Other relevant ASHRAE resources include the following.
There is increased impetus to select energy-efficient systems to limit potential climate impact,
conserve fossil fuel reserves, and avoid fuel poverty. In Europe, the Energy Performance
Directive sets out a strategy for each European country to achieve targets toward this
objective. Other countries have similar schemes. In North America, ASHRAE Standards 90.1 and 189.1 are setting progressive reductions also aimed
zero net energy.
Where natural gas is available, gas-fired condensing boilers are used, with modulating controls
linked to load monitoring such as an outdoor temperature detector.
Heating and cooling applications generally include water-source and air-source heat pumps. In
areas with ample solar radiation, water-source heat pumps may be solar assisted, and/or solar
thermal collectors can be used. Energy-efficient equipment generally has the lowest operating
cost and should be kept simple, an important factor where skilled operating personnel are
unlikely to be available. Most systems allow individual operation and thermostatic control. The
typical system allows individual metering so that most, if not all, of the cooling and heating
costs can be metered directly to the occupant (McClelland 1983). Existing buildings can be
retrofitted with heat flow meters and timers on fan motors for individual metering, and there is
a drive toward providing better real-time energy use data to allow occupants to make changes
that reduce their costs at judicious times.
The water-loop heat pump has a lower operating cost than air-cooled unitary equipment and allows
a degree of heat recovery because the condenser water loop acts to balance energy use when
possible. The lower installed cost encourages its use in mid- and high-rise buildings where
individual dwelling units have floor areas of 800 ft2 or larger. Some
systems incorporate sprinkler piping as the water loop.
The system has a central plant consisting of circulating pumps, heat rejection when there is
surplus heat capacity in the building, and supplementary gas-fired boiler heat input when there
is an overall deficit of heat. The water-loop heat pump is predominantly decentralized;
individual metering allows most of the operating cost to be paid by the occupant. Its life
should be longer than for other unitary systems because most of the mechanical equipment is in
the building and not exposed to outdoor conditions. Also, load on the refrigeration circuit is
not as severe because water temperature is controlled for optimum operation. Operating costs are
low because of the system’s inherent energy conservation. Excess heat may be stored during
the day for the following night, and heat may be transferred from one part of the building to
another.
Although heating is required in many areas during cool weather, cooling could be needed in rooms
having high solar loads. This should be avoided by effective solar shading design. On a mild
day, surplus heat throughout the building is frequently transferred into the hot-water loop by
water-cooled condensers on cooling cycle, so that water temperature rises. The heat remains
stored in the water and can be extracted at night; a water heater is therefore avoided. This
heat storage is improved by the presence of a greater mass of water in the pipe loop; some
systems include a storage tank for this reason, or water tank with phase-change material (PCM)
thermal storage. Because the system is designed to operate during the heating season with water
supplied at a temperature as low as 60°F, the water-loop heat pump lends itself
to solar assist; relatively high solar collector efficiencies result from the low water
temperature.
The installed cost of the water-loop heat pump is higher in very small buildings. In severe cold
climates with prolonged heating seasons, even where natural gas or fossil fuels are available at
reasonable cost, the operating cost advantages of this system may diminish unless heat can be
recovered from some another source, such as solar collectors, geothermal, or internal heat from
a commercial area served by the same system.
To qualify as energy-neutral, a system must have controls that prevent simultaneous operation of
the cooling and heating cycles. Some examples are (1) packaged terminal air conditioners (PTACs)
(through-the-wall units), (2) window units or radiant ceiling panels for cooling combined with
finned or baseboard radiation for heating, (3) unitary air conditioners with an integrated
heating system, (4) fan coils with remote condensing units, (5) variable-air-volume (VAV)
systems with either perimeter radiant panel heating or baseboard heating, and (6)
variable-refrigerant-flow (VRF) systems. For unitary equipment, control may be as simple as a
heat/cool switch. For other types, dead-band thermostatic control may be required.
PTACs are frequently installed to serve one or two rooms in buildings with mostly small,
individual units. In a common two-room arrangement, a supply plenum diverts some of the
conditioned air serving one room into the second, usually smaller, room. Multiple PTAC units
allow additional zoning in dwellings with more rooms. Additional radiation heat is sometimes
needed around the perimeter in cold climates.
Heat for a PTAC may be supplied either by electric resistance heaters or by hot-water or steam
heating coils. Initial costs are lower for a decentralized system using electric resistance
heat. Operating costs are lower for coils heated by combustion fuels. Despite its relatively
inefficient refrigeration circuits, a PTAC’s operating cost is quite reasonable, mostly
because of individual thermostatic control over each machine, which eliminates the use of reheat
while preventing the space from being overheated or overcooled. Also, because equipment is
located in the space being served, little power is devoted to circulating the room air.
Servicing is simple: a defective machine is replaced by a spare chassis and forwarded to a
service organization for repair. Thus, building maintenance can be done by relatively unskilled
personnel.
Noise levels are generally no higher than NC 40, but some units are noisier than others.
Installations near a seacoast should be specially constructed (usually with stainless steel or
special coatings) to avoid accelerated corrosion of aluminum and steel components caused by
salt. In high-rise buildings of more than 12 stories, special care is required, both in design
and construction of outdoor partitions and in installation of air conditioners, to avoid
operating problems associated with leakage (caused by stack effect) around and through the
machines.
Frequently, the least expensive installation is finned or baseboard radiation for heating and
window-type room air conditioners for cooling. The window units are often purchased individually
by the building occupants. This choice offers a reasonable operating cost and is relatively
simple to maintain. However, window units have the shortest equipment life, highest operating
noise level, and poorest distribution of conditioned air of any systems discussed in this
section.
Fan-coils with remote condensing units are used in smaller buildings. Fan-coil units are located
in closets, and the ductwork distributes air to the rooms in the dwelling. Condensing units may
be located on roofs, at ground level, or on balconies.
The heat recovery VRF fan-coil system has one of the lowest operating costs of all dwelling unit
temperature control options, but it typically has a higher initial cost. Special design
considerations must be made for refrigerant management and piping layout, outdoor air design,
and serviceability/maintenance.
Low-capacity residential warm-air furnaces may be used for heating, but with gas- or oil-fired
units, combustion products must be vented. In a one- or two-story structure, it is possible to
use individual chimneys or flue pipes, but a high-rise structure requires a multiple-vent
chimney or a manifold vent. Local codes should be consulted.
Sealed combustion furnaces draw all combustion air from, and discharge flue products through a
windproof vent to, the outdoors. The unit must be located near an outer wall, and exhaust gases
must be directed away from windows and intakes. In one- or two-story structures, outdoor units
mounted on the roof or on a pad at ground level may also be used. All of these heating units can
be obtained with cooling coils, either built-in or add-on. Evaporative-type cooling units are
popular in motels, low-rise apartments, and residences in mild climates.
Desiccant dehumidification should be considered when independent control of temperature and
humidity is required to avoid reheat.
Energy-Inefficient Systems
Energy-inefficient systems allow simultaneous cooling and heating. Examples include two-, three-,
and four-pipe fan coil units, terminal reheat systems, and induction systems. Some units, such
as the four-pipe fan coil, can be controlled so that they are energy-neutral by ensuring that
the two circuits do not simultaneously serve the PTAC. They are primarily used for humidity
control.
Four-pipe systems and two-pipe systems with electric heaters can be designed for complete
temperature and humidity flexibility during summer and intermediate season weather, although
neither provides winter humidity control. Both systems provide full dehumidification and cooling
with chilled water, reserving the other two pipes or an electric coil for space heating or
reheat. The equipment and necessary controls are expensive, and only the four-pipe system, if
equipped with an internal-source heat-recovery design for the warm coil energy, can operate at
low cost. When year-round comfort is essential, four-pipe systems or two-pipe systems with
electric heat should be considered.
A total energy system is an option for any multiple or large housing facility with high
year-round service water heating requirements. Total energy systems are a form of cogeneration
in which all or most electrical and thermal energy needs are met by on-site systems, as
described in Chapter 7 of the 2020 ASHRAE Handbook—HVAC Systems and
Equipment. A detailed load profile must be analyzed to determine the merits
of using
a total energy system. The reliability and safety of the heat-recovery system must also be
considered.
Any of the previously described systems can perform the HVAC function of a total energy system.
The major considerations, as they apply to total energy in choosing an HVAC system, are as
follows:
-
Optimum use must be made of thermal energy recoverable from the prime mover during
all or most operating modes, not just during conditions of peak HVAC demand.
-
Heat recoverable through the heat pump may become less useful because the heat
required during many of its potential operating hours will be recovered from the
prime mover. The additional investment for heat pump or heat recovery cycles may be
more difficult to justify because operating savings are lower.
-
The best application for recovered waste heat is for those services that use only
heat (i.e., service hot water, laundry facilities, and space heating).
Local building codes govern ventilation air quantities for most buildings. Where they do not,
ASHRAE Standards 62.1 and 62.2 should be followed. The quantity of
outdoor air introduced into rooms or corridors is usually slightly in excess of the exhaust
quantities to pressurize the building. To avoid adding load to individual systems, outdoor air
should be treated to conform to indoor air temperature and humidity conditions. In humid
climates, special attention must be given to controlling humidity from outdoor air. Otherwise,
the outdoor air may reach corridor temperature while still retaining a significant amount of
moisture.
In buildings having a centrally controlled exhaust and supply, the system is regulated by a time
clock or a central management system for certain periods of the day. In other cases, the outdoor
air may be reduced or shut off during extremely cold periods, although this practice is not
recommended and may be prohibited by local codes. These factors should be considered when
estimating heating load.
For buildings using exhaust and supply air on a 24 h basis, air-to-air heat recovery devices may
be merited (see Chapter 26 of the 2020 ASHRAE Handbook—HVAC Systems
and Equipment). These devices can reduce energy consumption by capturing 60
to
80% of
the sensible and latent heat extracted from the air source.
Infiltration loads in high-rise buildings without ventilation openings for perimeter units are
not controllable year-round by general building pressurization. When outer walls are pierced to
supply outdoor air to unitary or fan-coil equipment, combined wind and thermal stack-effect
forces create equipment operating problems. These factors must be considered for high-rise
buildings (see Chapter 16 of the 2021 ASHRAE
Handbook—Fundamentals).
Interior public corridors should have tempered supply air with transfer into individual area
units, if necessary, to provide kitchen and toilet makeup air requirements. Transfer louvers
need to be acoustically lined. Corridors, stairwells, and elevators should be pressurized for
fire and smoke control (see Chapter 54).
Kitchen air can be recirculated through hoods with activated charcoal filters rather than
exhausted. Toilet exhaust can be VAV with a damper operated by the light switch. A controlled
source of supplementary heat in each bathroom is recommended to ensure comfort while bathing.
Air-conditioning equipment must be isolated to reduce noise generation or transmission. The
cooling tower or condensing unit must be designed and located to avoid disturbing occupants of
the building or of adjacent buildings.
An important but frequently overlooked load is the heat gain from piping for hot-water services.
Insulation thickness should conform to the latest local energy codes and standards (at minimum).
In large, luxury-type buildings, a central energy or building management system allows
supervision of individual air-conditioning units for operation and maintenance.
Some facilities conserve energy by reducing indoor temperature during the heating season. Such a
strategy should be pursued with caution because it could affect occupant comfort, and,
consequently, the competitiveness of a hotel/motel. Local building codes may also govern
occupancy control and thermostat setback requirements for dwelling units.
Hotel and motel accommodations are usually single guest rooms with a toilet and bath adjacent to a
corridor, flanked on both sides by other guest rooms. The building may be single-story, low-rise, or
high-rise. Multipurpose subsidiary facilities range from stores and offices to ballrooms, dining
rooms, kitchens, lounges, auditoriums, and meeting halls. Luxury motels may be built with similar
facilities. Occasional variations are seen, such as the inclusion of kitchenettes, multiroom suites,
and outer doors to patios and balconies. Hotel classes range from the deluxe hotel to the economy
hotel/motel as outlined in Table 1.
A hotel can be divided into three main areas:
-
Guest rooms
-
Public areas
-
Lobby, atrium, and lounges
-
Ballrooms
-
Meeting rooms
-
Restaurants and dining rooms
-
Stores
-
Swimming pools
-
Health clubs
-
Spas
-
Back-of-the-house (BOTH) areas
The two main areas of use are the guest rooms and the public areas. Maximum comfort in these areas is
critical to success of any hotel. Normally the BOTH spaces are less critical than the remainder of
the hotel with the exception of a few spaces where a controlled environment is required or
recommended.
Air conditioning in hotel rooms should be quiet, easily adjustable, and draft free. It must also
provide ample outdoor air. Because the hotel business is so competitive and space is at a
premium, systems that require little space and have low total owning and operating costs should
be selected.
Design Concepts and Criteria. Table
2 lists design criteria for hotel guest rooms. In addition, the design criteria for
hotel room HVAC services must consider the following factors:
-
Individual and quickly responding temperature control
-
Draft-free air distribution
-
Toilet room exhaust
-
Ventilation (makeup) air supply
-
Humidity control
-
Acceptable noise level
-
Simple controls
-
Reliability
-
Ease of maintenance
-
Operating efficiency
-
Use of space
Load Characteristics. The great diversity in the
design, purpose, and use of hotels and motels makes analysis and load studies very important.
Load diversification is possible because of transient occupancy of guest rooms and the diversity
associated with support facility operation.
The envelope cooling and heating load is dominant because the guest rooms normally have exterior
exposures. Other load sources such as people, lights, appliances, etc. are a relatively small
part of the space sensible and latent loads. The ventilation load can represent up to 15% of the
total cooling load.
Because of the nature of the changing envelope sensible load and the transient occupancy of the
guest room, large fluctuations in the space sensible load in a one-day cycle are common. The
ventilation sensible cooling load can vary from 0 to 100% in a single day, whereas the
ventilation latent load can remain almost constant for the entire day. A low sensible heat ratio
is common in moderate to very humid climates. Usually, the HVAC equipment must only handle
partial or low loads and peak loads rarely occur. For example, in humid climates, introducing
untreated outdoor air directly into the guest room or into the return air plenum of the HVAC
unit operating at part or low load creates a severe high-humidity problem, which is one of the
causes of mold and mildew. The situation is further aggravated when the HVAC unit operates in
on/off cycle during part- or low-load conditions.
Applicable Systems. Most hotels use all-water or
unitary refrigerant-based equipment for guest rooms. All-water systems include
Unitary refrigerant-based systems include
-
Packaged terminal air conditioner or packaged terminal heat pump (with electric heat)
-
Air-to-air heat pump (ductless, split)
-
Water-source heat pump
-
Variable-refrigerant-flow system (heat recovery)
Except for the two-pipe fan-coil, all these systems cool, heat, or dehumidify independently of
any other room and regardless of the season. A two-pipe fan-coil system should be selected only
when economics and design objectives dictate that performance must be compromised. Selection of
a particular system should be based on
Compared to unitary refrigerant-based units, all-water systems offer the following advantages:
-
Reduced total installed cooling capacity due to load diversity
-
Lower operating cost due to a more efficient central cooling plant
-
Lower noise level (compared to PTAC and water-source heat pump)
-
Longer service life
-
Less equipment to be maintained in the occupied space
-
Less water in circulation (compared to water-source heat pump)
-
Smaller pipes and pumps (compared to water-source heat pump)
Unitary refrigerant-based systems offer the following advantages:
-
Lower first cost (typically)
-
Immediate, all year availability of heating and cooling
-
No seasonal changeover required
-
Cooling available without operating a central refrigeration plant
-
Can transfer energy from spaces being cooled to spaces being heated (with
water-source heat pump)
-
Range of circulated water temperature requires no pipe insulation (for water-source
heat pump)
-
Less dependence on a central plant for heating and cooling
-
Simplicity, which results in lower operating and maintenance staff costs
The type of facility, sophistication, and quality desired by the owner/operator, as well as
possible code requirements; typically influence the selection. An economic analysis (life-cycle
cost) is particularly important when selecting the most cost-effective system. Chapter 38 has further
information on economic analysis techniques. Computer software like the NIST Building Life-Cycle
Cost Program (BLCC) performs life-cycle cost analyses quickly and accurately (NIST 2022).
Chapters 2, 5, 13 and 49 of the 2020 ASHRAE
Handbook—HVAC Systems and
Equipment provide additional information about all-water systems and unitary
refrigerant-based systems.
Room fan-coils and room unitary refrigerant-based units are available in many configurations,
including horizontal, vertical, exposed, and concealed. The unit should be located in the guest
room so that it provides excellent air diffusion without creating unpleasant drafts. Air should
not discharge directly over the head of the bed, to keep cold air away from a sleeping guest.
The fan-coil/heat pump unit is most commonly located
-
Above the ceiling in the guest room entry corridor or above the bathroom ceiling
(horizontal air discharge),
-
On the room’s perimeter wall (vertical air discharge), or
-
In a floor-to-ceiling enclosed chase (horizontal air discharge).
Locating the unit above the entry corridor is preferred because air can flow directly along the
ceiling and the unit is relatively accessible for maintenance (see Figures
1 and 2).
Most units are designed for free-air discharge. The supply air grille should be selected
according to the manufacturer’s recommendations for noise and air diffusion. Also, airflow
should not interfere with the room drapes or other wall treatment.
Other factors that should be considered include
-
Sound levels at all operating modes, particularly with units that cycle on and off
-
Adequately sized return air grille
-
Access for maintenance, repair, and filter replacement
Ventilation (makeup) supply and exhaust rates must meet local code requirements. Ventilation
rates vary and the load imposed by ventilation must be considered.
Providing conditioned ventilation air directly to the guest room is the preferred approach.
Normally, outdoor air is conditioned in a primary makeup air unit and distributed by a primary
air duct to every guest room. This approach controls the supply air conditions, ensures
satisfactory room conditions and room air balance (room pressurization) even during part- or
no-load conditions, and controls mold and mildew.
Other ventilation techniques are to
-
Transfer conditioned ventilation air from the corridor to each guest room. This
approach controls ventilation air conditions better; however, the air balance
(makeup versus exhaust) in the guest room may be compromised. This approach is
prohibited under many code jurisdictions.
-
Introduce unconditioned outdoor air directly to the air-conditioning unit’s
return air plenum (perimeter wall installations). This approach can cause mold and
mildew and should be avoided. During periods of part or low load, which occur during
most of the cooling season, the thermostatically controlled air conditioner does not
adequately condition the constant flow of outdoor air because the cooling coil valve
closes and/or the compressor cycles off. As a result, humidity in the room
increases. Also, when the air conditioner’s fan is off, outdoor air
infiltrates through the ventilation opening and again elevates the room’s
humidity level.
Guest-room HVAC units are normally controlled by a room thermostat. Thermostats for fan-coils
normally control valves in two-pipe, four-pipe, and two-pipe chilled-water/electric heat
systems. Control should include dead-band operation to separate the heating and cooling set
points. Two-pipe system control valves are normally equipped with automatic changeover, which
senses the water temperature and changes operation from heating to cooling. The thermostat may
provide modulation or two-position control of the water control valve. The fan can be adjusted
to high, medium, or low speed on most units.
Occupancy sensors, or key-card control, of the HVAC units and partial electrical load are
becoming more common, and are required by many code jurisdictions. Special design considerations
should be evaluated to maintain ventilation rates and prevent high humidity levels during
unoccupied periods.
Typical unitary refrigerant-based units have a push button off/ fan/heat/cool selector switch,
adjustable thermostat, and fan cycle switch. Heat pumps include a defrost cycle to remove ice
from the outdoor coil. Chapter 48 has more
information on control for fan coils.
Public areas are generally the showcase of a hotel. Special attention must be paid to
incorporating a satisfactory system into the interior design. Locations of supply diffusers,
grilles, air outlets, etc. must be coordinated to satisfy the architect. The HVAC designer must
pay attention to access doors for servicing fire dampers, smoke dampers, volume dampers, valves,
and variable-air-volume (VAV) terminals.
Design Concepts and Criteria. Design criteria for
public areas are given in Table 2. In addition, the following
design criteria must be considered:
-
Year-round availability of heating and cooling
-
Independent unit for each main public area
-
Economical and satisfactory operation at part- and low-load conditions
-
Coordination with adjacent back-of-the-house (BOTH) areas to ensure proper air
pressurization (e.g., restaurants, kitchens)
Load Characteristics. The hours of use vary widely
with each public area. In many cases, the load is from internal sources from people, lights, and
equipment. The main lobby normally is operational 24 hours per day. Areas like restaurants,
meeting rooms, and retail areas have intermittent use, so the load changes frequently. HVAC
systems that respond effectively and economically must be selected for these areas.
Applicable Systems. All-air systems, single-duct
constant-volume, and VAV are most frequently used for public areas. Chapter 4 of the 2020 ASHRAE
Handbook—HVAC Systems and Equipment has more
information
on these systems, and Chapter 48 in this
volume covers control for all-air VAV systems.
Back-of-the-House (BOTH) Areas
The BOTH area normally includes service or support areas. Climatic conditions in these areas are
typically less critical than in the remainder of the hotel. However, a few spaces require
special attention.
Design Concepts and Criteria. Recommended design
criteria for several areas in the BOTH are shown in Table 3.
Humidity, Mildew, Moisture Control, and IAQ. Humidity control is
critical to ensure satisfactory air quality and to minimize costly mold and mildew problems in
hotels. Moisture can be introduced and infiltrate into the guest rooms in the following ways:
-
Unconditioned ventilation air is delivered directly into the guest room through the
HVAC unit. At part or low sensible loads or in situations where the unit cycles on
and off, the air-conditioning unit will not dehumidify the air adequately to remove
the excess moisture.
-
Outdoor humid air infiltrates through openings, cracks, gaps. shafts, etc. because of
insufficient space pressurization.
-
Moisture migrates through external walls and building elements because of a vapor
pressure differential.
-
An internal latent load or moisture is generated.
Removing water vapor from the air is the most feasible way to control mold and mildew,
particularly when the problem spreads to walls and carpeting. Good moisture control can be
achieved by applying the following techniques:
-
Introduce adequately dried ventilation (makeup) air (i.e., with a dew point of
53°F [60 grains/lb of dry air] or less) directly to
the guest room.
-
Maintain slightly positive pressure in the guest room to minimize infiltration of hot
and humid air into the room. Before a new HVAC system is accepted by the owner, a
certified air balance contractor should be engaged to demonstrate that the volume of
dry makeup air exceeds the volume of exhaust air. As the building ages, it is
important to maintain this slight positive pressure; otherwise, humid air that
infiltrates into the building cavities will be absorbed regardless of how dry the
room is maintained (Banks 1992).
-
Provide additional dehumidification capability to the ventilation (makeup air) by
dehumidifying the air to a lower level than the desired space humidity ratio. For
example, introducing 60 cfm of makeup air at 55 gr/lb can
provide approximately 400 Btu/h of internal latent cooling (assuming
65 gr/lb is a desirable space humidity ratio).
-
Allow air conditioning to operate in unoccupied rooms instead of turning the units
off, especially in humid areas.
-
Improve the room envelope by increasing its vapor and infiltration resistance.
The third method allows ventilation air to handle part of the internal latent load (people,
internal moisture generation, and moisture migration from external walls and building elements).
In addition, this method can separate the internal sensible cooling, internal latent cooling,
and ventilation loads. Independent ventilation/ dehumidification allows room pressurization and
space humidity control regardless of the mode of operation or magnitude of the air-conditioning
load. Desiccant dehumidifiers can be retrofitted to solve existing moisture problems.
Dedicated Outdoor Air Systems (DOAS). DOAS air
units are designed to condition ventilation air introduced into a space and to replace air
exhausted from the building. The geographic location and class of the hotel dictate the
functions of the makeup air units, which may filter, heat, cool, humidify, and/or dehumidify the
ventilation air. Makeup air may be treated directly or by air-to-air heat recovery (sensible or
combined sensible and latent) and other heat recovery techniques. Equipment to condition the air
by air-to-air heat recovery and final heating, cooling, humidification, and/or dehumidification
is also available.
Chapter 14 of the 2021 ASHRAE
Handbook—Fundamentals provides
design weather data for ventilation (full data tables for over 9000 locations worldwide are
included with the PDF download of that chapter and on Handbook Online). Analyzing and selecting
the proper makeup unit for the full range of air conditions are critical for efficient and
sufficient all-year operation. Air-to-air heat recovery helps stabilize entering conditions,
which helps provide efficient and stable operation. However, heat recovery may not al-ways be
feasible. Often, exhaust air comes from many individual stacks. In this case, the cost of
combining many exhausts for heat recovery may not be warranted.
Typical design criteria for ventilation (makeup) air units are listed in Table 4.
Makeup air units can be stand-alone packaged (unitary) or integrated in an air handler. A typical
makeup air unit usually has the following features:
Humidification should be considered for all cold climates. The HVAC designer must also consider
avoiding coil freeze up in water based systems.
Chapters 26 and 28 of the 2020 ASHRAE
Handbook—HVAC Systems and Equipment provide information
about air-to-air energy recovery and makeup air units, respectively.
Hotel location, environmental quality desired by the owner, and design sophistication determine
the system selected. For example, in locations with cool summers, dehumidification with
mechanical cooling only is satisfactory. For humid locations or where enhanced dehumidification
is required, a desiccant-based unit can provide lower supply air humidity, to help prevent mold
and mildew and provide internal latent cooling.
Central Mechanical Plant. Designing a
reliable and energy-efficient mechanical plant is essential to ensuring a profitable hotel. The
chiller plant must operate efficiently at part-load conditions. Some redundancy should be
considered in case of equipment failure. Designs often include spare critical equipment where
spare parts and qualified service are not readily available. Chillers with multistage
compressors should be considered because they provide partial cooling during failures and
enhance part-load operation. When using two chillers, each should provide at least 60% of the
total load. Combinations of three chillers providing 40% each or four chillers providing 30%
each are better for tracking part-load conditions. Cooling towers, pumps, etc., can be sized in
a similar manner.
The heating plant should be designed to accommodate the winter heating load and could provide
domestic hot water, swimming pool heating, and service to kitchens and laundries as well. The
type of fuel used depends on location, availability, use, and cost.
Multipurpose boiler design for the kitchen and laundry should offer redundancy, effective
part-load handling, and efficient operation during summer, when the HVAC heating load does not
exist.
In areas with mild winters, a two-pipe system or an air-to-water heat pump chiller/heater can be
considered. In any event, the HVAC designer must understand the need for all-year cooling and
heating availability in the public areas. In this case, a combination of air-to-water heat pump,
chiller/heater for the guest rooms, and independent heat pumps for public areas can be
installed.
Acoustics and Noise
Control. The sound level in guest room and public areas is a major
design element. Both the level and constancy of noise generated by the HVAC are of concern.
Normally, packaged terminal air conditioners/heat pumps and water-source heat pumps are noisier
due to the compressor. Some equipment, however, has extra sound insulation, which reduces the
noise significantly.
Lowering fan speed, which is usually acceptable, can reduce fan noise levels. On/off cycling of
the fan and compressor can be objectionable, even if the generated noise is low. Temperature
control by cycling the fan only (no flow control valve) should not be used.
Another source of noise is sound that transfers between guest rooms through the toilet exhaust
duct. Internal duct lining and sound attenuators are commonly used to minimize this problem.
Noise from equipment located on the roof or in a mechanical room located next to a guest room
should be avoided. Proper selection of vibration isolators should prevent vibration
transmission. In critical cases, an acoustician must be consulted.
New Technology in Hotels. Modern hotels are
implementing techniques to enhance comfort and convenience. For example, the telephone, radio,
TV, communications, lighting, and air-conditioning unit can be integrated into one control
system. Occupancy sensors conserve energy by resetting the temperature control when the room is
occupied or when guests leave. As soon as a new guest checks in at the front desk, the room
temperature is automatically reset. But even with this improved technology, it is important to
remember that temperature reset may create humidity problems.