CHAPTER 52. SNOW MELTING AND FREEZE PROTECTION

 

The practicality of melting snow or ice by supplying heat to the exposed surface has been demonstrated in many installations, including sidewalks, roadways, ramps, bridges, access ramps, and parking spaces for the handicapped, and runways. Melting eliminates the need for snow removal by chemical means, provides greater safety for pedestrians and vehicles, and reduces the labor and cost of slush removal. Other advantages include eliminating piled snow, reducing liability, and reducing health risks of manual and mechanized shoveling.

This chapter covers three types of snow-melting and freeze protection systems:

  1. Hot fluid circulated in slab-embedded pipes (hydronic)

  2. Embedded electric heater cables or wire

  3. Overhead high-intensity infrared radiant heating

Detailed information about slab heating can be found in Chapter 6 of the 2020 ASHRAE Handbook—HVAC Systems and Equipment. More information about infrared heating can be found in Chapter 16 of the same volume.

Components of the system design include (1) heat requirement, (2) slab design, (3) control, and (4) hydronic or electric system design.

1. SNOW- MELTING HEAT FLUX REQUIREMENT

The heat required for snow melting depends on five atmospheric factors: (1) rate of snowfall, (2) snowfall-coincident air dry-bulb temperature, (3) humidity, (4) wind speed near the heated surface, and (5) apparent sky temperature. The dimensions of the snow-melting slab affect heat and mass transfer rates at the surface. Other factors such as back and edge heat losses must be considered in the complete design.

 Heat Balance

The processes that establish the heat requirement at the snow-melting surface can be described by terms in the following equation, which is the steady-state energy balance for required total heat flux (heat flow rate per unit surface area) qo at the upper surface of a snow-melting slab during snowfall.

(1)

where

qo = heat flux required at snow-melting surface, Btu/h  ·  ft2
qs = sensible heat flux, Btu/h  ·  ft2
qm = = latent heat flux, Btu/h  ·  ft2
Ar = snow-free area ratio, dimensionless
qh = convective and radiative heat flux from snow-free surface, Btu/h  ·  ft2
qe = heat flux of evaporation, Btu/h  ·  ft2

Sensible and Latent Heat Fluxes. The sensible heat flux qs is the heat flux required to raise the temperature of snow falling on the slab to the melting temperature plus, after the snow has melted, to raise the temperature of the liquid to the assigned temperature tf of the liquid film. The snow is assumed to fall at air temperature ta. The latent heat flux qm is the heat flux required to melt the snow. Under steady-state conditions, both qs and qm are directly proportional to the snowfall rate s.

Snow-Free Area Ratio. Sensible and latent (melting) heat fluxes occur on the entire slab during snowfall. On the other hand, heat and mass transfer at the slab surface depend on whether there is a snow layer on the surface. Any snow accumulation on the slab acts to partially insulate the surface from heat losses and evaporation. The insulating effect of partial snow cover can be large. Because snow may cover a portion of the slab area, it is convenient to think of the insulating effect in terms of an effective or equivalent snow-covered area As, which is perfectly insulated and from which no evaporation and heat transfer occurs. The balance is then considered to be the equivalent snow-free area Af. This area is assumed to be completely covered with a thin liquid film; therefore, both heat and mass transfer occur at the maximum rates for the existing environmental conditions. It is convenient to define a dimensionless snow-free area ratio Ar:

(2)

where

Af = equivalent snow-free area, ft2
As = equivalent snow-covered area, ft2
At = Af + As = total area, ft2

Therefore,

To satisfy Ar = 1, the system must melt snow rapidly enough that no accumulation occurs. For Ar = 0, the surface is covered with snow of sufficient thickness to prevent heat and evaporation losses. Practical snow-melting systems operate between these limits. Earlier studies indicate that sufficient snow-melting system design information is obtained by considering three values of the free area ratio: 0, 0.5, and 1.0 (Chapman 1952).

Heat Flux because of Surface Convection, Radiation, and Evaporation. Using the snow-free area ratio, appropriate heat and mass transfer relations can be written for the snow-free fraction of the slab Ar. These appear as the third and fourth terms on the right-hand side of Equation (1). On the snow-free surface, maintained at film temperature tf, heat is transferred to the surroundings and mass is transferred from the evaporating liquid film. Heat flux qh includes convective losses to the ambient air at temperature ta and radiative losses to the surroundings, which are at mean radiant temperature TMR. The convection heat transfer coefficient is a function of wind speed and a characteristic dimension of the snow-melting surface. This heat transfer coefficient is also a function of the thermodynamic properties of the air, which vary slightly over the temperature range for various snowfall events. The mean radiant temperature depends on air temperature, relative humidity, cloudiness, cloud altitude, and whether snow is falling.

The heat flux qe from surface film evaporation is equal to the evaporation rate multiplied by the heat of vaporization. The evaporation rate is driven by the difference in vapor pressure between the wet surface of the snow-melting slab and the ambient air; it is a function of wind speed, a characteristic dimension of the slab, and the thermodynamic properties of the ambient air.

 Heat Flux Equations

Sensible Heat Flux. The sensible heat flux qs is given by the following equation:

(3)

where

cp,ice = specific heat of ice, Btu/lb  ·  °F
cp,water = specific heat of water, Btu/lb · °F
s = snowfall rate water equivalent, typically assumed to be snowfall rate divided by 10, in/h
ta = ambient temperature coincident with snowfall, °F
tf = liquid film temperature, °F
ts = melting temperature, °F
ρwater = density of water, lb/ft3
c1 = 12 in/ft

The density of water, specific heat of ice, and specific heat of water are approximately constant over the temperature range of interest and are evaluated at 32°F. The ambient temperature and snowfall rate are available from weather data. The liquid film temperature is usually taken as 33°F.

Melting Heat Flux. The heat flux qm required to melt the snow is given by the following equation:

(4)

where hif = heat of fusion of snow, Btu/lb.

Convective and Radiative Heat Flux from a Snow-Free Surface. The corresponding heat flux qh is given by the following equation:

(5)

where

hc = convection heat transfer coefficient for turbulent flow, Btu/h · ft2 · °F
Tf = liquid film temperature, °R
TMR = mean radiant temperature of surroundings, °R
σ = Stefan-Boltzmann constant = 0.1712 × 10−8 Btu/h · ft2 · °R4
εs = emittance of surface, dimensionless

The convection heat transfer coefficient over the slab on a plane horizontal surface is given by the following equations (Incropera and DeWitt 1996):

(6)

where

kair = thermal conductivity of air at ta, Btu · ft/h · ft2 · °F
L = characteristic length of slab in direction of wind, ft
Pr = Prandtl number for air, taken as Pr = 0.7
ReL = Reynolds number based on characteristic length L

and

(7)

where

V = design wind speed near slab surface, mph
νair = kinematic viscosity of air, ft2/h
c2 = 5280 ft/mile

Without specific wind data for winter, the extreme wind data in Chapter 14 of the 2017 ASHRAE Handbook—Fundamentals may be used; note, however, that these wind speeds may not correspond to actual measured data. Furthermore, oversizing systems based on weather extremes should be avoided. If the snow-melting surface is not horizontal, the convection heat transfer coefficient might be different, but in many applications, this difference is negligible.

From Equations (6) and (7), the turbulent convection heat transfer coefficient is a function of L−0.2. Because of this relationship, shorter snow-melting slabs have higher convective heat transfer coefficients than longer slabs. For design, the shortest dimension should be used (e.g., for a long, narrow driveway or sidewalk, use the width). A snow-melting slab characteristic length L = 20 ft is used in the heat transfer calculations that resulted in Tables 1, 2, and 3.

It is not practical or even sometimes possible to size systems to a snow-free ratio of Ar = 1 at a confidence ratio of 100%. Designers should evaluate the critical nature of the area to be treated and size the system for the lowest acceptable heat flux. See Table 3 for guidance on appropriate snow-free area ratios and confidence frequencies, typically used based on application. Under normal atmospheric conditions and given minimum thermal mass coverage (thermal resistance), an upper limit to heat flux is typically bounded by the maximum allowable flow temperature for a pipe embedded in a thermal mass. This is particularly important for concrete, where entering fluid temperatures should not exceed 150°F.

The mean radiant temperature TMR in Equation (5) is the equivalent blackbody temperature of the surroundings of the snow-melting slab. Under snowfall conditions, the entire surroundings are approximately at the ambient air temperature (i.e., TMR = Ta). When there is no snow precipitation (e.g., during idling and after snowfall operations for Ar < 1), the mean radiant temperature is approximated by the following equation:

(8)

where

Fsc = fraction of radiation exchange that occurs between slab and clouds
Tcloud = temperature of clouds, °R
Tsky clear = temperature of clear sky, °R

The equivalent blackbody temperature of a clear sky is primarily a function of the ambient air temperature and the water content of the atmosphere. An approximation for the clear sky temperature is given by the following equation, which is a curve fit of data in Ramsey et al. (1982):

(9)

where

Ta = ambient temperature, °R
Φ = relative humidity of air at elevation for which typical weather measurements are made, decimal; see energyplus.net/weather for typical meteorological year data by location

The cloud-covered portion of the sky is assumed to be at Tcloud. The height of the clouds may be assumed to be 10,000 ft. The temperature of the clouds at 10,000 ft is calculated by subtracting the product of the average lapse rate (rate of decrease of atmospheric temperature with height) and the altitude from the atmospheric temperature Tatm. The average lapse rate, determined from the tables of U.S. Standard Atmospheres (COESA 1976), is 3.5°F per 1000 ft of elevation (Ramsey et al. 1982). Therefore, for clouds at 10,000 ft,

(10)

Under most conditions, this method of approximating the temperature of the clouds provides an acceptable estimate. However, when the atmosphere contains a very high water content, the temperature calculated for a clear sky using Equation (9) may be warmer than the cloud temperature estimated using Equation (10). When that condition exists, Tcloud is set equal to the calculated clear sky temperature Tsky clear.

Table 1 Frequencies of Snow-Melting Surface Heat Fluxes at Steady-State Conditions*

Location

Snowfall Hours per Year

Snow-Free Area Ratio, Ar

Heat Fluxes Not Exceeded During Indicated Percentage of Snowfall Hours from 1982 to 1993, Btu/h · ft2

75%

90%

95%

98%

99%

100%

Albany, NY

156

1

89

125

149

187

212

321

0.5

60

86

110

138

170

276

0

37

62

83

119

146

276

Albuquerque, NM

44

1

70

118

168

191

242

393

0.5

51

81

96

117

156

229

0

30

46

61

89

92

194

Amarillo, TX

64

1

113

150

168

212

228

318

0.5

71

88

108

124

142

305

0

24

46

62

89

115

292

Billings, MT

225

1

112

164

187

212

237

340

0.5

64

89

102

116

128

179

0

22

33

45

60

68

113

Bismarck, ND

158

1

151

199

231

275

307

477

0.5

83

107

124

148

165

243

0

16

30

39

60

73

180

Boise, ID

85

1

58

79

100

126

146

203

0.5

38

52

66

80

89

164

0

22

31

40

53

62

164

Boston, MA

112

1

96

137

165

202

229

365

0.5

65

95

112

149

190

365

0

37

75

93

121

172

365

Buffalo, NY

292

1

115

166

210

277

330

570

0.5

68

97

127

164

188

389

0

23

39

55

93

112

248

Burlington, VT

204

1

91

130

154

184

200

343

0.5

58

78

92

113

128

343

0

23

40

55

78

94

343

Cheyenne, WY

224

1

119

172

201

229

261

354

0.5

70

97

111

132

149

288

0

16

37

52

77

100

285

Chicago, IL, O’Hare International Airport

124

1

96

126

153

186

235

521

0.5

58

77

94

113

137

265

0

23

38

53

75

83

150

Cleveland, OH

188

1

85

124

157

195

230

432

0.5

52

73

92

118

147

235

0

23

37

47

69

92

225

Colorado Springs, CO

159

1

89

135

167

202

219

327

0.5

57

82

99

124

140

218

0

23

45

61

87

112

165

Columbus, OH, International Airport

92

1

71

101

123

149

175

328

0.5

45

60

71

87

95

184

0

15

30

45

60

62

135

Des Moines, IA

127

1

120

174

208

255

289

414

0.5

74

102

120

149

180

310

0

24

46

69

94

108

231

Detroit, MI, Metro Airport

153

1

92

130

156

192

212

360

0.5

57

77

94

118

134

227

0

23

38

47

75

89

194

Duluth, MN

238

1

123

171

201

238

250

370

0.5

71

97

114

131

142

213

0

22

32

46

68

77

196

Ely, NV

153

1

67

97

116

134

162

242

0.5

44

66

83

111

129

241

0

23

45

67

97

112

240

Eugene, OR

18

1

59

110

139

165

171

224

0.5

47

77

93

119

122

164

0

30

53

70

102

120

164

Fairbanks, AK

288

1

91

121

144

174

202

391

0.5

52

68

78

94

108

200

0

15

23

31

40

48

87

Baltimore, MD, BWI Airport

56

1

87

139

172

235

282

431

0.5

69

108

147

200

238

369

0

46

84

119

181

214

306

Great Falls, MT

233

1

123

171

193

233

276

392

0.5

71

93

107

129

144

210

0

17

31

45

60

75

143

Indianapolis, IN

96

1

95

134

158

194

215

284

0.5

58

80

96

116

124

209

0

23

38

52

83

99

209

Lexington, KY

50

1

81

108

123

150

170

233

0.5

49

65

74

85

95

197

0

16

30

39

46

55

162

Madison, WI

161

1

99

138

164

206

241

449

0.5

61

82

98

129

163

245

0

23

39

60

91

113

194

Memphis, TN

13

1

106

141

172

200

206

213

0.5

75

96

115

118

130

157

0

40

75

76

90

97

123

Milwaukee, WI

161

1

101

135

164

196

207

431

0.5

62

83

101

128

147

246

0

23

46

68

98

120

239

Minneapolis-St. Paul, MN

199

1

119

169

193

229

254

332

0.5

73

99

114

138

154

287

0

23

45

61

91

113

245

New York, NY, JFK Airport

61

1

91

134

164

207

222

333

0.5

63

93

118

145

164

325

0

38

68

86

113

133

316

Oklahoma City, OK

35

1

117

168

215

248

260

280

0.5

72

101

123

133

144

208

0

24

46

68

78

113

190

Omaha, NE

94

1

108

148

189

222

259

363

0.5

65

89

105

128

135

186

0

23

38

60

90

100

136

Peoria, IL

91

1

95

139

166

201

227

436

0.5

58

83

99

119

130

250

0

23

38

53

76

92

228

Philadelphia, PA, International Airport

56

1

94

129

154

208

246

329

0.5

65

90

112

162

185

267

0

38

63

79

111

150

225

Pittsburgh, PA, International Airport

168

1

83

125

159

194

219

423

0.5

51

75

94

111

129

216

0

16

31

46

68

77

136

Portland, ME

157

1

120

168

195

234

266

428

0.5

76

108

132

168

199

376

0

39

67

90

130

152

324

Portland, OR

15

1

50

78

102

177

239

296

0.5

39

55

81

114

130

199

0

23

45

60

78

102

128

Rapid City, SD

177

1

139

203

252

312

351

482

0.5

78

111

132

164

183

245

0

16

30

38

53

65

179

Reno, NV

63

1

50

72

89

116

137

191

0.5

36

55

75

105

115

172

0

23

45

68

91

113

159

Salt Lake City, UT

142

1

52

77

89

110

120

171

0.5

39

62

76

96

104

171

0

30

60

75

89

104

171

Sault Ste. Marie, MI

425

1

112

153

183

216

249

439

0.5

66

88

104

125

142

239

0

23

37

47

68

83

188

Seattle, WA

27

1

56

107

138

171

205

210

0.5

45

72

97

122

133

175

0

37

52

75

96

123

151

Spokane, WA

144

1

67

98

116

141

159

227

0.5

45

61

73

84

95

145

0

23

37

45

54

67

112

Springfield, MO

58

1

110

155

179

215

224

292

0.5

70

95

117

142

171

240

0

32

54

76

115

129

227

St. Louis, MO, International Airport

62

1

97

147

170

193

227

344

0.5

66

90

105

126

144

269

0

31

53

68

97

104

194

Topeka, KS

61

1

102

153

192

234

245

291

0.5

64

92

110

132

139

185

0

23

39

52

68

84

167

Wichita, KS

60

1

115

163

209

248

285

326

0.5

71

96

116

137

153

168

0

24

45

57

75

83

158

* Heat fluxes are at the snow-melting surface only. See text for calculation of back and edge heat loss fluxes.


Table 2 Mean Sensitivity of Snow-Melting Surface Heat Fluxes to Wind Speed and Slab Length For loads not exceeded during 99% of snowfall hours, 1982 through 1993

Snow-Free Area Ratio, Ar

Ratio of Flux at Stated Condition to Flux at L = 20 ft and V = Vmet

L = 20 ft

L = 5 ft

V = 0.5Vmet

V = 2Vmet

V = Vmet

V = 0.5Vmet

V = 2Vmet

1

0.7

1.6

1.2

0.8

2.0

0.5

0.8

1.4

1.2

0.9

1.7

0

1.0

1.0

1.0

1.0

1.0

Note: Based on data from U.S. locations.

L = characteristic length

Vmet = meteorological wind speed from NCDC


Table 3 Annual Operating Data at 99% Satisfaction Level of Heat Flux Requirement

City

Time, h/yr

2% Min. Snow Temp., °F

Annual Energy Requirement per Unit Area at Steady-State Conditions,* Btu/ft2

System Designed for Ar = 1

System Designed for Ar = 0.5

System Designed for Ar = 0

Melting

Idling

Melting

Idling

Melting

Idling

Melting

Idling

Albany, NY

156

1,883

9.3

10,132

109,230

7,252

109,004

4,371

108,420

Albuquerque, NM

44

954

16.3

2,455

38,504

1,729

38,495

984

38,332

Amarillo, TX

64

1,212

6.8

5,276

62,557

3,314

62,136

1,357

61,170

Billings, MT

225

1,800

−10.8

17,299

116,947

10,526

111,803

3,716

91,360

Bismarck, ND

158

2,887

−8.8

16,295

207,888

9,321

201,565

2,300

157,503

Boise, ID

85

1,611

5.3

3,543

74,724

2,449

73,015

1,345

68,456

Boston, MA

112

1,273

16.3

7,694

77,992

5,455

77,907

3,218

77,747

Buffalo, NY

292

1,779

3.8

23,929

105,839

14,735

105,521

5,563

101,945

Burlington, VT

204

2,215

4.3

13,182

147,122

8,485

143,824

3,783

134,634

Cheyenne, WY

224

2,152

−15.8

20,061

126,714

11,931

125,635

3,782

120,915

Chicago, IL, O’Hare International Airport

124

1,854

3.8

8,501

116,663

5,402

112,763

2,252

100,427

Cleveland, OH

188

1,570

8.8

11,419

86,539

7,359

85,470

3,208

80,851

Colorado Springs, CO

159

1,925

−8.8

11,137

97,060

7,089

96,847

3,026

96,244

Columbus, OH, International Airport

92

1,429

12.8

4,581

71,037

2,972

68,002

1,367

62,038

Des Moines, IA

127

1,954

−1.8

10,884

128,140

6,796

125,931

2,654

116,545

Detroit, MI, Metro Airport

153

1,781

11.3

10,199

104,404

6,467

102,289

2,704

95,777

Duluth, MN

238

3,206

0.3

20,838

251,218

12,423

236,657

3,969

187,820

Ely, NV

153

2,445

13.3

7,421

141,288

5,268

139,242

3,098

136,920

Eugene, OR

18

481

15.8

841

17,018

634

16,997

429

16,992

Fairbanks, AK

288

4,258

−15.8

19,803

343,674

11,700

318,880

3,559

194,237

Baltimore, MD, BWI Airport

56

957

16.3

3,827

45,132

2,970

45,132

2,121

45,130

Great Falls, MT

233

1,907

−15.8

19,703

123,801

11,731

120,603

3,736

101,712

Indianapolis, IN

96

1,473

10.8

6,558

80,942

4,132

78,532

1,705

75,926

Lexington, KY

50

1,106

13.3

2,696

54,084

1,718

52,278

733

45,859

Madison, WI

161

2,308

5.3

11,404

149,363

7,279

147,112

3,094

140,108

Memphis, TN

13

473

12.8

1,010

21,756

691

21,518

373

21,102

Milwaukee, WI

161

1,960

7.3

11,678

127,230

7,564

123,960

3,431

119,945

Minneapolis-St. Paul, MN

199

2,513

0.3

16,532

183,980

10,325

178,495

4,097

166,921

New York, NY, JFK Airport

61

885

18.3

4,193

50,680

2,988

50,467

1,797

50,049

Oklahoma City, OK

35

686

6.8

2,955

40,957

1,850

39,725

741

38,308

Omaha, NE

94

1,981

−2.3

7,425

124,274

4,613

119,565

1,790

112,700

Peoria, IL

91

1,748

2.3

6,544

104,380

4,078

100,581

1,606

94,045

Philadelphia, PA, International Airport

56

992

18.3

3,758

50,494

2,669

50,412

1,588

50,203

Pittsburgh, PA, International Airport

168

1,514

9.3

10,029

79,312

6,350

77,750

2,626

72,361

Portland, ME

157

1,996

7.3

13,318

115,248

8,969

115,196

4,630

114,836

Portland, OR

15

329

21.8

623

13,399

464

13,194

310

12,918

Rapid City, SD

177

2,154

−4.8

16,889

137,523

9,738

135,024

2,535

106,102

Reno, NV

63

1,436

16.3

2,293

54,713

1,792

54,706

1,302

54,703

Salt Lake City, UT

142

1,578

16.3

5,263

70,254

4,271

69,927

3,286

69,927

Sault Ste. Marie, MI

425

2,731

−0.3

34,249

176,517

20,779

174,506

7,250

155,508

Seattle, WA

27

260

17.8

1,212

10,482

943

10,473

682

10,452

Spokane, WA

144

1,832

10.8

6,909

81,000

4,721

79,177

2,512

75,659

Springfield, MO

58

1,108

6.8

4,401

57,165

2,950

56,929

1,503

56,238

St. Louis, MO, International Airport

62

1,150

6.8

4,516

64,668

2,981

63,428

1,446

60,764

Topeka, KS

61

1,409

−1.8

4,507

75,598

2,821

74,028

1,126

68,402

Wichita, KS

60

1,223

0.3

4,961

69,187

3,106

67,828

1,229

60,991

Source: Ramsey et al. 1999.

* Does not include back and edge heat losses.


Evaporation Heat Flux. The heat flux qe required to evaporate water from a wet surface is given by

(11)

where

hm = mass transfer coefficient, ft/h
Wa = humidity ratio of ambient air, lbvapor/lbair
Wf = humidity ratio of saturated air at film surface temperature, lbvapor/lbair
hfg = heat of vaporization (enthalpy difference between saturated water vapor and saturated liquid water), Btu/lb
ρdry air = density of dry air, lb/ft3

Determining the mass transfer coefficient is based on the analogy between heat transfer and mass transfer. Details of the analogy are given in Chapter 5 of the 2017 ASHRAE Handbook—Fundamentals. For external flow where mass transfer occurs at the convective surface and the water vapor component is dilute, the following equation relates the mass transfer coefficient hm to the heat transfer coefficient hc [Equation (6)]:

(12)

where Sc = Schmidt number. In applying Equation (11), the values Pr = 0.7 and Sc = 0.6 were used to generate the values in Tables 1 to 4.

The humidity ratios both in the atmosphere and at the surface of the water film are calculated using the standard psychrometric relation given in the following equation (from Chapter 1 of the 2017 ASHRAE Handbook—Fundamentals):

(13)

where

p = atmospheric pressure, psi
pv = partial pressure of water vapor, psi

The vapor pressure pv for calculating Wa is equal to the saturation vapor pressure ps at the dew-point temperature of the air. Saturated conditions exist at the water film surface. Therefore, the vapor pressure used in calculating Wf is the saturation pressure at the film temperature tf. The saturation partial pressures of water vapor for temperatures above and below freezing are found in tables of the thermodynamic properties of water at saturation, or can be calculated using appropriate equations. Both are presented in Chapter 1 of the 2017 ASHRAE Handbook—Fundamentals. The atmospheric pressure in Equation (13) is corrected for altitude using the following equation (Kuehn et al. 1998):

The atmospheric pressure in Equation (13) is corrected for altitude using the following equation (Kuehn et al. 1998):

(14)

where

pstd = standard atmospheric pressure, psi
A = 0.00356°R /ft
z = altitude of the location above sea level, ft
To = 518.7°R

Altitudes of specific locations are found in Chapter 14 of the 2017 ASHRAE Handbook—Fundamentals.

Heat Flux Calculations. Equations (1) to (14) can be used to determine the required heat fluxes of a snow-melting system. However, calculations must be made for coincident values of snowfall rate, wind speed, ambient temperature, and dew-point temperature (or another measure of humidity). By computing the heat flux for each snowfall hour over a period of several years, a frequency distribution of hourly heat fluxes can be developed. Annual averages or maximums for climatic factors should never be used in sizing a system because they are unlikely to coexist. Finally, it is critical to note that the preceding analysis only describes what is happening at the upper surface of the snow-melting surface. Edge losses and back losses have not been taken into account.

Example 1.

During the snowfall that occurred during the 8 pm hour on December 26, 1985, in the Detroit metropolitan area, the following simultaneous conditions existed: air dry-bulb temperature = 17°F, dew-point temperature = 14°F, wind speed = 19.7 mph, and snowfall rate = 0.10 in. of liquid water equivalent per hour. Assuming L = 20 ft, Pr = 0.7, and Sc = 0.6, calculate the surface heat flux qo for a snow-free area ratio of Ar = 1.0. The thermodynamic and transport properties used in the calculation are taken from Chapters 1 and 33 of the 2017 ASHRAE Handbook—Fundamentals. The emittance of the wet surface of the heated slab is 0.9.

Solution:

By Equation (3),

By Equation (4),

By Equation (7),

By Equation (6),

By Equation (5),

By Equation (12),

Obtain the values of the saturation vapor pressures at dew-point temperature 14°F and film temperature 33°F from Table 3 in Chapter 1 of the 2017 ASHRAE Handbook—Fundamentals. Then, use Equation (13) to obtain Wa = 0.00160 lbvapor/lbair and Wf = 0.00393 lbvapor/lbair. By Equation (11),

By Equation (1),

Note that this is the heat flux needed at the snow-melting surface of the slab. Back and edge losses must be added as discussed in the section on Back and Edge Heat Losses.


 Weather Data and Heat Flux Calculation Results

Table 1 shows frequencies of snow-melting loads for 46 cities in the United States (Ramsey et al. 1999). For the calculations, the temperature of the surface of the snow-melting slab was taken to be 33°F. Any time the ambient temperature was below 32°F and it was not snowing, it was assumed that the system was idling (i.e., that heat was supplied to the slab so that melting would start immediately when snow began to fall).

Weather data were taken for the years 1982 through 1993. These years were selected because of their completeness of data. The weather data included hourly values of the precipitation amount in equivalent depth of liquid water, precipitation type, ambient dry-bulb and dew-point temperatures, wind speed, and sky cover. All weather elements for 1982 to 1990 were obtained from the Solar and Meteorological Surface Observation Network 1961 to 1990 (SAMSON), Version 1.0 (NCDC 1993). For 1991 to 1993, all weather elements except precipitation were taken from DATSAV2 data obtained from the National Climatic Data Center as described in Colliver et al. (1998). The precipitation data for these years were taken from NCDC’s Hourly Cooperative Dataset (NCDC 1990).

All wind speeds used were taken directly from the weather data. Wind speed Vmet is usually measured at height of approximately 33 ft. As indicated in the section on Heat Balance, the heat and mass transfer coefficients are functions of a characteristic dimension of the snow-melting slab. The dimension used in generating the values of Table 1 was 20 ft. Sensitivity of the load to both wind speed and the characteristic dimension is included in Table 2. During snowfall, the sky temperature was taken as equal to the ambient temperature.

The first data column in Table 1 presents the average number of snowfall hours per year for each location. All surface heat fluxes were computed for snow-free area ratios of 1, 0.5, and 0, and the frequencies of snow-melting loads are presented. The frequency indicates the percentage of time that the required snow-melting surface heat flux does not exceed the value in the table for that ratio.

Snow-Melting Surface Heat Fluxes Required to Provide Snow-Free Area Ratio of 0.5 for 90% of Snowfall Hours at That Location

Figure 1. Snow-Melting Surface Heat Fluxes Required to Provide Snow-Free Area Ratio of 0.5 for 90% of Snowfall Hours at That Location


This table is used to design a snow-melting system for a given level of customer satisfaction depending on criticality of function. For example, although a heliport at the rooftop of a hospital may require almost 100% satisfactory operation at a snow-free ratio of 1, a residential driveway may be considered satisfactory at 90% and Ar = 0.5 design conditions. To optimize cost, different percentiles may be applied to different sections of the slab. For example, train station slab embark/disembark areas may be designed for a higher percentile and Ar than other sections.

Figure 1 shows the distribution in the United States of snow-melting surface heat fluxes for a snow-free area ratio of 0.5. The values presented satisfy the loads 90% of the snowfall hours for each location (as listed in the 90% column of Table 1). Local values can be approximated by interpolating between values given on the figure; however, extreme care must be taken because special local climatological conditions exist for many areas (e.g., lake effect snow). Both altitude and geography should be considered in making interpolations. Generally, locations in the northern plains of the United States require the maximum snow-melting heat flux (Chapman 1999).

Table 4 General Guidance for Snow-Free Area Ratio and Frequency Distributions by Application Type

Application Type

Free Area Ratio, Ar

Frequency Distribution, %

Private residential

  Sidewalk, steps

0.5 or 1.0

75 or 90

  Driveway

0.0 or 0.5

75 or 90

  Steep incline

1.0

90

Multiunit building

  Sidewalk, steps, wheelchair ramp

1.0

95

  Parking lot

0.5

75 or 90

  Parking ramp

0.5 or 1.0

90 or 95

Commercial building

  Sidewalk, steps, wheelchair ramp

1.0

90 or 95

  Parking lot

0.5

75 or 90

  Parking ramp

0.5 or 1.0

90 or 95

Public building

  Sidewalk, steps, wheelchair ramp

1.0

95

  Parking lot

0.5

90

  Parking ramp

1.0

95

K-12 school

  Sidewalk, steps, wheelchair ramp

1.0

90

  Parking lot

0.5

90

  Parking ramp

1.0

95

Fire/rescue station

  Sidewalk, steps, wheelchair ramp

1.0

95

  Parking lot

0.5

95

  Parking ramp

1.0

95

Hospital

  Sidewalk, steps, wheelchair ramp

1.0

95

  Parking lot

0.5

90 or 95

  Parking ramp

1.0

95

  MedEvac landing pad

1.0

99

Private landing pad/runway

1.0

90

Car wash aprons

1.0

90


To help avoid excessive sizing of snow-melting systems, Table 4 outlines typical free area ratios and frequency distributions based on application. However, these ratios should be considered general guidance only: each design should be considered on a case-by-case basis to meet the needs of that specific application.

 Example for Surface Heat Flux Calculation Using Table 1

Example 2.

Consider the design of a system for Albany, New York, which has an installed heat flux capacity at the top surface of approximately 149 Btu/h · ft2. Based on data in Table 1, this system will keep the surface completely free of snow 95% of the time. Because there are 156 snowfall hours in an average year, this design would have some accumulation of snow approximately 8 h per year (the remaining 5% of the 156 h). This design will also meet the load for more than 98% of the time (i.e., more than 153 of the 156 snowfall hours) at an area ratio of 0.5 and more than 99% of the time for an area ratio of 0. Ar = 0.5 means that there is a thin snow layer on part of the slab such that it acts as though half the slab is insulated by a snow layer; Ar = 0 means that the snow layer is sufficient to insulate the surface from heat and evaporation losses, but that snow is melting at the base of this layer at the same rate that it is falling on the top of the layer.

Therefore, the results for this system can be interpreted to mean the following (all times are rounded to the nearest hour):

  1. For all but 8 h of the year, the slab will be snow free.

  2. For the less than 5 h between the 95% and 98% nonexceedance values, there will be a thin build-up of snow on part of the slab.

  3. For the less than 2 h between the 98% and 99% nonexceedance values, snow will accumulate on the slab to a thickness at which the snow blanket insulates the slab, but the thickness will not increase beyond that level.

  4. For less than 2 h, the system cannot keep up with the snowfall.

An examination of the 100% column shows that to keep up with the snowfall the last 1% of the time, in this case less than 2 h for an average year, would require a system capacity of approximately 276 Btu/h · ft2; to attempt to keep the slab completely snow free the entire season requires a capacity of 321 Btu/h · ft2. Based on this interpretation, the designer and customer must decide the acceptable operating conditions. Note that the heat flux values in this example do not include back or edge losses, which must be added in sizing energy source and heat delivery systems.


 Sensitivity of Design Surface Heat Flux to Wind Speed and Surface Size

Some snow-melting systems are in sheltered areas, whereas others may be in locations where surroundings create a wind tunnel effect. Similarly, systems vary in size from the baseline characteristic length of 20 ft. For example, sidewalks exposed to a crosswind may have a characteristic length on the order of 5 ft. In such cases, the wind speed will be either less than or greater than the meteorological value Vmet used in Table 1. To establish the sensitivity of the surface heat flux to wind speed and characteristic length, calculations were performed at combinations of wind speeds 0.5Vmet, Vmet, and 2Vmet and L values of 5 ft and 20 ft for area ratios Ar of 1.0 and 0.5. Wind speed and system size do not affect the load values for Ar = 0 because the calculations assume that no heat or mass transfer from the surface occurs at this condition. Table 2 presents a set of mean values of multipliers that can be applied to the loads presented in Table 1; these multipliers were established by examining the effect on the 99% nonexceedance values. The ratio of V to Vmet in a given design problem may be determined from information given in Chapter 24 of the 2017 ASHRAE Handbook—Fundamentals. The closest ratio in Table 2 can then be selected. The designer is cautioned that these are to be used only as guidelines on the effect of wind speed and size variations.

 Back and Edge Heat Losses

The surface heat fluxes in Table 1 do not account for heat losses from the back and edges of the slab. Adlam (1950) demonstrated that these back and edge losses may vary from 4 to 50%, depending on factors such as slab construction, operating temperature, ground temperature, and back and edge insulation and exposure. With the construction shown in Figure 2 or Figure 5 and ground temperature of 40°F at a depth of 24 in., back losses in steady state are approximately 20%. Higher losses occur with (1) colder ground, (2) more cover over the slab, or (3) exposed back, such as on bridges or parking decks. Spitler et al. (2002) estimated back losses in transient operation to range between approximately 12 and 29%, depending on storm conditions. Adding a 2 in. insulation layer reduces back losses to approximately 1 to 3% for the same storm conditions. Spitler et al. (2001) include a more detailed report, and provide the source code needed to repeat an analysis for other specific cases.

Detail of Typical Hydronic Snow-Melting System

Figure 2. Detail of Typical Hydronic Snow-Melting System


 Transient Analysis of System Performance

Determination of snow-melting surface heat fluxes as described in Equations (1) to (14) is based on steady-state analysis. Snow-melting systems generally have heating elements embedded in material of significant thermal mass. Transient effects, such as occur when the system is started, may be significant. A transient analysis method was developed by Spitler et al. (2002) and showed that particular storm conditions could change the snow-melting surface heat flux requirement significantly, depending on the precipitation rate at a particular time in the storm. It is therefore difficult to find simple general design rules that account for transient effects. To keep slab surfaces clear from snow during the first hour of the snowstorm, when the system is just starting to operate, heat fluxes up to five times greater than those indicated by steady-state analysis could be required. In general, greater heat input is required for greater spacing and greater depth of the heating elements in the slab; however, because of transient effects, this is not always true.

Transient analysis (Spitler et al. 2002) has also been used to examine back and edge losses. Heat fluxes because of back losses in systems without insulation ranged from 10 to 30% of the surface heat flux, depending primarily on the particular storm data, though higher losses occurred where heating elements were embedded deeper in the slab. In cases where 2 in. of insulation was applied below the slab, back losses were significantly reduced, to 1 to 4%. Although peak losses were reduced, the surface heat fluxes required to melt the snow were not significantly affected by the presence of insulation, because transient effects at the start of system operation drive the peak design surface heat fluxes. Edge losses ranged from 15 to 35% of the heat delivered by the heating element nearest the edge. This may be converted to an approximately equivalent surface heat flux percentage by reducing the snow-melting surface length and width by an amount equal to two-thirds of the heating element spacing in the slab. Then the design surface heat flux may be adjusted by the ratio of the actual snow-melting surface area to the reduced surface area as described here. The effect of edge insulation was found to be similar to that at the back of the slab. Although edge insulation does not reduce the surface heat flux requirement significantly, increased snow accumulation at the edges should be expected.

 Annual Operating Data

Annual operating data for the cities in Table 1 are presented in Table 3. Melting and idling hours are summarized in this table along with the energy per unit area needed to operate the system during an average year based on calculations for the years 1982 to 1993. Back and edge heat losses are not included in the energy values in Table 3. Data are presented for snow-free area ratios of 1.0, 0.5, and 0.

The energy per unit area values are based on systems designed to satisfy the loads 99% of the time (i.e., at the levels indicated in the 99% column in Table 1) for each Ar value. The energy use for each melting hour is taken as either (1) the actual energy required to maintain the surface at 33°F or (2) the design output, whichever is less. The design snow-melting energy differs, of course, depending on whether the design is for Ar = 1.0, 0.5, or 0; therefore, the annual melting energy differs as well.

The idling hours include all non-snowfall hours when the ambient temperature is below 32°F. The energy consumption for each idling hour is based on either (1) the actual energy required to maintain the surface at 32°F or (2) the design snow-melting energy, whichever is less.

In Table 3, the column labeled “2% Min. Snow Temp.” is the temperature below which only 2% of the snowfall hours occur. This table should only be used to predict annual operating costs. Use Table 1 for system sizing.

 Annual Operating Cost Example

Example 3.

A snow-melting system of 2000 ft2 is to be installed in Chicago. The application is considered critical enough that the system is designed to remain snow free 99% of the time. Table 3 shows that the annual energy requirement to melt the snow is 8501 Btu/ft2. Assuming a fossil fuel cost of $8 per 106 Btu, an electric cost of $0.07 per kWh, and back loss at 30%, find and compare the annual cost to melt snow with hydronic and electric systems. For the hydronic system, boiler combustion efficiency is 0.85 and energy distribution efficiency is 0.90.

Solution: Operating cost O may be expressed as follows:

(15)

where

O = annual operating cost $/yr
At = total snow-melting area, ft2
Qa = annual snow-melting or idling energy requirement, Btu/ft2 or kWh/ft2
F = primary energy cost $/Btu or $/kWh
B = back heat loss percentage, %
ηb = combustion efficiency of boiler (or COP of a heat pump in heating mode), dimensionless. If a waste energy source is directly used for snow-melting or idling purposes, the combustion efficiency term is neglected.
ηd = energy distribution efficiency, dimensionless (in an electric system, efficiencies may be taken to be 1)

Operating cost for a hydronic system is

Operating cost for an electric system is

It is desirable to use waste or alternative energy resources to minimize operating costs. If available in large quantities, low-temperature energy resources may replace primary energy resources, because the temperature requirement is generally moderate (Kilkis 1995). Heat pipes may also be used to exploit ground heat (Shirakawa et al. 1985).


Table 5 Thermal Conductivity of Concrete Based on Concrete Density

Thermal Conductivity kc, Btu · in/h · ft2 · °F

Density, lb/ft3

4.43

100

5.42

110

6.61

120

8.08

130

9.87

140

12.1

150

Source: ACI (2014).


2. SLAB DESIGN

Either concrete or asphalt slabs may be used for snow-melting systems. The thermal conductivity of asphalt is less than that of concrete; pipe or electric cable spacing and required fluid temperatures are thus different. Hot asphalt may damage plastic or electric (except mineral-insulated cable) snow-melting systems unless adequate precautions are taken. Typically, hydronic pipes are embedded in a sand layer below the asphalt before it is laid. For specific recommendations, see the sections on Hydronic System Design and Electric System Design.

Concrete slabs containing hydronic or electric snow-melting apparatus must have a subbase, expansion-contraction joints, reinforcement, and drainage to prevent slab cracking; otherwise, crack-induced shearing or tensile forces could damage the pipe or cable. The pipe or cable must not run through expansion-contraction joints, keyed construction joints, or control joints (dummy grooves); however, the pipe or cable may be run under 0.12 in. score marks or saw cuts (block and other patterns). Sleeved pipe is allowed to cross expansion joints (see Figure 3). Control joints must be placed wherever the slab changes size or incline. The maximum distance between control joints for ground-supported slabs should be less than 15 ft, and the length should be no greater than twice the width, except for ribbon driveways or sidewalks. In ground-supported slabs, most cracking occurs during the early cure. Depending on the amount of water used in the concrete mix, shrinkage during cure may be up to 0.75 in. per 100 ft. If the slab is more than 15 ft long, the concrete does not have sufficient strength to overcome friction between it and the ground while shrinking during the cure period.

Analysis requiring the thermal conductivity of a concrete slab can be approximated based on the values in Table 5 or from Equation (16). This equation is based on the American Concrete Institute’s Guide to Thermal Properties of Concrete and Masonry Systems (ACI 2014).

(16)

Design of the concrete slab is ultimately the responsibility of the civil engineer. For general information purposes,

  • The concrete mix of the top layer should give maximum weatherability

  • Compressive strength should be 4000 to 5000 psi

  • Recommended slump is 3 in. maximum, 2 in. minimum

The pipe or cable may be placed in contact with an existing sound slab (either concrete or asphalt) and then covered as described in the sections on Hydronic System Design and Electric System Design. If there are signs of cracking or heaving, the slab should be replaced. Pipe or cable should not be placed over existing expansion-contraction, control, or construction joints. The finest grade of asphalt is best for the top course; stone diameter should not exceed 0.38 in.

A moisture barrier should be placed between any insulation and the fill. If insulation is used, it should be nonhygroscopic. The joints in the barrier should be sealed and the fill made smooth enough to eliminate holes or gaps for moisture transfer. Also, the edges of the barrier should be flashed to the surface of the slab to seal the ends.

Snow-melting systems should have good surface drainage. When the ambient air temperature is 32°F or below, runoff from melting snow freezes immediately after leaving the heated area. Any water that gets under the slab also freezes when the system is shutdown, causing extreme frost heaving. Runoff should be piped away in drains that are heated or below the frost line. If the snow-melting surface is inclined (e.g., a ramp), surface runoff may collect at the lowest point. In addition to effective drainage down the ramp, the adjacent area may require heating to prevent freezing the accumulated runoff.

The area to be protected by the snow-melting system must first be measured and planned. For total snow removal, hydronic or electric heat must cover the entire area. In larger installations, it may be desirable to melt snow and ice from only the most frequently used areas, such as walkways and wheel tracks for trucks and autos. Planning for separate circuits should be considered so that areas within the system can be heated individually, as required.

Where snow-melting apparatus must be run around obstacles (e.g., a storm sewer grate), the pipe or cable spacing should be uniformly reduced. Because some drifting will occur adjacent to walls or vertical surfaces, extra heating capacity should be provided in these areas, and if possible also in the vertical surface. Drainage flowing through the area expected to be drifted tends to wash away some snow.

3. HYDRONIC SYSTEM DESIGN

Hydronic system design includes selection of the following components: (1) heat transfer fluid, (2) piping, (3) fluid heater, (4) pump(s) to circulate the fluid, and (5) controls. With concrete slabs, thermal stress is also a design consideration.

 Heat Transfer Fluid

Various fluids, including brines, oils, and glycol/water solutions, are suitable for transferring heat from the fluid heater to the slab. Freeze protection is essential because most systems will not be operated continuously in subfreezing weather. Without freeze protection, power loss or pump failure could cause freeze damage to the piping and slab.

Brine is the least costly heat transfer fluid, but it has a lower specific heat than glycol. Using brine may be discouraged because of the cost of heating equipment that resists its corrosive potential. Although heat transfer oils are not corrosive, they are more expensive than brine or glycol, have a lower specific heat and higher viscosity, and are potentially flammable, and as such are no longer used in common practice.

Table 6 Steady-State Surface Heat Fluxes and Average Fluid Temperature for Hydronic Snow-Melting System in Figure 2 (Average fluid temperature based on 12 in. tube spacing)

s, Rate of Snowfall in/h

Ar

 

ta = 0°F

ta = 10°F

ta = 20°F

ta = 30°F

Wind Speed V, mph

Wind Speed V, mph

Wind Speed V, mph

Wind Speed V, mph

5

10

15

5

10

15

5

10

15

5

10

15

0.08

1.0

qo

166

222

272

138

180

217

108

135

159

76

86

94

tm

116

144

169

102

123

142

87

100

112

71

76

80

0.0

qo

67

67

67

65

65

65

63

63

63

61

61

61

tm

66

66

66

65

65

65

64

64

64

63

63

63

0.16

1.0

qo

233

289

339

203

244

282

171

197

221

136

146

155

tm

149

177

202

134

155

174

118

132

144

101

106

110

0.0

qo

133

133

133

129

129

129

125

125

125

121

121

121

tm

100

100

100

98

98

98

96

96

96

93

93

93

0.25

1.0

qo

308

363

414

275

317

354

241

268

292

204

214

223

tm

187

215

240

171

192

210

154

167

179

135

140

144

0.0

qo

208

208

208

202

202

202

195

195

195

189

189

189

tm

137

137

137

134

134

134

131

131

131

127

127

127

Note: Table based on a characteristic slab length of 20 ft, standard air pressure, a water film temperature of 33°F, and relative humidity of 80%. Heat flux and temperature values in bold underline are not achievable based on material temperature limits of concrete.

Ar = snow-free area ratio
qo = slab heating flux, Btu/h · ft2
ta = atmospheric dry-bulb temperature, °F
tm = average fluid temperature based on construction shown in Figure 2, °F


Glycols (ethylene glycol and propylene glycol) are the most popular in snow-melting systems because of their moderate cost, high specific heat, and low viscosity; ease of corrosion control is another advantage. Automotive glycols containing silicates are not recommended because they can cause fouling, pump seal wear, fluid gelation, and reduced heat transfer. The piping should be designed for periodic addition of an inhibitor. Glycols should be tested annually to determine any change in reserve alkalinity and freeze protection. Only inhibitors obtained from the manufacturer of the glycol should be added. Heat exchanger surfaces should be kept below 285°F, which corresponds to about 40 psig steam. Temperatures above 300°F accelerate deterioration of the inhibitors.

Because ethylene glycol and petroleum distillates are toxic, no permanent connection should be installed between the snow-melting system and the drinking water supply. Gordon (1950) discusses precautions concerning internal corrosion, flammability, toxicity, cleaning, joints, and hook-up that should be taken during installation of hydronic piping. The properties of brine and glycol are discussed in Chapter 31 of the 2017 ASHRAE Handbook—Fundamentals. The effect of glycol on system performance is detailed in Chapter 13 of the 2020 ASHRAE Handbook—HVAC Systems and Equipment.

 Piping

Historically, piping may have been metal or ethylene-propylene terpolymer (EPDM), though cross-linked polyethylene (PEX) is typically used today.

Chapman (1952) derived the equation for the fluid temperature required to provide an output qo. For construction as shown in Figure 2, the equation is

(17)

where tm = average fluid (antifreeze solution) temperature, °F. Equation (16) applies to 1 in. as well as 3/4 in. IPS pipe (Figure 2).

Design information about heated slabs given in Chapter 6 of the 2020 ASHRAE Handbook—HVAC Systems and Equipment may be used for all other types of slab construction, pipe spacing, and pipe material. In using these design equations, snow cover or water film on the slab may be treated as surface covers.

Table 7 Typical Dependency of Maximum Heat Flux Deliverable by Plastic Pipes on Pipe Spacing and Concrete Overpour (Mean fluid temperature = 130°F)

Heat Flux, Btu/h · ft2

Pipe Spacing on Centers, * in.

140

12

175

9

210

6

* Space pipes 1 in. closer for each 1 in. of concrete cover over 2 in. Space pipes 2 in. closer for each 1 in. of brick paver and mortar.


For specific conditions or for cities other than those given in Table 1, Equations (1) and (16) are used. Table 6 gives solutions to these equations at a relative humidity of 80%. Splitting the surface heat flux among four components as in Equation (1) also affects the required water temperature; therefore, Equation (16) and Table 5 should be used with caution. Table 5 may also be used to determine successful systems operation conditions. For example, if a system as shown in Figure 2 is designed for 250 Btu/h · ft2, it will satisfy eight severe snow conditions such as 10°F, 0.16 in./h, and 10 mph wind speed (Chapman 1999).

Satisfactory standard practice is to use 3/4 in. pipe or tube on 9 in. centers, unless the snow-melting surface heat flux is too high. If pumping loads require reduced friction, circuit lengths can be reduced. Piping should be supported by a minimum of 2 in. of concrete above. This requires a 5 in. slab for 3/4 in. pipe.

Plastic Pipe. Plastic (polyethylene [PE], cross-linked polyethylene [PEX]), or multilayer pipe such as PEX-AL-PEX (a PEX inner and outer layer with a middle layer of aluminum) is popular because of lower material cost, lower installation cost, and corrosion resistance. Typical PEX pipe diameters for snow-melting applications are 5/8, 3/4, and 1 in. nominal diameter (CTS) as per ASTM Standard F876. Considerations when using plastic pipe include stress crack resistance, temperature limitations, and thermal conductivity. Heat transfer oils should not be used with plastic pipe.

Plastic pipe is furnished in coils. Smaller pipe can be bent to form a variety of heating panel designs without elbows or joints. Mechanical compression connections can be used to connect heating panel pipe to the larger supply and return piping leading to the pump and fluid heater, typically supplied by a distribution manifold where circuits can be balanced according to differences in length and associated pressure drop. PE pipe may be fused using appropriate fittings and fusion equipment. Fusion joining eliminates metallic components and thus the possibility of corrosion in the piping; however, it requires considerable installation training.

When plastic pipe is used, the system must be designed so that the fluid temperature required will not damage the pipe. If a design requires a temperature above the tolerance of plastic pipe, the delivered heat flux will never meet design requirements. The PE temperature limit is typically 140°F. For PEX, the temperature is 200°F (up to 80 psi) sustained fluid temperature, or 180°F (up to 100 psi). However, the entering water temperature for the concrete is typically the constraint: it usually must be less than 150°F, or the value specified in the relevant standard (e.g., CSA Standard A23). A potential solution to temperature limitations is to decrease the pipe spacing or depth. Closer pipe spacing also helps eliminate striping of snow (unmelted portions between adjacent pipe projections on the surface). Adlam (1950) addresses the parameter of pipe size and the effect of pipe spacing on heat output. A typical solution is summarized in Table 7, which shows a way of designing pipe spacing according to flux requirements.

Oxygen permeation (see DIN Standard 4726 for typical permeation values) through plastic pipes may lead to corrosion on metal surfaces in the entire system unless plastic pipes are equipped with an oxygen barrier layer. Otherwise, either a heat exchanger must separate the plastic pipe circuitry from the rest of the system or corrosion-inhibiting additives must be used in the entire hydronic system.

Pipe Installation. It is good design practice to avoid passing any embedded piping through a concrete expansion joint; otherwise, the pipe may be stressed and possibly ruptured. Figure 3 shows a method of protecting piping that must pass through a concrete expansion joint from stress under normal conditions.

Piping Details for Concrete Construction for Metal and Fibrous Expansion Joints

Figure 3. Piping Details for Concrete Construction for Metal and Fibrous Expansion Joints


After pipe installation, but before slab installation, all piping should be air-tested to about 100 psig. This pressure should be maintained until all welds and connections have been checked for leaks. Isolate the air pressure test to manifold and piping, because boilers or other energy-converting, accumulating, or conditioning equipment may have lower pressure test limits. For example, boilers normally have an air test capability of 30 psi. Testing should not be done with water because (1) small leaks may not be observed during slab installation; (2) water leaks may damage the concrete during installation; (3) the system may freeze before antifreeze is added; and (4) it is difficult to add antifreeze when the system is filled with water.

Air Control. Because introducing air causes deterioration of the antifreeze, the piping should not be vented to the atmosphere. It should be divided into smaller zones to facilitate filling and allow isolation when service is necessary.

Air can be eliminated from piping during initial filling by pumping the antifreeze from an open container into isolated zones of the piping. A properly sized pump and piping system that maintains adequate fluid velocity, together with an air separator and expansion tank, will keep air from entering the system during operation.

A strainer, sediment trap, or other means for cleaning the piping system may be provided. It should be placed in the return line ahead of the heat exchanger and must be cleaned frequently during initial system operation to remove scale and sludge. A strainer should be checked and cleaned, if necessary, at the start of and periodically during each snow-melting season.

An ASME safety relief valve of adequate capacity should be installed on a closed system.

 Fluid Heater

The heat transfer fluid can be heated using any of a variety of energy sources, depending on availability. A fluid heater can use steam, hot water, gas, oil, or electricity. In some applications, heat may be available from secondary sources, such as engine generators, condensate, and other waste heat sources. Other low-temperature waste, or alternative energy resources may also be used with or without heat pumps or heat pipes. In a district heating system, the snow-melting system may be tied to the return piping of the district, which increases the overall temperature drop in the district heating system (Brown 1999).

Design of the fluid heater should follow standard practice, with adjustments for the film coefficient. Consideration should be given to flue gas condensation and thermal shock in boilers because of low fluid temperatures. Bypass flow and temperature controls may be necessary to maintain recommended boiler temperatures. Boilers should be derated for high-altitude applications.

 Thermal Stress

Chapman (1955) and Kilkis (1994) discuss the problems of thermal stress in a concrete slab. In general, thermal stress will cause no problems if the following installation and operation rules are observed:

  • Minimize the temperature difference between the fluid and the slab surface by maintaining (1) close pipe spacing (see Figure 2), (2) a low temperature differential in the fluid (less than 30°F), and (3) continuous operation (if economically feasible). According to Shirakawa et al. (1985), the temperature difference between the slab surface and the heating element skin should not exceed 70°F during operation.

  • Install pipe within about 2 in. of the surface.

  • Use reinforcing steel designed for thermal stress if high structural loads are expected (e.g., on highways).

Thermal shock to the slab may occur if heated fluid is introduced from a large source of residual heat such as a storage tank, a large piping system, or another snow-melting area. The slab should be brought up to temperature by maintaining the fluid temperature differential at less than 35°F.

Heated concrete slab creates temperature gradients, which in turn causes tensile stress. When tensile stress exceeds the concrete’s tensile strength, thermal cracking results. Figure 4 shows the maximum allowable temperature difference based on properties of concrete calculated per ACI (2014) guidelines.

Relationship Between Concrete Compressive Strength and Maximum Allowable Temperature Difference

Figure 4. Relationship Between Concrete Compressive Strength and Maximum Allowable Temperature Difference


In a heated slab, the largest temperature difference occurs between the heating element skin td and slab surface tmax. The temperature difference (td − tmax) must be less than the maximum allowable temperature difference to prevent concrete damage. The designer should apply a safety factor to further ensure the integrity of the concrete slab and system design. Ultimately, the design of the concrete slab should be the responsibility of the civil engineer of record.

(18)

(19)

(20)

(21)

(22)

(23)

(24)

(25)

where

Ar = snow-free ratio, dimensionless
Do = outside diameter of heating element, ft
hf = coefficient of surface heat loss intensity, Btu/h · ft2 · °F
k = thermal conductivity of material in which heating element is embedded, Btu/h · ft2 · °F
ke = equivalent thermal conductivity of composite slab for lateral heat diffusion, Btu/h · ft2 · °F
kfilm = thermal conductivity of film of melted snow, Btu/h · ft2 · °F
kh = thermal conductivity of heating element, Btu/h · ft2 · °F
ki = thermal conductivity of each material layer on top of slab, Btu/h · ft2 · °F
L = distance from center of heating element to surface of slab, ft
M = embedded heating element spacing on centers, in.
m = fin coefficient, ft−1
ni = number of layers above heated slab, dimensionless
qe = evaporative heat loss intensity during snowfall, Btu/h · ft2
qf = total surface heat loss intensity, Btu/h · ft2
qh = radiation and convention heat loss intensity during snowfall, Btu/h · ft2
qo = design heat load intensity, Btu/h · ft2
Rco = total thermal resistance of layers above slab, h · ft2 · °F/Btu
Si = thickness of each material layer on top of slab, ft
ta = air temperature at snowfall, °F
td = heating element surface temperature, °F
tmax = maximum slab surface temperature, °F
∇T = temperature gradient, dimensionless
ttotal = distance from center of heating element to surface, including thickness of water film, ft
W = half of net spacing between adjacent heating elements (M − Do)/2, ft
η = fin efficiency of composite fin, dimensionless

Example 4.

Determine the maximum temperature difference for a 5 in. concrete slab with the following properties: compressive strength ~5000 psi; density: ~150 lb/ft3; conductivity kc ~ 1.01 Btu/h · ft · °F. Pipe outside diameter is 0.75 in., pipe spacing 12 in. on center; pipe depth 2 in. below slab.

Parameters from Example 1:

0.0625 ft
ta = 17°F
tp = 33°F
kfilm = 0.31 Btu/h · ft · °F
qh = 83.5 Btu/h · ft2
qe = 51.3 Btu/h · ft2
qf = 134.8 Btu/h · ft2
qo = 214.0 Btu/h · ft2
Do =
L = 2.375 in. = 0.1979 ft
M = 1 ft
W = (1 ‣ 0.0625)/2 = 0.4688 ft(
(keTtotal) = 0.4872 Btu/h · °F, by Equation (19)
hf = 8.4 Btu/h · ft2 · °F, by Equation (20)
m = 4.16 ft−1, by Equation (21)
η = 0.49, by Equation (22)
Rco = [1/16 in./12kfilm+ (0.5 in./12kc)] = 0.058 h · ft2 · °F/Btu; by Equation (23)
tmax = 47.7°F, by Equation (24)
td = 95.3°F, by Equation (25)
(td − tmax) = (95.3 − 47.5) = 47.8°F


The maximum allowable temperature difference for concrete with a 5000 psi compressive strength is about 73°F; therefore, (td − tmax) is well within concrete’s strength.

4. ELECTRIC SYSTEM DESIGN

Snow-melting systems using electricity as an energy source have heating elements in the form of (1) mineral-insulated (MI) cable, (2) self-regulating cable, (3) constant-wattage cable, or (4) high-intensity infrared heaters.

 Heat Flux

The basic load calculations for electric systems are the same as presented in the section on Snow-Melting Heat Flux Requirement. However, because electric system output is determined by the resistance installed and the voltage impressed, it cannot be altered by fluid flow rates or temperatures. Consequently, neither safety factors nor marginal capacity systems are design considerations.

Heat flux within a slab can be varied by altering the heating cable spacing to compensate for anticipated drift areas or other high-heat-loss areas. Power density should not exceed 120 W/ft2 (NFPA Standard 70).

 Electrical Equipment

Installation and design of electric snow-melting systems is governed by Article 426 of the National Electrical Code® (NEC, or NFPA Standard 70), which requires that each electric snow-melting circuit (except mineral-insulated, metal-sheathed cable embedded in a noncombustible medium) be provided with a ground fault protection device. An equipment protection device (EPD) with a trip level of 30 mA should be used to reduce the likelihood of nuisance tripping.

Double-pole, single-throw switches or tandem circuit breakers should be used to open both sides of the line. The switchgear may be in any protected, convenient location. It is also advisable to include a pilot lamp on the load side of each switch so that there is a visual indication when the system is energized.

Junction boxes located at grade level are susceptible to water ingress. Weatherproof junction boxes installed above grade should be used for terminations.

The power supply conduit is run underground, outside the slab, or in a prepared base. With concrete slab, this conduit should be installed before the reinforcing mesh.

 Mineral-Insulated Cable

Mineral-insulated (MI) heating cable is a magnesium oxide (MgO)-filled, die-drawn cable with one or two copper or copper alloy conductors and a seamless copper or stainless steel alloy sheath. Copper sheath versions are usually protected from salts and other chemicals by a polyvinyl chloride (PVC) or high-density polyethylene jacket.

Cable Layout. To determine the characteristics of the MI heating cable needed for a specific area, the following must be known:

  • Heated area size

  • Power density required

  • Voltage(s) available

  • Approximate cable length needed

To find the approximate MI cable length, estimate 2 ft of cable per square foot of concrete. This corresponds to 6 in. on-center spacing. Actual cable spacing will vary between 3 and 9 in. for proper power density.

Cable spacing is dictated primarily by the heat-conducting ability of the material in which the cable is embedded. Concrete has a higher heat transmission coefficient than asphalt, permitting wider cable spacing. The following is a procedure to select the proper MI heating cable:

  1. Determine total power required for each heated slab.

    (26)

  2. Determine total resistance.

    (27)

  3. Calculate cable resistance per foot.

    (28)

    where

    W = total power needed, W
    A = heated area of each heated slab, ft2
    w = required power density input, W/ft2
    R = total resistance of cable, Ω
    E = voltage available, V
    r1 = calculated cable resistance, Ω per foot of cable
    L1 = estimated cable length, ft
    L = actual cable length needed, ft
    r = actual cable resistance, Ω/ft
    M = cable on-center spacing, in.
    I = total current per MI cable, A

    Commercially available mineral-insulated heating cables have actual resistance values (if there are two conductors, the value is the total of the two resistances) ranging from 0.0016 to 0.6 Ω/ft. Manufacturing tolerances are ±10% on these values. MI cables are die-drawn, with the internal conductor drawn to size indirectly by pressures transmitted through the mineral insulation.

  4. From manufacturers’ literature, choose a cable with a resistance r closest to the calculated r1. Note that r is generally listed at ambient room temperature. At the specific temperature, r may drift from the listed value. It may be necessary to make a correction as described in Chapter 6 of the 2020 ASHRAE Handbook—HVAC Systems and Equipment.

  5. Determine the actual cable length needed to give the wattage desired.

    (29)

  6. Determine cable spacing within the heated area.

    (30)

    For optimum performance, heating cable spacing should be within the following limits: in concrete, 3 to 9 in.; in asphalt, 3 to 6 in.

    Because the manufacturing tolerance on cable length is ±1%, and installation tolerances on cable spacing must be compatible with field conditions, it is usually necessary to adjust the installed cable as the end of the heating cable is rolled out. Cable spacing in the last several passes may have to be altered to give uniform heat distribution.

    The installed cable within the heated areas follows a serpentine path originating from a corner of the heated area (Figure 5). As heat is conducted evenly from all sides of the heating cable, cables in a concrete slab can be run within half the spacing dimension of the perimeter of the heated area.

  7. Determine the current required for the cable.

    (31)

  8. Choose cold-lead cable as dictated by typical design guidelines and local electrical codes (see Table 8).

Typical Mineral Insulated Heating Cable Installation in Concrete Slab

Figure 5. Typical Mineral Insulated Heating Cable Installation in Concrete Slab


Cold-Lead Cable. Every MI heating cable is factory-fabricated with a non-heat-generating cold-lead cable attached. The cold-lead cable must be long enough to reach a dry location for termination and of sufficient wire gage to comply with local and NEC standards. The NEC requires a minimum cold-lead length of 6 in. within the junction box. MI cable junction boxes must be located such that the box remains dry and at least 3 ft of cold-lead cable is available at the end for any future service (Figure 5). Preferred junction box locations are indoors; on the side of a building, utility pole, or wall; or inside a manhole on the wall. Boxes should have a hole in the bottom to drain condensation. Outdoor boxes should be completely watertight except for the condensation drain hole. Where junction boxes are mounted below grade, the cable end seals must be coated with an epoxy to prevent moisture entry. Cable end seals should extend into the junction box far enough to allow the end seal to be removed if necessary.

Table 8 Mineral-Insulated Cold-Lead Cables (Maximum 600 V)

Single-Conductor Cable

Two-Conductor Cable

Current Capacity, A

American Wire Gage

Current Capacity, A

American Wire Gage

35

14

25

14/2

40

12

30

12/2

55

10

40

10/2

80

8

55

8/2

105

6

75

6/2

140

4

95

4/2

165

3

  

190

2

  

220

1

  

Source: National Electrical Code® (NFPA Standard 70).


Although MgO, the insulation in MI cable, is hygroscopic, the only vulnerable part of the cable is the end seal. However, should moisture penetrate the seal, it can easily be detected with a megohmmeter and driven out by applying a torch 2 to 3 ft from the end and working the flame toward the end.

Installation. When MI electric heating cable is installed in a concrete slab, the slab may be poured in one or two layers. In single-pour application, the cable is hooked on top of the reinforcing mesh before the pour is started. In two-layer application, the cable is laid on top of the bottom structural slab and embedded in the finish layer. For a proper bond between layers, the finish slab should be poured within 24 h of the bottom slab, and a bonding grout should be applied. The finish slab should be at least 2 in. thick. Cable should not run through expansion, control, or dummy joints (score or groove). If the cable must cross such a joint, it should cross the joint as few times as possible and be protected at the point of crossing with RTV rubber and a 1 by 1 by 12 in. angle iron as shown in Figure 5.

The cable is uncoiled from reels and laid as described in the section on Cable Layout. Prepunched copper or stainless steel spacing strips are often nailed to the lower slab for uniform spacing.

A high-density polyethylene (HDPE) or polyvinyl chloride (PVC) jacket is extruded by the manufacturer over the cable to protect from chemical damage and to protect the cable from physical damage without adding excessive thermal insulation.

If unjacketed MI cables are used, calcium chloride or other chloride additives should not be added to a concrete mix in winter because chlorides are destructive to copper. Cinder or slag fill under snow-melting slabs should also be avoided. The cold-lead cable should exit the slab underground in suitable conduits to prevent physical and chemical damage.

In asphalt slabs, the MI cable is fixed in place on top of the base pour with prepunched stainless steel strips or 6 in. by 6 in. wire mesh. A coat of bituminous binder is applied over the base and the cable to prevent them from floating when the top layer is applied. The layer of asphalt over the cable should be 1.5 to 3 in. thick (Figure 6).

Typical Section, Mineral-Insulated Heating Cable in Asphalt (Potter 1967—ASHRAE Journal)

Figure 6. Typical Section, Mineral-Insulated Heating Cable in Asphalt (Potter 1967—ASHRAE Journal)


Testing. Mineral-insulated heating cables should be thoroughly tested before, during, and after installation to ensure they have not been damaged either in transit or during installation.

Because MgO insulation is hygroscopic, damage to the cable sheath is easily detectable with a 500 V field megohmmeter. Cable insulation resistance should be measured on arrival of the cable. Cable with insulation resistance of less than 20 MΩ should not be used. Cable that shows a marked loss of insulation resistance after installation should be investigated for damage. Cable should also be checked for electrical continuity.

 Self-Regulating Cable

Self-regulating heating cables consist of two parallel conductors embedded in a heating core made of conductive polymer. These cables automatically adjust their power output to compensate for local temperature changes. Heat is generated as electric current passes through the core between the conductors. As the slab temperature drops, the number of electrical paths increases, and more heat is produced. Conversely, as the slab temperature rises, the core has fewer electrical paths, and less heat is produced.

Power output of self-regulating cables may be specified as watts per unit length at a particular temperature or in terms of snow-melting performance at a given cable spacing. In typical slab-on-grade applications, adequate performance may be achieved with cables spaced up to 12 in. apart. Narrower cable spacings may be required to achieve the desired snow-melting performance. The parallel construction of the self-regulating cable allows it to be cut to length in the field without affecting the rated power output.

Layout. For uniform heating, the heating cable should be arranged in a serpentine pattern that covers the area with 12 in. on-center spacing (or alternative spacing determined for the design). The heating cable should not be routed closer than 4 in. to the edge of the slab, drains, anchors, or other material in the concrete.

Crossing expansion, control, or other slab joints should be avoided. Self-regulating heating cables may be crossed or overlapped as necessary. Because the cables limit power output locally, they will not burn out.

Both ends of the cable should terminate in an aboveground weatherproof junction box. Junction boxes installed at grade level are susceptible to water ingress. An allowance of heating cable should be provided at each end for termination.

The maximum circuit length published by the manufacturer for the cable type should be respected to prevent tripping of circuit breakers. Use ground fault circuit protection as required by national and local electrical codes.

Installation. Figure 7 shows a typical self-regulating cable installation. The procedure for installing a self-regulating system is as follows:

  1. Hold a project coordination meeting to discuss the role of each trade and contractor. Good coordination helps ensure a successful installation.

  2. Attach the heating cable to the concrete reinforcing steel or wire mesh using plastic cable ties at approximately 12 in. intervals. Reinforcing steel or wire mesh is necessary to ensure that the slab is structurally sound and that the heating cable is installed at the design depth.

  3. Test the insulation resistance of the heating cable using a 2500 V dc megohmmeter connected between the braid and the two bus wires. Readings of less than 20 MΩ indicate cable jacket damage. Replace or repair damaged cable sections before the slab is poured.

  4. Pour the concrete, typically in one layer. Take precautions to protect the cable during the pour. Do not strike the heating cable with sharp tools or walk on it during the pour.

  5. Terminate one end of the heating cable to the power wires, and seal the other end using connection components provided by the manufacturer.

Typical Self-Regulating Cable Installation

Figure 7. Typical Self-Regulating Cable Installation


 Constant-Wattage Systems

In a constant-wattage system, the resistance elements may consist of a length of copper wire or alloy with a given amount of resistance. When energized, these elements produce the required amount of heat. Witsken (1965) describes this system in further detail.

Elements are either solid-strand conductors or conductors wrapped in a spiral around a nonconducting fibrous material. Both types are covered with a layer of insulation such as PVC or silicone rubber.

The heat-generating portion of an element is the conductive core. The resistance is specified in ohms per linear foot of core. Alternately, a manufacturer may specify the wire in terms of watts per foot of core, where the power is a function of the resistance of the core, the applied voltage, and the total length of core. As with MI cable, the power output of constant-wattage cable does not change with temperature.

Considerations in the selection of insulating materials for heating elements are power density, chemical inertness, application, and end use. Polyvinyl chloride is the least expensive insulation and is widely used because it is inert to oils, hydrocarbons, and alkalies. An outer covering of nylon is often added to increase its physical strength and to protect it from abrasion. The linear power density of embedded PVC is limited to 5 W/ft. Silicone rubber is not inert to oils or hydrocarbons. It requires an additional covering (metal braid, conduit, or fiberglass braid) for protection. This material can dissipate heat of up to 10 W/ft.

Lead can be used to encase resistance elements insulated with glass fiber. The lead sheath is then covered with a vinyl material. Output is limited to approximately 10 W/ft by the PVC jacket.

Polytetrafluoroethylene (PTFE) has good physical and electrical properties and can be used at temperatures up to 500°F.

Low-power-density (less than 10 W/ft) resistance wires may be attached to plastic or fiber mesh to form a mat unit. Prefabricated factory-assembled mats are available in a variety of watt densities for embedding in specified paving materials to match desired snow-melting capacities. Mats of lengths up to 60 ft are available for installation in asphalt sidewalks and driveways.

Preassembled heating mats of appropriate widths are also available for stair steps. Heating mats are seldom made larger than 60 ft2, because larger ones are more difficult to install, both mechanically and electrically. With a series of cuts, in the plastic or fiber mesh heating mats can be tailored to follow contours of curves and fit around objects, as shown in Figure 8. Extreme care should be exercised to prevent damage to the heater wire (or lead) insulation during this operation.

Mats should be installed 1.5 to 3.0 in. below the finished surface of asphalt or concrete. Installing mats deeper decreases the snow-melting efficiency. Only mats that can withstand hot-asphalt compaction should be used for asphalt paving.

Shaping Heating Mats Around Curves and Obstacles

Figure 8. Shaping Heating Mats Around Curves and Obstacles


Layout. Heating wires should be long enough to fit between the concrete slab dummy groove control or construction joints. Because concrete forms may be inaccurate, 2 to 4 in. of clearance should be allowed between the edge of the concrete and the heating wire. Approximately 4 in. should be allowed between adjacent heating wires at the control or construction joints.

For asphalt, the longest wire or largest heating mat that can be used on straight runs should be selected. The mats must be placed at least 12 in. in from the slab edge. Adjacent mats must not overlap. Junction boxes should be located so that each accommodates the maximum number of mats. Wiring must conform to requirements of the NEC (NFPA Standard 70). It is best to position junction boxes adjacent to or above the slab.

 Installation

General

  1. Check the wire or heating mats with an ohmmeter before, during, and after installation.

  2. Temporarily lay the mats in position and install conduit feeders and junction boxes. Leave enough slack in the lead wires to permit temporary removal of the mats during the first pour. Carefully ground all leads using the grounding braids provided.

  3. Secure all splices with approved crimped connectors or set screw clamps. Tape all of the power splices with plastic tape to make them waterproof. All junction boxes, fittings, and snug bushings must be approved for this class of application. The entire installation must be completely waterproof to ensure trouble-free operation.

In Concrete

  1. Pour and finish each slab area between the expansion joints individually. Pour the base slab and rough level to within 1.5 to 2 in. of the desired finish level. Place the mats in position and check for damage.

  2. Pour the top slab over the mats while the rough slab is still wet, and cover the mats to a depth of at least 1.5 in., but not more than 2 in.

  3. Do not walk on the mats or strike them with shovels or other tools.

  4. Except for brief testing, do not energize the mats until the concrete is completely cured.

In Asphalt

  1. Pour and level the base course. If units are to be installed on an existing asphalt surface, clean it thoroughly.

  2. Apply a bituminous binder course to the lower base, install the mats, and apply a second binder coating over the mats. The finish topping over the mats should be applied in a continuous pour to a depth of 1.25 to 1.5 in. Note: Do not dump a large mass of hot asphalt on the mats because the heat could damage the insulation.

  3. Check all circuits with an ohmmeter to be sure that no damage occurred during the installation.

  4. Do not energize the system until the asphalt has completely hardened.

 Infrared Snow-Melting Systems

Although overhead infrared systems can be designed specifically for snow-melting and freeze protection, they are usually installed for additional features they offer. Infrared systems provide comfort heating, which is particularly useful at entrances of plants, office buildings, and hospitals or on loading docks. Infrared lamps can improve a facility’s security, safety, and appearance. These additional benefits may justify the somewhat higher cost of infrared systems.

Infrared fixtures can be installed under entrance canopies, along building facades, and on freestanding poles. Approved equipment is available for recessed, surface, and pendant mounting.

Infrared Fixture Layout. The same infrared fixtures used for comfort heating installations (as described in Chapter 16 of the 2020 ASHRAE Handbook—HVAC Systems and Equipment) can be used for snow-melting systems. The major differences are in the orientation of the target area: whereas in comfort applications, the vertical surfaces of the human body constitute the target of irradiation, in snow-melting applications, a horizontal surface is targeted. When snow melting is the primary design concern, fixtures with narrow beam patterns confine the radiant energy within the target area for more efficient operation. Asymmetric reflector fixtures, which aim the thermal radiation primarily to one side of the fixture centerline, are often used near the periphery of the target area.

Infrared fixtures usually have a longer energy pattern parallel to the long dimension of the fixture than at right angles to it (Frier 1965). Therefore, fixtures should be mounted in a row parallel to the longest dimension of the area. If the target area is 8 ft or more in width, it is best to locate the fixtures in two or more parallel rows. This arrangement also provides better comfort heating because radiation is directed across the target area from both sides at a more favorable incident angle.

Radiation Spill. An ideal energy distribution is uniform throughout the snow-melting target area at a density equal to the design requirement. The design of heating fixture reflectors determines the percentage of the total fixture radiant output scattered outside the target area design pattern.

Even the best-controlled beam fixtures do not produce a completely sharp cutoff at the beam edges. Therefore, if uniform distribution is maintained for the full width of the area, a considerable amount of radiant energy falls outside the target area. For this reason, infrared snow-melting systems are designed so that the power density on the slab begins to decrease near the edge of the area (Frier 1964). This design procedure minimizes stray radiant energy losses.

Figure 9 shows the power densities obtained in a sample snow-melting problem (Frier 1965). The sample design average is 45 W/ft2. It is apparent that the incident power density is above the design average value at the center of the target area and below average at the periphery. Figure 9 shows how the power density and distribution in the snow-melting area depend on the number, wattage, beam pattern, and mounting height of the heaters, and on their position relative to the slab (Frier 1964).

Typical Power Density Distribution for Infrared Snow-Melting System 8 by 15 ft target area, four single-element quartz lamps located 10 ft above floor (Potter 1967).

Figure 9. Typical Power Density Distribution for Infrared Snow-Melting System 8 by 15 ft target area, four single-element quartz lamps located 10 ft above floor (Potter 1967).


With distributions similar to the one in Figure 9, snow begins to collect at the edges of the area as the energy requirements for snow melting approach or exceed system capacity. As snowfall lessens, the snow at the edges of the area and possibly beyond is then melted if the system continues to operate.

Target Area Power Density. Theoretical target area power densities for snow melting with infrared systems are the same as those for commercial applications of constant-wattage systems except that back and edge heat losses are smaller. However, note that theoretical density values are for radiation incident on the slab surface, not that emitted from the lamps. Merely multiplying the recommended snow-melting power density by the slab area to obtain the total power input for the system does not result in good performance. Experience has shown that multiplying this product by a correction factor of 1.6 gives a more realistic figure for the total required power input. The resulting wattage compensates not only for the radiant inefficiency involved, but also for the radiation falling outside the target area. For small areas, or when the fixture mounting height exceeds 16 ft, the multiplier can be as large as 2.0; large areas with sides of approximately equal length can have a multiplier of about 1.4.

The point-by-point method is the best way to calculate the fixture requirements for an installation. This method involves dividing the target area into 1 ft squares and adding the radiant energy from each infrared fixture incident on each square (Figure 9). The radiant energy distribution of a given infrared fixture can be obtained from the equipment manufacturer and should be followed for that fixture size and placement.

With infrared energy, the target area can be preheated to snow-melting temperatures in 20 to 30 min, unless the air temperature is well below 20°F or wind velocity is high (Frier 1965). This short warm-up time makes it unnecessary to turn on the system before snow begins to fall. The equipment can be turned on either manually or with a snow detector. A timer is sometimes used to turn the system off 4 to 6 h after snow stops falling, allowing time for the slab to dry completely.

If snow is allowed to accumulate before the infrared system is turned on, there will be a delay in clearing the slab, as with embedded hydronic or electric systems. Because infrared energy is absorbed in the top layer of snow rather than by the slab surface, the time needed depends on snow depth and on atmospheric conditions. Generally, a system that maintains a clear slab by melting 1 in. of snow per hour as it falls requires 1 h to clear 1 in. of accumulated snow under the same conditions.

To ensure maximum efficiency, fixtures should be cleaned at least once a year, preferably at the beginning of the winter season. Other maintenance requirements are minimal.

 Snow Melting in Gutters and Downspouts

Electrical heating cables are used to prevent heavy snow and ice accumulation on roof overhangs and to prevent ice dams from forming in gutters and downspouts (Lawrie 1966). Figure 10 shows a typical cable layout for protecting a roof edge and downspout. Cable for this purpose is generally rated at approximately 6 to 16 W/ft, and about 2.5 ft of wire is installed per linear foot of roof edge. One foot of heated wire per linear foot of gutter or downspout is usually adequate.

Typical Insulated Wire Layout to Protect Roof Edge and Downspout

Figure 10. Typical Insulated Wire Layout to Protect Roof Edge and Downspout


If the roof edge or gutters (or both) are heated, downspouts that carry away melted snow and ice must also be heated. A heated length of cable (weighted, if necessary) is dropped inside the downspout to the bottom, even if it is underground.

Lead wires should be spliced or plugged into the main power line in a waterproof junction box, and a ground wire should be installed from the downspout or gutter. Ground fault circuit protection is required per the NEC (NFPA Standard 70).

The system can be controlled with a moisture/temperature controller, ambient thermostat, or manual control. The moisture/temperature controller is the most energy efficient. If manual control is used, a protective thermostat should also be used to prevent system operation at ambient temperatures above 41°F.

5. CONTROL

 Automated Controls

Manual operation, where an operator must activate and deactivate the system when snow falls, does not comply with current energy standards such as ASHRAE Standard 90.1 and is not recommended. ASHRAE Standard 90.1-2016 requires that snow and ice melting systems include automatic controls that can shut off the systems when the pavement temperature is above 50°F and no precipitation is falling, and an automatic or manual control that allows shutoff when the outdoor temperature is above 40°F so that the potential for snow or ice accumulation is negligible.

In addition, hydronic systems require fluid temperature control for safety and for component longevity. Slab stress and temperature limits of the heat transfer fluid, pipe components, and fluid heater need to be considered. Some nonmetallic pipe materials should not be subjected to temperatures above 140°F. If the primary control fails, a secondary fluid temperature sensor should deactivate the snow-melting system and possibly activate an alarm.

 Control Selection

Automatic controls provide satisfactory operation by activating the system when light snow starts, allowing adequate warm-up before heavy snowfall develops. Automatic deactivation reduces operating costs.

Snow Detectors. Snow detectors monitor precipitation and temperature. They allow operation only when snow is present and may incorporate a delay-off timer. Snow detectors located in the heated area activate the snow-melting system when precipitation (snow) occurs at a temperature below the preset slab temperature (usually 40°F). Another type of snow detector is mounted above ground, adjacent to the heated area, without cutting into the existing system; however, it does not detect tracked or drifting snow. Both types of sensors should be located so that they are not affected by overhangs, trees, blown snow, or other local conditions.

Slab Temperature Sensor. To limit energy waste during normal and light snow conditions, a remote temperature sensor is commonly installed midway between two pipes or cables in the slab; the set point is adjusted between 40 and 60°F. Thus, during mild-weather snow conditions, the system is automatically modulated or cycled on and off to keep the slab temperature (at the sensor) at set point.

Outdoor Thermostat. The control system may include an outdoor thermostat that deactivates the system when the outdoor ambient temperature rises above 35 to 40°F as automatic protection against accidental operation in summer or mild weather.

For optimum operating convenience and minimum operating cost, all of the preceding controls should be incorporated in the snow-melting system.

 Operating Cost

To evaluate operating cost during idling or melting, use the annual output data from Table 3. Idling and melting data are based on slab surface temperature control at 32°F during idling, which requires a slab temperature sensor. Without a slab temperature sensor, operating costs will be substantially higher.

6. FREEZE PROTECTION SYSTEMS

If the slab surface temperature is below 32°F, any water film present on that surface freezes. Water may be present because of accidental spillage, runoff from a nearby source, or premature shutoff of snow-melting operation after precipitation ends but before the surface dries (temperature usually drops rapidly after snow). Therefore, for cases with Ar < 1, if the system is shut off too soon, the remaining snow and fluid film on the surface may freeze (Adlam 1950). As previously discussed, idling keeps the slab surface from freezing by maintaining a surface temperature of at least 33.5°F and also reduces the required start-up surface heat flux for snow-melting.

To calculate surface heat flux during idling, the surface may be assumed to be free of snow, covered with a film of water. Unless there is a constant influx of water from the vicinity, the evaporation heat flux of that film may be ignored and the surface may be assumed to be uncovered because the insulation effect of the water film is negligible. In this case, surface heat flux can be calculated by Equation (5).

The surface is free of snow; therefore, Equation (5) approximates the surface heat flux. The mean radiant temperature that appears in Equation (5) is evaluated using Equations (8), (9), and (10). The fraction Fsc of radiation between the surface and the clouds is equal to the cloud cover fraction in the meteorological data.

Chapman (1952) also proposed the following equation to determine the required surface heat flux for idling qi in Btu/h  ·  ft2, if the mean ambient air temperature tmduring freezing is known:

(32)

A slab surface temperature monitor may control the freeze protection system. Whenever the slab surface temperature drops below 33°F, the system activates. However, idling the slab during the entire winter, as given in Table 3, may be too costly, and unnecessary if the main purpose is to reduce high snow-melting surface heat flux at start-up. For example, the annual energy requirement for idling is 45 times more than that for snow-melting in Chicago, Ar = 0.5. Therefore, a cost-effective operation may require starting the system to idle only before an anticipated snow. The lead time may be determined by the thermal mass of the slab, local meteorological conditions, idling and start-up snow-melting heat fluxes, and energy cost. Depending on local weather conditions, idling may also be started automatically when prevailing atmospheric conditions make snowfall likely.

Freeze protection systems may also be used in a variety of applications. For example, the foundation of a cold-storage warehouse may be protected from heaving by using a heated floor slab similar to a snow-melting system. The slab must be insulated at the top as well as the back and edges. Top insulation prevents the heated slab from interfering with the space-cooling process in the warehouse. Edge insulation must penetrate below the freezing line. Generally, design heat flux is taken to be between 5 and 10 Btu/(h  ·  ft2) and the system is operated year-round.

Another freeze protection application is pipe tracing, where a pipe or conduit exposed to the atmosphere is protected against freezing of the fluid within. If a highly viscous fluid is transported, the desired pipe (fluid) temperature may need to be higher than the fluid-freezing temperature to maintain the viscosity required for fluid flow. Figure 11 shows a typical application in which small “tracer” pipes or electrical heating cables are banded along the lower surface of the pipe (Kenny 1999). In a hydronic tracing system, hot fluid or steam may be used. In electric systems, heating cable or mats may be used. Pipe and the tracing elements are covered with thermal insulating material such as fiberglass, polyurethane, calcium silicate, or cellular glass. Sometimes multiple insulation layers may be used. Insulating material must be protected from rain and other external conditions by a weather barrier. Pipe-tracing heat load per unit pipe length qk is given by the following formula (IEEE 1983):

(33)

where

qk = pipe tracing heat load per unit pipe length, Btu/h  ·  ft
tp = desired pipe temperature, °F
ta = design ambient temperature, °F
Di = inside diameter of inner insulation layer (and outer diameter of pipe), ft
Do = outside diameter of inner insulation layer (and inside diameter of outer insulation layer, if present), ft
D3 = outside diameter of outer insulation layer (if present), ft. Otherwise, the expression ln(D3/Do)/2πk2 in Equation (24) is dropped and D3 in the last two terms in the denominator of the same equation is replaced by Do.
k1 = thermal conductance of inner insulation layer, Btu/h  ·  ft  ·  °F (evaluated at its average operating temperature)
k2 = thermal conductance of outer insulation layer, if present, Btu/h  ·  ft  ·  °F (evaluated at its average operating temperature)
hi = thermal convection coefficient of air film between pipe and inner insulation surface, Btu/h  ·  ft  ·  °F.
hco = thermal convection coefficient of air between outer insulation surface and weather barrier (if present), Btu/h  ·  ft  ·  °F.
ho = combined surface heat transfer coefficient for radiation and convection between weather barrier, if present (otherwise, the outer insulation layer), to ambient, Btu/h  ·  ft  ·  °F. Values for ho may be calculated from information in Chapter 4 of the 2017 ASHRAE Handbook—Fundamentals and Chapter 16 of the 2020 ASHRAE Handbook—HVAC Systems and Equipment.

Typical Heat Tracing Arrangement (Hydronic or Electric)

Figure 11. Typical Heat Tracing Arrangement (Hydronic or Electric)


An appropriate pipe-tracing system is selected to satisfy qk. For ease of product selection, some manufacturers offer design software or simple charts and graphs of heat losses for various pipe temperatures and insulation configurations. Safety factors are usually added by explicitly increasing the calculated heat load, by decreasing the design ambient temperature, or by conservative selection of k and h values. Pipe- or conduit-tracing heat loads can be more complex because of the heat sinks that penetrate the insulation surface(s); they often require a complex analysis to determine total heat loss, so a heat trace supplier should be consulted.

 Steam Pipe-Tracing Systems

Steam tracing involves circulating steam in a pipe or tube that runs parallel to the pipe being traced. As the steam recondenses, it releases its latent heat and transfers it into the traced pipe. A typical steam pipe-tracing system is shown in Figure 12.

Steam systems have relatively high installed costs, particularly if an appropriately sized boiler and header system is not already in place. Steam is widely used for industrial applications, and the design is familiar to pipe installers. Steam is well suited for applications that require a high heat flux, but often is not as efficient for lower-heat-flux applications such as pipe freeze protection.

Typical Pipe-Tracing System with Steam System

Figure 12. Typical Pipe-Tracing System with Steam System


 Electric Pipe-Tracing Systems

Electric pipe-tracing systems involve placing (tracing) an electrical resistance wire parallel to the pipe or tube being traced. This electric heater provides heat to the pipe to balance heat loss to the lower-ambient surrounding. A typical electric system is shown in Figure 13.

Types of electric heating cables include the following:

  • Self-regulating heating cables consist of two parallel conductors embedded in a heating core made of conductive polymers. These cables automatically adjust their power output to compensate for local temperature changes. Heat is generated as electric current passes through the conductive core between the conductors. As the pipe temperature drops, the number of electrical paths increases, and more heat is produced. Power output of self-regulating heating cables is specified as watts per unit length at a particular temperature. The self-regulating feature makes the heating cables more energy efficient, because they change their power output based on the need at that point in the pipe. Because they are parallel, they can be cut to length and spliced in the field. Disadvantages are that they are often more expensive and have shorter maximum run lengths because of inrush current.

  • Series heating cables are one or two copper, copper alloy, or nichrome elements surrounded by a polymer insulating jacket. Power outputs of series cables are specified in watts per unit length. These heating cables are usually inexpensive. Their main disadvantage is that the length cannot be adjusted without changing the power output.

  • Mineral-insulated (MI) heating cables are series heating cables composed of a magnesium oxide (MgO)-filled, die-drawn cable with one or two copper or copper alloy conductors and a seamless copper or stainless steel alloy sheath. Power output of an MI heating cable is specified in watts per unit length. MI heating cables are rugged and can withstand high temperatures, but are not very flexible. They generally must be ordered in the size needed; splicing in the field is craft-sensitive.

  • Zone heaters consist of two insulated copper bus wires wrapped with a small-gage (38 to 41 AWG) nichrome heating wire, covered with polymer insulation. The heating wire is connected to alternate bus wires at nodes spaced 1 to 4 ft apart. Current flowing between the bus wires on the heating element generates heat. Power output of a zone heating cable is specified in watts per unit length. Zone heaters are parallel heaters, and thus can be cut to length and spliced in the field. Care must be used to prevent the thin heating wire from being damaged.

Typical Pipe Tracing with Electric System

Figure 13. Typical Pipe Tracing with Electric System


 Control

The pipe-tracing system is designed to replace pipe heat loss in the worst case (at the lowest ambient temperature). Most of the time, when the temperature is above the lowest ambient temperature, the heat trace system will produce more heat than is required. To conserve energy, or to prevent the pipe from getting too warm, a control system is usually added.

Approaches to basic control include the following:

  • None. Sometimes heat trace can be allowed to remain energized, most commonly with short lengths of self-regulating electric heat trace or in cases where the ambient temperature does not change (such as a pipe inside a cold-storage area). This is the least efficient control method from an energy usage standpoint, but the easiest to design. A slight variation on this is a manual switch to disconnect power when not needed, using a switch or circuit breaker.

  • Ambient thermostat. This involves reading the air temperature and activating the system when the air temperature approaches freezing (often at 40°F). This ensures that the system is energized when the pipe could freeze and de-energized when it is warm. This system is often the best compromise between energy efficiency and ease of design.

  • Pipe-sensing thermostat. This involves reading the pipe temperature and activating the heat trace system when the pipe temperature approaches freezing (often at 40°F). This is the most energy-efficient system, but is more complex to design so that the sensor reading is representative of all areas of the pipe. Always put the control sensor on the smallest pipe and at the coldest anticipated location.

REFERENCES

ASHRAE members can access ASHRAE Journal articles and ASHRAE research project final reports at technologyportal.ashrae.org. Articles and reports are also available for purchase by nonmembers in the online ASHRAE Bookstore at www.ashrae.org/bookstore.

ACI. 2014. Guide to thermal properties of concrete and masonry systems. American Concrete Institute, Farmington Hills, MI.

Adlam, T.N. 1950. Snow melting. Industrial Press, New York; University Microfilms, Ann Arbor, MI.

Brown, B. 1999. Klamath Falls geothermal district heating systems. GHC Bulletin (March):5-9.

Chapman, W.P. 1952. Design of snow melting systems. Heating and Ventilating (April):95 and (November):88.

Chapman, W.P. 1955. Are thermal stresses a problem in snow melting systems? Heating, Piping and Air Conditioning (June):92 and (August): 104.

Chapman, W.P. 1999. A review of snow melting system design. ASHRAE Transactions 105(1).

COESA. 1976. U.S. Standard Atmosphere 1976. U.S. Committee on Extension to the Standard Atmosphere. U.S. Government Printing Office, Washington, D.C.

Colliver, D.G., R.S. Gates, H. Zhang, T. Burks, and K.T. Priddy. 1998. Updating the tables of design weather conditions in the ASHRAE Handbook—Fundamentals. ASHRAE RP-890 Final Report.

CSA. 2014. Concrete materials and methods of concrete construction: Test methods and standard practices for concrete. Standard A23.14/A23.2-14. Canadian Standards Association Group.

Frier, J.P. 1964. Design requirements for infrared snow melting systems. Illuminating Engineering (October):686. Also discussion (December).

Frier, J.P. 1965. Snow melting with infrared lamps. Plant Engineering (October):150.

Gordon, P.B. 1950. Antifreeze protection for snow melting systems. Heating, Piping and Air Conditioning Contractors National Association Official Bulletin (February):21.

IEEE. 1983. IEEE recommended practice for the testing, design, installation, and maintenance of electrical resistance heat-tracing for industrial applications. IEEE Standard 515-1983. Institute of Electrical and Electronics Engineers.

Incropera, F.P., and D.P. DeWitt. 1996. Introduction to heat transfer, pp. 332-334. John Wiley & Sons, New York.

Kenny, T.M. 1999. Effective steam tracing, ASHRAE Journal 41(1):42-44.

Kilkis, I.B. 1994. Design of embedded snow-melting systems: Part 1, heat requirements—An overall assessment and recommendations; Part 2, heat transfer in the slab—A simplified model. ASHRAE Transactions 100(1):423-433, 434-441.

Kilkis, I.B. 1995. An energy efficient design algorithm for snow-melting systems. Proceedings of the International Conference ECOS ’95. Simulation and Environmental Impact of Energy Systems, ASME, NY.

Kuehn, T.H., J.W. Ramsey, and J.L. Threlkeld. 1998. Thermal environmental engineering, 3rd ed. Prentice Hall, Upper Saddle River, NJ.

Lawrie, R.J. 1966. Electric snow melting systems. Electrical Construction and Maintenance (March):110.

NCDC. 1990. Precipitation—Hourly cooperative TD-3240 documentation manual. National Climatic Data Center, Asheville, NC.

NCDC. 1993. Solar and meteorological surface observation network 1961-1990 (SAMSON), Version 1.0.

NFPA. 1996. National electrical code®. ANSI/NFPA Standard 70-96. National Fire Protection Association, Quincy, MA.

Potter, W.G. 1967. Electric snow melting systems. ASHRAE Journal 9(10): 35-44.

Ramsey, J.W., H.D. Chiang, and R.J. Goldstein. 1982. A study of the incoming long-wave atmospheric radiation from a clear sky. Journal of Applied Meteorology 21:566-578.

Ramsey, J.W., M.J. Hewett, T.H. Kuehn, and S.D. Petersen. 1999. Updated design guidelines for snow melting system. ASHRAE Transactions 105(1):1055-1065.

Shirakawa, K., S. Kobayashi, S. Koyama, and M. Syuniji. 1985. Snow melting pavement with steel reinforced concrete. Summimoto Research 31.

Spitler, J.D., S.J. Rees, X. Xia, and M. Chulliparambil. 2001. Development of a two-dimensional transient model of snow-melting systems and use of the model for analysis of design alternatives. ASHRAE Research Project RP-1090, Final Report.

Spitler, J.D., S.J. Rees, and X. Xia. 2002. Transient analysis of snow-melting system performance. ASHRAE Transactions 108(2):406-425.

Witsken, C.H. 1965. Snow melting with electric wire. Plant Engineering (September):129.

BIBLIOGRAPHY

Chapman, W.P. 1955. Snow melting system hydraulics. Air Conditioning, Heating and Ventilating (November).

Chapman, W.P. 1957. Calculating the heat requirements of a snow melting system. Air Conditioning, Heating and Ventilating (September through August).

Chapman, W.P., and S. Katunich. 1956. Heat requirements of snow melting systems. ASHAE Transactions 62:359.

Erickson, C.J. 1995. Handbook of electrical heating for industry. Institute of Electrical and Electronic Engineers.

Hydronics Institute. 1994. Snow melting calculation and installation guide. Berkeley Heights, NJ.

Mohinder, L.N. 2000. Piping handbook, 7th ed. McGraw-Hill, New York.

NACE. 1978. Basic corrosion course text (October). National Association of Corrosion Engineers, Houston, TX.



The preparation of this chapter is assigned to TC 6.5, Radiant Heating and Cooling.