No one established procedure applies to all systems. The bibliography lists sources of additional information.
Air Testing and Balancing
Inclined Manometer. The inclined manometer is made of a single tube, inclined (usually 10:1 slope), to enlarge the reading. Alcohol or special oils are normally used in place of water. Such oils have a lower specific gravity than water which serves to further enlarge the reading. Manometers using these fluids have scales calibrated in in. of water corresponding to the pressure indicated on the oil of a known specific gravity. Recommended for use with pitot tubes or static pressure probes.
The combination vertical-inclined manometer is constructed of an inclined fluid column with a scale of 0 to 1.0 or 2.0 in. of water connected to a vertical fluid column with scales of 5 or 10 in. of water. Recommended for use with pitot tubes or static pressure probes.
Limitations:
-
Not to be used to measure air velocities less than 600 fpm. A micromanometer, hook gage, or another sensitive instrument should be used to decrease the uncertainty of measurements between 450 and 600 fpm.
-
The manometer must be carefully leveled during use and held in a rigid position so that when zero pressure is registered, the end of the meniscus arc of the fluid exactly bisects the center of the zero line.
-
Calibration is required. The manometer must be verified by comparison to a recently calibrated reference instrument. If the reading on the instrument to be verified is not within 2% of the reading on the reference instrument, then the manometer must be calibrated by an ISO-certified air speed laboratory before it can be used.
Pitot Tube. A pitot tube, used in conjunction with a manometer, provides a basic method of determining the air velocity within a duct. The typical pitot tube is of a double concentric tube construction, consisting of an 1/8 in. OD inner tube concentrically located inside a 5/16 in. OD outer tube that measures total pressure. The outer static tube has eight equally spaced 0.04 in. diameter holes around the circumference of the outer tube, located 2.5 in. back from the nose or open end of the pitot tube tip. At the base (tube connection) end, the inner tube is open ended, as is the head. The outer tube has a side outlet tube connector perpendicular to the outer tube, directly parallel with and in the same direction as the head end of the pitot static tube. Recommended for measuring an airstream’s
-
Total pressure, by connecting the inner tube outlet connector to one side of a manometer or draft gage
-
Static pressure, by connecting the outer tube side outlet connector to one side of a manometer or draft gage
-
Velocity pressure, by connecting both the inner and outer tube connectors to opposite sides of a manometer or draft gage.
When used with a manometer or micromanometer, the pitot tube is very reliable and rugged. Its use as a direct measurement tool is preferred over many other methods for the field measurement of air velocity, system total air, outdoor air, return air quantities, fan static pressure, fan total pressure, and fan outlet velocity pressures where such measured quantities may be required and within the range or capabilities of the instrument.
Instruments that may be used with the pitot static tube include the following:
-
Micromanometer: very low pressure differential, less than 1 in. of water
-
Inclined manometer: moderate pressure differential, 0 to 10 in. of water
-
U-tube manometer: medium pressure differential, greater than 10 in. of water
-
Diaphragm-type pressure gage
-
Electronic differential pressure meters
Limitations:
-
Pitot tubes should not be used to measure velocities below 450 fpm, regardless of the electronic sensors used to identify differentials in pressure, because of the inherent high uncertainties in pitot measurement.
-
Accuracy depends on uniformity of flow and completeness of traverse.
-
A reasonably large space is required adjacent to duct penetrations for maneuvering the instrument.
-
Care is needed to avoid pinching or puncturing instrument tubing.
-
Because of the distance between the impact and static holes, the pitot static tube cannot be used to measure flow through orifice-type openings.
-
Pitot static tubes are susceptible to plugging in airstreams with heavy dust or moisture loadings.
-
Acceptance of the standard pitot static tube rests in its accuracy on the correct determination of the static pressure. The total pressure is not affected by yaw or angularity up to approximately 8° on either side of parallel flow. The static pressure, however, is extremely sensitive to direction of flow.
Accuracy of field measurement. Rigorous error analysis shows that flow rate determinations by the pitot static tube and manometer combination method can range from 5 to 10% error. Experience shows that qualified technicians can obtain measurements within 5 and 10% accuracy of actual flow under good field conditions. It has also been determined that suitable traverse conditions do not always exist, and measurements can then exceed a ±10% error rate.
Chronometric Tachometer. The chronometric tachometer is a hand-held instrument that combines an accurate timer and a revolution counter. After the instrument tip is placed on the rotating shaft, pushing the stopwatch button simultaneously activates the counter and the stopwatch. After the timer has run for either 3 or 6 s, the instrument stops counting revolutions even though it is still in contact with the rotating shaft. The scale is calibrated to give readings directly in rpm. Instrument accuracy is within ±0.5% of full scale. Hand tachometers (e.g., dial face [Eddy current], solid-state with digital readout) can produce instantaneous rpm measurement readings, with accuracy within ±1% of full scale. Tachometers are recommended for determining the speed of any shaft having a countersunk end.
Limitations:
-
The shaft end must be accessible and countersunk.
-
Calibration is required. Readings must be verified with a recently calibrated chronometric tachometer on each project. If the reading is not within ±2% of the recently calibrated tachometer, have the instrument recalibrated by a qualified testing lab.
Accuracy of field measurements. Accuracy is within one-half of a scale division mark.
Clamp-on Volt-Ammeter. This instrument has trigger-operated, clamp-on transformer jaws that allow current readings without interrupting electrical service. Most volt-ammeters have several scale ranges, in amperes and volts. Two voltage test leads are furnished that may be quick-connected to the bottom of the volt-ammeter opposite the end used for measuring current. Some models have a built-in ohmmeter. Instrument accuracy is within ±3% of full scale. Recommended for measuring operating voltages and currents of electric motors and of electric resistance heating coils.
Limitations:
-
The proper range must be selected. It is desirable for readings to occur about mid-scale. When in doubt, begin with the highest range for both voltage and current scales. Accuracy of reading low currents can be improved by looping the conductor wire around the jaw once and dividing the current reading by 2.
-
Depending on conditions at the point of measurement and the size of the volt-ammeter, access for measurement may be restrictive. Caution is required, particularly when taking measurements under confined conditions.
-
To avoid distortion of current readings by other fields, move the meter along the wire to verify that the reading remains constant.
-
Calibration is required. Readings must be verified with a recently calibrated clamp-on volt-ammeter on each project. If the reading is not within ±2% of the recently calibrated instrument, have the instrument recalibrated by a qualified testing lab.
Accuracy of field measurements. Accuracy is ±3% of full scale.
Anemometers. There are several types of anemometers. The deflecting vane anemometer consists of a pivoted vane enclosed in a case. As it passes through the anemometer, air exerts a pressure on the vane. Movement of the vane is resisted by a hairspring. The instrument gives instantaneous readings of directional velocities on an indicating scale, and can be supplied with various remote- and direct-connected measuring tips (jets). Recommended for measuring air quantities through both supply and return air terminals using the proper air terminal factor Ak (effective area) for airflow calculation, as well as for indicating low velocities (100 to 300 fpm) where the instrument case itself with the appropriate probe attached is placed in the airstream.
Limitations:
-
It should not be used in extremely hot, cold, or contaminated air.
-
It is affected by static electricity.
-
The instrument duct probe is sensitive to presence and proximity of duct walls, and tends to read high on the suction side and low on the discharge side of a fan.
-
Accuracy is affected by position.
-
Calibration is required. Readings must be verified with a recently calibrated deflecting vane anemometer on each project. If the reading is not within ±2% of the recently calibrated instrument, have the instrument recalibrated by a qualified testing lab.
Accuracy of field measurements. Accuracy is within ±10% when the instrument is calibrated and used in accordance with the manufacturers’ recommendations. Air inlet and outlet device flow Ak factors are a function of duct and damper conditions, which affect velocity immediately before the device. Use under conditions not identical to the manufacturers’ test conditions produces measurement error. The instrument must be calibrated in the field for correction factor by pitot tube traverse within the limitations of the system.
The revolving vane or propeller anemometer can be either mechanical or direct-reading digital. For the mechanical type, a mechanical propeller or revolving vane anemometer consists of a light wind-driven wheel connected through a gear train to a set of recording dials that read the linear feet of air passing through the wheel in a measured length of time. The instrument is made in various sizes, but 3, 4, and 5 in. are the most common. Each instrument requires individual calibration. The required instrument accuracy of calibration is 1 to 3% of scale (using a corrective chart). Recommended for measuring supply, return, and exhaust air quantities at air inlets and outlets, as well as air quantities at the faces of return air dampers or openings, total air across the filter or coil face areas, etc.
The direct-reading digital type differs from the mechanical type mainly in that it uses a powered electronic circuit to convert a pulse generated by the rotating vane into a small electric current to give a meter reading calibrated directly in air velocity units. Generally, these instruments have microprocessor software to compensate for any nonlinearity. Recommended for measuring supply, return, and exhaust air quantities at air inlets and outlets; air quantities at the faces of return air dampers or openings; total air across the filter or coil face areas, etc.
Limitations:
-
For mechanical anemometers, each reading must be corrected by the instrument’s calibration chart.
-
The air inlet or outlet device manufacturers’ specified flow Ak factor for the device must be used in computing air quantities.
-
Total inlet area of the instrument must be in the measured airstream.
-
It is not suitable for measurement in ducts.
-
It is fragile and cannot be used in dusty or corrosive air.
-
The instrument has a turbine wheel of very low inertia, so be cautious regarding reliability of readings in nonuniform, turbulent, or stratified airstreams. This is likely to occur downstream of dampers, face-and-bypass coils, or any device that causes turbulence in the airstream being measured.
-
The mechanical anemometer is not direct reading and must be timed manually.
-
At low velocities, the instrument’s friction drag is considerable. To compensate, a gear is commonly used. Thus, the correction is additive at the lower range and subtractive at the upper range, with the least correction in the middle of the range. Most of these instruments are not sensitive enough for use below 200 fpm, although ball-bearing models claim ranges down to 30 fpm. The useful range is from 200 to 2000 fpm.
-
Calibration is required. Readings must be verified with a recently calibrated instrument on each project. If the reading is not within ±2% of the recently calibrated instrument, have the anemometer recalibrated by a qualified testing lab.
Accuracy of field measurements:
-
Smooth flow: ±5% of reading above 200 fpm. Not recommended for velocities below 200 fpm.
-
Nonuniform flow: ±30% (or greater, for direct-reading digital type).
-
The instrument must be calibrated in the field for a correction factor by pitot tube traverse within the limitations of the system.
Operation of the thermal anemometer, which can be either single point or omnidirectional, depends on the fact that the resistance of a heated element changes with its temperature. As airflows over the element in the probe, the temperature of the element changes from its temperature in still air. The resistance change is indicated as a velocity on the indicating scale of the instrument. Instruments are available using a heated thermocouple, heated thermistor, or a heated wire. They have similar characteristics regarding uses, limitations, and accuracy. Some instruments are also provided with temperature scales that can be used by setting the proper selector button. Others can measure static pressure with provided accessories. Recommended uses include measuring the following:
-
Very low air velocities, such as room air currents and airflow in hoods (10 to 600 fpm)
-
Air movement at grilles and diffusers
-
Velocity measurements in ducts
Limitations:
-
The instrument probe is very directional for velocity readings and must be located at the exact location and orientation on the air inlet or outlet device, as specified by the air device manufacturer.
-
Probes are subject to fouling by dust and corrosive air.
-
The instrument probe must be used in the direction of calibration.
-
In general, these instruments should not be used in flammable or explosive atmosphere. However, there are special thermal anemometer probes available for use in these environments.
-
Calibration is required. Readings must be verified with a recently calibrated instrument on each project. If the reading is not within ±2% of the recently calibrated instrument, have the anemometer recalibrated by a qualified testing lab.
Accuracy of field measurements. Accuracy is ±3% above 100 fpm. The instrument must be calibrated in the field for correction factor by pitot tube traverse within the limitations of the system.
Thermometers. Dial thermometers are of two general types: stem and flexible capillary. Their dial heads can be 1 3/4 to 5 in., with stainless steel encapsulated temperature sensing elements. Hermetically sealed, they are rust-, dust-, and leakproof and are actuated by sensitive bimetallic helix coils. Some can be field calibrated. Sensing elements range in length from 2 1/2 to 24 in. and are available in many temperature ranges with or without thermometer wells.
Small dial thermometers usually use a bimetallic temperature-sensing element in the stem. Temperature changes cause a change in the twist of the element, and this movement is transmitted to the pointer by a mechanical linkage.
The flexible capillary dial thermometer has a rather large temperature-sensing bulb connected to the instrument with a capillary tube. The instrument contains a Bourdon tube, the same as in pressure gages. The temperature sensing system, consisting of the bulb, capillary tube, and Bourdon tube, is charged with either liquid or gas. Temperature changes at the bulb cause the contained liquid or gas to expand or contract, resulting in changes in the pressure exerted within the Bourdon tube. This causes the pointer to move over a graduated scale as in a pressure gage, except that the thermometer dial is graduated in degrees. The advantage of this type is that it can be used to read temperature in a remote location. In using a dial thermometer, the stem or bulb must be immersed a sufficient distance to allow this part of the thermometer to reach the temperature being measured.
Recommended uses include checking both air and water temperature in ducts and pipe thermometer wells.
Limitations:
-
Dial thermometers have a relatively long time lag, so enough time must be allowed for the thermometer to reach equilibrium and the pointer to come to rest.
-
Calibration is required. Readings must be verified with a recently calibrated instrument on each project. If the reading is not within ±2% of the recently calibrated instrument, have the dial thermometer recalibrated by a qualified testing lab.
Accuracy of field measurements. Accuracy is within one-half of a scale division mark.
There are four basic types of digital electronic thermometers: thermocouple, thermistor, resistance temperature detector (RTD), and diode sensors. They consist of a portable, handheld, battery-powered, digital thermometer connected by a short cable to various interchangeable probes that are designed for sensing the temperature of air or other gases, immersion in liquids, or contact with a solid surface. Some instruments have a calibration reference, which allows calibrating out offsets introduced by mechanical shocks, ambient temperature variations, or component drift. Some instruments can switch between I-P and SI units and between resolutions of 0.1 and 1.0. Response times are 1 to 10 s for liquids and solids, and 5 to 50 s for gases. Instrument accuracy is ±0.5°F where the range is below 700°F and ±1.5°F for broader ranges. The lower-range instruments should be used unless the expected measurements will be out of their range.
Recommended uses include all TAB temperature measurements, including air and other gases, liquids, and surfaces of pipes and other components with the appropriate probe. The manufacturers’ directions must be followed regarding proper use of probe and maximum allowable temperature for the probe and or thermometer. Equipment is available to measure from −380 to 2250°F. A common range is +14 to +248°F.
Limitations:
-
Batteries must be recharged or changed when required.
-
In piping applications, it should be remembered that the surface temperature of the pipe is not equal to the fluid temperature and that a relative comparison is more reliable than an absolute reliance on readings at a single circuit or terminal unit.
-
Be sure measurement is taken at least as long as response time.
-
Calibration is required. Readings must be verified with a recently calibrated instrument on each project. If the reading is not within ±2% of the recently calibrated instrument, have the digital electronic thermometer recalibrated by a qualified testing lab.
Accuracy of field measurements. When properly used, the instrument accuracy shall be attainable in the field.
Other Air or Fluid System Measurements
Revolution Counter (Odometer) and Timing Device. The revolution counter is a small handheld counting device that is pressed to the center of a rotating shaft for a period of 30 to 60 s. Reasonable accuracy can be obtained by using a good watch with a sweep second hand or a digital watch if a stopwatch is not available. Recommended use is for determining shaft speed on any shaft having an accessible shaft end with a countersink.
Limitations:
-
Not to be used on flat-ended shafts without the correct adaptor. Otherwise, slip and inaccurate readings are inevitable.
-
Some types have a clutch engagement in which a certain amount of force is required to activate the recording mechanism.
-
Must be used and coordinated with an accurate timepiece.
-
Normally cannot be reset to zero; the shaft speed measured is the difference between the initial and final instrument readings divided by the time interval.
-
Calibration is required. Readings must be verified with a recently calibrated instrument on each project. If the reading is not within ±2% of the recently calibrated instrument, have the odometer recalibrated by a qualified testing lab.
Accuracy of field measurement. Accuracy is ±2%, when used properly.
Electronic Tachometer (Stroboscope and Photoelectric). The stroboscope has a controlled high-speed electronic flashing light whose frequency is electronically controlled and adjustable. When the frequency of the flashing light is adjusted to equal the frequency of the rotating machine, the machine appears to stand still. This unit need not be in contact with the machine during use. Instrument accuracy is generally within 1.5% of the indicated value, and within 1% if a magnetic pickup is used.
The solid-state photoelectric tachometer is an optional instrument that is pointed at the device to be measured and the revolution speed is directly read on the dial face. A reflective paint or material must be spotted on the rotating device; this spot is counted and electronically integrated over time to give an instantaneous reading. The instruments usually have several ranges, and no electrical or physical contact with the device is necessary. Accuracy is within ±1% of the dial scale reading when properly calibrated.
Recommended use is for measuring rotational speeds when instrument contact with the rotating equipment is not feasible.
Limitations:
-
Care must be taken to avoid reading multiples of the actual rpm when using the stroboscope. Readings must be started at the lower end of the scale.
-
Calibration is required. Readings must be verified with a recently calibrated instrument on each project. If the reading is not within ±2% of the recently calibrated instrument, have the tachometer recalibrated by a qualified testing lab.
Accuracy of field measurements. Accuracy is within one-half of a scale division.
Dual-Function Tachometer. This instrument provides both optical and contact measurements of rotation and linear motions. Many allow a choice of ranges, depending on the application. A digital display always indicates the unit of measurement to identify the operating range. A memory button may be used to recall the last, maximum, minimum, and average readings. Compact size and light weight make for easy operation. Recommended use is for measuring rotation speeds by direct contact or by counting the speed of a reflective mark.
Limitations:
Accuracy of field measurements. Accuracy is within one-half of a scale division.
Low-Density Fluid U-Tube Manometer. The manometer is a simple, useful way to measure partial vacuum and pressure. In its simplest form, it consists of a U-shaped glass tube partially filled with liquid; a difference in height of the two fluid columns denotes a pressure difference in the two legs. Recommended uses include measuring pressure drops above 1.0 in. of water across filters, coils, eliminators, fans, grilles, and duct sections; and measuring low manifold gas pressures.
Limitations:
-
To ensure accuracy, manometer tubes must be chemically cleaned and filled with the correct fluid.
-
U-tube manometers cannot be used for readings under 1.0 in. of water.
-
Reading accuracy depends on the user’s ability to gage the level in each tube simultaneously; this is especially troublesome if surges occur in the flow being measured.
Diaphragm-Type Differential Pressure Gage. A dry diaphragm-operated differential pressure gage that uses a calibrated spring-loaded horseshoe magnet lever operated from the differential pressure on the diaphragm, causing rotation of a highly magnetic permeable helix that positions a pointer on the pressure scale. The pressure gage is operated by magnetic field linkage only, so it is extremely sensitive and accurate; its construction design makes it resistant to shock and vibration. The helix rotates on antishock-mounted sapphire bearings. A zero-calibration screw is located on the plastic cover. Common ranges are 0 to 0.5, 1.0, or 5.0 in. of water. There are approximately 30 available pressure ranges. The minimum accuracy of the instrument is ±2% of full dial range. Recommended for use with pitot tube or with static probe, or with specially constructed induction unit primary air total pressure measuring tip for primary air distribution balancing on high-pressure induction systems.
Limitations:
-
Should not be used in preference to liquid or electronic manometer.
-
Readings should be made in mid-scale of range.
-
Should not be mounted on a vibrating surface.
-
Should be held in same position as when zeroed
-
Should be checked against a known pressure source with each use
-
Calibration is required. Readings must be verified with a recently calibrated instrument on each project. If the reading is not within ±2% of the recently calibrated instrument, have the pressure gage recalibrated by a qualified testing lab.
Smoke Devices. These devices are generally used in special studies of airflow and duct leakage. Candles are available in various sizes and durations of burning time. The chemical element in the smoke is zinc chloride.
Sticks are activated by crushing the end of the device, releasing a smoke stream approximately double that of a cigarette. Guns generally use a chemical that readily combines with atmospheric moisture. A cartridge produces 500 to 1000 puffs of smoke, or releases the same quantity in a steady stream. Borazine guns emit dense white clouds of smoke that tend to remain suspended in air for some time. A valve adjustment regulates the discharge.
Recommended uses include determining the direction and observing the velocity and pattern of airflow in room studies, hoods, filters, etc. Discharge patterns from exhaust systems, driers, hoods, and stacks can be identified.
Limitations:
-
Some smoke devices may be toxic, and protective apparatus may be required. After extreme use, special removal efforts may be necessary.
-
Smoke devices may activate fire and or smoke alarms in ductwork, computer rooms, or critical areas of the building; or cause panic if occupants are not notified.
Flow Capture Hoods. A conical or pyramid shaped hood may be used to collect the airflow from a terminal and guide it over a flow measuring system which reads directly in cubic feet per minute. The instrument can be a swinging vane anemometer, differential pressure air gage (diaphragm type), manometer, or thermal anemometer. The balancing cone should be tailored for the particular job. The large end of the cone should be sized to fit over the complete air inlet or outlet device and should have a seal to eliminate air leakage. The cone should terminate in a straight section with factory designed and calibrated pressure grids, straighteners, and instruments.
Recommended uses include proportionally balancing air distribution devices.
Limitations:
-
Should not be used where discharge velocities exceed 2000 fpm.
-
Recognize that the device generally redirects the normal pattern of air discharge and that it contributes an artificially imposed pressure drop in the branch of the air terminal being measured. These may result in a decrease in the delivered airflow of the outlet.
-
Contact the air inlet and outlet device manufacturer for details in using this instrument with their devices.
-
The instrument must be calibrated for the intended use. For use with supply distribution devices, the instrument should have been calibrated in the supply mode. For use with return distribution devices, the instrument should have been calibrated in the return mode.
-
Calibration is required. Flow-measuring instrument and hood assembly should be field checked with a velocity traverse. Readings must be verified with a recently calibrated instrument on each project. If the reading is not within ±2% of the recently calibrated instrument, have the pressure gage recalibrated by a qualified testing lab.
Accuracy of field measurements. If the hood is properly shaped and positioned at the air terminal, accuracy of field measurements will be within the limitations of the flow reading instrument.
Micromanometer (Hook Gage). These instruments are designed to read small differences in air pressure accurately and usually have a wide scale range. Most scales read pressures of 0 to 4 in. of water, in hundredths of an inch of water on the vertical scale, and thousandths of an inch of water on a vernier scale.
Different versions of this instrument exist. The most common type contains two glass vials about 2 to 3 in. in diameter. A pointed needle or hook is positioned by a micrometer adjustment until the point dimples the water surface but does not break the surface tension. The difference in level is determined in micrometer readings.
Another variation of this instrument has a single vial or well and an inclined scale. The well is positioned by a micrometer or vernier adjustment. It is very important that all micromanometers, including the electronic units, be accurately leveled.
The solid-state electronic hook gage will measure positive, negative, or differential pressures to ±0.00025 in. of water over a 0 to 2 in. of water range. It can also be used with pitot tubes for accurate measurement of air velocities as low as 350 fpm. Recommended uses include readings at hoods, perforated ceilings, etc.; calibrating other instruments; and measurements of velocities between 450 and 600 fpm, when used with a standard pitot tube.
Limitations:
-
Difficult to use with pulsating pressures.
-
Stability and leveling requirements make the instrument difficult to use in the field.
-
Generally not as sensitive as thermal anemometers below 600 fpm, when used with a standard pitot tube.
Double Reverse Tube. Other names for this device include impact reverse tube, combined reverse tube, and type S tube. It consists of two stainless steel tubes approximately 0.38 in. OD, permanently joined lengthwise. The tubes open facing opposite directions at the probe end with open ends at the base for connection to a manometer. (See Figure 1.) Recommended for use in dirty or wet airstreams where the amount of particulate matter in the airstream impairs the use of a pitot static tube. The instrument can be used to measure total pressure, static pressure, and obtain velocity pressure.
Limitations:
-
Requires a large (0.75 in.) duct hole for insertion.
-
The tube requires calibration and must be used in the same orientation as calibrated. The flow direction should be marked on the tube.
-
The tube cannot be used to measure static pressure directly. It must be connected to two manometers and static pressure must be calculated.
-
Tube ends must be kept smooth, clean, and free of burrs.
Accuracy of field measurements. Accuracy for field use of the combination of a double reverse tube with manometers is ±10%.
Clamp-On AC Power Meter (Wattmeter). The clamp-on type power meter has trigger-operated, clamp-on transformer jaws, like a voltammeter. This instrument measures true rms voltage and current, in addition to power in single phase or balanced three phase circuits. Compared with mean value measurement, true rms measurement is especially valuable for distorted waves, such as noise and multiplexed signals. Typical ranges are 20 to 600 V rms, 2 to 200 A rms, and 2 to 200 kW; or 20 to 600 V rms, 0.2 to 20 A rms, and 0.2 to 20 kW. Recommended uses include measurement of single, split-phase, and three-phase power sources. Given motor efficiency and power factor, power draw can be related to motor brake horsepower on a fan or pump curve and the operating point determined.
Limitations:
-
Caution is required, particularly when taking measurements under confined conditions.
-
Readings below 10% of input range are not recommended.
-
Batteries must be checked before use.
-
Calibration is required. Readings must be verified with a recently calibrated instrument on each project. If the reading is not within ±2% of the recently calibrated instrument, have the pressure gage recalibrated by a qualified testing lab.
Accuracy of field measurements. Accuracy is within ±1% of reading plus 0.5% of range
Recording Instruments. Recording instruments exist in wide variety, available to record any measurement taken by an instrument, such as dry-bulb temperature, wet-bulb temperature, relative humidity, and operating periods of cycling electrical equipment. The recording charts may be either continuous strip or circular, with chart rotation once every 24 h or 7 days. Some instruments are available with one or more remote bulbs. Recommended for obtaining round-the-clock data on the operation or performance of equipment. They are particularly useful for studying and diagnosing questionable operation in refrigerators, greenhouses, processing rooms, ovens, and comfort air conditioning systems.
Limitations. Some judgment must be used in the application of recording instruments. There are great differences in quality, accuracy, and cost. Care must be used to start the instrument at the correct time of day, and on the right day when a seven-day chart is used. Calibration is required. Readings must be verified with a recently calibrated instrument on each project. If the reading is not within ±2% of the recently calibrated instrument, have the pressure gage recalibrated by a qualified testing lab.
Accuracy of field measurements. Carefully study the manufacturer catalog data for instrument accuracy. It is important to read and observe specific operating instructions to obtain the published accuracy from a given instrument.
Humidity-Measuring Devices. A number of instruments are available to measure the level of moisture in air, including
-
Battery-powered hygrometer
-
Powered dew point indicator
-
Powered psychrometer with built in pump and fan
-
Digital psychrometer with built-in reservoir and fan
Calibration is required. Readings must be verified with a recently calibrated instrument on each project. If the reading is not within ±2% of the recently calibrated instrument, have the instrument recalibrated by a qualified testing lab.
Recommended use varies by type; hygrometers give direct, rapid relative humidity readings, and digital psychrometers provide dry- and wet-bulb depression within approximately 30 s.
Accuracy of field measurements. Hygrometers have an accuracy of ±2 to 3% rh in the 20 to 95% rh range. Psychrometer thermometer readings have an accuracy of ±0.5°F.
Barometer. A barometer measures atmospheric pressure, which is required to correct all airflow readings to standard conditions. A Bourdon tube type with accuracy of 1% of full scale should be used.
Barometric pressure information may also be obtained from weather radio stations or airports in the immediate vicinity. Actual pressure at local elevation must be used for air density calculations.
Fluid System Digital Electronic Differential Pressure Meter. This instrument measures the differential pressure across an element in a system when flow is present, providing digital readings in the range of 3.6 to 600 in. of water. Some instruments include a temperature probe for a range of 32 to 248°F, hoses with snap-on fittings, and automatic air purging. A computer is available for calculating the flow in a range of 0.2 to 4750 gpm and computing the hand wheel setting of compatible valves by proportional balancing procedures. Maximum working pressures can be up to 300 psig.
Recommended uses include measurement of fluid flow, temperature, and differential pressure, as well as computing the setting of compatible valves by proportional balancing procedures.
Limitations:
-
The computing feature is limited to compatible valves.
-
Calibration is required. Readings must be verified with a recently calibrated instrument on each project. If the reading is not within ±2% of the recently calibrated instrument, have the instrument recalibrated by a qualified testing lab.
Accuracy of field measurements. Accuracy of differential pressure within 12 in. of water or 2% of valve readout (whichever is greater). This same accuracy is true for measurement of flow, done via the computing feature.
Electronic Differential Pressure Meter. This instrument is a portable device which measures differential pressure and gives a digital readout directly in pressure or velocity. Some instruments are also available with adapters and probes to measure flow and temperature. Typical ranges are 0 to 100 in. of water for low-density fluids, and 0 to 2400 in. of water or 0 to 100 psi for high-density fluids. Temperatures can be measured from −55 to 250°F. Recommended for use with a pitot tube, static probe, flow grid, orifice plate, or special balancing valve. Some instruments can also be combined with a flow-measuring hood. Many instruments have memories, averaging capabilities, and printers.
Limitations:
-
When air velocities are below 600 fpm, a micromanometer or hook gage should be used. Some instruments of this type have micromanometer accuracies.
-
These instruments are battery powered and require checking batteries and replacing or recharging them.
-
Some instruments should not be stored below 15°F or operated below 32°F.
-
Calibration is required. Readings must be verified with a recently calibrated instrument on each project. If the reading is not within ±2% of the recently calibrated instrument, have the instrument recalibrated by a qualified testing lab.
Accuracy of field measurements. Experience shows that qualified technicians can obtain measurements that range between ±5 and 10% accuracy under good field conditions. However, good field conditions do not always exist, and measurements can easily exceed ±10% error.
Ultrasonic Flowmeters. This is a device that determines flow through the use of acoustic signals, measured in design units (e.g., gallons per minute). The ultrasonic flow metering station is either an integral part of the piping system or a strap-on meter. In either case, there is no intrusion into the pipe or liquid flow that would generate a pressure drop. There are no moving parts in the flow to maintain or service. Two distinct types of ultrasonic flow meters exist: a transit-time device for HVAC or clear water measurement, and a Doppler-effect device for flows containing a required volume of particulate in the liquid. Recommended use includes measurement of flow in full pipes; these devices are excellent when low or nonexistent pressure drop is a requirement. These are best for larger pipes, and most manufacturers’ specifications are based on flows of 1 fps or greater.
Limitations:
-
For Doppler flow meters, liquid must contain particulate or gas bubbles.
-
Transit-time flowmeters require liquid to be acoustically transparent (implies low particulate content [e.g., typical lake or river water or cleaner]).
-
Portable (strap-on) flowmeters require that pipe details (e.g., diameter, wall thickness, material of construction) are known or determinable. Pipe must be acoustically transparent (both concrete and lined pipe are not).
-
Calibration is required. Readings must be verified with a recently calibrated instrument on each project. If the reading is not within ±2% of the recently calibrated instrument, have the instrument recalibrated by a qualified testing lab.
Accuracy of field measurements.
Doppler Flowmeters:
Transit-Time Flowmeters:
-
Typically within 2 to 3% for strap-on transducers
-
Typically within 1 to 2% for integral transducers
-
Typically within 0.5 to 1% for integral transducers mounted to a calibrated flow tube
Turbine Flowmeter. This mechanical device uses a wheel placed in the path of the flow. Liquid causes the wheel to turn at speeds relative to the velocity, generating a signal and providing flow information directly in design units (e.g., gallons per minute) or a milliamp output. Recommended for measurement of flow in pipes with clean fluid flow.
Limitations:
-
Care must be exercised to maintain the turbine flowmeter, because wear may affect the wheel bearings.
-
Bearings may drag if impurities lodge in them.
-
Debris can clog or break the wheel.
-
Calibration is required. Readings must be verified with a recently calibrated instrument on each project. If the reading is not within ±2% of the recently calibrated instrument, have the instrument recalibrated by a qualified testing lab.
Accuracy of field measurements. Accuracy is within 2%.
Permanently Installed Airflow Measuring Stations. There are two main types of permanent airflow measuring stations. The velocity pressure array comprises a fixed array of velocity pressure measuring devices.
Recommended uses. These stations measure the fan total airflow and distribution of air in branch ducts. Other useful measurements include those of outdoor, return, and relief airflow.
Limitations:
-
The required length of straight sections upstream and downstream of the measuring device depends on both velocity of airflow and the effects of the nearest obstruction. The location of the airflow measuring station must be in accordance with the manufacturer’s recommendations.
-
Inlet velocity magnitude, profile temperature, dust, moisture, and gas products may limit the use of airflow measuring stations.
Accuracy of field measurements. Under ideal conditions, a velocity pressure airflow measuring station should produce an accuracy of ±5% plus the error rate of the pressure sensor. Because of sensitivity to disturbances and duct conditions, the manufacturer’s duct placement recommendations or ASHRAE Handbook—Fundamentals requirements for measurement with technologies based on velocity-pressure equalizing principles should be observed.
The thermal dispersion array airflow measuring station obtains velocity measurements directly using independent measurement points in a fixed array before averaging. Communications options allow technicians to download instantaneous point velocity and temperature data independently from the control system. A remote traverse without time lag between samples is possible either using an infrared reading device or over an RS-485 network using BACnet™ or Modbus® protocols. The independent nature of the sensor data allows for accurate duct area averaging.
Recommended uses:
-
Direct measurement of outdoor airflow rates (low flow sensitivity and accuracy, wide operating velocity range, wide temperature range, fewer space restrictions)
-
Maintaining fixed volumetric differentials for space pressurization control, using its high repeatability
-
As a reference for other velocity and temperature instruments because of their stability and factory calibration (higher precision)
-
Any conditioned air velocity, volume, or temperature averaging application that would benefit from highly repeatable measurement
Limitations:
-
Performance depends on local conditions, velocity sensor density (number/unit area), and type of the nearest obstructions (upstream and downstream).
-
Avoid placement downstream of modulating dampers or immediately upstream of a damper that may close completely.
-
The discharge side of duct silencers can be problematic when the measuring station is within the absorption distance of a humidifier or wet coil face.
Accuracy of field measurements. Accuracy should be within ±3% of reading, when placement is within the manufacturer’s guidelines.
Multifunction Portable Instruments. Digital electronic instruments are available with a wide selection of probes that can be fitted into the various channel ports of a single handheld meter with various uses, accuracies, and limitations. These uses can be singular (e.g., thermohygrometers for temperature and relative humidity) or many. Types of measurements include temperature of air, gas, and liquids with a wide choice of sensing elements, such as thermocouples or RTDs; pressure of air, gas, and liquids with manometers or pitot tubes; differential air pressure, static pressure, or barometric pressure; and differential water pressure or gage pressure. Amongst the specific tools used are wind vane, hot wire, or pitot tube anemometers; optical, inductive, and rotational tachometers; and water and air quality attachments for pH, conductivity, salinity, and mV, O2, and ion concentration.
Some instruments have both battery and plug-in AC power; recording memory for downloading onto computers or transmission over RS-232 or RS-500 interface; hold, alternating, and averaging circuits for applications as traverses; relative humidity calibrating devices; and other features.
Individual manufacturers must be consulted for details of accuracy, limitations, usage, and response times of the individual measurements.
Instruments should be calibrated in accordance with ASHRAE Standard 111 to verify their accuracy and repeatability before use in the field.