Modern laboratories require regulated temperature, humidity, relative
static pressure, air motion, air cleanliness, sound, and exhaust. This chapter addresses biological,
chemical, animal, and physical laboratories. Within these generic categories, some laboratories have
unique requirements. This chapter provides an overview of the HVAC characteristics and design criteria
for laboratories, including a brief overview of architectural and utility concerns. This chapter does
not cover pilot plants, which are essentially small manufacturing units.
The function of a laboratory is important in determining the appropriate HVAC system selection and
design. Air-handling, hydronic, control, life safety, and heating and cooling systems must function as a
unit and not as independent systems. HVAC systems must conform to applicable safety and environmental
regulations.
Providing a safe environment for all personnel is a primary objective in the design of HVAC systems for
laboratories. A vast amount of information is available, and HVAC engineers must study the subject
thoroughly to understand all the factors that relate to proper and optimum design. This chapter serves
only as an introduction to the topic of laboratory HVAC design. HVAC systems must integrate with
architectural planning and design, electrical systems, structural systems, other utility systems, and
the functional requirements of the laboratory. The HVAC engineer, then, is a member of a team that
includes other facility designers, users, industrial hygienists, safety officers, security, operators,
and maintenance staff. Decisions or recommendations by the HVAC engineer may significantly affect
construction, operation, and maintenance costs. Greater detail on the design of laboratory HVAC systems
can be found in both ASHRAE Laboratory Design Guide (2002) and The Classification of Laboratory Ventilation Design Levels (2018), both
developed by TC 9.10.
Laboratories frequently are 100% exhausted and use high amounts of outdoor air, which broadens the range
of conditions to which the systems must respond. They seldom operate at maximum design conditions, so
the HVAC engineer must pay particular attention to partial load operations that are continually changing
due to variations in internal space loads, exhaust requirements, external conditions, and day/night
variances. Most laboratories will be modified at some time. Consequently, the HVAC engineer must also
consider to what extent laboratory systems should be adaptable for other needs. Both economics and
integration of the systems with the rest of the facility must be considered.
1. GENERAL DESIGN GUIDANCE
Laboratories can be divided into the following general types:
-
Biological laboratories are those that
contain biologically active materials or involve the chemical manipulation of these
materials. This includes laboratories that support such disciplines as biochemistry,
microbiology, cell biology, biotechnology, genomics, immunology, botany,
pharmacology, and toxicology. Both chemical fume hoods and biological safety
cabinets are commonly installed in biological laboratories.
-
Chemical laboratories support both organic
and inorganic synthesis and analytical functions. They may also include laboratories
in the material and electronic sciences. Chemical laboratories commonly contain a
number of fume hoods.
-
Animal laboratories are areas for
manipulation, surgical modification, and pharmacological observation of laboratory
animals. They also include animal holding rooms, which are similar to laboratories
in many of the performance requirements but have an additional subset of
requirements.
-
Physical laboratories are spaces
associated with physics; they commonly incorporate lasers, optics, radioactive
material, high- and low-temperature material, electronics, and analytical
instruments.
Laboratory Resource Materials
The following are general or specific resource materials applicable to various types of
laboratories.
-
ACGIH. Industrial Ventilation: A Manual of Recommended
Practice. American Conference of Governmental Industrial Hygienists,
Cincinnati, OH.
-
FGI guidelines for design and construction. The Facilities Guideline Institute,
American Society of Healthcare Engineering, Chicago, IL.
-
ASSE. Laboratory Ventilation. ANSI/ASSE Standard
Z9.5-2022. American Society of Safety Engineers, Des Plaines, IL
-
ASHRAE Laboratory Design Guide.
-
ASHRAE Classification of Laboratory Ventilation Design
Levels.
-
CAP. Medical Laboratory Planning and Design. College
of American Pathologists, Northfield, IL.
-
DHHS. Biosafety in Microbiological and Biomedical
Laboratories. U.S. Department of Health and Human Services (CDC).
-
EEOC. Americans with Disabilities Act Handbook. Equal
Employment Opportunity Commission.
-
I2SL. I2SL’s Electronic
Library. i2sl.org/elibrary/index.html.
International Institute for
Sustainable Laboratories.
-
NFPA. Fire Protection Guide for Hazardous Materials.
National Fire Protection Association, Quincy, MA.
-
NFPA. Fire Protection for Laboratories Using Chemicals. ANSI/NFPA Standard 45. National Fire Protection Association,
Quincy, MA.
-
NRC. Biosafety in the Laboratory: Prudent Practices for
Handling and Disposal of Infectious Materials. National Research
Council, National Academy Press, Washington, D.C.
-
NRC. Prudent Practices in the Laboratory: Handling and
Management of Chemical Hazards, updated version. National Research
Council, National Academy Press, Washington, D.C.
-
NSF. Class II Biosafety Cabinetry. NSF/ANSI Standard
49.
-
OSHA. Occupational Exposure to Chemicals in
Laboratories. ppendix VII, 29 CFR 1910.1450. www.ecfr.gov.
-
SEFA. Laboratory Fume Hoods Recommended Practices.
Scientific Equipment and Furniture Association, Garden City, NY.
Other regulations and guidelines may apply to laboratory design. All applicable
institutional, local, state, and federal requirements should be identified before design
begins.
Laboratory operations potentially involve some hazard; nearly all laboratories contain some type of hazardous
materials. Before the laboratory is designed, the owner’s designated safety officers
should perform a comprehensive hazard assessment. These safety officers include, but are not
limited to, the chemical hygiene officer, radiation safety officer, biological safety officer,
and fire and loss prevention officials. The hazard assessment should be incorporated into the
chemical hygiene plan, radiation safety plan, and biological safety protocols.
Hazard study methods such as hazard and operability analysis (HAZOP) can be used to evaluate
design concepts and certify that the HVAC design conforms to the applicable safety plans. Nature
and quantity of the contaminants, types of operations, and degree of hazard dictate the types of
containment and local exhaust devices. For functional convenience, operations posing less hazard
potential are conducted in devices that use directional airflow for personnel protection (e.g.,
laboratory fume hoods and biological safety cabinets). However, these devices do not provide
absolute containment. Operations having a significant hazard potential are conducted in devices
that provide greater protection but are more restrictive (e.g., sealed glove boxes).
The risk of exposure to unsafe concentrations of airborne chemicals in laboratories can range
from negligible to extreme, depending on the activities conducted in the laboratories, types of
hazardous chemicals, quantities of materials, characteristics of generation, duration of
exposure, and the protection afforded by the laboratory airflow and airborne contaminant control
systems. For this reason, a risk assessment must be conducted based on the best available
information about the chemical work to be conducted in the laboratory. The ability to mitigate
the risk to people, property, and the environment depends on providing an adequate level of
protection through proper design, operation, and utilization of the laboratory; the exposure control devices (ECDs), such as fume hoods;
and the laboratory ventilation systems. Collectively, the ECDs, the exhaust systems, the air
supply systems, and the elements of the laboratory that may affect airflow and control of
airborne contaminants are referred to as the laboratory airflow
control system (LACS). The purpose of the LACS is twofold: it must (1)
help prevent overexposure to airborne chemical hazards generated during laboratory scale
activities and (2) satisfy the temperature and humidity conditioning requirements of the
occupants and the processes they conduct in the laboratory workspace. The protective capability
afforded by a LACS must be commensurate with the level of risk associated with the airborne
chemical hazards that may be generated.
The ASHRAE (2018) Classification of Laboratory Ventilation Design
Levels guide divides design attributes and operating specifications for a LACS
divided into five laboratory ventilation design levels (LVDLs) ranging from LVDL-0 to LVDL-4.
The attributes and specifications for each LVDL are intended to provide increasing levels of
protection and control of air-borne chemical hazards to minimize the risk of overexposure.
Greater detail can be found in the guide.
The design team should visit similar laboratories to assess successful design approaches and safe
operating practices. Each laboratory is somewhat different. Design must be evaluated using
appropriate, current standards and practices as well, rather than simply duplicating existing
(and possibly outmoded) facilities.
The following ventilation system design parameters must be established for a laboratory space:
-
Temperature and humidity, both indoor and outdoor
-
Air quality, from both process and safety perspectives, including the need for air
filtration and special treatment (e.g., charcoal, HEPA, or other filtration of
supply or exhaust air)
-
Equipment and process heat gains, both sensible and latent
-
Minimum allowable air change rates
-
Equipment and process exhaust quantities
-
Exhaust and air intake locations
-
Style, capture velocities, and usage factors of the exhaust device
-
Need for standby equipment and emergency power
-
Alarm requirements.
-
Potential changes in the size and number of laboratory hoods
-
Anticipated increases in internal heat loads
-
Isolation and room pressurization requirements
-
Biological containment provisions
-
Decontamination provisions
It is important to (1) review design parameters with the safety officers and scientific staff,
(2) determine limits that should not be exceeded, and (3) establish the desirable operating
conditions. For areas requiring variable temperature or humidity, these parameters must be
carefully reviewed with the users to establish a clear understanding of expected operating
conditions and system performance.
Because laboratory HVAC systems often incorporate 100% exhaust resulting in high percentages of
outdoor air systems, the selection of design parameters has a substantial effect on capacity,
first cost, and operating costs. The selection of proper and prudent design conditions is very
important.
Internal Thermal Considerations
In addition to the heat gain from people and lighting, laboratories frequently have
significant sensible and latent loads from equipment and processes. Often, data for
equipment used in laboratories are unavailable or the equipment has been custom built.
Information for some common laboratory equipment is listed in the appendix of the ASHRAE Laboratory Design Guide (ASHRAE 2002). Data on heat release
from animals that may be housed in the space can be found in Table 2 of this
chapter and in Alereza and Breen (1984).
Careful review of the equipment to be used, a detailed understanding of how the laboratory
will be used, and prudent judgment are required to obtain good estimates of the heat gains
in a laboratory. The convective portion of heat released from equipment located within
exhaust devices can be discounted. Heat from equipment that is directly vented or heat from
water-cooled equipment should not be considered part of the heat released to the room. Any
unconditioned makeup air that is not directly captured by an exhaust device must be included
in the load calculation for the room. In many cases, additional equipment will be obtained
by the time a laboratory facility has been designed and constructed. The design should allow
for this additional equipment.
Internal load as measured in watts per square foot is the average continuous
internal thermal load discharged into the space. It is not a tabulation of the connected
electrical load because it is rare for all equipment to operate simultaneously, and most
devices operate with a duty cycle that keeps the average electrical draw below the nameplate
information. When tabulating the internal sensible heat load in a laboratory, the duty cycle
of the equipment should be obtained from the manufacturer. This information, combined with
the nameplate data for the item, may provide a more accurate assessment of the average
thermal load.
The HVAC system engineer should evaluate equipment nameplate ratings, applicable use and
usage factors, and overall diversity. Review use, usage factors, and diversity with lab
occupants. Much laboratory equipment includes computers, automation, sample changing, or
robotics; this can result in high levels of use even during unoccupied periods. The HVAC
engineer must evaluate internal heat loads under all anticipated laboratory operating modes.
Because of highly variable equipment heat gain, individual laboratories should have
dedicated temperature controls. See Chapter 18 in the 2021 ASHRAE
Handbook—Fundamentals for more information on load calculation.
Two cases encountered frequently are (1) building programs based on generic laboratory
modules and (2) laboratory spaces that are to be highly flexible and adaptive. Both
situations require the design team to establish heat gain on an area basis. The values for
area-based heat gain vary substantially for different types of laboratories. Heat gains of
5 to 25 W/ft2 or more are common for laboratories with high
concentrations of equipment.
Architectural Considerations
Integrating utility systems into the architectural planning, design, and detailing is
essential to providing successful research facilities. The architect and the HVAC system
engineer must seek an early understanding of each other’s requirements and develop
integrated solutions. HVAC systems may fail to perform properly if the architectural
requirements are not addressed correctly. Quality assurance of the installation is just as
important as proper specifications. The following play key roles in the design of research
facilities:
Modular Planning. Most laboratory programming and
planning is based on developing a module that becomes the base building block for the
building layout. Laboratory planning modules are frequently 10 to 12 ft wide
and 20 to 30 ft deep. The laboratory modules may be developed as single work
areas or combined to form multiple-station work areas. Utility systems should be arranged to
reflect the architectural planning module, with services provided for each module, or pair
of modules, as appropriate.
Development of Laboratory Units or Control Areas.
National Fire Protection Association (NFPA) Standard 45 requires
that laboratory units be designated. Similarly, the International
Building Code® (ICC 2015) requires the development of control
areas. Laboratory units or control areas should be developed, and the appropriate hazard
levels should be determined early in the design process. The HVAC designer should review the
requirements for maintaining separations between laboratories and note requirements for
exhaust ductwork to serve only a single laboratory unit or control area.
Additionally, NFPA Standard 45 requires that no fire dampers be
installed in laboratory exhaust ductwork. Building codes offer no leeway on maintaining
required floor-to-floor fire separations. Review these criteria and the proposed solutions
early in the design process with the appropriate building code officials. The combination of
the two requirements commonly necessitates the construction of dedicated fire-rated shafts
from each occupied floor to the penthouse or building roof.
Provisions for Adaptability and Flexibility.
Research objectives frequently require changes in laboratory operations and programs. Thus,
laboratories must be flexible and adaptable, able to accommodate these changes without
significant modifications to the infrastructure. For example, the utility system design can
be flexible enough to supply ample cooling to support the addition of heat-producing
equipment without requiring modifications to the HVAC system. Adaptable designs should allow
programmatic research changes that require modifications to the laboratory’s
infrastructure within the limits of the individual laboratory area and/or interstitial and
utility corridors. For example, an adaptable design would allow addition of a fume hood
without requiring work outside that laboratory space. Further, the HVAC designer should
consider the consequences of future programmatic changes on the sizing of main ductwork and
central system components. The degree of flexibility and adaptability for which the
laboratory HVAC system is designed should be determined from discussion with the
researchers, laboratory programmer, and laboratory planner. The HVAC designer should have a
clear understanding of these requirements and their financial impact.
Early Understanding of Utility Space Requirements.
The amount and location of utility space are significantly more important in research
facility design than in that of most other buildings. The available ceiling space and the
frequency of vertical distribution shafts are interdependent and can significantly affect
architectural planning. The HVAC designer must establish these parameters early, and the
design must reflect these constraints. The designer should review alternative utility
distribution schemes, weighing advantages and disadvantages.
High-Quality Envelope Integrity. Laboratories that
have stringent requirements for control of temperature, humidity, relative static pressure,
and background particle count generally require architectural features to allow the HVAC
systems to perform properly. The building envelope may need to be designed to handle
relatively high levels of humidification and slightly negative building pressure without
moisture condensation in the winter or excessive infiltration. Some of the architectural
features that the HVAC designer should evaluate include
-
Vapor and air barriers: position, location, and kind
-
Insulation: location, thermal resistance, and kind
-
Window frames and glazing
-
Caulking
-
Internal partitions: their integrity in relation to air pressure, vapor barriers,
and insulation value
-
Finishes: vapor permeability and potential to release particles into the space
-
Doors
-
Air locks
Air Intakes and Exhaust Locations. Mechanical
equipment rooms and their outdoor air intakes and exhaust stacks must be located to avoid
intake of fumes into the building. As with other buildings, air intake locations must be
chosen to minimize fumes from loading docks, cooling tower discharge, vehicular traffic,
adjacent structures and processes, etc.
2. LABORATORY EXHAUST AND
CONTAINMENT DEVICES
The Scientific Equipment and Furniture Association (SEFA 2010) defines a laboratory fume hood as
a “safety device specifically designed to carry undesirable effluents
(generated . . . during a laboratory procedure) away from laboratory
personnel and out of the building, when connected to a properly designed laboratory ventilation
system.” The hood can be mounted on a bench, a pedestal, or the floor. Materials should
mainly be flame resistant. The face opening has a sash and an optional additional protective
shield, and usually has an airfoil to reduce reverse airflow on the lower surface. The hood
should have a baffle, and usually a bypass system to control airflow patterns in the hood and
distribute air evenly at the opening. For variable-air-volume (VAV) systems, the bypass system
may be partially blocked. Figure
1 shows the basic elements of a general-purpose benchtop fume hood.
Fume hoods may be equipped with a variety of accessories, including internal lights, service
outlets, sinks, air bypass openings, airfoil entry devices, flow alarms, special linings,
ventilated base storage units, and exhaust filters. Under-counter cabinets for storage of
flammable materials require special attention to ensure safe installation. NFPA Standard 30 does not recommend venting these cabinets; however,
ventilation is often required to avoid accumulation of toxic or hazardous vapors. Ventilation of
these cabinets by a separately ducted supply and exhaust that will maintain the temperature rise
of the cabinet interior within the limits defined by NFPA Standard
30 should be considered.
The following are the primary types of fume hoods and their applications:
-
Constant Volume (approximately
constant-volume airflow with variable face velocity). Hood that meets basic SEFA
definition. Sash may be vertical, horizontal, or combination.
Application: Moderate to highly hazardous processes;
varying procedures.
-
Variable Volume (constant face
velocity). Hood has an opening or bypass designed to provide a prescribed
minimum air intake when sash is closed, and an exhaust system designed to vary
airflow in accordance with sash opening. Sash may be vertical, horizontal, or a
combination of both.
Application: Moderate to highly hazardous processes;
varying procedures.
-
Auxiliary Air (approximately
constant-volume airflow). A plenum above the face receives air from a secondary
air supply that provides partially conditioned or unconditioned outdoor air.
Note: Many organizations restrict the use of this
type of hood.
-
High-Performance (approximately
constant-volume airflow with variable face velocity or variable volume).
High-performance hoods are designed to provide equivalent or better containment
than a conventional hood at 30 to 40% less flow and average face velocity.
Application: Moderate to highly hazardous processes;
varying procedures.
-
Filtered, Recirculating (approximately
constant-volume airflow). Particulate filtration combined with chemical
adsorption to remove contaminants.
Application: Moderate process with predictable
procedures.
-
Radioisotope. Hood with special
integral work surface, linings impermeable to radioactive materials, and
structure strong enough to support high-density shielding materials. The
interior must be constructed to prevent radioactive material buildup and allow
complete cleaning. Ductwork should have flanged gasketed joints with
quick-disconnect fasteners that can be readily dismantled for decontamination.
High-efficiency particulate air (HEPA) and/or charcoal filters may be needed in
exhaust duct.
Application: Laboratories using radioactive isotopes.
-
Perchloric Acid. Hood with special
integral work surfaces, coved corners, and nonorganic lining materials.
Perchloric acid is an extremely active oxidizing agent. Its vapors can form
unstable deposits in the ductwork that present a potential explosion hazard. To
alleviate this hazard, the exhaust system must be equipped with an internal
water washdown and drainage system, and the ductwork must be constructed of
smooth, impervious, cleanable materials that are resistant to acid attack. The
internal washdown system must completely flush the ductwork, exhaust fan,
discharge stack, and fume hood inner surfaces. Ductwork should be kept as short
as possible with minimum elbows. Perchloric acid exhaust systems with longer
duct runs may need a zoned washdown system to avoid water flow rates in excess
of the capacity to drain water from the hood. Because perchloric acid is an
extremely active oxidizing agent, organic materials should not be used in the
exhaust system in places such as joints and gaskets. Ducts should be constructed
of a stainless steel material, with a chromium and nickel content not less than
that of 316L stainless steel, or of a suitable nonmetallic material. Joints
should be welded and ground smooth. A perchloric acid exhaust system should only
be used for work involving perchloric acid.
Application: Process and research laboratories using
perchloric acid. Mandatory use because of explosion hazard.
-
California. Special hood with sash
openings on multiple sides (usually horizontal).
Application: For enclosing large and complex research
apparatus that require access from two or more sides.
-
Floor-Mounted Hood (Walk-In). Hood
with sash openings to the floor. Sash can be either horizontal or vertical.
Application: For enclosing large or complex research
apparatus. Not designed for personnel to enter while operations are in progress.
-
Distillation. Fume hood with extra
depth and 1/3- to 1/2-height benches.
Application: For enclosing tall distillation
apparatus.
-
Process (approximately constant-volume
airflow with approximately constant face velocity). Standard hood with a fixed
opening and without a sash. Not a fume hood. Considered a ventilated enclosure.
Application: Low-hazard processes; known procedures.
-
Canopy. Open hood with an overhead
capture structure.
Application: Not a fume hood. Useful for heat or
water vapor removal from some work areas. Not to be substituted for a fume hood.
Not recommended when workers must bend over the source of heat or water vapor.
Fume Hood Sash Configurations
The work opening has operable glass sash(es) for observation and shielding. A sash may be
vertically operable, horizontally operable, or a combination of both. A vertically operable
sash can incorporate single or multiple vertical panels. A horizontally operable sash
incorporates multiple panels that slide in multiple tracks, allowing the open area to be
positioned across the face of the hood. The combination of a horizontally operable sash
mounted within a single vertically operable sash section allows the entire hood face to be
opened for setup. The opening area can then be limited by closing the vertical panel, with
only the horizontally sliding sash sections used during experimentation. Both the multiple
vertical sash section and combination sash arrangement allow the use of larger fume hoods
with limited opening areas, resulting in reduced exhaust airflow requirements. Fume hoods
with vertically rising sash sections should include provisions around the sash to prevent
the bypass of ceiling plenum air into the fume hood.
Containment of hazards in a fume hood is based on the principle that a flow of air entering
at the face of the fume hood, passing through the enclosure, and exiting at the exhaust port
prevents the escape of airborne contaminants from the hood into the room.
The following variables affect the performance of the fume hood:
-
Face velocity
-
Size of face opening
-
Sash position
-
Shape and configuration of entrance
-
Shape of any intermediate posts
-
Inside dimensions and location of work area relative to face area
-
Location of service fittings inside the fume hood
-
Heat generated in the hood
-
Size and number of exhaust ports
-
Back baffle and exhaust plenum arrangement
-
Bypass arrangement, if applicable.
-
Auxiliary air supply, if applicable
-
Arrangement and type of replacement supply air outlets
-
Air velocities near the hood
-
Distance from openings to spaces outside the laboratory
-
Movements of the researcher within the hood opening
-
Location, size, and type of research apparatus placed in the hood
-
Distance from the apparatus to the researcher’s breathing zone
Air Currents. Air currents external to the fume
hood can jeopardize the hood’s effectiveness and expose the researcher to materials
used in the hood. Detrimental air currents can be produced by
-
Air supply distribution patterns in the laboratory
-
Movements of the researcher
-
People walking past the fume hood
-
Thermal convection
-
Opening (or open) doors and windows
Caplan and Knutson (1977, 1978) conducted tests to determine the interactions between room
air motion and fume hood capture velocities with respect to the spillage of contaminants
into the room. Their tests indicated that the effect of room air currents is significant and
of the same order of magnitude as the effect of the hood face velocity. Consequently,
improper design and/or installation of the replacement air supply can lower performance of
the fume hood.
Disturbance velocities at the face of the hood should be no more than one-half and preferably
one-third the face velocity of the hood. This is an especially critical factor in designs
that use low face velocities. For example, a fume hood with a face velocity of 100
fpm could tolerate a maximum disturbance velocity of 50 fpm. If the
design face velocity were 60 fpm, the maximum disturbance velocity would be
30 fpm.
To the extent possible, the fume hood should be located so that traffic flow past the hood is
minimal. Also, the fume hood should be placed to avoid any air currents generated from the
opening of windows and doors. Air currents from open doors and windows can be significantly
higher than acceptable maximum disturbance velocities. To ensure optimum placement of the
fume hoods, the HVAC system designer must take an active role early in the design process.
Use of Auxiliary Air Fume Hoods. ASSE Standard Z9.5 discourages the use of auxiliary air fume hoods.
These hoods incorporate an air supply at the fume hood to reduce the amount of room air
exhausted. The following difficulties and installation criteria are associated with
auxiliary air fume hoods:
-
The auxiliary air supply must be introduced outside the fume hood to maintain
appropriate velocities past the researcher.
-
The flow pattern of the auxiliary air must not degrade the containment
performance of the fume hood.
-
The volume of auxiliary air must not be enough to degrade the fume hood’s
containment performance.
-
Auxiliary air must be conditioned to avoid blowing cold air on the researcher;
often the air must be cooled to maintain the required temperature and humidity
within the hood. Auxiliary air can introduce additional heating and cooling
loads in the laboratory.
-
Only vertical sash should be used in the hood.
-
Controls for the exhaust, auxiliary, and supply airstreams must be coordinated.
Fume Hood Performance Criteria. ASHRAE Standard 110 describes a quantitative method of determining the
containment performance of a fume hood. This method requires the use of a tracer gas and
instruments to measure the amount of tracer gas that enters the breathing zone of a
mannequin; this simulates the containment capability of the fume hood as a researcher
conducts operations in the hood. The following tests are commonly used to judge the
performance of the fume hood: (1) face velocity test, (2) flow visualization test, (3)
tracer gas test, and (4) sash movement test. These tests should be performed under the
following conditions:
-
Usual amount of research equipment in hood; room air balance fixed
-
Doors and windows in normal positions
-
Fume hood sash set in varying positions to simulate both static and dynamic
performance
All fume hoods should be tested annually, at minimum, to verify their performance. Refer to
ASHRAE Standard 110 for procedures.
2.2 BIOLOGICAL SAFETY CABINETS
A biological safety cabinet protects the researcher and, in some configurations, the research
materials as well. Biological safety cabinets are also referred to as ventilated safety
cabinets, laminar flow cabinets, and glove boxes. Biological safety cabinets are categorized
into six groups (four of which are shown in Figure 2):
The researcher must make several key decisions before selecting a biological safety cabinet
(Eagleston 1984). An important difference in biological safety cabinets is their ability to
handle chemical vapors properly (Stuart et al. 1983). Of special concern to the HVAC engineer
are the proper placement of the biological safety cabinet in the laboratory and the room’s
air distribution. Rake (1978) concluded the following:
A general rule of thumb should be that, if the cross draft or other disruptive room
airflow exceeds the velocity of the air curtain at the unit’s face, then problems
do exist. Unfortunately, in most laboratories such disruptive room airflows are present
to various extents. Drafts from open windows and doors are the most hazardous sources
because they can be far in excess of 200 fpm and accompanied by substantial
turbulence. Heating and air-conditioning vents perhaps pose the greatest threat to the
safety cabinet because they are much less obvious and therefore seldom
considered. . . . It is imperative then that all room airflow
sources and patterns be considered before laboratory installation of a safety cabinet.
Class II biological safety cabinets should only be placed in the laboratory in compliance with
NSF International Standard 49, Class II (Laminar Flow) Biohazard
Cabinetry. Assistance in procuring, testing, and evaluating performance parameters of Class II
biological safety cabinets is available from NSF as part of the standard. The cabinets should be
located away from drafts, active walkways, and doors. The air distribution system should be
designed to avoid air patterns that impinge on the cabinet.
The different biological safety cabinets have varying static pressure resistance requirements.
Generally, Class II Type A1 cabinets have pressure drops ranging between 0.005 and 0.1 in.
of water. Class II Type B1 cabinets have pressure drops in the range of 0.6 to
1.2 in. of water, and Class II Type B2 cabinets have pressure drops ranging from
1.5 to 2.3 in. of water. The manufacturer must be consulted to verify specific
requirements.
Pressure requirements also vary based on filter loading and the intermittent operation of
individual biological safety cabinets. Exhaust systems for biological safety cabinets must be
designed with these considerations in mind. Take care when manifolding biological safety cabinet
exhausts to ensure that the varying pressure requirements are met.
The manufacturer of the biological safety cabinet may be able to supply the transition to the
duct system. The transition should include an access port for testing and balancing and an
airtight damper for decontamination. As with any containment ductwork, high-integrity duct
fabrication and joining systems are necessary.
Biological safety cabinets may require periodic decontamination before service and filter
replacement. During decontamination, the cabinet must be isolated or sealed from the laboratory
and the exhaust system. The responsible safety officer should be consulted to determine the need
for, and placement of, isolation dampers to facilitate decontamination operations. If provisions
for decontamination are necessary, the ventilation system design should maintain laboratory
airflow and pressure during the decontamination procedure.
The Class I cabinet is a partial containment device designed for research operations with
low- and moderate-risk etiologic agents. It does not provide protection for materials used
in the cabinet. Room air flows through a fixed opening and prevents aerosols that may be
generated in the cabinet enclosure from escaping into the room. Depending on cabinet usage,
air exhausted through the cabinet may be HEPA filtered before being discharged into the
exhaust system. The fixed opening through which the researcher works is usually
8 in. high. To provide adequate personnel protection, air velocity through
the fixed opening is usually at least 75 fpm.
If approved by the appropriate safety officer, the Class I cabinet can be modified to safely
contain chemical carcinogens by adding appropriate exhaust air treatment and increasing the
velocity through the opening to 100 fpm. Large pieces of research equipment can
be placed in the cabinet if adequate shielding is provided.
The Class I cabinet is not appropriate for containing systems that are vulnerable to airborne
contamination because the air flowing into the cabinet is untreated. Also, the Class I
cabinet is not recommended for use with highly infectious agents because an interruption of
the inward airflow may allow aerosolized particles to escape.
Class II cabinets provide protection to personnel, product, and the environment. The cabinets
feature an open front with inward airflow and HEPA-filtered recirculated and exhaust air.
Microbiological containment, product protection, and cross-contamination performance is
established for certain cabinets by NSF International’s Standard 49. Measurement techniques in NSF Standard 49 vary from those often used by building system testing
and balancing agencies; therefore, it is important to coordinate activities of the
biological safety cabinet (BSC) certification agency and the testing and balancing agency.
The Class II Type A1 cabinet has a fixed opening with a minimum inward airflow velocity of
75 fpm. The average downward velocity is established by the manufacturer and is
typically 50 to 80 fpm. The Class II Type A1 cabinet is suitable for use with
agents meeting Biosafety Level 2 criteria (DHHS 1999), and, if properly certified, can meet
Biosafety Level 3. However, because approximately 70% of the airflow is recirculated, the
cabinet is not suitable for use with flammable, toxic, or radioactive agents.
The Class II Type A2 cabinet maintains an inward airflow velocity of 100 fpm and
is similar in performance to the Class II Type A1.
The Class II Type B1 cabinet has a vertical sliding sash and maintains an inward airflow of
100 fpm at a sash opening of 8 in. The average downward velocity
of the internal airflow is typically in the range of 50 to 80 fpm. The Class II
Type B1 cabinet is suitable for use with agents meeting Biosafety Level 3. Approximately 60%
of the internal airflow is exhausted through HEPA filters; this allows the use of biological
agents treated with limited quantities of toxic chemicals and trace amounts of
radionuclides, provided the work is performed in the direct exhaust area of the cabinet.
The Class II Type B2 cabinet maintains an inward airflow velocity of 100 fpm
through the work opening. The cabinet is 100% exhausted through HEPA filters to the
outdoors; all downward-velocity air is drawn from the laboratory or other supply source and
is HEPA filtered before being introduced into the workspace. The Class II Type B2 cabinet
may be used for the same level of work as the Class II Type B1, and is used when the primary
consideration is protection of the material in the hood. In addition, the design allows use
of small quantities of toxic chemicals and radionuclides in microbiological studies.
In Class II Type A2 cabinets, exhaust air delivered to the outlet of the cabinet by internal
blowers must be handled by the laboratory exhaust system. This arrangement requires a
delicate balance between the cabinet and the laboratory’s exhaust system, and it may
incorporate a thimble connection between the cabinet and the laboratory exhaust ductwork.
Thimble (or canopy) connections incorporate an air gap between the biological safety cabinet
and the exhaust duct. The purpose of the air gap is to buffer the effect of any exhaust
system fluctuations on the biological safety cabinet airflow. The exhaust system must pull
more air than is exhausted by the biological safety cabinet to make airflow in through the
gap. The designer should confirm the amount of air to be drawn through the air gap. A
minimum flow is required to provide the specified level of containment, and a maximum flow
cannot be exceeded without causing an imbalance through aspiration. In the event of an
exhaust system failure, the air gap allows the cabinet to maintain safe intake velocity by
exhausting HEPA-filtered air through the air gap.
Class II Type B1 and Type B2 cabinets rely on the building exhaust system to pull the air
from the cabinet’s workspace and through the exhaust HEPA filters. The pressure
resistance that must be overcome by the building exhaust system can be obtained from the
cabinet manufacturer. In a fire or smoke condition, exhaust flow should continue through the
cabinet, as for a fume hood; therefore, fire and smoke dampers should not be installed in
the exhaust ductwork. The cabinet should be provided with a gastight damper to isolate it
from the downstream ductwork to allow for decontamination. Because containment in this type
of cabinet depends on the building’s exhaust system, the exhaust fan(s) should have
redundant back-ups and the proper controls to maintain required flow rates.
The Class III cabinet is a gastight, negative-pressure containment system that physically
separates the agent from the worker. These cabinets provide the highest degree of personnel
protection. Work is performed through arm-length rubber gloves attached to a sealed front
panel. Room air is drawn into the cabinet through HEPA filters. The American Glovebox
Society (AGS 2007) indicates that Class III cabinets should be maintained at 0.5 in.
of water below ambient pressure. Exhaust flow rate should provide a minimum of
100 fpm inward containment velocity through a glove port opening in the event
of a glove being inadvertently removed. HEPA filtration or incineration before discharge to
the atmosphere removes or destroys particulate material entrained in the exhaust air. A
Class III system may be designed to enclose and isolate incubators, refrigerators, freezers,
centrifuges, and other research equipment. Double-door autoclaves, liquid disinfectant dunk
tanks, and pass boxes are used to transfer materials into and out of the cabinet.
Class III systems can contain highly infectious materials and radioactive contaminants.
Although there are operational inconveniences with these cabinets, they are the equipment of
choice when a high degree of personnel protection is required. Note that explosions have
occurred in Class III cabinets used for research involving volatile substances.
2.3 MISCELLANEOUS EXHAUST DEVICES
Snorkels are used in laboratories to remove heat or
nontoxic particles that may be generated from benchtop research equipment. Snorkels usually have
funnel-shaped inlet cones connected to 3 to 6 in. diameter flexible or
semi-flexible ductwork extending from the ceiling to above the benchtop level.
Benchtop slots are used to remove nontoxic particles
or fumes that may be generated by benchtop equipment.
Often, hoods are installed over weigh stations to contain and minimize disturbances from room air
currents.
2.4 LAMINAR FLOW CLEAN BENCHES
Laminar flow clean benches are available in two configurations: horizontal (crossflow) and
vertical (downflow). Both configurations filter the supply air and usually discharge the air out
the front opening into the room. Clean benches protect the experiment or product but do not
protect the researcher; therefore, they should not be used with any potentially hazardous or
allergenic substances. Clean benches are not recommended for any work involving hazardous
biological, chemical, or radionuclide materials.
2.5 COMPRESSED GAS STORAGE AND
VENTILATION
Most laboratory buildings require storage closets for cylinders of compressed gases, which
may be inert, flammable, toxic, corrosive, or poisonous. The requirements for storage and
ventilation are covered in building codes and NFPA standards and codes. Water sprinklers are
usually required, but other types of fire suppression may be needed based on the gases
stored. Explosion containment requires a separate structural study, and closets generally
require an outer wall for venting. One design used by a large chemical manufacturer to house
gases with explosion potential specifies a completely welded 0.25 in. steel
inner liner for the closet, heavy-duty door latches designed to withstand the force of an
internal explosion, and venting out the top of the closet.
Closet temperature should not exceed 125°F per NFPA Standard 55. Ventilation for cylinder storage is established in
NFPA Standard 55 at a minimum of 1
cfm/ft2. Ventilation rates can be calculated by determining both the
amount of gas that could be released by complete failure of the cylinder outlet piping
connection and the time the release would take, and then finding the dilution airflow
required to reduce any hazard below the maximum allowable limit.
Ventilation air is usually exhausted from the closet; makeup air comes from the surrounding
space through openings in and around the door or through a transfer duct. That makeup air
must be considered for the building air balance. Ventilation for a closet containing
materials with explosion potential must be carefully designed, with safety considerations
taken into account. See NFPA Standard 68 for information on
explosion venting.
Cylinder closet exhausts should be connected through a separate duct system to a dedicated
exhaust fan or to a manifold system in which constant volume can be maintained under any
possible manifold condition. A standby source of emergency power should be considered for
the exhaust system fan(s).
Compressed gases that present a physical or health hazard are often placed in premanufactured
gas cylinder cabinets. Gas cylinder cabinets are available for single-, dual-, or
triple-cylinder configurations and are commonly equipped with valve manifolds, fire
sprinklers, exhaust connections, access openings, and operational and safety controls. The
engineer must fully understand safety, material, and purity requirements associated with
specific compressed gases when designing and selecting cylinder cabinets and the components
that make up the compressed gas handling system.
Exhaust from the gas cylinder cabinets is provided at a high rate. Air is drawn into the gas
cylinder cabinet from the surrounding space through a filtered opening, usually on the lower
front of the cylinder cabinet. Depending on the specific gas stored in the cabinet, the
exhaust system may require emission control equipment and a source of emergency power.
3. LABORATORY VENTILATION
The total airflow rate for a laboratory is dictated by
one of the following:
-
Total amount of exhaust from containment and exhaust devices
-
Cooling required to offset internal heat gains
-
Minimum ventilation rate requirements
-
Airflow required to maintain pressure relationships
Fume hood exhaust requirements (including evaluation of alternate sash configurations as described in
the section on Fume Hoods) must be determined in consultation with the safety officers. The HVAC
engineer must determine the expected heat gains from the laboratory equipment after consulting with
the laboratory staff (see the section on Internal Thermal Considerations).
The ASHRAE (2018) Classification of Laboratory Ventilation Design Levels
Guide provides direction on the minimum ventilation rates to provide a safe and healthy
environment under normal and expected operating conditions. The dilution ventilation provided by
this airflow is no substitute for the containment performance of a laboratory fume hood or other
primary containment device, regardless of the room ventilation rate. The appropriate ventilation
rate for clearing a room of fugitive emissions or spills varies significantly based on the amount of
release, the chemical’s evaporation rate and hazard level, and ventilation system
effectiveness.
Fixed minimum airflow rates of 4 to 12 air changes per hour (ach) when the space is occupied have
been used in the past. Recent university research (Klein et al. 2009) has shown a significant
increase in dilution and clearing performance by increasing the air change rate from 6 to 8 ach with
diminishing returns above 12 ach. Similarly, CFD research (Schuyler 2009) found that increasing the
lab’s dilution ventilation rate from 4 to 8 ach reduced the background contaminant level by
greater than a factor of 10. This indicates that minimum ventilation rates at the lower end of the 4
to 12 ach range may not be appropriate for all laboratories. Minimum ventilation rates should
be established on a room-by-room basis, considering the hazard level of materials expected to be
used in the room and the operation and procedures to be performed. As the operation, materials, and
hazard level of a room change, evaluate the prospect of increasing or decreasing the minimum
ventilation rate.
Active sensing of air quality in individual laboratories (Sharp 2010) is an alternative approach for
dealing with the variability of appropriate ventilation rates, particularly when energy efficiency
is important or when hazard level is less established. With this approach, the minimum airflow rate
is varied based on sensing the laboratory’s actual air quality level or air cleanliness.
Sensors used to determine air quality should be evaluated for their ability to detect chemicals
being used in the space. When air contaminants are sensed in the laboratory above a given threshold,
the minimum air change rate is increased proportionally to an appropriate level to purge the room.
When the air is clean and contaminants are below the threshold, lower minimum airflow rates may be
appropriate. Extensive studies of lab room environmental conditions (Sharp 2010) have shown that the
air in labs is typically clean over 98% of the time.
The maximum airflow rate for the laboratory should be reviewed to ensure that supply air delivery
methods are appropriate and that supply airflows do not impede performance of the exhaust devices.
Laminar-flow (nonaspirating) supply air outlets can be used to create predictable air flow patterns
in the laboratory, generating directional flows toward exhaust and containment device locations.
Laboratory ventilation systems can be arranged for either constant-volume or variable-volume
airflow. The specific type should be selected with the research staff, safety officers, and
maintenance personnel. Special attention should be given to unique areas such as glass washing
areas, hot and cold environmental rooms and labs, fermentation rooms, and cage washing rooms.
Emergency power systems to operate the laboratory ventilation equipment should be considered based
on hazard assessment or other specific requirements. Ensure that an adequate amount of makeup air is
available whenever exhaust fans are operated on emergency power.
When considering an overall facility, all laboratory personnel, scientific equipment, and exhaust
devices are seldom, if ever, present or in use simultaneously. Accordingly, the system designer
should consider the impact of nonsimultaneous use on the sizing and selection of building
systems. Many variables influence diversity factors, including
-
Type and size of facility
-
Total number of fume hoods
-
Number of fume hoods per researcher
-
Scientific equipment use diversity
-
Type of fume hood controls
-
Fume hood sash configuration and minimum airflow required
-
Type of laboratory ventilation systems
-
Number of devices that must operate continuously due to chemical storage requirements
or contamination prevention
-
Number of current and projected research programs
Apply diversity carefully when sizing equipment. For example, teaching laboratories may have all
hoods in full use when class is in session; fans and ducts should be sized accordingly.
If the sizing assumptions are incorrect, design airflow and containment performance may not be
maintained under all operating conditions. It is usually expensive and disruptive to add
capacity to an operating laboratory’s supply or exhaust system. Detailed discussions with
research staff are required to ascertain maximum diversity as well as potential future
requirements.
Noise level in the laboratory should be considered at the beginning of the design so that the
sound levels do not interfere with scientific work. Sound generated by the building HVAC
equipment should also be evaluated to ensure that excessive levels do not escape to the
outdoors. Remedial correction of excessive sound levels can be difficult and expensive. See Chapter 48 for more
information.
Supply air systems for laboratories provide the following:
-
Thermal comfort for occupants
-
Minimum and maximum airflow rates
-
Replacement for air exhausted through fume hoods, biological safety cabinets, or
other exhaust devices
-
Space pressurization control
-
Environmental control to meet process or experimental criteria
The design parameters must be well defined for selection, sizing, and layout of the supply air
system. Installation and setup should be verified as part of the commissioning process. Design
parameters are covered in the section on Design Parameters, and commissioning is covered in the
section on Commissioning. Laboratories in which chemicals and compressed gases are used
generally require nonrecirculating air supply systems. The selection of 100% exhaust air systems
versus return air systems should be made as part of the hazard assessment process, which is
discussed in the section on Hazard Assessment. A 100% outdoor air system must have a very wide
range of heating and cooling capacity, which requires special design and control.
Filtration for the air supply depends on the
requirements of the laboratory. Conventional chemistry and physics laboratories commonly use
minimum efficiency reporting value (MERV) 13 filters (see ASHRAE Standard 52.2-2012 for more on MERVs). Biological and biomedical
laboratories usually require MERV 14 or 15 filtration. HEPA filters should be provided for
spaces where research materials or animals are particularly susceptible to contamination
from external sources. HEPA filtration of the supply air is necessary for such applications
as environmental studies, studies involving specific pathogen-free research animals or nude
mice, dust-sensitive work, and electronic assemblies. In many instances, biological safety
cabinets or laminar flow clean benches (which are HEPA filtered) may be used rather than
HEPA filtration for the entire laboratory.
Air supplied to a laboratory must be distributed to keep temperature
gradients and air currents to a minimum. Air outlets (preferably nonaspirating diffusers)
must not discharge into the face of a fume hood, a biological safety cabinet, or an exhaust
device. Acceptable room air velocities are covered in the sections on Fume Hoods and
Biological Safety Cabinets. Special techniques and diffusers are often needed to introduce
the large air quantities required for a laboratory without creating disturbances at exhaust
devices or on work surfaces.
Laboratory exhaust systems remove air from containment devices and from the laboratory itself.
The exhaust system must be controlled and coordinated with the supply air system to maintain
correct pressurization. Additional information on the control of exhaust systems is included in
the section on Control. Design parameters must be well defined for selection, sizing, and layout
of the exhaust air system. Installation and setup should be verified as part of the
commissioning process. See the sections on Design Parameters and Commissioning. Laboratory
exhaust systems should be designed for high reliability and ease of maintenance. This can be
achieved by providing multiple exhaust fans and by sectionalizing equipment so that maintenance
work may be performed on an individual exhaust fan while the system is operating. Another option
is to use predictive maintenance procedures to detect problems prior to failure and to allow for
scheduled shutdowns for maintenance. To the extent possible, components of exhaust systems
should allow maintenance without exposing maintenance personnel to the exhaust airstream. Access
to filters and the need for bag-in, bag-out filter housings should be considered during the
design process.
Depending on the effluent of the processes being conducted, the exhaust airstream may require
filtration, scrubbing, or other emission control to remove environmentally hazardous materials.
Any need for emission control devices must be determined early in design so that adequate space
can be provided and cost implications can be recognized.
Laboratory exhaust systems can be constant-volume, variable-volume, or high-low volume
systems with low-, medium-, or high-pressure ductwork, depending on the static pressure of
the system. Each fume hood may have its own exhaust fan, or fume hoods may be manifolded and
connected to one or more common central exhaust fans. Maintenance, functional requirements,
and safety must be considered when selecting an exhaust system. Part of the hazard
assessment analysis is to determine the appropriateness of variable-volume systems and the
need for individually ducted exhaust systems. Laboratories with a high hazard potential
should be analyzed carefully before variable-volume airflow is selected, because minimum air
flow requirements could affect the design criteria.Airflow monitoring and
pressure-independent control may be required even with constant-volume systems. In addition,
fume hoods or other devices in which extremely hazardous or radioactive materials are used
should receive special review to determine whether they should be connected to a manifolded
exhaust system.
It is rare for all exhaust devices installed in a laboratory to be used simultaneously at
full capacity, so it is possible to conserve energy and potentially to reduce equipment
capacities by installing a variable-volume system that includes an overall system usage
factor. Selection of an appropriate usage factor is discussed in the section on Usage
Factor.
Manifolded Exhaust Systems. These can be
classified as pressure dependent or independent. Pressure-dependent systems are constant volume only
and incorporate manually adjusted balancing dampers for each exhaust device. If an
additional fume hood is added to a pressure-dependent exhaust system, the entire system must
be rebalanced, and the speed of the exhaust fans may need to be adjusted. Because
pressure-independent systems are more flexible, pressure-dependent systems are not common in
current designs.
A pressure-independent system can be
constant-volume, variable-volume, or a mix of the two. It incorporates pressure-independent
volume regulators with each device. The system offers two advantages: (1) flexibility to add
exhaust devices without having to rebalance the entire system and (2) variable-volume
control.
The volume regulators can incorporate either direct measurement of the exhaust airflow rate
or positioning of a calibrated pressure-independent air valve. The input to the volume
regulator can be (1) a manual or timed switch to index the fume hood airflow from minimum to
operational airflow, (2) sash position sensors, (3) fume hood cabinet pressure sensors, or
(4) velocity sensors. The section on Control covers this topic in greater detail. Running
many exhaust devices into the manifold of a common exhaust system offers the following
potential benefits:
-
Lower ductwork cost
-
Fewer pieces of equipment to operate and maintain
-
Fewer roof penetrations and exhaust stacks
-
Opportunity for energy recovery
-
Centralized locations for exhaust discharge
-
Ability to take advantage of exhaust system diversity
-
Ability to provide a redundant exhaust system by adding one spare fan per
manifold
-
Higher stack momentum, which can be beneficial for exhaust dispersion
Individually Ducted Exhaust Systems. These
comprise a separate duct, exhaust fan, and discharge stack for each exhaust device or
laboratory. The exhaust fan can be single-speed, multiple-speed, or variable-speed and can
be configured for constant volume, variable volume, or a combination of the two. Potential
benefits include the following:
-
Provision for installation of special exhaust filtration or treatment systems
-
Customized ductwork and exhaust fan corrosion control for specific applications
-
Provision for selected emergency power backup
-
Simpler initial balancing
-
Failure of an individual fan may affect smaller areas of the facility
-
Suitability for smaller laboratories
Maintaining correct flow at each exhaust fan requires (1) periodic maintenance and balancing
and (2) consideration of flow rates with the fume hood sash in different positions. One
problem encountered with individually ducted exhaust systems occurs when an exhaust fan is
shut down. In this case, air can be drawn in reverse flow through the exhaust ductwork into
the laboratory because the laboratory is maintained at a negative pressure.
A challenge in designing independently ducted exhaust systems for multistory buildings is to
provide extra vertical ductwork, extra space, and other provisions for future installation
of additional exhaust devices. In multistory buildings, dedicated fire-rated shafts may be
required from each floor to the penthouse or roof level. This issue should be evaluated in
conjunction with requirements of the relevant fire code. As a result, individually ducted
exhaust systems (or vertically manifolded systems) consume greater floor space than
horizontally manifolded systems. However, less height between floors may be required.
Ductwork should have low leakage rates and should be tested to confirm that the specified
leakage rates have been attained. Leaks from positive-pressure exhaust ductwork can
contaminate the building. The design goal should be zero leakage from any positive-pressure
exhaust ductwork. Designs that minimize the amount of positive-pressure ductwork are
desirable. It is recommended (and required by some codes) that positive-pressure ductwork
transporting potentially hazardous materials be located outside of the building; if these
ducts must be inside the building, they should be of the highest possible integrity. The fan
discharge should connect directly to the vertical discharge stack. Careful selection and
proper installation of airtight flexible connectors at the exhaust fans are essential. Some
feel that flexible connectors should be used on the exhaust fan inlet only. If flexible
connectors are used on the discharge side of the exhaust fan, they must be of high quality
and included on a preventative maintenance schedule, because a connector failure could
result in the leakage of hazardous fumes into the equipment room. Another viewpoint contends
that the discharge side of the exhaust fan should be hard connected to the ductwork, without
using flexible connectors. The engineer should evaluate these details carefully. The
potential for vibration and noise transmission must also be considered. Machine rooms that
house exhaust fans should be ventilated to minimize exposure to exhaust effluent (e.g.,
leakage from the shaft openings of exhaust fans).
Containment Device Leakage
Leakage of the containment devices themselves must also be considered. For example, in
vertical sash fume hoods, the clearance to allow sash movement creates an opening from the
top of the fume hood into the ceiling space or area above. Air introduced through this
leakage path also contributes to the exhaust airstream. The amount that such leakage sources
contribute to the exhaust airflow depends on the fume hood design. Edge seals can be placed
around sash tracks to minimize leaks. Although the volumetric flow of air exhausted through
a fume hood is based on the actual face opening, appropriate allowances for air introduced
through paths other than the face opening must be included.
Materials and Construction
The selection of materials and the construction of exhaust ductwork and fans depend on the
following:
-
Nature of the effluents
-
Ambient temperature
-
Ambient relative humidity
-
Effluent temperature
-
Length and arrangement of duct runs
-
Constant or intermittent flow
-
Flame spread and smoke developed ratings
-
Duct velocities and pressures
Effluents may be classified generically as organic or inorganic chemical gases, vapors,
fumes, or smoke; and qualitatively as acids, alkalis (bases), solvents, or oils. Exhaust
system ducts, fans, dampers, flow sensors, and coatings are subject to (1) corrosion, which
destroys metal by chemical or electrochemical action; (2) dissolution, which destroys
materials such as coatings and plastics; and (3) melting, which can occur in certain
plastics and coatings at elevated temperatures.
Common reagents used in laboratories include acids and bases. Common organic chemicals
include acetone, ether, petroleum ether, chloroform, and acetic acid. The HVAC engineer
should consult with the safety officer and scientists, because the specific research to be
conducted determines the chemicals used and therefore the necessary duct material and
construction.
The ambient temperature in the space housing the ductwork and fans affects the condensation
of vapors in the exhaust system. Condensation contributes to the corrosion of metals, and
the chemicals used in the laboratory may further accelerate corrosion.
Ducts are less subject to corrosion when runs are short and direct, flow is maintained at
reasonable velocities, and condensation is avoided. Horizontal ductwork may be more
susceptible to corrosion if condensate accumulates in the bottom of the duct. Applications
with moist airstreams (cage washers, sterilizers, etc.) may require condensate drains. The
design should include provisions to minimize joint or seam corrosion problems.
If flow through the ductwork is intermittent, condensate may remain for longer periods
because it will be unable to reevaporate into the airstream. Moisture can also condense on
the outside of ductwork exhausting cold environmental rooms.
Flame spread and smoke developed ratings, which are specified by codes or insurance
underwriters, must also be considered when selecting duct materials. In determining the
appropriate duct material and construction, the HVAC engineer should
-
Determine the types of effluents (and possibly combinations) handled by the
exhaust system
-
Classify effluents as either organic or inorganic, and determine whether they
occur in the gaseous, vapor, or liquid state
-
Classify decontamination materials
-
Determine the concentration of the reagents used and the temperature of the
effluents at the hood exhaust port (this may be impossible in research
laboratories)
-
Estimate the highest possible dew point of the effluent
-
Determine the ambient temperature of the space housing the exhaust system
-
Estimate the degree to which condensation may occur
-
Determine whether flow will be constant or intermittent (intermittent flow
conditions may be improved by adding time delays to run the exhaust system long
enough to dry the duct interior prior to shutdown)
-
Determine whether insulation, watertight construction, or sloped and drained
ductwork are required
-
Select materials and construction most suited for the application
Considerations in selecting materials include resistance to chemical attack and corrosion,
reaction to condensation, flame and smoke ratings, ease of installation, ease of repair or
replacement, and maintenance costs.
Appropriate materials can be selected from standard references and by consulting with
manufacturers of specific materials. Materials for chemical fume exhaust systems and their
characteristics include the following:
Galvanized steel. Subject to acid and alkali
attack, particularly at cut edges and under wet conditions; cannot be field welded without
destroying galvanization; easily formed; low in cost.
Stainless steel. Subject to acid and chloride
compound attack depending on nickel and chromium content of the alloy; relatively high in
cost. The most common stainless steel alloys used for laboratory exhaust systems are 304L
and 316L. Cost increases with increasing chromium and nickel content.
Asphaltum-coated steel. Resistant to acids;
subject to solvent and oil attack; high flame and smoke rating; base metal vulnerable when
exposed by coating imperfections and cut edges; cannot be field welded without destroying
coating; moderate cost.
Epoxy-coated steel. Epoxy phenolic resin coatings
on mild black steel or fluoropolymer coatings on stainless steel can be selected for
particular characteristics and applications; they have been successfully applied for both
specific and general use, but no one compound is inert or resistive to all effluents.
Requires sand blasting to prepare the surface for a shop-applied coating, which should be
specified as pinhole free, and field touch-up of coating imperfections or damage caused by
shipment and installation; cannot be field welded without destroying coating; cost is
moderate.
Plastic-coated galvanized steel. Subject to
corrosion at cut edges; cannot be field welded; easily formed; moderate in cost.
Fiberglass. When additional glaze coats are used,
this is particularly good for acid applications, including hydrofluoric acid. May require
special fire-suppression provisions. Special attention to hanger types and spacing is needed
to prevent damage.
Plastic materials. Have particular resistance to
specific corrosive effluents; limitations include physical strength, flame spread and smoke
developed rating, heat distortion, and high cost of fabrication. Special attention to hanger
types and spacing is needed to prevent damage.
Borosilicate glass. For specialized systems with
high exposure to certain chemicals such as chlorine.
3.3 FIRE SAFETY
FOR VENTILATION SYSTEMS
Fire safety for ventilation systems is addressed in the different model building codes and in
NFPA Standard 45. The HVAC designer needs to understand which codes
apply based on project-specific requirements. The hazard classification of the exhaust air
stream, requirements for fail-safe operation of dampers, system response on the detection of
fire or smoke, appropriateness of installing fire dampers in exhaust air ductwork, and placement
of fume hoods away from traffic and egress paths are some of the many factors that must be
understood and addressed.
Laboratory controls must regulate temperature and humidity, control and monitor
laboratory safety devices that protect personnel, and control and monitor secondary safety
barriers used to protect the environment outside the laboratory from laboratory operations.
Reliability, redundancy, accuracy, and monitoring are important factors in controlling the lab
environment. Many laboratories require precise control of temperature, humidity, and airflows.
Components of the control system must provide the necessary accuracy and corrosion resistance if
they are exposed to corrosive environments. Laboratory controls should provide fail-safe
operation, which should be defined jointly with the safety officer. A fault tree can be
developed to evaluate the impact of the failure of any control system component and to ensure
that safe conditions are maintained.
Temperature in laboratories with a constant-volume air supply is generally regulated with a
room temperature sensor and controller that positions control valve on a reheat coil in the
supply air. In laboratories with a variable-volume ventilation system, room exhaust
device(s) are generally regulated as well. The room exhaust device(s) are modulated to
handle greater airflow in the laboratory when additional cooling is needed. The exhaust
device(s) may determine the total supply air quantity for the laboratory.
Most microprocessor-based laboratory control systems can use proportional-integral-derivative
(PID) algorithms to eliminate the error between the measured temperature and the temperature
set point. Anticipatory control strategies increase accuracy in temperature regulation by
recognizing the increased reheat requirements associated with changes in the ventilation
flow rates and adjusting the position of reheat control valves before the thermostat
measures space temperature changes (Marsh 1988).
Constant-Air-Volume (CAV)
Versus Variable-Air-Volume (VAV)
Room Airflow Control
Several factors can influence the decision of whether VAV or CAV airflow control in a
laboratory is most appropriate, including required air change rates, density of exhausted
containment devices, and the potential hazards related to the lab operations.
Many laboratories that are considered CAV systems are not truly constant. Even when the fume
hoods operate continuously and are of the bypass type, considerable variations in airflow
may occur. Variations in airflow result from
-
Static pressure changes due to filter loading
-
Wet or dry cooling coils
-
Wear of fan belts that change fan speed
-
Position of chemical fume hood sash or sashes
-
Outdoor wind speed and direction
-
Position of doors and windows
Current controls can achieve good conformance to the requirements of a CAV system, subject to
normal deviations in control performance (i.e., the dead band characteristics of the
controller and the hysteresis present in the control system). The same is true for VAV
systems, although they are more complex. Systems may be either uncontrolled or controlled.
An uncontrolled CAV system can be designed with no automatic controls for airflow other than
two-speed fan motors to reduce flow during unoccupied periods. These systems are balanced by
manual dampers and adjustable drive pulleys. They provide reasonable airflow rates relating
to design values but do not provide true CAV under varying conditions, maintain constant
fume hood face velocity, or maintain relative static pressures in the spaces. For
laboratories that are not considered hazardous and do not have stringent safety
requirements, uncontrolled CAV may be satisfactory.
For laboratories housing potentially hazardous operations (i.e., involving toxic chemicals or
biological hazards), a true CAV or VAV system ensures that proper airflow and room pressure
relationships are maintained at all times. A true CAV system requires volume controls on the
supply and exhaust systems.
The principal advantage of using a VAV system is its ability to (1) ensure that face
velocities of chemical fume hoods are maintained within a set range and (2) reduce energy
use by reducing laboratory airflow. The appropriate safety officer and the users should
concur with the choice of VAV or CAV with reduced airflow during unoccupied periods.
Consider giving laboratory users the ability to reset VAV systems to full airflow volume in
the event of a chemical spill. Education of the laboratory occupants in proper use of the
system is essential. The engineer should recognize that the use of variable-volume exhaust
systems may result in higher concentrations of contaminants in the exhaust airstream, which
may increase corrosion, which influences the selection of materials.
In most experimental work, the laboratory apparatus, fume hood, or biological safety cabinet
is considered to be the primary method of containment. The facility is considered the
secondary level of containment.
The laboratory envelope acts as the secondary containment barrier. It is important that the
walls surrounding, and door openings into, the laboratory be of appropriate construction.
Because maintaining an airtight seal is rarely practical, air pressure in the laboratory
must be maintained slightly negative with respect to adjoining areas. Exceptions are sterile
facilities or clean spaces that may need to be maintained at a positive pressure with
respect to adjoining spaces. Positively pressurized spaces in which hazardous materials are
used should have an anteroom or vestibule to maintain overall negative pressurization.
Proper isolation is accomplished through the air balance/pressure relationship to adjacent
areas. The pressure relationship is
-
Negative, for hazardous isolation of hazardous or toxic operations (dirty
operations), or
-
Positive, for protective isolation of precious or delicate operations (clean
operations)
Common methods of room pressure control include manual balancing, direct pressure control,
volumetric flow tracking, and cascade control. All methods manipulate airflow into or out of
the space; however, each method measures a different variable. Regardless of the method of
space pressure control, the goal is to maintain an inward flow of air through small gaps in
the secondary barrier (room envelope). In critical applications, airlocks (entry vestibules)
may be required to ensure that pressure relationships are maintained as personnel enter or
leave the laboratory. The airlocks have an outer and inner door, with a vestibule in
between, allowing personnel to enter or exit the lab without a direct, open passage between
the laboratory and the adjoining space. Normal operation, by practice or through interlocks,
keeps one door closed as the second door is opened. If interlocks are necessary, take care
to prevent personnel from being trapped in the vestibule in a system malfunction. The
airlocks also serve as a buffer space between the laboratory and adjoining spaces, allowing
personal protective equipment (PPE) to be donned or doffed, and also provide a convenient
location for storing lab coats and for hand wash sinks.
Direct Pressure Control. This method measures the
pressure differential across the room envelope and adjusts the amount of supply air into the
laboratory to maintain the required differential pressure. Challenges encountered include
(1) maintaining the pressure differential when the laboratory door is open, (2) finding
suitable sensor locations, (3) maintaining a well-sealed laboratory envelope, and (4)
obtaining and maintaining accurate pressure sensing devices. The direct pressure control
arrangement requires tightly constructed and compartmentalized facilities and may require a
vestibule on entry/exit doors. Engineering parameters pertinent to envelope integrity and
associated flow rates are difficult to predict.
Because direct pressure control works to maintain the pressure differential, the control
system automatically reacts to transient disturbances. Entry/exit doors may need a switch to
disable the control system when they are open. Pressure controls recognize and compensate
for unquantified disturbances such as stack effects, infiltration, and influences of other
systems in the building. Expensive, complex controls are not required, but the controls must
be sensitive and reliable. In noncorrosive environments, controls can support a combination
of exhaust applications, and they are insensitive to minimum duct velocity conditions.
Successful pressure control provides the desired directional airflow but cannot guarantee a
specific volumetric flow differential.
Factors that favor direct pressure control include the following:
-
High pressurization level (>0.04 in. of water) and very tight
construction
-
Complex set of relative pressurization requirements
-
Slow disturbances only (e.g., stack effect, filter loading)
-
Poor conditions for airflow measurement
Volumetric Flow Tracking Control. This method
measures both exhaust and supply airflow and controls the amount of supply air to maintain
the desired pressure differential. Volumetric control requires controlling air at each
supply and exhaust point. It does not recognize or compensate for unquantified disturbances
such as stack effects, infiltration, and influences of other systems in the building. Flow
tracking is essentially independent of room door operation. Engineering parameters are easy
to predict, and extremely tight construction is not required. Balancing is critical and must
be addressed across the full operating range. The flow offset required should be greater
than the accuracy of the flow measurement and associated control error. The error in offset
airflow should be evaluated to ensure that the space remains under proper offset control.
Controls may be located in corrosive and contaminated environments; however, the controls may
be subject to fouling, corrosive attack, and/or loss of calibration. Flow measurement
controls are sensitive to minimum duct velocity conditions. Volumetric control may not
guarantee directional airflow.
Factors that favor volumetric flow tracking include the following:
-
Low pressurization level (usually 0.01 to 0.04 in. of water), less
tight construction
-
Fast disturbances (e.g., VAV fume hoods)
-
Simple set of relative pressurization levels (one or two levels)
Cascade Control. This method measures the pressure
differential across the room envelope to reset the flow tracking differential set point.
Cascade control includes the merits and shortcomings of both direct pressure control and
flow tracking control; however, first cost is greater, and the control system is more
complex to operate and maintain. It is used less often than the two preceding methods, but
its popularity is increasing. The trend toward tighter envelope construction makes it more
challenging to select effective flow offset values in pressurized suites, but using cascade
control makes this selection easier.
Factors that favor cascade control include fast disturbances and a complex set of relative
pressurization levels.
Criteria for fume hood control differ depending on the type of hood. The exhaust volumetric
flow is kept constant for standard, auxiliary air, and air-bypass fume hoods. In
variable-volume fume hoods, exhaust flow is varied to maintain a constant face velocity. The
fume hood control method should be selected in consultation with the safety officer.
Regardless of control decisions, fume hoods must be equipped with an airflow indicator for
the hood user.
Constant-volume fume hoods can further be split into pressure-dependent or
pressure-independent systems. Although simple in configuration, the pressure-dependent
system is unable to adjust the damper position in response to any fluctuation in system
pressure across the exhaust damper.
Variable-volume fume hood control strategies can be grouped into two categories. The first
either measures the air velocity entering a small sensor in the wall of the fume hood or
determines face velocity by other techniques. The measured variable is used to infer the
average face velocity based on an initial calibration. This calculated face velocity is then
used to modulate the exhaust flow rate to maintain the desired face velocity.
The second category of variable-volume fume hood control measures the fume hood sash opening
and computes the exhaust flow requirement by multiplying the sash opening by the face
velocity set point. The controller then adjusts the exhaust device (e.g., by a
variable-frequency drive on the exhaust fan or a damper) to maintain the desired exhaust
flow rate. The control system may measure the exhaust flow for closed-loop control, or it
may not measure exhaust flow in an open-loop control by using linear calibrated flow control
dampers.
An additional energy reduction feature for variable-volume hoods that can be incorporated
into the fume hood controls is provision to automatically close the fume hood sash,
improving sash management, when no presence is sensed in front of the hood.
Provision of a purge feature on the fume hood can allow the fume hood user to manually index
the exhaust airflow higher if needed.
3.5 STACK HEIGHTS AND
AIR INTAKES
Laboratory exhaust stacks should release effluent to the atmosphere without producing undesirable
high concentrations at fresh air intakes, operable doors and windows, and locations on or near
the building where access is uncontrolled. Three primary factors that influence the proper
disposal of effluent gases are stack/intake separation, stack height, and stack height plus
momentum (plume height). Chapter 24 of the
2021 ASHRAE
Handbook—Fundamentals and Chapter
45 of this volume cover the
criteria and formulas to calculate the effects of these physical relationships. For complex
buildings or buildings with unique terrain or other obstacles to the airflow around the
building, either scale model wind tunnel testing or computational fluid dynamics should be
considered. However, standard k-ε computational fluid dynamics
methods as applied to airflow around buildings need further development (Castro 2003; Murakami
et al. 1996; Zhou and Stathopoulos 1996). HVAC system designers who do not have the analytical
skills required to undertake a dispersion analysis should consider retaining a specialized
consultant.
Separation of the stack discharge and air intake locations allows the atmosphere to dilute
the effluent. Separation is simple to calculate with the use of short to medium-height
stacks; however, to achieve adequate atmospheric dilution of the effluent, greater
separation than is physically possible may be required, and the building roof near the stack
will be exposed to higher concentrations of the effluent. However, when stacks are much
taller than the intake, the best location for the intake may be very close to the stack but
this should evaluated on a case-by-case basis.
Chapter 45 describes a geometric
method to determine the stack discharge height high enough above the turbulent zone around
the building so that little or no effluent gas impinges on air intakes of the emitting
building. This technique is conservative and generally requires tall stacks that may be
visually unacceptable or fail to meet building code or zoning requirements. Also, this
technique does not ensure acceptably low concentrations of effluents at air intakes (e.g.,
if there are large releases of hazardous materials or elevated intake locations on nearby
buildings). A minimum stack height of 10 ft is required by ASSE Standard Z9.5 and is recommended by Appendix A of NFPA Standard 45 to protect rooftop maintenance workers. However, a
taller stack height may be necessary to ensure that harmful contaminants are not reentrained
into nearby air intakes.
Stack Height plus Vertical
Momentum
Concentrations at downwind locations are directly related to the height of the centerline of
the plume. Plume height is a function of the physical stack height and plume rise (vertical
momentum). To increase the plume height, increase the volumetric flow and/or the discharge
velocity to increase the discharge momentum (Momentum flow = Density × Volumetric flow
rate × Velocity), or increase the physical stack height. The momentum of a large
vertical flow lifts the plume above the stack top, thereby potentially reducing the
necessary physical height of the stack and making it easier to screen from view. This
technique is particularly suitable when (1) many small exhaust streams can be clustered
together or manifolded prior to the exhaust fan to provide the large volumetric flow and (2)
outdoor air can be added through automatically controlled dampers to provide constant
exhaust vertical momentum under variable load. The drawbacks to the second arrangement are
the amount of energy consumed to achieve the constant high vertical momentum and the added
complexity of the controls to maintain constant volumetric flow rates. Dilution equations in
Chapter 45 can be used to predict
the performance of a particular stack design, or performance can be validated through wind
tunnel testing. Current numerical procedures tend to have a high degree of uncertainty, and
the results should be judged accordingly.
Rooftop architectural screens around exhaust stacks are known to adversely affect exhaust
dispersion. In general, air intakes should not be placed within the same screen enclosure as
laboratory exhausts. Petersen et al. (1997) describe a method of adjusting dilution
predictions of Chapter 45 using a stack height
adjustment factor, which is essentially a function of screen porosity.
Criteria for Suitable Dilution
An example criterion based on Halitsky (1988) dictates that the release of 15
cfm of pure gas through any stack in a moderate wind (3 to
18 mph), from any direction with a near-neutral atmospheric stability
(Pasquill Gifford Class C or D), must not produce concentrations exceeding 3
ppm at any air intake. This criterion is meant to simulate an accidental release
such as would occur in a spill of an evaporating liquid or after the fracture of the neck of
a small lecture bottle of gas in a fume hood.
The intent of this criterion is to limit the concentration of exhausted gases at the air
intake locations to levels below the odor thresholds of gases released in fume hoods,
excluding highly odorous gases such as mercaptans. Laboratories that use extremely hazardous
substances should conduct a chemical-specific analysis based on published health limits. A
more lenient limit may be justified for laboratories with low levels of chemical usage.
Project-specific requirements must be developed in consultation with the safety officer. The
equations in Chapter 45 are presented in terms
of dilution, defined as the ratio of stack exit concentration to receptor concentration. The
exit concentration, and therefore the dilution required to meet the criterion, varies with
the total volumetric flow rate of the exhaust stack. For the preceding criterion, with the
emission of 15 cfm of a pure gas, a small stack with a total flow rate of
1000 cfm will have an exit concentration of 15/1000 or 15,000 ppm.
A dilution of 1:5000 is needed to achieve an intake concentration of 3 ppm. A
larger stack with a flow rate of 10,000 cfm will have a lower exit
concentration of 15/10,000 or 1500 ppm and would need a dilution of only 1:500
to achieve the 3 ppm intake concentration.
The preceding criterion is preferred over a simple dilution standard because a defined
release scenario (15 cfm) is related to a defined intake concentration (3
ppm) based on odor thresholds or health limits. A simple dilution requirement
may not yield safe intake concentrations for a stack with a low flow rate.
Adjacent Building Effects
The influence of adjacent building effects was studied under ASHRAE research project RP-897
(Wilson et al. 1998). Several guidelines were developed from this project:
-
Avoid locating stacks near the edge of a roof.
-
With the emitting building upwind, an adjacent building will always have higher
dilution on a lower roof than would occur on a roof at the emitting
building’s height. Ignoring the step-down in roof level will produce
conservative designs.
-
If the lower adjacent building is upwind of the emitting building, it will block
flow approaching the emitting building, producing lower velocities and
recirculation cavities on the emitting building roof and increasing dilution by
factors of 2 to 10 on the emitting building.
-
Designers should increase either the physical stack height or the vertical
momentum of the exhaust when the plume will be trapped in the recirculation
cavity from a high upwind adjacent building.
-
When the adjacent building is higher than the emitting building, designers should
try to avoid placing air intakes on the adjacent building at heights above the
roof level of the emitting building.
Also see Chapter 45 for more information.
4.1 LABORATORY ANIMAL FACILITIES
Laboratory animals must be housed in comfortable, clean, temperature- and humidity-controlled
rooms. Animal welfare must be considered in the design; the air-conditioning system must provide
the macroenvironment (for the animal room) and microenvironment (in the animal’s primary
enclosure or cage) specified by the facility’s veterinarian (Besch 1975; ILAR 2011; Woods
1980). Early and detailed discussions with the veterinarian regarding airflow patterns, cage
layout, and risk assessment help ensure a successful animal room HVAC design. The elimination of
research variables (fluctuating temperature and humidity, drafts, and spread of airborne
diseases) is another reason for a high-quality air-conditioning system. See Chapter 24 for
additional information on environments for laboratory animals.
Primary Uses of Animal Housing
Facilities
Primary uses of animal facilities include the following:
-
Acute (short-term) studies: generally
less than 90 days in length, although the animal species and particular
experiments involved could affect duration. Most frequently found in
pharmaceutical, medical, or other life science laboratories, and includes
-
Chronic (long-term) studies: generally
more than 90 days in length, although the species and experiment involved could
affect the length. Includes
-
Toxicology
-
Teratology
-
Neurological
-
Quality control
-
Long-term holding of animals,
including
-
Agricultural studies, including food
and fiber animals
There are a number of regulations and guidelines that pertain to the housing of laboratory
animals. Additional regulations cover the housing of animals that may be used in some way in
the production of pharmaceuticals, testing for agricultural products, or used for quality
control. Pertinent regulations, as found in the United States, are outlined below. Other
countries have similar regulations that should be consulted when designing animal facilities
located in that country. Regulations and guidelines include the following:
-
Code of Federal Regulations (CFR) 21
-
Part 58; Good Laboratory Practices for Nonclinical Laboratory Studies
-
Part 210; Current Good Manufacturing Practice in Manufacture,
Processing, Packing or Holding of Human and Veterinary Drugs
-
Guide for the Care and Use of Laboratory Animals,
National Research Council
-
Biosafety in Microbiological and Biomedical
Laboratories, Centers for Disease Control (CDC).
-
The Animal Welfare Act of 1966 and as subsequently amended. Regulatory authority
is vested in the Secretary of the U.S. Department of Agriculture (USDA) and
implemented by the USDA’s Animal and Plant Health Inspection Service.
-
American Association for Accreditation of Laboratory Animal Care (AAALAC), a
nonprofit organization to which many institutions and corporations belong. This
group provides accreditation based upon inspections and reports from member
groups. Many organizations that build or maintain animal facilities adhere to
AAALAC programs and HVAC engineers are expected to design to their guidelines.
Local ordinances or user organization requirements may also apply. HVAC engineers should
confirm which regulations are applicable for any project.
Due to the nature of research programs, air-conditioning design temperature and humidity
control points may be required. Research animal facilities require more precise
environmental control than farm animal or production facilities (as covered in Chapter
24) because variations affect the experimental results. A totally flexible system
permits control of the temperature of individual rooms to within
±2°F for any set point in a range of 64 to 85°F.
This flexibility requires significant capital expenditure, which can be mitigated by
designing the facility for selected species and their specific requirements.
Table
1 lists dry-bulb temperatures recommended by ILAR (2011) for several common species.
In the case of animals in confined spaces, the range of daily temperature fluctuations
should be kept to a minimum. Relative humidity should also be controlled. ILAR (2011)
suggests the acceptable range of relative humidity is 30 to 70%.
Providing 10 to 15 fresh air changes per hour in animal housing rooms is an acceptable
guideline to maintain macroenvironmental air quality by constant-volume systems, and may
also ensure microenvironmental air quality (NRC 2011). Although this range is effective in
many animal housing settings, it does not take into account the range of possible heat
loads; species, size, and number of animals involved; type of primary enclosure and bedding;
frequency of cage changing; room dimensions; or efficiency of air distribution both in the
macroenvironment and between the macro- and microenvironments. In some situations, using
such a broad guideline might overventilate a macroenvironment containing few animals,
thereby wasting energy, or underventilate a microenvironment containing many animals,
allowing heat, moisture, and pollutants to accumulate.
VAV systems allow ventilation rates to be set in accordance with heat load and other
variables. These systems offer considerable advantages in flexibility and energy
conservation, but should always provide a minimum amount of air exchange, as recommended for
general-use laboratories. Active sensing of contaminants in the secondary enclosure and
varying the air change rates based on the room environmental conditions is one approach that
can be considered to meet these requirements more energy efficiently.
For small-animal caging systems, studies suggest that room conditions have very little
influence on the cage environments. ASHRAE research project RP-730 (Maghirang et al. 1995;
Riskowski et al. 1996) found the following:
-
No relationship between room ventilation rate and cage microenvironments for
shoebox and microisolator cages exists. In fact, 5 ach provided the same
cage ventilation rates for shoebox cages as did 10 and 15 ach. Memarzadeh (2000)
also found this lower air change rate satisfactory.
-
Diffuser type (perforated square versus radial) had only a small effect on
shoebox cage ventilation rates. The radial diffuser provided higher wire cage
ventilation rates.
-
One high return provided the same cage ventilation rates as four high returns or
as one low return.
-
Room size had no effect on cage ventilation rates.
This research is further discussed in Chapter
24.
In certain types of animal rooms, usually those used for long-term studies involving
high-value work or animals, the outdoor air change rate is maintained at 10 to 15 per hour,
but the total airflow in the rooms ranges from 90 to 150 ach (mass flow spaces similar to
clean rooms). The air supply is generally terminal HEPA filtered to reduce the potential for
disease. These rooms are energy intensive, and may not be required with newer filter
capability and caging systems.
The air-conditioning load and flow rate for an animal room should be determined by the
following factors:
-
Desired animal microenvironment (Besch 1975, 1980; ILAR 2011)
-
Species of animal(s)
-
Animal population
-
Recommended ambient temperature (Table
1)
-
Heat produced by motors on special animal housing units (e.g., laminar flow racks
or HEPA-filtered air supply units for ventilated racks)
-
Heat generated by the animals (Table 2)
Additional design factors include method of animal cage ventilation; operational use of a
fume hood or a biological safety cabinet during procedures such as animal cage cleaning and
animal examination; airborne contaminants (generated by animals, bedding, cage cleaning, and
room cleaning); and institutional animal care standards (Besch 1980; ILAR 2011). Note that
ambient conditions of the animal room might not reflect the actual conditions within a
specific animal cage.
Air-conditioning systems must remove the sensible and latent heat produced by laboratory
animals. The literature concerning the metabolic heat production appears to be divergent,
but new data are consistent. Current recommended values are given in Table 2. These values
are based on experimental results and the following equation:
where
| ATHG = average total heat gain, Btu/h per animal |
| M = metabolic rate of animal, Btu/h per
animal = 6.6W0.75 |
| W = weight of animal, lb |
Conditions in animal rooms must be kept constant. This may require year-round availability of
refrigeration and, in some cases, dual/standby chillers and emergency electrical power for
motors and control instrumentation. Storing critical spare parts is one alternative to
installing a standby refrigeration system.
If the entire animal facility or extensive portions of it are permanently planned for species
with similar requirements, the range of individual adjustments may be reduced. Each animal
room or group of rooms serving a common purpose should have separate temperature and
humidity controls. The animal facility and human occupancy areas should be conditioned
separately. The human areas may use a return air HVAC system and may have unoccupied mode
setback on weekends for energy conservation. Separation prevents exposure of personnel to
biological agents, allergens, and odors from animal rooms.
Control of air pressure in animal housing and service areas is important to ensure
directional airflow. For example, quarantine, isolation, soiled equipment, and biohazard
areas should be kept under negative pressure, whereas clean equipment and pathogen-free
animal housing areas and research animal laboratories should be kept under positive
pressure.
Supply air outlets should not cause drafts on research animals. Efficient air distribution
for animal rooms is essential; this may be accomplished effectively by supplying air through
ceiling outlets and exhausting air at floor level (Hessler and Moreland 1984). Supply and
exhaust systems should be sized to minimize noise.
A study by Neil and Larsen (1982) showed that predesign evaluation of a full-size mock-up of
the animal room and its HVAC system was a cost-effective way to select a system that
distributes air to all areas of the animal-holding room. Wier (1983) describes many typical
design problems and their resolutions. Evaluate room air distribution using ASHRAE Standard 113 procedures to evaluate drafts and temperature
gradients.
HVAC ductwork and utility penetrations must be minimized and sealed. Exposed ductwork is not
generally recommended; however, if constructed of 316 stainless steel, in a fashion to
facilitate removal for cleaning, it can provide a cost-effective alternative. Joints around
diffusers, grilles, and the like should be sealed. Exhaust air grilles with 1
in. washable or disposable filters are normally used to prevent animal hair and
dander from entering the ductwork. Noise from the HVAC system and sound transmission from
nearby spaces should be evaluated. Sound control methods such as separate air-handling
systems or sound traps should be used as required.
Multiple-cubicle animal rooms enhance the operational flexibility of the animal room (i.e.,
housing multiple species in the same room, quarantine, and isolation). Each cubicle should
be treated as if it were a separate animal room, with air exchange/balance, temperature, and
humidity control.
Animal facilities use a number of different caging systems that can significantly affect the
environment within the cage or the total heat load in the room. The purpose of the caging
systems is to
-
Protect the health and wellbeing of the animals
-
Protect support staff from antigens released or shed by the animals
-
Minimize exposure of animals to pheromones released by other animals in the space
To provide the appropriate design, the HVAC engineer must be aware of the type of caging
system to be used. Some common caging systems include the following:
-
Cage boxes made of sheet metal, plastic, or wire mesh, with the space inside the
cage open to the room so the room’s macroenvironment is essentially
identical to the cage’s microenvironment.
-
Cage boxes made primarily of plastic, with the top shielded from the room by a
filter material to provide some level of isolation from the room. The filter is
usually not sealed to the cage, so some open space between the room and the
interior of the cage remains. Exchange of air, vapors, particulates, and gases
between the room and the cage interior does occur, but the rate of exchange is
reduced by the filter. The microenvironment of the interior of the cage is
usually different from that of the room.
-
Plastic and wire cages that are part of a cage rack assembly, which provides
varying degrees of isolation from the room. These usually provide filtered
(generally HEPA-filtered) air directly to each individual or shelf of cage
boxes. In some cases, both a fan-powered supply and an exhaust unit are used. In
other cases, cage units are connected to the facility exhaust system to provide
airflow. Facilities with this kind of caging system must be designed to
accommodate the heat gain in the space if the exhaust is released in the room.
Some heat gain may be excluded if the caging assembly is connected directly to
the facility exhaust system. When the facility is used to provide the exhaust by
direct connection to the caging assembly, the design must include provisions to
control the airflow to ensure that the overall proper airflow and relative
static pressure of the room and each cage rack assembly is maintained,
especially when caging and rack connections may be changed over time. The
temperature and specific humidity in each cage will be higher than the ambient
conditions of the room.
4.2 ANCILLARY SPACES FOR ANIMAL
LABORATORIES
In addition to animal holding rooms, a facility intended to provide for an animal colony
generally requires other areas, such as
-
Cage washer: Usually provided with some
temperature control to minimize heat stress for occupants. In addition, specific
exhaust hoods and separate exhaust ductwork should be considered for the space and
equipment.
-
Feed storage: Usually provided with
temperature and humidity control to protect quality and shelf life of feed.
-
Diagnostic laboratory: Usually provided
with laboratory-quality air conditioning.
-
Treatment laboratory: Usually provided
with laboratory-quality air conditioning.
-
Quarantine spaces: To separate incoming
animals from the remainder of the colony until their health can be evaluated. These
rooms are frequently located near the receiving location. Animal-room-quality air
conditioning is provided.
-
Surgery suite: Sterile-quality air
conditioning is provided. The suites frequently have provisions to exhaust
anesthetic gases.
-
Necropsy laboratory: Usually provided with
laboratory-quality air conditioning and frequently fitted with special exhaust
tables or other means of protecting laboratory workers from exposure to chemical
preservatives or biological contamination. For high-risk or high-hazard work, Type
III biological safety cabinets may be provided.
-
Waste-holding room: Usually only provided
with heating and ventilation, but maintained at negative pressure relative to
adjacent areas. When used to store carcasses, a refrigerated storage unit of
appropriate size should be provided.
4.3 CONTAINMENT LABORATORIES
With the initiation of biomedical research involving recombinant DNA technology, federal
guidelines on laboratory safety were published that influence design teams, researchers, and
others. Containment describes safe methods for managing hazardous chemicals and infectious
agents in laboratories. The three elements of containment are laboratory operational practices
and procedures, safety equipment, and facility design. Thus, the HVAC design engineer helps
decide two of the three containment elements during the design phase.
In the United States, the U.S. Department of Health and Human Services (DHHS), Centers for
Disease Control and Prevention (CDC), and National Institutes of Health (NIH) classify
biological laboratories into four levels (Biosafety Levels 1 to 4) listed in DHHS (1999). The
USDA Agricultural Research Service (ARS) Manual 242.1 (ARS 2012)
similarly classifies biological laboratories, and also identifies a BSL 3Ag containment level.
Biosafety Level 1 is suitable for work involving well-known agents not thought to
consistently cause disease in healthy adult humans, and of minimal potential hazard to
laboratory personnel and the environment. The laboratory is not necessarily separated from
the general traffic patterns in the building. Work is generally conducted on open benchtops
using standard microbiological practices. Special containment equipment is neither required
nor generally used. The laboratory can be cleaned easily and contains a sink for washing
hands. Federal guidelines for these laboratories contain no specific HVAC requirements.
Biosafety Level 2 is suitable for work involving agents of moderate potential hazard to
personnel and the environment. Laboratory access is limited when certain work is in
progress. The laboratory can be cleaned easily and contains a sink for washing hands.
Biological safety cabinets (Class I or IIA2) are used when
-
Procedures with a high potential for creating infectious aerosols are conducted.
These include centrifuging, grinding, blending, vigorous shaking or mixing,
sonic disruption, opening containers of infectious materials, inoculating
animals intranasally, and harvesting infected tissues or fluids from animals or
eggs.
-
High concentrations or large volumes of infectious agents are used. Federal
guidelines for these laboratories contain minimum facility standards.
At this level of biohazard, most research institutions have a full-time safety officer (or
safety committee) who establishes facility standards. The federal guidelines for Biosafety
Level 2 contain no specific HVAC requirements; however, typical HVAC design criteria can
include the following:
-
100% outdoor air systems
-
6 to 15 air changes per hour
-
Directional airflow into the laboratory rooms
-
Site-specified hood face velocity at fume hoods (many institutions specify
80 to 100 fpm)
-
An assessment of research equipment heat load in a room.
-
Inclusion of biological safety cabinets
Most biomedical research laboratories are designed for Biosafety Level 2. However, the
laboratory director must evaluate the risks and determine the correct containment level
before design begins.
Biosafety Level 3 applies to facilities in which work is done with indigenous or exotic
agents that may cause serious or potentially lethal disease as a result of exposure by
inhalation. The Biosafety Level 3 laboratory uses a physical barrier of two sets of
self-closing doors to separate the laboratory work area from areas with unrestricted
personnel access. This barrier reinforces biological containment to within the laboratory
work area.
The ventilation system must be single-pass, nonrecirculating, and configured to maintain the
laboratory at a negative pressure relative to surrounding areas. Audible alarms and visual
monitoring devices are recommended to notify personnel if the laboratory pressure
relationship changes from negative to positive. The user may wish to have alarms reported to
a remote, constantly monitored location. Gastight dampers are required in the supply and
exhaust ductwork to allow decontamination of the laboratory. Ductwork between these dampers
and the laboratory must also be gastight. All penetrations of the Biosafety Level 3
laboratory envelope must be sealable for containment and to facilitate gaseous
decontamination of the work area.
All procedures involving the manipulation of infectious materials are conducted inside
biological safety cabinets. The engineer must ensure that the connection of the cabinets to
the exhaust system does not adversely affect performance of either cabinets or exhaust
system. Refer to the section on Biological Safety Cabinets for further discussion.
Exhaust air from biological safety cabinets and/or the laboratory work area may require HEPA
filtration. Review the need for filtration or special exhaust handling from any scientific
equipment with the appropriate safety officers. If required, HEPA filters should be equipped
with provisions for bag-in, bag-out filter handling systems and gastight isolation dampers
for biological decontamination of the filters.
Biosafety Level 4 is required for work with dangerous and exotic agents that pose a high risk
of aerosol-transmitted laboratory infections and life-threatening disease. HVAC systems for
these areas have stringent design requirements that must be determined by the biological
safety officer. Design of Level 4 laboratories requires significant specialization and
understanding of best practices.
Biosafety Level 3Ag is required for work with certain biological agents in large animal
species. Using the containment features of the standard BSL 3 facility as a starting point,
BSL 3Ag facilities are specifically designed to protect the environment by including almost
all of the features ordinarily used for BSL 4 facilities as enhancements. All BSL 3Ag
containment spaces must be designed, constructed, and certified as primary containment
barriers.
4.4 SCALE-UP LABORATORIES
Scale-up laboratories are defined differently depending on the nature and volume of work being
conducted. For laboratories performing recombinant DNA research, large-scale experiments
generally involve vessels between 10 and 100 L or more. A chemical or biological laboratory is
defined as scale-up when the principal holding vessels are glass or ceramic. When the vessels
are constructed primarily of metals, the laboratory is considered a pilot plant, which this
chapter does not address. The amount of experimental materials present in scale-up laboratories
is generally significantly greater than the amount found in the small-scale laboratory.
Experimental equipment is also larger and therefore requires more space; these may include
larger chemical fume hoods or reaction cubicles that may be of the walk-in type. Significantly
higher laboratory airflow rates are needed to maintain the face velocity of the chemical fume
hoods or reaction cubicles, although their size frequently presents problems of airflow
uniformity over the entire face area. Walk-in hoods are sometimes entered during an experimental
run, so provisions for breathing-quality air stations and other forms of personnel protection
should be considered. Environmental containment or the ability to decontaminate the laboratory,
the laboratory exhaust airstream, or other effluent may be needed in the event of an accidental
discharge. Scale-up laboratories may be in operation for sustained periods.
For large walk-in hoods or reaction cubicles, the large volume of exhaust air required and the
simultaneous requirement for supply air can result in temperature gradient problems in the
space.
Large hoods, similar to what sometimes are called “California hoods,” may also be
provided in scale-up laboratories. These hoods are large in volume and height, provide access on
multiple sides, and can be customized using standard components. Before beginning any custom
hood design, the HVAC engineer, working with the user, should first determine what activities
will be conducted. Then the HVAC engineer can develop a custom hood design that considers
-
What access is required for setup of experimental apparatus
-
How the hood is expected to function during experimental runs
-
Which doors or sashes should be open during a run
-
Safety and ergonomic issues
-
What features should be incorporated
-
Airflow required to achieve satisfactory containment
Testing and balancing criteria should also be defined early in the design process. Mockups and
factory testing of prototypes should be considered to avoid problems with installed hoods.
4.5 TEACHING LABORATORIES
Laboratories in academic settings can generally be classified as either those used for
instruction or those used for research. Research laboratories vary significantly depending on
the work being performed; they generally fit into one of the categories of laboratories
described previously.
The design requirements for teaching laboratories also vary based on their function. The designer
should become familiar with the specific teaching program, so that a suitable hazard assessment
can be made. For example, the requirements for the number and size of fume hoods vary greatly
between undergraduate inorganic and graduate organic chemistry teaching laboratories. Unique
aspects of teaching laboratories include the need of the instructor to be in visual contact with
the students at their work stations and to have ready access to the controls for the fume hood
operations and any safety shutoff devices and alarms. Frequently, students have not received
extensive safety instruction, so easily understood controls and labeling are necessary. Because
the teaching environment depends on verbal communication, sound from the building ventilation
system is an important concern. See Lewis (2007) for additional considerations.
4.6 CLINICAL LABORATORIES
Clinical laboratories are found in hospitals and as stand-alone operations. Work in these
laboratories generally consists of handling human specimens (blood, urine, etc.) and using
chemical reagents for analysis. Some samples may be infectious; because it is impossible to know
which samples may be contaminated, good work practices require that all be handled as
biohazardous materials. The primary protection of the staff at clinical laboratories depends on
the techniques and laboratory equipment (e.g., biological safety cabinets) used to control
aerosols, spills, or other inadvertent releases of samples and reagents. People outside the
laboratory must also be protected.
The building HVAC system can provide additional protection with suitable exhaust, ventilation,
and filtration. The HVAC engineer is responsible for providing an HVAC system that meets the
biological and chemical safety requirements. The engineer should consult with appropriate senior
staff and safety professionals to ascertain what potentially hazardous chemical or biohazardous
conditions will be in the facility and then provide suitable engineering controls to minimize
risks to staff and the community. Appropriate laboratory staff and the design engineer should
consider using biological safety cabinets, chemical fume hoods, and other specific exhaust
systems.
4.7 RADIOCHEMISTRY LABORATORIES
In the United States, laboratories located in Department of Energy (DOE) facilities are governed
by DOE regulations. All other laboratories using radioactive materials are governed by the
Nuclear Regulatory Commission (NRC), state, and local regulations. Other agencies may be
responsible for the regulation of other toxic and carcinogenic materials present in the
facility. Laboratory containment equipment for nuclear processing facilities are treated as
primary, secondary, or tertiary containment/confinement zones, depending on the level of
radioactivity anticipated for the area and the materials to be handled. Chapter
28 has additional information on nuclear laboratories.
4.8 OPERATION, TRAINING, AND MAINTENANCE
During long-term research studies, laboratories may need to maintain design performance conditions, with no interruptions, for long periods. Even when
research needs are not so demanding, systems that maintain air balance, temperature, and
humidity in laboratories must be highly reliable, with a minimal amount of downtime. The
designer should work with the commissioning agent, operation and maintenance personnel, as well
as users, early in the design of systems to gain their input and agreement to develop a lab
ventilation management plan. Refer to the ASHRAE (2002) Laboratory Design
Guide and ANSI/ASSP Standard Z9.5-2022 for additional
detail.
System components must be of adequate quality to achieve reliable HVAC operation, and they should
be reasonably accessible for maintenance. Laboratory work surfaces should be protected from
possible leakage of coils, pipes, and humidifiers. Changeout of supply and exhaust filters
should require minimum downtime.
Centralized monitoring of laboratory variables (e.g., pressure differentials, face velocity of
fume hoods, supply flows, and exhaust flows) is useful for predictive maintenance of equipment
and for ensuring safe conditions. For their safety, laboratory users should be instructed in the
proper use of laboratory fume hoods, safety cabinets, ventilated enclosures, and local
ventilation devices.
Personnel who know the particular nature of the contaminants in a given laboratory should be
responsible for decontamination of equipment and ductwork before they are turned over to
maintenance personnel for work.
Maintenance personnel should be trained to keep laboratory systems in good operating order and
should understand the critical safety requirements of those systems. Schedule preventive
maintenance of equipment and periodic checks of air balance. High-maintenance items should be
placed outside the actual laboratory (in service corridors or interstitial space) to reduce
disruption of laboratory operations and exposure of the maintenance staff to laboratory hazards.
Maintenance personnel must be aware of and trained in procedures for maintaining good indoor air
quality (IAQ) in laboratories. Many IAQ problems have been traced to poor maintenance due to
poor accessibility (Woods et al. 1987).
Because of the nature of the functions they support, laboratory HVAC systems consume large
amounts of energy (high flow rates; high static pressure filtration; critical cooling, heating,
and humidification). Efforts to reduce energy use must not compromise standards established by
safety officers. Typically, HVAC systems supporting laboratories and animal areas use high
percentages of outdoor air and operate continuously. All HVAC systems serving laboratories can
benefit from energy reduction techniques that are either an integral part of the original design
or added later. Energy reduction techniques should be analyzed in terms of both appropriateness
to the facility and economic payback.
Energy-efficient design is an iterative process that begins with establishing communication among
all members of the design team. Each design discipline has an effect on the energy load. On a
macro scale, air change rate, building orientation, window shading devices, and high-performance
envelopes offer opportunity for energy use reduction. On a micro scale, for example, the choice
of a lighting system can affect sensible heat gain. Energy-efficient designs should recognize
the variability of exhaust, envelope, and equipment loads and use systems that respond
appropriately and perform efficiently during partial-load conditions.
The HVAC engineer must understand and respond to the scientific requirements of the facility.
Research requirements typically include continuous control of temperature, humidity, relative
static pressure, and air quality. Energy reduction systems must maintain required environmental
conditions during both occupied and unoccupied modes.
Energy can be used more efficiently in laboratories by reducing exhaust air requirements. One
way to achieve this is to use variable-volume control of exhaust air through the fume hoods
to reduce exhaust airflow when the fume hood sash is not fully open. Recent changes in ASSE
Standard Z9.5 allow a much lower fume hood minimum flow rate
with variable-volume hoods, depending on system design and aspects of laboratory operations.
Any airflow control must be integrated with the laboratory control system, described in the
section on Control, and its setting and operation must not jeopardize the safety and
function of the laboratory.
Fume hood selection also affects exhaust airflow requirements and energy consumption. Modern
fume hood designs use several techniques to reduce airflow requirements, including
reduced-face-opening sashes and specially designed components that allow operation with
reduced inflow velocities. These reduced-face-opening sash hoods or low-capture-velocity
hoods may reduce overall airflow requirements to the degree that additional variable-volume
controls may not be justifiable. When considering these features, it is important to obtain
approval of laboratory occupants and safety personnel.
Energy efficiency in laboratories and other buildings depends on many examples of dynamically
adjusting consumption to match changing needs, rather than simply running systems at
constant output. Laboratory ventilation is part of this trend.
Ventilation designers and safety professionals attempt to take scientific, quantitative
approach to setting airflow levels, but they face many unknown factors. They are forced to
make assumptions and exercise judgment. This leads to conservatively selected ventilation
rates. Dynamic ventilation eliminates some of the
uncertainty by using real-time information, making it possible to lower ventilation rates
without sacrificing a conservative approach. It is not necessary to set one constant
ventilation rate, based only on information available at design time: a range of rates can
be selected, with the specific value determined according to information gained in operation
(e.g., presence or absence of lab workers [ventilation setback], or measured concentration
of selected contaminants in the room air [demand-controlled ventilation]; these two example
strategies are completely complementary, and can deliver benefits when used together or
separately).
Reducing ventilation requirements in laboratories and vivariums based on real-time sensing of
contaminants in the room environment offers opportunities for energy conservation. This
approach can potentially safely reduce lab air change rates to as low as 2 ach when the lab
air is clean and the fume hood exhaust or room cooling load requirements do not require
higher airflow rates. Sharp (2010) showed that lab rooms are on average clean of
contaminants about 98% of the time. With fixed ventilation rates, engineers are forced to
design for the 2% of the time when high flow is needed; dynamic ventilation takes advantage
of the 98% of the time that it is not.
Using a reduced ventilation rate when the laboratory is unoccupied can save significant
amounts of energy. The savings potential that justifies a ventilation setback depends on the
amount that the ventilation can be reduced and the amount of reliably unoccupied operating
time. To use it properly, ventilation designers need to confirm that premise applies: that
is, when the workers cease their activities and leave the laboratory, the contamination
hazard is significantly reduced.
The following design steps should be considered when designing unoccupied setback ventilation
systems:
-
Determine whether the unoccupied period presents an opportunity to reduce
ventilation. This depends on how the lab is used and its condition at the end of
the day. The designer should work with the responsible health and safety
professional and the lab users to establish that their work practices lead to
reduced hazard when the room is unoccupied. Lab processes that continue
unattended or erratic occupancy patterns may eliminate the opportunity.
-
When using an unoccupied setback approach, select the minimum flow rates that
apply during occupied and unoccupied periods. This step still requires making
assumptions. Combining contaminant sensing with setback can allow lower values
for both periods.
-
A trigger approach also needs to be selected to inform the control system when to
switch between occupied and unoccupied settings. This is a common BAS function
implemented in many familiar ways: schedules, occupancy sensors, or manual
switches. It is important to select the trigger or combination of triggers that
work effectively for the space.
-
Consider an indicator for users so that anyone in the room or entering the room
knows that the ventilation system is in the correct mode. Train workers on the
meaning of the airflow indicator and the procedure to follow if the wrong mode
is indicated.
-
Consider connecting room HVAC operation with access control to reduce the chance
of low ventilation rates when a worker is present.
-
Consider coordinating HVAC operation with lighting controls and temperature
setback to maximize the value of occupancy-sensing components.
Laboratory exhaust systems often use constant-speed fans to discharge exhaust air at a
constant velocity to prevent cross contamination with supply air intakes. Alternative
approaches to reduce the considerable energy consumption of exhaust fans include using
taller stacks, and real-time reduction of exhaust exit velocity based on sensing either wind
direction, velocity, or reduced contaminant levels in the exhaust fan plenum.
Room cooling approaches, such as hydronic cooling using local fan-coil units or
noncondensing, chilled radiant ceiling panels, passive chilled beams, or active chilled
beams offer opportunities for energy conservation. These approaches decouple the room
cooling function from the ventilation air requirements, potentially reducing outdoor air
needs, overall HVAC capacity, and reheat energy. Less energy is needed to pump chilled water
than to provide the equivalent amount of airflow required for a given level of cooling. Note
that some form of dew-point sensing and possibly condensation monitoring is recommended
(Rumsey and Weale 2007) for noncondensing hydronic cooling approaches. Chapter 5 of the 2020
ASHRAE Handbook—HVAC Systems and Equipment and Chapter 47 of
this volume offer more information on controlling chilled beams.
Often, offices spaces have recirculating air-handling systems, and laboratory spaces have
separate 100% outdoor-air-handling systems. Significant energy savings can be achieved by
using combined air-handling systems to serve both offices and laboratories: air supplied to
offices can be recirculated, and air supplied to the laboratory spaces exhausted. This
approach, on both a peak and annual basis, reduces the amount of outdoor air that must be
processed and the associated heating and cooling energy.
Energy can often be recovered economically from the exhaust airstream in
laboratory buildings with large quantities of exhaust air. Many energy recovery systems are
available, including rotary air-to-air energy exchangers or heat wheels, coil energy
recovery loops (runaround cycle), twin tower enthalpy recovery loops, heat pipe heat
exchangers, fixed-plate heat exchangers, and thermosiphon heat exchangers, many of which can
be coupled with direct evaporative cooling. Some of these technologies can be combined with
indirect evaporative cooling for further energy recovery. See Chapters 26 and 41 of the 2020
ASHRAE Handbook—HVAC Systems and Equipment for
more
information.
Concerns about using energy recovery devices in laboratory HVAC systems include (1) the
potential for cross-contamination of chemical and biological materials from exhaust air to
the intake airstream, and (2) the potential for corrosion and fouling of devices located in
the exhaust airstream. It is important to understand the potential hazard of the exhaust air
stream and to select the style and materials of the energy recovery equipment appropriately.
The ASHRAE Classification of Laboratory Ventilation Design
Levels guide and ASHRAE Standard 62.1 provide
guidance on the use of different energy recovery systems. Particular caution should be
applied relative to the use of rotary air-to-air heat exchangers for systems that include
fume hood exhaust, which may be precluded. Refer to ASSP/ANSI Standard Z9.5-2022, section 6.4.7, for additional details.
Energy recovery is also possible for hydronic systems associated with HVAC. Rejected heat
from centrifugal chillers can be used to produce low-temperature reheat water. Potential
also exists in plumbing systems, where waste heat from washing operations can be recovered
to heat makeup water.
Laboratories present unique challenges and opportunities for energy efficiency and
sustainable design. Laboratory systems are complex, use significant energy, have health and
life safety implications, need long-term flexibility and adaptability, and handle
potentially hazardous effluent with associated environmental impacts. Therefore, before
implementing energy-efficiency and sustainable-design protocols, the engineer must be aware
of the effects of these measures on the laboratory processes, which affect the safety of the
staff, environment, and scientific procedures.
Several laboratory facilities have achieved high levels of energy efficiency, including
achieving net zero energy and reduced or carbon-neutral goals. Sustainable design features
specific to laboratory facilities include all aspects of design, construction, and
operations. These features include (1) managing air and water effluent on the site; (2)
reducing water used by laboratory processes; (3) rightsizing equipment and improving its
energy efficiency; (4) hazardous material handling; (5) ventilation system enhancements,
including modeling airflow patterns, fume hood testing, and additional safety alarming; (6)
use of renewable energies; (7) low embedded carbon construction materials; and (8)
laboratory-specific opportunities for innovation.
In addition to HVAC systems, electrical systems and chemical handling and storage areas should be
commissioned. Training of technicians, scientists, and maintenance personnel is a critical
aspect of the commissioning process. Users should understand the systems and their operation.
It should be determined early in the design process whether any laboratory systems must comply
with Food and Drug Administration (FDA) regulations because these systems have additional
design, commissioning, and potential validation requirements. Commissioning is defined in Chapter
43; the process is outlined in ASHRAE Guidelines 0 and 1.1,
and further defined in ANSI/ASHRAE/IES Standard 202. Laboratory
commissioning can be more demanding than that described in ASHRAE guidelines and includes
systems that are not associated with other occupancies. Requirements for commissioning should be
clearly understood by all participants, including the contractors and the owner’s
personnel. Roles and responsibilities should be defined, and responsibilities for documenting
results should be established.
Laboratory commissioning starts with the intended use of the laboratory, as described in the
owner’s project requirements (OPR), and should include development of a commissioning
plan, as outlined in the ASHRAE guidelines. The start-up and prefunctional testing of individual
components should come first; after individual components are successfully tested, the entire
system should be functionally tested under a range of anticipated design operating modes. This
requires verification and documentation that the design meets applicable codes and standards and
that it has been constructed in accordance with the design intent and owner’s project
requirements. Most facilities require integrated systems testing to verify that the HVAC system
is properly coordinated with other systems, such as fire alarm or emergency power systems.
Before general commissioning begins, obtain the following data:
-
Owner’s project requirements
-
Basis of design (BOD) that includes the intent of system operation
-
Definition of the use of the laboratory and an understanding of the work being
performed
-
Complete set of the laboratory utility drawings
-
Equipment requirements
-
All start-up and prefunctional test results
For HVAC and associated integrated system commissioning, the following should be verified and
documented:
-
Manufacturer’s requirements for airflow for biological safety cabinets and
laminar flow clean benches have been met.
-
Exhaust system configuration, damper locations, and performance characteristics,
including any required emission equipment, are correct.
-
Approved test and balance report.
-
Control system operates as specified. Controls include fume hood alarm; miscellaneous
safety alarm systems; fume hood and other exhaust airflow regulation; laboratory
pressurization control system; laboratory temperature control system; and main
ventilation unit controls for supply, exhaust, and heat recovery systems. Control
system performance verification should include speed of response, accuracy,
repeatability, turndown, and stability.
-
Desired laboratory pressurization relationships are maintained throughout the
laboratory, including entrances, adjoining areas, air locks, interior rooms, and
hallways. Balancing terminal devices within 10% of design requirements will not
provide adequate results. Additionally, internal pressure relationships can be
affected by airflow around the building. See Chapter 24 of the 2021 ASHRAE Handbook—Fundamentals for more
information.
-
Fume hood containment performance is within specification. ASNI/ASSP Standard Z9.5-2022 provides criteria for this evaluation.
-
Dynamic response of the laboratory’s control system is satisfactory over the
range of anticipated operating modes.
-
System fault tree and failure modes are as specified, including life safety fan
system shutdown impact on proper provisions for egress from the building within
allowable limits of door-opening force requirements
-
Standby electrical power systems function properly.
-
Design noise criterion (NC) levels of occupied spaces have been met.
Training of facilities staff and laboratory occupants should also be considered part of the
commissioning and design process. Training should address both the operation of individual
system components and the overall system.
In laboratories, HVAC systems make up a significant part (often 30 to 50%) of the overall
construction budget. The design criteria and system requirements must be reconciled with the
budget allotment for HVAC early in the planning stages and continually throughout the design
stages to ensure that the project remains within budget.
Every project must be evaluated on both its technical features and its economics. The following
common economic terms are discussed in Chapter 37 and defined
here as follows:
Initial cost: Costs to design,
install, and test an HVAC system such that it is fully operational and suitable for use.
Operating cost: Cost to operate a system (including
energy, maintenance, and component replacements) such that the total system can function until
the end of its normal useful life.
Life-cycle cost: Cost related to the total cost over
the life of the HVAC system, including initial capital cost, considering the time value of
money.
Mechanical and electrical costs related to HVAC systems are commonly assigned a depreciation life
based on current tax policies. This depreciation life may be different from the projected
functional life of the equipment, which is influenced by the quality of the system components
and of the maintenance they receive. Some parts of the system, such as ductwork, could last the
full life of the building. Other components, such as air-handling units, may have a useful life
of 15 to 30 years, depending on their original quality and ongoing maintenance efforts.
Estimated service life of equipment is listed in Chapter 37.
Engineering economics can be used to evaluate life-cycle costs of configuration (utility corridor
versus interstitial space), systems, and major equipment. The user or owner makes a business
decision concerning the quality and reliability of the system and its ongoing operating costs.
The HVAC engineer may be asked to provide an objective analysis of energy, maintenance, and
construction costs, so that an appropriate life-cycle cost analysis can be made. Other
considerations that may be appropriate include economic influences related to the long-term use
of energy and governmental laws and regulations.
Many technical considerations and the great variety of equipment available influence the design
of HVAC systems. Factors affecting design must be well understood to ensure appropriate
comparisons between various systems and to determine the impact on either first or operating
costs.
ASHRAE members can access ASHRAE Journal articles and ASHRAE research project
final reports at technologyportal.ashrae
.org. Articles and reports are also available for purchase by
nonmembers in the online ASHRAE Bookstore at www.ashrae.org/bookstore.
AGS. 2007. Guidelines for
gloveboxes, 3rd ed. American Glovebox Society, Santa Rosa, CA.
Alereza, T., and J. Breen, III. 1984. Estimates of
recommended heat gains due to commercial appliances and equipment (RP-391). ASHRAE Transactions 90(2A):25-58. Paper
KC-2828.
ASHRAE. 1995. Method of testing performance of
laboratory fume hoods. ANSI/ASHRAE Standard 110-1995.
ASHRAE. 2013. Method of testing for room air diffusion.
ANSI/ASHRAE Standard 113-2013.
ASHRAE. 2013. Commissioning process for buildings and
systems. ANSI/ASHRAE/IES Standard 202-2013.
ASHRAE. 2013. The commissioning process. Guideline 0-2013.
ASHRAE. 2007. HVAC&R technical requirements for the
commissioning process. Guideline 1.1.
ASHRAE. 2002. Laboratory design
guide.
ASHRAE. 2018. Classification of
laboratory ventilation design levels. Developed by ASHRAE Technical Committee 9.10,
Laboratory Systems.
ASSP. 2022. Laboratory ventilation. ANSI/ASSP Standard Z9.5. American Society of Safety Engineers, Des Plaines,
IL.
Besch, E. 1975. Animal cage room dry bulb and dew point
temperature differentials. ASHRAE Transactions 81(2):459-458. Paper BO-75-08-3.
Besch, E. 1980. Environmental quality within animal
facilities. Laboratory Animal Science 30(2II):385-406.
Caplan, K., and G. Knutson. 1977. The effect of room air
challenge on the efficiency of laboratory fume hoods (RP-70). ASHRAE
Transactions 83(1):141-156. Paper CH-2438.
Caplan, K., and G. Knutson. 1978. Laboratory fume hoods:
Influence of room air supply. ASHRAE Transactions 84(1):511-537.
Paper AT-78-03-2.
Castro, I.P. 2003. CFD for external aerodynamics in the
built environment. The QNET-CFD Network Newsletter 2(2):4-7.
Code of Federal Regulations. (Annual). Good laboratory practices for nonclinical laboratory studies. 21 CFR
58. U.S. Government Printing Office, Washington, D.C. www.ecfr.gov.
Code of Federal Regulations. (Annual). Current good manufacturing practice in manufacturing, processing, packing, of
holding of drugs. 21 CFR 210. U.S. Government Printing Office, Washington, D.C. www.ecfr.gov.
DHHS. 1999. Biosafety in microbiological and biomedical
laboratories, 4th ed. Publication (CDC) 93-8395. U.S. Department of
Health and Human Services, NIH, Bethesda, MD.
Eagleston, J., Jr. 1984. Aerosol contamination at work.
In The international hospital federation yearbook. Sabrecrown
Publishing, London.
Halitsky, J. 1988. Dispersion of laboratory exhaust gas
by large jets. 81st Annual Meeting of the Air Pollution Control Association, June,
Dallas.
Hessler, J., and A. Moreland. 1984. Design and
management of animal facilities. In Laboratory animal medicine, J.
Fox, B. Cohen, and F. Loew, eds. Academic Press, San Diego, CA.
ICC. 2015. International building
code®. International Code Council, Washington, D.C.
ILAR. 2011. Guide for the care and
use of laboratory animals, 8th ed. Institute for Laboratory Animal Research, National
Academy of Sciences, the National Academies Press, Washington, D.C. www.nap.edu/catalog.php?record_id=12910.
Klein, R., C. King, and A. Kosior. 2009. Laboratory air
quality and room ventilation rates. Journal of Chemical Health and
Safety (9/10).
Maghirang, R.G., G.L. Riskowski, L.L. Christianson, and
P.C. Harrison. 1995. Development of ventilation rates and design information for laboratory
animal facilities—Part I: Field study. ASHRAE Research Project RP-730. ASHRAE Transactions 101(2):208-218. Paper
3898.
Marsh, C.W. 1988. DDC systems for pressurization, fume
hood face velocity and temperature control in variable air volume laboratories. ASHRAE Transactions 94(2):1947-1968. Paper
OT-88-18-2.
Memarzadeh, F. 2000. Ventilation design in animal
research facilities using static microisolators. ASHRAE Transactions
106(1). Paper DA-00-14-1.
Murakami, S., A. Mochida, R. Ooka, S. Kato, and S.
Iizuka. 1996. Numerical prediction of flow around buildings with various turbulence models:
Comparison of k-ε, EVM, ASM, DSM, and LES with wind tunnel
tests. ASHRAE Transactions 102(1):741-753. Paper AT-96-10-1.
Neil, D., and R. Larsen. 1982. How to develop
cost-effective animal room ventilation: Build a mock-up. Laboratory Animal
Science (Jan-Feb): 32-37.
NFPA. 2010. Fire protection guide
for hazardous materials. National Fire Protection Association, Quincy, MA.
NFPA. 2015. Flammable and combustible liquids code.
ANSI/NFPA Standard 30-15. National Fire Protection Association,
Quincy, MA.
NFPA. 2011. Fire protection for laboratories using
chemicals. ANSI/NFPA Standard 45-11. National Fire Protection
Association, Quincy, MA.
NFPA. 2013. Compressed gases and cryogenic fluids code.
NFPA Standard 55-13. National Fire Protection Association, Quincy,
MA.
NFPA. 2013. Explosion protection by deflagration
venting. ANSI/NFPA Standard 68-13. National Fire Protection
Association, Quincy, MA.
NSF. 2012. Biosafety cabinetry: Design, construction,
performance, and field certification. ANSI/NSF Standard 49-12 NSF
International, Ann Arbor, MI.
Petersen, R.L., J. Carter, and M. Ratcliff. 1997. The
influence of architectural screens on exhaust dilution. ASHRAE Research
Project RP-805. Draft Report approved by Technical Committee June 1997.
Rake, B. 1978. Influence of crossdrafts on the
performance of a biological safety cabinet. Applied and Environmental
Microbiology (August):278-283.
Riskowski, G.L., R.G. Maghirang, and W. Wang. 1996.
Development of ventilation rates and design information for laboratory animal
facilities—Part II: Laboratory tests. ASHRAE Research Project RP-730. ASHRAE Transactions 102(2):195-209. Paper
4001.
Rumsey, P., and J. Weale. 2007. Chilled beams in labs:
Eliminating reheat and saving energy on a budget. ASHRAE Journal
49(1):18-25.
Schuyler, G. 2009. The effect of air change rate on
recovery from a spill. In Seminar 26, presented at 2009 ASHRAE Winter Conference,
Chicago.
SEFA. 2010. Laboratory fume hoods
recommended practices. SEFA 1. Scientific Equipment and Furniture Association, Hilton
Head, SC.
Sharp, G.P. 2010. Demand-based control of lab air change
rates. ASHRAE Journal 52(2):30-41.
Stuart, D., M. First, R. Rones, and J. Eagleston. 1983.
Comparison of chemical vapor handling by three types of Class II biological safety cabinets.
Particulate & Microbial Control (March/April).
Wier, R.C. 1983. Toxicology and animal facilities for
research and development. ASHRAE Transactions 89(2B):533-541. Paper DC-83-10-1.
Wilson, D.J., I.C. Fabris, J. Chen, and M.Y. Ackerman.
1998. Adjacent building effects on laboratory fume hood stack design. ASHRAE Research Project
RP-897, Final Report.
Woods, J. 1980. The animal enclosure—A
microenvironment. Laboratory Animal Science 30(2II):407-413.
Woods, J., J. Janssen, P. Morey, and D. Rask. 1987.
Resolution of the “sick” building syndrome. Proceedings of
ASHRAE Conference: Practical Control of Indoor Air Problems, pp. 338-348.
Zhou, Y., and T. Stathopoulos. 1996. Application of
two-layer methods for the evaluation of wind effects on a cubic building. ASHRAE Transactions 102(1):754-764. Paper
AT-96-10-2.
Abramson, B., and T. Tucker. 1988. Recapturing lost
energy. ASHRAE Journal 30(6):50-52.
ACGIH. 2013. Industrial
ventilation: A manual of recommended practice. American Conference of Governmental
Industrial Hygienists, Cincinnati, OH.
Adams, J.B., Jr. 1989. Safety in the chemical
laboratory: Synthesis—Laboratory fume hoods. Journal of Chemical
Education 66(12).
Ahmed, O., and S.A Bradley. 1990. An approach to
determining the required response time for a VAV fume hood control system. ASHRAE Transactions 96(2):337-342. Paper
3421.
Ahmed, O., J.W. Mitchell, and S.A. Klein. 1993. Dynamics
of laboratory pressurization. ASHRAE Transactions 99(2):223-229.
Paper 3713.
Albern, W., F. Darling, and L. Farmer. 1988. Laboratory
fume hood operation. ASHRAE Journal 30(3):26-30.
Anderson, S. 1987. Control techniques for zoned
pressurization. ASHRAE Transactions 93(2B):1123-1139. Paper NT-87-04-1.
Anderson, C.P., and K.M. Cunningham. 1988. HVAC controls
in laboratories—A systems approach. ASHRAE Transactions
94(1):1514-1520. Paper DA-88-19-2.
ASHRAE. 2017. Method of testing general ventilation
air-cleaning devices for removal efficiency by particle size. ANSI/ASHRAE Standard 52.2-2017.
ASHRAE. 2016. Ventilation for acceptable indoor air
quality. ANSI/ASHRAE Standard 62.1-2016.
Barker, K.A., O. Ahmed, and J.A. Parker. 1993. A
methodology to determine laboratory energy consumption and conservation characteristics using an
integrated building automation system. ASHRAE Transactions
99(2):1155-1167. Paper DE-93-21-2.
Bell, G.C., E. Mills, G. Sator, D. Avery, M.
Siminovitch, and M.A. Piette. 1996. A design guide for energy-efficient
research laboratories. LBNL-PUB-777. Lawrence Berkeley National Laboratory, Berkeley,
CA.
Bossert, K.A., and S.M. McGinley. 1994. Design
characteristics of clinical supply laboratories relating to HVAC systems. ASHRAE Transactions 94(100):1655-1659. Paper NO-94-29-1.
Brown, W.K. 1993. An integrated approach to laboratory
energy efficiency. ASHRAE Transactions 99(2):1143-1154. Paper DE-93-21-1.
Carnes, L. 1984. Air-to-air heat recovery systems for
research laboratories. ASHRAE Transactions 90(2A):327. Paper KC-2847.
Coogan, J.J. 1994. Experience with commissioning VAV
laboratories. ASHRAE Transactions 100(1):1635-1640. Paper NO-94-28-2.
Crane, J. 1994. Biological laboratory ventilation and
architectural and mechanical implications
of biological safety cabinet selection, location, and
venting. ASHRAE Transactions 100(1):1257-1265. Paper NO-94-18-1.
Dahan, F. 1986. HVAC systems for chemical and
biochemical laboratories. Heating, Piping and Air Conditioning
(May):125-130.
Davis, S., and R. Benjamin. 1987. VAV with fume hood
exhaust systems. Heating, Piping and Air Conditioning
(August):75-78.
Degenhardt, R., and J. Pfost. 1983. Fume hood system
design and application for medical facilities. ASHRAE Transactions
89(2B):558-570. Paper DC-82-10-4.
DiBeradinis, L., J. Baum, M. First, G. Gatwood, E.
Groden, and A. Seth. 1992. Guidelines for laboratory design: Health and
safety considerations. John Wiley & Sons, Boston.
Dorgan, C.B., C.E. Dorgan, and I.B.D. McIntosh. 2002.
ASHRAE laboratory design guide. ASHRAE.
Doyle, D.L., R.D. Benzuly, and J.M. O’Brien. 1993.
Variable-air-volume retrofit of an industrial research laboratory. ASHRAE
Transactions 99(2): 1168-1180. Paper DE-93-21-3.
EEOC. 2018. Americans with
disabilities act handbook, 5th ed. Equal Employment Opportunity Commission,
Washington, D.C.
FGI. 2018. Guidelines for design
and construction of hospitals; Guidelines for design and construction of outpatient
facilities; Guidelines for design and construction of residential health, care, and support
facilities. Facilities Guidelines Institute, American Society of Healthcare
Engineering, Chicago, IL
Flanherty, R.J., and R. Gracilieri. 1994. Documentation
required for the validation of HVAC systems. ASHRAE Transactions
100(1):1629-1634. Paper NO-94-28-1.
Ghidoni, D.A., and R.L. Jones, Jr. 1994. Methods of
exhausting a BSC to an exhaust system containing a VAV component. ASHRAE
Transactions 100(1):1275-1281. Paper NO-94-18-3.
Halitsky, J. 1989. A jet plume model for short stacks.
APCA Journal 39(6).
Hitchings, D.T., and R.S. Shull 1993. Measuring and
calculating laboratory exhaust diversity—Three case studies. ASHRAE
Transactions 99(2): 1059-1071. Paper DE-93-18-1.
ILAR. 1996. Laboratory animal management—Rodents.
ILAR News 20(3).
Kirkpatrick, A.T., and R. Reither. 1998. Numerical
simulation of laboratory fume hood airflow performance. ASHRAE
Transactions 104(2). Paper TO-98-15-2.
Knutson, G. 1984. Effect of slot position on laboratory
fume hood performance. Heating, Piping and Air Conditioning
(February):93-96.
Knutson, G. 1987. Testing containment laboratory hoods:
A field study. ASHRAE Transactions 93(2B):1801-1812. Paper NT-87-18-1.
Koenigsberg, J., and H. Schaal. 1987. Upgrading existing
fume hood installations. Heating, Piping and Air Conditioning
(October):77-82.
Koenigsberg, J., and E. Seipp. 1988. Laboratory fume
hood—An analysis of this special exhaust system in the post “Knutson-Caplan”
era. ASHRAE Journal 30(2):43-46.
Lacey, D.R. 1994. HVAC for a low-temperature biohazard
facility. ASHRAE Transactions 100(1):1282-1286. Paper NO-94-18-4.
Lentz, M.S., and A.K. Seth. 1989. A procedure for
modeling diversity in laboratory VAV systems. ASHRAE Transactions
95(1):114-120. Paper 3211.
Maghirang, R.G., G.L. Riskowski, P.C. Harrison, H.W.
Gonyou, L. Sebek, and J. McKee. 1994. An individually ventilated caging system for laboratory
rats. ASHRAE Transactions 100(1):913-920. Paper NO-94-10-3.
Maust, J., and R. Rundquist. 1987. Laboratory fume hood
systems—Their use and energy conservation. ASHRAE Transactions
93(2B):1813-1821. Paper NT-87-18-2.
Mikell, W., and F. Fuller. 1988. Safety in the chemical
laboratory: Good hood practices for safe hood operation. Journal of
Chemical Education 65(2).
Moyer, R.C. 1983. Fume hood diversity for reduced energy
consumption. ASHRAE Transactions 89(2B):552-557. Paper DC-83-10-3.
Moyer, R., and J. Dungan. 1987. Turning fume hood
diversity into energy savings. ASHRAE Transactions 93(2B):1822-1834.
Paper NT-87-18-3.
NFPA. 2017. Water spray fixed systems for fire
protection. ANSI/NFPA Standard 15-17. National Fire Protection
Association, Quincy, MA.
NFPA. 1999. Gaseous hydrogen systems at consumer sites.
ANSI/NFPA Standard 50A-99. National Fire Protection Association,
Quincy, MA.
NFPA. 2017. Liquefied petroleum gas code. NFPA Standard 58-17. National Fire Protection Association, Quincy,
MA.
NFPA. 2017. National electrical code. ANSI/NFPA Standard 70-17. National Fire Protection Association, Quincy,
MA.
NFPA. 2018. Installation of air conditioning and
ventilating systems. ANSI/NFPA Standard 90A-18. National Fire
Protection Association, Quincy, MA.
NFPA. 2018. Health care facilities code. ANSI/NFPA Standard 99-18. National Fire Protection Association, Quincy,
MA.
Neuman, V. 1989. Design considerations for laboratory
HVAC system dynamics. ASHRAE Transactions 95(1):121-124. Paper 3212.
Neuman, V. 1989. Disadvantages of auxiliary air fume
hoods. ASHRAE Transactions 95(1):70-75. Paper 3204.
Neuman, V. 1989. Health and safety in laboratory
plumbing. Plumbing Engineering (March):21-24.
Neuman, V., and H. Guven. 1988. Laboratory building HVAC
systems optimization. ASHRAE Transactions 94(2):432-451. Paper 3171.
Neuman, V., and W. Rousseau. 1986. VAV for laboratory
hoods—Design and costs. ASHRAE Transactions 92(1A):330-346.
Paper 2956.
Neuman, V., F. Sajed, and H. Guven. 1988. A comparison
of cooling thermal storage and gas air conditioning for a lab building. ASHRAE Transactions 94(2):452-468. Paper
3172.
NRC. 1989. Biosafety in the
laboratory: Prudent practices for handling and disposal of infectious materials.
National Research Council, National Academy Press, Washington, D.C.
NRC. 2011. Prudent practices in the
laboratory: Handling and management of chemical hazards, updated version. National
Research Council, National Academy Press, Washington, D.C.
OSHA. [Annual] Occupational
exposure to chemicals in laboratories. ppendix VII, 29 CFR 1910.1450. www.ecfr.gov.
Parker, J.A., O. Ahmed, and K.A. Barker. 1993.
Application of building automation system (BAS) in evaluating diversity and other
characteristics of a VAV laboratory. ASHRAE Transactions
99(2):1081-1089. Paper DE-93-18-3.
Peterson, R. 1987. Designing building exhausts to
achieve acceptable concentrations of toxic effluents. ASHRAE
Transactions 93(2):2165-2185. Paper NT-87-25-2.
Peterson, R.L., E.L. Schofer, and D.W. Martin. 1983.
Laboratory air systems—Further testing. ASHRAE Transactions
89(2B):571-596. Paper DC-83-10-5.
Pike, R. 1976. Laboratory-associated infections: Summary
and analysis of 3921 cases. Health Laboratory Science
13(2):105-114.
Rabiah, T.M., and J.W. Wellenbach. 1993. Determining
fume hood diversity factors. ASHRAE Transactions 99(2):1090-1096.
Paper DE-93-18-4.
Richardson, G. 1994. Commissioning of VAV laboratories
and the problems encountered. ASHRAE Transactions 100(1):1641-1645.
Paper NO-94-28-3.
Rizzo, S. 1994. Commissioning of laboratories: A case
study. ASHRAE Transactions 100(1):1646-1652. Paper NO-94-28-4.
Sandru, E. 1996. Evaluation of the laboratory equipment
component of cooling loads. ASHRAE Transactions 102(1):732-737.
Paper AT-96-09-3.
Schuyler, G., and W. Waechter. 1987. Performance of fume
hoods in simulated laboratory conditions. Report 487-1605 by Rowan
Williams Davies & Irwin, Inc., under contract for Health and Welfare Canada.
Schwartz, L. 1994. Heating, ventilating and air
conditioning considerations for pharmaceutical companies. Pharmaceutical
Engineering 14(4).
Sessler, S., and R. Hoover. 1983. Laboratory fume hood
noise. Heating, Piping, and Air Conditioning
(September):124-137.
Simons, C.G. 1991. Specifying the correct biological
safety cabinet. ASHRAE Journal 33(8).
Simons, C.G., and R. Davoodpour. 1994. Design
considerations for laboratory facilities using molecular biology techniques. ASHRAE Transactions 100(1):1266-1274. Paper NO-94-18-2.
Smith, W. 1994. Validating the direct digital control
(DDC) system in a clinical supply laboratory. ASHRAE Transactions
100(1):1669-1675. Paper NO-94-29-3.
Streets, R.A., and B.S.V. Setty. 1983. Energy
conservation in institutional laboratory and fume hood systems. ASHRAE
Transactions 89(2B): 542-551. Paper DC-83-10-2.
Stuart, D., R. Greenier, R. Rumery, and J. Eagleston.
1982. Survey, use, and performance of biological safety cabinets. American
Industrial Hygiene Association Journal 43:265-270.
Varley, J.O. 1993. The measurement of fume hood use
diversity in an industrial laboratory. ASHRAE Transactions
99(2):1072-1080. Paper DE-93-18-2.
Vzdemir, I.B., J.H. Whitelaw, and A.F. Bicen. 1993. Flow
structures and their relevance to passive scalar transport in fume cupboards. Proceedings of the Institution of Mechanical Engineers
207:103-115.
West, D.L. 1978. Assessment of risk in the research
laboratory: A basis for facility design. ASHRAE Transactions
84(1):547-557. Paper AT-78-03-4.
Wilson, D.J. 1983. A design procedure for estimating air
intake contamination from nearby exhaust vents (RP-204). ASHRAE
Transactions 89(2A): 136. Paper DC-2769.
Yoshida, K., H. Hachisu, J.A. Yoshida, and S. Shumiya.
1994. Evaluation of the environmental conditions in a filter-capped cage using a one-way airflow
system. ASHRAE Transactions 100(1):901-905. Paper NO-94-10-1.