outdoor equipment from moving debris.
ASHRAE members can access ASHRAE Journal articles and ASHRAE research project
final reports at technologyportal.ashrae.org. Articles and reports are also available for purchase
by nonmembers in the online ASHRAE Bookstore at www.ashrae.org/bookstore.
ACI. 2014. Building code requirements for structural
concrete (ACI 318-08) and commentary. Standard 318-08. American
Concrete Institute, Farmington Hills, MI.
AISC. 1989. Manual of steel
construction—Allowable stress design, 9th ed. American Institute of Steel
Construction, Chicago.
ASCE. 2016. Minimum design loads for buildings and other
structures. Standard ASCE7-16. American Society of Civil Engineers,
Reston, VA.
ASHRAE. 2012. Practical guide to
seismic restraint.
ASME. 2003. Nuclear air and gas treatment. Code
AG-1-2003. American Society of Mechanical Engineers, New York.
ASTM. 1996. Test methods for strength of anchors in
concrete and masonry elements. Standard E488-96 (R2003). American
Society for Testing and Materials, West Conshohocken, PA.
ATC. Proceedings of seminar on
seismic design, performance, and retrofit of nonstructural components on critical
facilities. ATC 29-2. Applied Technology Council, Washington, D.C.
AWC. 1997. National design
specification (NDS®) for wood construction. American Wood Council,
Washington, D.C.
BOCA. 1996. The BOCA national
building code, 13th ed. Building Officials & Code Administrators International,
Inc., Country Club Hills, IL.
Cover, L.E., et al. 1985. Handbook of nuclear power
plant seismic fragilities. Report NUREG/CR-3558. Lawrence Livermore
National Laboratory and U.S. Nuclear Regulatory Commission, Washington, D.C.
DOD. 1990. Structures to resist the effects of
accidental explosions. Technical Manual TM 5-1300. U.S. Department
of Defense, Washington, D.C.
DOD. 2002. Design and analysis of hardened structures to
conventional weapons effects. Technical Manual TM 5-855-1. U.S.
Department of Defense, Washington, D.C.
ICC. 2010. Florida building
code. International Code Council, Inc., Washington, D.C.
ICC. 2012. International building
code®. International Code Council, Washington, D.C.
ICC-ES. 2007. Acceptance criteria
for seismic qualification by shake-table testing of nonstructural components and
systems. AC156. ICC Evaluation Service, Inc., Whittier, CA.
ICBO. 1997. Uniform building
code. International Conference of Building Officials, Whittier, CA. (Now part of
ICC.)
NRC-IRC. 2010. National building
code of Canada. National Research Council Institute for Research in Construction,
Ottawa.
SBCCI. 1994. Standard building
code 1996. Southern Building Code Congress International, Inc., Birmingham,
AL.
SMACNA. 2008. Seismic restraint
manual: Guidelines for mechanical systems, 3rd ed. Sheet Metal and Air Conditioning
Contractors’ National Association, Chantilly, VA.
U.S. Army, Navy, and Air Force. 1992. Seismic design for buildings. TM 5-809-10, NAVFAC P-355, AFN 88-3,
Chapter 13.
U.S. COE. 1998. Technical
instructions: Seismic design for buildings. TI 809-04. U.S. Army Corps of Engineers,
Washington, D.C.
AISC. 1995. Manual of steel
construction—Load and resistance factor design, 2nd ed. American Institute of
Steel Construction, Chicago.
Associate Committee on the National Building Code. 1985.
National building code of Canada 1985, 9th ed. National Research
Council of Canada, Ottawa.
Associate Committee on the National Building Code. 1986.
Supplement to the National Building Code of Canada 1985, 2nd ed.
National Research Council of Canada, Ottawa. First errata, January.
ATC. Proceedings of seminar and
workshop on seismic design and performance of equipment and nonstructural elements in
buildings and industrial structures. ATC 29, NCEER (New York) & NSF (Washington
D.C.).
ATC. Seminar on seismic design,
retrofit, and performance of nonstructural components. ATC 29-1, NCEER (New York)
& NSF (Washington D.C.).
AWS. 2000. Structural welding
code. AWS D1.1-2000. Steel American Welding Society, Miami.
Ayres, J.M., and R.J. Phillips. 1998. Water damage in
hospitals resulting from the Northridge earthquake. ASHRAE
Transactions 104(1B):1286-1296.
Batts, M.E., M.R. Cordes, L.R Russell, J.R. Shaver, and
E. Simiu. 1980. Hurricane wind speeds in the United States. NBS BSS
124. National Institute of Standards and Technology, Gaithersburg, MD.
Bolt, B.A. 1988. Earthquakes. W.H. Freeman, New York. DOE. 1989. General design
criteria. DOE Order 6430.1A. U.S. Department of Energy, Washington, D.C.
FEMA 368 & 369. NEHRP
recommended provisions for seismic regulations for new buildings and other structures. Part
1, Provisions; Part 2, Commentary. Building Seismic Safety Council, Washington,
D.C.
FEMA 413. Installing seismic
restraints for electrical equipment. Federal Emergency Management Agency, Washington,
D.C.
FEMA 414. Installing seismic
restraints for duct and pipe. Federal Emergency Management Agency, Washington,
D.C.
Jones, R.S. 1984. Noise and
vibration control in buildings. McGraw-Hill, New York.
Kennedy, R.P., S.A. Short, J.R. McDonald, M.W. McCann,
and R.C. Murray. 1989. Design and evaluation guidelines for the Department
of Energy facilities subjected to natural phenomena hazards.
Lama, P.J. 1998. Seismic codes, HVAC pipe systems and
practical solutions. ASHRAE Transactions 104(1B):1297-1304.
Maley, R., A. Acosta, F. Ellis, E. Etheredge, L. Foote,
D. Johnson, R. Porcella, M. Salsman, and J. Switzer. 1989. Department of the Interior, U.S.
geological survey. U.S. geological survey strong-motion records from the Northern California
(Loma Prieta) earthquake of October 17, 1989. Open-file Report
89-568.
Meisel, P.W. 2001. Static modeling of equipment acted on
by seismic forces. ASHRAE Transactions 107(1):775-786.
Naeim, F. 1989. The seismic design
handbook. Van Nostrand Reinhold International Company Ltd., London, England.
Naeim, F. 2001. The seismic design
handbook, 2nd ed. Kluwer Academic, Boston.
NFPA. 2016. Standard for the installation of sprinkler
systems. Standard 13-2016. National Fire Protection Association,
Quincy, MA.
Peterka, J.A., and J.E. Cermak. 1974. Wind pressures on
buildings—Probability densities. Journal of Structural
Division, ASCE 101(6):1255-1267.
Simiu, E., M.J. Changery, and J.J. Filliben. 1979. Extreme wind speeds at 129 stations in the contiguous United States.
U.S. NBS BSS 118. National Institute of Standards and Technology, Gaithersburg, MD.
SMACNA. 2005. HVAC duct
construction standard—metal and flexible, 3rd ed. Sheet Metal and Air
Conditioning Contractors’ National Association, Chantilly, VA.
VISCMA. 2014. Installing seismic restraints for
mechanical equipment. Standard 412. Vibration Isolation and Seismic
Control Manufacturers Association, Wayne, PA.
Wasilewski, R.J. 1998. Seismic restraints for piping
systems. ASHRAE Transactions 104(1B):1273-1295.
Weigels, R.L. 1970. Earthquake
engineering, 10th ed. Prentice-Hall, Englewood Cliffs, NJ.